| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Investigation Report | |
| Published: June 2019 | |
| Investigation Report | |
| KEY ISSUES: | |
| • Emergency Planning and Response | |
| (Preparedness) | |
| • | |
| Implementation of Process Safety | |
| Management Systems | |
| • Assessment of Process Safety Culture | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| The U.S. Chemical Safety and Hazard Investigation Board (CSB) is an independent federal | |
| agency whose mission is to drive chemical safety change through independent investigations to | |
| protect people and the environment. | |
| The CSB is a scientific investigative organization, not an enforcement or regulatory body. | |
| Established by the Clean Air Act Amendments of 1990, the CSB is responsible for determining | |
| accident causes, issuing safety recommendations, studying chemical safety issues, and evaluating the | |
| effectiveness of other government agencies involved in chemical safety. More information about the | |
| CSB is available at www.csb.gov. | |
| The CSB makes public its actions and decisions through investigative publications, all of which may | |
| include safety recommendations when appropriate. Types of publications include: | |
| Investigation Reports: Formal, detailed reports on significant chemical incidents that | |
| include key findings, root causes, and safety recommendations | |
| Investigation Digests: Plain-language summaries of Investigation Reports | |
| Case Studies: Reports that examine fewer issues than Investigation Reports | |
| Safety Bulletins: Short publications typically focused on a single safety topic | |
| Hazard Investigations: Broader studies of significant chemical hazards | |
| Safety Videos: Videos that animate aspects of an incident or amplify CSB safety messages | |
| CSB products can be freely accessed at www.csb.gov or obtained by contacting: | |
| U.S. Chemical Safety and Hazard Investigation Board | |
| Office of Congressional, Public, and Board Affairs | |
| 1750 Pennsylvania Ave NW, Suite 910 | |
| Washington, DC 20006 | |
| (202) 261-7600 | |
| No part of the conclusions, findings, or recommendations of the Board relating to any accidental | |
| release or the investigation thereof shall be admitted as evidence or used in any action or suit for | |
| damages arising out of any matter mentioned in such report. See 42 U.S.C. § 7412(r)(6)(G). | |
| Page 2 | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| TABLE OF CONTENTS | |
| EXECUTIVE SUMMARY.............................................................................................................................................. 7 | |
| INCIDENT DESCRIPTION ......................................................................................................................................... 12 | |
| METHYL MERCAPTAN RELEASE ............................................................................................................................... 13 | |
| EMERGENCY RESPONSE ......................................................................................................................................... 20 | |
| DELAYED AWARENESS OF TOXIC CHEMICAL RELEASE BY OPERATIONS .................................................................. 27 | |
| EMERGENCY RESPONSE OPERATIONS .................................................................................................................... 30 | |
| ERT BACKGROUND .............................................................................................................................................. 31 | |
| PROCESS COORDINATOR WAS MISSING .................................................................................................................... 33 | |
| DELAY IN ERT READINESS TO SEARCH FOR MISSING WORKERS ....................................................................................... 36 | |
| 4.3.1 Call for ERT Response .................................................................................................................................. 36 | |
| ERT Mini-‐Pumper Truck Not Operational ..................................................................................................... 37 | |
| 4.3.2 | |
| THE SEARCH FOR MISSING WORKERS WAS HIGH RISK .................................................................................................. 38 | |
| 4.4.1 | |
| Entry into Potentially Explosive Atmosphere ................................................................................................ 38 | |
| 4.4.2 No Technology to Locate Missing Workers .................................................................................................. 40 | |
| 4.4.3 Unrecognized Manufacturing Building Collapse Hazard ............................................................................... 41 | |
| DIFFICULTIES NAVIGATING MANUFACTURING BUILDING ................................................................................................ 42 | |
| NO ANALYSIS OF PROCESS DATA TO IDENTIFY SOURCE OF LEAK....................................................................................... 45 | |
| INADEQUATE CREATION AND CONTROL OF HOT ZONE .................................................................................................. 48 | |
| DEFICIENCIES IN EVALUATING RISK TO THE PUBLIC ....................................................................................................... 50 | |
| 4.8.1 Release Modeling ....................................................................................................................................... 51 | |
| 4.8.2 Physical Properties of Methyl Mercaptan .................................................................................................... 54 | |
| 4.8.3 Chemical Sensor Data ................................................................................................................................. 56 | |
| 4.8.4 Air Monitoring ............................................................................................................................................ 57 | |
| EMERGENCY RESPONSE CONCLUSIONS ...................................................................................................................... 58 | |
| DUPONT’S PROCESS SAFETY MANAGEMENT SYSTEM ............................................................................................ 59 | |
| OSHA .............................................................................................................................................................. 60 | |
| 5.1.1 | |
| The Process Safety Management Standard ................................................................................................. 60 | |
| 5.1.2 DuPont La Porte’s Implementation of PSM .................................................................................................. 61 | |
| 5.1.3 Recent Developments Affecting the PSM Standard ...................................................................................... 63 | |
| ENVIRONMENTAL PROTECTION AGENCY .................................................................................................................... 63 | |
| 5.2.1 Risk Management Plan Rule........................................................................................................................ 63 | |
| 5.2.2 DuPont La Porte’s Implementation of RMP .................................................................................................. 65 | |
| 5.2.3 Recent Developments Affecting the RMP Rule ............................................................................................. 65 | |
| AMERICAN CHEMISTRY COUNCIL ............................................................................................................................. 67 | |
| 5.3.1 History of Responsible Care ......................................................................................................................... 68 | |
| 5.3.2 Responsible Care Requirements .................................................................................................................. 69 | |
| 5.3.3 Responsible Care Conformance Audits ........................................................................................................ 71 | |
| Page 3 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 5.3.4 Recent Developments in Responsible Care ................................................................................................... 74 | |
| 5.3.5 Responsible Care Improvement Opportunities ............................................................................................. 75 | |
| DUPONT’S DEVELOPMENT AND IMPLEMENTATION OF ITS PROCESS SAFETY MANAGEMENT SYSTEM ........................................ 78 | |
| 5.4.1 Building a Safety Culture ............................................................................................................................. 80 | |
| 5.4.2 Using the Process Safety Management and Risk Model ............................................................................... 90 | |
| DUPONT’S PROCESS SAFETY MANAGEMENT SYSTEM CONCLUSIONS ................................................................................ 92 | |
| PROCESS SAFETY MANAGEMENT DEFICIENCIES...................................................................................................... 92 | |
| PROCESS HAZARD ANALYSIS EVALUATION .................................................................................................................. 93 | |
| IMPLEMENTATION OF CORRECTIVE ACTIONS ............................................................................................................... 96 | |
| PROCESS SAFETY PRACTICES DURING TROUBLESHOOTING OPERATIONS ............................................................................. 99 | |
| MOC PRACTICES .............................................................................................................................................. 101 | |
| 6.4.1 No MOC for Heating Piping or for New Piping Alignment ........................................................................... 102 | |
| 6.4.2 No MOC for New Piping Alignment to Nitrogen Relief Valves ..................................................................... 105 | |
| 6.4.3 No MOC or Procedure for Vent Header Draining Operation ....................................................................... 106 | |
| LINE-‐BREAKING PRACTICES .................................................................................................................................. 109 | |
| SHIFT COMMUNICATION PRACTICES ....................................................................................................................... 113 | |
| ADDITIONAL FACTS, CONDITIONS, AND CIRCUMSTANCES IDENTIFIED ................................................................. 114 | |
| EMPLOYEE INCENTIVE PROGRAM ........................................................................................................................... 115 | |
| KEY FINDINGS ....................................................................................................................................................... 120 | |
| SAFETY GUIDANCE ................................................................................................................................................ 121 | |
| 10 RECOMMENDATIONS ........................................................................................................................................... 124 | |
| DUPONT LA PORTE, TEXAS, CHEMICAL FACILITY ....................................................................................................... 125 | |
| LOCAL 900C OF THE INTERNATIONAL CHEMICAL WORKERS UNION COUNCIL (ICWUC) OF THE UNITED FOOD AND COMMERCIAL | |
| WORKERS (UFCW) ....................................................................................................................................................... 126 | |
| REFERENCES .................................................................................................................................................................. 128 | |
| APPENDIX A: CAUSAL ANALYSIS.................................................................................................................................... 144 | |
| APPENDIX B: INCIDENT TIMELINE ................................................................................................................................. 145 | |
| APPENDIX C: ODOR COMPLAINTS FROM NOVEMBER 15, 2014 ..................................................................................... 150 | |
| APPENDIX D: EMERGENCY RESPONSE TABLES .............................................................................................................. 151 | |
| APPENDIX E: DUPONT SAFETY PERCEPTION SURVEYS................................................................................................... 156 | |
| Page 4 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| ACRONYMS AND INITIALISMS | |
| AAO | |
| ACC | |
| AEGL | |
| API | |
| CCPS | |
| CCTV | |
| CSB | |
| DCS | |
| DOT | |
| EMT | |
| EPA | |
| EOC | |
| acetaldehyde oxime | |
| American Chemistry Council | |
| acute exposure guideline level | |
| American Petroleum Institute | |
| Center for Chemical Process Safety | |
| closed circuit television | |
| U.S. Chemical Safety and Hazard Investigation Board | |
| distributed control system | |
| U.S. Department of Transportation | |
| emergency medical technician | |
| U.S. Environmental Protection Agency | |
| Emergency Operations Center | |
| ERPGs | |
| Emergency Response Planning Guidelines | |
| ERT | |
| FBU | |
| emergency response team | |
| Fluoroproducts Business Unit | |
| FEMA | |
| U.S. Federal Emergency Management Agency | |
| HAZCOM | |
| Hazard Communication Standard | |
| HAZWOPER | |
| Hazardous Waste Operations and Emergency Response Standard | |
| IBU | |
| Insecticide Business Unit | |
| ICWUC | |
| International Chemical Workers Union Council | |
| IDLH | |
| LEL | |
| LFL | |
| LPBC | |
| MeSH | |
| MOC | |
| MSDS | |
| Immediately Dangerous to Life or Health | |
| lower explosive limit | |
| lower flammability limit | |
| Local Performance Based Compensation program | |
| methyl mercaptan | |
| methyl isocyanate | |
| management of change | |
| material safety data sheet | |
| Page 5 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| NAICS | |
| North American Industrial Classification System | |
| mph | |
| NEP | |
| NFPA | |
| NIMS | |
| miles per hour | |
| National Emphasis Program | |
| National Fire Protection Association | |
| National Incident Management System | |
| NIOSH | |
| National Institute for Occupational Safety and Health | |
| NRS | |
| OSHA | |
| NOx (nitrogen oxides) reduced scrubbed | |
| U.S. Occupational Safety and Health Administration | |
| OSH Act | |
| U.S. Occupational Safety and Health Act of 1970 | |
| PEL | |
| PHA | |
| ppb | |
| PPE | |
| ppm | |
| PSM | |
| permissible exposure limit | |
| process hazard analysis | |
| parts per billion | |
| personal protective equipment | |
| parts per million | |
| Process Safety Management | |
| RCMS | |
| Responsible Care Management System® | |
| RCS | |
| REL | |
| RMP | |
| Relative Culture Strength | |
| recommended exposure limit | |
| Risk Management Plan | |
| SCBA | |
| self-contained breathing apparatus | |
| SDS | |
| SHI | |
| TWA | |
| UFCW | |
| safety data sheet | |
| Substance Hazards Index | |
| Time-Weighted Average | |
| United Food and Commercial Workers | |
| Page 6 | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| 1 EXECUTIVE SUMMARY | |
| On November 15, 2014, approximately 24,000 poundsa of highly toxic methyl mercaptan was released from an | |
| insecticide productionb unit (Lannate® Unit) at the E. I. du Pont de Nemours and Company (DuPont) chemical | |
| manufacturing facility in La Porte, Texas.c The release killed three operators and a shift supervisor inside a | |
| manufacturing building.d They died from a combination of asphyxia and acute exposure (by inhalation) to | |
| methyl mercaptan. | |
| The CSB determined that the cause of the highly toxic methyl mercaptan release was the flawed engineering | |
| design and the lack of adequate safeguards.e Contributing to the severity of the incident were numerous safety | |
| management system deficiencies, including deficiencies in formal process safety culture assessments, auditing | |
| and corrective actions, troubleshooting operations, management of change, safe work practices, shift | |
| communications, building ventilation design, toxic gas detection, and emergency response. Weaknesses in the | |
| DuPont La Porte safety management systems resulted from a culture at the facility that did not effectively | |
| support strong process safety performance. | |
| The highly toxic methyl mercaptan release resulted from a long chain of process safety management system | |
| implementation failures stemming from ineffective implementation of the process safety management system at | |
| the DuPont La Porte facility. | |
| The CSB investigation viewed the chain of implementation failures as starting with the flawed engineering | |
| design of the $20 million nitrogen oxides (NOx) reduced scrubbed (NRS) incinerator, a capital project | |
| implemented in 2011. DuPont La Porte had long-standing issues with vent piping to this incinerator because the | |
| design did not address liquid accumulation in waste gas vent header vapor piping to the NRS, and DuPont La | |
| Porte did not fully resolve the liquid accumulation problem through hazard analyses or management of change | |
| reviews. Instead, to deal with these problems, daily instructions had been provided to operations personnel to | |
| drain liquid from these pipes to the atmosphere inside the Lannate® manufacturing building without specifically | |
| addressing the potential safety hazards this action could pose to the workers. DuPont La Porte’s instructions did | |
| a 29 C.F.R. § 1910.119 Appendix A (2013). | |
| b The Insecticide Business Unit (IBU) was divided into two primary insecticide product lines: Lannate®, which is DuPont’s trade name | |
| for methomyl, and agricultural products intermediates, which were used to produce insecticides and nematicides known as Vydate®, the | |
| trade name for oxamyl [1, p. 11]. | |
| c Multiple business units were located at the DuPont La Porte site. The Lannate® Unit was part of the IBU. In addition to the IBU, the | |
| facility had an Herbicides Business Unit and a Fluoroproducts Business Unit (FBU). The FBU included an anhydrous hydrogen fluoride | |
| (HF) manufacturing unit. FBU assets were sold to Chemours on July 1, 2015. | |
| d The victims included operators Robert Tisnado (39), Gilbert Tisnado (48), Crystle Wise (53), and shift supervisor Wade Baker (60). | |
| One victim on the third floor was located near a methyl mercaptan leak source on the wet end (east) side. The other two victims on the | |
| third floor were on the dry end (west) side. The IBU was further subdivided into four functional areas: the wet end, the MIC (methyl | |
| isocyanate) area, the damp end, and the dry end. The wet end contained liquid reaction equipment. The MIC area contained equipment | |
| to generate and consume the MIC intermediate. The damp end isolated and dried insecticide crystals. The dry end processed the crystals | |
| and packaged them into various products [1, pp. 10-11]. | |
| e In September 2018, the CSB produced a Winterization Safety Digest that discussed DuPont La Porte’s lack of safeguards to prevent | |
| methyl mercaptan hydrate formation [173, p. 1]. | |
| Page 7 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| not specify additional breathing protection for this task (Section 6.4.3 and Interim Recommendations) [1, p. 18]. | |
| On the night of the incident, not realizing the hydrate blockage in the methyl mercaptan feed piping was cleared, | |
| workers went to drain liquid from the waste gas vent piping. They did not know that high pressure in the waste | |
| gas vent piping was related to the fact that liquid methyl mercaptan was flowing through the methyl mercaptan | |
| feed piping and into the waste gas vent piping. | |
| The chain further developed when the ineffective building ventilation system failed to be addressed after | |
| DuPont auditors identified it as a safety concern about five years before the incident. DuPont La Porte’s | |
| management system did not resolve the process safety management recommendation (i.e., did not take | |
| corrective action) to address the building ventilation system (Section 6.1 and Interim Recommendations) [1, p. | |
| 34]. The ventilation design for the manufacturing building was based on flammability characteristics and did | |
| not take into consideration toxic chemical exposure hazards, even though the building contained two highly | |
| toxic materials, chlorine and methyl mercaptan. DuPont La Porte records indicated that the manufacturing | |
| building’s dilution air ventilation design was based on providing sufficient ventilation to ensure that the | |
| concentration of flammable gases did not exceed 25 percent of the lower explosion limit (LEL).a At the time of | |
| the incident, neither of the manufacturing building’s two rooftop ventilation fans was working, despite an | |
| “urgent” work order written nearly a month earlier. Even had the fans worked, they probably would not have | |
| prevented a lethal atmosphere inside the building due to the large amount of toxic gas released (Section 5.4.1.2 | |
| and Interim Recommendations) [1, pp. 3, 33-34]. | |
| DuPont La Porte’s installation of a methyl mercaptan detection system inside the manufacturing building added | |
| another link to the chain. Neither the workers nor the public was protected by DuPont’s toxic gas detection | |
| system on the night of the incident. The building where the workers died was not equipped with an adequate | |
| toxic gas detection system to alert personnel to the presence of dangerous chemicals. First, DuPont La Porte set | |
| the detector alarms well above safe exposure limits for workers. Second, DuPont La Porte relied on verbal | |
| communication of alarms that automatically displayed on a continuously manned control board. Finally, | |
| DuPont La Porte did not provide visual lights or audible alarms for the manufacturing building to warn workers | |
| of highly toxic gas concentrations inside it. When a release caused a detector to register a concentration above | |
| the alarm limit, the toxic gas detection system did not warn workers in the field about the potential leak and the | |
| need to evacuate. Among other factors, this detection system contributed to workers’ growing accustomed to | |
| smelling the methyl mercaptan odor in the unit. Additionally, when the toxic gas detectors triggered alarms, | |
| DuPont La Porte personnel investigated potential methyl mercaptan leaks without using respiratory protection. | |
| Personnel normalized unsafe methyl mercaptan detection practices by using odor to detect the gas, further | |
| a DuPont records indicate that the manufacturing building ventilation system design code is NFPA 497, Recommended Practice for the | |
| Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical | |
| Process Areas. NFPA 497 defines adequate ventilation as that sufficient to ensure that the concentration of flammable gases does not | |
| exceed 25 percent of the lower flammability limit (also referred to as lower explosion limit (LEL)) [136, p. 9]. However, there were no | |
| LEL detectors to monitor the atmospheric conditions inside the manufacturing building and alert workers of potential fire or explosion | |
| conditions. Furthermore, a methyl mercaptan concentration of 25 percent of the LEL is equivalent to 65 times greater than the 150 parts | |
| per million concentration that is considered immediately dangerous to life or health (IDLH). | |
| Page 8 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| deteriorating the importance or effectiveness of utilizing instrumentation in response to alarms signaling | |
| potential toxic gas releases (Section 3 and Interim Recommendations) [1, pp. 38-39]. | |
| In the spring of 2014, the chain propagated when DuPont La Porte’s interlock program did not require | |
| verification that interlocks that had been bypassed for turnaround maintenance were returned to service before | |
| the plant resumed operating. Because of this ineffective program, a bypassed interlock caused acetaldehyde | |
| oxime (AAO), a critical raw material, to become diluted, leading to a shutdown of the Lannate® Unit days | |
| before the November 2014 incident.a During the shutdown, water entered the methyl mercaptan feed piping | |
| and, due to the cold weather, formed a hydrate (an ice-like material) that plugged the piping and prevented | |
| workers from restarting the unit. Furthermore, DuPont La Porte did not establish adequate safeguards after a | |
| 2011 DuPont La Porte process hazard analysis identified hydrate formation in this piping, revealing yet another | |
| link in the chain (Section 6.1 and Interim Recommendations) [1, p. 22]. | |
| When the hydrate formed, lacking safeguards to control the potential safety hazards associated with dissociating | |
| (breaking up) the hydrate (such as using heat tracing to prevent the hydrate from forming a solid inside the | |
| piping or developing a procedure to dissociate the hydrate safely), DuPont workers went into troubleshooting | |
| mode (Section 6.3). Ineffective hazard management while troubleshooting the plugged methyl mercaptan feed | |
| piping formed yet another link in the chain and allowed liquid methyl mercaptan to flow into the waste gas vent | |
| header piping toward the NRS incinerator—a location where it was never intended to go (Section 6.4.1 and | |
| Interim Recommendations) [1, pp. 25-26]. As discussed earlier, DuPont La Porte did not fully resolve liquid | |
| accumulation in the waste gas vent header by the NRS incinerator. Consequently, DuPont La Porte workers | |
| dealt with the common problem of liquid accumulation in the waste gas vent header on a routine basis by | |
| draining the liquid (line breaking) without an engineered solution or without ensuring the use of safety | |
| procedures or personal protective equipment (Section 6.4.3 and Interim Recommendations) [1, pp. 18, 28]. | |
| However, when the liquid drain valves were opened on November 15, 2014, flammable and highly toxic methyl | |
| mercaptan flowed onto the floor and filled the manufacturing building with toxic vapor. | |
| Once the methyl mercaptan release began, an ineffective emergency response program at La Porte contributed to | |
| the extent and duration of the chemical release, placed other workers in harm’s way, and did not effectively | |
| evaluate whether the chemical release posed a safety threat to the public (Section 3 and Section 4). | |
| a During the AAO truck unloading, a block valve downstream of what should have been an out-of-service water dilution control valve | |
| was inadvertently opened, allowing water to flow into the tank. The water dilution system had been installed in 2006 when container | |
| shipments of 100 percent AAO were judged to be more economical than diluted AAO. AAO is now typically purchased and stored as a | |
| 50 percent solution with water. A logistical problem resulted in an unusual delivery of 50 percent AAO by tank truck instead of by | |
| railcar. Two factors contributed to the tank overflow incident. First, DuPont did not have a procedure for unloading a 50 percent tank | |
| truck of AAO. Second, the AAO water dilution control valve was supposed to interlock closed when (1) the truck-unloading pump was | |
| off or (2) the AAO tank had a high liquid level. However, the interlock function had been bypassed in the field so that water could be | |
| used to decontaminate the tank during the turnaround in spring 2014. Instrument air supply tubing was connected directly to the | |
| interlock valve actuator, bypassing the interlock activation solenoid, and forcing the valve to remain fully open. The interlock could not | |
| function because the bypass was not removed at the completion of the turnaround [1, p. 33]. DuPont defines a safety interlock as a | |
| system or function that detects an out-of-limits (abnormal) condition or improper sequence and brings it to a safe condition [1, p. 38]. | |
| Page 9 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| This chain of events illustrates DuPont La Porte’s ineffective implementation of its process safety management | |
| system. The individual components of this process safety management system exhibited cross-cutting | |
| weaknesses, resulting in the deaths of four workers and leading to the ultimate decision to close the DuPont La | |
| Porte facility. | |
| The DuPont La Porte incident is the CSB’s third investigation of a fatal DuPont incident in five years.a On | |
| September 30, 2015, the CSB issued a presentation, a safety video, and an Interim Recommendations report [1], | |
| which detailed needed safety improvements at the DuPont La Porte facility and issued recommendations for | |
| implementation before resuming operations of the Lannate® Unit [2].b Due to the amount of methyl mercaptan | |
| stored at the DuPont La Porte site, the Lannate® process was covered by the Process Safety Management (PSM) | |
| standard of the U.S. Occupational Safety and Health Administration (OSHA) and the Risk Management Plan | |
| (RMP) rule of the U.S. Environmental Protection Agency (EPA) [3]. In the Interim Recommendations, the CSB | |
| identified significant process safety management deficiencies at the La Porte facility, including delayed | |
| maintenance of safety-critical equipment, lack of written procedures, poor hazard analysis practices, lack of | |
| implementation of important inherently safer design concepts, and a lack of hazard recognition [1]. | |
| In response to the CSB findings and recommendations, DuPont committed to making changes at the La Porte | |
| facility. DuPont La Porte, however, was not able to address all of these findings and recommendations, because | |
| in the spring of 2016 DuPont announced that it would not reopen the Lannate® Unit. The company had | |
| determined that “significant changes in market conditions during the period of the shutdown [would] persist | |
| over the long term” [4] and that the cost required for the restart was “not a long-term viable and cost-efficient | |
| option for the DuPont Crop Protection business” [5]. In 2017, DuPont dismantled and removed from the | |
| DuPont La Porte facility the buildings and equipment that had been associated with its insecticide and herbicide | |
| business units, including the Lannate® Unit.c | |
| Despite the closure of the insecticide and herbicide units, the CSB determined that the DuPont La Porte incident | |
| offers important lessons for the chemical industry relating to the following areas: | |
| • Emergency Response. The emergency response efforts at the DuPont La Porte facility during the | |
| toxic chemical release were disorganized and placed at risk operators, emergency responders, and | |
| potentially the public. Chemical plants need a robust emergency response program to mitigate | |
| emergencies and to protect the health of workers, emergency responders, and the public.d | |
| a The CSB also investigated an incident at a DuPont plant in Belle, West Virginia (three incidents that occurred in a 33-hour period over | |
| January 22–23, 2010, resulting in one fatality) [121], and another in Buffalo, New York (a single incident that occurred on November 9, | |
| 2010, resulting in one fatality and one serious injury) [122]. | |
| b This report incorporates by reference the DuPont La Porte Interim Recommendations [1]. | |
| c Although DuPont dismantled the La Porte Crop Protection business, DuPont La Porte still operates as a landlord to other companies | |
| located at the La Porte site and provides wastewater treatment and utilities, as well as owning the emergency response program. | |
| d Emergency response and planning is one of five key safety topics that the CSB found needed improvement across industry nationwide; | |
| as a result, the CSB included that topic in its Drivers of Critical Chemical Safety Change program. Inadequate or poor emergency | |
| planning or response is a recurring finding in CSB investigations. At least 17 CSB incident investigations, including this one, identified | |
| emergency response deficiencies, resulting in 46 emergency response recommendations [33]. | |
| Page 10 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| • DuPont’s Process Safety Management System. DuPont created its own corporate process safety | |
| management system that integrated its internal safety requirements with those of the American | |
| Chemistry Council’s Responsible Care® programa and those required by regulations under the EPA | |
| RMP rule and the OSHA PSM standard. Over the course of five years, despite implementing its | |
| corporate process safety management system, DuPont experienced three major process safety | |
| incidents. | |
| In addition to developing an integrated process safety management system, DuPont established a | |
| program to implement it. According to DuPont, the implementation of the process safety | |
| management system can be broken down into two parts: (1) Building a Safety Culture and (2) Using | |
| the Process Safety Management and Risk Model. Although DuPont’s corporate standard | |
| recommended that its sites assess their process safety culture, DuPont La Porte had not formally | |
| evaluated process safety culture at its facility before the November 2014 incident. DuPont La Porte | |
| used a proprietary Safety Perception Survey that focused on personal or occupational safety but did | |
| not evaluate or assess the process safety culture. Because the Safety Perception Survey did not | |
| reasonably evaluate all safety aspects of culture, it could not help identify the significant process | |
| safety weaknesses at the DuPont La Porte facility, leaving the site vulnerable to potential process | |
| safety incidents. While measuring worker perceptions of personal safety is important, a safety | |
| culture assessment program should also provide an effective gauge of process safety. The second | |
| tool that DuPont used to implement its process safety management system was the Process Safety | |
| Management and Risk Model, the company’s visual representation of an effective process safety | |
| management system, showing the implementation and interaction of Management Leadership and | |
| Commitment, Comprehensive Process Safety Management Program, and Operational Discipline. | |
| • DuPont La Porte’s Process Safety Management Deficiencies. The CSB identified significant | |
| process safety deficiencies at the DuPont La Porte site that contributed to the incident. DuPont’s | |
| corporate process safety management system did not identify, prevent, or mitigate these | |
| deficiencies. A company must effectively implement a process safety management system and its | |
| corresponding programs to reap the accompanying process safety benefits. | |
| • DuPont La Porte’s Employee Incentive Program. The DuPont La Porte bonus structure may have | |
| disincentivized workers from reporting injuries, incidents, and “near misses.” Ensuring that | |
| employees can report injuries or incidents in accordance with the Occupational Safety and Health | |
| (OSH)Act and OSHA regulations, without fear of discrimination, retaliation, or other adverse | |
| consequence is central to protecting worker safety and health, and aiding accident prevention. | |
| a The American Chemistry Council (ACC) is a trade group that represents chemical companies. ACC’s Responsible Care Program is a | |
| voluntary industry program. | |
| Page 11 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| This report encourages legacy DuPonta sites to strengthen employee incentive programs. It additionally presents | |
| a set of recommendations to the DuPont La Porte facility and Local 900C of the International Chemical Workers | |
| Union Council (ICWUC) of the United Food and Commercial Workers (UFCW) to improve emergency | |
| preparedness and response at the La Porte facility. Based on the CSB’s investigative findings related to | |
| emergency response, process safety management systems, and incentive programs (see Appendix A: Causal | |
| Analysis), this report presents lessons for the chemical industry in Guidance to Industry sections and | |
| summarizes them at the end of the report in Section 9: Safety Guidance. | |
| 2 INCIDENT DESCRIPTION | |
| The November 15, 2014 incident occurred in DuPont | |
| La Porte’s Lannate®b Unit, which produced | |
| insecticides. Part of the Lannate® process occurred | |
| inside a closed building (the manufacturing building) | |
| Figure 1. The Lannate® Manufacturing Building. The methyl | |
| mercaptan release occurred in the manufacturing building. Source: | |
| CSB. | |
| a DuPont and Dow completed a merger of equals on August 31, 2017. The combined entity operated as a holding company called | |
| DowDuPont [105]. On April 1, 2019, DowDuPont successfully completed the spin-off of its Material Science division, Dow. | |
| DowDuPont intends to separate its Agriculture and Specialty Products divisions into independent, publicly traded companies by June | |
| 2019, subject to board approval [134]. | |
| b Lannate® is the DuPont trade name for methomyl, an insecticide [94, p. 1]. For more detail on the incident, see public meeting | |
| presentation, DuPont La Porte animation, public meeting transcript, and Interim Recommendations report [2]. | |
| Page 12 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| (Figure 1),a where most of the methyl mercaptan release occurred.b The Lannate® process used methyl | |
| mercaptan, a toxic and flammable chemical.c,d | |
| The sections below discuss the eventse leading to the methyl mercaptan release and the subsequent emergency | |
| response. | |
| METHYL MERCAPTAN RELEASE | |
| On Monday, November 10, 2014, an inadvertent chemical dilution caused operating difficulties that forced a | |
| shutdown of DuPont’s Lannate® Unit.f In response, DuPont La Porte personnel adjusted the unit’s control | |
| system to resume operations. On Wednesday, November 12, 2014, operators tried to restart the Lannate® | |
| process. During the shutdown, the methyl mercaptan piping to the reaction section of the process had become | |
| plugged due to the formation of a clathrate hydrate (hydrate),g halting restart. At that time, operators did not | |
| a Chlorine and methyl isocyanate (MIC) were also used in the manufacturing building. | |
| b Although the bulk of the release occurred inside the manufacturing building, methyl mercaptan was also released from the nitrogen | |
| relief valves located at the methyl mercaptan railcar spots. | |
| c Symptoms of methyl mercaptan toxicity include narcosis (a state of stupor, drowsiness, or unconsciousness) and cyanosis (blue or | |
| purple coloration of the skin or mucous membranes caused by inadequate oxygenation of the blood) [50]. Methyl mercaptan is also a | |
| chemical asphyxiant [95]. Chemical asphyxiants are toxic agents that prevent red blood cells from carrying oxygen [90, p. 58]. The | |
| OSHA ceiling exposure limit is 10 parts per million (ppm). OSHA recommends that employers consider using the alternative | |
| occupational exposure limits because the agency believes that exposures above some of these alternative occupational exposure limits | |
| may be hazardous to workers, even when the exposure level complies with the relevant permissible exposure limit (PEL) [162]. The | |
| Division of Occupational Safety and Health of California (Cal-OSHA) PEL is an 8-hour time-weighted average (TWA) of 0.5 ppm, and | |
| the National Institute of Occupational Safety and Health (NIOSH) recommends a recommended exposure limit (REL) of a 15-minute | |
| ceiling limit of 0.5 ppm [163]. Methyl mercaptan is immediately dangerous to life and health at 150 ppm [50]. For methyl mercaptan, the | |
| 10-minute acute exposure guideline level (AEGL)-2 (disabling) is 40 ppm and the 10-minute AEGL-3 (lethal) is 120 ppm. According to | |
| the National Center for Biotechnology Information, “AEGL-2 is the airborne concentration (expressed as ppm or mg/m3) of a substance | |
| above which it is predicted that the general population, including susceptible individuals, could experience irreversible or other serious, | |
| long-lasting adverse health effects or an impaired ability to escape. AEGL-3 is the airborne concentration (expressed as ppm or mg/m3) | |
| of a substance above which it is predicted that the general population, including susceptible individuals, could experience life-threatening | |
| health effects or death” [130]. | |
| d Methyl mercaptan is flammable at concentrations between 3.9 percent and 21.8 percent in air [50]. | |
| e The sequence of events is also presented in | |
| Appendix B: Incident Timeline. | |
| f The chemical involved in this dilution was acetaldehyde oxime (AAO). Additional information about the AAO dilution portion of the | |
| incident is in the CSB DuPont La Porte Interim Recommendations [1, pp. 20-21]. | |
| g At low temperatures (≤ 52 degrees Fahrenheit (°F)), water and methyl mercaptan form a solid, ice-like material called methyl | |
| mercaptan clathrate hydrate [72]. Temperatures in the Houston area for the 24 hours preceding the incident averaged approximately | |
| 40°F and had been consistently below 55°F since Tuesday, November 11, 2014. Although the potential for methyl mercaptan hydrate | |
| formation had been identified in DuPont’s methyl mercaptan technical standard and in process hazard analyses years earlier, DuPont | |
| never implemented safeguards, such as heat tracing, or developed a procedure to dissociate the hydrate safely [1, p. 22]. | |
| Page 13 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| know the source of the plugging and began troubleshooting the process to try to clear the piping, unaware that | |
| the solid hydrate had formed. | |
| Two days later, on Friday, November 14, 2014, the troubleshooting efforts to clear the plugging were still | |
| ongoing. That morning, the Lannate® Unit Technical Team (Technical Team), composed of engineers and other | |
| employees experienced in the process, met with operations personnel to discuss troubleshooting options to clear | |
| the plugging. This meeting identified the likely scenario that water had entered the methyl mercaptan system, | |
| forming a solid hydrate. | |
| DuPont’s methyl mercaptan technical standard identifies the potential to form a hydrate at low temperatures. | |
| The technical standard states that methyl mercaptan “will form a hydrate with water, which is a solid below 40 | |
| deg F [degrees Fahrenheit] per information provided by a [methyl mercaptan] supplier.” Based on this | |
| understanding, the Technical Team asked that operators put hot water on the outside of the methyl mercaptan | |
| piping, under the insulation, to warm the piping and its contents to break up (dissociatea) the plugging. The | |
| Technical Team also realized that when heated, methyl mercaptan would expand, requiring a safe place to vent | |
| to avoid over-pressuring the piping. To address this concern, operations personnel opened valves between the | |
| methyl mercaptan piping and a waste gas vent header (vent header), not recognizing that this alignment created | |
| a pathway for liquid methyl mercaptan to eventually release from the piping inside the manufacturing building | |
| when drain valves were opened. | |
| In addition, when operations personnel opened other valves while troubleshooting, such as drain valves, methyl | |
| mercaptan was released to the atmosphere, causing a strong methyl mercaptan odorb that could be smelled by | |
| site personnel. During troubleshooting, methyl mercaptan was released both outside and inside the | |
| manufacturing building, triggering 32 methyl mercaptan gas alarmsc on the control panel throughout the 17 | |
| hours preceding the incident. Although methyl mercaptan is a toxic and flammable chemical, and at high | |
| enough concentrations lethal, some operations personnel did not respond in accordance with the nature of the | |
| emergency circumstances because they associated the alarms with the ongoing troubleshooting efforts. They | |
| did not perceive the methyl mercaptan alarms as signifying a serious hazard because they had normalizedd the | |
| methyl mercaptan odor within the Lannate® Unit, as well as the detector alarms. | |
| Early in the morning on Saturday, November 15, 2014, the hot water from the hoses warmed the hydrate | |
| plugging, causing it to dissociate, clearing the plugging. Due to the valve alignment, liquid methyl mercaptan | |
| a Methyl mercaptan clathrate hydrate dissociates back to the liquid phases of methyl mercaptan and water at approximately 52°F [72]. | |
| b Methyl mercaptan has a low odor threshold. It gives off a smell like rotten cabbage. It can be smelled at only two parts per billion | |
| (ppb) [80, p. 1]. OSHA’s permissible exposure limit (PEL), however, is 10 parts per million (ppm), which is 5,000 times the minimum | |
| concentration that can be smelled. The low odor threshold of mercaptans makes them useful as fuel gas odorants [80, p. 2]. | |
| c DuPont used hydrogen sulfide (H2S) detectors to identify methyl mercaptan. The alarms activated when the detectors sensed the | |
| hydrogen sulfide equivalent of 25 ppm methyl mercaptan. Twenty-five ppm is the ERPG-2 level for methyl mercaptan (see Section 4.8) | |
| [82, p. 27]. This level “is the maximum airborne concentration below which nearly all individuals could be exposed for up to 1 hour | |
| without experiencing or developing irreversible or other serious health effects or symptoms which could impair an individual’s ability to | |
| take protective action.” Emergency responders use ERPG-1, -2, and -3 concentration data to determine how to protect the public [167]. | |
| DuPont records indicate that the device manufacturer stated the detector should be capable of detecting methyl mercaptan within 1 ppm | |
| [1, p. 37]. | |
| d Normalization of deviance is a phenomenon in which individuals or work teams gradually accept a lower standard of performance until | |
| the lower standard becomes the norm. It is typically the result of slowly changing and eroding conditions over time [79, p. 4]. | |
| Page 14 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| flowed into the waste gas vent header, located inside the manufacturing building [1, pp. 25-26]. The vent | |
| header, however, was not intended nor designed for liquid methyl mercaptan. At 2:51 am, alarms began to | |
| sound on the control system indicating high pressure in equipment inside the manufacturing building. | |
| Operations personnel did not realize that liquid methyl mercaptan was causing the high pressure. Instead, they | |
| attributed the high pressure to a common, long-standing problem with process condensate, which DuPont La | |
| Porte personnel believed to be mostly water, accumulating in the vent header piping [1, p. 28]. The Lannate® | |
| control room board operator (Board Operator) contacted the night shift supervisor (Shift Supervisor) and another | |
| operator (Operator 1) separately, asking them to help troubleshoot the high-pressure situation. Manually | |
| draining the vent header inside the manufacturing building, a long-standing practice, was the typical approach | |
| used to remove process condensate from the vent header, as it successfully reduced system pressure many times | |
| in the past.a The Shift Supervisor and Operator 1 each went separately to the manufacturing building, likely in | |
| order to drain liquid from the vent header piping manually. | |
| Sometime between 3:01 am and 3:13 am, a worker (likely the Shift Supervisor)b manually opened two sets of | |
| drain valves on the vent header piping, located on the third floor of the manufacturing building (Figure 2). But | |
| instead of the expected condensate composed mostly of water, the liquid methyl mercaptan that had filled the | |
| piping escaped out of the valves, vaporized, and killed the Shift Supervisor. Between 3:24 am and 3:26 am, | |
| three methyl mercaptan detectors inside the manufacturing building sensed at least 25 parts per million (ppm)c | |
| of methyl mercaptand and triggered alarms at the control panel (Figure 3). The Board Operator—still focused | |
| on reducing the high pressure—did not realize a major chemical release was occurring inside the manufacturing | |
| building (Section 3). | |
| a In 2011, DuPont installed a NOx (nitrogen oxides) reduced scrubbed (NRS) incinerator system. The waste gas vent header piping to the | |
| NRS incinerator was designed without sufficient consideration of liquid accumulation. It contained low points where liquid could | |
| accumulate, and there was no engineered equipment provided, such as a knock-out drum, to remove liquid safely from the waste gas vent | |
| header piping system. The liquid accumulation in the piping would create pressure in process equipment. Pressure buildup within the | |
| equipment was resolved by manually draining liquid from the waste gas vent header. See Section 6, Process Safety Management | |
| Deficiencies, and DuPont La Porte, Texas Chemical Facility Toxic Chemical Release: Interim Recommendations [1, p. 18]. | |
| b The Shift Supervisor was most likely the worker who opened the valves, based on both the location in the manufacturing building | |
| where he was recovered and information learned in interviews that suggested he was the worker most likely to have opened those specific | |
| valves to drain the vent header piping. | |
| c The methyl mercaptan detectors were evaluated post-incident. Although the detectors inside the building have the ability to span 0–50 | |
| ppm, these detectors were set to span 0–25 ppm. Post-incident, the span was increased to 50 ppm. Additionally, information from the | |
| methyl mercaptan detectors inside the manufacturing building displayed only on the distributed control system (DCS) monitor and was | |
| not recorded by the site’s DCS and data historian [1, p. 37]. CSB investigators, however, were able to obtain information about the | |
| alarms associated with the detectors from alarm logs. | |
| d The methyl mercaptan detectors alarm at 25 ppm—well above the NIOSH recommended exposure limit (REL) of 0.5 ppm and the | |
| OSHA enforceable PEL ceiling limit of 10 ppm. OSHA recommends that employers consider using the lower alternative occupational | |
| exposure limits because the agency believes that exposures above some of these alternative occupational exposure limits may be | |
| hazardous to workers, even when the exposure levels comply with the relevant PELs [149]. The Cal-OSHA permissible exposure limit | |
| (PEL) is an 8-hour time-weighted average (TWA) of 0.5 ppm, and the NIOSH REL is a 15-minute ceiling limit of 0.5 ppm [159], [50]. | |
| Page 15 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 2. Waste Gas Vent Header Piping on the Third Floor of the Manufacturing Building. This portion, where several waste gas | |
| sources come together, is referred to as the waste gas vent header. Waste gas from this portion of the vent header traveled up to | |
| reach the NRS incinerator, a piping configuration that created a low spot where liquid accumulated. To remove the liquid during waste | |
| gas vent header piping high-‐pressure events, operators were instructed to open valves (yellow circle) and drain the system through a | |
| hose routed to a floor drain located near a safety shower. The floor drain is connected an open trench-‐type sump on the first floor. At | |
| the time of the incident, a second set of drain valves (red circle) were also opened directly to the floor inside the manufacturing | |
| building. Source: CSB. | |
| Page 16 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 3. Depiction Showing Where Drain Valves Were Opened. These drain valves released toxic methyl mercaptan into the | |
| manufacturing building. Methyl mercaptan detectors on the first and fourth floors detected high concentrations of methyl | |
| mercaptan shortly after the release began. This depiction is a simplified graphic of the manufacturing building (see Section 4.5) and | |
| does not show the location of Operator 1. Source: CSB. | |
| At about 3:30 am, Operator 1 made an urgent call for help over the radio. Various personnel interpreted her | |
| communication in different ways, generally as either “We need help!” or “I need help on the fourth floor!” The | |
| Board Operator tried to get more information through radio communication, but neither the Shift Supervisor nor | |
| Operator 1 ever responded [1, p. 29]. | |
| Two operators (Operator 2 and Operator 3) who were in the control room and heard the distress call ran to the | |
| manufacturing building to help. Another operator (Operator 4) saw Operator 2 and Operator 3 running to the | |
| manufacturing building, and he followed them. None of these operators knew of the major release of toxic | |
| methyl mercaptan inside of the manufacturing building; therefore, they did not wear any respiratory protection | |
| when they ran into the manufacturing building. The manufacturing building lacked automatic visual or audible | |
| Page 17 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| alarms to alert fieldworkers or prevent them from entering a potentially toxic atmosphere (Section 3). In | |
| addition, the building’s ventilation fans were not working, a situation that, in DuPont’s operating procedures, | |
| required “restricted access” to the building. But DuPont La Porte’s procedures did not define “restricted access” | |
| or require that operators wear respiratory protection in the building when access was restricted, even though a | |
| toxic chemical release could accumulate in the unventilated building [1, p. 29]. | |
| Operator 2, Operator 3, and Operator 4 each entered the south stairway and took different a route inside the | |
| manufacturing building to try to find Operator 1 (Figure 4). Operator 2 went to the third floor, where he was | |
| fatally overcome by methyl mercaptan [1, p. 29]. Operator 4 went to the second floor. He walked about 10 feet | |
| and hit what he later described as a “wall” of methyl mercaptan, but he managed to retreat to the stairwell [1, p. | |
| 29]. Operator 3 went to the fourth floor but did not find anyone. He then announced on the Lannate® Unit’s | |
| public-address system that he did not see anyone on the fourth floor. The Board Operator responded that the | |
| Shift Supervisor and Operator 1 may be on the third floor [1, p. 29]. Operator 3 then began to feel light-headed. | |
| He made his way to the stairwell and lost consciousness while descending from the fourth floor [1, p. 29]. | |
| Page 18 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 4. Depiction of Paths Taken by Operator 2, Operator 3, and Operator 4 When Whey Responded to Operator 1’s Distress Call. | |
| Locations of the deceased Shift Supervisor and Operator 1 are also shown. Operator 2 was killed by methyl mercaptan exposure, | |
| and Operator 3 and Operator 4 were exposed to high concentrations of methyl mercaptan. This figure shows the opposite side of | |
| the manufacturing building from the view in Figure 3. Source: CSB. | |
| The Board Operator then tried to reach the Shift Supervisor, Operator 1, and Operator 2 over the radio, but they | |
| did not respond. An operator in the control room, Operator 6a (the brother of Operator 2), then grabbed three 5- | |
| minute escape respirators. Other operators in the control room warned him not to enter the manufacturing | |
| building because they did not know what was going on or where the nonresponsive operators were. Operator 6, | |
| however, took the escape respirators and rushed to the manufacturing building [1, p. 29]. | |
| At about 3:40 am, Operator 6 encountered Operator 4 in the south stairway of the manufacturing building and | |
| put an escape respirator on him (Figure 5). The breathing air helped Operator 4 recover, and he exited the | |
| manufacturing building safely. A worker—likely Operator 6—then manually activated the manufacturing | |
| building fume release alarm, an alarm intended to alert area workers of a toxic chemical release in the building. | |
| Operator 6 then went to the third floor of the manufacturing building. At some point after helping Operator 4, | |
| a Operator 6 was a board operator for another process in the Lannate® Unit. | |
| Page 19 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Operator 6 retrieved a self-contained breathing apparatus (SCBA) from inside the manufacturing building. He | |
| tried to rescue his brother (Operator 2) by putting one of the escape respirators on his face. Operator 6 was then | |
| fatally overcome by methyl mercaptan before he could connect his own respirator mask to his SCBA tank. | |
| Figure 5. Depiction of the Path Taken by Operator 6 Inside the Manufacturing Building. Operator 6 helped Operator 4 escape by | |
| providing him with a respirator. Operator 6 was fatally overcome by methyl mercaptan when trying to rescue his brother, | |
| Operator 2, on the third floor. Source: CSB. | |
| EMERGENCY RESPONSE | |
| At about 3:50 am, the Board Operator called for the plant emergency response team (ERT)a to respond to the | |
| manufacturing building, stating over the intercom system, “We need rescue people, and there’s people missing.” | |
| This announcement started a chain of miscommunication. To the ERT, a request for “rescue” meant specifically | |
| a At the time of the incident, three companies (DuPont, Kuraray, and Invista) operated at the La Porte site and shared one ERT for the | |
| site, which had members from each company and was managed by DuPont. The ERT members worked other, primary jobs for one of | |
| the three companies (such as unit operators), and they responded as ERT members during emergencies. The site’s ERT staffing included | |
| about 60 employees. Section 4.1 discusses the composition of the ERT in more detail. | |
| Page 20 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| high-anglea or confined-space rescue. Therefore, the ERT responded to the request for help by gathering only | |
| technical rescue gear (e.g., harnesses and ropes), not knowing that there was a major toxic chemical release | |
| (Section 4.3.1) [1, p. 30]. | |
| At 3:57 am, the Board Operator called the security guard at the main entrance to ask the guard to call 9-1-1. The | |
| Board Operator communicated only that workers were missing and requested rescue. The guard, in turn, gave | |
| limited information to the 9-1-1 operator: | |
| 9-1-1 Operator: Harris County 911. What is the location of your emergency? | |
| Caller: This is DuPont on Strang Road…. They had an emergency out here. They got four people | |
| missing.… I was just called by the Lannate® supervisor [Board Operator] that he has four people | |
| missing. | |
| 9-1-1 Operator: So, are they somewhere there, or you don’t know where they’re at? | |
| Caller: I don’t know, ma’am. I am up in the front. I just got the phone call. | |
| 9-1-1 Operator: Okay, you don’t know their names or anything? | |
| Caller: No ma’am, just they needed rescue. | |
| 9-1-1 Operator: They need rescue? | |
| Caller: Yes ma’am. | |
| 9-1-1 Operator: And you don’t know their names, no descriptions, nothing? | |
| Caller: No ma’am. I just know that they’re workers. | |
| At 3:58 am, site emergency responders from the ERT arrived at the scene with only their technical rescue gear. | |
| They quickly realized that there was an ongoing chemical release and that they needed additional personal | |
| protective equipment (PPE). At 4:05 am, the Incident Commander, who had responded to the initial rescue | |
| request, called for the ERT to come to the scene with bunker gearb and SCBAs—the PPE necessary to enter an | |
| area with a toxic and flammable chemical release. When ERT members attempted to start the mini-pumper | |
| truck that contained SCBAs and radios, however, it would not start and could not make it to the incident scene | |
| (Section 4.3.2).c | |
| a A high-angle rescue uses a variety of technical rope rescue techniques to retrieve injured or otherwise incapacitated persons on terrain at | |
| slopes of 60º or greater. Victims are hoisted from one level to another using ropes, pulleys, harnesses, belay devices, and various hauling | |
| implements [120]. | |
| b “Bunker gear” is a common term for firefighting protective clothing [96]. | |
| c The mini-pumper truck was located more than 2,000 feet from the control room. | |
| Page 21 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| The Incident Commander also requested safety data sheets for chemicals processed inside the manufacturing | |
| building, including methyl mercaptan. The ERT, however, did not initially use air monitoring equipment to | |
| determine what chemical was leaking. According to DuPont La Porte’s Lannate® emergency response plan,a | |
| area personnel control air monitoring equipment for their unit. Because the Shift Supervisor (Process | |
| Coordinator) who oversaw process operations was a victim of the incident and was not available to fulfill the | |
| assigned role of providing chemical hazard and unit-specific information about each of the processes to the ERT | |
| during an emergency, air monitoring was delayed during the early hours of the incident. Meanwhile, site | |
| personnel recognized the release by odor and believed that methyl mercaptan was the chemical leaking inside | |
| the building.b | |
| At around 4:10 am, the Incident Commander established a hot zone around the manufacturing building. The hot | |
| zone’s boundaries, however, were not clearly communicated or marked by the ERT (Section 4.7). | |
| At 4:12 am, an emergency operations center coordinator made a second 9-1-1 call, but he had not yet been | |
| informed by ERT personnel what chemical was leaking, or whether the leak posed a public threat, and was | |
| therefore unable to relay this critical information to the 9-1-1 operator: | |
| 9-1-1 Operator: Harris County 911. What is the location of your emergency? | |
| Caller: This is in La Porte, Texas.… We have an emergency at the DuPont Plant in La Porte.… | |
| We have a possible casualty five, is what my medics are telling me. We have some injuries. We | |
| need La Porte EMS for transportation.… | |
| 9-1-1 Operator: Okay, sir. How did this happen? Is it chemical-related? | |
| Caller: I am not certain. I just know … they’re doing a rescue—they’re doing a rescue right now. | |
| We have some injured people. I’m not sure if there’s any chemicals involved or not. I am just | |
| relaying the message. | |
| … | |
| Caller: I have just got some more information. We have five people unaccounted for. We have | |
| had a chemical release … I am not sure what chemical, in one of our buildings. Five people are | |
| unaccounted for. Rescue team is trying to reach them at this point. That’s all the information I | |
| can give you right now. | |
| … | |
| a The Lannate® Unit emergency planning and response manual was developed to comply with the OSHA Process Safety Management of | |
| Highly Hazardous Chemicals standard, 29 C.F.R. § 1910.119(n) (2013). Under this standard, facilities are required to develop an | |
| emergency action plan and potentially an emergency response plan (29 C.F.R. § 1910.38 (2002); 29 C.F.R. §§ 1910.120 (a), (p), and (q) | |
| (2013)). An emergency response plan under the Hazardous Waste Operations and Emergency Response (HAZWOPER) standard is | |
| required if an internal emergency response team is responding to or has substantial threat of responding to releases of hazardous | |
| substances (29 C.F.R. §§ 1910.120 (a)(2)(iv) and (q)(1) (2013)). Because the La Porte site had an internal emergency response team that | |
| responded to releases of hazardous substances, HAZWOPER required that the site have an emergency response plan. | |
| b Using smell to locate or characterize sources of a release is a poor practice. Chemicals have different physical properties, including | |
| olfactory fatigue, no odor, and toxicity if inhaled. | |
| Page 22 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 9-1-1 Operator: Okay sir. And can you tell me, is this any risk to the public? Is it going to be a | |
| possible escaping from your premises? | |
| Caller: No ma’am, it is not. | |
| 9-1-1 Operator: No threat? | |
| Caller: No ma’am. | |
| … | |
| 9-1-1 Operator: And we don’t know what kind of chemical it is? | |
| Caller: No ma’am. As soon as I find out, I will let you know. I’ve got my team trying to | |
| determine that right now. | |
| At about 4:15 am, ERT members assigned an operator | |
| (Operator 7) to bring them SCBAs because the ERT | |
| mini-pumper truck holding SCBAs could not respond | |
| to the scene. DuPont stored additional SCBAs outside | |
| a building closer to the manufacturing building. | |
| Assisting the ERT as requested, Operator 7 went alone | |
| to retrieve these SCBAs and unknowingly walked into | |
| the path of the methyl mercaptan being released from | |
| the manufacturing building (Figure 6).a The hot zone | |
| was not clearly identified or communicated to plant | |
| personnel. As a result, when Operator 7 went to | |
| retrieve the SCBAs, she was unaware that she was | |
| entering a potentially hazardous area. When Operator | |
| 7 went outside, though unable to smell methyl | |
| mercaptan, she felt ill.b Realizing that she might be in | |
| a dangerous position, she retreated to the control roomc | |
| (Section 4.7). | |
| At about 4:20 am, Operator 3 regained consciousness and | |
| managed to exit the manufacturing building [1, p. 29]. | |
| Figure 6. Depiction of Path Taken by Operator 7 to Retrieve | |
| SCBAs for ERT When the Mini Pumper Truck Would Not Start. | |
| The hot zone was not controlled adequately to ensure that | |
| personnel did not enter a hazardous area. Source: Google | |
| Earth, with annotations by CSB. | |
| a At 3:50 am, at Ellington Field, Texas (about 10.5 miles southwest of the DuPont La Porte facility), the wind was blowing from the | |
| northeast at 8.1 miles per hour (mph) [100]. | |
| b These symptoms are consistent with methyl mercaptan exposure. Olfactory fatigue is known to occur with exposure to methyl | |
| mercaptan, resulting in the exposed person not being able to detect the chemical by smell. Inhaling methyl mercaptan can also induce | |
| headaches, dizziness, nausea, vomiting, coma, and death [80]. | |
| c Operator 7 believes she was exposed to a high concentration of methyl mercaptan, but she was able to return to safety. | |
| Page 23 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| ERT members saw him near the manufacturing building and escorted him to safety. | |
| Beginning at about 4:25 am, the first ERT entry team entered the manufacturing building. Although the ERT | |
| used breathing air (SCBAs) to protect themselves from toxic exposure, they did not monitor the atmosphere | |
| during this building entry to assess explosive hazards. Portions of the building likely had an explosive | |
| atmosphere during the incident (Section 4.4.1), and air monitoring could have alerted personnel to this potential | |
| hazard during this entry. The ERT’s post-incident critique stated “metering and [air] monitoring equipment | |
| were maintained by the unit. Since the technical knowledge basea was incapacitated, there was a delay in | |
| establishing [air] monitoring.” | |
| During the building entry, an ERT member found drain valvesb from the waste gas vent header on the third floor | |
| open, with a gas (later identified as methyl mercaptan) flowing from them. The ERT members also found the | |
| Shift Supervisor on the floor of the third story, about 30 feet north of the drain valves. They also found | |
| Operator 6 next to his brother (Operator 2), and both men were unresponsive. Operator 2 had a 5-minute escape | |
| respirator bag over his head. This respirator was one of the three escape packs brought into the building by | |
| Operator 6. Operator 6 had a 30-minute SCBA air bottle in front of him and the mask on his face, but he had | |
| not connected the mask to the air bottle. Methyl mercaptan likely incapacitated Operator 6 while he was trying | |
| to don his SCBA [1, p. 31]. A postmortem examination determined that the Shift Supervisor, Operator 2, and | |
| Operator 6 were killed by asphyxia through exposure to methyl mercaptan. | |
| During the release, the ERT used a plume dispersion model to predict the methyl mercaptan plume (cloud) size | |
| and concentration profile releasing from the manufacturing building. To predict the methyl mercaptan plume | |
| effectively, the modeling software required an estimate of the methyl mercaptan release rate. The emergency | |
| response personnel, however, did not have an available method to estimate the methyl mercaptan release rate. | |
| Lacking other data sources and based on the perceived low odor of methyl mercaptan outside the manufacturing | |
| building, they estimated a release rate of 10 pounds per hour. With this input, the model predicted that methyl | |
| mercaptan would not leave DuPont property at concentrations harmful to the public. The CSB determined, | |
| however, that the emergency response personnel greatly underestimated the release rate. It was not possible for | |
| the CSB to determine the exact off-site methyl mercaptan concentration immediately after the release; however, | |
| the CSB concluded that the total release of about 24,000 pounds of methyl mercaptan created the potential for a | |
| dangerous concentration of methyl mercaptan to have been released off-site (Section 4.8.1). | |
| Beginning at 5:08 am, three external firefighter groups arrived on-site, and at 5:15 am the ERT conducted its | |
| second entry into the manufacturing building. On the third floor, an ERT responder closed the open drain valves | |
| from which he had observed vapor (methyl mercaptan) escaping. | |
| a The Shift Supervisor who served as the Process Coordinator—that is, the technical liaison—was killed by the release. | |
| b These drain valves were not closed at this time. | |
| Page 24 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| At about 5:40 am, emergency responders established and barricaded the hot zone. Until this point, the hot zone | |
| had not been marked clearly. At 5:57 am, the Incident Commander requested Harris County personnel to | |
| perform air monitoring off-site. | |
| At 6:02 am, approximately three hours after the release started, DuPont La Porte personnel turned off the methyl | |
| mercaptan storage tank pump, which had been operating since the last startup attempt, before the release began | |
| (Figure 7). Shutting off this pump significantly slowed the methyl mercaptan release rate (Section 4.6).a | |
| Figure 7. Location of Methyl Mercaptan Pump. The pump was turned off nearly three hours after the release began. Source: | |
| Google Earth, with annotations by CSB. | |
| From 6:10 am to 9:30 am, the ERT conducted the third, fourth, and fifth ERT building entries to search for | |
| Operator 1, who was still missing. Due to the complex layout and emergency responders’ lack of knowledge of | |
| the manufacturing building, the emergency responders had difficulty finding Operator 1. They had no maps to | |
| reference during their search, and DuPont La Porte did not have cameras in the manufacturing building to | |
| a The design of the nitrogen relief valves at the railcar loading and unloading stations did not consider a scenario in which the relief | |
| valves could be lined up with the discharge of the methyl mercaptan pumps, as they were at the time of the incident. The methyl | |
| mercaptan pump discharge pressure (90 pounds per square inch gauge (psig)) was higher than the set pressure (80 psig) of these nitrogen | |
| relief valves. Therefore, the methyl mercaptan pump would cause the relief valve to open and release the highly toxic and highly | |
| flammable chemical to the atmosphere. When tested post-incident, three of the four nitrogen rupture discs burst, and all four of the | |
| nitrogen relief valves leaked. Because the rupture discs and relief valves would not hold pressure when tested, an atmospheric release of | |
| highly toxic and highly flammable liquid methyl mercaptan likely occurred during the incident through this relief system that was | |
| intended to release and disburse nitrogen vapor [1, p. 46]. A rupture disc is a non-reclosing pressure relief device, a type of emergency | |
| relief device. According to the Center for Chemical Process Safety (CCPS), an emergency relief device is designed to open during an | |
| emergency or during abnormal conditions to prevent rise of internal fluid pressure in excess of a specified value. The device also may be | |
| designed to prevent excessive internal vacuum [110]. For more information on pressure relief devices, see “An Overview of Pressure | |
| Relief Devices” [111, pp. 20-27]. | |
| Page 25 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| provide a view of the different floors of the building (Section 4.5). To facilitate the search efforts, the ERT | |
| assigned area operators—including the Board Operator—to draw building maps to help emergency responders | |
| navigate the manufacturing building. During this time, ERT responders continued closing valves throughout the | |
| Lannate® Unit to stop the release of methyl mercaptan. | |
| At 6:14 am, a Harris County Sheriff’s sergeant noticed an “intense smell” in Deer Park (west of La Porte), and | |
| at 6:30 am, he communicated, “the odor on [Highway] 225 [is] strong” (Figure 8). | |
| At 8:07 am, Harris County’s Hazardous Materials Team performed off-site air monitoring to measure the | |
| concentration of toxic methyl mercaptan outside of the DuPont fence line. Harris County’s instrumentation did | |
| not detect methyl mercaptan in the air (Section 4.8.4). | |
| At 10:07 am—seven hours after the release began—DuPont activated the methyl mercaptan tank emergency | |
| isolation valve to isolate the methyl mercaptan storage tank completely from the leaking process piping (Section | |
| 4.6). | |
| Between 11:15 am and 11:55 am, during the sixth ERT entry into the manufacturing building, Operator 1 was | |
| found unresponsive in the north stairwell of the manufacturing building. The coroner later determined that | |
| Operator 1 had died from asphyxia and acute exposure to methyl mercaptan. | |
| Figure 8. Locations Where a Sheriff’s Sergeant Reported Strong Methyl Mercaptan Odor During the Incident. Source: Google Earth, with | |
| annotations by CSB. | |
| Page 26 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 3 DELAYED AWARENESS OF TOXIC CHEMICAL RELEASE BY OPERATIONS | |
| Highly toxic methyl mercaptan was released into the manufacturing building for about 40 minutes before | |
| operations personnel in the control room realized the extent of the emergency in the building, and for more than | |
| six additional hours before the release was fully controlled. The CSB identified factors that led to this delay in | |
| recognizing a major chemical release, including: | |
| 1. The Board Operator was focused on process equipment high-pressure events that he believed | |
| were critical. Operations personnel became aware of the high-pressure events when insecticide | |
| manufacturing equipment venting into the waste gas vent header began to exhibit high-pressure | |
| alarms. At this point, operations personnel shifted their attention from the problem of plugging in | |
| the methyl mercaptan feed system to the current problem of high pressure in the waste gas vent | |
| header piping to the NRS incinerator. DuPont La Porte operations staff did not correlate the high- | |
| pressure problem with the troubleshooting efforts to unplug the methyl mercaptan feed piping | |
| through hydrate dissociation. Rather, they attributed the high-pressure events to the routine problem | |
| of liquid accumulation in the waste gas vent header piping. The Board Operator directed personnel | |
| to help troubleshoot the high-pressure problem [1, p. 28]. The operating pressure of various pieces | |
| of process equipment inside the manufacturing building, however, continued to increase, in some | |
| equipment exceeding the high-scale detection limits of process instrumentation. The Board | |
| Operator was concerned about the potential for equipment overpressure and the release of toxic | |
| chemicals to the atmosphere outside the manufacturing building. Even though methyl mercaptan | |
| detectors were beginning to alarm, the Board Operator either was unaware of them or had | |
| normalized them, not realizing the alarms were alerting him that a significant release had started to | |
| occur inside the building. Unaware that a significant methyl mercaptan release had begun, the | |
| Board Operator remained focused on controlling the high pressure he was observing inside the | |
| equipment.a | |
| 2. Lannate® Unit personnel accepted methyl mercaptan releases and the associated alarms as | |
| normal because of methyl mercaptan’s low odor threshold,b a history of frequent alarms, and | |
| a lack of hazard recognition that methyl mercaptan could be lethal. Methyl mercaptan is a | |
| highly toxic chemical, but its odor can be detected at very low concentrations that are not | |
| a Although the Board Operator acknowledged the methyl mercaptan alarms on the control system during the incident, afterwards he did | |
| not recall that any methyl mercaptan detectors inside the manufacturing build had alarmed. | |
| b Odor threshold, in general, is the lowest concentration of a gas or other material’s vapor that can be detected by odor. Odor threshold | |
| values are not fixed physiological parameters or physical constants but instead statistical points representing the best estimated value | |
| from a group of individual responses [112, p. 2]. The odor threshold for methyl mercaptan is approximately two parts per billion (2 ppb). | |
| However, olfactory fatigue is known to occur with methyl mercaptan, causing the exposed person no longer to be able to detect the | |
| chemical by smell. As a result, odor may not provide adequate warning of hazardous concentrations [80, p. 1]. | |
| Page 27 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| considered a health risk to people.a Additionally, the Lannate® Unit used methyl isocyanate (MIC)b | |
| and chlorine,c which are generally accepted as being more hazardous (toxic) than methyl | |
| mercaptan.d As a result, even though Lannate® Unit personnel were trained on methyl mercaptan | |
| toxicity hazards,e personnel at the site became accustomed to smelling methyl mercaptan daily | |
| without experiencing negative health effects, leading workers to become less wary of methyl | |
| mercaptan leaks and the risks associated with them. According to one DuPont worker, there was a | |
| perception that methyl mercaptan (which workers called “MeSH”) was not dangerous: | |
| And I smell MeSH all the time … but it never … I smelled MeSH, but I | |
| never felt I couldn’t breathe. Like whether it’s, there’s—whether it’s a | |
| small leak or anything, it just never—I didn’t think MeSH was that | |
| dangerous. I thought it, you know, but it is. | |
| During the troubleshooting efforts before the major release began, smaller releases of methyl | |
| mercaptan had caused the site to have a strong odor of methyl mercaptan. Therefore, when the | |
| major release began, site personnel did not realize there was a major release, in part because they | |
| were accustomed to smelling the chemical. | |
| 3. Personnel were not wearing personal methyl mercaptan detectors. DuPont La Porte had some | |
| personal methyl mercaptan detectors available, but they were never issued to operators to wear in | |
| the field. Such detectors could have warned Operator 2, Operator 3, and Operator 4 (personnel who | |
| initially responded to Operator 1’s distress call) of the high methyl mercaptan concentration inside | |
| the manufacturing building. | |
| a Methyl mercaptan gives off a smell like rotten cabbage. It can be smelled at only 2 parts per billion [80, p. 1]. OSHA’s permissible | |
| exposure limit, however, is 10 parts per million, which is 5,000 times the minimum concentration that can be smelled. The low odor | |
| threshold of mercaptans makes them useful as fuel gas odorants [80, p. 2]. | |
| b MIC is a raw material used in the production of insecticides at La Porte, including the Lannate® process. The 1984 MIC release at the | |
| Union Carbide insecticide plant in Bhopal, India, that killed thousands of people is an example of the extremely toxic properties of MIC | |
| [148]. For more information, see Reflections on Bhopal after Thirty Years [148]. | |
| c DuPont’s corporate standard for the management of highly toxic materials identifies both methyl mercaptan and chlorine as highly | |
| toxic. DuPont considers a material to be highly toxic if it is handled, stored, or shipped in a sufficient quantity that a credible event could | |
| result in a concentration of Emergency Response Planning Guidelines (ERPG)–3, and if it has a Substance Hazards Index (SHI) greater | |
| than or equal to 4,000. This level “is the maximum airborne concentration below which nearly all individuals could be exposed for up to | |
| 1 hour without experiencing or developing life-threatening health effects.” Emergency responders use ERPG-1, -2, and -3 concentration | |
| data to determine how to protect the public [167]. DuPont determines the SHI using vapor pressure and ERPG-3 data for each chemical. | |
| Using this approach, DuPont derived an SHI of 19,855 for methyl mercaptan and 385,197 for chlorine. | |
| d Methyl mercaptan’s threshold quantity (5,000 pounds) that presents the potential for a catastrophic event, under PSM, is larger than that | |
| of chlorine (1,500 pounds) or MIC (250 pounds), making it less hazardous than either of the other two chemicals (29 C.F.R. § 1910.119, | |
| Appendix A). | |
| e DuPont La Porte used computer-based training to communicate hazards about methyl mercaptan (i.e., to perform hazard | |
| communication, or HAZCOM), consisting of methyl mercaptan hazard information and a quiz. The information gives some of the toxic | |
| exposure limits for methyl mercaptan. Additionally, the training details that gross exposure can result in death, but it does not specify the | |
| value at which the chemical is immediately dangerous to life and health. The training advises workers to use at a minimum an SCBA | |
| when responding to a methyl mercaptan alarm, and not to use smell to detect leaks because methyl mercaptan can cause olfactory fatigue, | |
| causing anyone exposed to it to stop perceiving an odor within minutes. If there is a leak, personal protective equipment (PPE) is | |
| supposed to be upgraded. Upgraded PPE also applies to line breaking, and it includes a chemical suit with taped sleeves and cuffs, | |
| chemical hood, chemical boots, chemical gloves, and an SCBA. | |
| Page 28 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 4. DuPont La Porte did not have audible or visual alarms on or in the manufacturing building to | |
| alert field personnel of a methyl mercaptan release automatically. DuPont La Porte relied on | |
| verbal communication of alarms, which automatically displayed on a continuously manned control | |
| board. | |
| The delay in recognizing this event as a major toxic chemical release that was becoming a deadly concentration | |
| of methyl mercaptan inside the building contributed to the response of Operator 2, Operator 3, and Operator 4 to | |
| Operator 1’s distress call without respiratory protection. According to DuPont La Porte’s Lannate® emergency | |
| planning and response manual, if a sensor detected a methyl mercaptan leak and initiated an alarm, personnel | |
| were required to notify a shift supervisor, sound a plantwide fume release alarm, and wear appropriate PPE | |
| (including SCBA) during any attempts to stop the leak. The manufacturing building, however, including the | |
| building’s overall construction, detectors, and alarms, was not designed such that personnel could be readily | |
| notified of a major chemical release in the manufacturing building. Without being made aware of the major | |
| chemical release inside the building, Operator 2, Operator 3, and Operator 4 entered without respiratory | |
| protection. As a result, Operator 2 was killed by methyl mercaptan exposure, and Operator 3 and Operator 4 | |
| were exposed to dangerous concentrations of methyl mercaptan. | |
| GUIDANCE TO INDUSTRY | |
| It is crucial that workers understand when an emergency is occurring. OSHA’s Hazardous Waste Operations | |
| and Emergency Response (HAZWOPER) standard requires that an emergency response plan address emergency | |
| recognition and prevention.a For this standard to be effective, companies should ensure that their systems | |
| associated with emergency recognition and prevention, such as alarms and training, can inform workers of | |
| hazards and emergencies. | |
| For example, audible or visual alarms can automatically relay to personnel in the field information about a | |
| hazardous condition—such as a release of a toxic chemical. Systems like those implemented at DuPont, on the | |
| other hand, where alarms displayed only on an operator’s control board and still needed an operator to verbally | |
| communicate alarms, have inherent potential delays. The Center for Chemical Process Safety’s book | |
| Continuous Monitoring for Hazardous Material Releases provides guidance on the use of such alarms: | |
| There are occasions when process equipment must be located indoors due to weather-related or | |
| quality control issues. Combustible [and toxic] gas detection should be provided in these | |
| buildings…. This detection should be configured to: | |
| • Send an alarm signal to a continuously manned location; | |
| • Activate visible and audible alarm devices on the exterior of the building at each | |
| entranceway and within the structure. The devices within the structure should be | |
| a 29 C.F.R. § 1910.120 (q)(2)(iii) (Feb. 8, 2013). | |
| Page 29 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| configured using the guidance for fire alarm devices, as provided in NFPA 72, National | |
| Fire Alarm and Signaling Code®; and | |
| • | |
| Include a local means of silencing the alarms [6, pp. 63-64]. | |
| Training is another important way to address emergency recognition and prevention. Under OSHA’s Hazard | |
| Communication (HAZCOM) standard, companies are required to provide information to employees about the | |
| hazardous chemicals that they may be exposed to at work, including through training.a Companies should | |
| ensure that, in addition to having access to chemical information, employees understand the hazards of all | |
| chemicals they are working with and may be potentially exposed to if there is a release. In cases of multiple | |
| hazardous chemicals, such as MIC, chlorine, and methyl mercaptan, it is important that companies effectively | |
| train workers on the hazards of each chemical. This training is important for workers to help ensure they have a | |
| working knowledge of chemical hazards. | |
| Working knowledge of the hazards of all chemicals they are working with and may be potentially exposed to if | |
| a release occurs can improve employees’ recognition of emergency conditions and help them prevent major | |
| accidents in the manner that an emergency response plan intends. | |
| 4 EMERGENCY RESPONSE OPERATIONS | |
| On the night of the incident, the Board Operator’s request for the emergency response team (ERT) to come to | |
| the scene triggered the start of emergency response operations. From this initial request for ERT aid to the final | |
| response activities, the La Porte site’s emergency response efforts were characterized by miscommunication, | |
| disorganization, and a lack of situational awareness. The following key emergency response weaknesses are | |
| discussed in this section: | |
| • Based on DuPont La Porte’s emergency response plan, emergency response personnel relied on the | |
| expertise of the shift supervisor, who was the designated process coordinator. The Shift Supervisor, | |
| however, was a victim of the incident, and no one else on the shiftb was designated to backfill the role of | |
| process coordinator. This gap led to weaknesses in several aspects of the emergency response | |
| operations (Section 4.2), including the initial assessment of the problem and of the resources needed for | |
| an effective response. | |
| • There was a delay in ERT deployment and readiness to respond to the release, due to both a | |
| misunderstanding of the type of emergency and the failure of an ERT mini-pumper truck that stored | |
| SCBAs to start (Section 4.3). | |
| • Searching for the missing workers put the ERT responders at high risk. ERT responders entered a | |
| hazardous and potentially explosive atmosphere without performing air monitoring. Additionally— | |
| a 29 C.F.R. § 1910.1200 (b)(1) (Feb. 8, 2013). | |
| b The Lannate® Unit’s emergency planning and response manual designated a primary and secondary backup for the process coordinator. | |
| These backups, however, were not on-site during the evenings and weekends, including when the incident occurred on November 15, | |
| 2014. | |
| Page 30 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| unbeknownst to them—they entered an area of the manufacturing building that DuPont La Porte had | |
| previously identified as a collapse risk in the event of an explosion (Section 4.4). | |
| • DuPont La Porte’s emergency planning and response manual lacked a building map or floor plans to aid | |
| emergency responders in navigating the manufacturing building. As a result, the ERT experienced | |
| difficulties navigating the manufacturing building while searching for a missing operator; they resorted | |
| to assigning unit operators, including the Board Operator, to draw maps of the building to help guide | |
| them. This assignment diverted the Board Operator’s attention from other critical tasks, such as | |
| viewing process data on the control room computer screen to try to identify the source of the release | |
| (Section 4.5). | |
| • The methyl mercaptan release was not controlled until three hours after it began. Personnel did not | |
| evaluate process data to determine the cause of the release until hours into the response efforts. | |
| Analysis of process data from the methyl mercaptan storage tank earlier during the release may have | |
| revealed that the methyl mercaptan storage tank level was continually dropping and that isolating the | |
| tank could stop the release (Section 4.6). | |
| • Emergency responders established a hot zone that was not clearly marked or communicated, thereby | |
| allowing an operator to be potentially exposed to a dangerous concentration of methyl mercaptan when | |
| tasked to assist the ERT (Section 4.7). | |
| • The ERT underestimated the quantity of toxic methyl mercaptan released. Because DuPont La Porte | |
| lacked fence-line monitors and the ERT did not conduct air monitoring to determine the concentration | |
| of methyl mercaptan leaving the site, the ERT did not have accurate values to use in its dispersion | |
| model. Instead, ERT members estimated a small quantity of methyl mercaptan based on verbal | |
| descriptions of the release’s downwind odor. As a result, the incident command did not issue warnings | |
| to the community surrounding the La Porte facility to take protective actions from the possibility of | |
| toxic concentration of methyl mercaptan exiting the site during the release. Furthermore, because air | |
| monitoring had not occurred during the release, neither DuPont La Porte nor the CSB can pinpoint the | |
| exact methyl mercaptan concentration that left the site, or what the potential health risk was to the | |
| public, if any (Section 4.8). | |
| ERT BACKGROUND | |
| DuPont was originally the sole operator of the La Porte site. In recent years, however, DuPont had sold portions | |
| of the operations and leased its facilities to other companies, including Kuraraya and Invista.b Kuraray, Invista, | |
| and DuPont formed a consolidated ERT at the site, managed by DuPont but jointly staffed by members of the | |
| a Kuraray is a chemical company that specializes in functional materials [169]. | |
| b Invista is a subsidiary of Koch Industries, Inc., that manufactures nylon, spandex, polyester, and specialty materials. | |
| Page 31 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| three companies.a All of the ERT members had other primary jobs for one of the three tenant companies (such | |
| as unit operators), and they responded as ERT members when alerted during emergencies. In its 2012 Risk | |
| Management Plan, DuPont La Porte stated that it used the National Incident Management System (NIMS) to | |
| systematically manage safety, tactics, strategy, personnel, equipment, and logistics, and to work seamlessly with | |
| any responding departments and agencies [7].b The site’s ERT was staffed by about 60 employees and had the | |
| following structure: | |
| • | |
| Incident Command Organization: 2–4 trained incident commanders on each shift | |
| o Training: National Pro Board Certifiedc as Fire Service Instructors (based on National Fire | |
| Protection Association, or NFPA, 1041 competencies), and Advanced Exterior Fire Fighters, | |
| Interior Structural Fire Fighters, and Industrial Fire Brigade Leaders (based on NFPA 1081 | |
| competencies) | |
| • Fire Brigade Members: 12 members on each shift | |
| o Training: National Pro Board Certified as Advanced Exterior Fire Fighters and Interior | |
| Structural Fire Fighters (based on NFPA 1081 competencies) | |
| • Emergency Medical Services: 2–3 members on each shift | |
| o Training: Texas Department of State Health Services–Certified Emergency Medical | |
| Technicians (EMTs), Basic and Intermediate Training | |
| • Rescue Technicians: 3–5 members on each shift | |
| o National Pro Board Certified in Rope, Confined Space, and High Line Rescue (based on | |
| NFPA 1006 competencies) | |
| • HAZMAT Technicians: most ERT members | |
| o Training: National Pro Board Certified (based on NFPA 472 competencies) | |
| Although ERT members were trained to perform emergency response functions, they were not trained on the | |
| specific hazards of each unit because there were many units within the three companies that processed various | |
| chemicals with different hazards. The La Porte site attempted to bridge this gap by designating a technical | |
| liaison position called the “process coordinator” to provide chemical hazard and unit-specific information about | |
| each of the processes to the ERT during an emergency. This position, along with the emergency operations | |
| a Post-incident, on July 1, 2015, DuPont La Porte’s performance chemicals business unit was spun off to Chemours [107], [108, p. 35]. | |
| Chemours also provides ERT members to the La Porte site. | |
| b According to the U.S. Federal Emergency Management Agency (FEMA), “NIMS provides a common, nationwide approach to enable | |
| the whole community to work together to manage all threats and hazards. NIMS applies to all incidents, regardless of cause, size, | |
| location, or complexity” [132]. | |
| c The National Board on Fire Service Professional Qualifications (aka the Pro Board) is an accreditation body in the fire service training | |
| community. It accredits fire service training organizations, which in turn certify emergency responders to specific levels of training and | |
| competency in accordance with professional qualification consensus standards developed by the National Fire Protection Association | |
| [97]. | |
| Page 32 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| center coordinators, was intended to play a critical role in interfacing with and helping to develop and execute | |
| emergency response actions with the ERT incident commander. | |
| PROCESS COORDINATOR WAS MISSING | |
| The DuPont La Porte’s emergency response plan required the appointment of a shift “process coordinator” from | |
| each unit to assist the incident commander in providing technical knowledge specific about their unit. The | |
| emergency response plan defined the process coordinator as “the area emergency response director of the shop, | |
| warehouse, office building, or process unit involved in the incident who is responsible for developing an action | |
| plan with the Incident Commander and directing area resources.” The process coordinator was responsible for | |
| assisting the incident commander in several tasks during emergencies (see Figure 10), including the following: | |
| 1. Communicating (by radio) with the ERT’s incident commander and the site’s emergency operations | |
| center, as the operations technical liaison | |
| 2. Determining the source and size of chemical leaks (see Figure 9) | |
| Figure 9. Responsibilities of the Process Coordinator (Production Shift Supervisor). In the Lannate® Unit’s emergency | |
| planning and response manual, DuPont La Porte provided this checklist for a process coordinator to use to gather | |
| information. Source: DuPont. | |
| 3. Deciding whether the site needs to perform off-site air monitoring | |
| 4. Deciding whether to evacuate the unit | |
| Page 33 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 10. A Section from the Lannate® Unit’s Emergency Planning and Response Manual. It details the process | |
| coordinator’s role during an emergency. Source: DuPont. | |
| As with most shifts, the Lannate® area process coordinator on the night of the incident was the Shift Supervisor. | |
| The Shift Supervisor in this case, however, was a victim of the toxic chemical release, and DuPont La Porte had | |
| not designated an on-site backup process coordinator for this shift.a As a result, these important functions were | |
| either performed in a disorganized manner by other operations personnel or never performed at all. | |
| In DuPont’s emergency response critiques conducted after the incident, emergency response personnel | |
| communicated the following: | |
| - “Weakness: Loss of area technical expertise led to confusion and lack of communication about the | |
| process. Personnel that would have staffed the technical specialists’ positions … were victims.” | |
| - “What are contingency plans? If team leader or subject expert are not available, how is that handled?” | |
| a The primary and secondary backup coordinator noted in Figure 10 were day shift employees and were not on-site at the time of the | |
| incident. | |
| Page 34 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| GUIDANCE TO INDUSTRY | |
| Specific technical knowledge from process unit experts—including technical and operations personnel—can be | |
| invaluable to the incident commander in an emergency at a chemical processing facility. The Hazardous Waste | |
| Operations and Emergency Response (HAZWOPER) standard identifies persons who can provide this | |
| information as specialist employees.a Companies need to ensure that these individuals are preidentified as | |
| technical support personnel and to provide backup capability for all situations in the event the primary technical | |
| support personnel are unavailable. | |
| The emergency response plan can address how technical and operations personnel are integrated into emergency | |
| response roles—the HAZWOPER standard requires that the emergency response plan address “personnel roles, | |
| lines of authority, training, and communication.”b When developing an emergency response plan, companies | |
| should also consider the nature and extent of duties designated to particular people to ensure they can reasonably | |
| carry out those duties during an emergency. | |
| One way companies can ensure that a backup is available during a shift is to have a recall list that identifies | |
| alternates who can provide technical support. The Center for Chemical Process Safety (CCPS) gives the | |
| following guidance in its book Guidelines for Technical Planning for On-Site Emergencies: | |
| Technical support consists of personnel within the organization and outside emergency response | |
| groups. Technical support personnel within the organization include engineers, chemists, | |
| operators, maintenance personnel, and managers having special knowledge of process operations, | |
| emergency systems, building plans and equipment layout, and hazardous materials present. A | |
| technical support team consisting of these experts or others with similar qualifications will | |
| provide the incident commander with a pool of knowledge to draw on during emergencies. | |
| Technical support team members should be placed on the recall list with designated alternates | |
| in the event team members are directly involved with the emergency or are not available [8, pp. | |
| 283-284] (emphasis added). | |
| Another valuable tool that an emergency response team can use is a checklist. As suggested by CCPS, | |
| Planners should develop emergency action checklists to augment the emergency plan by | |
| providing memory joggers for actions. Action checklists are concise reminders to personnel of | |
| key actions that need to be undertaken [8, pp. 158-159]. | |
| a The HAZWOPER standard defines specialist employees as “employees who, in the course of their regular job duties, work with and are | |
| trained in the hazards of specific hazardous substances, and who will be called upon to provide technical advice or assistance at a | |
| hazardous substance release incident to the individual in charge”; it further specifies that they “shall receive training or demonstrate | |
| competency in the area of their specialization annually” (29 C.F.R. § 1910.120 (q)(5)). | |
| b 29 C.F.R. § 1910.120 (q)(2)(ii). | |
| Page 35 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| A company can develop these checklists in the incident response planning stage and use them during | |
| emergencies to ensure proper performance of important emergency response tasks like those DuPont assigned to | |
| the process coordinator, even in scenarios in which the primary assignee is unavailable. | |
| DELAY IN ERT READINESS TO SEARCH FOR MISSING WORKERS | |
| It took 35 minutes from the request for ERT assistance for the La Porte ERT to initiate the first entry into the | |
| manufacturing building to search for the missing workers. Discussed below, miscommunication, the lack of a | |
| process coordinator, and inadequate emergency preparation by DuPont all contributed to the ERT’s delayed | |
| response. | |
| 4.3.1 CALL FOR ERT RESPONSE | |
| When the Board Operator made his call for ERT assistance over the intercom system, he stated, “We need | |
| rescue people, and there’s people missing.” To the ERT, rescue specifically meant retrieval of a person from an | |
| area, so the team brought to the scene only technical rescue gear (e.g., ropes and harnesses). As discussed in | |
| Section 2.2, ERT members realized upon arrival that contrary to their presumption, there was a chemical release | |
| and they needed additional PPE. | |
| DuPont provided the CSB with a May 2014 slide presentation for new employees showing the structure of the | |
| ERT and how to request assistance from the ERT. The presentation detailed the differences in response groups | |
| (fire brigade, EMT, rescue, and fume release). While some operations personnel may have understood the | |
| organization of the ERT, a key problem at the time of the request for the ERT during the incident under study | |
| was that the incident was not yet fully understood. As a result, important details could not be communicated in | |
| the initial ERT call. In addition, DuPont lacked an on-site backup process coordinator to communicate and | |
| coordinate response operations with the ERT. | |
| In one of DuPont’s emergency response critiques conducted after the incident, emergency response | |
| personnel communicated the following: | |
| - “There was confusion on who was to respond.… For [a request for] EMT, only EMT responds. | |
| For [a request for] rescue, only rescue responds, and for [a request for] ERT (fume/fire) then | |
| everyone responds.” | |
| - “There was a communication problem initially. [We attempted] radio communication, not | |
| realizing that [the] leader had been lost. Operators were lost. No one [in the unit] knew how ERT | |
| worked.” | |
| Page 36 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| GUIDANCE TO INDUSTRY | |
| Plant emergency procedures should clearly define the alerting and notification process for different types of | |
| plant emergencies. These procedures should also include guidance for situations in which initial information to | |
| effectively assess the nature of the problem and the amount and type of ERT resources required is incomplete. | |
| 4.3.2 ERT MINI-‐PUMPER TRUCK NOT OPERATIONAL | |
| When the ERT learned that the incident involved a chemical release, the Incident Commander asked ERT | |
| members to come to the scene with bunker gear and SCBAs. ERT members stored their SCBAs on a mini- | |
| pumper truck. When an ERT member tried to start this mini-pumper truck to bring the gear to the site where it | |
| was needed,a the vehicle did not start because of multiple mechanical malfunctions. An October 2, 2014, work | |
| order states, “Check[ed] batteries and they were not good, remove[d] and replace[d] with new ones.” Replacing | |
| the batteries, however, did not fully repair the truck, which failed to start at the time of the incident, impairing | |
| the effectiveness of the ERT response. After the incident, DuPont La Porte personnel replaced the truck’s | |
| alternator, battery cable, and belts to make it operable. Although the pumper truck was a critical piece of | |
| emergency response equipment, DuPont La Porte did not adequately maintain it before the incident to ensure its | |
| availability during an emergency. | |
| In DuPont’s emergency response critiques conducted after the incident, emergency response | |
| personnel communicated: | |
| - “Opportunity: Exercise and inspect the emergency services apparatus on a more frequent basis. | |
| Perform maintenance in a timely fashion to ensure the functionality and reliability.” | |
| - “Weakness: I had gear and equipment that didn’t make it to the scene. We get in a comfort zone | |
| and [think] it won’t happen to us, and it did.” | |
| Since the mini-pumper truck holding SCBAs could not come to the scene, the ERT assigned an operator to | |
| retrieve additional SCBAs in the Lannate® Unit for the ERT to use.b Retrieving the SCBAs may have exposed | |
| the operator to a high methyl mercaptan concentration because these SCBAs were downwind of the methyl | |
| mercaptan release point (Section 4.7). | |
| a The pumper truck was a Ford F-450 Mini Pumper. | |
| b The SCBAs on the truck were rated for 60 minutes. Initially, the ERT had to use SCBAs from the area that were rated for 30 minutes. | |
| Later on, 60-minute SCBAs were transported to the scene. | |
| Page 37 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| GUIDANCE TO INDUSTRY | |
| Under the HAZWOPER standard, an emergency response plan must address PPE and emergency equipment,a | |
| such as the SCBAs and mini-pumper truck. It should also contain information on how to ensure that PPE and | |
| emergency equipment are always functional. | |
| Even though industrial facilities may call upon emergency response vehicles infrequently, it is essential that | |
| these vehicles operate as intended when needed. To ensure emergency vehicle reliability, companies need to | |
| develop and apply regular maintenance schedules. The National Fire Protection Association’s Standard for the | |
| Inspection, Maintenance, Testing, and Retirement of In-Service Emergency Vehicles (NFPA 1911) requires | |
| weekly visual and operational checks for emergency vehicles.b Annex C of NFPA 1911, titled Developing a | |
| Preventive Maintenance Program, also provides guidance and example checklists to use when performing | |
| preventive maintenance on emergency vehicles [9, pp. 79-99]. | |
| THE SEARCH FOR MISSING WORKERS WAS HIGH RISK | |
| When the HAZMAT-trained ERT members and the necessary PPE arrived at the scene of the release, the | |
| emergency response still faced three major issues: | |
| 1. The ERT initially did not use air monitoring equipment to identify whether the building had an | |
| explosive atmosphere. | |
| 2. Emergency responders did not know the locations of the missing workers. | |
| 3. Emergency responders were not familiar with the layout of the building and processes. | |
| While no emergency responders were injured, operations under these conditions exposed responders to | |
| increased risk. | |
| 4.4.1 ENTRY INTO POTENTIALLY EXPLOSIVE ATMOSPHERE | |
| During the incident, Harris County emergency responders used a QRAE monitorc and a MultiRAE monitord | |
| during their building entries. These monitors can inform personnel whether the environment is explosive or | |
| a 29 C.F.R. § 1910.120 (q)(2)(xi). | |
| b The 2017 version of NFPA 1911 states, “A visual and operational check of the apparatus shall be performed within 24 hours of a run or | |
| at least weekly” [9, p. 17]. The 2012 version of NFPA 1911, which was the applicable standard at the time of the incident, states, “An | |
| operational check and visual check of the fire apparatus shall be performed on a daily/weekly basis to ensure the operational readiness of | |
| the unit” [98, p. 13]. | |
| c The QRAE monitor is a four-sensor monitor specifically manufactured by RAE to continuously monitor, for example, oxygen, | |
| percentage of lower explosive limit, and toxic gases [124]. | |
| d The MultiRAE monitor, specifically manufactured by RAE, has up to six gas sensors to continuously monitor, for example, percentage | |
| of lower explosive limit (LEL), oxygen, and toxic gases [123]. To obtain percentage LEL, this type of detector is typically calibrated | |
| using methane, and the user multiplies the percentage LEL reading by a given correction factor to obtain the percentage LEL of the | |
| chemical of interest [84]. | |
| Page 38 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| immediately dangerous to life or health (IDLH). Colorimetric gas detection tubes (e.g., Dräger-Tubes) can also | |
| measure gas concentrations during emergencies.a Air monitoring by ERT personnel is a critical element in | |
| employing a risk-based emergency response operation.b Failure to conduct air monitoring increases the | |
| potential for significant risks to emergency responders, employees, and the public, and it can lower the | |
| probability of a safe and effective emergency response. Emergency responders typically use portable air | |
| monitors to measure gas concentrations during entries into hazardous areas. | |
| During the ERT’s initial entry into the manufacturing building to search for the missing workers, ERT members | |
| did not use air monitoring equipment to characterize the building atmosphere. DuPont La Porte had assigned | |
| operations personnel to maintain and control air monitoring equipment within each of their business units to be | |
| made available to the incident commander or the process coordinator during emergencies. The DuPont La Porte | |
| emergency response plan identifies the incident commander as being responsible for directing personnelc to | |
| conduct air monitoring downwind of the release. | |
| There was a delay in air monitoring inside the building, and the ERT could not determine if there was an | |
| explosive atmosphere (methyl mercaptan is a flammable gas)d during the initial entry into the manufacturing | |
| building.e Without this monitoring, the ERT may have unknowingly entered an explosive atmosphere. Later, | |
| the ERT entered the building with other external emergency response groups that had air monitoring equipment. | |
| The potential for a methyl mercaptan explosion in the building posed a serious hazard to emergency responders, | |
| due to both the inherent explosion effects (e.g., overpressure, shrapnel) and the structural collapse risk (Section | |
| 4.4.3). | |
| GUIDANCE TO INDUSTRY | |
| Entering a structure with an unknown environment may pose additional risks to emergency responders. For | |
| example, it may have the potential to be explosive, as in the situation at DuPont La Porte. Recognizing the | |
| issues associated with uncharacterized environments, the HAZWOPER standard requires the individual in | |
| charge (here, the incident commander) to identify to the extent possible “all hazardous substances or conditions | |
| present and shall address as appropriate site analysis, use of engineering controls, maximum exposure limits, | |
| hazardous substance handling procedures, and use of any new technologies.”f Additionally, the HAZWOPER | |
| a “Dräger-Tubes are glass vials filled with a chemical reagent that reacts to a specific chemical or family of chemicals. A calibrated 100 | |
| ml sample of air is drawn through the tube. If the targeted chemical(s) is present, the reagent in the tube changes color and the length of | |
| the color change typically indicates the measured concentration” [125]. | |
| b A risk-based emergency response operation is an approach that sets policy and programmatic priorities based upon measured levels of | |
| risk to lives, property, and the environment [165, p. 6]. | |
| c Personnel can be either mechanics, operators, or emergency response personnel who are trained on air monitoring equipment and | |
| familiar with the area. | |
| d Methyl mercaptan is flammable at concentrations between 3.9 percent and 21.8 percent by volume [50]. | |
| e At approximately 7:30 am, the ERT was pulled out of the building to resolve issues with PPE because it was determined that methyl | |
| mercaptan posed a flammability risk. | |
| f 29 C.F.R. § 1910.120 (q)(3)(ii). | |
| Page 39 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| standard also identifies a safety officer as an individual who assists the incident commander in identifying these | |
| hazardsa and makes safety decisions surrounding them.b This standard gives the incident commander the | |
| responsibility of determining the risks associated with the emergency response using available personnel and | |
| tools (emergency equipment and PPE). Before directing emergency response activities, the nature of the | |
| hazards needs to be identified and characterized to determine the appropriate actions to be taken. | |
| Incident commanders, safety officers, and other emergency response personnel can look to industry guidance to | |
| help them determine the safest course of action in a given situation. For example, NFPA 472, Standard for | |
| Competence of Responders to Hazardous Materials/Weapons of Mass Destruction Incidents, gives illustrative | |
| example conditions—including those conditions present during the DuPont La Porte incident—in which NFPA | |
| recommends prohibiting emergency response personnel from entering the hot zone. They include, among other | |
| conditions: | |
| • | |
| • | |
| flammable or explosive atmosphere present and | |
| insufficient personnel to perform tasks [10, p. 100]. | |
| One method emergency responders can use to characterize unknown environments is air monitoring. To ensure | |
| that emergency responders can perform air monitoring of hazardous atmospheres, industrial facilities should | |
| provide ERT members with their own air monitoring equipment and train them in how to operate it (e.g., NFPA | |
| 472 requires that hazardous materials technicians be able “through detection, monitoring, and sampling,… [to] | |
| verify the presence of hazardous materials… [and] determine the concentration of hazardous materials in the | |
| atmosphere” [10, pp. 42-43]). | |
| If facilities choose to assign maintenance and storage of portable air monitoring equipment to non-ERT | |
| members, the company should also ensure that the ERT can readily locate and access the stored equipment. | |
| 4.4.2 NO TECHNOLOGY TO LOCATE MISSING WORKERS | |
| DuPont La Porte did not equip the manufacturing building with technology either to account for the entry of | |
| personnel into the building or to track their location once inside. The manufacturing building processed highly | |
| hazardous chemicals—including methyl mercaptan and chlorine—in an enclosed environment. Companies can | |
| use technology (such as cameras, badges, or chip readers) to track the locations of personnel upon entry into | |
| high-hazard areas or in the event of an incident. Knowing the location of personnel could help emergency | |
| responders conduct targeted rescues by allowing them to reach affected personnel quickly and minimize ERT | |
| member exposure to hazardous environments. | |
| a “The individual in charge of the [incident command system] shall designate a safety officer, who is knowledgeable in the operations | |
| being implemented at the emergency response site, with specific responsibility to identify and evaluate hazards and to provide direction | |
| with respect to the safety of operations for the emergency at hand” (29 C.F.R. § 1910.120 (q)(3)(vii)). | |
| b “When activities are judged by the safety officer to be an IDLH and/or to involve an imminent danger condition, the safety officer shall | |
| have the authority to alter, suspend, or terminate those activities. The safety official shall immediately inform the individual in charge of | |
| the [incident command system] of any actions needed to be taken to correct these hazards at the emergency scene” (29 C.F.R. § 1910.120 | |
| (q)(3)(viii)). | |
| Page 40 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| GUIDANCE TO INDUSTRY | |
| Facilities that handle large quantities of flammable or toxic chemicals have a responsibility to monitor high- | |
| hazard areas, such as DuPont’s Lannate® manufacturing building, for releases and personnel injuries. That | |
| monitoring capability must be available to emergency response personnel to assess the scope and nature of any | |
| incident, including possible locations of employees within the area. High-hazard areas should be equipped with | |
| sufficient monitoring devices, such as detectors, alarms, and surveillance technology, to identify whether there is | |
| a chemical release (or other type of emergency) and whether personnel are affected.a When surveillance | |
| cameras are used, companies should consider having the camera feeds go to multiple plant locations, including | |
| control rooms, plant security stations, and the plant emergency operations center (EOC). | |
| 4.4.3 UNRECOGNIZED MANUFACTURING BUILDING COLLAPSE HAZARD | |
| A 2002 DuPont La Porte facility siting study predicted potential damage to the manufacturing building based | |
| upon various explosion scenarios. In the analysis of a hypothetical methyl mercaptan explosion on the first floor | |
| of the manufacturing building, the study listed the “Predicted Building Damage Level” as “Collapse []-Building | |
| fails completely. Repair is not feasible.” | |
| Neither DuPont La Porte’s emergency response plan nor the Lannate® Unit’s emergency planning and response | |
| manual included information from the 2002 study on the potential risk of structural collapse in the event of an | |
| explosion. DuPont La Porte did not have a system in place to ensure that emergency planning documents were | |
| updated when site studies, such as a process hazard analysis (PHA), identified relevant information. | |
| Consequently, the emergency planning documents did not prepare ERT members for the risk that the | |
| manufacturing building could collapse. | |
| Although an explosion did not occur and the manufacturing building did not collapse, entry into the | |
| manufacturing building posed a serious safety risk to members of the ERT during emergency response activities | |
| following a significant methyl mercaptan release. | |
| GUIDANCE TO INDUSTRY | |
| NFPA 1620, Standard for Pre-incident Planning, states, “The pre-incident plan shall address the structural | |
| integrity of walls, roofs, and floors” [11, p. 9]. This standard is intended to provide information to the incident | |
| commander. To help emergency responders become knowledgeable of known unit hazards, companies should | |
| develop a system to update emergency planning documents when other studies identify pertinent hazards and | |
| risks. | |
| a According to Sutton, author of Plant Design and Operations, closed circuit television (CCTV) “can help with fire response—not so | |
| much with the initial detection but in providing information that can help with control of the facility and direction of the emergency | |
| response team. Cameras can be installed in a fixed position focused on high-risk areas or may permanently scan large areas.… Typical | |
| locations for CCTV cameras are pump floors in process and oil movement areas, road/railcar loading areas, jetties, and buildings that | |
| contain process equipment” [85, p. 203]. | |
| Page 41 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| DIFFICULTIES NAVIGATING MANUFACTURING BUILDING | |
| Many of the emergency responders searching the manufacturing building worked at the La Porte site as | |
| operators in other units or for other companies located there. Some of these responders, therefore, were | |
| unfamiliar with the manufacturing building—a four-story building containing a large amount of piping and | |
| process equipment, dividing walls, multiple stairwells, and an elevator. Figure 11 shows photos taken inside the | |
| manufacturing building, illustrating the complexity of the layout inside the building. | |
| Figure 11. Photos of the Interior of the Lannate® Manufacturing Building. Source: CSB. | |
| The CSB found that the Lannate® Unit’s emergency planning and response manual did not have a building map | |
| or floor plan to aid emergency responders in understanding and navigating the manufacturing building during | |
| the incident. Emergency responders assigned Lannate® Unit operators—including the Board Operator—to draw | |
| maps of the manufacturing building to assist in the search. The Board Operator informed the CSB as follows: | |
| They got the big pad … and had me sit down and start drawing pictures. And [the emergency | |
| responder] said, “We want it as detailed as you can get.” So, I drew the building, I drew the | |
| stairwells, I drew the reactors, what reactors were where, you know, and coolers, you know, on | |
| each floor. That’s what they wanted me to do, draw a description of each floor as well as I could | |
| … so when they go in, they know where they’re going. They can look, and of course three of | |
| [the missing operators were] found already, but they never did—at that time, they didn’t know | |
| where [the fourth missing operator] was.… It took me about an hour and a half to draw stuff, you | |
| know. | |
| Page 42 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Seven months before the incident, DuPont La Porte performed a response drill for operators in the Lannate® Unit | |
| and developed a follow-up action item that “plot plans should be readily available for responder reference” | |
| (Figure 12). The CSB found that the drill leader, however, did not assign this action item to specific personnel | |
| or input the item into the site’s action item tracking system. Consequently, no one took responsibility for the | |
| action items, and the recommended plot plans were never created. | |
| Figure 12. Excerpt from an April 2014 Drill Follow-‐Up. It recommended that plot plans be readily available | |
| for responder reference. A plot plan was never made for the manufacturing building. Source: DuPont. | |
| GUIDANCE TO INDUSTRY | |
| Although the HAZWOPER standard requires that emergency response plans detail evacuation routes, | |
| evacuation procedures, safe distances, and places of refuge, it does not specifically require development of plot | |
| plans.a NFPA 1620, Standard for Pre-incident Planning, on the other hand, supports the development of plot | |
| plans in complex hazardous environments. The standard establishes criteria for developing “pre-incident plans | |
| to assist personnel in effectively managing incidents and events for the protection of occupants, responding | |
| personnel, property, and the environment” [11, p. 5]. It also defines different complexity levels of pre-incident | |
| plans: (1) Level 1, Basic, (2) Level 2, Intermediate, and (3) Level 3, Comprehensive. NFPA 1620 states, | |
| Level 3 information is the most detailed level of pre-incident planning and is intended to include | |
| process hazards and protection schemes, detailed occupancy considerations, room or area layouts, | |
| and operational features (e.g. ventilation, power) [11, p. 17]. (emphasis added) | |
| In addition, it is a good practice for site-level emergency responders—and external emergency response | |
| groups—to be familiar with the layout of enclosed buildings within chemical facilities in the event of an | |
| emergency. Familiarity with buildings and process areas can reduce recovery time and aid in life-saving rescue | |
| a 29 C.F.R. § 1910.120 (q) (February 8, 2013). | |
| Page 43 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| operations. Periodic drills inside process structures can help familiarize responders with the buildings and | |
| improve responder navigation during emergencies.a | |
| To help prepare for emergencies, chemical facilities should do the following: | |
| 1. Develop site maps and plot plans of the facility, including the layout of process buildings. Ensure these | |
| maps are up-to-date and readily available to emergency responders. | |
| 2. Coordinate regularly scheduled site tours for both plant and external emergency responders to establish | |
| strong working relationships and help ensure emergency responders are familiar with facility access | |
| points, hazards, emergency response issues, and site or facility layout.b | |
| 3. Familiarize responders with process structures or buildings to improve responder navigation during | |
| emergencies by having periodic drills inside them at established, recurring intervals. To enhance | |
| responder performance, members of an emergency response team should train together, especially in | |
| situations in which multiple companies are staffing a single team. | |
| a NFPA 1, Fire Code, Annex D, “Hazardous Materials Management Plans and Hazardous Materials Inventory Statements,” requires | |
| detailed site, building, and structure drawings. Additionally, facilities are required to have inventory assessments that include chemical | |
| names and their common names. Annex D is not a requirement of NFPA 1 unless it is specifically adopted [106, pp. 731-740]. | |
| b NFPA 600, Standard on Industrial Fire Brigades, states, “Facility fire brigade management should maintain a close working relationship | |
| with all emergency response organizations that could reasonably be expected to respond to the facility during an incident. This | |
| relationship should include … an invitation to the emergency response organizations to participate in a pre-fire planning walk-through or | |
| tour of the facility” [103, p. 19]. | |
| Page 44 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| NO ANALYSIS OF PROCESS DATA TO IDENTIFY SOURCE OF LEAK | |
| Figure 13. Location of Methyl Mercaptan Emergency Isolation Valve Relative to Manufacturing Building | |
| Where Leak Occurred. The emergency isolation valve was not activated until seven hours after the | |
| release began. Source: Google Earth, with annotations by CSB. | |
| DuPont La Porte had installed an emergency isolation valve for the methyl mercaptan storage tank. Companies | |
| often install emergency isolation valves to avoid the need to isolate chemical release points manually during | |
| large releases of a flammable or toxic chemical; locations for such valves include, for example, points near | |
| property lines, at the boundaries of process units, or at liquid outlets of vessels containing flammable or toxic | |
| chemicals.a The installation and use of these valves can help prevent someone from having to enter a flammable | |
| or toxic atmosphere to stop a chemical release. Even though the methyl mercaptan storage tank had an | |
| emergency isolation valve, its closure was significantly delayed. | |
| The release began just after 3:00 am, but | |
| 1. | |
| 2. | |
| the methyl mercaptan storage tank pump was not turned off until 6:02 am—three hours after the release | |
| began—significantly reducing the rate of the methyl mercaptan release, and | |
| the methyl mercaptan storage tank emergency isolation valve was not closed until 10:07 am—seven | |
| hours after the release began—finally isolating the methyl mercaptan storage tank from the process | |
| (Figure 13). | |
| a Emergency isolation valves could be designed to (1) close automatically, for example, during an emergency shutdown of a unit; (2) | |
| close remotely, by manual activation; or (3) be manually closed [81, pp. 123-124]. | |
| Page 45 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Earlier performance of these two critical equipment manipulations could have controlled the release much | |
| sooner. | |
| The CSB determined that the delay in isolating the methyl mercaptan storage tank from the process occurred for | |
| two reasons: | |
| 1. Personnel did not recognize the need to close the methyl mercaptan storage tank isolation valve when | |
| they determined that methyl mercaptan was the chemical being released inside the manufacturing | |
| building. | |
| 2. | |
| No one evaluated process data to determine what was causing the release until hours into the response | |
| efforts. Had personnel looked at the process data earlier during the release, it should have been clear | |
| that methyl mercaptan was flowing from the methyl mercaptan storage tank, requiring closure of the | |
| emergency isolation valve (Figure 14). | |
| Figure 14. Process Data from November 15, 2014. Data shows that methyl mercaptan was | |
| abnormally flowing from the methyl mercaptan storage tank. No one analyzed these data during | |
| the first hours of the incident. Source: CSB graph based on DuPont data. | |
| The CSB identified three causes for not analyzing process data earlier during the release: | |
| Page 46 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 1. The Lannate® Unit’s Shift Supervisor (Process Coordinator), who was responsible for determining the | |
| source of any chemical release and identifying the valves to close to stop the release, had been | |
| overcome by methyl mercaptan exposure, and there was no designated backup on shift (Section 4.2). | |
| 2. During the chemical release, the Board Operator, who could have analyzed the process data, was | |
| repeatedly pulled away from monitoring the process to communicate with emergency responders and | |
| perform tasks such as drawing maps of the building (Section 4.5). | |
| 3. Even though there was a troubleshooting operation going on in the Lannate® Unit before the release, | |
| there was no technical or engineering support on-site to help the operators if the Lannate® process | |
| responded abnormally. Site personnel did not contact the on-call DuPont La Porte technical employeesa | |
| during the early stages of the incident for assistance in identifying the source of the methyl mercaptan | |
| release (Section 4.6). | |
| GUIDANCE TO INDUSTRY | |
| When a process safety incident such as a chemical release occurs, it can be beneficial for technical personnel | |
| who are not immediately involved in emergency response functions to analyze process data and quickly identify | |
| the cause, scope, and magnitude of the incident. This analysis will help the company (or incident commander) | |
| identify needed equipment manipulations to stop or control the incident, such as shutting down equipment or | |
| closing isolation valves, to mitigate the effects of a release and the threat to responders and the public. In | |
| Guidelines for Technical Planning for On-Site Emergencies, CCPS provides guidance on the possible | |
| emergency roles of various plant personnel during an incident [8, p. 161] (Figure 15). | |
| a The DuPont La Porte technical employees were contacted individually throughout the morning by a variety of persons. | |
| Page 47 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 15. Example Roles for Various Plant Personnel During and after an Emergency. | |
| Source: CCPS. | |
| INADEQUATE CREATION AND CONTROL OF HOT ZONE | |
| The ERT did not adequately establish, physically mark, or communicate the boundary of the hot zone during the | |
| early stages of the emergency response efforts. The zone was physically marked only after external emergency | |
| services groups arrived at the scene. The absence of a clear hot zone boundary as part of the early emergency | |
| response led to poor incident scene control, including trouble determining who had entered and exited the hot | |
| zone and whether they were wearing proper PPE. | |
| Page 48 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| During the incident, the ERT asked an operator who was not an ERT member (Operator 7) to assist the team by | |
| retrieving SCBAs from the Lannate® Unit. Because the hot zone was not physically defined, and entry/exit | |
| control points were not staffed and controlled, the operator did not realize the SCBAs were in a potentially | |
| hazardous location. She entered the hot zone without respiratory protection and, based on the symptoms she | |
| exhibited, believes she was exposed to a high concentration of methyl mercaptan (Figure 6). | |
| In one of DuPont’s emergency response critiques conducted after the incident, emergency response | |
| personnel communicated: | |
| “Weakness: Visual markers and communication of the control zone boundaries.” | |
| GUIDANCE TO INDUSTRY | |
| The establishment, communication, and control of a hot zone is necessary to help protect plant personnel and | |
| emergency responders. Under the HAZWOPER standard, an emergency response plan must address “safe | |
| distances and places of refuge.”a An emergency response plan can provide guidance in determining safe | |
| distances and places of refuge for different types of emergencies and in effectively communicating these zones. | |
| Companies can look to voluntary consensus standards for guidance on how to establish hot zones. For example, | |
| NFPA 472, Standard for Competence of Responders to Hazardous Materials/Weapons of Mass Destruction | |
| Incidents, requires that the hazardous materials safety officerb “identify whether the boundaries of the | |
| established control zones are clearly marked … and are being maintained” and “verify that each team is | |
| protected and prepared to perform its assigned tasks by … verify[ing] whether the selection of PPE and | |
| equipment is consistent with the site safety and control plan” [10, p. 61]. | |
| Once personnel establish and communicate a hot zone, they must control entry and exit. HAZWOPER states | |
| that the incident commander “shall limit the number of emergency response personnel at the emergency site, in | |
| those areas of potential or actual exposure to incident or site hazards, to those who are actively performing | |
| emergency operations. However, operations in hazardous areas shall be performed using the buddy system in | |
| groups of two or more.”c These requirements help ensure that emergency response personnel minimize their | |
| potential exposure to hazards. | |
| a 29 C.F.R. § 1910.120 (q)(2)(iv). | |
| b The hazardous materials safety officer is part of the incident command system and ensures that safe practices are followed during | |
| hazardous materials incidents [10, p. 58]. | |
| c 29 C.F.R. § 1910.120 (q)(3)(v). | |
| Page 49 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| ERPG Levels | |
| Emergency Response Planning Guidelines | |
| (ERPGs) are chemical concentration levels used | |
| when preparing for and responding to | |
| emergencies. They are designed to anticipate | |
| public health effects, not occupational health | |
| effects, from exposure to airborne chemicals. | |
| The three ERPG levels are as follows: | |
| ERPG-3: The maximum airborne concentration | |
| below which nearly all individuals could be | |
| exposed for up to one hour without experiencing | |
| or developing life-threatening health effects. | |
| ERPG-3 is a worst-case planning level. | |
| Exposure to concentrations above the ERPG-3 | |
| level will be lethal to some members of the | |
| community. | |
| ERPG-2: The maximum airborne concentration | |
| below which nearly all individuals could be | |
| exposed for up to one hour without experiencing | |
| or developing irreversible or other serious health | |
| effects, or symptoms that could impair an | |
| individual’s ability to take protective action. | |
| At concentrations above ERPG-2, some members | |
| of the community may experience significant | |
| health effects, which could impair them from | |
| taking protective action. Emergency responders | |
| often alert the community to take protective | |
| action in areas susceptible to the ERPG-2 | |
| concentration and above. | |
| ERPG-1: The maximum airborne concentration | |
| below which nearly all individuals could be | |
| exposed for up to one hour without experiencing | |
| more than mild, transient adverse health effects | |
| or without perceiving a clearly defined | |
| objectionable odor [86]. | |
| To prevent a similar hazardous situation to personnel assisting | |
| industrial emergency response teams, companies should ensure | |
| that emergency response team members are trained (1) to | |
| physically designate the hot zone, and (2) to communicate the | |
| location of the hot zone and its entry control points to all | |
| personnel assisting with the emergency response, including | |
| operations personnel. | |
| DEFICIENCIES IN EVALUATING RISK TO THE | |
| PUBLIC | |
| DuPont La Porte did not effectively evaluate the impact of a | |
| potential major methyl mercaptan release on members of the | |
| public. Site personnel had several available methods (discussed | |
| below) to help identify whether a hazardous concentration of | |
| toxic methyl mercaptan was traveling off-site. As discussed in | |
| this section, the emergency responders | |
| • | |
| • | |
| • | |
| • | |
| • | |
| used a model of the chemical release that had | |
| inaccurate model inputs, | |
| did not use available on-site methyl mercaptan | |
| concentration data to evaluate the potential for an off- | |
| site release, | |
| misinterpreted methyl mercaptan physical property | |
| data by mistakenly believing methyl mercaptan was | |
| lighter than air and would not expose people off-site to | |
| hazardous concentrations, | |
| did not adequately communicate to external emergency | |
| response parties the name of the chemical being | |
| released, and | |
| did not perform air monitoring during the release to | |
| predict possible off-site consequences. | |
| Although there was a potential that methyl mercaptan may have | |
| exceeded ERPG-3a concentrations outside the fence line (see | |
| ERPG Levels box), the CSB is not aware of the actual | |
| a The ERPG values for methyl mercaptan in parts per million are ERPG-1, 0.005; ERPG-2, 25; ERPG-3, 100 [82]. People can typically | |
| detect methyl mercaptan odor at about 2 parts per billion (ppb) [80, p. 1]. | |
| Page 50 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| concentrations because timely air monitoring was not performed. Additionally, the CSB is unaware of any | |
| reported off-site injuries. | |
| 4.8.1 RELEASE MODELING | |
| The ERT used software called SAFERa to model chemical releases in real time to help identify areas susceptible | |
| to hazardous concentrations of the chemical being released. Chemical release modeling is commonly used for | |
| assessing response scenarios during the emergency planning process and can also be used as part of incident | |
| management activities during a response. Its use is dependent upon having accurate source data, such as the | |
| chemical release rate. To create an effective model of a chemical release, SAFER needs an estimated chemical | |
| release rate based on accurate data. | |
| The Lannate® Unit’s emergency planning and response manual called for the SAFER operator to create a model | |
| of the release. Because there was no air monitoring information available, the SAFER operator estimated a | |
| release rate based upon an ERT member’s observations regarding the relative strength of the chemical odor | |
| outside of the manufacturing building. The SAFER operator informed the CSB as follows: | |
| Once I found out what the chemical was—methyl mercaptan—I plugged it in [to SAFER] and | |
| we still didn’t know what kind of release rate we had. So, I went ahead and plugged in 10 pounds | |
| [per hour] because based on what [they’re] telling me [they] could barely smell anything. I didn’t | |
| realize it was a significant release. … So, I just had to plug something in, so I plugged in 10 | |
| pounds an hour release rate. … We were just guessing at the release rate. | |
| Using the estimated release rate of 10 pounds per hour, the SAFER software predicted that a hazardous | |
| concentration of methyl mercaptan would not leave the company property. In part because the software model | |
| showed the chemical was not hazardous off-site, DuPont La Porte did not notify the authorities to alert the | |
| community to shelter-in-place or to divert traffic from the nearby Highway 225 (Figure 16). | |
| a At the time of the incident, DuPont La Porte was using SAFER Real-Time to do its emergency response dispersion modeling. This | |
| program is no longer supported, and SAFER has transitioned this program to SAFER TRACE [99]. | |
| Page 51 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 16. Overhead Image of DuPont La Porte Facility. A plume of methyl mercaptan left the DuPont property in a | |
| southeasterly direction toward a major highway and residential area. Source: Google Earth, with annotations by CSB. | |
| Companies should not rely on unsupported data when making critical emergency response decisions, such as | |
| those affecting workers or the surrounding public and community. Companies are best positioned to determine | |
| the types of hazards that their processes and chemicals pose. Moreover, in developing emergency response | |
| plans, companies can develop scenarios for potential releases, which can be an important resource during an | |
| emergency. The U.S. Department of Transportation’s (DOT) 2016 Emergency Response Guidebooka provides a | |
| format that can be used by companies to guide initial emergency response.b Table 1 in the guidebook provides | |
| a The 2016 Emergency Response Guidebook is a joint publication of Transport Canada, the U.S. Department of Transportation (DOT), | |
| and the Secretariat of Communications and Transport of Mexico, with collaboration from Centro de Información Química para | |
| Emergencias of Argentina. The guidebook “is primarily a guide to aid first responders in quickly identifying the specific or generic | |
| hazards of the material(s) involved in the incident, and protecting themselves and the general public during the initial response phase of | |
| the incident.” It is primarily intended for use in transportation incidents involving dangerous goods [12, p. 358]. | |
| b The CSB has found in several of its investigations that application of the Emergency Response Guidebook may not be appropriate at all | |
| fixed industrial facilities due to larger quantities of chemicals at fixed facilities, hazardous process conditions, or possible proximity to | |
| other hazardous chemicals [142, p. 1]. Fixed facilities may find guidance in the Emergency Response Guidebook beneficial in some | |
| scenarios, but such facilities should also consider other information when conducting emergency response operations, such as equipment | |
| inventory, site-specific emergency response plans, and company-specific safety data sheets. If a site does use the Emergency Response | |
| Guidebook as an initial reference early in the release, process data, equipment inventory, and specific site hazards should always be | |
| evaluated to help determine effective emergency response operations. | |
| Page 52 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| standardized instructions for determining the isolation and protective action distances for small and large spills | |
| by predicting the size of downwind areas that could be affected by a cloud of toxic gas [12, p. 292]. This | |
| information is used as initial guidance to determine the size of the public area that should be alerted to take | |
| protective measures, including evacuation. | |
| The 2016 Emergency Response Guidebook is intended to be a reference for emergency responders during | |
| transportation emergency events that could affect the public. It has limitations when it comes to fixed chemical | |
| facilities. For example, in the guidebook, a large spill is anything greater than 55 gallons, yielding a very wide | |
| range in spill amounts. On the night of the incident, approximately 2,530 gallons of methyl mercaptan was | |
| released inside the Lannate® Unit,a which is about 46 times larger than 55 gallons. Even at 55 gallons, the | |
| guidebook recommends that in the event of large outdoor methyl mercaptan spills at night, emergency | |
| responders alert people to take protective action within 1.9 miles (3.1 kilometers) downwind of the release [12, | |
| p. 297]. Figure 17 shows the area to be protected if this guidance had been followed, which includes Highway | |
| 225 and a residential area. If DuPont La Porte had created its own version of a guidebook for release scenarios | |
| (including release of methyl mercaptan), actions may have been taken to protect the public. | |
| Following the incident, based on the methyl mercaptan storage tank level decrease, the CSB calculated that the | |
| methyl mercaptan release rate was closer to 9,000 pounds per hour, much of which was inside the | |
| manufacturing building—a rate 900 times greater than the dispersion model input. In an earlier study, DuPont | |
| determined that a leak greater than 4,500 pounds per hour (from an outdoor, elevated source) could result in | |
| hazardous off-site concentrations (ERPG-3 level) of methyl mercaptan.b According to DuPont’s guide for | |
| consequence analysis, concentrations above ERPG-2 require evacuation of the affected area. No evacuation | |
| occurred, because DuPont lacked adequate release information to provide to authorities. | |
| a The amount of methyl mercaptan released is based on DuPont’s calculations of how much was released during the incident. | |
| b Previously, DuPont had found in a study on a methyl mercaptan storage tank that in the event of a fire, the tank’s relief valves could | |
| release about 10,000 pounds per hour of methyl mercaptan to the atmosphere, causing off-site concentrations exceeding the ERPG-3 | |
| value. To reduce this release rate, DuPont insulated the methyl mercaptan storage tank to decrease the amount of methyl mercaptan that | |
| would exit the relief valves during a fire. DuPont aimed to prevent any methyl mercaptan release rate of greater than 4,500 pounds per | |
| hour “to avoid ERPG-3 concentrations.” During the incident, methyl mercaptan released at a rate of 9,000 pounds per hour—double the | |
| threshold release rate DuPont specified to avoid ERPG-3 (100 ppm) concentrations. | |
| Page 53 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 17. Overhead Image of DuPont La Porte Facility with Recommended Downwind Protection Zone (Shown in Yellow) Based | |
| on the 2016 Emergency Response Guidebook [12, p. 297]. Downwind sections of Highway 225 and residential areas were within | |
| the area recommended for public protection from a methyl mercaptan chemical leak. Source: Google Earth, with annotations by | |
| CSB. | |
| GUIDANCE TO INDUSTRY | |
| Chemical dispersion modeling can be an effective risk-based emergency response tool, but its results are highly | |
| dependent on accurate input data. During an emergency, it can be difficult to obtain an accurate release rate, | |
| limiting the validity of resulting models [8, p. 239]. | |
| Companies can better protect the public from hazardous chemical exposures by identifying a conservative area | |
| where people should take protective action (e.g., sheltering-in-place) in the event of a chemical release, and then | |
| scaling back that area only when reliable information becomes available to justify reducing the protection zone. | |
| In addition, the data available to emergency responders can be enhanced by fence-line monitoring using fixed or | |
| portable monitors (Section 4.8.4). Such monitors can provide real-time data on whether the hazardous chemical | |
| is migrating off-site at dangerous concentrations. | |
| 4.8.2 PHYSICAL PROPERTIES OF METHYL MERCAPTAN | |
| The ERT did not alert the local authorities to notify the public of the chemical release because some emergency | |
| response personnel believed methyl mercaptan was lighter than air and would not affect the local community. A | |
| La Porte facility employee informed the CSB as follows: | |
| Page 54 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| The [sheriff’s deputy] asked me, how did I know that [methyl mercaptan] was not affecting | |
| anybody in the La Porte area. I said, “I’ll ask that question while I’ve got [an emergency response | |
| representative] on the phone.” So, I asked, and that’s when I was told that methyl mercaptan is | |
| lighter than air and it dilutes out, and that it would have dissipated, pretty much, by the fence | |
| line. | |
| Methyl mercaptan, however, is heavier than aira and will tend to stay near ground level. DuPont’s technical | |
| standard for methyl mercaptan states that methyl mercaptan “gas is colorless and heavier than air, so that it can | |
| spread at ground level.” Also, DuPont’s safety data sheet (SDS)b for methyl mercaptan specifies its vapor | |
| density, showing that methyl mercaptan is heavier than air (Figure 18). The CSB could not determine why the | |
| emergency response representative communicating this information believed that methyl mercaptan was lighter | |
| than air. | |
| Figure 18. DuPont’s Safety Data Sheet for Methyl Mercaptan. It indicates that methyl mercaptan is heavier | |
| than air. Source: DuPont. | |
| County emergency responders also had difficulty understanding the chemical properties of methyl mercaptan | |
| during the release. A post-incident narrative written by a member of the Harris County Hazardous Materials | |
| Response Team states: | |
| a The relative gas density or vapor density of methyl mercaptan is 1.66, meaning it is heavier than air, whose density is 1 [50]. | |
| b Beginning in 2012, OSHA’s Hazard Communication Standard (HAZCOM) renamed material safety data sheet (MSDS) to safety data | |
| sheet (SDS) [156, pp. 5, 7]. Although referred to in this report as an SDS, the document shown in Figure 16 uses the older MSDS | |
| language. | |
| Page 55 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Copies of the Safety Data Sheets were retrieved from the [Channel Industries Mutual Aid] | |
| Command Van. The terms “methyl mesh and methyl mash” were used in multiple conversations | |
| but there was no data in the SDSs concerning either term. | |
| “MeSH” is an industry initialism for methyl mercaptan, which DuPont personnel also use,a but personnel did not | |
| adequately communicate the formal chemical name to external emergency response agencies.b | |
| GUIDANCE TO INDUSTRY | |
| Companies should ensure that all personnel who may assist with technical emergency response functions are | |
| trained on and understand the information contained in SDSs. Companies should also consider how to | |
| communicate formal chemical names to outside parties, such as emergency responders, by either ensuring that | |
| all staff are trained on and familiar with formal chemical names (e.g., methyl mercaptan, rather than MeSH) or | |
| by ensuring that SDSs include all alternative substance names, such as shorthand names, initialisms, or | |
| abbreviations [13]. | |
| 4.8.3 CHEMICAL SENSOR DATA | |
| During the release, methyl mercaptan detectors inside and outside of the manufacturing building alarmed on the | |
| control panel. DuPont La Porte had designed the outside detectors to alarm on the control panel when they | |
| sensed a methyl mercaptan concentration of 25 parts per million (ppm) or greater,c specifically to “provide an | |
| early warning for a significant release of [methyl mercaptan] that could have impact off-site.” The three | |
| a “MeSH” is shorthand based upon methyl mercaptan’s chemical formula: CH3SH. “Me” represents the methyl group (CH3) and “SH” | |
| represents the mercaptan group (SH)—these initialisms combine to form “MeSH.” | |
| b The material safety data sheet in Figure 16 does include the term “MeSH” as a synonym for methyl mercaptan. Emergency responders | |
| had access to this sheet; however, they may have been specifically looking for the term “methyl mesh” as a synonym and may not have | |
| realized that the listed synonym “MeSH” referred to the same chemical. | |
| c The ERPG-2 level for methyl mercaptan is 25 ppm. This level “is the maximum airborne concentration below which nearly all | |
| individuals could be exposed for up to one hour without experiencing or developing irreversible or other serious health effects or | |
| symptoms which could impair an individual’s ability to take protective action.” Emergency responders use ERPG-1, -2, and -3 | |
| concentration data to determine how to protect the public [167]. | |
| Page 56 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| detectors inside the manufacturing buildinga (Figure 3) were also set to alarm on the control panel when they | |
| detected 25 ppm methyl mercaptan and were intended to protect workers from exposure to methyl mercaptan.b | |
| From DuPont’s management of change documentation for installation of methyl mercaptan detectors | |
| inside the manufacturing building: | |
| “Present Conditions and Description of Proposed Change: Personnel can enter a potentially | |
| hazardous location without knowing MeSH [methyl mercaptan] has been released to the environment.” | |
| The ERT, however, did not use the data from these detectors to identify whether there was a potential for an off- | |
| site release.c The CSB found that during the incident, the Board Operator communicated information about the | |
| process to emergency response personnel, possibly including readings from these detectors, but these | |
| concentration data do not appear to have been considered when determining the potential for dangerous methyl | |
| mercaptan concentrations off-site. The loss of the Shift Supervisor (Process Coordinator) appears to have | |
| contributed to DuPont La Porte’s not considering these data when assessing the magnitude of the release during | |
| the incident. | |
| 4.8.4 AIR MONITORING | |
| DuPont La Porte personnel did not monitor (test) the air for methyl mercaptan along the site’s property line | |
| (fence line) during the release. DuPont did not have fixed fence-line detectors, necessitating the assignment of | |
| individuals to perform air monitoring manually. The company never performed this critical monitoring along | |
| the fence line during the initial release. | |
| Harris County personnel performed air monitoring near Texas Highway 225 (Figure 16) at approximately 8:07 | |
| am and did not detect methyl mercaptan in the air.d This air monitoring, however, was performed five hours | |
| after the release began and two hours after the methyl mercaptan pump was turned off (which significantly | |
| slowed the release). This value, therefore, did not accurately represent the off-site methyl mercaptan | |
| a There were three methyl mercaptan detectors located inside the manufacturing building, on the first and fourth floors. The third floor, | |
| where the release occurred, did not have any methyl mercaptan detectors. | |
| b The 25 ppm alarm set point is 50 times NIOSH’s REL of 0.5 ppm, and more than double OSHA’s ceiling limit of 10 ppm [50]. | |
| Therefore, alarming at this detection level could not protect workers from exposure to methyl mercaptan. | |
| c Post-incident, the methyl mercaptan detectors were tested and evaluated to determine whether they worked. Not all of the detectors had | |
| the correct span of 0 to 50 ppm, and so some of them would not have been able to read up to 50 ppm. Additionally, these detectors are | |
| limited to detecting a maximum concentration of 50 ppm. | |
| d During the morning of November 15, 2014, the Harris County Pollution Control Services Department and the Houston Bureau of | |
| Pollution Control and Prevention investigated odor complaints. There were 10 confirmed odor complaints downwind from the DuPont | |
| La Porte facility (see Appendix C: Odor Complaints). | |
| Page 57 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| concentrations during the release. A measurable concentration of methyl mercaptan would have been more | |
| likely to be detected when the methyl mercaptan pump was operating. | |
| GUIDANCE TO INDUSTRY | |
| Monitoring for hazardous gases along the fence line at chemical facilities can help the company, emergency | |
| responders, and the public understand the nature and extent of a chemical release. Monitoring for hazardous | |
| gases at fence lines can be performed by fixed detectors, which can continually collect and record data, | |
| providing early notification of releases outside the property.a When fixed detectors are not available, a person | |
| using a portable gas detector may also perform air monitoring. This strategy, however, introduces additional | |
| risk because that individual may enter a hazardous or toxic environment. Proper PPE, including respiratory | |
| protection, must be worn during manual air monitoring operations. In conditions with an unknown | |
| concentration and a potential inhalation hazard, the proper respiratory PPE for personnel, under HAZWOPER, | |
| would be positive pressure air-supplying respirators (i.e., SCBAs) until it is determined to be otherwise.b | |
| Including air monitoring requirements in company emergency response plans and action checklists can help | |
| ensure that fence-line air monitoring is performed during emergencies. Personnel responsible for performing air | |
| monitoring should also be preassigned and quickly able to access air monitoring equipment. | |
| EMERGENCY RESPONSE CONCLUSIONS | |
| As discussed in this section, there were significant deficiencies in DuPont La Porte’s emergency response to the | |
| toxic and flammable methyl mercaptan release. Many of the deficiencies stemmed from a flawed emergency | |
| response system, including flawed implementation of the emergency response plan. Solutions to most of these | |
| deficiencies are covered in Appendix D: Emergency Response Tables. The CSB encourages companies to | |
| review their emergency response systems and related plans to ensure they incorporate the lessons learned from | |
| this investigation. | |
| a In 2015, the EPA finalized a rule for refineries to monitor benzene at their fence lines [153, p. 3], [154], 40 C.F.R §§ 60, 63 (2015). In | |
| promulgating this rule, the EPA acknowledges the importance of monitoring potential sources of hazardous materials and their impact on | |
| the surrounding community [153, pp. 6, 9]. The CSB supported the EPA’s proposal for fence-line monitoring and advocated for an | |
| automatic, continuous system providing real-time data for several reasons, including strengthening community planning and | |
| preparedness [141, pp. 1-3]. | |
| b “Employees engaged in emergency response and exposed to hazardous substances presenting an inhalation hazard or potential | |
| inhalation hazard shall wear positive pressure self-contained breathing apparatus while engaged in emergency response, until such time | |
| that the individual in charge of the [incident command system] determines through the use of air monitoring that a decreased level of | |
| respiratory protection will not result in hazardous exposures to employees” (29 C.F.R. § 1910.120 (q)(3)(iv). | |
| Page 58 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 5 DUPONT’S PROCESS SAFETY MANAGEMENT SYSTEM | |
| DuPont, an American Chemistry Council (ACC) member company and Responsible Care practitioner, | |
| experienced three major process safety incidents that the CSB investigated over the course of five years, despite | |
| implementing its own corporate process safety management system. These incidents were the 2014 La Porte, | |
| Texas, methyl mercaptan release; the 2010 Belle, West Virginia, phosgene release [14];a and the 2010 Buffalo, | |
| New York, hot work incident [15].b During the present investigation, the CSB found a large number of | |
| significant process safety deficiencies at DuPont La Porte that contributed to the incident (see Interim | |
| Recommendations and Section 6) [1]. | |
| According to CCPS, process safety management systemsc are “comprehensive sets of policies, procedures, and | |
| practices designed to ensure that barriers to episodic incidents are in place, in use, and effective” [16]. A | |
| process safety management system will have a variety of programs to address process safety. In addition to | |
| process safety, chemical manufacturing facilities typically also have programs to address personal safety. | |
| Personal safetyd programs and process safetye programs are distinct, and both are important. | |
| DuPont developed its own corporate process safety management system that integrated regulatory requirements | |
| and voluntaryf elements. Companies create their own process safety management systems to address regulatory | |
| requirements, including those under OSHA’s Process Safety Management (PSM) standard and the EPA’s Risk | |
| Management Plan (RMP) rule. Based on the chemicals stored on-site, including methyl mercaptan, DuPont La | |
| Porte determined that PSM and RMP applied to the Lannate® process (Sections 5.1.1 and 5.2.1). These federal | |
| safety regulations provide a process safety management system framework for companies to use in developing | |
| their own programs. In addition to meeting these regulatory requirements, DuPont also voluntarily sought to | |
| integrate the Responsible Careg Management System (RCMS) framework into the company’s own management | |
| system. | |
| a The CSB investigated three separate incidents that occurred in a 33-hour period at a DuPont facility in Belle, West Virginia. One | |
| worker was killed by the release of the highly toxic chemical phosgene [14]. | |
| b The CSB investigated a hot work incident in Buffalo, New York, that killed one contractor and seriously injured another [15]. | |
| c In general, the term process safety management system is interchangeable with process safety management program. | |
| d “Personal safety” incidents affect individual workers, resulting in first aid cases, recordable injuries, lost-time injuries, or fatalities. | |
| Typical causes of personal safety incidents include slips, trips, falls, lacerations, and dropped objects. Personal safety programs try to | |
| reduce the number of worker injuries from these types of hazards by managing individual behaviors. Common areas that personal safety | |
| programs address include personal protective equipment, stop work authority programs, working at heights, hazardous material | |
| communications, confined space permitting, lockout/tagout, cranes and heavy lifts, area access controls, and vehicle operation. | |
| e “Process safety” incidents, on the other hand, include chemical releases, fires, and explosions. Process safety incidents can result in | |
| large-scale destruction to site and community infrastructure and can lead to multiple injuries and fatalities. Process safety programs try to | |
| prevent these incidents by identifying and controlling the process hazards. Examples of process safety programs include process hazard | |
| analysis, inherently safer design, pressure relief systems, automated safety controls, operating procedures, management of change, audits, | |
| emergency response systems, and community involvement programs. | |
| f ACC’s Responsible Care Management System is one example of a voluntary process safety management system. Another is CCPS’s | |
| Risk Based Process Safety Management System, whose 20 process safety elements are detailed in Guidelines for Risk Based Process | |
| Safety [52]. | |
| g The chemical industry developed Responsible Care to help guide companies toward safe and responsible operation. | |
| Page 59 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| This section addresses DuPont’s requirements under OSHA, the EPA, and ACC that the DuPont La Porte site | |
| integrated into its site process safety management system used at the time of the November 15, 2014 incident: | |
| • OSHA’s Process Safety Management Standard (Section 5.1) | |
| • EPA’s Risk Management Plan Rule (Section 5.2) | |
| • ACC’s Responsible Care (Section 5.3) | |
| Additionally, this section discusses how DuPont integrated and implemented the frameworks provided by PSM, | |
| RMP, and Responsible Care into its own corporate safety management system. Ultimately, this PSM system | |
| governed operations at the DuPont La Porte facility at the time of the November 2014 incident (Section 5.4). | |
| DuPont La Porte’s ineffective implementation of the PSM standard, the RMP rule, Responsible Care, and | |
| DuPont’s corporate process safety management system resulted in numerous process safety deficiencies that led | |
| to the incident (Section 6). The incident prompted OSHA and the EPA to investigate the DuPont La Porte site | |
| and resulted in each of these agencies’ initiating enforcement actions for alleged violations of federal process | |
| safety regulations (Section 5.1.2 and Section 5.2.2). The November 2014 incident also caused both ACC and | |
| DuPont to evaluate and make changes to their process safety management systems (Section 5.3.4, Section | |
| 5.4.1.3, and Section 6.1). | |
| OSHA | |
| The Occupational Safety and Health Act of 1970 (OSH Act) was | |
| enacted “to assure safe and healthful working conditions for working | |
| men and women; by authorizing enforcement of the standards | |
| developed under the Act; by assisting and encouraging the States in | |
| their efforts to assure safe and healthful working conditions; by | |
| providing for research, information, education, and training in the field of occupational safety and health; and | |
| for other purposes.”a The Act led to the establishment of OSHA on April 28, 1971 [17, p. 16]. | |
| OSHA developed the Process Safety Management standard in response to the 1990 Clean Air Act Amendments | |
| and multiple safety incidents, such as the 1984 Union Carbide toxic release in Bhopal, India, and the 1989 | |
| Phillips Petroleum Company explosions and fires in Pasadena, Texas [18]. | |
| 5.1.1 THE PROCESS SAFETY MANAGEMENT STANDARD | |
| The stated purpose of the PSM standard is to prevent or minimize the consequences of catastrophic releases of | |
| toxic, reactive, flammable, or explosive chemicals that may result in toxicity, fire, or explosion hazards.b The | |
| standard aims to prevent these releases in locations where employees and others could be exposed to serious | |
| a President Richard M. Nixon signed the Willams-Steiger Occupational Safety and Health Act of 1970 on December 29, 1970 [17, p. 17]. | |
| The OSH Act of 1970 (Jan. 1, 2004). | |
| b 29 C.F.R. § 1910.119. | |
| Page 60 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| hazards resulting from chemicals that pose catastrophic risk when stored in quantities greater than stated | |
| thresholds [19]. | |
| Through this standard, OSHA strives to bring a systematic approach to addressing the hazards associated with | |
| these chemicals by establishing a framework for a process safety management system that integrates | |
| technologies, procedures, and management practices [18]. It does so through the PSM standard’s 14 elements,a | |
| which formalize bedrock safety principles in the form of regulatory requirements. Some of the requirements | |
| include performing a process hazard analysis (PHA), managing changes to a process or equipment, establishing | |
| sound operating procedures, ensuring adequate employee training and involvement, maintaining the mechanical | |
| integrity of all process equipment, and ensuring a satisfactory level of emergency preparedness in the event of a | |
| hazardous chemical release.b | |
| 5.1.2 DUPONT LA PORTE’S IMPLEMENTATION OF PSM | |
| One of the avenues for the PSM standard to apply to a process is that a facility must store at least the established | |
| threshold quantity of what OSHA considers to be a highly hazardous chemical.c Based on the amount of methyl | |
| mercaptan stored at the DuPont La Porte facility, DuPont La Porte determined that PSM regulations applied.d | |
| Additionally, DuPont La Porte personnel integrated PSM requirements into the site’s process safety | |
| management system, including performing periodic PSM compliance audits. DuPont La Porte’s first-party PSM | |
| compliance audits,e which were divided over a three-year cycle, took 68 auditor-days to complete between 2012 | |
| and 2014.f These audits, however, did not identify or effectively correct long-standing PSM deficiencies in | |
| DuPont La Porte’s process safety management system (e.g., deficiencies in performing process hazard analysis | |
| and management of change) (for more detail, see Section 6: Process Safety Management Deficiencies). In the 10 | |
| years before the November 2014 incident, OSHA conducted one inspection at the DuPont La Porte facility | |
| following an oleumg release from the fluoroproducts section of the plant [20] [21]. After the November 2014 | |
| a The 14 PSM elements are the following: employee participation, process safety information, process hazard analysis, operating | |
| procedures, training, contractor management, pre-startup safety review, mechanical integrity, hot work permits, management of change, | |
| incident investigation, emergency planning and response, compliance, and trade secrets. See 29 C.F.R. § 1910.119. | |
| b 29 C.F.R. § 1910.119. | |
| c The PSM standard applies to “(i) A process which involves a chemical at or above the specified threshold quantities listed in appendix | |
| A to this section; (ii) A process which involves a Category 1 flammable gas (as defined in 1910.1200(c)) or a flammable liquid with a | |
| flashpoint below 100°F (37.8°C) on-site in one location, in a quantity of 10,000 pounds (4,535.9 kg) or more except for: (A) | |
| Hydrocarbon fuels used solely for workplace consumption as a fuel (e.g., propane used for comfort heating, gasoline for vehicle | |
| refueling), if such fuels are not a part of a process containing another highly hazardous chemical covered by this standard; (B) Flammable | |
| liquids with a flashpoint below 100°F (37.8°C) stored in atmospheric tanks or transferred which are kept below their normal boiling point | |
| without benefit of chilling or refrigeration.” The PSM standard does not apply to “(i) Retail facilities; (ii) Oil or gas well drilling or | |
| servicing operations; or (iii) Normally unoccupied remote facilities” (29 C.F.R. § 1910.119(a)). | |
| d Under the PSM standard, the threshold quantity of methyl mercaptan is 5,000 pounds. 29 C.F.R. § 1910.119 (App. A). | |
| e 29 C.F.R. § 1910.119(o). | |
| f By dividing the PSM audits into a three-year cycle, the DuPont La Porte site was continually evaluated to see if it met PSM | |
| requirements. | |
| g Oleum is a dense, corrosive liquid consisting of concentrated sulfuric acid containing excess sulfur trioxide in solution [133]. | |
| Page 61 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| incident, OSHA investigated DuPont La Porte’s Lannate® facility for potential violations,a including identified | |
| PSM deficiencies that contributed to the methyl mercaptan release [22].b OSHA also performed an expanded | |
| inspection of the DuPont La Porte site (i.e., evaluated other business units’ compliance) under its National | |
| Emphasis Program (NEP) for chemical facilities [22].c | |
| Although the PSM standard was intended to be performance-based [23],d, e in some respects it functions | |
| primarily as a reactive and activity-basedf regulatory scheme. While OSHA intends for PSM program elements | |
| to reduce risk, no explicit requirement appears under the PSM standard to reduce risks or prevent catastrophic | |
| accidents. Moreover, OSHA is not responsible for proactively evaluating the effectiveness of controls or | |
| safeguards [24, pp. 31-32]. As discussed in the CSB’s investigation report Drilling Rig Explosion and Fire at | |
| the Macondo Well, Volume 4, the United States relies on a regulatory framework that can be satisfied by | |
| “checking the box” when completing a variety of required safety-related activities, such as a PHA or MOC. Yet | |
| mere compliance with those requirements can still fail to improve safety. The safety-related activity may not | |
| adequately identify major hazards or control major accident events, in part because the regulatory regime lacks | |
| targeted risk-reduction, goal-setting requirements [25, p. 26].g For example, a properly completed MOC can | |
| effectively reduce the potential for an accident; however, an ineffective one can satisfy regulatory requirements | |
| and still leave a facility with substantial unmitigated risk. | |
| Under the OSH Act, it is the employer’s responsibility to “furnish to each of his employees employment and a | |
| place of employment which are free from recognized hazards that are causing or are likely to cause death or | |
| serious physical harm to his employees” and to “comply with occupational safety and health standards.”h | |
| Consequently, it is a company’s responsibility to ensure that its implementation of the PSM standard protects | |
| a Under Section 9 of the OSH Act, OSHA has six months to issue citations after a violation has occurred. | |
| b In May 2015, OSHA cited DuPont for 11 alleged safety violations stemming from the incident, including deficiencies in PHAs, | |
| operating procedures, equipment, MOCs, process safety information, training, alarm system, preventing toxic exposure, and contractor | |
| injury logs [164]. DuPont entered into a formal settlement with OSHA on July 17, 2017 [161]. | |
| c On July 9, 2015, OSHA cited DuPont for 8 alleged safety violations from an NEP inspection of the adjacent herbicide and | |
| fluoroproducts (hydrofluoric acid) business units at the DuPont La Porte site, including deficiencies in process safety information, | |
| process hazard analysis, operating procedures, inspections, and documenting and using recognized and generally accepted good | |
| engineering practices [155]. After issuing these citations, OSHA placed DuPont in its Severe Violator Enforcement Program [22]. On | |
| July 17, 2017, DuPont entered into a formal settlement agreement with OSHA [157]. | |
| d Also referred to as performance-based regulations, such goal-setting regulatory requirements and acceptance criteria are specified, and | |
| industry must document that its specific solutions meet the requirements, for example in terms of achieving acceptable risk levels. | |
| e Preamble to Process Safety Management of Highly Hazardous Chemicals; Explosives and Blasting Agents. Section III. Summary and | |
| Explanation of the Final Rule (February 24, 1992). | |
| f Activity-based standards and regulations require the mere completion of an activity and do not focus on the effectiveness of major | |
| accident prevention or risk reduction efforts. | |
| g The only two PSM elements that include goal-setting attributes are process hazard analysis and mechanical integrity. The PSM | |
| standard requires a PHA to “be appropriate to the complexity of the process and [to] identify, evaluate, and control the hazards involved | |
| in the process” (29 C.F.R. §1910.119(e)(1)). Additionally, under the heading “Mechanical Integrity,” the PSM standard requires that | |
| “the employer shall correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in | |
| paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation” | |
| (29 C.F.R. §1910.119(j)(5)). None of the other 12 elements include goal-setting requirements. Another example of a goal-setting system | |
| is ALARP (“As Low as Reasonably Practicable”). | |
| h 29 U.S.C. § 654 (a) (2010). | |
| Page 62 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| workers. OSHA typically investigates whether a company is effectively complying with PSM requirements, | |
| such as management of change, after an incident occurs. Some companies may be complying with PSM | |
| elements without actually reducing risks to employees, and that situation may not be recognized until after an | |
| incident occurs. For PSM elements to be effective in accident prevention, a facility’s implementation must be | |
| aimed at risk reduction, and company audits must be substantive, helping companies ensure that their PSM | |
| programs are working. | |
| 5.1.3 RECENT DEVELOPMENTS AFFECTING THE PSM STANDARD | |
| The PSM standard has undergone little reform since its inception in the 1990s. Following the April 2013 | |
| explosion and fire at a fertilizer storage and distribution facility in West, Texas, President Obama issued | |
| Executive Order 13650, “Improving Chemical Facility Safety and Security.”a The executive order tasked a | |
| working group of federal agencies, including OSHA and the EPA, with modernizing policies, regulations, and | |
| standards to improve the safety and security of chemical facilities. In addition, the CSB placed “process safety | |
| management for the 21st century” on its Drivers of Critical Chemical Safety Change list because additional | |
| work is necessary to modernize federal process safety regulations [26]. | |
| ENVIRONMENTAL PROTECTION AGENCY | |
| In early 1970, the United States began to experience a new and | |
| elevated sense of public concern about the environment, including | |
| air, land, and water pollution and protection. President Nixon sent | |
| to Congress a plan to consolidate many of the federal government’s | |
| environmental responsibilities under one new agency, the Environmental Protection Agency. Reorganizing | |
| would permit response to environmental problems in a manner that would exceed the previous capability of | |
| government pollution control programs. The EPA was established on December 2, 1970 [27]. | |
| 5.2.1 RISK MANAGEMENT PLAN RULE | |
| The EPA’s Risk Management Plan rule constitutes that agency’s efforts aimed at chemical accident prevention | |
| through the creation of a process safety management system framework, paralleling OSHA’s PSM standard, | |
| discussed in the previous section.b Similar to OSHA’s PSM standard, the RMP rule applies to facilities that the | |
| Clean Air Act defines as stationary sources of air pollution, and that use or store specific regulated substances | |
| that the EPA has determined to be extremely hazardous in nature. If any of the specified toxic chemicals or | |
| flammable substances are present at a facility at or above established threshold quantities listed by the EPA in its | |
| regulation, then the RMP rule applies to the chemical process using that substance at that facility. | |
| a Exec. Order No. 13,650, 80 Fed. Reg. 34936 (Aug. 1, 2013). | |
| b 40 C.F.R. § 68. | |
| Page 63 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| After determining that the RMP rule covers a process, a facility must determine which “prevention program” | |
| level (Program 1, 2, or 3) applies to the process, based on the process’s potential impact on the public, by using | |
| off-site consequence analyses, accident history, North American Industrial Classification System (NAICS) code | |
| classification, and PSM program applicability. Program 3a processes are subject to additional, more stringent | |
| requirements than Program 1b and Program 2c processes and must implement elementsd of a prevention program | |
| that are based primarily on OSHA’s PSM standard. In addition, the RMP rule requires all facilities to complete | |
| a hazard assessment based on analysis of worst-case and alternative (more likely) accident scenarios, and | |
| identify off-site consequences, compile a 5-year accident history, and coordinate with local emergency | |
| responders. Program 2 and 3 facilities must develop a management system to implement the RMP elements and | |
| address emergency response requirements of a responding or nonresponding facility to accidental releases of | |
| RMP substances. All of these facilities must submit to the EPA a risk management plan, which is a high-level | |
| summary of a facility’s implementation of and conformance with the RMP rule for all covered processes. | |
| A facility’s EPA risk management plan summary must include | |
| • | |
| • | |
| • | |
| • | |
| • | |
| • | |
| an executive summary; | |
| the registration information of the facility; | |
| at least one worst-case scenario for regulated toxics and at least one worst-case scenario for flammables; | |
| the five-year accident history of covered processes; | |
| information concerning emergency response at the facility; | |
| at least one alternative release scenario analysis for each regulated toxic substance and at least one | |
| alternative release scenario to represent all flammable substances; | |
| • | |
| a summary of the prevention program for each Program 2 process; and | |
| a Program 3 is the highest-level management program. Most PSM-covered processes are in Program 3, which requires a rigorous | |
| management program with detailed record retention criteria and all PSM program elements. Program 3 processes are either subject to | |
| OSHA’s PSM standard under federal or state OSHA programs or classified in one of 10 specified NAICS codes that require placement in | |
| Program 3. This designation imposes OSHA’s PSM standard as the prevention program as well as additional hazard assessment, | |
| management, and emergency response requirements [152], (40 C.F.R. § 68.12). | |
| b Program 1 is the lowest, simplest management program, covering processes that would not affect the public in a worst-case scenario | |
| and facilities that have recorded no accidents with specific off-site consequences within the past five years. This designation imposes | |
| limited hazard assessment requirements and minimal prevention and emergency response requirements [152], (40 C.F.R. § 68.12). | |
| c Program 2 is an intermediate management-level program and covers processes that cannot be designated as Program 1 but are not | |
| hazardous enough to be in Program 3. Program 2 imposes streamlined prevention program requirements, as well as additional hazard | |
| assessment, management, and emergency response requirements [152], (40 C.F.R. § 68.12). | |
| d Elements of RMP, similar to PSM requirements, include the following: process safety information, process hazard analyses, standard | |
| operating procedures, training, mechanical integrity, compliance audits, incident investigations, management of change, pre-startup | |
| reviews, employee participation, hot work permits, and contractors (40 C.F.R. §§ 68.65–68.87, Program 3 Prevention Program). | |
| Page 64 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| • | |
| a summary of the prevention program for each Program 3 process [28, pp. 1-2]. | |
| According to the EPA, the risk management plan can provide valuable information by identifying potential | |
| impacts of a chemical release, steps taken to prevent that release, and emergency procedures should the release | |
| occur, enhancing local first responders’ ability to prepare for and respond to an accident on a covered RMP | |
| process by fostering communications about and understanding of the hazards in the event of an emergency | |
| situation [29]. | |
| 5.2.2 DUPONT LA PORTE’S IMPLEMENTATION OF RMP | |
| Based on the amount of methyl mercaptan stored at the DuPont La Porte facility, DuPont La Porte personnel | |
| determined that the RMP rule applied to the Lannate® process.a Additionally, DuPont La Porte personnel | |
| decided that Program 3 requirements applied to the Lannate® process and integrated Program 3 requirements | |
| into its process safety management system. For example, DuPont La Porte personnel conducted first-party | |
| compliance audits on its RMP program. These audits, however, were superficial, focusing on information | |
| presented in the submitted EPA risk management plan summary and not the substance of the RMP rule | |
| requirements. Although completing and submitting the risk management plan summary satisfies a part of the | |
| EPA’s regulatory requirement, the EPA typically does not assess the risk management plan’s effectiveness in | |
| reducing risk until after an incident. Similar to PSM, a company and its site managers are responsible for | |
| making their risk management plan effective.b | |
| After the incident, the EPA conducted an inspection of the DuPont La Porte facility and alleged 22 separate | |
| violations of the RMP, including failure to develop and implement written operating procedures, failure to | |
| adequately implement MOC procedures, failure to implement safe work practices, and mechanical integrity | |
| violations. This RMP inspection was the first one conducted at the DuPont La Porte facility. Based on these | |
| allegations, on behalf of the EPA, the U.S. Department of Justice filed a complaint on Monday, July 23, 2018, | |
| along with a stipulation of settlement with DuPont, in the U.S. District Court for the Southern District of Texas. | |
| According to the settlement, DuPont was required to pay $3.1 million in civil penalties without admitting | |
| liability. The EPA did not seek corrective actions because the DuPont La Porte facility is no longer | |
| manufacturing chemicals [30]. | |
| 5.2.3 RECENT DEVELOPMENTS AFFECTING THE RMP RULE | |
| As noted above, President Obama’s Executive Order 13650, “Improving Chemical Facility Safety and | |
| Security,” created what the order referred to as the Chemical Facility Safety and Security Working Group. The | |
| a Under RMP, the threshold quantity for methyl mercaptan is 10,000 pounds (40 C.F.R. § 68.130, Table 1). DuPont La Porte identified in | |
| its RMP a methyl mercaptan scenario that could lead to an off-site impact. | |
| b Under the General Duty Clause of the Clean Air Act Amendments of 1990, the owners and operators of facilities that have regulated | |
| and other extremely hazardous substances are responsible for ensuring that their chemicals are managed safely (42 U.S.C. § 7412(r)(1)). | |
| Page 65 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| working group took on many tasksa required by the executive order, including reviewing chemical hazards | |
| covered by RMP and PSM to determine if the RMP or PSM regulatory structures could and should be expanded | |
| to address additional regulated substances and types of hazards. In addition, the EPA and the Department of | |
| Labor were thereafter required to develop a plan, including a timeline and resource requirements, to implement | |
| and enforce any expansion of RMP and PSM in a manner that would address those additional regulated | |
| substances and types of hazards.b | |
| In response to the executive order, on July 31, 2014, the EPA published a request for information concerning its | |
| proposed supplementation of its RMP rule [31]. On March 14, 2016, the EPA published its proposed rule, titled | |
| Accidental Release Prevention Requirements: Risk Management Programs Under the Clean Air Act, Section | |
| 112(r)(7), for notice and comment [32]. On January 13, 2017, the EPA published a final RMP rule amending 40 | |
| C.F.R. § 68 requirements (82 Fed. Reg. 4594). Before the rule took effect, the EPA delayed the implementation | |
| of the January 13, 2017 amendments until February 19, 2019, to review three petitions it had received requesting | |
| reconsideration of the final rule.c Because PSM and RMP modernization is a priority goal of the CSB (see | |
| “Drivers of Critical Chemical Safety Change” [33]), the CSB provided written comments to the EPA on these | |
| occasions.d On September 21, 2018, the U.S. Court of Appeals for the D.C. Circuit issued its mandate, making | |
| the 2017 RMP Amendments Rule effective [34]. On December 3, 2018, the EPA published a final rule that will | |
| incorporate the RMP amendments into the Code of Federal Regulations (40 C.F.R. § 68) [34]. The EPA is also | |
| working on an RMP Reconsideration Rule, which proposes rescinding certain amendments, including those | |
| related to safer technology and alternative analyses, third-party audits, incident investigations, and information | |
| availability [35]. This proposed rule would also modify amendments relating to local emergency coordination, | |
| emergency exercises, public meetings, and compliance dates [35]. | |
| a For more information, see the Department of Homeland Security’s “Actions to Improve Chemical Facility Safety and Security—A | |
| Shared Commitment.” | |
| b Exec. Order No. 13,650, 80 Fed. Reg. 34936 (Aug. 1, 2013). | |
| c On June 14, 2017, the EPA published a final rule to delay the effective date of the RMP rule amendments until February 19, 2019 (82 | |
| Fed. Reg. 27133 (June 14, 2017)). In July 2017, various plaintiffs filed a petition for judicial review of the June 14, 2017 delay rule. On | |
| August 17, 2018, the U.S. Court of Appeals for the D.C. Circuit vacated the June 14, 2017 EPA regulation that delayed the effective date | |
| of the final RMP Amendments Rule (Air Alliance Houston et al. v. EPA et al., No. 17-1155 (DC Cir. 2018)). | |
| d Before the EPA issued its final RMP Amendments Rule on January 13, 2017, the CSB also expressed encouragement to the EPA over | |
| the needed improvements contained in its new regulations intended to prevent chemical incidents. The CSB viewed this activity to be a | |
| good initial step, since the rule adopted several new requirements to help advance chemical safety and the prevention of accidental | |
| releases, including improving communication between facilities and emergency responders, requiring root cause analyses of incidents | |
| and near misses, and requiring chemical facilities to consider “inherently safer” chemicals and production processes [143]. That is why, | |
| in July 2018, the CSB wrote with great concern to the EPA in response to that agency’s May 30, 2018, proposed rule, which proposed | |
| scaling back what had been previously proposed on January 13, 2017 [137]. For more information on the current RMP rule requirements, | |
| see “RMP Amendments Compliance Information” from the EPA. | |
| Page 66 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| AMERICAN CHEMISTRY COUNCIL | |
| The roots of the American Chemistry Council | |
| (ACC) go back to the late 1800s and the formation | |
| of the Manufacturing Chemists’ Association. In | |
| 1978, the association changed its name to | |
| Chemical Manufacturers’ Association. Finally, in | |
| 2000, the association became the ACC [36]. | |
| The ACC’s mission is “to deliver value to our members through advocacy, using best-in-class member | |
| engagement, political advocacy, communications, and scientific research” [37]. The ACC is a trade | |
| organization in the United States that represents chemical companies [37] and requires its member companies to | |
| adhere to its Responsible Care program, a voluntary program developed by the chemical industry to help guide | |
| companies toward safe and responsible operation [38]. The design and implementation of this program are | |
| independent of government involvement and legislative or regulatory requirements.a According to the ACC, | |
| industry-based trade associations and process safety management systems, however, can only supplement | |
| government process safety regulations.b | |
| Even though DuPont experienced major chemical safety incidents and process safety management deficiencies, | |
| it still met its Responsible Care requirements. At the time of the November 15, 2014 incident, DuPont’s process | |
| safety management system conformed to the requirements of the Responsible Care Management System | |
| (RCMS), a key part of Responsible Care. As part of RCMS, DuPont La Porte’s process safety management | |
| system was audited for conformance. Neither first-party nor third-party Responsible Care conformance audits | |
| identified, prevented, or mitigated deficiencies in DuPont La Porte’s implementation of its management system | |
| (see Section 6). The November 15, 2014 incident at DuPont La Porte played a role in the ACC’s launch of a | |
| Process Safety Performance Improvement Task Force, discussed later in this section, endorsed to drive | |
| continuous improvement in process safety and occupational safety. | |
| This section discusses the history of Responsible Care (Section 5.3.1), the current requirements for Responsible | |
| Care (Section 5.3.2), the Responsible Care conformance audits at DuPont La Porte (Section 5.3.3), recent | |
| a Responsible Care is practiced in 65 economies around the world [89]. In some instances, Responsible Care is a requirement of a local | |
| trade association, allowing the associations to implement it according to their needs [88, p. 2]. | |
| b In the ACC’s public comment to the EPA’s RMP revisions (see Section 5.2.1), it suggested that instead of having new requirements for | |
| Safer Technology and Alternatives Analysis, there should be a working group to evaluate leveraging the use of voluntary programs such | |
| as Responsible Care to achieve these goals [126, p. 43]. Additionally, the ACC’s Process Safety Code states that the code “is also | |
| intended to complement regulatory requirements (e.g., OSHA’s PSM standard and EPA’s RMP standard). Regulatory standards, by | |
| necessity, focus on process safety at an individual facility. In contrast, the Process Safety Code addresses issues at a more universal | |
| level, such as across a division or corporation, and includes a company commitment to set expectations regarding process safety, define | |
| accountability for process safety performance, and allocate adequate resources to achieve performance expectations” [44, p. 1]. | |
| Page 67 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| developments in Responsible Care (Section 5.3.4), and improvement opportunities for Responsible Care | |
| (Section 5.3.5). | |
| 5.3.1 HISTORY OF RESPONSIBLE CARE | |
| Prompted by several serious process safety incidents in the 1980s (notably the 1984 Bhopal disaster),a the | |
| Canadian Chemical Producers’ Association drafted the original Responsible Care Codes. Member companies | |
| were required to adhere to these codes to build public trust by showing that they were committed to “doing the | |
| right thing” by operating safely and responsibly [39]. In 1988, the ACCb—a U.S. trade association that | |
| currently represents 187 companiesc—adopted Responsible Care and made it a condition of membership [40].d | |
| Since its adoption, ACC’s Responsible Care program has evolved through efforts to meet the needs of industry | |
| and its members.e For example, in 2003, ACC reshaped its Responsible Care obligations from a series of codes | |
| into a management system called RCMS,f which is intended to provide a framework for integrating Responsible | |
| Care within a company’s management system. In 2003, ACC also added a third-party audit verification | |
| requirement to determine whether member companies are meeting their Responsible Care obligations. ACC | |
| made additional changes to the Responsible Care requirements in 2004, 2005, 2008, 2012, 2013, and 2017.g | |
| Furthermore, according to the ACC, “the development of the Process Safety Code demonstrates how | |
| Responsible Care evolves to maintain and improve effectiveness, as well as responds to industry trends and field | |
| learnings.” The ability to make such changes to the Responsible Care program quickly gives the ACC the | |
| flexibility to adapt the program as needed areas of improvement are identified from industry trends and field | |
| learnings. Regulatory changes, on the other hand, are historically more difficult and time-intensive to | |
| implement (see Sections 5.1.1 and 5.2.1). | |
| a On December 3, 1984, a methyl isocyanate release at the Union Carbide insecticide plant in Bhopal, India, resulted in an estimated | |
| 3,800 deaths within days, and tens of thousands of injuries. Over a period of years, the release killed tens of thousands of people [148]. | |
| b At the time of adoption of Responsible Care, the ACC was known as the Chemical Manufacturers Association. It changed its name to | |
| American Chemistry Council in June 2000 [119]. | |
| c The ACC represents 140 members, 17 affiliates, and 17 associate companies [170]. | |
| d An international trade association, the International Council of Chemical Associations, manages Responsible Care. The requirements, | |
| however, vary between member countries [89]. In this section, unless otherwise stated, Responsible Care requisites refer to the ACC’s | |
| obligations in the United States. | |
| e For example, an explosion occurred at the First Chemical plant in Pascagoula, Mississippi, in 2002. The CSB investigated the incident | |
| and found significant differences between what the company asserted in its Responsible Care self-audit report and the actual facility | |
| status before the explosion. After the accident, the ACC changed its audit methodology from sole reliance on first-party audits to the use | |
| of independent third-party audits [146, p. 59], [87, p. 20]. | |
| f The ACC defines a management system as a set of organized policies, procedures, and practices that express a set of commitments | |
| around a set of core objectives and values. | |
| g The ACC changed the Technical Specification in 2004, 2005, 2008, and 2013 [41, p. 18]. The Guiding Principles were revised in 2008 | |
| [40]. The third-party audit requirements were changed in 2017 [92]. The Product Safety Code and Process Safety Code were approved | |
| in 2012 and required beginning in 2013 [40], [41, p. 16]. | |
| Page 68 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 5.3.2 RESPONSIBLE CARE REQUIREMENTS | |
| Today’s Responsible Care program has four main program elements: | |
| 1. Adhering to the Responsible Care Guiding Principles | |
| 2. Implementing the Responsible Care Product Safety Code, Process Safety Code, and Security Code | |
| 3. Measuring and publicly reporting performancea | |
| 4. Applying the Responsible Care Management System to achieve and verify results [38] | |
| According to the ACC, the Guiding Principles serve as the ethical foundation of the Responsible Care program | |
| [41, p. 1]; the Technical Specification of the RCMS and the supplemental codes are the portions of the system | |
| that have to be audited [42]. DuPont—as a member of the ACC—agreed to implement the latest versions of the | |
| Guiding Principles, Technical Specification, Security Code,b Product Safety Code,c and Process Safety Code. | |
| Per the ACC, Responsible Care’s 12 Guiding Principles are its foundation [41, p. 1]. ACC member companies | |
| endorse and commit to these aspirational objectives, which include the following: | |
| • To design and operate facilities in a safe, secure, and environmentally sound manner | |
| • To instill a culture throughout all levels of the organizations to continually identify, reduce, and manage | |
| process safety risks | |
| • To make continual progress toward a goal of no accidents, injuries, or harm to human health and the | |
| environment from products and operations, and openly report health, safety, environmental, and | |
| security performance [43] | |
| The ACC built the RCMS from its Responsible Care principles. The ACC asserts that the RCMS “is an | |
| integrated health, safety, security and environmental management system based on the principles of Responsible | |
| Care and the Policy-Plan-Do-Check-Act continual improvement cycle” [41, p. 1]. The Responsible Care | |
| Technical Specification divides the requirements of the RCMS into five categories: policy and leadership; | |
| planning; implementation, operation, and accountability; performance measurement and corrective and | |
| preventive action; and management review [41, p. 5]. The requirements stated in the Technical Specification | |
| overlap with both PSM and RMP. These requirements incorporate developing a management system that | |
| a The ACC publicly reports specific personal and process safety metrics by company and personal and process safety metrics in | |
| aggregate [127]. | |
| b According to the ACC, it adopted the Responsible Care Security Code “to further enhance the security of our facilities, our | |
| communities, and the essential products we produce” [128]. | |
| c According to the ACC, it adopted the Responsible Care Product Safety Code “to drive continuous improvement in chemical product | |
| safety as part of the industry’s signature environmental, health, safety, and security management system” [129]. | |
| Page 69 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| includes employee participation, process safety information, compliance (conformance audits), incident | |
| investigation, training, emergency planning and response, MOC, PHA, and contractor management. | |
| The ACC expanded its third-party audit requirements by adding codes. The organization states that these codes | |
| aim to supplement the Technical Specification of the RCMS [44, p. 1]. In 2012, the ACC published its | |
| Responsible Care Process Safety Code of Management Practices [44], requiring member companies to | |
| implement it by January 1, 2013 [41, p. 16]. The ACC states that the code sets forth its “collective commitment | |
| to a culture of process safety throughout our chemical processing operations, management systems and | |
| leadership organizations” [44, p. 1]. Additionally, the code “aims to supplement existing process safety | |
| requirements contained within the Responsible Care Management System® … technical specifications, by | |
| specifically addressing process safety concepts such as leadership, accountability, and culture in order to drive | |
| overall process safety performance improvement” [44, p. 1]. The Process Safety Code breaks down its | |
| management practices into seven categories: leadership and culture; accountability; knowledge, expertise, and | |
| training; understanding and prioritization of process safety risk; comprehensive process safety management | |
| system; information sharing; and monitoring and improving performance [44, pp. 1-3]. This code strengthens | |
| and expands obligations stated in the Responsible Care Technical Specification for practitioners to establish a | |
| comprehensive process safety management system [44, p. 2]. | |
| From Responsible Care’s Process Safety Code of Management Practices: | |
| “Companies will design systems to manage and mitigate identified risks with adequate safeguards. | |
| Management of process safety will take into account passive controls; engineering controls; operational | |
| controls; inherently safer approaches; inspection, maintenance and mechanical integrity programs; | |
| management of change procedures; and scenario planning” [44, p. 2]. | |
| Page 70 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 5.3.3 RESPONSIBLE CARE CONFORMANCE AUDITS | |
| To verify conformance with the RCMSa and Responsible Care Codes,b ACC member companies must undergo | |
| an independent third-party auditc performed by a qualified auditord every three years [41, pp. 4, 16]. This audit | |
| evaluates the practicese of the corporation’s headquarters and a sampling of the company’s facilities,f depending | |
| on the number of facilities a company has [42, pp. 6-8]. For example, large companies, such as DuPont, which | |
| had more than 40 facilities at the time of the 2014 incident, can retain their certification by auditing only eight of | |
| their facilities and their headquarters every three years.g The ACC designed the auditing system to allow | |
| companies to manage their auditing process, including multiple location visits over their audit cycles. | |
| According to the ACC, companies can consider risk and other factors to determine which facilities to submit for | |
| third-party audits [42, pp. 7-8]. For example, DuPont’s Responsible Care auditing process began in 2005 and | |
| the company planned on completing all of its facility audits by 2019. As seen in DuPont’s plan, it could take | |
| more than 14 years before a facility is audited again under Responsible Care, potentially allowing facilities to | |
| fall out of certification or to be inconsistent with other company facilities for many years while the company | |
| remains certified under Responsible Care. Additionally, Responsible Care’s third-party audit requirements are | |
| divided into three groups, depending on the number of facilities a company has. As shown in Figure 19, the | |
| more facilities a company has, the smaller the percentage of its facilities that have to be audited during an audit | |
| cycle to obtain Responsible Care certification [42, p. 7]. | |
| a RCMS is contained in the Technical Specification of the code. This specification is the only portion of RCMS that is required to be | |
| audited. Responsible Care has undergone multiple changes including a shift to third-party audits and the addition of a Process Safety | |
| Code. The CSB recommended to the ACC in its investigation into an explosion at First Chemical that the ACC “ensure that ACC | |
| members understand the audit requirements of Responsible Care and accurately identify and address gaps in facility process safety | |
| programs” [146, p. 67]. Beginning in 2004, the ACC shifted from first-party to independent third-party audits for certification of a | |
| company’s RCMS program. It also required companies to report their statistics on the Responsible Care website. In 2012, Responsible | |
| Care added the Process Safety Code to supplement the Technical Specification, making it auditable as well [40]. | |
| b In November 2017, the ACC changed its third-party audit requirements [92, pp. 3-4]. | |
| c DuPont used both third-party audits and self-audits (first-party) to demonstrate conformance with Responsible Care. Self-audits are | |
| conducted by auditors from the facility being audited, and third-party audits are conducted by auditors from an independent organization | |
| [66, pp. 27-28]. | |
| d Third-party audits are not done by ACC; they are performed by independent auditing firms accredited by the ANSI-ASQ National | |
| Accreditation Board (ANAB). | |
| e The portions of Responsible Care that are audited are the Technical Specification and supplemental codes (Process Safety, Security, and | |
| Product) [45, p. 10]. | |
| f According to the ACC, for purposes of auditing, a facility is defined as a “location falling under an ACC member’s/Responsible Care | |
| Partner’s dues calculations at which commercial chemicals are manufactured, handled, transported, [and] stored and where employees or | |
| others working on behalf of the ACC member/Responsible Care Partner are present” [42, p. 2]. | |
| g The ACC requires that two-thirds of the facilities currently being audited be among those not audited in the previous audit cycle [42, p. | |
| 7]. | |
| Page 71 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 19. Excerpt from Responsible Care’s Third-‐party Audit Requirements. It shows the more facilities a | |
| company has, the lesser are the audit requirements [42, p. 7]. Source: ACC. | |
| The ACC acknowledged that the DuPont La Porte site met its Responsible Care requirementsa in 2007, | |
| following a third-party audit conducted at the DuPont La Porte facility that certified the facility to be in | |
| conformance with the RCMS Technical Specification requirements.b This was the only third-party Responsible | |
| Care evaluation ever performed at the DuPont La Porte facility. A third-party evaluator determines only if a | |
| facility is meeting the Responsible Care requirements that exist at the time of the third-party audit. Furthermore, | |
| a third-party certification does not imply that a facility is meeting its RCMS requirements years later without an | |
| additional evaluation of the facility. Additionally, DuPont La Porte personnel performed six self-audits between | |
| 2007 and the date of the incident.c None of these audits, however, identified or effectively corrected the many | |
| serious and long-standing process safety deficiencies at the site. These process safety deficiencies were | |
| discussed in the CSB Interim Recommendations for this incident and are also described in this report in Section | |
| 6 [1]. | |
| a At the time of the 2007 audit, the Product Safety and Process Safety codes were not in place and the Guiding Principles were located in | |
| the Technical Specification. | |
| b According to the ACC, conformance means meeting code implementation and reporting deadlines; completion of required RCMS third- | |
| party certification in three-year cycles; and annual reporting of performance results, including process safety incident data. | |
| c The DuPont La Porte facility did include in its first-party audit the new requirements for Responsible Care. | |
| Page 72 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Although Responsible Care requires robust process safety programs at its member facilities, the CSB found that | |
| the RCMS on its own is not sufficient to ensure that a particular facility’s safety programs are effective.a For | |
| example, the quality of an audit or assessment can be affected by the amount of information it evaluates. An | |
| average Responsible Care third-party audit that evaluates a facility’s management system lasts three to five days | |
| [45, p. 6],b a relatively short amount of time to analyze significant and complex matters, which could potentially | |
| limit the scope and depth of any audit. | |
| The ACC’s expectation is that a company’s internal audit process be more detailed than the Responsible Care | |
| external audit. For example, a DuPont La Porte environmental, health, and safety manager stated that the | |
| facility’s Responsible Care audits were not as detailed as the audits the company performed to verify | |
| compliance under OSHA’s PSM standard.c DuPont La Porte’s 2007 third-party audit, which covered about 800 | |
| employees and contractors and three business units, took 12 auditor-days.d On the other hand, DuPont La | |
| Porte’s first-party PSM compliance audits,e which were divided over a three-year cycle, took 68 auditor-days to | |
| complete between 2012 and 2014.f Despite taking more than five times the auditor-days of the Responsible | |
| Care audit, the PSM compliance audit requirements were not sufficientg to identify and resolve process safety | |
| management deficiencies that contributed to the November 2014 incident (see Section 6). The ACC believes | |
| that Responsible Care audits verify that a robust, effective management system is in place [46]. The ACC | |
| further believes its auditable Process Safety Code “differs from regulatory standards that, by necessity, focus on | |
| process safety at an individual facility. The Process Safety Code is more universal—it addresses issues across a | |
| division or corporation, and includes a company commitment to set process safety expectations, define | |
| accountability for process safety performance and allocate adequate resources to achieve performance | |
| expectations” [47]. Understanding the health of an organization’s process safety management system, however, | |
| requires a comprehensive assessment of the content and implementation of its programs. | |
| a The ACC has stated to the CSB, “RCMS is not intended to be a company’s sole safety program. RCMS is one component of the | |
| Responsible Care program.… Responsible Care is intended to complement regulatory requirements, a company’s safety processes, and | |
| other initiatives—not replace them.” Moreover, the 2004 RCMS Technical Specification states, “the RCMS is also designed to | |
| incorporate individual company processes for maintaining regulatory compliance and implementing other company programs and | |
| commitments such as sustainable development initiatives.” | |
| b According to a 2015 ACC document, the usual cost for a third-party conformance audit ranges from $6,000 to $10,000. The audit | |
| typically costs $2,000 per audit day (travel plus auditor time). The CSB calculated the three to five days for audits based on these | |
| numbers [45, p. 6]. See American Chemistry Council and National Association of Chemical Distributors, A Comparison of ACC | |
| Responsible Care® and NACD Responsible Distribution® Initiatives. | |
| c OSHA requires PSM audits to be performed at least every three years at all facilities covered by the standard (29 C.F.R. § 1910.119(o)). | |
| d Two auditors worked six days to complete the audit. | |
| e 29 C.F.R. § 1910.119(o). | |
| f Through the division of the PSM audits into a three-year cycle, the DuPont La Porte site was continually evaluated to see if it met PSM | |
| requirements. | |
| g In past investigations, the CSB has identified areas of PSM that could be improved upon. “Modernization of U.S. Process Safety | |
| Management Systems,” previously on the CSB’s Drivers of Critical Chemical Safety Change List, was renamed in 2018 to “Process | |
| Safety Management for the 21st century” and remains on the list [26]. | |
| Page 73 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Although the ACC can remove membership from companies not satisfactorily conforming to the Responsible | |
| Care program,a one of the program’s objectives “is to keep as many companies actively implementing the | |
| program and striving to continuously improve their performance as possible” [48, p. 1]. This objective is | |
| contained in its Guiding Principles: | |
| To make continual progress toward a goal of no accidents, injuries or harm to human health and | |
| the environment from products and operations and openly report health, safety, environmental | |
| and security performance [43]. | |
| DuPont was meeting its Responsible Care requirements, as demonstrated by its audits, even though it | |
| continued to have major process safety incidents across the company.b The ACC informed the CSB that | |
| the November 2014 incident at the DuPont La Porte facility, however, “played a role in the launch of an | |
| ACC Process Safety Performance Improvement Task Force.” | |
| 5.3.4 RECENT DEVELOPMENTS IN RESPONSIBLE CARE | |
| As noted in the previous section, the November 15, 2014 incident played a role in launching the ACC Process | |
| Safety Performance Improvement Task Force. The ACC Board’s Responsible Care Committeec proposed the | |
| task force, and it was endorsed by the ACC in November 2015 to drive continuous improvement by industry in | |
| process safety and occupational safety. In June 2016, the ACC Board approved the task force’s | |
| recommendations, including the following: | |
| • Establishment of new incident information and practice sharing forums | |
| • Formation of regional support networks | |
| • Enhanced collaboration with professional societies | |
| • Enriched data analytics and modified responsible metrics reporting | |
| • Continuous improvement | |
| Since the adoption of these recommendations, the ACC has begun implementing several of them. According to | |
| the ACC, starting in 2016, its Process Safety Committee has held annual process safety forums for ACC | |
| members to “share process safety information, lessons learned, and exemplary practices.” Additionally, the | |
| ACC developed a regional network model for sharing noncompetitive process safety knowledge and solutions | |
| between site process safety practitioners. Specifically, the ACC established regional networks in Houston and | |
| a In the last 10 years, the ACC has removed six companies from its membership due to their failure to meet their Responsible Care | |
| requirements, and in other instances, companies opted to resign voluntarily from Responsible Care prior to potential removal. | |
| b The three major investigations were CSB DuPont La Porte Interim Recommendations [1]; E.I. DuPont de Nemours & Co., Inc., Belle, | |
| West Virginia: Methyl Chloride Release, Oleum Release, Phosgene Release [121]; E.I. DuPont de Nemours & Co Inc. Buffalo, New York | |
| Flammable Vapor Explosion [122]. | |
| c The Board Responsible Care Committee is composed of ACC member CEOs or presidents [45, p. 22]. | |
| Page 74 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Philadelphia and is developing three additional networks. Another development within the Responsible Care | |
| program is the ACC’s adoption of American Petroleum Institute (API) Recommended Practice 754—Process | |
| Safety Indicators for the Refining and Petrochemical Industries [49].a The ACC assessed some of its 2017 data | |
| and publicly reported its high-level findings in 2018.b | |
| 5.3.5 RESPONSIBLE CARE IMPROVEMENT OPPORTUNITIES | |
| In light of the multiple DuPont incidents, the CSB encourages the ACC to evaluate Responsible Care and the | |
| RCMS for additional improvement opportunities, with the goals of helping member companies identify and | |
| correct process safety deficiencies, and preventing major chemical incidents at member company facilities.c | |
| An example of an opportunity for Responsible Care to strengthen its verification systems is including the | |
| aspirational Guiding Principles in its third-party verification audits. For example, a Responsible Care auditor | |
| could delve deeper than the management system and evaluate buildings that contain process equipment, given | |
| that one of the Responsible Care Guiding Principles is “to design and operate facilities in a safe, secure, and | |
| environmentally sound manner” [43].d As demonstrated by the facts of this incident, the Lannate® | |
| manufacturing building had design deficiencies. The portion of the manufacturing building where the incident | |
| took place did not have a stated design purpose—the building was not designed for the process, and the process | |
| a API 754 covers leading and lagging process safety indicators. According to API 754, “The purpose of process safety indicators is to | |
| identify events or conditions that could ultimately lead to higher-level consequences. Indicators provide a means to measure activity, | |
| status, or performance against requirements and goals. Monitoring and analyzing performance enables Companies to take corrective | |
| action as needed. Properly defined and understood indicators can give Companies confidence that the right things are being managed and | |
| tracked” [49, p. 23]. API further explains, “Leading indicators tend to be forward-looking and indicate the performance of the key work | |
| processes, operating discipline, or protective barriers that prevent incidents. They are designed to give an indication of potential | |
| problems or deterioration in key safety systems early enough that corrective actions may be taken” [49, p. 24]. Conversely, API 754 | |
| elaborates, “Lagging indicators tend to be outcome-oriented and retrospective; they describe events that have already occurred and may | |
| indicate potential recurring problems [that] may include fires, releases, and explosions” [49, p. 23]. In reliance on the now-familiar four- | |
| tier pyramid diagram first introduced by H. W. Heinrich in 1931 as a representation of his study of accident data gleaned from the | |
| insurance industry, API 754 breaks down indicators across four tiers. From top to bottom, indicators progress from lagging (Tier 1) to | |
| leading (Tier 4) [49, pp. 11-12]. The ACC has adopted API 754 to the Tier 2 level—a loss of primary containment but of lesser | |
| consequence than a Tier 1 incident (e.g., no casualties, property damage less than $2,000, on a release of less than a predefined reportable | |
| quantity of a process chemical) [145, p. 153]. The ACC has required mandatory reporting under API 754 beginning in calendar year 2018 | |
| for 2017. | |
| The CSB has discussed API 754 in its Macondo (Volume 3) and Williams investigations. Additionally, as part of the Macondo | |
| investigation, the CSB held a public hearing on process safety indicators. The CSB has also looked toward CCPS on approaches to | |
| leading and lagging indicators in its Guidelines for Process Safety Metrics. | |
| b The ACC reported Tier 1 findings and is still in the process of reviewing Tier 2 events [104]. For more information, see Responsible | |
| Care Process Safety. | |
| c As a result of its First Chemical investigation, the CSB previously made a recommendation to the ACC to evaluate its audit program: | |
| “Ensure that ACC members understand the audit requirements of Responsible Care and accurately identify and address gaps in facility | |
| process safety programs” (2003-01-I-MS-R11), [146, p. 67]. | |
| d At the time of the 2007 third-party RCMS conformance audit, the Responsible Care Guiding Principles were different and were | |
| included in the RCMS Technical Specification. The principle at the time of the audit that most closely relates is “To operate our facilities | |
| in a manner that protects the environment and the health and safety of our employees and the public.” | |
| Page 75 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| equipment did not need to be inside a fully enclosed manufacturing building.a Yet even without a process | |
| requirement to do so, DuPont accepted significant process risk by housing process equipment inside the | |
| enclosed building, making personnel vulnerable to highly toxic chemical exposure and asphyxiation hazards that | |
| DuPont had not effectively identified or controlled. | |
| The manufacturing building was not designed to limit the impact of a toxic chemical leak by containing the leak | |
| and routing it to a destruction device, such as an incinerator or scrubber. The manufacturing building trapped | |
| vapors from highly toxic chemical leaks and concentrated them inside the building, increasing risk to workers | |
| [1, p. 3]. Furthermore, this design did not eliminate the hazards associated with a release to the community or | |
| environment, which an effectively designed containment buildingb could have done. Since the manufacturing | |
| building’s ventilation fans (if functional) routed any toxic chemicals within the manufacturing building to the | |
| roof, discharging them directly to the atmosphere without an additional destruction device, they did not decrease | |
| the potential for a hazardous off-site release [1, p. 33]. In this case, a robust assessment of the process’s location | |
| inside the manufacturing building could have identified the hazards presented. To achieve the ACC’s | |
| aspirational objectives, such as “design[ing] and operat[ing] facilities in a safe, secure and environmentally | |
| sound manner” [43], Responsible Care auditors should look for deficiencies inconsistent with Responsible | |
| Care’s Guiding Principles. | |
| When the ACC developed the original RCMS Technical Specification in 2003, it fully incorporated the entire | |
| aspirational Guiding Principles into the specification. The ACC informed the CSB that adding the Guiding | |
| Principles as an element into its RCMS Technical Specification proved challenging for auditors and those | |
| audited, since the Guiding Principles overlapped with requirements found in other sections of the Technical | |
| Specification or within a company’s existing procedures, creating confusion as to whether separate, additional | |
| actions were necessary to show conformance with this element. In 2008, the ACC replaced the listing of the | |
| Guiding Principles within the RCMS Technical Specification with what it believed was a streamlined set of | |
| auditable requirements intended to reflect the key objectives of the Guiding Principles. The ACC stated that | |
| based on its experience, it believes the change it adopted in 2008 is the most effective way to address the key | |
| objectives of the Responsible Care Guiding Principles. | |
| Another opportunity for Responsible Care to improve its verification program is to evaluate whether the | |
| company’s process safety management system is functioning as the company intends. For example, | |
| Responsible Care requires companies to establish and maintain systems to “protect the environment, conserve | |
| resources, protect worker health and create a safe and secure work environment” and to “establish and maintain | |
| procedures to respond to accidents and emergency situations, and for preventing and/or mitigating the impacts | |
| that may be associated with them” [41, pp. 8-9]. The CSB identified that the DuPont La Porte Responsible Care | |
| a The packaging area of the building on the ground floor (west side) may have had a legitimate need to be inside a building. Dust control | |
| and keeping the packaging equipment and methomyl product dry appeared to be important considerations that may have justified keeping | |
| packaging area equipment housed inside a building [1, p. 32]. | |
| b A containment building is an enclosure around process equipment to contain potential releases to the environment. Companies | |
| typically use containment buildings to reduce off-site risk. DuPont La Porte has stated that the manufacturing building was not a | |
| containment building [1, p. 3]. According to CCPS, “a containment building provides protection outside the building, but can also trap | |
| and concentrate material from small leaks inside the building, increasing the risk to personnel. Provisions must be made to ensure worker | |
| protection for a process located in a containment building, such as monitoring the atmosphere in the containment structures, restricting | |
| access, and requiring proper personal protective equipment when entry into the containment structure becomes necessary” [109, p. 59]. | |
| Page 76 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| audits, however, did not evaluate whether the safety programs implemented to protect employees from | |
| potentially hazardous environments, such as the toxic methyl mercaptan detectors inside the manufacturing | |
| building, met the facility’s stated design purpose. | |
| For example, the 2007 La Porte Responsible Care third-party audit identified the existence of the methyl | |
| mercaptan detection system but did not evaluate whether this system could effectively protect workers by | |
| warning them of potentially toxic environments. It found the detection system to be in conformance simply | |
| because it existed. The CSB, on the other hand, found by evaluating DuPont La Porte’s MOC documentation | |
| and relevant chemical safety information that the alarm limits did not meet the intent of protecting personnel. | |
| Specifically, the methyl mercaptan detectors inside the manufacturing building were set to alarm at 25 parts per | |
| million—a value 50 times greater than the NIOSH recommended exposure ceiling limit and more than double | |
| OSHA’s ceiling limit [50], [51]. During the November 2014 incident, these methyl mercaptan detectors were | |
| alarming; however, the system did not signify an early release of methyl mercaptan (see Section 4.8.3), and the | |
| detectors did not warn workers that they were potentially in a life-threatening toxic environment, because the | |
| alarms were set above OSHA’s ceiling limit and they were not communicated to personnel. Additionally, | |
| Responsible Care audits did not identify the gaps in DuPont’s corporate standard for the Management of Highly | |
| Toxic Materials that allowed toxic gas detection systems to be set above OSHA exposure limits. | |
| Although the ACC does not make prescriptive requirements for its member companies, it should ensure that | |
| safety systems, such as toxic gas detection systems, will protect workers from unsafe conditions by functioning | |
| as the company intended. An effective Responsible Care audit can identify these discrepancies and an auditor | |
| can issue nonconformances or recommendations (opportunities for improvement) at the end of the audit. | |
| The ACC has multiple opportunities to improve Responsible Care, including assessing Responsible Care’s | |
| Guiding Principles in conformance audits, ensuring that safety systems effectively control hazards presented, | |
| and seeking to add value to the safe operation of member companies where possibilities present themselves. | |
| Because Responsible Care is a voluntary program applied by 187 companies in the United States and can readily | |
| adapt to change, it has the potential to be a powerful process safety program.a To fulfill Responsible Care’s | |
| original mission to build public trust by showing that chemical companies are committed to “doing the right | |
| thing” by operating safely and responsibly, and its Guiding Principles “to seek continual improvement in the | |
| integrated Responsible Care Management System to address environmental, health, safety and security | |
| performance,” the ACC should continue to seek opportunities to strengthen its Responsible Care program [15], | |
| [43]. | |
| GUIDANCE TO INDUSTRY | |
| Although this section focused on Responsible Care, these learnings can apply to any safety management system. | |
| Companies can use a variety of programs to manage and evaluate their process safety management systems. | |
| Without an adequate focus on the effectiveness of a process safety management system and its corresponding | |
| a The ACC’s Responsible Care program covers multiple aspects of safety, including process safety, security, product safety, | |
| environmental protection, and occupational safety. | |
| Page 77 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| safety program elements, such as the 20 elements of Risk Based Process Safety [52], implementing the system | |
| will likely not be sufficient to prevent major chemical incidents. Chemical companies should conduct | |
| comprehensive assessments of their process safety management systems and the accompanying implementation | |
| of those systems and safety program elements to understand the overall health of their organizations, including | |
| the effectiveness of accident prevention efforts and the resiliency of operations. | |
| Companies should assess the implementation of these systems and their associated safety program elements | |
| associated with them. Some ways in which a company can ensure effectiveness include these: | |
| 1. Ensuring that all company sites adhere to core process safety management system elements and stay | |
| current with all updates and changes to that system. Because companies can adapt to process safety | |
| learnings quickly, their process safety management systems should ensure that sites are evaluated to | |
| ensure consistency with evolving practices to maximize the effectiveness of these safety improvements. | |
| 2. Investing sufficient time and resources to conduct robust audits. This investment should help ensure | |
| that audits are not rushed and help companies meet the goal of preventing major chemical accidents. | |
| DUPONT’S DEVELOPMENT AND IMPLEMENTATION | |
| OF ITS PROCESS SAFETY MANAGEMENT SYSTEM | |
| DuPont has long been perceived as a safety leadera and has asserted | |
| that its history of process safety extends over two centuries, from its | |
| gunpowder manufacturing through its present-day production of | |
| chemicals [53, p. 114]. Over the course of this time, DuPont’s process safety management system evolved with | |
| the emergence of federal regulations, such as the PSM standard and the RMP rule, as well as the decision to | |
| engage in Responsible Care. | |
| DuPont developed several methods that it uses to manage and integrate its process safety systems, including its | |
| proprietary Safety Perception Surveys and Process Safety Management and Risk Model.b Its corporate process | |
| safety management system and implementation process involves four steps: (1) building a safety culture, (2) | |
| management leadership and commitment, (3) implementing a comprehensive process safety management | |
| program, and (4) operational discipline [54, p. 2]. According to DuPont, the effective implementation of these | |
| steps will result in a robust process safety management system [55, p. 10]. Consequently, DuPont La Porte used | |
| a As recently as 2013, the DuPont Corporation received the Robert W. Campbell Award from the National Safety Council. According to | |
| the National Safety Council, “winners represent organizations that have taken great strides in [environmental health and safety] | |
| excellence. Award winners are acknowledged not only as leaders in the business realm, but also as those that recognize the value of | |
| protecting employees and their environment” [115]. | |
| b According to DuPont, there was a demand from other companies for DuPont to share its learnings and safety practices. In 1968, it | |
| established DuPont Sustainable Solutions, the branch of DuPont (now DowDuPont) that sells the company’s safety systems [113], [114]. | |
| DowDuPont’s Specialty Products division announced it will divest its DuPont Sustainable Solutions to create a new, independent global | |
| operations management consulting firm. The transaction is expected to close in July 2019 pending the completion of all closing | |
| conditions [135]. | |
| Page 78 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| both the Safety Perception Surveys and the Process Safety Management and Risk Model in implementing its | |
| process safety management system. | |
| Despite having robust written process safety management programs (i.e., MOC and PHA), over the course of | |
| five years, DuPont had major process safety incidents—including those at its Belle, West Virginia; Buffalo, | |
| New York; and La Porte, Texas sites, each of which resulted in fatalities. The CSB found that DuPont La | |
| Porte’s ineffective implementation of its integrated process safety management system contributed to the | |
| severity of the highly toxic material release in the manufacturing building at La Porte. | |
| According to DuPont Sustainable Solutions’ “Quick 4-Step Review of Process Safety Management,” | |
| “A strong safety culture, based on a commitment to core values on safety, health, and environmental | |
| issues, and as evidenced by organizational policies, goals, metrics, and day-to-day decision-making, | |
| supports establishing safety systems where safety priorities are recognized, not as conflicting with | |
| other priorities, but rather as inherently necessary for completing any task the right way” [54]. | |
| DuPont’s corporate process safety management standard lists four key steps for the implementation and | |
| sustainability of an effective process safety management program: | |
| 1. Establishing an effective and sustainable unified safety culture (addressed in Section 5.4.1 below) | |
| 2. Providing management leadership and commitment (Section 5.4.2) | |
| 3. Implementing a comprehensive process safety management program, including organizational learning | |
| and continuous improvement to integrate new risk management knowledge, learnings, and practices into | |
| existing site and corporate systems (Section 5.4.2) | |
| 4. Achieving operational excellence through operational discipline (Section 5.4.2) | |
| This section breaks down these steps into two parts: (1) Building a Safety Culture (step one); and (2) Using the | |
| Process Safety Management and Risk Model (steps two through four). | |
| Page 79 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 5.4.1 BUILDING A SAFETY CULTURE | |
| DuPont’s corporate process safety management standard states that process safety culturea “determines the | |
| manner by which PSM is implemented and managed at each site as part of both individual and group values and | |
| behaviors to enable sound decision making and continuous improvement.” Therefore, DuPont links the | |
| effectiveness of process safety management implementation to the process safety culture of a facility. | |
| Moreover, previous CSB investigations also support DuPont’s corporate standard that links effective process | |
| safety management systems with a strong process safety culture.b | |
| According to DuPont, establishing a safety culture is the first step in developing a process safety management | |
| system because a system will be only as effective as its safety culture permits. Additionally, DuPont’s corporate | |
| process safety management standard recommends periodic site evaluations of process safety culture.c DuPont’s | |
| standard further recommends that sites use the results of process safety culture assessments to highlight | |
| strengths and develop potential improvement strategies. | |
| In Essential Practices for Creating, Strengthening, and Sustaining Process Safety Culture, CCPS | |
| states, | |
| “A strong, positive process safety culture enables the facility’s [process safety management system] to | |
| perform at its best. This gives the facility its best chance to prevent catastrophic fires, explosions, toxic | |
| releases, and major environmental damage” [56, p. 2]. | |
| For more than a decade, DuPont developed and honed a safety culture program to reduce its OSHA total | |
| recordable injury rate by assessing and improving occupational (personal) safety, using its Bradley Curve and | |
| Safety Perception Survey tools (Appendix E). These tools, however, focus on only one aspect of safety | |
| culture—personal safety. | |
| DuPont La Porte used the Safety Perception Survey without doing a process safety culture assessment as | |
| recommended in the corporate process safety management standard. Because this survey did not formally | |
| assess process safety culture perceptions, DuPont La Porte never evaluated its process safety culture. Had its | |
| efforts included a focus on perceptions of process safety as well as personal safety in its Safety Perception | |
| a Examples of a process safety culture from DuPont’s corporate standard include maintaining a sense of vulnerability in terms of process | |
| safety management risks to prevent complacency or overconfidence, and transparent, timely, and thorough responses to PSM concerns, | |
| action items, and issues, including leadership measures to prevent a “check-the-box” mentality (i.e., simply accomplishing a task as the | |
| objective rather than ensuring a high degree of focus on risk management and prevention). | |
| b Among other investigations, the CSB investigation of the Williams Geismar Olefins Plant Reboiler Rupture and Fire demonstrates the | |
| CSB’s position that to prevent process incidents, organizations must develop a culture that promotes effective process safety management | |
| systems [71, p. 52]. | |
| c DuPont’s corporate process safety management standard does not specifically address how its sites should perform process safety | |
| culture assessments. DuPont’s standard directs sites to include interactions and discussions with employees, review results of audits, and | |
| observe physical conditions of the site in performing process safety culture assessments. | |
| Page 80 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Survey, or had it performed a separate process safety culture assessment with the intent of improving process | |
| safety culture as recognized in DuPont’s corporate process safety management standard, DuPont La Porte likely | |
| would have been more aware of potential process safety issues and better positioned to prevent or mitigate | |
| future process safety incidents. CCPS recognizes the importance of a strong process safety culture in preventing | |
| major accidents [56, p. 2]. | |
| This section discusses the following: | |
| • The investigations into the catastrophic 2005 BP Texas City explosion that emphasized the way in | |
| which culture is shaped by the level of focus an organization places on process safety (Section 5.4.1.1) | |
| • The lack of formal process safety culture assessments at DuPont La Porte (Section 5.4.1.2) | |
| • Post-incident initiation of formal process safety culture assessments at DuPont legacy sites to address | |
| gaps in process safety culture perceptions in 2017 (Section 5.4.1.3) | |
| Page 81 | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| 5.4.1.1 BP TEXAS CITY INCIDENT | |
| The CSB investigated a 2005 | |
| incident at a BP refinery in Texas | |
| City, Texas,a and due to concerns | |
| about the effectiveness of the safety | |
| management systems at this refinery | |
| and BP’s other North American | |
| refineries, as well as concerns about | |
| BP’s corporate safety culture, the | |
| CSB issued an urgent safety | |
| recommendation to the BP Global | |
| Executive Board of Directors to | |
| commission an independent panel to | |
| conduct a thorough review of BP’s | |
| corporate organizational culture, | |
| safety management systems, and | |
| corporate safety oversight at its U.S. | |
| refineries [57, pp. 3-4]. As a result, | |
| BP formed the BP U.S. Refineries | |
| Independent Safety Review Panel, | |
| commonly referred to as the Baker | |
| Panel,b which conducted an independent organizational assessment of BP’s culture and its corporate-level | |
| oversight of safety management systems at its U.S. refineries [58, pp. viii-ix]. The Baker Panel developed a | |
| process safety culture survey and supervised its administration among BP’s U.S. refinery workforce, including | |
| employees and contractors [58, p. 7]. The survey contained 65 items related to the process safety culture at | |
| participants’ workplaces. | |
| Figure 20. Excerpt from the Baker Panel Report. The Baker Panel found that BP | |
| emphasized personal (worker) safety performance and did not adequately focus on | |
| process safety. Similarly, 12 years after this accident, DuPont La Porte’s safety culture | |
| assessments at its site focused solely on personal safety performance. Source: Baker | |
| Panel Report [58]. | |
| The Baker Panel concluded that BP “mistakenly interpreted improving personal [worker] injury rates as an | |
| indication of acceptable process safety performance” (Figure 20) [58, p. xii]. The panel also noted, “the | |
| presence of an effective personal safety management system does not ensure the presence of an effective process | |
| safety management system … [and] BP’s [worker] injury rates were not predictive of process safety | |
| performance at BP’s five U.S. refineries” [58, p. 21]. | |
| a On March 23, 2005, a series of explosions occurred at the BP Texas City, Texas, refinery during the restarting of a hydrocarbon | |
| isomerization unit—killing 15 workers and injuring 180 others. The explosions occurred when a distillation tower flooded with | |
| hydrocarbons and was overpressurized, causing a geyser-like release from the vent stack [140]. For more information, see the CSB’s BP | |
| America Refinery Explosion investigation. | |
| b Former Secretary of State James Baker III chaired the BP U.S. Refineries Independent Safety Review Panel (the Baker Panel) [58, p. | |
| viii]. | |
| Page 82 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| After the 2005 BP accident and the published findings of both the Baker Panel and the CSB, much of the | |
| chemical process industry began to emphasize the importance of understanding and assessing process safety | |
| culture.a A major process safety incident, such as the one at DuPont La Porte, can reveal weaknesses in the | |
| management of process safety.b | |
| 5.4.1.2 DUPONT LA PORTE DID NOT FORMALLY ASSESS PROCESS SAFETY CULTURE | |
| DuPont La Porte did not use any type of robust, formal process safety culture assessment. Process safety culture | |
| can affect whether a site has a sense of vulnerability in terms of process safety management risks; complacency | |
| or overconfidence; and transparent, timely, and thorough responses to PSM concerns, action items, and issues, | |
| including leadership measures to prevent a “check-the-box” mentality (i.e., simply accomplishing a task as the | |
| objective rather than ensuring a high degree of focus on risk management and prevention). The Safety | |
| Perception Surveys conducted at the DuPont La Porte facility before the November 2014 incident were designed | |
| to lower OSHA total recordable injury rates [59, p. 8]. DuPont did not intend for these surveys to measure or | |
| address the perception of process safety performance. | |
| As part of DuPont La Porte’s 2012 Safety Perception Survey, comments were collected and organized by job | |
| position. Some of these comments, from different levels of the organization, raised safety culture concerns. For | |
| example, one hourly worker (operator) stated, | |
| Some fi[rs]t line [supervisors]c turn the other way if a worker put[s] production over safety.d | |
| A professional employee expressed concerns about PSM initiatives at the site: | |
| Some days it seems like the focus is more about creating documentation and reviewing that | |
| documentation than on targeting those areas that will have the biggest impact on improved PSM | |
| performance. From my perspective, I feel like “real” process safety management has suffered in | |
| some respects and that our processes may actually be less safe than they were before the | |
| initiatives. | |
| Safety concerns were expressed by multiple supervisors in the survey comments: | |
| I hate to say it but not all employees put the same value on safety. That includes [wage roll] | |
| employees and first line supervisors. DuPont employee actions demonstrate to me that safety | |
| rules are suggestions and do not have to be followed. | |
| a In March 2007—two years after the BP Texas City explosion—CCPS published its book Guidelines for Risk Based Process Safety, | |
| which featured “process safety culture” as an element in its new Risk Based Process Safety model [91]. | |
| b Other CSB investigations that found a weak process safety culture contributing to an incident include Williams Geismar Olefins Plant | |
| Reboiler Rupture and Fire [71, p. 52], CSB Macondo Investigation Report, Volume 3 [61, pp. 233-241], and CSB BP Texas City | |
| Investigation Report [60, pp. 142-195]. | |
| c At DuPont La Porte, first-line supervisors include shift supervisors. | |
| d Original comment was written using all capital letters. | |
| Page 83 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| DuPont has always been a strong leader in safety principles for the industry that we work in. The | |
| [La Porte] plant has a strong leadership for safety yet sometimes the message does not always | |
| get across to the employe[es]. Some still feel that production is above safety yet all managers | |
| have stated and demonstrated that production is far down the list when it comes to safety. | |
| I believe our “passion” for safety has slipped over the past 10 years. I believe this has impacted | |
| [our] ability to consistently achieve safety excellence. I interact with safety professionals from | |
| many companies in our area and my opinion is that, as a company, we are no longer the safety | |
| leader we were once thought of as. | |
| Despite concerns about its safety culture expressed by multiple levels of personnel within the organization, | |
| DuPont La Porte did not use these comments to take corrective actions that would institute process safety | |
| culture change at the DuPont La Porte facility. | |
| In 2014, DuPont La Porte hired an organizational consultant to increase production in the Lannate® Unit. Safety | |
| concerns resembling the ones from the 2012 Safety Perception Survey were raised again. According to an | |
| interview of a front-line supervisor in July 2014, four months before the incident, | |
| “…we just are not as good as we think we are.… not in pay, benefits, safety, etc.… We used to | |
| sell the safety program. We spend more time on driving incidents down, to keep the number | |
| down. We just have to make it look good. Don’t need to report every detail. Long slow slide— | |
| may not even notice how far we have fallen. | |
| This supervisor also noted in that interview that DuPont La Porte was at its most vulnerable point because | |
| younger engineers were most impressed by improved production, and “safety first” was not always the practice. | |
| Had DuPont La Porte formally assessed its process safety culture and taken effective corrective actions, cultural | |
| weakness that contributed to significant and long-standing process safety program deficiencies, which the CSB | |
| determined were causal to the November 15, 2014 incident (listed below), may have been identified, | |
| communicated, and addressed. These deficiencies are discussed in further detail in the CSB Interim | |
| Recommendations report on the incident [1] and Section 6: | |
| • Poor hazard analysis practices. Site personnel did not perform a hazard analysis on the | |
| troubleshooting techniques that they used leading up to the incident. Additionally, the DuPont La Porte | |
| site did not adequately analyze hazards associated with the manufacturing building’s ventilation system | |
| in PHAs. A PHA on the ventilation system could have evaluated the ability of the fans to handle toxic | |
| releases and established more robust management systems to protect workers when a fan was broken [1, | |
| pp. 47; 25-26]. | |
| • Poor design of the manufacturing building. DuPont housed the Lannate® process inside a | |
| manufacturing building. The building design increased hazards for the workforce by confining toxic | |
| chemicals indoors. The building’s ventilation design also did not consider chemical toxicity hazards | |
| inside the building [1, p. 33]. | |
| Page 84 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| • Failure to maintain safety-critical equipment. Two “PSM critical”a ventilation fans were not | |
| operational at the time of the incident [1, pp. 33-35]. DuPont recognized that a ventilation fan | |
| breakdown could result in a high-consequence event. Both fans, however, exhibited poor reliability. | |
| One fan had been down since June 2014, five months prior to the incident, due to an electrical problem. | |
| On October 20, 2014, the other fan was making a noise significant enough that DuPont operators turned | |
| it off and wrote an “urgent”b work order to have it repaired [1, p. 20]. Even had the fans worked, they | |
| probably would not have prevented a lethal atmosphere inside the building due to the large amount of | |
| toxic gas released [1, p. 3]. | |
| • Failure to develop written procedures for operator actions. DuPont La Porte did not establish a | |
| formal procedure for draining liquid from the waste gas vent header piping, aside from its line-breaking | |
| policy (Section 6.5). In addition, when the DuPont Technical Team met to discuss how to clear the | |
| plugging in the piping system, they did not develop a written procedure for the techniques used to clear | |
| plugging in equipment, even though the plugging formed where it had never been before [1, p. 25]. | |
| • Lack of hazard recognition. The methyl mercaptan detectors installed in the manufacturing building | |
| were not intended for worker safety—the alarms were set to alarm at 25 parts per million (ppm), which | |
| was above OSHA’s ceiling limitc of 10 ppm. Operators also normalized smelling methyl mercaptan | |
| because of its low odor threshold and perceived lack of negative health impacts at those low | |
| concentrations, even though it is a toxic chemical. Although formally trained,d numerous employees | |
| lacked a working knowledge of methyl mercaptan’s hazards and did not recognize that the chemical | |
| could be both lethal and explosive. As a result, operators often confirmed methyl mercaptan leaks by | |
| purposely smelling for the chemical’s odore without understanding the dangers of this practice. | |
| Furthermore, this method of leak confirmation is a poor, unsafe, and unreliable practice that could have | |
| been replaced by using portable monitors set at appropriate levels [1, pp. 37-39]. | |
| Further, as the CSB concluded in its 2005 BP Texas City investigation, personal safety performance is not an | |
| effective gauge of process safety performance [60]. Similar to its investigation findings from BP Texas City, | |
| the CSB found that DuPont La Porte also focused on personal safety and did not place enough emphasis on its | |
| process safety programs. For example, the Safety Perception Surveys used at the DuPont La Porte facility | |
| evaluated only the perception of personal safety performance and did not identify process safety weaknesses at | |
| the facility. Even though DuPont La Porte was aware of the importance of BP Texas City’s findings, before the | |
| a DuPont assigns the designation of “PSM Critical” to equipment whose failure could result in a high-consequence event [1, p. 34]. | |
| b While the timing required to complete an “urgent” work order is not specifically defined, based on CSB’s review of DuPont records and | |
| interviews conducted with DuPont employees, it has a practical meaning of two to three days. | |
| c The ceiling limit for a substance is the concentration that must never be exceeded under OSHA (29 C.F.R. § 1910.1000(a)(1) (2016)). | |
| d DuPont La Porte included a toxic fume release and methyl mercaptan procedures in its emergency response plan. | |
| e The DuPont La Porte facility had an emergency response procedure for a methyl mercaptan leak. If a leak was detected, personnel were | |
| required to put on an air demand mask and contact a supervisor or the control room to sound a plantwide fume alarm. | |
| Page 85 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| incident it continued to use the Safety Perception Survey without conducting additional formal process safety | |
| culture assessments that could identify process safety weaknesses. | |
| 5.4.1.3 DUPONT’S INITIATION OF PROCESS SAFETY CULTURE ASSESSMENTS | |
| DuPont La Porte’s safety culture assessment program (the Safety Perception Survey) before the November 2014 | |
| incident focused on lowering its OSHA total recordable injury rate. Even as the industry concentrated on | |
| improving process safety following the 2005 BP Texas City incident, and DuPont’s consultant arm developed | |
| process safety questions for the survey, DuPont La Porte lagged and did not incorporate DuPont’s process safety | |
| questions into its Safety Perception Survey.a Furthermore, DuPont La Porte did not formally assess aspects of | |
| its culture beyond the Safety Perception Survey. | |
| In 2017, however, DuPont required each site to assess its process safety culture periodically and added process | |
| safety questions to the Safety Perception Surveys.b This shift in incorporating process safety culture questions | |
| in its Safety Perception Surveys is important because, as explained in Chapter 6.2 of Volume 3 of the CSB’s | |
| Macondo report, the accuracy of a site’s culture assessment may be called into question if all aspects of culture | |
| are not considered as part of the assessment [61, pp. 236-238]. Furthermore, DuPont practice has become more | |
| aligned with its corporate philosophy that a process safety management program is only as effective as its safety | |
| culture. The CSB views the adoption of process safety culture questions in DuPont’s Safety Perception Survey | |
| as a positive development. | |
| GUIDANCE TO INDUSTRY | |
| The CSB has investigated several major incidents caused by weaknesses in process safety culture.c In recent | |
| years, process safety culture has been studied as a component of the broader topic of organizational culture, an | |
| analytical approach that the CSB first articulated in Volume 3 of its Macondo report [61, pp. 233-41]. | |
| Referencing the work of Sonja Haber and Edgar Schein, the CSB explained that organizational culture refers to | |
| characteristics of the overall environment, values, and rules that shape employees’ perceptions and attitudes [61, | |
| pp. 234-36]. This analytical framework extends to a culture for process safety, as these same varied components | |
| work together to determine the importance that an organization places on process safety. A “safety culture” is | |
| thus often accurately described as “the way we do things around here,” or “how the organization behaves when | |
| no one is watching” [62, pp. 9-10]. The chemical process industry then further defined process safety culture as | |
| a DuPont corporate conducted Safety Perception Surveys at all of its manufacturing sites. It chose not to include process safety | |
| perception questions in these surveys. | |
| b DuPont changed some of its process safety culture questions and increased the number of questions from 13 to 14. In 2017, DuPont | |
| updated its corporate process safety management standard to require each site to evaluate the process safety culture survey results and | |
| identify opportunities for improvement. | |
| c Other CSB investigations in which a weak process safety culture was found to contribute to the incident include Williams Geismar | |
| Olefins Plant Reboiler Rupture and Fire [71, p. 52], CSB Macondo Investigation Report, Volume 3 [61, pp. 233-241], and CSB BP Texas | |
| City Investigation Report [60, pp. 142-195]. | |
| Page 86 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| “the common set of values, behaviors, and norms at all levels in a facility or in the wider organization that affect | |
| process safety” [63]. | |
| According to CCPS, a sound or positive safety culture is “the pattern of shared written and unwritten attitudes | |
| and behavioral norms that positively influence how a facility or company collectively supports the successful | |
| execution and improvement of its Process Safety Management System (PSMS) resulting in preventing process | |
| safety incidents” [56, p. 6]. Additionally, a company’s espoused commitments and values, its messages from | |
| management to its workforce and the public, the quality of its written safety management programs, and the | |
| effectiveness of the implementation of those programs in sound operations are all paramount.a | |
| In its book Guidelines for Risk Based Process Safety, CCPS identified six themes of process safety culture: | |
| • Maintain a sense of vulnerability | |
| • Combat normalization of deviance | |
| • Establish an imperative for safety | |
| • Perform valid/timely hazard/risk assessments | |
| • Ensure open and frank communications | |
| • Learn and advance the culture [56, p. 23], [52, pp. 39-66] | |
| CCPS expanded on these process safety culture themes in Guidelines for Risk Based Process Safety and | |
| developed 10 core principles of process safety culture in Essential Practices for Creating, Strengthening, and | |
| Sustaining Process Safety Culture [56, p. 23]. To successfully implement the process safety culture principles | |
| in Figure 21, the later principles should build upon the earlier principles because each principle depends on the | |
| others [56, pp. 24-25]. | |
| a CCPS focuses on the quality of programs and the fidelity to those programs as “Conduct of Operations” and “Operational Discipline,” | |
| respectively [63]. | |
| Page 87 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 21. Excerpt from “Overview of Core Principles of Process Safety Culture,” in CCPS, Essential | |
| Practices for Creating, Strengthening, and Sustaining Process Safety Culture [56, p. 24]. Source: | |
| CCPS. | |
| One tool to evaluate a facility’s process safety culture is the use of anonymous process safety culture | |
| assessments of staff. These assessments have historically been conducted by surveying a site’s employees | |
| through multiple-choice questionnaires. Facilities may also use qualitative assessment practices that go beyond | |
| simple employee questionnaire surveys. Such process safety culture assessments include personnel interviews, | |
| focus group discussions, and detailed document analyses. In qualitative assessments, workers interact with | |
| Page 88 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| auditors, “using their own terms and concepts to express their point of view…. Intensive and in-depth | |
| information can be obtained using the [workers’] own language” [64]. | |
| Guidance published in recent years describes how to conduct process safety culture assessments of chemical | |
| process facilities. In 2011, Contra Costa County in California published a guidance document on conducting | |
| process safety culture assessments, and CCPS released the second edition of its book Guidelines for Auditing | |
| Process Safety Management Systems [65], [66]. Chapter 4 of the CCPS book provides detailed guidance for | |
| auditors evaluating an organization’s process safety culture [66]. Additionally, in 2018, CCPS published | |
| Essential Practices for Creating, Strengthening, and Sustaining Process Safety Culture, which details how to | |
| assess, develop, and sustain a process safety culture in relation to a company’s process safety management | |
| system [56].a In developing a process safety culture assessment, companies should follow the findings of the | |
| Baker Panel and ensure that improved injury rates are not perceived as an indication of acceptable process safety | |
| performance.b | |
| Process safety culture assessments are a tool for understanding a company’s overall commitment to process | |
| safety. Furthermore, companies can use the assessments’ findings to develop action items for continual | |
| improvement efforts. To ensure a strong culture of process safety, companies must address any process safety | |
| culture assessment findings not consistent with the core principles of their process safety culture. Leadership plays an | |
| important role in ensuring that deficiencies in the process safety culture are addressed. As Andrew Hopkins noted in | |
| his article “Why Safety Cultures Don’t Work,” improving an organization’s process safety culture flows from top | |
| management commitment and cascades down to managers and employees [67, pp. 1, 3-4]. Hopkins argued that | |
| companies with strong leadership will best achieve process safety excellence by establishing systems (including the | |
| use of leading indicators) that drive catastrophic accident prevention [48, pp. 1-3]. Such companies are better | |
| equipped to avoid or prevent major process safety incidents because, as Hopkins observed, such companies can better | |
| “identify the obvious precursors to catastrophe and get serious about eliminating them” [67, pp. 1, 3-4]. | |
| a Essential Practices for Creating, Strengthening, and Sustaining Process Safety Culture includes in an appendix that contains a sample | |
| process safety culture assessment protocol [56, pp. 343-380]. | |
| b The Baker Panel found that BP “mistakenly interpreted improving personal injury rates as an indication of acceptable process safety | |
| performance” (see Figure 20). | |
| Page 89 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 5.4.2 USING THE PROCESS SAFETY MANAGEMENT AND RISK MODEL | |
| Figure 22. DuPont’s Process Safety Management and Risk Model [54, p. 2]. Source: DuPont | |
| Sustainable Solutions. | |
| DuPont created the Process Safety Management and Risk Model (also called the PSM Wheel) to represent | |
| visually how the last three steps (management leadership and commitment, implementing a comprehensive | |
| process safety management program, and operational discipline) should interact with each other, using a wheel | |
| to show that DuPont’s process safety management system integrates management leadership and commitment | |
| with operational discipline (Figure 22) [54, p. 2]. | |
| The second step in implementing DuPont’s process safety management system, management leadership and | |
| commitment, is at the center of the PSM Wheel. According to DuPont, it placed this core value at the center | |
| because it affects all aspects of a process safety management system, from forming and fostering a safety culture | |
| to implementing policies and providing resources for safety-related activities [54, p. 2]. Additionally, “the | |
| actions of all levels of management must support and reinforce strong PSM programs and accountability” [54, p. | |
| Page 90 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 2]. DuPont believes that visible top management involvement (i.e., “felt leadership”a) in safety systems, | |
| processes, and programs is necessary for their sustainability. In addition, it notes that felt leadership, | |
| commitment, and role modeling greatly influence employees’ interest in, understanding of, and value for safety. | |
| The third step in establishing DuPont’s process safety management system, Implementing a Comprehensive | |
| PSM Program, is in the spokes of the wheel. Each spoke represents one of 14 aspects of DuPont’s corporate | |
| process safety management program.b These spokes are divided into three groups: | |
| a. Facilities to handle and manufacture hazardous materials: | |
| 1. Management of “subtle changes” | |
| 2. Mechanical integrity | |
| 3. | |
| 4. Quality assurance | |
| Pre-startup safety reviews | |
| b. Technology of the process: | |
| 1. Management of technology change | |
| 2. Operating procedures and safe practices | |
| 3. | |
| 4. | |
| Process hazards analysis | |
| Process safety information | |
| c. Personnel who operate, maintain, and support the process: | |
| 1. Auditing | |
| 2. | |
| Emergency planning and response | |
| 3. Management of personnel change | |
| 4. | |
| 5. | |
| 6. | |
| Incident investigation | |
| Contractors | |
| Training and performance [68, p. 2] | |
| a DuPont defines “felt leadership” as a respect through action for the well-being of people. It is a building block in constructing trust and | |
| real-world relationships among employees, customers, shareholders, and communities [116]. CCPS also defined felt leadership in its | |
| CCPS Vision 20/20: “Felt leadership means that the executives and other leaders personally involve themselves in process safety | |
| activities. Employees know the executives care about process safety because of what they see and feel executives doing, not just by | |
| [what] they hear them saying. Felt leadership is leading by passionate example” [56, p. 31]. | |
| b Note that DuPont’s PSM Wheel does not include trade secrets and employee participation, which are elements of OSHA’s PSM | |
| standard. | |
| Page 91 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| The final step, Operational | |
| Discipline, is the rim of the | |
| PSM Wheel. DuPont defines | |
| operational discipline as “the | |
| deeply rooted dedication and | |
| commitment by every member | |
| of an organization to carry out | |
| each task, the right way, each | |
| time” [54, p. 2]. According to | |
| DuPont, operational discipline | |
| translates a documented | |
| process safety management | |
| system into tangible results | |
| (see Figure 23). Additionally, | |
| DuPont believes that it reflects | |
| the strength of an | |
| organization’s safety culture in | |
| making safety, health, and | |
| environmental (also known as | |
| SHE) systems effective and in | |
| providing observable results for preventing injuries and incidents [69, p. 58]. | |
| Figure 23. Excerpt from DuPont Presentation Titled “Developing a Robust PSM Framework | |
| at DuPont.” This slide illustrates DuPont’s perception of the characteristics of an effective | |
| operational discipline program that translates to operational excellence [118, p. 11]. | |
| Source: DuPont Sustainable Solutions. | |
| DuPont management uses the Process Safety Management and Risk Model at its sites, including DuPont La | |
| Porte, and sells its process safety management system to other companies. | |
| DUPONT’S PROCESS SAFETY MANAGEMENT SYSTEM CONCLUSIONS | |
| DuPont integrated the PSM standard, RMP rule, and Responsible Care into its corporate process safety | |
| management system. In addition to other requirements, these frameworks obligate companies to establish a | |
| comprehensive corporate process safety management system. As shown in this section, companies need to | |
| ensure that there is an adequate focus on the effectiveness of a corporate process safety management system and | |
| its corresponding safety program elements. Without sufficient focus, implementing a corporate process safety | |
| management system will likely not be enough to prevent major chemical incidents. At the DuPont La Porte | |
| facility, an inadequate focus on the effective implementation of the corporate process safety management system | |
| resulted in process safety management deficiencies that led to the November 2014 incident. The following | |
| section discusses some of the deficiencies in DuPont La Porte’s process safety management system. | |
| 6 PROCESS SAFETY MANAGEMENT DEFICIENCIES | |
| As part of its investigation, the CSB evaluated DuPont La Porte’s implementation of its process safety | |
| management system at the site (see Appendix A: Causal Analysis). The CSB found that DuPont La Porte had | |
| multiple deficiencies in its process safety management program elements that contributed to the incident, | |
| Page 92 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| including process hazard analysis (PHA), auditing, management of change (MOC), operating procedures, and | |
| safe work practices.a This section details some of these process safety management system deficiencies at the | |
| DuPont La Porte facility. Section 4 discusses the deficiencies in DuPont La Porte’s emergency response | |
| program.b Additionally, the CSB found that DuPont La Porte’s incentive compensation program did not | |
| conform to the OSHA guidance that existed at the time of the incident. | |
| Even though DuPont and DuPont La Porte had extensive written policies, these policies did not translate into | |
| effective implementation of or adequate focus on the effectiveness of its process safety management system at | |
| the DuPont La Porte site. The CSB determined that a company’s development of its own process safety | |
| management system is critical to prevent major accidents. Companies should ensure that the safety program | |
| elements within their process safety management system are effective, fully implemented, and functioning as | |
| intended. | |
| PROCESS HAZARD ANALYSIS EVALUATION | |
| DuPont’s internal PHA training | |
| documents state, “historically, the | |
| most significant failure in PHAs, | |
| identified through the investigation | |
| of incidents in which a breakdown | |
| of the PHA element was found to be | |
| a key factor, is the failure to identify | |
| the specific sequence of events that | |
| led to the accident (e.g., either failed | |
| to ask the right What If question or | |
| failed to completely develop the | |
| hazardous event scenario).” | |
| Without identifying the full extent of | |
| a potential hazardous event scenario, | |
| PHA teams are not likely to develop | |
| adequate safeguards to mitigate a | |
| hazard. | |
| Figure 24. Where PHA is Located on DuPont’s Process Safety Management and Risk | |
| Model (PSM Wheel) [54, p. 2]. Source: DuPont, with annotations by CSB. | |
| One of the causes of the highly toxic | |
| methyl mercaptan release was a lack | |
| of safeguards to prevent the methyl | |
| mercaptan hydrate from solidifying in the feed piping. In one of the hundred-plus what-if scenarios considered | |
| a Section 4 covers process safety management deficiencies related to emergency response. | |
| b The PSM standard requires companies to have either an emergency action plan or an emergency response plan. Although the standard | |
| does not detail requirements for an emergency response program, it incorporates by reference regulations that dictate requirements for | |
| emergency action plans and emergency response plans (29 C.F.R. § 1910.119(n)). | |
| Page 93 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| in the 2011 PHA, the DuPont La Porte PHA team acknowledged the potential for methyl mercaptan hydrate to | |
| solidify in the feed piping. The PHA team identified a scenario in which water back-flowing into the methyl | |
| mercaptan feed system could cause the formation of methyl mercaptan hydrate (Figure 25). The consequence of | |
| this scenario was the hydrate plugging the methyl mercaptan feed piping. The team identified that heating | |
| would dissociate the hydrate and unplug the system, but it did not fully develop (evaluate) the potential hazards | |
| resulting from the plugging, including hazards caused by dissociating the methyl mercaptan hydrate. The PHA | |
| team assessed the plugging as presenting an unlikely, low-severity hazard, assigning it the lowest possible risk | |
| ranking.a As a result of this risk ranking, no additional safeguards or further protective actions were required to | |
| address this scenario. | |
| Figure 25. CSB’s Reproduction of the Hazard Evaluation Worksheet from the 2011 PHA. It that identified the methyl mercaptan | |
| hydrate formation as a hazard. Source: DuPont, with modifications by CSB for readability. | |
| As discussed earlier, the PHA team did not comprehensively evaluate this scenario. For example, it did not | |
| ensure that a procedure or safeguard existed to heat the piping safely. Figure 25 shows that the PHA team | |
| identified one existing safeguard for the hydrate plugging scenario—the company’s standard for backflow | |
| prevention. This safeguard, however, was inadequate because this standard addresses backflow from a process | |
| (MeSNa cooler) to a service or a utility (water supply). Therefore, applying this standard would not have | |
| prevented or offered protection from water flowing into the methyl mercaptan feed piping. | |
| Hence, the PHA team underestimated the risk, noting, “Ultimately by heating the line externally it will vaporize | |
| and return to [methyl mercaptan] and water vapor.” Even though the PHA team identified heating as a means to | |
| dissociate the methyl mercaptan hydrate, DuPont La Porte did not identify the need to develop a formal | |
| procedure or engineered system to safely heat the line and address the hazard the team had identified. As a | |
| result, on November 14, 2014, the DuPont Technical Team had to develop a troubleshooting plan to address the | |
| a DuPont La Porte used a risk matrix that evaluated risk by assessing consequence and frequency. The DuPont La Porte PHA team | |
| assigned the lowest-level possible consequence (C-1) and frequency (F-1) to the methyl mercaptan hydrate. This assignation resulted in | |
| the methyl mercaptan hydrate having the lowest possible risk (IV), which meant the PHA team did not have to mitigate the hazard. A C- | |
| 1 consequence equates to no significant injury or health impact on-site or off-site and no significant environmental impact. As long as | |
| the consequence was classified as C-1, the frequency of the event would not have mattered; the PHA still would not have had to mitigate | |
| the risk. | |
| Page 94 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| hydrate plugging (Section 6.3). This plan was developed without performing any hazard analysis, developing a | |
| written procedure, training personnel, or providing sufficient technical resources for the night shift. | |
| Although DuPont La Porte’s 2011 PHA of the process identified methyl mercaptan hydrate formation,a the PHA | |
| team did not recognize the need to address the potential methyl mercaptan hydrate formation risk by providing | |
| additional safeguards, such as heat tracing,b or to develop a written procedure to safely dissociate the hydrate | |
| (see Section 6.3). When critically evaluating any PHA scenario following a major accident, it is not uncommon | |
| to identify how a PHA team could have recommended additional or more effective safeguards. The difficulty | |
| PHA teams face is how to ensure that what is perceived as “good enough” when evaluating a potential hazard | |
| scenario will ultimately provide sufficient protection (effective risk mitigation). Had DuPont La Porte installed | |
| effective safeguards, such as heat tracing, to maintain the piping contents above 52°F, the facility could have | |
| avoided the abnormal situation that led to the deaths of four workers. Following the November 15, 2014 | |
| incident, DuPont completed two new baseline PHAs using a more robust PHA methodology for the Insecticide | |
| Business Unit. Despite performing PHAs for more than 30 years, DuPont La Porte employees told CSB | |
| investigators that the improved approach for conducting PHAs was resulting in hundreds of action items, never | |
| previously identified, to control hazards. Difficulties in performing PHAs highlight the importance of having a | |
| strong process safety culture foundation to drive site personnel to effectively respond to real-time events with | |
| robust process safety management system programs, including MOCs or safe work practices. | |
| GUIDANCE TO INDUSTRY | |
| PHAs can be subjective and can result in underestimating the risk of potential hazardous event scenarios. | |
| Because in PHAs the assignment of event frequencies and consequence severities can make a significant | |
| difference in safeguard requirements, companies need to ensure that PHA teams have a robust process and | |
| adequate resources in place to fully develop hazard scenarios and assign appropriate initiating event frequencies | |
| and consequence severities to them. Additionally, PHA teams need to ensure that the safeguards applied to the | |
| hazard scenarios are relevant and effective in controlling the hazards. | |
| a The methyl mercaptan hydrate hazard was also identified in DuPont La Porte’s technical standard (see Section 6.3). | |
| b “Heat tracing is used to prevent heat loss from liquids inside process piping in situations where low fluid temperatures could lead to | |
| problems such as an unacceptable increase in viscosity, hydrate formation, congealing or solidification, the separation of components, or | |
| when water in the line could form corrosive materials” [131, p. 157]. Heat tracing can be either steam or electrical heat applied to the | |
| surface of a pipe and covered by insulation [131, p. 158]. | |
| Page 95 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| IMPLEMENTATION OF CORRECTIVE ACTIONS | |
| According to OSHA’s Process | |
| Safety Management Guidelines for | |
| Compliance, taking corrective | |
| actions is one of the most | |
| important parts of an audit and | |
| includes identifying deficiencies, | |
| planning, following up, and | |
| documenting needed corrections | |
| [19]. Audits, PHAs, incident | |
| investigations, and emergency | |
| response drills are among the | |
| various PSM program elements | |
| that can generate corrective action | |
| items. At times, the corrective | |
| action program at DuPont La Porte | |
| did not appropriately correct gaps | |
| identified by site PSM audits | |
| (Figure 26). | |
| Figure 26. Where Auditing is Located on DuPont’s PSM Wheel [54, p. 2]. Source: | |
| DuPont, with annotations by CSB. | |
| One of DuPont’s process safety metrics was tracking the completion of corrective action items. However, this | |
| metric addressed only one aspect of the site’s corrective action program—time needed to close the corrective | |
| action. Time to close corrective actions can indicate the priority management gives to completion of corrective | |
| action items. DuPont La Porte’s focus on time to complete, however, sometimes resulted in closing action items | |
| after developing a plan to correct a deficiency rather than actually correcting it. In Guidelines for Risk Based | |
| Process Safety CCPS states, | |
| A safety management system can be seriously deficient, yet appear satisfactory by superficial | |
| measures—the paperwork appears to be in place and no serious incidents have been recorded. | |
| Complacency replaces a sense of vulnerability, and the execution of program tasks becomes | |
| perfunctory [52, p. 639]. | |
| Similarly, based on its corrective actions metric, the DuPont La Porte facility did not appear to have a large | |
| number of process safety management deficiencies—while the CSB’s review of corrective actions at La Porte | |
| Page 96 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| revealed that some corrective actions were closed without addressing the issue identified by the underlying | |
| recommendation.a As such, closing out some corrective actions became perfunctory paperwork closures. | |
| For example, in 2009, a second-party PSM audit found that the DuPont La Porte site lacked documentation | |
| showing the manufacturing building’s ventilation systemb was ever tested to ensure it could effectively | |
| distribute fresh air within the building. Based on this finding, the audit recommended that the site set up a | |
| program to test the manufacturing building’s ventilation system periodically. | |
| The two sides of the manufacturing building were separately ventilated by dilution air exhaust fans located on | |
| the roof of the building. The dilution air ventilation system design used roof-mounted fans to pull fresh dilution | |
| air into the manufacturing building. Fans drew fresh air into each floor on each side of the building, at floor | |
| level, through a mechanical louver system.c When the system operated properly, air would flow from the fresh | |
| air louvers, across the process equipment, and up into return ducts on the ceiling along the internal wall to sweep | |
| away any flammable or toxic gases.d Exhaust air from each side of each floor moved inside the ceiling-mounted | |
| duct toward the north end of the building (Figure 27), where it was collected in a vertical duct header that | |
| directed the exhaust air from all of the floors on each side up to the respective (wet or dry end) dilution air | |
| exhaust fan on the roof. Exhaust air from the fans discharged directly to atmosphere. The ventilation system | |
| was not equipped with any kind of environmental destruction system, such as a scrubber or incinerator, to | |
| remove contaminants. | |
| a The CSB found multiple incidents at the DuPont La Porte facility in which corrective actions were closed by sending emails to relevant | |
| parties without following up to ensure effective implementation (e.g., coordination with other companies located on-site, deviation from a | |
| highly toxic material requirement, etc.). | |
| b The stated design objective for the ventilation system is as follows: “The main objectives of industrial ventilation for the LANNATE®/ | |
| [agricultural products intermediates] manufacturing building are to: a. control contaminants to acceptable work place exposure levels, | |
| e.g., comply with OSHA regulation or Corporate AELs (acceptable exposure limits), and b. prevent fires and explosions.” The actual | |
| design calculations, however, do not take toxicity into consideration. In addition, DuPont has not established an AEL for methyl | |
| mercaptan [1, p. 33]. | |
| c The louver is a set of angled slats or flat strips fixed or hung at regular intervals in a shutter to allow air to pass through [1, p. 13]. | |
| d DuPont La Porte records indicate that the manufacturing building ventilation system design code is National Fire Protection | |
| Association (NFPA) 497, Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous | |
| (Classified) Locations for Electrical Installations in Chemical Process Areas. NFPA 497 defines adequate ventilation as that sufficient | |
| to ensure that the concentration of flammable gases does not exceed 25 percent of the lower flammability limit (also called the lower | |
| explosive limit (LEL)). DuPont’s methyl mercaptan safety data sheet indicates that the LEL for methyl mercaptan is 3.9 percent [1, p. | |
| 13]. | |
| Page 97 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 27. Simplified Graphical Representation of a Typical Floor of the Manufacturing Building. It shows how fresh | |
| air was pulled in from the outside walls, swept across the floor, and entered the exhaust return air ducts on each | |
| side. Source: CSB. | |
| To close the action item generated—to ensure the ventilation system was routinely tested—DuPont La Porte | |
| personnel created a program within their computerized maintenance system that periodically generated a work | |
| order to conduct dilution air flow testing [1, p. 34]. DuPont La Porte closed the corrective action in March 2010 | |
| after creating this program. But the CSB found serious deficiencies in the implementation of this program: | |
| • DuPont La Porte personnel were supposed to schedule the first ventilation system test in November | |
| 2010. This test was delayed and did not occur until two years later, in 2012 [1, p. 34]. This delay | |
| occurred in part because personnel closed the corrective action without assigning a specific individual | |
| to ensure completion of the ventilation testing. | |
| • On the dry end side of the building, DuPont La Porte personnel measured dilution air flow without | |
| analyzing the data or establishing acceptable air flow criteria. Additionally, they never measured the | |
| air flow on the wet end side where the November 15, 2014 release occurred. Therefore, DuPont La | |
| Porte never verified whether the manufacturing building’s ventilation system could effectively remove | |
| flammable or toxic chemical leaks. | |
| Had the corrective action met the intent of the PSM audit recommendation, the need for additional safeguards in | |
| the manufacturing building (e.g., a better ventilation system, increased chemical detectors, respiratory | |
| protection) should have been evaluated. Effective ventilation system testing and analysis should have identified | |
| and corrected poorly ventilated areas to reduce worker hazards posed by potential flammable or toxic gas leaks | |
| in the manufacturing building.a | |
| a For more information on the ventilation systems, see the Interim Recommendations report (CSB DuPont La Porte Interim | |
| Recommendations [1, pp. 12-16]). | |
| Page 98 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| At the time of the November 2014 incident, neither the wet end nor the dry end fans were functioning. Had the | |
| deficiencies in the DuPont La Porte ventilation system been recognized, access to the manufacturing building | |
| should have been restricteda and personnel could have been required to wear SCBAs inside it. Adequate | |
| safeguards could have protected workers when the fatal toxic release occurred. | |
| Closing corrective action items with only a limited plan to address an audit finding is a poor practice—it can | |
| result in the action item’s being implemented ineffectively or not at all. At DuPont La Porte, even though | |
| personnel closed as complete the ventilation system testing action item, they never completed the testing to | |
| ensure the effectiveness of the ventilation system. | |
| GUIDANCE TO INDUSTRY | |
| Companies should ensure that their corrective actions meet the intent of their recommendations. One way to | |
| make the intention of the recommendation the focus of any follow-up activity is to evaluate the substance of the | |
| corrective action in addition to the time it takes to complete the action. | |
| PROCESS SAFETY PRACTICES DURING TROUBLESHOOTING OPERATIONS | |
| A robust strategy for troubleshooting | |
| is important because if hazards are not | |
| identified before starting an activity, | |
| workers could be unprepared for | |
| dealing with them, like what happened | |
| during the November 2014 incident. | |
| Troubleshooting implicates multiple | |
| PSM elements, including management | |
| of change, operating procedures, and | |
| safe work practices (Figure 28). | |
| Although DuPont La Porte had written | |
| policies and procedures for MOCs, | |
| operating procedures, and safe work | |
| practices, it did not have a strong | |
| process safety approach for dealing | |
| with troubleshooting operations. | |
| Figure 28. Where troubleshooting Could Fall on DuPont’s PSM Wheel [54, p. | |
| 2]. Source: DuPont, with annotations by CSB. | |
| During the morning of November 14, 2014, Lannate® Unit engineers and managers (Technical Team) met as a | |
| group with the day shift supervisor to discuss the plugging problem in the methyl mercaptan piping and to | |
| develop a troubleshooting plan for clearing the piping and restarting both the Lannate® and agricultural products | |
| a The CSB Interim Recommendations report discusses how DuPont La Porte’s emergency procedures called for restricting access to the | |
| manufacturing building if a ventilation fan, such as the wet end or dry end fans, is out of service. However, the actual practice for | |
| manufacturing building access was no different with a fan out of service than if all the fans were operating [1, p. 35]. | |
| Page 99 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| intermediates processes [1, p. 23]. In this meeting, the Technical Team identified the likely scenario that water | |
| had entered the methyl mercaptan system, developing a solid hydrate. DuPont’s methyl mercaptan technical | |
| standard shows the potential formation of a hydrate at low temperatures. The technical standard states that | |
| methyl mercaptan “will form a hydrate with water, which is a solid below [40°F [degrees Fahrenheit]] per | |
| information provided by a [methyl mercaptan] supplier” [1, p. 23]. | |
| Prior to implementing the troubleshooting plan developed by the Technical Team, however, site personnel did | |
| not develop written procedures, conduct any type of hazard analysis for abnormal conditions, conduct a job | |
| safety analysis, perform an MOC process, or conduct any other type of hazard analysis [1, p. 25]. Several | |
| methods can identify potential hazards and prevent or mitigate potential incidents caused by troubleshooting, | |
| including development and use of MOC processes, operating procedures, or safe work practices. A robust | |
| troubleshooting approach can include the following methods: | |
| • An MOC approach, which should identify and address possible hazards [52, pp. 423-426, 255-256] | |
| • An operating procedure approach, which should incorporate safeguards while methodically working | |
| through troubleshooting steps [52, pp. 255-256] | |
| • A safe work practices approach, which should address unexpected process upsets by using work permits | |
| (i.e., line-breaking permits) that can address specific troubleshooting hazards [70, p. 393], [52, pp. 285- | |
| 298] | |
| A combination of these PSM approaches may be prudent depending on the complexity and urgency of the | |
| problem. One or more of the noted PSM approaches could have identified the pathway the liquid methyl | |
| mercaptan took into the manufacturing building before personnel put hot water on the insulated piping, leading | |
| to the November 2014 incident. | |
| GUIDANCE TO INDUSTRY | |
| Companies should develop an action plan to manage troubleshooting operations. There are multiple approaches | |
| a company can take, including addressing troubleshooting hazards in PHAs, operating procedures, MOCs, or | |
| work permits. | |
| Page 100 | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| MOC PRACTICES | |
| According to OSHA, “contemplated | |
| changes to a process must be | |
| thoroughly evaluated to fully assess | |
| their impact on employee safety and | |
| health and to determine needed | |
| changes to operating procedures” | |
| [18]. Therefore, to prevent safety | |
| incidents and ensure worker safety, | |
| companies must ensure that the | |
| following considerations are | |
| addressed in their MOC process | |
| prior to the implementation of any | |
| change: | |
| • The technical basis for the | |
| proposed change | |
| Figure 29. Where MOC is Located on DuPont’s PSM Wheel [54, p. 2]. Source: | |
| DuPont, with annotations by CSB. | |
| • | |
| Impact of the change on employee safety and health | |
| • Modifications to operating procedures | |
| • Necessary time period for the change | |
| • Authorization requirements for the proposed change [18]a | |
| As explained in the CSB’s Williams Geismar Olefin Plant Case Study, robust management of change practices | |
| are needed to ensure that personnel review hazards for the entire process affected by the change [71, p. 23]. | |
| Within DuPont, MOC policies are defined in standards at the corporate level and adopted according to each | |
| site’s procedures. The DuPont corporate standard defines three types of MOCs: technology, subtle changes, and | |
| personnel (Figure 29). An MOC for technology is defined as “any change in the technology of the process.”b A | |
| “subtle change” is defined as “any change within the documented technology that is not a replacement in kind.”c, | |
| d MOCs are intended to be completed prior to any implementation of these types of change. DuPont La Porte | |
| adopted DuPont’s corporate MOC policies into its own site policies and procedures. The CSB found, however, | |
| a 29 C.F.R. § 1910.119 (l)(2). | |
| b According to DuPont, management of change of “subtle changes” includes rerouting a piping system during field modifications or | |
| replacement and installation of an automatic valve to replace a manual valve with the same function. | |
| c According to DuPont, management of change technology includes managing changes in the design basis for existing equipment, | |
| changes in process materials or operating parameters, and process control changes. | |
| d In its Belle investigation, the CSB recommended that DuPont “[r]eevaluate and clarify the DuPont corporate MOC policies to ensure | |
| that staff can properly identify and use the distinctions between subtle and full changes and train appropriate personnel how to properly | |
| apply the distinctions on any changes in the policy.” [144, p. 110]. The CSB closed the recommendation in April 2013 [147]. | |
| Page 101 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| that DuPont La Porte personnel did not use MOCs for changes to equipment or procedures that contributed to | |
| the incident. | |
| 6.4.1 NO MOC FOR HEATING PIPING OR FOR NEW PIPING ALIGNMENT | |
| To clear the plugging, the Technical Team asked operators to put hot water on the outside of the methyl | |
| mercaptan feed piping, under the insulation, to warm the piping and its contents to dissociate the hydrate back to | |
| liquid methyl mercaptan and water (Figure 30) [1, p. 23]. | |
| Figure 30. Hot Water Hose Positioned on the Liquid Methyl Mercaptan Feed Piping. Hot water flowed | |
| between the piping and the insulation to heat the piping and dissociate the solid hydrate that had formed | |
| after water inadvertently entered the methyl mercaptan storage tank. Source: CSB. | |
| At low temperatures (≤ 52°F), water and methyl mercaptan form a solid, ice-like material called methyl | |
| mercaptan clathrate hydrate [72]. Temperatures in the Houston area for the 24 hours preceding the incident | |
| averaged approximately 40°F and had been consistently below 55°F since Tuesday, November 11, 2014. | |
| Although years earlier, DuPont’s methyl mercaptan technical standard and a PHA identified the potential for | |
| methyl mercaptan hydrate formation, DuPont did not have safeguards, such as heat tracing, or develop a | |
| procedure to dissociate the hydrate safely [1, p. 22]. | |
| The Technical Team realized that when methyl mercaptan was heated it would expand and need a safe place to | |
| vent to avoid overpressure in the feed piping. To address this concern, DuPont operations personnel opened | |
| three valves between the methyl mercaptan feed line and the waste gas vent header—piping intended to remove | |
| excess or unwanted vapor from the process and route it to the NRS incinerator for thermal destruction. DuPont | |
| La Porte personnel used pressure gauges at those three valves (Figure 31) to determine the location of the | |
| Page 102 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| blockage and their progress in clearing it. At the time of the incident, one of these three valves between the | |
| methyl mercaptan feed system and the waste gas vent header was fully open, and a second valve was slightly | |
| open [1, p. 25]. | |
| Figure 31. Excerpt from CSB Animation. It depicts the three locations where valves connected the methyl mercaptan feed piping | |
| (blue) to the waste gas vent header piping (orange). Workers used the pressure gauges shown at these locations to monitor the | |
| progress of clearing the hydrate blockage inside the methyl mercaptan feed piping. Source: CSB. | |
| Operations personnel began implementing the plan that the Technical Team had developed by applying hot | |
| water under the insulation, on the outside of the liquid methyl mercaptan piping. DuPont La Porte operators | |
| started this process at the methyl mercaptan storage tank and the associated methyl mercaptan feed pump piping | |
| segments, and then worked their way down the methyl mercaptan feed piping toward the reaction system. | |
| Workers used pressure gauges at each of the three block valves between the liquid methyl mercaptan feed piping | |
| and the vapor waste gas vent header piping system to determine the success and progress of the work [1, p. 26]. | |
| Page 103 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 32. Excerpt from CSB Animation. It depicts the piping arrangement that allowed liquid methyl mercaptan from the | |
| feed line (blue) to flow into the waste gas vent header piping (orange). Source: CSB. | |
| Using these valves in this way followed the plan developed by the Technical Team. This alignment, however, | |
| created a direct path between the liquid methyl mercaptan system and the waste gas vent header (vapor system), | |
| as shown in Figure 32, which was not DuPont’s design intent [1, p. 26]. Additionally, applying hot water to the | |
| outside of the methyl mercaptan liquid piping system exceeded the heat input design for the thermal expansion | |
| relief valve on this system [1, p. 26]. But DuPont La Porte personnel did not perform an MOC before | |
| instructing operations personnel to use the hot water to heat the piping, or before creating the piping alignment. | |
| DuPont corporate standards, as well as the EPA’s Risk Management Plan (RMP) rule and OSHA’s PSM | |
| regulations, require an MOC for these types of process changes [1, p. 25]. Performing an effective MOC before | |
| heating the piping with the hot water hose, and before creating the unusual piping alignment, could have | |
| identified and controlled the hazards that led to the incident. | |
| An MOC should have also triggered the creation of a written troubleshooting procedure. On the day of the | |
| incident, the Technical Team did not provide a written procedure to guide operations or to track the progress | |
| toward clearing the plugged methyl mercaptan feed piping. A written procedure should communicate the | |
| planned approach to multiple shifts and help avoid confusion. Additionally, it should alert personnel to potential | |
| hazards, such as the valve alignment that created the pathway for liquid methyl mercaptan to flow into the | |
| manufacturing building. | |
| Page 104 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 6.4.2 NO MOC FOR NEW PIPING ALIGNMENT TO NITROGEN RELIEF VALVES | |
| During the troubleshooting operations, the nearly identical nitrogen relief systems located at two railcar loading | |
| and unloading stations were lined up to the discharge of the methyl mercaptan pumps (Figure 33). The nitrogen | |
| relief valves, however, were not designed for this new piping alignment. DuPont La Porte PHAs and relief | |
| valve design documents did not consider the possibility of lining up the methyl mercaptan storage tank pumps to | |
| these relief valves—as they were at the time of the incident. As a result, liquid methyl mercaptan discharged | |
| from a system designed for nitrogen vapor because the methyl mercaptan pump discharge pressure (90 psig)a | |
| was higher than the set pressure (80 psig) of these nitrogen relief valves. Pressurized methyl mercaptan from | |
| the pump caused the relief valves to open and release the highly toxic and highly flammable methyl mercaptan | |
| to the atmosphere [1, p. 46]. No one recognized this serious hazard because DuPont La Porte personnel did not | |
| perform an MOC when it changed the piping alignment during troubleshooting operations. An effective MOC | |
| should look at the design basis for equipment to determine whether the proposed use is compatible with its | |
| design. | |
| a The abbreviation psig stands for pounds per square inch gauge (pressure). | |
| Page 105 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 33. Nitrogen Relief Valves at One of the Two Methyl Mercaptan Railcar Unloading Stations. DuPont PHAs and | |
| relief valve design documents never considered the possibility of lining up the methyl mercaptan storage tank pumps | |
| to these relief valves—as they were at the time of the incident. As a result, liquid methyl mercaptan was discharged | |
| from a system designed for nitrogen vapor. Source: CSB. | |
| 6.4.3 NO MOC OR PROCEDURE FOR VENT HEADER DRAINING OPERATION | |
| In 2011, DuPont La Porte invested about $20 million in a project to increase production rates and reduce | |
| environmental emissions for the Insecticide Business Unit.a The key piece of equipment installed for this | |
| project was the nitrogen oxides (NOx) reduced scrubbed incinerator (NRS) shown in Figure 34.b | |
| a Lannate® was a sold-out product, and DuPont routinely looked for opportunities to increase capacity [1, p. 17]. | |
| b The NOx (nitrogen oxides) reduced scrubbed (NRS) incinerator system was a vertical thermal oxidizer system for the destruction of | |
| organics, halogenated organics, and nitrogen-containing wastes with removal of acid gas from discharge [1, p. 18]. | |
| Page 106 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 34. NRS Incinerator. NRS was installed in 2011 to reduce emissions and allow | |
| increased production at the DuPont La Porte facility. Source: CSB. | |
| The NRS incinerator destroyed process waste gas streams that vented from equipment throughout the process. | |
| One of these waste gas streams contained methyl mercaptan vapor collected in a process vent system, referred to | |
| as the waste gas vent header piping. This header originated from various Lannate® and agricultural products | |
| intermediates process vessels, from methyl mercaptan railcar unloading facilities, and from the methyl | |
| mercaptan storage tank. The waste gas vent header piping provided the path for these waste gas streams to be | |
| directed to the NRS incinerator for thermal destruction (combustion) [1, p. 18]. | |
| Following the 2011 installation of the NRS incinerator, DuPont experienced frequent high-pressure events in | |
| equipment connected to the waste gas vent header piping.a DuPont decided one significant cause of these high- | |
| a The high pressure in the waste gas vent header piping restricted vent sources flowing into the header, causing high-pressure events in | |
| process equipment. If left unaddressed, these high-pressure events could result in relief valves’ opening and discharging hazardous | |
| chemicals to the atmosphere [1, p. 18]. | |
| Page 107 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| pressure events was liquid accumulation in the vapor waste gas vent header piping.a DuPont La Porte personnel | |
| had designed and installed the waste gas vent header piping to the NRS incinerator in 2011 without sufficient | |
| consideration of liquid accumulation. For example, the piping had low points where liquid could accumulate, | |
| and with no engineered equipment provided, such as a knock-out drum,b liquids could not be safely removed | |
| from the waste gas vent header piping system.c Because some of the process vents contained water vapor, the | |
| common belief was that the accumulated liquid consisted primarily of condensed water with small amounts of | |
| other process chemicals, including methyl mercaptan. As a result, area management instructed operations | |
| personnel to address high-pressure events in the waste gas vent header piping by opening manual drain valves | |
| from the waste gas vent header piping to the atmosphere, directing the liquid toward floor drains located within | |
| the manufacturing building [1, p. 18]. | |
| DuPont La Porte personnel never completed an MOC or established a specific procedure or used safe work | |
| practices, such as line-breaking permits, for draining this liquid from the waste gas vent header piping. Rather, | |
| area management directed operators to drain the system through written instructions to operations staff in a daily | |
| instruction log book [1, p. 18]. Beginning January 14, 2014, and continuing until the incident, the daily | |
| instructions directed operators to drain the methyl mercaptan waste gas vent header’s “low point” on the third | |
| floor once per shift. After installation of a flexible hose from the waste gas vent header drain valve to the floor, | |
| the instructions changed to include directing the liquid through the hose under a running safety shower until the | |
| liquid stopped flowing from the hose [1, p. 18]. | |
| DuPont La Porte personnel never sampled or analyzed the liquid workers routinely drained from this system [1, | |
| p. 18]. Daily instructions before the incident asked the operators to sample the unknown liquid. DuPont La | |
| Porte wanted samples of the liquid for a subsequent laboratory analysis to identify its chemical composition | |
| because workers reported that the liquid had a strong, noxious odor of sulfur compounds [1, p. 18]. Even | |
| though DuPont La Porte was aware that the liquid likely contained more than just water and was unaware of the | |
| actual chemical composition [1, p. 18], instructions to workers did not specify that additional precautions—such | |
| as wearing additional personal protective equipment (PPE)—were needed when draining the waste gas vent | |
| header. | |
| Weeks before the November 2014 incident, DuPont La Porte employees started an MOC to reduce liquid | |
| buildup by connecting a hose from the waste gas vent header piping to a process vessel, thus eliminating the | |
| need to drain the header liquid onto the floor. This MOC recognized that draining the waste gas vent header on | |
| the third floor was “not a good practice, since sometimes nitrogen is used to purge the line, which can lead to a | |
| a DuPont personnel believed the likely source of liquid accumulation was condensation from saturated vapor streams that originated in | |
| equipment operating above ambient temperatures. As these vapor streams entered the cooler waste gas vent header, liquid could | |
| condense and accumulate over time [1, p. 18]. | |
| b Knock-out drum is an industry term for a process vessel that provides for separation of vapor and liquid. | |
| c The CSB identified three locations in the waste gas vent header piping to the NRS incinerator where liquid could accumulate: (1) inside | |
| the manufacturing building, (2) the piping outside the manufacturing building as it passed through the MIC unit, and (3) at detonation | |
| arresters just prior to where the waste gas from the waste gas vent header entered the NRS incinerator. Each location was equipped with | |
| a drain valve—two locations had atmospheric drains and only one location’s drain was routed to a caustic scrubber [1, p. 18]. | |
| Page 108 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| nitrogen release inside the building.” Although area management recognized that this draining “was not a good | |
| practice” and could lead to a release of nitrogen,a the practice continued. Once personnel recognized the | |
| hazardous nature of this practice, the draining should have at least required additional safeguards, such as | |
| restricted access and respiratory protection. | |
| GUIDANCE TO INDUSTRY | |
| Companies should always use MOCs where required by corporate policy or federal process safety regulations. | |
| Special attention should be paid to nonroutine or abnormal operations because these may involve issues with | |
| safety systems, equipment, procedures, or personnel practices that can create additional hazards, potentially | |
| leading to serious safety incidents if there are poor MOC practices. Company MOC reviewers should be | |
| thoughtful and comprehensive so that potential dangers can be avoided or mitigated. | |
| LINE-‐BREAKING PRACTICES | |
| Companies should ensure the use of | |
| safe work practices,b such as line- | |
| breaking permits, to manage | |
| nonroutinec processes, such as | |
| draining the waste gas vent header | |
| piping. Under the PSM standard, a | |
| company must develop and | |
| implement safe work practices to | |
| provide for the control of hazards | |
| during work activities, such as | |
| lockout/tagout, confined space entry, | |
| or opening process equipment or | |
| Figure 35. Where Safe Work Practices Are Located on DuPont’s PSM Wheel [54, p. | |
| 2]. Source: DuPont, with annotations by CSB. | |
| a As an asphyxiant, nitrogen can displace oxygen, creating a potentially hazardous environment [168, p. 2]. | |
| b CCPS defines safe work practices as “an integrated set of policies, procedures, permits, and other systems that are designed to manage | |
| risks associated with non-routine activities such as performing hot work, opening process vessels or lines, or entering a confined space” | |
| [150]. | |
| c CCPS defines a nonroutine activity as any activity that is not fully described in an operating procedure. Additionally, nonroutine does | |
| not refer to the frequency of an activity; rather, it refers to whether the activity is part of the normal sequence of converting raw materials | |
| to finished materials [52, p. 288]. | |
| Page 109 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| piping (i.e., line breaking).a According to Guidelines for Risk Based Process Safety, from CCPS, safe work | |
| practices help control hazards and manage risks involved with nonroutine activities [52, p. 286]. Managing | |
| risks associated with nonroutine processes requires robust systems, thorough training and awareness, sound | |
| culture, and diligence [52, p. 293]. CCPS further suggests developing an integrated system for safe work | |
| practices, including safe work procedures, permits, checklists, and other written standards [52, pp. 291-92] | |
| (Figure 35). | |
| Any time a valve is opened to the atmosphere, the mechanical integrity of the system is compromised. Under | |
| PSM, employers must develop and implement safe work practices to control hazards during line breaking [18].b | |
| Figure 36 shows an approach to line and equipment opening (breaking) from a document that was produced | |
| under OSHA’s grant program. | |
| Figure 36. Triangle Approach to Line and Equipment Opening Permits. This slide is from a training | |
| document about OSHA operating procedures, safe work practices, and training [73, p. 27]. | |
| Source: OSHA website. | |
| Employees at the DuPont La Porte facility understood that there were hazards associated with nonroutine | |
| procedures, such as line breaking. DuPont’s corporate standard, which was also DuPont La Porte’s line- | |
| breaking procedure, specifically includes opening a valve to the atmosphere in its definition of line breaking, | |
| a 29 C.F.R. § 1910.119 (f)(4). | |
| b According to OSHA, line breaking “means the intentional opening of a pipe, line, or duct that is or has been carrying flammable, | |
| corrosive, or toxic material, an inert gas, or any fluid at a volume, pressure, or temperature capable of causing injury” 29 C.F.R. § | |
| 1926.1202. | |
| Page 110 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| which requires a written job plan if it involves a hazardousa process or system.b Personnel at the DuPont La | |
| Porte facility, however, did not understand that draining the waste gas vent header through the flexible hose | |
| constituted a line break and required a permit. To drain the header using the existing equipment and work | |
| instructions, operations personnel had no choice but to open a valve to let the liquid flow toward the floor drain | |
| (and thus to the atmosphere), breaking the mechanical integrity of the line. | |
| Although area management left written instructions, there was no written job plan and no specific requirement | |
| to obtain a line-breaking permit before draining the header. Had the instructions specified the requirement, the | |
| personnel could have recognized the need.c | |
| Figure 37. Photo Showing Another Line Break. Operators drained liquid accumulation in another vent header | |
| without using line-‐breaking procedures. Source: CSB. | |
| In addition to the periodic draining of the waste gas vent header, the CSB found that DuPont La Porte operators | |
| routinely drained other hazardous process equipment (see Figure 37 and Figure 38) without using line-breaking | |
| procedures. | |
| a DuPont line-breaking training defines a hazardous process or system as a “process or system that contains any material at any pressure | |
| that could cause a risk of injury to an individual(s), a risk of fire or explosion, an environmental risk, or an off-site risk. Examples of | |
| hazardous processes or systems include, but are not limited to, compressed fluids, especially gases in pipes and vessels; corrosive and/or | |
| flammable substances and toxic process lines; and any other lines that could contain material that is hazardous on contact or inhalation, | |
| including fluid whose temperature is higher than 140°F (60°C) or lower than 14°F (-10°C).” | |
| b DuPont’s corporate line-breaking standard and DuPont La Porte’s site line-breaking procedure states, “A written job plan that | |
| specifically addresses safety, health, and environment (SHE) issues shall be prepared and implemented for all line breaks on hazardous | |
| processes and systems until all hazards have been learned or controlled. The job plan shall be prepared by qualified personnel and | |
| reviewed by everyone involved in the work prior to the start of the line break.” | |
| c At the DuPont La Porte site, if a procedure described how to do a line break and the appropriate precautions to take, personnel were not | |
| required to obtain a permit. | |
| Page 111 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 38. Methylene Chloridea Compressor. Photo shows where operators routinely drained liquid accumulation | |
| from a methylene chloride compressor without using line-‐breaking procedures. Source: CSB. | |
| In both February and October 2014, DuPont La Porte personnel held problem-solving meetings with two | |
| different shifts of operations personnel to discuss high-pressure events in the waste gas vent header, and both | |
| times personnel identified liquid accumulation in piping low points as well as draining liquid from the vent | |
| header. Additionally, both shifts proposed modifying piping to eliminate low points where liquid accumulated | |
| as a potential solution. These meetings, however, did not ensure that personnel were safely troubleshooting the | |
| high-pressure events. It is important for companies to recognize that problem-solving sessions are opportunities | |
| to evaluate hazards and ensure that MOCs, operating procedures, and safe work practices are being used. | |
| In situations with unknown conditions, safe work practices required by PSM provide an organized approach to | |
| proceed safely. Consistently using safe work practices, such as line-breaking permits, ensures that each time a | |
| piece of process equipment is put into a nonroutine situation, personnel use effective safeguards. Furthermore, a | |
| permit process can address procedures, hazard analysis, PPE, and safeguards. Additionally, if hazards are | |
| identified, corrective actions should be developed, and effective safeguards should be implemented. | |
| GUIDANCE TO INDUSTRY | |
| Companies should recognize that nonroutine operations such as line breaking—even with established permit | |
| processes—can represent significant potential dangers. One way to help ensure that personnel understand the | |
| permit process is to train them on the different scenarios that would trigger a permit. Companies should analyze | |
| a Methylene chloride is a toxic chemical that can cause death at certain concentrations [93]. | |
| Page 112 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| recurring operational or safety issues that trigger permits and eliminate the underlying causes of those issues. In | |
| instances requiring repeated line breaking, a hazard analysis should be performed, and an engineering solution | |
| should be applied (following an effective MOC) to avoid recurrence of the hazard. | |
| SHIFT COMMUNICATION PRACTICES | |
| Companies should develop procedures | |
| and practices for effective | |
| communication among their personnel | |
| (Figure 39). Effective communication | |
| depends on reliable and complete | |
| information that is transmitted and | |
| received in a timely manner. | |
| Understanding the information is | |
| imperative for safe operations. | |
| In its Guidelines for Risk Based | |
| Process Safety, CCPS outlines several | |
| approaches for communications | |
| including formalizing | |
| communications between workers, | |
| formalizing communications between | |
| shifts, and formalizing communications | |
| between work groups. Depending on the type of communication and group involved, verbal or written | |
| communication may be appropriate. When verbal communication is used, there should be a sufficient dialogue | |
| to verify that the person receiving information understands it. Additionally, personnel can use log books and | |
| written communications to transmit particularly important information. Using a combination of these two | |
| methods can benefit operations, as the CCPS book notes in the section on how formalize shift communications | |
| [52, pp. 475-76]. | |
| Figure 39. Where Shift Communication Falls on DuPont’s PSM Wheel [54, p. 2]. | |
| Source: DuPont, with annotations by CSB. | |
| During the troubleshooting operations, DuPont personnel relied upon verbal communications to convey the | |
| Technical Team’s plan to the incoming shift (the shift working at the time of the incident) [1, pp. 25-26]. Post- | |
| incident, it remains unclear what the prior shift communicated to the incoming shift about the Technical Team’s | |
| plan and the status of the troubleshooting, because this information was communicated only verbally.a | |
| According to a DuPont training, “An effective shift turnover is important for chemical operations to ensure | |
| continuity across operating shifts and ensure all operating personnel fully understand both normal and abnormal | |
| or unusual conditions within the operating area in order to avoid misunderstandings or lack of information.” | |
| a The only written communication to the night shift supervisor was a note in the shift log that stated: “Unplugging M[e]SH Header.” | |
| MeSH is DuPont’s abbreviation for methyl mercaptan [1, p. 26]. | |
| Page 113 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Having continuity in operations from shift to shift ensures that processes run smoothly and equips workers | |
| coming on shift with information that helps strengthen process safety performance. | |
| During the troubleshooting operations, DuPont relied upon verbal communications at several key times: | |
| • The Technical Team’s verbal communication of the plan to the day shift supervisor [1, p. 25]. | |
| • The face-to-face verbal communication between shift supervisors to transition the efforts from the day | |
| shift to the night shift [1, pp. 25-26]. | |
| Reliance on verbal communication during this troubleshooting operation proved detrimental because this | |
| problem was novel, and the night shift supervisor (referred to in this report as the “Shift Supervisor”) was | |
| learning of the shutdown and subsequent startup difficulties for the first time when he came on shift. Although | |
| the Technical Team verbally communicated with the day shift supervisor, the Technical Team did not meet with | |
| the newly involved night shift supervisor, nor did it communicate verbally or in writing with the night shift | |
| operations personnel. Improved communication could have helped ensure continuity of the troubleshooting | |
| operation by better informing the night shift of all the relevant activities that had occurred during the week and | |
| the steps needed to continue with the troubleshooting process. | |
| It is important for a company to assess the type of communication necessary for effective information sharing | |
| between shifts and between departments or divisions of a company. The more complicated the process and the | |
| more novel the problem, the more imperative it is to have effective communication. Consideration should be | |
| given to using multiple modes of communication (including written communication) to ensure that all affected | |
| employees get the information they need to perform their jobs safely, within the broader context of other | |
| ongoing operational and process safety issues, to maximize the chance for continuity and safety in operations. | |
| GUIDANCE TO INDUSTRY | |
| Effective communication between different operational units at a facility, and between supervisors and workers | |
| on changing shifts, is critical to safety. Communication is necessary to convey the status of operations, ongoing | |
| changes, abnormalities, unusual operating conditions, or other relevant issues associated with chemical process | |
| equipment. The more complex the process involved, the greater the imperative to ensure that communication is | |
| effective. Reliance solely upon one form of communication, especially verbal communication, can leave the | |
| workforce vulnerable to potential gaps in information communicated, misunderstandings, or absence of critical | |
| information in what oftentimes can be an evolving situation. | |
| 7 ADDITIONAL FACTS, CONDITIONS, AND CIRCUMSTANCES IDENTIFIED | |
| The CSB is tasked with investigating and reporting “to the public in writing the facts, conditions, and | |
| circumstances and the cause or probable cause of any accidental release resulting in a fatality, serious injury, or | |
| Page 114 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| substantial property damages.”a This information is beneficial in promoting safe workplaces and helping to | |
| protect workers, the public, and the environment. | |
| The CSB identified numerous conditions and circumstances that existed at the time of the November 15, 2014 | |
| DuPont La Porte incident. In September 2015, the CSB issued an Interim Recommendations report to address | |
| conditions and circumstances, some of which were causal to the incident, before the DuPont La Porte Lannate® | |
| facility restarted [1]. Similar to its Interim Recommendations, the CSB identified a condition and circumstance, | |
| DuPont La Porte’s employee incentive program, that could be strengthened to further promote safe workplaces | |
| at DuPont legacy sites. Section 7.1 addresses the guidance for incentive compensation programs that existed at | |
| the time, and the corresponding Guidance to Industry section covers newly published OSHA guidance and | |
| industry guidance. | |
| EMPLOYEE INCENTIVE PROGRAM | |
| Companies should ensure that safety incentive programs do not disincentivize personnel from reporting injuries | |
| or other deficiencies in process safety management systems.b The DuPont La Porte facility implemented a | |
| variable compensation (bonus) system called the La Porte Local Performance Based Compensation (LPBC) | |
| program. The LPBC, however, did not use process safety management performance metrics. Instead, it used a | |
| safety modifier based solely on OSHA total recordable injuries, and it was constructed in a way that could have | |
| potentially disincentivized reporting injuries. | |
| The stated purpose of the LPBC, which was in effect at the time of the November 2014 incident, was “to | |
| provide the opportunity for eligible employees to share in business results that exceed expectations.” This | |
| program created incentive compensation opportunities for DuPont La Porte employees in various categories, | |
| including operators, mechanics, and general helpers, who were represented by the International Chemical | |
| Workers Union Council of the United Food and Commercial Workers (ICWUC/UFCW) Local 900C labor | |
| union. | |
| The structure of the LPBC program for this group of employees evolved over the established range of | |
| performance years but involved two primary components. The first part, referred to as the Business Metric, | |
| a 42 U.S.C. § 7412(6)(C)(i). | |
| b Under OSHA’s Recording and Reporting Occupational Injuries and Illnesses regulations, an employer “must establish a reasonable | |
| procedure for employees to report work-related injuries and illnesses promptly and accurately. A procedure is not reasonable if it would | |
| deter or discourage a reasonable employee from accurately reporting a workplace injury or illness” (29 C.F.R. § 1904.35(b)(1)(i)). The | |
| OSH Act and OSHA regulations, including its Recording and Reporting Occupational Injuries and Illnesses regulations, prohibit | |
| employers from discriminating, retaliating, or instituting other adverse consequences on employees who report injuries or other safety | |
| concerns. According to OSHA, “OSHA’s Whistleblower Protection Program enforces the whistleblower provisions of more than twenty | |
| whistleblower statutes protecting employees who report violations of various workplace safety and health, airline, commercial motor | |
| carrier, consumer product, environmental, financial reform, food safety, health insurance reform, motor vehicle safety, nuclear, pipeline, | |
| public transportation agency, railroad, maritime, and securities laws. Rights afforded by these whistleblower protection laws include, but | |
| are not limited to, worker participation in safety and health activities, reporting a work-related injury, illness or fatality, or reporting a | |
| violation of the statutes herein” [166] (29 C.F.R. § 1904.35(b)(1)(iv)). | |
| Page 115 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| rewarded success with respect to site financial goals, such as increases in after-tax operating income and | |
| improvement in cash flow from operations. The second part, referred to as Line of Sight, represented a | |
| weighted average of operational performance metrics among the different units at the DuPont La Porte site, and | |
| consisted of things like reducing costs and exceeding production targets. | |
| Any incentive eligible to be paid for exceeding business performance goals, however, would then potentially be | |
| reduced by what the LPBC termed a “safety modifier.” For example, in performance year 2011, the DuPont La | |
| Porte site established the safety modifier based on the number of OSHA total recordable injuries, with the | |
| number of recordable injuries causing a reduction in available incentive award payments that were otherwise | |
| due to be paid to members of that portion of the workforce. Specifically, at the program’s start in 2011, if there | |
| were three or fewer recordable injuries, the LPBC set the safety modifier value at 1, which did not reduce the | |
| incentive payable for business performance; however, as more recordable injuries occurred, the safety modifier | |
| incrementally reduced the total incentive paid to employees.a | |
| Over the years, the LPBC evolved in terms of how the safety modifier worked. In 2014, the year of this | |
| incident, the LPBC adjusted the safety modifier so that every reported worker injury would decrease the group’s | |
| bonus payout by 5 percent, with a maximum 50 percent reduction of any available bonus paid to employees. | |
| By using a safety modifier that considered only worker injuries, DuPont La Porte equated safety performance | |
| with occupational safety metrics, similar to DuPont’s Safety Perception Surveys. Thus, DuPont La Porte did not | |
| include a process safety performance metric in its incentive. A disproportionate emphasis on occupational | |
| safety metrics as the measurement for safety performance could confuse personnel into viewing occupational | |
| safety and process safety as the same or perceiving that occupational safety is more important than process | |
| safety. Furthermore, emphasizing a low number of total recordable injuries could give personnel false | |
| confidence about process safety performance. | |
| As stated recently by CCPS in its publication on process safety culture, Essential Practices for | |
| Creating, Strengthening, and Sustaining Process Safety Culture, | |
| “Money is one of the strongest influences on human behavior, for better or worse. When developing | |
| compensation and incentive schemes based on process safety performance, it is critical to design them | |
| carefully to reinforce the desired cultural attributes and behaviors. It is equally critical to be aware of | |
| the many pitfalls that lead a well-intentioned compensation scheme to unwittingly support negative | |
| behaviors [56, p. 109].” | |
| a In 2011, if there were four recordable injuries, then the modifier reset to 0.9, if there were five recordable injuries it reset to 0.8, and for | |
| six or more recordable injuries it reset to 0.75. Over subsequent years, the safety modifier became more impactful in a negative way if the | |
| site had not improved its total recordable injury rate from the previous year. | |
| Page 116 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| If a company decides to use an incentive to focus on safety performance, it should consider having a process | |
| safety component that uses leading indicators over multiple years. Because process safety incidents are | |
| typically infrequent, personnel can perform poorly in process safety for a long time without experiencing a | |
| major accident [56, p. 110]. Therefore, using lagging indicators, such as the number of process safety incidents, | |
| could hide poor process safety performance [56, p. 110]. On the other hand, using leading indicators related to | |
| correct behaviors, such as percentage of inspection completion, is better because the events on which such | |
| indicators are based happen more frequently [56, p. 110]. Additionally, companies can drive long-term process | |
| safety performance by using multiyear incentives because process safety needs to be performed consistently | |
| well over time [56, p. 110]. If companies employ yearly schemes, management should ensure that rewards are | |
| provided in recognition of steady process safety performance over the course of a year [56, pp. 110-111]. If a | |
| process safety incentive is used, companies should ensure that process safety incentives are measuring key | |
| aspects of process safety management systems or process safety culture, and not personal or occupational safety | |
| metrics [56, p. 112]. Furthermore, to prevent confusion between process safety and occupational safety, | |
| management should not combine process safety indicators and occupational safety indicators into a single safety | |
| incentive [56, p. 112]. | |
| Regardless of its precise formulation and despite small changes made to the safety modifier throughout the | |
| range of years represented in this program, DuPont La Porte’s LPBC potentially created a disincentive for | |
| workers to report injuries. Employees working under these types of programs would report injuries at financial | |
| risk to themselves and their co-workers. In addition, safety incentive programs like this one may not be | |
| effective in driving safety improvement [74]. Furthermore, when constructed in this manner, a safety incentive | |
| program can be susceptible to “gaming,” with workers refraining from reporting workplace injuries to earn the | |
| otherwise available incentive due to be paid [74].a This phenomenon can make it difficult to spot trends in | |
| worker safety issues, leaving other workers vulnerable to the same injury as potentially dangerous conditions go | |
| uncorrected, among other practical concerns. As OSHA Deputy Assistant Secretary Fairfax explained in a | |
| March 12, 2012, memorandum to agency regional administrators and whistleblower program managers, | |
| If employees do not feel free to report injuries or illnesses, the employer’s entire workforce is | |
| put at risk. Employers do not learn of and correct dangerous conditions that have resulted in | |
| injuries, and injured employees may not receive the proper medical attention, or the workers’ | |
| compensation benefits to which they are entitled. Ensuring that employees can report injuries | |
| or illnesses without fear of retaliation is therefore crucial to protecting worker safety and health | |
| [75]. | |
| The memorandum further expressed concern that these types of safety incentive bonus programs may place | |
| implicit pressure on employees not to report workplace injuries or illnesses: | |
| a In a recent National Safety Council article, one corporate safety manager noted that these types of incentive programs have surface | |
| allure but do not usually drive actual safety improvement, and suggested that some incentive programs may instead actually promote | |
| “covering up” and “cooking the books” through underreporting or nonreporting of workplace illnesses or injuries so employees can | |
| remain eligible for rewards [74]. | |
| Page 117 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Some employers establish programs that unintentionally or intentionally provide employees an | |
| incentive to not report injuries. For example, an employer might enter all employees who have | |
| not been injured in the previous year in a drawing to win a prize, or a team of employees might | |
| be awarded a bonus if no one from the team is injured over some period of time. Such | |
| programs might be well-intentioned efforts by employers to encourage their workers to use safe | |
| practices. However, there are better ways to encourage safe work practices, such as incentives | |
| that promote worker participation in safety-related activities, such as identifying hazards or | |
| participating in investigations of injuries, incidents or “near misses.” OSHA’s [Voluntary | |
| Protection Programs] Guidance materials refer to a number of positive incentives, including | |
| providing tee shirts to workers serving on safety and health committees; offering modest | |
| rewards for suggesting ways to strengthen safety and health; or throwing a recognition party at | |
| the successful completion of company-wide safety and health training [75]. | |
| After the November 2014 incident, the DuPont La Porte site changed its LPBC bonus system to align it with | |
| OSHA guidance that existed at the time, such that the safety modifier would not discourage workers from | |
| reporting injuries. The new 2015 La Porte safety modifier was based on employees’ completing computer- | |
| based training courses and annual medical examinations. The CSB viewed DuPont La Porte’s correction of the | |
| potential disincentive in the LPBC as a positive development. | |
| The CSB lacks documentation showing that workers on DuPont La Porte’s Safety Committee or those covered | |
| by the LPBC objected to this safety modifier prior to the incident. None of the workers on the Safety | |
| Committee participated in the capacity of official union representative of ICWUC/UFCW Local 900C. | |
| However, when workers have concerns about an incentive program that can impact the reporting of incidents, | |
| they should report these concerns to their union, if they are represented, or to a health and safety committee or a | |
| manager. It is imperative, regardless of having a particular incentive program, that workers report unsafe | |
| conditions and safety (personal or process) incidents to help prevent future incidents. | |
| Consistent with OSHA regulations and guidance, all legacy DuPont sites should evaluate any safety incentive | |
| programs or variable pay initiatives that reduce employee bonus awards based solely upon injury rates, or that | |
| otherwise potentially impair OSHA record-keeping requirements, and change the payout structure to incentivize | |
| improved safety performance. OSHA itself does not consider “conditioning a benefit on compliance with | |
| legitimate safety rules or participation in safety-related activities” to violate section 1904.35(b)(1)(iv), so long as | |
| programs that do so are instituted appropriately.a As DuPont reviews incentive programs at its legacy sites, the | |
| CSB similarly encourages DuPont to continue to explore ways to encourage positive safety performance, with | |
| respect to both personal and process safety. Specifically, the CSB encourages DuPont to consider expanding | |
| consideration of safety incentive programs by broadening the company’s focus beyond personal safety | |
| a “For example, raffling off a $500 gift card each month in which employees universally complied with legitimate workplace safety | |
| rules—such as using required hard hats and fall protection and following lockout-tagout procedures—would not violate the rule. | |
| Likewise, rewarding employees for participating in safety training or identifying unsafe working conditions would not violate the rule. | |
| On the contrary, OSHA encourages employers to find creative ways to incentivize safe work practices and accident-prevention measures | |
| that do not disproportionately penalize workers who report work-related injuries or illnesses” [158]. | |
| Page 118 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| programs. If DuPont desires to retain safety incentive programs, the company should also consider how it can | |
| incentivize safety more holistically, ensuring that process safety and major accident prevention efforts are | |
| bolstereda along with more traditional efforts aimed at reducing workplace illnesses and injuries. In no case, | |
| however, should any incentive program act in any way to discourage the required reporting of safety issues such | |
| as injuries, illnesses, incidents, hazards, or near-miss incidents. | |
| GUIDANCE TO INDUSTRY | |
| Understanding how incidents occur can be beneficial in preventing future worker injuries and strengthening | |
| process safety management systems. Some safety incentive programs, however, may create a culture of | |
| nonreporting of safety incidents, potentially hampering learning from the underlying events, possibly resulting | |
| in a failure to address the causes of the incident. In response to these types of concerns, OSHA created record- | |
| keeping requirements and issued regulations to prevent whistleblower retaliation for reporting injuries.b, c | |
| Additionally, OSHA recently published guidance on how to formulate an incentive without disincentivizing | |
| workers from reporting injuries. | |
| On October 11, 2018, Kim Stille, Acting Director of Enforcement Programs at OSHA, issued a memorandum to | |
| Regional Administrators titled “Clarification of OSHA’s Position on Workplace Safety Incentive Programs and | |
| Post-Incident Drug Testing Under 29 C.F.R. § 1904.35(b)(1)(iv)” [76]. In that memorandum, Acting Director | |
| Stille sought to clarify OSHA enforcement around workplace safety incentives paid by employers. She stated | |
| that “29 C.F.R. § 1904.35(b)(1)(iv) does not prohibit workplace safety incentive programs” as long as such | |
| programs “are not implemented in a manner that discourages reporting” of workplace injuries [76]. The | |
| memorandum then elaborated on how an employer could avoid even “inadvertent deterrent effects of a rate- | |
| based incentive program by taking positive steps to create a workplace culture that emphasizes safety, and not | |
| a According Andrew Hopkins, “Other things like incentives need to be rethought. Performance agreements and bonuses now reinforce | |
| the priorities of speed and production. They’ve been made to reinforce personal safety in recent years. They need now to be rethought | |
| again to incentivize the avoidance of catastrophe” [67, p. 3]. | |
| b According to the 2012 Fairfax memorandum, “Incentive programs that discourage employees from reporting their injuries are | |
| problematic because, under section 11(c), an employer may not ‘in any manner discriminate’ against an employee because the employee | |
| exercises a protected right, such as the right to report an injury.… If an employee of a firm with a safety incentive program reports an | |
| injury, the employee, or the employee’s entire work group, will be disqualified from receiving the incentive, which could be considered | |
| unlawful discrimination. One important factor to consider is whether the incentive involved is of sufficient magnitude that failure to | |
| receive it ‘might have dissuaded reasonable workers from’ reporting injuries. Burlington Northern & Santa Fe Railway Co. v. White, | |
| 548 U.S. 53, 68 (2006).” The memorandum continues, “In addition, if the incentive is great enough that its loss dissuades reasonable | |
| workers from reporting injuries, the program would result in the employer’s failure to record injuries that it is required to record under | |
| Part 1904. In this case, the employer is violating that rule, and a referral for a recordkeeping investigation should be made.… This may | |
| be more likely in cases where an entire workgroup is disqualified because of a reported injury to one member, because the injured worker | |
| in such a case may feel reluctant to disadvantage the other workgroup members” [75]. | |
| c In explaining OSHA’s amended regulation found at 29 C.F.R. § 1904.35(b)(1)(i), OSHA Deputy Assistant Secretary Dorothy | |
| Dougherty made explicit the longstanding requirement for employers to have a reasonable procedure for employees to report work- | |
| related injuries and illnesses, and (b)(1)(iv) incorporated the existing prohibition on retaliating against employees for reporting work- | |
| related injuries or illnesses under section 11(c) of the OSH Act, 29 U.S.C. § 660(c). She also made clear, however, that “Section | |
| 1904.35(b)(1)(iv) does not prohibit safety incentive programs. Rather, it prohibits taking adverse action against employees simply | |
| because they report work-related injuries or illness. Withholding a benefit—such as a cash prize drawing or other substantial award— | |
| simply because of a reported injury or illness would likely violate section 1904.35(b)(1)(iv) regardless of whether such an adverse action | |
| is taken pursuant to an incentive program [158].” | |
| Page 119 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| just rates” [76]. For example, Acting Director Stille noted that any inadvertent deterrent effect caused by a rate- | |
| based incentive program could be “counterbalanced” by affirmative steps such as | |
| • | |
| • | |
| • | |
| creating an incentive program that rewards employees for identifying unsafe conditions in the | |
| workplace; | |
| implementing a training program for all employees to reinforce reporting rights and responsibilities, | |
| emphasizing the employer’s nonretaliation policy; or | |
| instituting a mechanism for accurately evaluating employees’ willingness to report injuries and illnesses | |
| [76]. | |
| In Essential Practices for Creating, Strengthening, and Sustaining Process Safety Culture, CCPS posed the | |
| question of whether a company should forgo all process safety–related incentives. CCPS stated that an | |
| argument can be made to that effect, with working injury-free serving as a long-term benefit for any worker. | |
| Nevertheless, money is a strong human motivator, and if used with care, it can influence behavior for the better | |
| [56, p. 109]. As with occupational safety–based incentives, management should consider whether the use of a | |
| process safety incentive creates a potential for inverse effects. An incentive could lead to the opposite of the | |
| desired behavior (e.g., using incident numbers or incident reduction for the basis of an incentive “may drive | |
| personnel to hide or under-report incidents”) [56, p. 110]. | |
| Companies should assess safety incentive programs currently in place to ensure they are effective in driving | |
| positive safety change and do not serve as a disincentive for reporting workplace safety issues. | |
| 8 KEY FINDINGS | |
| In its investigation of the November 15, 2014, DuPont La Porte incident, the CSB found that | |
| 1. DuPont did not effectively respond to a toxic chemical release; | |
| 2. DuPont’s corporate process safety management system did not ensure that DuPont La Porte | |
| implemented and maintained an effective process safety management system; and | |
| 3. DuPont La Porte did not assess its culture for process safety in the site’s Safety Perception Surveys or | |
| any other formal assessment program, allowing serious process safety deficiencies to exist at the site. | |
| The CSB issues recommendations to the DuPont La Porte facility, DuPont, and the Local 900C of the | |
| International Chemical Workers Union Council of the United Food and Commercial Workers, as well as | |
| guidance and key lessons for the chemical industry, to address these key findings and to help prevent future | |
| incidents. | |
| Page 120 | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| 9 SAFETY GUIDANCE | |
| The CSB, through the course of its investigation, identified key lessons from the November 15, 2014 incident | |
| that companies can use at their facilities (for more information, see Guidance to Industry from referenced | |
| sections). | |
| 1. Companies should ensure that employees understand the hazards of chemicals that they are working | |
| with and may be potentially exposed to if there is a release. Where there are multiple hazardous | |
| chemicals, such as methyl isocyanate (MIC) and methyl mercaptan, it is important that companies | |
| effectively train workers on the hazards of each chemical at their facility. Furthermore, companies | |
| should train workers who handle multiple highly toxic chemicals, such as methyl mercaptan and MIC, | |
| to treat these chemicals with equal importance. This training is important for workers to help ensure | |
| they have a working knowledge of the relevant chemical hazards. (Section 3: Delayed Awareness of | |
| Toxic Chemical Release) | |
| 2. Automatic alarms designed to alert personnel of hazardous conditions—such as a release of a toxic | |
| chemical or the existence of an explosive atmosphere—can relay critical safety information immediately | |
| to personnel, without the potential delays inherent in a system that relies solely on a control room | |
| operator to communicate safety alarms verbally to operators in the field. (Section 3: Delayed | |
| Awareness of Toxic Chemical Release) | |
| 3. Specific technical knowledge from unit experts—including technical and operations personnel—can be | |
| invaluable to the incident commander in an emergency at a chemical processing facility. Companies | |
| need to ensure that these individuals are preidentified as technical support personnel and that backup | |
| capability is available in the event the primary technical support personnel become unavailable. | |
| (Section 4.2: Process Coordinator Was Missing) | |
| 4. Plant emergency procedures should clearly outline the alerting and notification protocols for different | |
| types of plant emergencies. These procedures should also include guidance for situations in which there | |
| is insufficient initial information to effectively assess the nature of the problem and the level of | |
| emergency response team resources required. (Section 4.3.1: Call for ERT Response) | |
| 5. Even though industrial facilities may infrequently call upon emergency response vehicles, it is essential | |
| that those vehicles function as intended when needed. To ensure emergency vehicle reliability, | |
| companies must develop and apply regular maintenance and testing schedules for their emergency | |
| response vehicles. (Section 4.3.2: ERT Mini-Pumper Truck Not Operational) | |
| 6. Companies need a reliable means for emergency response teams to characterize hazardous atmospheres. | |
| Companies should provide air monitoring equipment to emergency response teams and train those | |
| teams on how to operate the equipment and interpret monitoring results. At facilities that assign the | |
| inspection, maintenance, and storage of portable air monitoring equipment to personnel who are not | |
| members of the emergency response team, the company should ensure that team members know where | |
| Page 121 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| the equipment is stored and can access it. (Section 4.4.1: Entry into Potentially Explosive | |
| Atmosphere) | |
| 7. High-hazard areas should be equipped with adequate detectors, alarms, and surveillance technology to | |
| identify whether there is a chemical release (or other type of emergency) and if personnel are affected. | |
| (Section 4.4.2: No Technology to Locate Missing Workers) | |
| 8. Companies need to develop a system to update emergency planning documents when pertinent hazards | |
| are identified. Changes to emergency planning documents should be effectively communicated to the | |
| site emergency response team. (Section 4.4.3: Unrecognized Manufacturing Building Collapse | |
| Hazard) | |
| 9. Chemical facilities should ensure that their emergency response plans include maps showing the layout | |
| of buildings containing hazardous chemicals, for use by emergency responders and to aid evacuation | |
| and rescue efforts. Facilities should also coordinate regularly scheduled site tours for both plant and | |
| external emergency responders to develop strong working relationships and help ensure responders are | |
| familiar with facility access points, hazards, emergency response issues, and site or facility layout. | |
| Additionally, facilities should familiarize responders with process structures or buildings by having | |
| periodic drills inside them, to improve responder navigation during emergencies. To enhance responder | |
| performance, members of an emergency response team should train together, especially when multiple | |
| companies are staffing a single, integrated team. (Section 4.5: Difficulties Navigating Manufacturing | |
| Building) | |
| 10. When a process safety incident occurs, such as a chemical release, it can be beneficial for technical | |
| personnel who are not immediately involved in emergency response functions to analyze process data to | |
| assess the source, scope, and magnitude of the incident. This analysis can help the company (and the | |
| incident commander) identify needed equipment manipulations to stop or control the incident, such as | |
| shutting down pumps or closing isolation valves. (Section 4.6: No Analysis of Process Data to | |
| Identify Source of Leak) | |
| 11. Companies should ensure emergency response team members are trained to (1) physically designate the | |
| hot zone; (2) communicate the location of the hot zone and entry control points to all personnel assisting | |
| with the emergency response, including operations personnel; and (3) control entry and exit points of | |
| the hot zone. (Section 4.7: Inadequate Creation and Control of Hot Zone) | |
| 12. Dispersion modeling of chemical releases can be an effective risk-based emergency response tool, but | |
| its results are highly dependent on accurate input data. During an emergency, it can sometimes be | |
| difficult to obtain an accurate release rate, limiting the accuracy of resulting models. Companies should | |
| not rely on unsupported data when making critical emergency response decisions, such as those | |
| affecting workers, members of the public, or people or property in the surrounding area. In emergencies | |
| that could affect the public and in which chemical release rates cannot be accurately estimated (for | |
| model input), written guidelines for how and when to alert the public should be available to emergency | |
| responders. As better information about the release becomes available, the public protection zone can | |
| be adjusted accordingly. (Section 4.8.1: Release Modeling) | |
| Page 122 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 13. Monitoring for hazardous gases along the fence line at chemical facilities can help companies | |
| understand the extent of a release. This monitoring can be performed by fixed detectors, which can | |
| continually collect and record data, providing early notification of releases outside the property. When | |
| fixed detectors are not available, a person using a portable gas detector may also perform air monitoring. | |
| This strategy, however, introduces additional risk because that individual may enter a hazardous | |
| environment unknowingly. Proper personal protective equipment, including respiratory protection, is | |
| needed during manual air monitoring operations. (Section 4.8.4: Air Monitoring) | |
| 14. Employing any particular management system on its own, without additional work aimed at successful | |
| implementation, may not be sufficient to prevent major chemical incidents. Companies should conduct | |
| periodic comprehensive assessments of their process safety management systems and their | |
| implementation of these systems at established intervals to evaluate and identify opportunities to | |
| strengthen their systems’ effectiveness. (Section 5.3: American Chemistry Council) | |
| 15. Companies should ensure that when a process safety management system changes, their sites update | |
| their programs simultaneously and adhere to those changes. The ability to adapt quickly to industry | |
| trends and field learnings can be beneficial. To maximize the value of improvements, companies should | |
| consider reevaluating sites to ensure consistency with evolving practices. (Section 5.3.3: Responsible | |
| Care Conformance Audits) | |
| 16. Companies should invest time and resources to conduct audits. These resources should be used to | |
| ensure that audits are robust and comprehensive. (Section 5.3.3: Responsible Care Conformance | |
| Audits) | |
| 17. Personal safety performance and process safety performance are two different safety measures that all | |
| chemical process facilities should evaluate. Personal injury statistics are not an effective gauge of the | |
| quality of process safety management systems or process safety culture. (Section 5.4.1: Building a | |
| Safety Culture) | |
| 18. Companies should have a process in place to ensure that hazard scenarios are fully developed and that | |
| process hazard analysis (PHA) teams assign appropriate initiating event frequencies and consequence | |
| severities to the scenario because it can make a significant difference in safeguard requirements. | |
| Additionally, PHA teams need to ensure that the safeguards applied to the hazard scenario are relevant | |
| and effective in controlling the hazard. (Section 6.1:Process Hazard Analysis Evaluation) | |
| 19. Companies should ensure before corrective actions are closed that the intent of a recommendation is | |
| met. One way to make the intention of the recommendation the focus of a corporate or site action is to | |
| evaluate the substance of the corrective action in addition to the time it takes to complete the action. | |
| (Section 6.2: Implementation of Corrective Actions) | |
| 20. Companies should develop an action plan to identify and control hazards during troubleshooting | |
| operations. There are multiple approaches a company can take to address troubleshooting, including | |
| PHAs, operating procedures, management of change (MOC) procedures, and safe work practices. | |
| (Section 6.3: Process Safety Practices during Troubleshooting Operations) | |
| Page 123 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 21. Companies should always use MOCs where required by corporate policy or federal safety regulations | |
| (OSHA’s Process Safety Management standard or the EPA’s Risk Management Plan rule). Special | |
| attention should be paid to nonroutine or abnormal operations because there may be issues with safety | |
| systems, equipment, procedures, or personnel practices that can create additional hazards, potentially | |
| leading to serious safety incidents if there are poor management of change practices. MOC reviewers | |
| should be thoughtful and comprehensive, so potential dangers can be avoided or mitigated. (Section | |
| 6.4: MOC Practices) | |
| 22. Companies should recognize that nonroutine operations such as line breaking—even with established | |
| permit processes—can represent significant potential dangers. One way to help ensure that personnel | |
| understand the permit process is to train them on the different scenarios that would trigger a line- | |
| breaking permit. Companies should analyze recurring operational or safety issues that trigger permits | |
| and eliminate their underlying causes. In instances requiring repeated line breaking, for example, a | |
| hazard analysis should be performed, and an engineering solution should be applied (following an | |
| effective MOC) to avoid recurrence of the hazard. (Section 6.5: Line-Breaking Practices) | |
| 23. Effective communication between different operational units at a facility, and between supervisors and | |
| workers on changing shifts, is critical to safety. Communications are essential to convey the status of | |
| operations, any ongoing changes, abnormalities, unusual operating conditions, or other relevant issues | |
| associated with chemical process equipment. The more complex the process involved, the more of an | |
| imperative exists to ensure that communication is effective. Reliance solely upon one form of | |
| communication, especially verbal communication, can leave the workforce vulnerable to potential gaps | |
| in information communicated, misunderstandings, or the absence of critical information in what | |
| oftentimes can be an evolving situation. (Section 6.6: Shift Communication Practices) | |
| 24. Employee incentive programs that reduce bonuses to employees based upon the number of recordable | |
| injuries—or other similar metric—can create a disincentive for workers to report injuries or incidents. | |
| Understanding how incidents occur can be beneficial in preventing future worker injuries and | |
| strengthening process safety management systems. Some safety incentive programs, however, may | |
| create a culture of nonreporting of safety incidents, potentially hampering learning from the underlying | |
| events, possibly resulting in a failure to address the causes of the incident. If employees do not feel free | |
| to report workplace injuries, incidents, or near misses, the employer’s entire workforce is put at risk. | |
| Ensuring that employees can report injuries or other process safety management system deficiencies is | |
| therefore central to protecting worker safety and health and aiding accident prevention. (Section 7.1: | |
| Employee Incentive Program) | |
| 10 RECOMMENDATIONS | |
| The CSB makes the following safety recommendations: | |
| Page 124 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| DUPONT LA PORTE, TEXAS, CHEMICAL FACILITY | |
| 2015-01-I-TX-R8 | |
| Work together with emergency response team (ERT) member companies (DuPont, Chemours, Kuraray, and | |
| Invista), the International Chemical Workers Union Council of the United Food and Commercial Workers | |
| (ICWUC/UFCW) Local 900C, and the ICWUC/UFCW staff (if requested by the Local 900C) to update the | |
| DuPont La Porte emergency response plan. The emergency response program should ensure that periodic | |
| exercises or drills are performed on new procedures developed to address key lessons to strengthen ERT | |
| capabilities. The emergency response program should address the following: | |
| • Preidentifying unit experts as technical support personnel and ensuring that backup capability is | |
| available in the event the primary technical support personnel become unavailable. (Section 4.2: | |
| Process Coordinator Was Missing) | |
| • Clearly detailing in plant emergency procedures the alerting and notification protocols for different | |
| types of plant emergencies. Provide initial training to new plant personnel and periodic training to all | |
| plant personnel on these emergency communication procedures. These procedures should also include | |
| guidance for emergency responders when there is insufficient initial information to effectively assess | |
| the nature of the problem and the level of ERT resources required. (Section 4.3.1: Call for ERT | |
| Response) | |
| • Developing and applying regular maintenance schedules for emergency response vehicles consistent | |
| with the National Fire Protection Association’s Standard for the Inspection, Maintenance, Testing, and | |
| Retirement of In-Service Emergency Vehicles (NFPA 1911), which requires weekly visual and | |
| operational checks of emergency vehicles and has example checklists to use when performing | |
| preventive maintenance on emergency vehicles. (Section 4.3.2: ERT Mini-Pumper Truck Not | |
| Operational) | |
| • Ensuring that ERTs have reliable means to characterize hazardous atmospheres, for example equipment | |
| that monitors toxicity, explosivity, and oxygen levels. Additionally, ensure that ERT members know | |
| where the equipment is stored, can access it, and are trained on its proper use. (Section 4.4.1: Entry | |
| into Potentially Explosive Atmosphere) | |
| • Evaluating high-hazard areas, including PSM covered processes, to determine whether detectors and | |
| alarms are necessary to identify chemical releases (or other types of emergencies). Additionally, | |
| consider equipping high-hazard areas with surveillance technology to identify personnel in the field. | |
| (Section 4.4.2: No Technology to Locate Missing Workers) | |
| • Developing and implementing written policy and procedures to update emergency response plan | |
| documents when hazards are identified. For example, personnel can identify these types of hazards in | |
| process hazard analyses, facility siting studies, management of change reviews, and incident | |
| investigations. Changes to emergency planning documents should be effectively communicated to the | |
| Page 125 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| site ERT as soon as possible after identifying the hazard. (Section 4.4.3: Unrecognized | |
| Manufacturing Building Collapse Hazard) | |
| • Ensuring that emergency response planning accounts for difficulties in conducting response efforts, | |
| including (1) maps included in emergency response plans to show the layout of buildings containing | |
| hazardous chemicals, for use by emergency responders and to aid evacuation and rescue efforts; (2) | |
| coordination of periodic (at least annual) site tours for plant and external emergency responders; (3) | |
| training emergency responders to help ensure familiarity with facility access points, hazards, emergency | |
| response issues, and site or facility layout; and (4) building teamwork by having members (from the | |
| different companies) of the ERT field train (by conducting drills) together when practicable. (Section | |
| 4.5: Difficulties Navigating Manufacturing Building) | |
| • Assigning knowledgeable personnel the responsibility to analyze process data to assess the source, | |
| scope, and magnitude of any incident. (Section 4.6: No Analysis of Process Data to Identify Source | |
| of Leak) | |
| • Training emergency response team members to (1) physically designate the hot zone; (2) communicate | |
| the location of the hot zone and entry control points to all personnel assisting with the emergency | |
| response, including operations personnel; and (3) control entry and exit points of the hot zone. (Section | |
| 4.7: Inadequate Control of Hot Zone) | |
| • Addressing in the emergency response plan how to characterize (including size, concentration, location, | |
| and direction of release) hazardous chemical releases and providing guidance on how and where people | |
| should take protective action (e.g., sheltering-in-place) in the event of a chemical release. (Section | |
| 4.8.1: Release Modeling) | |
| • Developing a procedure in the emergency response plan to effectively monitor for hazardous gases | |
| along the fence line at chemical facilities during the release to help workers understand and clearly | |
| communicate the extent of a release. (Section 4.8.4: Air Monitoring) | |
| In addition, provide a copy of the emergency response plan to the Emergency Response Team and their local | |
| union representatives. | |
| LOCAL 900C OF THE INTERNATIONAL CHEMICAL WORKERS UNION COUNCIL | |
| (ICWUC) OF THE UNITED FOOD AND COMMERCIAL WORKERS (UFCW) a | |
| 2015-01-I-TX-R9 | |
| a The union members at the DuPont La Porte facility were represented by the (ICWUC) of the (UFCW) and Local 900C. | |
| Page 126 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Work together with DuPont to develop and implement the emergency response plan described in | |
| Recommendation R8 (2015-01-I-TX-R8). | |
| Page 127 | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| REFERENCES | |
| [1] | |
| [2] | |
| [3] | |
| [4] | |
| [5] | |
| [6] | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "DuPont La Porte, Texas Chemical Facility | |
| Toxic Chemical Release: Interim Recommendations," 30 September 2015. [Online]. Available: | |
| https://www.csb.gov/assets/1/20/dupont_la_porte_interim_recommendations_2015-09-30_final1.pdf?15526. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "DuPont LaPorte Facility Toxic Chemical | |
| Release," [Online]. Available: http://www.csb.gov/dupont-laporte-facility-toxic-chemical-release-/. | |
| U.S. Environmental Protection Agency (USEPA), "List of Regulated Substances under the Risk | |
| Management Plan (RMP) Program," [Online]. Available: https://www.epa.gov/rmp/list-regulated- | |
| substances-under-risk-management-plan-rmp-program. [Accessed 2017 August 28]. | |
| K. Baker, "DuPont Closing Texas Plant Where 4 Died," The News Journal, 1 April 2016. [Online]. | |
| Available: https://www.usatoday.com/story/money/2016/04/01/dupont-closing-texas-plant-where-4- | |
| died/82512270/. [Accessed 29 June 2017]. | |
| DuPont, "Form 8-K," 31 March 2016. [Online]. Available: | |
| https://www.sec.gov/Archives/edgar/data/30554/000003055416000115/dd33116form8-k.htm. | |
| Center for Chemical Process Safety (CCPS), Continuous Monitoring for Hazardous Material Releases, | |
| CCPS/AIChE, 2009. | |
| [7] | |
| DuPont, "EPA RMP Submission for EPA Facility ID: 100000148912 La Porte Plant," 2012. | |
| [8] | |
| [9] | |
| [10] | |
| Center for Chemical Process Safety (CCPS), Guidelines for Technical Planning for On-Site Emergencies, | |
| 1995. | |
| National Fire Protection Association (NFPA), "NFPA 1911: Standard for the Inspection, Maintenance, | |
| Testing, and Retirement of In-Service Emergency Vehicles," 2017. [Online]. Available: | |
| http://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and- | |
| standards/detail?code=1911. | |
| National Fire Protection Association (NFPA), "NFPA 472: Standard for Competence of Responders to | |
| Hazardous Materials/Weapons of Mass Destruction Incidents," 2018. [Online]. Available: | |
| http://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and- | |
| standards/detail?code=472. [Accessed 26 12 2017]. | |
| [11] | |
| National Fire Protectioon Association (NFPA), "NFPA 1620: Standard for Pre-Incident Planning," 2015. | |
| [Online]. Available: http://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and- | |
| standards/detail?code=1620. [Accessed 29 December 2017]. | |
| Page 128 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [12] | |
| [13] | |
| [14] | |
| [15] | |
| [16] | |
| [17] | |
| [18] | |
| [19] | |
| [20] | |
| [21] | |
| [22] | |
| U.S. Department of Transportation (USDOT), "2016 Emergency Response Guidebook," 2016. [Online]. | |
| Available: https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/docs/ERG2016.pdf. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "OSHABrief | |
| - Hazard Communication Standard: Safety Data Sheets," [Online]. Available: | |
| https://www.osha.gov/Publications/OSHA3514.html. [Accessed 10 Jan 2018]. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "DuPont Corporation Toxic Chemical | |
| Releases," [Online]. Available: http://www.csb.gov/dupont-corporation-toxic-chemical-releases/. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "E.I. DuPont De Nemours Co. Fatal | |
| Hotwork Explosion," [Online]. Available: https://www.csb.gov/e-i-dupont-de-nemours-co-fatal-hotwork- | |
| explosion/. | |
| Center for Chemical Process Safety (CCPS), "Process Safety Glossary - Process Safety Management | |
| Systems," [Online]. Available: https://www.aiche.org/ccps/resources/glossary/process-safety- | |
| glossary/process-safety-management-systems. [Accessed 29 May 2019]. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "OSHA | |
| Celebrates 40 years of accomplishments in the Workplace," 2011. [Online]. Available: | |
| https://www.osha.gov/osha40/OSHATimeline.pdf. [Accessed 25 September 2018]. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "OSHA | |
| 3132: Process Safety Management," 2000. [Online]. Available: | |
| https://www.osha.gov/Publications/osha3132.html. [Accessed 29 March 2018]. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Process | |
| Safety Management Guidelines for Compliance," 1993. [Online]. Available: | |
| https://www.osha.gov/Publications/osha3133.html. [Accessed 31 August 2017]. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Inspection: | |
| 310260567 - Dupont Packaging & Industrial Polymers," [Online]. Available: | |
| https://www.osha.gov/pls/imis/establishment.inspection_detail?id=310260567. [Accessed 18 March 2019]. | |
| K. Moran, "DuPont plant in La Porte releases acidic compound," 26 January 2007. [Online]. Available: | |
| https://www.chron.com/news/houston-texas/article/DuPont-plant-in-La-Porte-releases-acidic-compound- | |
| 1805747.php. [Accessed 18 March 2019]. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Deaths of | |
| four workers prompts deeper look at DuPont Safety Practices," 9 July 2015. [Online]. Available: | |
| https://www.osha.gov/news/newsreleases/region6/07092015. [Accessed 25 September 2018]. | |
| Page 129 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [23] | |
| [24] | |
| [25] | |
| [26] | |
| [27] | |
| [28] | |
| [29] | |
| [30] | |
| [31] | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Preamble to | |
| Process Safety Management of Highly Hazardous Chemicals; Explosives and Blasting Agents.," 24 | |
| February 1992. [Online]. Available: https://www.osha.gov/laws-regs/federalregister/1992-02-24. [Accessed | |
| 29 May 2019]. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Regulatory Report: Chevron Richmond | |
| Refinery Pipe Rupture and Fire," 10 2014. [Online]. Available: https://www.csb.gov/chevron-refinery-fire/. | |
| [Accessed 29 10 2018]. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Drilling Rig Explosion and Fire at the | |
| Macondo Well Report: Volume 4," 17 April 2016. [Online]. Available: https://www.csb.gov/macondo- | |
| blowout-and-explosion/. [Accessed 20 November 2018]. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Process Safety Management for the 21st | |
| Century," [Online]. Available: https://www.csb.gov/recommendations/most-wanted-program-modernize-us- | |
| process-safety-management-regulations/. [Accessed 25 September 2018]. | |
| U.S. Environmental Protection Agency (USEPA), "The Origins of EPA," [Online]. Available: | |
| https://www.epa.gov/history/origins-epa. [Accessed 3 October 2018]. | |
| U.S. Environmental Protection Agency (USEPA), "General Guidance on Risk Management Program for | |
| Chemical Accident Prevention (40 CFR Part 68): Chapter 9," March 2009. [Online]. Available: | |
| https://www.epa.gov/sites/production/files/2013-11/documents/chap-09-final.pdf. [Accessed 12 October | |
| 2018]. | |
| U.S. Environmental Protection Agency (USEPA), "Risk Management Plan (RMP) Rule Overview," | |
| [Online]. Available: https://www.epa.gov/rmp/risk-management-plan-rmp-rule-overview. [Accessed 3 | |
| October 2018]. | |
| U.S. Environmental Protection Agency (USEPA), "EPA and Justice Department Reach $3.1 Million | |
| Settlement with DuPont for Alleged Chemical Accident Prevention Violations," 26 July 2018. [Online]. | |
| Available: https://www.epa.gov/newsreleases/epa-and-justice-department-reach-31-million-settlement- | |
| dupont-alleged-chemical-accident. [Accessed 14 November 2018]. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "U.S. Chemical Safety and Hazard | |
| Investigation Board’s (CSB’s) response to the EPA’s July 31, 2014 Request for Information (at 79 Fed. Reg. | |
| 44604) on potential revisions to its Risk Management Program regulations and program," 29 October 2014. | |
| [Online]. Available: https://www.csb.gov/assets/1/6/epa_rfi2.pdf. [Accessed 3 October 2018]. | |
| [32] | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "CSB’s response to the EPA’s March 14, | |
| 2016 Proposed Rule, “Accidental Release Prevention Requirements: Risk Management Programs Under the | |
| Clean Air Act, Section 112(r)(7)” (Docket No. EPA-HQ-QEM-2015-0725)," 10 May 2016. [Online]. | |
| Page 130 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [33] | |
| [34] | |
| [35] | |
| [36] | |
| [37] | |
| [38] | |
| [39] | |
| [40] | |
| [41] | |
| [42] | |
| Available: https://www.csb.gov/assets/1/6/csb_comments_epa-hq-oem-2015-0725_51020161.pdf. [Accessed | |
| 3 October 2018]. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Drivers of Critical Chemical Safety | |
| Change," [Online]. Available: https://www.csb.gov/recommendations/mostwanted/. [Accessed 29 June | |
| 2017]. | |
| U.S. Environmental Protection Agency (USEPA), "Risk Management Plan (RMP) Delay Rule Vacatur," | |
| [Online]. Available: https://www.epa.gov/rmp/risk-management-plan-rmp-delay-rule-vacatur. [Accessed 15 | |
| October 2018]. | |
| U.S. Environmental Protection Agency (USEPA), "Proposed Risk Management Program (RMP) | |
| Reconsideration Rule," [Online]. Available: https://www.epa.gov/rmp/proposed-risk-management-program- | |
| rmp-reconsideration-rule. [Accessed 26 February 2019]. | |
| Chemtrec, "History," [Online]. Available: https://www.chemtrec.com/about-chemtrec/who-we-are/history. | |
| [Accessed 3 October 2018]. | |
| American Chemistry Council, "About the American Chemistry Council," [Online]. Available: | |
| https://www.americanchemistry.com/About/. [Accessed 2 November 2017]. | |
| American Chemistry Council, "Responsible Care Program Elements," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/ResponsibleCare/Responsible-Care-Program-Elements.aspx. | |
| [Accessed 06 Oct 2017]. | |
| Chemistry Industry Association of Canada, "A Brief History of Responsible Care," [Online]. Available: | |
| https://web.archive.org/web/20180610195147/http://www.canadianchemistry.ca/responsible_care/index.php/ | |
| en/responsible-care-history. [Accessed 10 Oct 2017]. | |
| American Chemistry Council, "30 Years Responsible Care: Milestones and Achievements," 2018. [Online]. | |
| Available: https://responsiblecare.americanchemistry.com/rc/media/30-Years-Responsible-Care-Milestones- | |
| Achievements.pdf. | |
| American Chemistry Council, "Responsible Care Management System: Technical Specification," 1 May | |
| 2013. [Online]. Available: https://responsiblecare.americanchemistry.com/Responsible-Care-Program- | |
| Elements/Management-System-and-Certification/RCMS-Technical-Specifications.pdf. | |
| American Chemistry Council, "Responsible Care Third-Party Audit Requirement Requirements for ACC | |
| Members and Responsible Care Partners," October 2017. [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/Program-Elements/Management-System-and- | |
| Certification/RC501.pdf. [Accessed 29 March 2018]. | |
| Page 131 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [43] | |
| [44] | |
| [45] | |
| [46] | |
| [47] | |
| [48] | |
| [49] | |
| [50] | |
| [51] | |
| [52] | |
| [53] | |
| American Chemistry Council , "Responsible Care Guiding Principles," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/Responsible-Care-Program-Elements/Guiding- | |
| Principles/PDF-Responsible-Care-Guiding-Principles.pdf. [Accessed 2 March 2018]. | |
| Amercian Chemistry Council, "Responsible Care Process Safety Code of Management Practices," 9 | |
| November 2012. [Online]. Available: https://responsiblecare.americanchemistry.com/Responsible-Care- | |
| Program-Elements/Process-Safety-Code/Responsible-Care-Process-Safety-Code-PDF.pdf. [Accessed 26 | |
| March 2018]. | |
| American Chemistry Council and National Association of Chemical Distributors, "A Comparison of ACC | |
| Responsible Care and NACD Responsible Distribution Initiatives," 2015. [Online]. Available: | |
| https://www.nacd.com/pub/?id=35145BAD-93AE-F152-9978-FD6AE231C5F8. [Accessed 27 May 2019]. | |
| American Chemistry Council, "Accountability & Impacts," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/AccountabilityandImpacts.html. [Accessed 20 November | |
| 2018]. | |
| American Chemistry Council, "Process Safety Code," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/Process-Safety-Code/. [Accessed 30 May 2019]. | |
| American Chemistry Council, "American Chemistry Council Letter to Center for Effective Government," 16 | |
| October 2015. [Online]. Available: https://www.foreffectivegov.org/sites/default/files/blowing-smoke/acc- | |
| response.pdf. [Accessed 10 December 2017]. | |
| American Petroleum Institute (API), API Recommended Practice 754 - Process Safety Indicators for the | |
| Refining and Petrochemical Industries, 2016. | |
| Centers for Disease Control and Prevention, "NIOSH Pocket Guide to Chemical Hazards: Methyl | |
| mercaptan," 11 April 2016. [Online]. Available: https://www.cdc.gov/niosh/npg/npgd0425.html. [Accessed | |
| 29 June 2017]. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Methyl | |
| Mercaptan," [Online]. Available: https://www.osha.gov/chemicaldata/chemResult.html?recNo=560. | |
| [Accessed 2 March 2018]. | |
| Center for Chemical Process Safety (CCPS), Guidelines for Risk Based Process Safety, Hoboken, NJ: | |
| Wiley, 2007. | |
| J. A. Klein, "Two Centuries of Process Safety at DuPont," Process Safety Progress, vol. 28, no. 2, pp. 114- | |
| 122, June 2009. | |
| Page 132 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [54] | |
| [55] | |
| [56] | |
| [57] | |
| [58] | |
| [59] | |
| [60] | |
| [61] | |
| [62] | |
| DuPont Sustainable Solutions, "Quick 4-Step Review of Process Safety Management," [Online]. Available: | |
| http://www2.dupont.com/DuPont_Sustainable_Solutions/en_US/assets/downloads/Quick_4- | |
| Step_Review_Sheet.pdf. [Accessed 25 September 2018]. | |
| DuPont Sustainable Solutions, "Developing a Robust PSM Framework at DuPont," February 2013. [Online]. | |
| Available: http://ips.se/files/pages/59/ips-david-guss-dupont-februari-2013.pdf. [Accessed 7 September | |
| 2018]. | |
| Center for Chemical Process Safety (CCPS), Essential Practices for Creating, Strengthening, and Sustaining | |
| Process Safety Culture, Hoboken, NJ: John Wiley & Sons, Inc., 2018. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "CSB Urgent Recommendation BP Global | |
| Executive Board of Directors," 17 August 2005. [Online]. Available: | |
| https://www.csb.gov/assets/1/20/bp_recs.pdf?13851. | |
| Baker Panel, "The Report of The BP U.S. Refineries Independent Safety Review Panel," January 2007. | |
| [Online]. Available: https://www.csb.gov/assets/1/20/baker_panel_report1.pdf?13842. [Accessed 27 | |
| December 2017]. | |
| DuPont, "Relative Culture Strength: A Key to Sustainable World-Class Safety Performance," 2011. | |
| [Online]. Available: http://www.dupont.com/content/dam/dupont/products-and-services/consulting-services- | |
| and-process-technologies/consulting-services-and-process-technologies- | |
| landing/documents/Sustainable_World-Class_Safety_Performance.pdf. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Investigation Report: Refinery Explosion | |
| and Fire: BP, Texas City, March 23, 2005," March 2007. [Online]. Available: https://www.csb.gov/bp- | |
| america-refinery-explosion/. [Accessed 27 December 2017]. | |
| U.S. Chemical Safety and Hazard Identification Board (USCSB), "Investigation Report Volume 3: Drilling | |
| Rig Explosion and Fire at the Macondo Well," 17 April 2016. [Online]. Available: | |
| https://www.csb.gov/macondo-blowout-and-explosion/. [Accessed 29 May 2019]. | |
| U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Tesoro Martinez Refinery: Process Safety | |
| Culture Case Study: Martinez, California: February 12, 2014 and March 10, 2014 Sulfuric Acid Release | |
| Incidents," 2016. [Online]. Available: | |
| https://www.csb.gov/assets/1/20/tesoro_martinez_final_case_study1.pdf?15674. [Accessed 19 February | |
| 2017]. | |
| [63] | |
| Center for Chemical Process Safety (CCPS), Conduct of Operations and Operational Discipline-For | |
| Improving Process Safety in Industry, Hoboken, New Jersey: CCPS/John Wiley & Sons, Inc., 2011. | |
| Page 133 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [64] | |
| [65] | |
| [66] | |
| [67] | |
| [68] | |
| [69] | |
| [70] | |
| [71] | |
| [72] | |
| [73] | |
| [74] | |
| [75] | |
| D. A. Wiegmann, H. Zhang, T. L. von Thaden, G. Sharma and A. M. Gibbons, "Safety Culture: An | |
| Integrative Review," The International Journal of Aviation Psychology, vol. 14, no. 2, pp. 117-134, 2004. | |
| Contra Costa Health Services, "Industrial Safety Ordinance Guidance Document, Section F-Safety Culture | |
| Assessments," 15 June 2011. [Online]. Available: http://cchealth.org/hazmat/pdf/iso/section_f.pdf. | |
| [Accessed 11 01 2018]. | |
| Center for Chemical Process Safety (CCPS), Guidelines for Auditing Process Safety Management Systems, | |
| New York, New York: Wiley, 2011. | |
| A. Hopkins, "Why Safety Cultures Don't Work," [Online]. Available: | |
| http://www.futuremedia.com.au/docs/Why_Safety_Cultures_Don't_Work.pdf. [Accessed 26 September | |
| 2018]. | |
| DuPont, "DuPont Process Safety Management," [Online]. Available: | |
| http://www2.dupont.com/DuPont_Safety_Resources/en_SG/assets/downloads/PSM%20Brochure.pdf. | |
| [Accessed 26 September 2018]. | |
| J. A. Klein, "A Revised Program for Operational Discipline," Process Safety Progress, vol. 27, no. 1, pp. 58- | |
| 65, March 2008. | |
| Center for Chemical Process Safety (CCPS), Guidelines for Auditing Process Safety Management Systems, | |
| Hoboken: Wiley, 2011. | |
| U.S. Chemical Safety and Hazard Identifcation Board (USCSB), "Williams Geismar Olefins Plant: Reboiler | |
| Rupture and Fire: Geismar, Louisiana," 2013. [Online]. Available: https://www.csb.gov/williams-olefins- | |
| plant-explosion-and-fire-/. [Accessed 29 May 2019]. | |
| A. H. a. R. D. Mohammadi, "Equilibrium Data of Sulfur Dioxide and Methyl Mercaptan Clathrate | |
| Hydrates," Journal of Chemical & Engineering Data, vol. 56, pp. 1666-1668, 2011. | |
| Georgia Tech Applied Research Corporation, "Process Safety Management of Highly Hazardous & | |
| Explosive Chemicals Module 4: PSM Standard Operating Procedures," [Online]. Available: | |
| https://www.osha.gov/harwoodgrants/grantmaterials/fy2008/sh-17811-08. [Accessed 29 5 2019]. | |
| K. W. Morrison, "What's your reward? The debate over incentive programs," 1 April 2011. [Online]. | |
| Available: http://www.safetyandhealthmagazine.com/articles/5501-whats-your-reward. [Accessed 10 | |
| January 2018]. | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Employer | |
| Safety Incentive and Disincentive Policies and Practices," 12 March 2012. [Online]. Available: | |
| https://www.osha.gov/as/opa/whistleblowermemo.html. [Accessed 2015]. | |
| Page 134 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [76] | |
| [77] | |
| [78] | |
| [79] | |
| [80] | |
| [81] | |
| [82] | |
| [83] | |
| [84] | |
| U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Clarification | |
| of OSHA’s Position on Workplace Safety Incentive Programs and Post-Incident Drug Testing Under 29 | |
| C.F.R. § 1904.35(b)(1)(iv)," 11 October 2018. [Online]. Available: https://www.osha.gov/laws- | |
| regs/standardinterpretations/2018-10-11. [Accessed 26 October 2018]. | |
| DuPont Sustainable Solutions, "The DuPont Bradley Curve (video)," 5 November 2015. [Online]. Available: | |
| https://www.youtube.com/watch?v=tMoVi7vxkb0. [Accessed 17 November 2017]. | |
| DuPont, "DuPont Bradley Curve," 2017. [Online]. Available: http://www.dupont.com/products-and- | |
| services/consulting-services-process-technologies/brands/sustainable-solutions/sub-brands/operational-risk- | |
| management/uses-and-applications/bradley-curve.html. [Accessed 17 November 2017]. | |
| Center for Chemical Process Safety (CCPS), in RECOGNIZING CATASTROPHIC INCIDENT WARNING | |
| SIGNS IN THE PROCESS INDUSTRIES, Hoboken, New Jersey: Wiley, 2012. | |
| Agency for Toxic Substances and Disease Registry (ATSDR), "Methyl Mercaptan," [Online]. Available: | |
| https://www.atsdr.cdc.gov/MHMI/mmg139.pdf. [Accessed 29 June 2017]. | |
| Center for Chemical Process Safety (CCPS), Guidelines for Fire Protection in Chemical, Petrochemical, and | |
| Hydrocarbon Processing Facilities, New York, New York: American Institute of Chemical Engineers, 2003. | |
| American Industrial Hygiene Association (AIHA), "Current ERPG Values," 2014. [Online]. Available: | |
| https://www.aiha.org/get- | |
| involved/AIHAGuidelineFoundation/EmergencyResponsePlanningGuidelines/Documents/2014%20ERPG% | |
| 20Values.pdf. | |
| DowDuPont, "About DowDuPont," 2017. [Online]. Available: http://www.dow-dupont.com/about-dow- | |
| dupont/default.aspx. [Accessed 6 Oct 2017]. | |
| RAE Systems by Honeywell, "Technical Note TN-156, Correction Factors for Combustible Gas (LEL) | |
| Sensors," [Online]. Available: | |
| http://www.raesystems.com/sites/default/files/content/resources/Technical%20Note%20156%20Correction | |
| %20Factors%20For%20Combustible%20Gas%20LEL%20Sensorsnr%2002%2016.pdf. [Accessed 06 Oct | |
| 2017]. | |
| [85] | |
| I. Sutton, Plant Design and Operations, 2nd ed., Cambridge, MA: Gulf Professional Publishing, 2017. | |
| [86] | |
| F. Cavender, S. Phillips and M. Holland, "Development of Emergency Response Planning Guidelines | |
| (ERPGs)," Journal of Medical Toxicology, vol. 4, no. 2, pp. 127-131, June 2008. | |
| Page 135 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [87] | |
| [88] | |
| American Chemistry Council, "ACC Responsible Care Management System and Certification Overview," | |
| 18 March 2003. [Online]. Available: | |
| https://texasiof.ceer.utexas.edu/texasshowcase/pdfs/presentations/b5/bstutts.pdf. [Accessed 10 Oct 2017]. | |
| International Council of Chemical Associations, "2015 Responsible Care Status Report," [Online]. | |
| Available: https://www.icca-chem.org/wp-content/uploads/2015/09/2015-Responsible-Care-Status- | |
| Report.pdf. [Accessed 2 November 2017]. | |
| [89] | |
| International Council of Chemical Associations, "Responsible Care: The Quest for Performance Excellence," | |
| [Online]. Available: https://www.icca-chem.org/responsible-care/. | |
| [90] M. Speegle, Safety, Health, and Environmental Concepts for the Process Industry, 2nd ed., New York: | |
| Delmar, 2013, p. 58. | |
| [91] W. L. Frank, "Process safety culture in the CCPS risk based process safety model," Process Safety Progress, | |
| vol. 26, no. 3, pp. 203-208, September 2007. | |
| [92] | |
| [93] | |
| [94] | |
| [95] | |
| [96] | |
| American Chemistry Council, "Responsible Care Third-Party Audit Requirement," 10 2017. [Online]. | |
| Available: https://responsiblecare.americanchemistry.com/Program-Elements/Management-System-and- | |
| Certification/RC501.pdf. [Accessed 6 12 2017]. | |
| CCOHS, "Methylene Chloride," 3 January 2017. [Online]. Available: | |
| http://www.ccohs.ca/oshanswers/chemicals/chem_profiles/methylene.html. [Accessed 9 December 2017]. | |
| DuPont, "DuPont Lannate SP Insecticide," 14 1 2016. [Online]. Available: | |
| http://www.dupont.ca/content/dam/dupont/tools-tactics/crop/canada-label-msds/documents/cp_PSD- | |
| 68_Lannate_130000000505_20160114_MSDS_E.pdf. [Accessed 14 12 2017]. | |
| U.S. National Library of Medicine, "Haz-Map Methyl Mercaptan," [Online]. Available: | |
| https://hazmap.nlm.nih.gov/category-details?id=192&table=copytblagents. [Accessed 14 12 2017]. | |
| P. Hasenmeier, "The History of Firefighter Personal Protective Equipment," Fire Engineering , 6 6 2008. | |
| [Online]. Available: http://www.fireengineering.com/articles/2008/06/the-history-of-firefighter-personal- | |
| protective-equipment.html. [Accessed 14 12 2017]. | |
| [97] | |
| The Pro Board, "The Pro Board," [Online]. Available: http://www.theproboard.org/. [Accessed 15 12 2017]. | |
| [98] | |
| National Fire Protection Association (NFPA), "NFPA 1911: Standard for the Inspection, Maintenance, | |
| Testing, and Retirement of In-Service Emergency Vehicles," 2012. [Online]. Available: | |
| http://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and- | |
| standards/detail?code=1911&year=2012. [Accessed 28 December 2017]. | |
| [99] | |
| SAFER Systems, "SAFER Trace," [Online]. Available: https://www.safersystem.com/products/safer-trace/. | |
| [Accessed 29 December 2017]. | |
| Page 136 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [100] Weather Underground, "Ellington Field, TX," [Online]. Available: | |
| https://www.wunderground.com/history/airport/KEFD/2018/1/8/DailyHistory.html?cm_ven=localwx_histor | |
| y. [Accessed 08 01 2018]. | |
| [101] American Society of Mechanical Engineers (ASME), Boiler & Pressure Vessel Code, VIII Rules for | |
| Construction of Pressure Vessels, Division 1, 2013. | |
| [102] American Petroleum Institute (API), API 521 - Pressure-relieving and Depressuring Systems, 6th ed., 2014. | |
| [103] National Fire Protection Association (NFPA), "NFPA 600: Standard on Facility Fire Brigades," 2015. | |
| [Online]. Available: http://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and- | |
| standards/detail?code=600. [Accessed 29 December 2017]. | |
| [104] American Chemistry Council, "Safety," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/ResponsibleCare/Performance-Results/Safety/. [Accessed 29 | |
| March 2018]. | |
| [105] Dow, "DowDuPont Merger Successfully Completed," 1 September 2017. [Online]. Available: | |
| https://www.dow.com/en-us/news/press-releases/dowdupont-merger-successfully-completed. [Accessed 4 | |
| April 2018]. | |
| [106] National Fire Protection Association (NFPA), "NFPA 1: Fire Code," 2018. [Online]. Available: | |
| https://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and- | |
| standards/detail?code=1. [Accessed 12 April 2018]. | |
| [107] DuPont, "DuPont Completes Spin-off of The Chemours Company," 1 July 2015. [Online]. Available: | |
| http://www.dupont.com/corporate-functions/media-center/press-releases/dupont-completes-spin-off-of-the- | |
| chemours-company.html. [Accessed 1 May 2018]. | |
| [108] Chemours, "Creating Higher Value Chemistry: The Chemours Company 2015 Annual Report," [Online]. | |
| Available: https://s21.q4cdn.com/411213655/files/doc_financials/annual_reports/Chemours-2015-Annual- | |
| Report.pdf. [Accessed 1 May 2018]. | |
| [109] Center for Chemical Process Safety (CCPS), Inherently Safer Chemical Processes - A Life Cycle Approach, | |
| 2nd ed., New York: John Wiley & Sons, Inc., 2009. | |
| [110] Center for Chemical Process Safety (CCPS), "Emergency Relief Device," [Online]. Available: | |
| https://www.aiche.org/ccps/resources/glossary/process-safety-glossary/emergency-relief-device. [Accessed 7 | |
| May 2018]. | |
| [111] Eastman Chemical Company, "An Overview of Pressure Relief Devices," 16 September 2014. [Online]. | |
| Available: | |
| https://www.google.com/url?sa=t&rct=j&q=&esrc=s&source=web&cd=5&ved=0ahUKEwj1q5yO9fXaAhU | |
| Page 137 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| C_4MKHesZAFcQFghVMAQ&url=https%3A%2F%2Fwww.aiche.org%2Fsites%2Fdefault%2Ffiles%2Fco | |
| mmunity%2F160956%2Faiche-community-site-files%2F198496%2Faichemeeting9162014.pptx&us. | |
| [112] S. S. Murnane, A. H. Lehocky and P. D. Owens, Odor Thresholds for Chemicals with Established | |
| Occupational Health Standards, 2nd ed., Falls Church, Virginia: American Industrial Hygiene Association | |
| (AIHA), 2013. | |
| [113] Chemical Processing, "DuPont Sustainable Solutions Celebrates 50th With Global Panel Series," 13 April | |
| 2018. [Online]. Available: https://www.chemicalprocessing.com/industrynews/2018/dupont-sustainable- | |
| solutions-celebrates-50th-with-global-panel-series-2/. [Accessed 6 September 2018]. | |
| [114] DuPont Sustainable Solutions, "DuPont Sustainable Solutions," [Online]. Available: | |
| http://www.dupont.com/products-and-services/consulting-services-process-technologies/brands/about- | |
| us.html. [Accessed 6 September 2018]. | |
| [115] National Safety Council, "Robert W. Campbell Award," [Online]. Available: | |
| https://www.campbellaward.org/winners/. [Accessed 6 September 2018]. | |
| [116] DuPont Sustainable Solutions , "Felt Leadership Workshop," [Online]. Available: | |
| https://www.training.dupont.com/safety-workshops/felt-leadership. [Accessed 18 September 2018]. | |
| [117] DuPont Sustainable Solutions, "DuPont Sustainable Solutions Can Help Create Lasting Improvements to | |
| Your Process Safety Management Systems," [Online]. Available: | |
| http://www2.dupont.com/Sustainable_Solutions/en_US/assets/downloads/psm_infographic/PSMOverview_ | |
| SustainableImprovements.pdf. [Accessed 26 September 2018]. | |
| [118] DuPont Sustainable Solutions, "Developing a Robust PSM Framework at DuPont," February 2013. [Online]. | |
| Available: http://ips.se/files/pages/59/ips-david-guss-dupont-februari-2013.pdf. [Accessed 26 September | |
| 2018]. | |
| [119] | |
| ICIS, "US CMA Changing Name to American Chemistry Council," 09 Jun 2000. [Online]. Available: | |
| https://www.icis.com/resources/news/2000/06/09/114009/us-cma-changing-name-to-american-chemistry- | |
| council/. [Accessed 30 June 2017]. | |
| [120] Code Red Safety, "High Angle Resccue," [Online]. Available: https://coderedsafety.com/rescue- | |
| services/high-angle-rescue/. [Accessed 4 October 2018]. | |
| [121] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Investigation Report: E.I. DuPont DE | |
| Nemours & Co. Inc.: Belle, West Virginia," September 2011. [Online]. Available: | |
| https://www.csb.gov/assets/1/20/csb%20final%20report.pdf?13966. | |
| Page 138 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [122] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Case Study: E.I. DuPont de Nemours & | |
| Co Inc.: Buffalo, New York," [Online]. Available: https://www.csb.gov/e-i-dupont-de-nemours-co-fatal- | |
| hotwork-explosion/. | |
| [123] RAE Systems, "MultiRAE," [Online]. Available: https://www.raesystems.com/products/multirae. [Accessed | |
| 23 October 2018]. | |
| [124] RAE Systems, "QRAE 3," [Online]. Available: http://www.raesystems.com/products/qrae-3. [Accessed 15 | |
| 12 2017]. | |
| [125] Drager, "Drager-Tubes & accuro-Pump," [Online]. Available: | |
| https://www.draeger.com/Products/Content/tubes-accuro-pump-pi-us.pdf. [Accessed 06 Oct 2017]. | |
| [126] American Chemistry Council, "www.regulations.gov," 13 May 2016. [Online]. Available: | |
| https://www.regulations.gov/document?D=EPA-HQ-OEM-2015-0725-0537. [Accessed 4 December 2017]. | |
| [127] American Chemistry Council, "Safety," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/ResponsibleCare/Performance-Results/Safety/. [Accessed 29 | |
| 10 2018]. | |
| [128] American Chemistry Council, "Security Code," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/Security-Code/. [Accessed 6 November 2018]. | |
| [129] American Chemistry Council, "Product Safety Code," [Online]. Available: | |
| https://responsiblecare.americanchemistry.com/Product-Safety-Code/. [Accessed 6 November 2018]. | |
| [130] National Center for Biotechnology Information, "Acute Exposure Guideline Levels for Selected Airborne | |
| Chemicals: Volume 15: 2. Methyl Mercaptan Acute Exposure Guideline Levels," [Online]. Available: | |
| https://www.ncbi.nlm.nih.gov/books/NBK201324/. [Accessed 14 November 2018]. | |
| [131] | |
| I. Sutton, Plant Design and Operations, Ashland: Elsevier, 2017. | |
| [132] USFEMA, "National Incident Management System," [Online]. Available: https://www.fema.gov/national- | |
| incident-management-system. [Accessed 21 February 2019]. | |
| [133] Oxford Dictionary, "Oleum," [Online]. Available: https://en.oxforddictionaries.com/definition/oleum. | |
| [Accessed 18 March 2019]. | |
| [134] DowDuPont, "DowDuPont," [Online]. Available: http://www.dow-dupont.com/home/default.aspx. | |
| [Accessed 26 April 2019]. | |
| [135] M. P. Bailey, "DuPont's Sustainable Solutions Business to Become Independent Consulting Firm," Chemical | |
| Engineering Essentials for the CPI Professional, 19 February 2019. [Online]. Available: | |
| Page 139 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| https://www.chemengonline.com/duponts-sustainable-solutions-business-to-become-independent- | |
| consulting-firm/. [Accessed 26 April 2019]. | |
| [136] National Fire Protection Association (NFPA), "NFPA 497: Recommended Practice for the Classification of | |
| Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in | |
| Chemical Process Areas," 2017. [Online]. Available: https://www.nfpa.org/codes-and-standards/all-codes- | |
| and-standards/list-of-codes-and-standards/detail?code=497. [Accessed 29 May 2019]. | |
| [137] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Docket No. EPA-HQ-OEM-2015-0725, | |
| Accidental Release Prevention," 20 July 2018. [Online]. Available: | |
| https://www.csb.gov/assets/1/6/csb_comments_epa_rmp_20180720.pdf. [Accessed 17 October 2018]. | |
| [138] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Board Order 22: Recommendations | |
| Program," [Online]. Available: https://www.csb.gov/assets/record/csb_board_order_022_final_20161.pdf. | |
| [139] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Board Order 40: Investigation Program," | |
| [Online]. Available: https://www.csb.gov/assets/record/board_order_040_approved_2_14_17.pdf. | |
| [140] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "BP American Refinery Explosion," | |
| [Online]. Available: https://www.csb.gov/bp-america-refinery-explosion/. [Accessed 15 May 2018]. | |
| [141] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "CSB Letter to EPA: Re: Docket Number | |
| EPA-HQ-OAR-2010-0682," 28 October 2014. [Online]. Available: | |
| http://www.csb.gov/assets/1/7/EPA_Proposed_Rule_(Refineries)_10-28-2014.pdf. | |
| [142] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "CSB Letter to PHMSA: Attention: Docket | |
| No. PHMSA-2014-0099; Notice No. 14-11," 3 October 2014. [Online]. Available: | |
| https://www.csb.gov/assets/1/6/dot_erg__rfi10_1_1411.pdf. [Accessed 23 October 2018]. | |
| [143] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Docket No. EPA-HQ-OEM-2015-0725, | |
| Accidental Release Prevention Requirements: Risk Management Programs Unde the Clean Air Action, | |
| Section 112(r)(7)," 10 May 2016. [Online]. Available: https://www.csb.gov/assets/1/6/csb_comments_epa- | |
| hq-oem-2015-0725_51020161.pdf. [Accessed 17 October 2018]. | |
| [144] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Final Investigation Report: E.I. DuPont de | |
| Nemours & Co., Inc. Belle, West Virginia," September 2011. [Online]. Available: | |
| https://www.csb.gov/assets/1/20/csb%20final%20report.pdf?13966. [Accessed 7 October 2018]. | |
| [145] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Investigation Report Volume 3: Drilling | |
| Rig Explosion and Fire at the Macondo Well," 17 April 2016. [Online]. Available: | |
| https://www.csb.gov/macondo-blowout-and-explosion/. [Accessed 27 March 2018]. | |
| Page 140 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [146] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Investigation Report: Explosion and Fire: | |
| First Chemical Corporation," October 2003. [Online]. Available: | |
| https://www.csb.gov/assets/1/20/first_report.pdf?13794. | |
| [147] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Recommendations Status Change | |
| Summary: 2010-6-I-WV-R14," 10 April 2013. [Online]. Available: | |
| https://www.csb.gov/assets/recommendation/status_change_summary_dupont_corporate_r14.pdf. [Accessed | |
| 10 October 2018]. | |
| [148] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Reflections on Bhopal after Thirty Year," | |
| 1 December 2014. [Online]. Available: http://www.csb.gov/videos/reflections-on-bhopal-after-thirty-years/. | |
| [Accessed 2 November 2017]. | |
| [149] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Permissible | |
| Exposure Limits – Annotated Tables," [Online]. Available: https://www.osha.gov/dsg/annotated-pels/. | |
| [Accessed 9 May 2018]. | |
| [150] Center for Chemical Process Safety (CCPS), "CCPS Process Safety Glossary- Safe Work Practices," | |
| [Online]. Available: https://www.aiche.org/ccps/resources/glossary/process-safety-glossary/safe-work- | |
| practices. [Accessed 1 February 2017]. | |
| [151] U.S. Environmental Protection Agency (USEPA), "Chapter 8: Emergency Response Program," [Online]. | |
| Available: https://www.epa.gov/rmp/general-rmp-guidance-chapter-8-emergency-response-program. | |
| [Accessed 14 May 2018]. | |
| [152] U.S. Environmental Protection Agency (USEPA), "General Guidance on Risk Management Programs for | |
| Chemical Accident Prevention (40 CFR Part 68): Chapter 2: Applicability of Program Levels," [Online]. | |
| Available: https://www.epa.gov/sites/production/files/2013-10/documents/chap-02-final.pdf. [Accessed 3 | |
| October 2018]. | |
| [153] U.S. Environmental Protection Agency (USEPA), "Petroleum Refinery Fenceline Monitoring Stakeholder | |
| Engagement Webinar," 22 6 2016. [Online]. Available: https://www.epa.gov/sites/production/files/2016- | |
| 06/documents/state_local_tribal_webinar_june_2016.pdf. [Accessed 19 12 2017]. | |
| [154] U.S. Environmental Protection Agency (USEPA), "Petroleum Refinery Sector Risk and Technology Review | |
| and New Source Performance Standards (NSPS)," [Online]. Available: https://www.epa.gov/stationary- | |
| sources-air-pollution/petroleum-refinery-sector-risk-and-technology-review-and-new-source. [Accessed 19 | |
| 12 2017]. | |
| [155] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Citation and | |
| Notification of Penalty- Inspection Number: 1019650," 9 July 2015. [Online]. Available: | |
| https://www.osha.gov/ooc/citations/EIDuPontDeNemoursCo_1019650.pdf. [Accessed 21 February 2019]. | |
| Page 141 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| [156] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Hazard | |
| Communication 2012 - The Revised Standard and What Changes You Can Expect in the Workplace," 13 8 | |
| 2012. [Online]. Available: | |
| https://www.osha.gov/dsg/hazcom/schc_alliance_webinar_20120809/schc_alliance_webinar_20120809.pptx | |
| . [Accessed 19 12 2017]. | |
| [157] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Inspection | |
| Detail: 1019650.015," [Online]. Available: | |
| https://www.osha.gov/pls/imis/establishment.inspection_detail?id=1019650.015. [Accessed 21 February | |
| 2019]. | |
| [158] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), | |
| "Interpretation of 1904.35(b)(1)(i) and (iv)," 19 October 2016. [Online]. Available: | |
| https://www.osha.gov/recordkeeping/finalrule/interp_recordkeeping_101816.html. [Accessed 1 December | |
| 2017]. | |
| [159] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "OSHA | |
| Annotated Table Z-1," [Online]. Available: https://www.osha.gov/dsg/annotated-pels/tablez-1.html. | |
| [Accessed 9 May 2018]. | |
| [160] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "OSHA | |
| News Release - Region 6," 9 July 2015. [Online]. Available: | |
| https://www.osha.gov/news/newsreleases/region6/07092015. [Accessed 29 June 2017]. | |
| [161] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "OSHA: | |
| Inspection Detail 1008319.015," [Online]. Available: | |
| https://www.osha.gov/pls/imis/establishment.inspection_detail?id=1008319.015. [Accessed 21 February | |
| 2019]. | |
| [162] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Permissible | |
| Exposure Limits - Annotated Tables," [Online]. Available: https://www.osha.gov/dsg/annotated-pels/. | |
| [Accessed 27 December 2017]. | |
| [163] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Permissible | |
| Exposure Limits / OSHA Annotated Table Z-1," 2017. [Online]. Available: | |
| https://www.osha.gov/dsg/annotated-pels/tablez-1.html. [Accessed 27 December 2017]. | |
| [164] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "Proper | |
| protections could have saved four DuPont workers killed by gas," 14 May 2015. [Online]. Available: | |
| https://www.osha.gov/news/newsreleases/region6/05142015. [Accessed 21 February 2019]. | |
| [165] U.S. Federal Emergency Management Agency (USFEMA), "Risk-Based A Principal in Emergency | |
| Management," [Online]. Available: | |
| Page 142 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| https://training.fema.gov/hiedu/docs/principlesofem/principles%20of%20em%20-%20session%205%20- | |
| %20risk-based.ppt. [Accessed 9 May 2018]. | |
| [166] U.S. Department of Labor (USDOL) Occupational Safety and Health Administration (OSHA), "The | |
| Whistleblower Protection Programs," [Online]. Available: https://www.whistleblowers.gov/. [Accessed 12 | |
| April 2019]. | |
| [167] National Oceanic Atmospheric Association (NOAA), "Office of Response and Restoration: Emergency | |
| Response Planning Guidelines (ERPGs)," 29 June 2017. [Online]. Available: | |
| http://response.restoration.noaa.gov/oil-and-chemical-spills/chemical-spills/resources/emergency-response- | |
| planning-guidelines-erpgs.html. | |
| [168] U.S. Chemical Safety and Hazard Investigation Board (USCSB), "Safety Bulletin - Hazards of Nitrogen | |
| Asphyxiation," 6 2003. [Online]. Available: https://www.csb.gov/hazards-of-nitrogen-asphyxiation/. | |
| [Accessed 8 12 2017]. | |
| [169] Kuraray, "Corporate Overview," [Online]. Available: https://www.kuraray.com/company/overview. | |
| [Accessed 29 May 2019]. | |
| [170] American Chemistry Council, "Responsible Care: About," [Online]. Available: | |
| https://www.americanchemistry.com/Membership/MemberCompanies/. [Accessed 29 May 2019]. | |
| [171] U.S. Department of Labor Bureau of Labor Statistics, "Appendix C, Bulletin 2424: Occupational Injuries | |
| and Illnesses in the United States by Industry, 1991," May 1993. [Online]. Available: | |
| https://books.google.com/books?id=msRH9BUNUP0C&pg=PA75&lpg=PA75&dq=%22Incidence+rates+ca | |
| n+be+used+to+show+the+relative+level+of+injuries+and+illnesses+among+different+industries%22&sourc | |
| e=bl&ots=nnEiD8ko8E&sig=3rCxnPVa8dOykr8BAXCed4MKOs0&hl=en&sa=X&ved=0a. [Accessed 27 | |
| December 2017]. | |
| [172] National Fire Protection Association (NFPA), "NFPA 921: Guide for Fire & Explosion Investigations," | |
| 2017. [Online]. Available: https://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes- | |
| and-standards/detail?code=921. | |
| [173] U.S. Chemical Safety and Hazard Identification Board (USCSB), "Safety Digest: Preparing Equipment and | |
| Instrumentation for Cold Weather Operations," September 2018. [Online]. Available: | |
| https://www.csb.gov/assets/1/6/csb_winterization_safety_digest.pdf. [Accessed 5 June 2019]. | |
| Page 143 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| APPENDIX A: CAUSAL ANALYSIS | |
| The AcciMapa (size 11" x 17") can be found at www.csb.gov on the DuPont La Porte investigation page. | |
| a An AcciMap is a multilayered causal diagram that arranges the various causes of an accident in terms of their remoteness from the | |
| initiating events. This approach differs from other analysis techniques in that it identifies causes in all parts of the system, ranging from | |
| the physical sequence of events right up to causes at the governmental, regulatory, and societal levels. It is a CSB internal investigation | |
| procedure that is especially useful for developing broadly applicable recommendations for prevention. | |
| Page 144 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| APPENDIX B: INCIDENT TIMELINE | |
| Approximate Time Activity | |
| Wednesday, | |
| November 12, 2014 | |
| 2:00–3:00 pm | |
| 3:00 pm | |
| Friday, November | |
| 14, 2014 | |
| 10:00 am–3:02 am | |
| Investigation Note | |
| Saturday, November | |
| 15, 2014 (Day of | |
| Incident) | |
| 2:51 am–2:54 am | |
| 2:58 am–3:03 am | |
| 3:01 am–3:13 am | |
| Operators attempt to restart the Lannate® process after a unit shutdown, but flow is | |
| not established because equipment is plugged. | |
| Operators begin troubleshooting the Lannate® process to try to clear the plugging. | |
| Methyl mercaptan is released outside and inside the manufacturing building while | |
| troubleshooting to clear the plugging continues. Detectors inside and outside the | |
| manufacturing building identify high levels of methyl mercaptan and trigger alarms | |
| 32 separate times. These alarms display only on the control panel (there are no | |
| building or exterior alarms). Operations personnel who are aware of the alarms and | |
| the troubleshooting do not perceive the leaks as posing a serious hazard (see | |
| Investigation Note below). | |
| Operations personnel likely normalized both the methyl mercaptan odor and the | |
| detector alarms. Personnel associated these methyl mercaptan leaks with the ongoing | |
| troubleshooting activities. | |
| High pressure in equipment inside the manufacturing building triggers control system | |
| alarms. Operations personnel attribute the high pressure to a common long-standing | |
| problem with process condensate accumulating in the waste gas vent header piping. | |
| Unknown to the operations personnel, in this instance the high pressure is not caused | |
| by the typical process condensate accumulation. The high pressure is a symptom of a | |
| different problem: liquid methyl mercaptan flowing into the waste gas vent header | |
| piping, due to the piping alignment being used to clear the plugging during the | |
| troubleshooting efforts. | |
| Shift Supervisor and Operator 1 separately go to the third floor of the manufacturing | |
| building to try to reduce the equipment pressure. They plan to drain the equipment of | |
| what they believe is normal process condensate to reduce the high pressure—a long- | |
| standing practice used to reduce pressure in this equipment. | |
| Two drain valves on the waste gas vent header are manually opened on the third floor | |
| of the manufacturing building. Highly toxic and highly flammable liquid methyl | |
| mercaptan flows out of the valves, overcoming the Shift Supervisor. | |
| Page 145 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 3:13 am | |
| 3:24 am–3:26 am | |
| 3:30 am | |
| 3:30 am | |
| 3:30 am – 3:40 am | |
| 3:30 am | |
| 3:30 am | |
| Investigation Note | |
| 3:30–3:35 am | |
| 3:30–3:35 am | |
| 3:30–3:35 am | |
| 3:35 am | |
| The second-floor chlorine detector records a value of -1. This type of detector is | |
| known to go negative when sensing methyl mercaptan (-1 parts per million chlorine | |
| indication ≈ 33 parts per million methyl mercaptan). | |
| Three methyl mercaptan detectors inside the manufacturing building (two on the first | |
| floor and one on the fourth floor) sense at least 25 parts per million methyl mercaptan, | |
| triggering alarms at the control panel. The Board Operator may see these alarms but | |
| does not realize a chemical release has begun, likely associating the alarms with | |
| process troubleshooting. His focus is on mitigating the equipment high-pressure | |
| event. | |
| Operator 1, who is likely on third floor of manufacturing building, makes an urgent | |
| distress call over the radio for help. Personnel do not know where Operator 1 is | |
| located or the type of emergency she is experiencing. Some DuPont La Porte | |
| personnel who hear her distress call interpret the communication to mean that | |
| Operator 1 has a personal injury—such as a broken leg. Personnel in the control room | |
| do not yet realize there is a toxic chemical release. | |
| Control room operator tries to get more information through radio communication, | |
| but neither the Shift Supervisor nor Operator 1 responds. | |
| An operator (Operator 5) on the first floor of the manufacturing building is exposed to | |
| methyl mercaptan and experiences dizziness and blurry vision. He escapes from the | |
| manufacturing building, runs across the street, and lies down in the grass, where he | |
| starts to recover. | |
| Two operators (Operator 2 and Operator 3) in the control room run into the | |
| manufacturing building to respond to the distress call made by Operator 1. They do | |
| not realize they are responding to a serious toxic methyl mercaptan leak. They do not | |
| wear or take with them any respiratory protection. | |
| Operator 4, who is outside, sees Operator 2 and Operator 3 running into the | |
| manufacturing building and follows them. He also does not realize they are | |
| responding to a serious toxic methyl mercaptan leak. He does not wear or take with | |
| him any respiratory protection. | |
| No visual or audible alarms are installed inside the manufacturing building to warn | |
| operators in the field of the hazardous concentration of methyl mercaptan inside the | |
| manufacturing building. Operations personnel entering the manufacturing building | |
| responding to Operator 1’s distress call have no indication of a lethal methyl | |
| mercaptan concentration in the manufacturing building. | |
| Operator 2 enters the south stairway and likely goes directly to the third floor, where | |
| he is incapacitated by methyl mercaptan. | |
| Operator 3 goes up the stairs to the fourth floor but does not find anyone. | |
| Operator 4 goes up the stairs to the second floor. He walks about 10 feet and hits a | |
| “wall” of methyl mercaptan. He manages to retreat to the stairwell. | |
| Operator 3 announces on the unit’s public-address system that he does not see anyone | |
| on the fourth floor. The control operator responds that the Shift Supervisor and | |
| Page 146 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Operator 1 may be on the third floor. Operator 3 begins to feel light-headed. He | |
| makes his way to the staircase and loses consciousness while descending the stairs | |
| from the fourth floor. | |
| The Board Operator attempts to reach the Shift Supervisor, Operator 1, and Operator | |
| 2 over the radio, but they do not respond. Personnel in the control room begin to | |
| realize something is wrong. Operator 6—the brother of Operator 2—grabs three 5- | |
| minute escape respirators. Other operators in the control room tell him not to enter | |
| the manufacturing building because they do not yet know what is going on or where | |
| the nonresponsive operators are. Operator 6, however, takes the escape respirators | |
| and heads into the manufacturing building. | |
| Operator 6 encounters Operator 4 in the stairway and puts an escape respirator on | |
| him. The breathing air helps Operator 4 recover, and he exits the manufacturing | |
| building safely. | |
| Operator 5 attempts to communicate by radio to inform co-workers of his exposure to | |
| a chemical release in the manufacturing building. (It is unclear if others hear him.) | |
| The manufacturing building fume release alarm sounds. It is a manually activated | |
| alarm intended to alert area workers of a toxic chemical release in the building. | |
| Operator 6 likely activated it. | |
| The Board Operator calls for the plant emergency response team (ERT) to respond, | |
| communicating that workers are missing. ERT members believe they are called to | |
| perform a rescue (e.g., broken bone) and do not know there is a toxic chemical | |
| release. | |
| The Board Operator calls the security guard at the main entrance and asks the guard to | |
| call 9-1-1. There is still confusion about what is going on, and the Board Operator | |
| communicates that workers are missing and requests rescue. The guard gives limited | |
| information to the 9-1-1 operator. | |
| Site emergency responders from the ERT arrive at the scene, but they do not have | |
| proper personal protective equipment (PPE) to enter a building with an active | |
| hazardous chemical release (methyl mercaptan is both highly toxic and highly | |
| flammable). They have prepared and responded to perform a technical rescue and | |
| brought gear only for that operation (harnesses, ropes, and haul systems). When they | |
| arrive at the manufacturing building, they realize it is a chemical release and they | |
| need additional PPE. | |
| The site Incident Commander who responded to the initial rescue request calls for the | |
| ERT to come to the scene with bunker gear and self-contained breathing apparatus | |
| (SCBA)—necessary PPE to enter an area with a toxic chemical release. | |
| 3:35 am | |
| 3:40 am | |
| 3:40 am | |
| 3:40 am | |
| 3:50 am | |
| 3:57 am | |
| 3:58 am | |
| 4:05 am | |
| Page 147 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| 4:10 am | |
| 4:12 am | |
| 4:18 am | |
| 4:20 am | |
| 4:25–4:45 am | |
| 5:08 am | |
| 5:09 am | |
| 5:10 am | |
| 5:15 am | |
| 6:02 am | |
| 6:10 am–9:30 am | |
| The truck containing the ERT’s SCBAs and radios does not start and cannot come to | |
| the scene. An October 2, 2014 work order stated, “Check batteries and they were not | |
| good, remove and replace with new ones.” Replacing the battery did not fully repair | |
| the truck, and it still could not start at the time of the incident. After the incident, | |
| DuPont replaced the truck’s alternator, battery cable, and belts. DuPont did not | |
| adequately maintain the SCBA truck before the incident to ensure it could operate | |
| during an emergency. | |
| A second 9-1-1 call is made by one of the area supervisors. | |
| Harris County Sherriff’s deputies arrive at control room. | |
| Operator 3 regains consciousness and manages to exit the manufacturing building of | |
| his own volition. Fire brigade members escort him to safety. | |
| First ERT team enters manufacturing building. While they are in the manufacturing | |
| building they do not monitor the concentration of methyl mercaptan, which in | |
| addition to being toxic, is a highly flammable chemical. CSB calculations indicate | |
| that at times a portion of the building had an explosive atmosphere from the release. | |
| A 2002 DuPont study found that a methyl mercaptan vapor cloud explosion could | |
| cause the manufacturing building to collapse, but the ERT did not know that. | |
| An ERT member finds drain valves from the waste gas vent header on the third floor | |
| open with a gas (later determined to be methyl mercaptan) flowing from them. The | |
| Shift Supervisor is found unconscious on the third floor approximately 30 feet north | |
| of the drain valves. Operator 6 is found next to his brother (Operator 2), both | |
| unconscious. Operator 2 has a 5-minute escape respirator on his head. The respirator | |
| is one of the three escape packs brought into the building by his brother (Operator 6). | |
| Operator 6 has a 30-minute SCBA air bottle in front of him and the mask on his face, | |
| but he has not connected the mask to the air bottle. (Operator 6 was likely | |
| incapacitated by methyl mercaptan while trying to don the SCBA, before he | |
| connected his mask to the SCBA air bottle.) It is later determined that the Shift | |
| Supervisor, Operator 2, and Operator 6 died from toxic exposure / asphyxiation. | |
| First group of external fire fighters arrive on-site. | |
| Second group of external fire fighters arrive on-site. | |
| Third group of external fire fighters arrive on-site. | |
| Second ERT entry conducted. DuPont and other plant ERT emergency responders do | |
| not monitor the methyl mercaptan concentration inside of the manufacturing building. | |
| On the third floor, an ERT responder closes an open drain valve from which a gas | |
| (methyl mercaptan) is escaping. | |
| Methyl mercaptan storage tank pump is turned off, significantly slowing the methyl | |
| mercaptan release to the atmosphere. | |
| Third, fourth, and fifth ERT entries are conducted to look for missing Operator 1. | |
| DuPont and other plant ERT emergency responders do not monitor the methyl | |
| mercaptan concentration inside of the manufacturing building. (When Harris County | |
| emergency responders conduct building entries, beginning after about 6:40 am, they | |
| Page 148 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| monitor the air inside the manufacturing building using a QRAE monitor and a | |
| MultiRAE monitor.) | |
| Emergency responders cannot find Operator 1, possibly because there could be areas | |
| inside the manufacturing building that they are not aware they have not searched. | |
| They have no maps to reference during their search, and the manufacturing building is | |
| not equipped with cameras to view the different floors of the building. Area | |
| operators—including the Board Operator—draw building maps to assist emergency | |
| responders in navigating the manufacturing building. | |
| ERT responders continue closing valves to stop the release of methyl mercaptan. | |
| Sheriff’s sergeant notices an “intense smell” in Deer Park (west of La Porte). | |
| A sheriff’s sergeant driving on Texas Highway 225 communicates that “the odor on | |
| 225 is strong.” | |
| Harris County performs first off-site air monitoring (near Highway 225) and does not | |
| detect methyl mercaptan in the air. | |
| DuPont activates the methyl mercaptan tank emergency isolation valve to stop methyl | |
| mercaptan from flowing to the process. | |
| Sixth ERT entry is conducted. Operator 1 is recovered in the north stairwell of the | |
| manufacturing building. She is later determined to be deceased, having died from | |
| toxic exposure / asphyxiation. | |
| Final waste gas vent header drain valve is closed to fully stop methyl mercaptan | |
| release. | |
| 6:14 am | |
| 6:38 am | |
| 8:07 am | |
| 10:07 am | |
| 11:15 am–11:55 am | |
| 11:40 am | |
| Page 149 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| APPENDIX C: ODOR COMPLAINTS FROM NOVEMBER 15, 2014 | |
| Figure 40. Map of the Odor Complaints (Yellow Pins) from the November 15, 2014 Incident. Source: Harris County, Texas. | |
| Page 150 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| APPENDIX D: EMERGENCY RESPONSE TABLES | |
| The regulatory tables in this appendix focus on the most significant OSHA and EPA requirements regarding | |
| Emergency Response and Preparedness. Companies should first determine what regulations apply to their | |
| process or facility and whether they are statutorily required to conduct or will voluntarily conduct an emergency | |
| response.a Based on this information, companies should develop an integrated approach to their requirements. | |
| Table 1. OSHA and EPA Regulations That Apply to Emergency Response Preparedness. | |
| Regulation | |
| Name | |
| Requirement | |
| 29 C.F.R. § 1910.119 | |
| Process Safety Management of | |
| Highly Hazardous Chemicals (PSM) | |
| 29 C.F.R. § 1910.38 | |
| Emergency Action Plans | |
| 29 C.F.R. § 1910.120 | |
| Hazardous Waste Operations and | |
| Emergency Response (HAZWOPER) | |
| 42 U.S.C. § 116 | |
| Emergency Planning and Community | |
| Right-to-Know Act (EPCRA) | |
| 40 C.F.R. § 68(G) | |
| Risk Management Plan (RMP)b | |
| Requires an emergency action plan or an | |
| emergency response plan (if there is an | |
| internal emergency response team). | |
| Dictates the minimum procedures necessary | |
| to alert emergency personnel of an | |
| emergency. | |
| Requires an emergency response plan if there | |
| are hazardous materials and there is an | |
| internal emergency response. | |
| Requires states to develop a state emergency | |
| planning commission and local emergency | |
| planning committees (LEPC). Requires an | |
| emergency response plan and emergency | |
| notifications. | |
| Requires an emergency response program. | |
| Requirements may potentially be fulfilled by | |
| developing emergency response plans | |
| required by other agencies. | |
| a The term response has the same meaning under OSHA’s Hazardous Waste Operations and Emergency Response (HAZWOPER) | |
| standard and EPA’s Risk Management Plan rule [151, p. 2]. OSHA defines emergency response under the HAZWOPER standard as “a | |
| response effort by employees from outside the immediate release area or by other designated responders (i.e., mutual aid groups, local | |
| fire departments, etc.) to an occurrence which results, or is likely to result, in an uncontrolled release of a hazardous substance. | |
| Responses to incidental releases of hazardous substances where the substance can be absorbed, neutralized, or otherwise controlled at the | |
| time of release by employees in the immediate release area, or by maintenance personnel are not considered to be emergency responses | |
| within the scope of this standard. Responses to releases of hazardous substances where there is no potential safety or health hazard (i.e., | |
| fire, explosion, or chemical exposure) are not considered to be emergency responses” (29 C.F.R. § 1910.120(a)(3)). | |
| b The EPA has published general guidance on Emergency Response Programs and other aspects of RMP. | |
| Page 151 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Table 2. Requirements for an Emergency Action Plan (29 C.F.R. § 1910.38) and Emergency Response Plan (29 C.F.R. § 1910.120) under | |
| OSHA. | |
| Requirement | |
| Procedures for reporting a fire or other emergency | |
| Procedures for emergency evacuation, including type of evacuation | |
| and exit route assignments | |
| Procedures for employees who remain to operate critical plant | |
| operations before they evacuate | |
| Procedures to account for all employees after evacuation | |
| Procedures for employees performing rescue or medical duties | |
| The name or job title of every employee who may be contacted by | |
| employees who need more information about the plan or an | |
| explanation of their duties under the plan | |
| Pre-emergency planning and coordination with outside parties | |
| Personnel roles, lines of authority, training, and communication | |
| Emergency recognition and prevention | |
| Safe distances and places of refuge | |
| Site security and control | |
| Evacuation routes and procedures | |
| Decontamination | |
| Emergency medical treatment and first aid | |
| Emergency alerting and response procedures | |
| Critique of response and follow-up | |
| Personal protective equipment and emergency equipment | |
| Emergency | |
| Action Plan | |
| ✓ | |
| Emergency | |
| Response Plan | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| ✓ | |
| Page 152 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Table 3. Emergency Response Program requirements under RMP for Responding Facilities. | |
| Elements | |
| Emergency response plan | |
| Planning coordination | |
| Emergency equipment | |
| Employee training | |
| Response plan evaluation | |
| Requirement | |
| An emergency response plan maintained at the facility that includes (1) | |
| procedures for informing the public and emergency response agencies about | |
| releases, (2) documentation of proper first aid and emergency medical treatment | |
| necessary to treat human exposures, and (3) procedures and measures for | |
| emergency response | |
| Coordination with local response agencies on responses to potential release of | |
| regulated substances | |
| Procedures for using, inspecting, testing, and maintaining emergency response | |
| equipment | |
| Training for all employees in relevant procedures | |
| Procedures for reviewing and updating the response plan to reflect changes at the | |
| facility and for ensuring that employees are informed of the changes | |
| Page 153 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Table 4. Industry and Government Guidance Related to Emergency Response. | |
| Organization | |
| Federal Emergency | |
| Management | |
| Agency (FEMA) | |
| American Petroleum | |
| Institute (API) | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| Name | |
| Description | |
| National Incident Management | |
| System (NIMS) | |
| RP API 1174, API Recommended | |
| Practice for Pipeline Emergency | |
| Preparedness and Response | |
| NFPA 472, Standard for | |
| Competence of Responders to | |
| Hazardous Materials/Weapons of | |
| Mass Destruction Incidents | |
| NFPA 475, Recommended Practice | |
| for Organizing, Managing, and | |
| Sustaining a Hazardous | |
| Materials/Weapons of Mass | |
| Destruction Response Program | |
| A common framework for overall incident | |
| management. A comprehensive approach that is | |
| applicable at all jurisdictional levels | |
| Enhanced framework for an emergency | |
| management system for onshore hazardous liquid | |
| pipeline operators | |
| Minimum levels of competence required by | |
| responders to emergencies involving hazardous | |
| materials or weapons of mass destruction | |
| Criteria for the organization, management, and | |
| deployment of personnel, resources, and | |
| programs for entities responsible for the | |
| hazardous materials/weapons of mass destruction | |
| emergency preparedness function | |
| NFPA 600, Standard on Facility Fire | |
| Brigades | |
| Requirements for organizing, operating, training, | |
| and equipping industrial fire brigades | |
| NFPA 704, Standard System for the | |
| Identification of the Hazards of | |
| Materials for Emergency Response | |
| NFPA 1221, Standard for the | |
| Installation, Maintenance, and Use | |
| of Emergency Services | |
| Communications Systems | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| NFPA 1250, Recommended Practice | |
| in Fire and Emergency Service | |
| Organization Risk Management | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| NFPA 1561, Standard on Emergency | |
| Services Incident Management | |
| System and Command Safety | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| NFPA 1600, Standard on Continuity, | |
| Emergency, and Crisis Management | |
| The NFPA’s Hazard Diamond, a labeling system | |
| that identifies the hazards of materials | |
| The installation, performance, operation, and | |
| maintenance of communications systems and | |
| facilities used by public emergency services | |
| Criteria to develop, implement, or evaluate a fire | |
| and emergency service organization risk | |
| management program for effective risk | |
| identification, control, and financing | |
| Requirements for the structure and operation of | |
| an incident management system for emergency | |
| services, including principles of command safety | |
| to be incorporated into all incidents, training, or | |
| emergencies, to ensure the safety of emergency | |
| responders and others on the scene of an incident | |
| Common set of criteria for all hazards, disaster, | |
| emergency management, and business continuity | |
| or continuity-of-operations programs | |
| Page 154 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Organization | |
| National Fire | |
| Protection | |
| Association (NFPA) | |
| Name | |
| Description | |
| NFPA 1620, Standard for Pre- | |
| Incident Planning | |
| Criteria for developing pre-incident plans to help | |
| responders effectively manage emergencies | |
| Page 155 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| APPENDIX E: DUPONT SAFETY PERCEPTION SURVEYS | |
| For more than a decade, DuPont developed and honed a safety culture program to reduce its OSHA total | |
| recordable injury rate by assessing and improving occupational (personal) safety, using its Bradley Curve and | |
| Safety Perception Survey tools. | |
| In the 1990s, DuPont identified a significant discrepancy in safety performance at different DuPont sites around | |
| the world. Some of the company’s sites had few recordable injuries, and other sites had many. To improve | |
| safety performance at DuPont sites, a former DuPont Chairman and CEO created a team dubbed the Discovery | |
| Team to find a sustainable way to strengthen safety performance at all DuPont facilities, with the ultimate goal | |
| of having zero incidents throughout the entire organization [77]. | |
| The Discovery Team found that the sites with the best worker safety records more prevalently practiced DuPont | |
| safety principles. The Discovery Team also asserted that sites with the most worker injuries had a lack of | |
| management commitment to safety, more communication breakdowns, and inconsistent safety leadership. | |
| Overall, the Discovery Team claimed that DuPont sites with fewer worker injuries had a distinctive safety | |
| culture that permeated the entire facility [77]. | |
| Verlon Bradley, then manager of the DuPont plant in Beaumont, Texas, along with the Discovery Team, created | |
| a model named the Bradley Curve (Figure 41). The Bradley Curve aimed to illustrate the strength of an | |
| organization’s safety culture and its relationship to the number of worker (OSHA recordable) injuries [77]. | |
| DuPont began using the Bradley Curve model internally, and in 1995, DuPont’s consulting service, DuPont | |
| Sustainable Solutions, began applying the Bradley Curve model to improve safety performance at other | |
| companies in various industries [78]. | |
| Page 156 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 41. The DuPont Bradley Curve. The Bradley Curve correlates improved safety culture with reduced OSHA | |
| recordable injury rates. For more information, see Bradley Curve. Source: DuPont. | |
| In 1999, DuPont formalized a method to assess an organization’s safety culture with its Safety Perception | |
| Surveya to measure the strength of the safety culture at each site. The Safety Perception Survey consists of 24 | |
| multiple-choice questions to measure safety culture across three categories of safety management: (1) | |
| leadership, (2) processes and actions, and (3) structure [59, p. 2]. The survey addresses only 12 of DuPont’s 22 | |
| essential elements of an integrated safety management system (Figure 42). It focuses on elements it labels | |
| “cultural” and places under “Management Commitment” and does not address components related to what it | |
| calls “risk-based” process safety, such as management of change. According to DuPont Sustainable Solutions, | |
| the Bradley Curve benchmarking system, combined with DuPont’s Safety Perception Surveys, has helped | |
| DuPont and its clients improve their safety culture performance [78]. | |
| a A safety management consultant and former DuPont executive developed the Safety Perception Survey, which was first published in | |
| 1999. DuPont acquired the survey in 2000. DuPont modified it and incorporated it into its consulting methodology for benchmarking | |
| and action planning [59, p. 2]. | |
| Page 157 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Figure 42. To DuPont, Each Wheel Represents Different Aspects of Safety. The wheel on the left | |
| (Cultural) represents the only aspects of safety that DuPont’s Safety Perception Surveys cover. | |
| The wheel on the right (Risk-‐Based) represents aspects of safety typically associated with process | |
| safety. Source: DuPont. | |
| Beginning in 2007, DuPont began calculating a “Relative Culture Strength” (RCS) score based on responses to | |
| the Safety Perception Surveys.a DuPont found that higher RCS correlated with a lower OSHA total recordable | |
| injury rate.b The correlation also fit the Bradley Curve (Figure 43) [59, p. 7]. Because of this correlation, | |
| DuPont often uses the OSHA total recordable injury rate “as [its] measure of safety performance” [59, p. 2]. | |
| Additionally, DuPont uses the RCS in combination with the Bradley Curve (Figure 43) to determine what stage | |
| of safety culture a facility has achieved. The curve represents the progress of a facility’s culture strength. The | |
| a RCS is a proprietary number calculated by comparing a company’s responses to survey questions against a benchmark established by | |
| DuPont in 2008 based on the best and worst sites that had taken the Safety Perception Survey [59, p. 3]. | |
| b The OSHA recordable injury rate is the annual number of injuries and illnesses per 100 full-time workers. The | |
| OSHA injury rate, which excludes fatalities, is a normalized rate that is used for comparison across industries [171, p. 75]. | |
| Page 158 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| higher the score, the further along the facility is on the curve, with the highest level designated “World Class.”a | |
| DuPont classified facilities with a calculated RCS value of 80 or greater as having a “World Class” safety | |
| culture. Results from a 2012 Safety Perception Survey conducted at the La Porte site, the last safety culture | |
| survey conducted at the site before the incident, classified its perception of safety performance as “World | |
| Class.” This safety classification, however, relied on the DuPont La Porte site’s employees’ perception of | |
| personal (worker) safety performance only, because the Safety Perception Survey used at DuPont La Porte did | |
| not include process safety considerations. | |
| Figure 43. DuPont Bradley Curve with Plotted RCS results from 169,000 Safety Perception Surveys. The yellow bars show the range | |
| of the middle 50 percent of the data in each category, and the horizontal blue line in each box indicates the median. DuPont found | |
| that a higher RCS correlated with a lower worker injury rate (OSHA total recordable injury rate). Source: DuPont. | |
| a The Safety Perception Survey ranks performance by five categories (from best to worst): World Class, Excellence, Skill, Awareness, | |
| and Fundamentals. World Class is defined as “the organization leads its industry in safety performance as a direct result of its safety | |
| focus, leadership, deliberate organizational design, and the portfolio of activities it carries out to maintain a safe workplace.” Excellence | |
| is defined as “the organization has strong capabilities to identify, learn from, and correct at-risk behaviors and workplace hazards. Safety | |
| is a top priority. There is a free flow and exchange of information without the fear of retribution, and the organization is focused on | |
| learning and improving. Hazard reporting, auditing, and corrective implementation are well designed and executed on a regular basis.” | |
| The Skill level is defined as “the organization shows numerous signs of continuous improvement and has a track record of modest and | |
| consistent improvement in safety performance. Personnel are skilled in the application of basic safety management tools and | |
| techniques.” The Awareness level is defined as “the organization is aware of its performance and has established basic policies and | |
| processes to measure and improve safety performance. There is relatively high value for safety efforts, and an auditing system is in place | |
| to eliminate workplace hazards.” The Fundamentals level is defined as “the organization has processes in place to avoid known | |
| workplace hazards and uses trailing injury statistics for performance measurement. Injuries and incidents are the main driving force | |
| behind discussion of safety management practices. There is a written safety policy that may not be familiar to employees or be perceived | |
| as of high value. Safety performance is known to some in the organization but is not widely known or thought out.” | |
| Page 159 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| DuPont Sustainable Solutions responded to the new learnings about process safety culture after BP Texas City | |
| by developing 13 new process safety questions for its Safety Perception Surveys. These questions are | |
| considered optional and may be included in the survey at clients’ request. | |
| Page 160 | |
| U.S. Chemical Safety and | |
| Hazard Investigation Board | |
| Toxic Chemical Release at the | |
| DuPont La Porte Chemical Facility | |
| La Porte, Texas | Incident Date: November 15, 2014 | No. 2015-01-I-TX | |
| Members of the U.S. Chemical Safety and Hazard Investigation Board: | |
| Kristen Kulinowski, PhD | |
| Interim Executive | |
| Manuel Ehrlich | |
| Member | |
| Richard Engler | |
| Member | |
| Page 161 |