Upload heating_load.py
Browse files- utils/heating_load.py +155 -23
utils/heating_load.py
CHANGED
|
@@ -1,7 +1,15 @@
|
|
| 1 |
"""
|
| 2 |
-
|
| 3 |
Implements ASHRAE steady-state methods with simplified thermal lag for compatibility.
|
| 4 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 5 |
"""
|
| 6 |
|
| 7 |
from typing import Dict, List, Any, Optional, Tuple
|
|
@@ -20,7 +28,7 @@ from utils.psychrometrics import Psychrometrics
|
|
| 20 |
from utils.heat_transfer import HeatTransferCalculations
|
| 21 |
|
| 22 |
# Import data modules
|
| 23 |
-
from
|
| 24 |
|
| 25 |
|
| 26 |
class HeatingLoadCalculator:
|
|
@@ -91,6 +99,11 @@ class HeatingLoadCalculator:
|
|
| 91 |
adjusted_delta_t = delta_t * lag_factor
|
| 92 |
|
| 93 |
load = self.heat_transfer.conduction_heat_transfer(wall.u_value, wall.area, adjusted_delta_t)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 94 |
return max(0, load)
|
| 95 |
|
| 96 |
def calculate_roof_heating_load(self, roof: Roof, outdoor_temp: float, indoor_temp: float) -> float:
|
|
@@ -114,6 +127,11 @@ class HeatingLoadCalculator:
|
|
| 114 |
adjusted_delta_t = delta_t * lag_factor
|
| 115 |
|
| 116 |
load = self.heat_transfer.conduction_heat_transfer(roof.u_value, roof.area, adjusted_delta_t)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 117 |
return max(0, load)
|
| 118 |
|
| 119 |
def calculate_floor_heating_load(self, floor: Floor, ground_temp: float, indoor_temp: float) -> float:
|
|
@@ -133,10 +151,22 @@ class HeatingLoadCalculator:
|
|
| 133 |
if delta_t <= 1:
|
| 134 |
return 0.0
|
| 135 |
|
| 136 |
-
if floor
|
|
|
|
|
|
|
|
|
|
| 137 |
# Dynamic F-factor based on insulation
|
| 138 |
-
|
| 139 |
-
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 140 |
else:
|
| 141 |
load = self.heat_transfer.conduction_heat_transfer(floor.u_value, floor.area, delta_t)
|
| 142 |
|
|
@@ -162,7 +192,32 @@ class HeatingLoadCalculator:
|
|
| 162 |
if delta_t <= 1:
|
| 163 |
return 0.0
|
| 164 |
|
| 165 |
-
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 166 |
return max(0, load)
|
| 167 |
|
| 168 |
def calculate_door_heating_load(self, door: Door, outdoor_temp: float, indoor_temp: float) -> float:
|
|
@@ -182,7 +237,48 @@ class HeatingLoadCalculator:
|
|
| 182 |
if delta_t <= 1:
|
| 183 |
return 0.0
|
| 184 |
|
| 185 |
-
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 186 |
return max(0, load)
|
| 187 |
|
| 188 |
def calculate_infiltration_heating_load(self, indoor_conditions: Dict[str, float],
|
|
@@ -217,9 +313,14 @@ class HeatingLoadCalculator:
|
|
| 217 |
)
|
| 218 |
total_pd = self.heat_transfer.combined_pressure_difference(wind_pd, stack_pd)
|
| 219 |
|
| 220 |
-
#
|
| 221 |
-
crack_length
|
| 222 |
-
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 223 |
|
| 224 |
# Calculate humidity ratio difference
|
| 225 |
w_indoor = self.psychrometrics.humidity_ratio(
|
|
@@ -307,16 +408,19 @@ class HeatingLoadCalculator:
|
|
| 307 |
|
| 308 |
return max(0, sensible_load), max(0, latent_load)
|
| 309 |
|
| 310 |
-
|
|
|
|
| 311 |
"""
|
| 312 |
Calculate internal heat gains from people, lighting, and equipment.
|
| 313 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.4.
|
| 314 |
|
| 315 |
Args:
|
| 316 |
internal_loads: Internal loads (people, lights, equipment)
|
|
|
|
|
|
|
| 317 |
|
| 318 |
Returns:
|
| 319 |
-
Total internal gains in W
|
| 320 |
"""
|
| 321 |
total_gains = 0.0
|
| 322 |
|
|
@@ -336,13 +440,15 @@ class HeatingLoadCalculator:
|
|
| 336 |
if equipment.get('power', 0) > 0:
|
| 337 |
total_gains += equipment['power'] * equipment.get('use_factor', 0.7)
|
| 338 |
|
| 339 |
-
|
|
|
|
| 340 |
|
| 341 |
def calculate_design_heating_load(self, building_components: Dict[str, List[Any]],
|
| 342 |
outdoor_conditions: Dict[str, float],
|
| 343 |
indoor_conditions: Dict[str, float],
|
| 344 |
internal_loads: Dict[str, Any],
|
| 345 |
-
p_atm: float = 101325
|
|
|
|
| 346 |
"""
|
| 347 |
Calculate design heating loads for all components.
|
| 348 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.
|
|
@@ -353,6 +459,7 @@ class HeatingLoadCalculator:
|
|
| 353 |
indoor_conditions: Indoor conditions (temperature, relative_humidity)
|
| 354 |
internal_loads: Internal loads (people, lights, equipment, infiltration, ventilation)
|
| 355 |
p_atm: Atmospheric pressure in Pa (default: 101325 Pa)
|
|
|
|
| 356 |
|
| 357 |
Returns:
|
| 358 |
Dictionary of design loads in W
|
|
@@ -368,6 +475,7 @@ class HeatingLoadCalculator:
|
|
| 368 |
'floors': 0.0,
|
| 369 |
'windows': 0.0,
|
| 370 |
'doors': 0.0,
|
|
|
|
| 371 |
'infiltration_sensible': 0.0,
|
| 372 |
'infiltration_latent': 0.0,
|
| 373 |
'ventilation_sensible': 0.0,
|
|
@@ -391,6 +499,10 @@ class HeatingLoadCalculator:
|
|
| 391 |
for door in building_components.get('doors', []):
|
| 392 |
loads['doors'] += self.calculate_door_heating_load(door, outdoor_conditions['design_temperature'], indoor_conditions['temperature'])
|
| 393 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 394 |
# Calculate infiltration and ventilation loads
|
| 395 |
building_height = internal_loads.get('infiltration', {}).get('height', 3.0)
|
| 396 |
infiltration_sensible, infiltration_latent = self.calculate_infiltration_heating_load(
|
|
@@ -405,8 +517,10 @@ class HeatingLoadCalculator:
|
|
| 405 |
loads['ventilation_sensible'] = ventilation_sensible
|
| 406 |
loads['ventilation_latent'] = ventilation_latent
|
| 407 |
|
| 408 |
-
# Calculate internal gains (negative
|
| 409 |
-
loads['internal_gains'] =
|
|
|
|
|
|
|
| 410 |
|
| 411 |
return loads
|
| 412 |
|
|
@@ -421,17 +535,26 @@ class HeatingLoadCalculator:
|
|
| 421 |
Returns:
|
| 422 |
Summary dictionary with total, subtotal, and safety factor
|
| 423 |
"""
|
|
|
|
| 424 |
subtotal = sum(
|
| 425 |
load for key, load in design_loads.items()
|
| 426 |
if key not in ['internal_gains'] and load > 0
|
| 427 |
)
|
| 428 |
internal_gains = design_loads.get('internal_gains', 0)
|
| 429 |
|
| 430 |
-
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 431 |
|
| 432 |
return {
|
| 433 |
'subtotal': subtotal,
|
| 434 |
'internal_gains': internal_gains,
|
|
|
|
| 435 |
'total': total,
|
| 436 |
'safety_factor': self.safety_factor
|
| 437 |
}
|
|
@@ -502,7 +625,8 @@ class HeatingLoadCalculator:
|
|
| 502 |
indoor_conditions: Dict[str, float],
|
| 503 |
internal_loads: Dict[str, Any],
|
| 504 |
monthly_temps: Dict[str, float],
|
| 505 |
-
p_atm: float = 101325
|
|
|
|
| 506 |
"""
|
| 507 |
Calculate monthly heating loads.
|
| 508 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.
|
|
@@ -514,6 +638,7 @@ class HeatingLoadCalculator:
|
|
| 514 |
internal_loads: Internal loads
|
| 515 |
monthly_temps: Dictionary of monthly average temperatures
|
| 516 |
p_atm: Atmospheric pressure in Pa (default: 101325 Pa)
|
|
|
|
| 517 |
|
| 518 |
Returns:
|
| 519 |
Dictionary of monthly heating loads in kW
|
|
@@ -531,7 +656,8 @@ class HeatingLoadCalculator:
|
|
| 531 |
|
| 532 |
try:
|
| 533 |
design_loads = self.calculate_design_heating_load(
|
| 534 |
-
building_components, modified_outdoor, indoor_conditions, internal_loads, p_atm
|
|
|
|
| 535 |
)
|
| 536 |
summary = self.calculate_heating_load_summary(design_loads)
|
| 537 |
monthly_loads[month] = summary['total'] / 1000 # kW
|
|
@@ -552,7 +678,8 @@ if __name__ == "__main__":
|
|
| 552 |
is_ground_contact=True, insulated=True, ground_temperature_c=10.0)],
|
| 553 |
'windows': [Window(id="win1", name="South Window", area=10.0, u_value=2.8, orientation=Orientation.SOUTH,
|
| 554 |
shgc=0.7, shading_coefficient=0.8)],
|
| 555 |
-
'doors': [Door(id="d1", name="Main Door", area=2.0, u_value=2.0, orientation=Orientation.NORTH)]
|
|
|
|
| 556 |
}
|
| 557 |
|
| 558 |
outdoor_conditions = {
|
|
@@ -569,7 +696,7 @@ if __name__ == "__main__":
|
|
| 569 |
'people': {'number': 10, 'sensible_gain': 70.0, 'operating_hours': '8:00-18:00'},
|
| 570 |
'lights': {'power': 1000.0, 'use_factor': 0.8, 'hours_operation': '8h'},
|
| 571 |
'equipment': {'power': 500.0, 'use_factor': 0.7, 'hours_operation': '8h'},
|
| 572 |
-
'infiltration': {'flow_rate': 0.05, 'height': 3.0, 'crack_length': 20.0},
|
| 573 |
'ventilation': {'flow_rate': 0.1},
|
| 574 |
'operating_hours': '8:00-18:00'
|
| 575 |
}
|
|
@@ -579,7 +706,10 @@ if __name__ == "__main__":
|
|
| 579 |
}
|
| 580 |
|
| 581 |
# Calculate design loads
|
| 582 |
-
design_loads = calculator.calculate_design_heating_load(
|
|
|
|
|
|
|
|
|
|
| 583 |
summary = calculator.calculate_heating_load_summary(design_loads)
|
| 584 |
|
| 585 |
# Log results
|
|
@@ -589,6 +719,7 @@ if __name__ == "__main__":
|
|
| 589 |
logger.info(f"Floor Load: {design_loads['floors']:.2f} W")
|
| 590 |
logger.info(f"Window Load: {design_loads['windows']:.2f} W")
|
| 591 |
logger.info(f"Door Load: {design_loads['doors']:.2f} W")
|
|
|
|
| 592 |
logger.info(f"Infiltration Sensible Load: {design_loads['infiltration_sensible']:.2f} W")
|
| 593 |
logger.info(f"Infiltration Latent Load: {design_loads['infiltration_latent']:.2f} W")
|
| 594 |
logger.info(f"Ventilation Sensible Load: {design_loads['ventilation_sensible']:.2f} W")
|
|
@@ -603,7 +734,8 @@ if __name__ == "__main__":
|
|
| 603 |
|
| 604 |
# Calculate monthly loads
|
| 605 |
monthly_loads = calculator.calculate_monthly_heating_loads(
|
| 606 |
-
components, outdoor_conditions, indoor_conditions, internal_loads, monthly_temps
|
|
|
|
| 607 |
)
|
| 608 |
logger.info("Monthly Heating Loads (kW):")
|
| 609 |
for month, load in monthly_loads.items():
|
|
|
|
| 1 |
"""
|
| 2 |
+
Enhanced heating load calculation module for HVAC Load Calculator.
|
| 3 |
Implements ASHRAE steady-state methods with simplified thermal lag for compatibility.
|
| 4 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.
|
| 5 |
+
|
| 6 |
+
ENHANCEMENTS:
|
| 7 |
+
- Added support for equipment and internal loads as heating sources
|
| 8 |
+
- Added support for custom U-values for materials
|
| 9 |
+
- Improved integration with enhanced component selection features (crack dimensions, drapery inputs)
|
| 10 |
+
- Ensured compatibility with winter design parameters from enhanced climate data
|
| 11 |
+
- Added support for skylights in heating load calculations
|
| 12 |
+
- Improved infiltration calculations using crack dimensions
|
| 13 |
"""
|
| 14 |
|
| 15 |
from typing import Dict, List, Any, Optional, Tuple
|
|
|
|
| 28 |
from utils.heat_transfer import HeatTransferCalculations
|
| 29 |
|
| 30 |
# Import data modules
|
| 31 |
+
from app.component_selection import Wall, Roof, Floor, Window, Door, Orientation, ComponentType, Skylight
|
| 32 |
|
| 33 |
|
| 34 |
class HeatingLoadCalculator:
|
|
|
|
| 99 |
adjusted_delta_t = delta_t * lag_factor
|
| 100 |
|
| 101 |
load = self.heat_transfer.conduction_heat_transfer(wall.u_value, wall.area, adjusted_delta_t)
|
| 102 |
+
|
| 103 |
+
# ENHANCEMENT: Log detailed information in debug mode
|
| 104 |
+
if self.debug_mode:
|
| 105 |
+
logger.debug(f"Wall {wall.name} heating load: u_value={wall.u_value}, area={wall.area}, delta_t={adjusted_delta_t}, load={load:.2f} W")
|
| 106 |
+
|
| 107 |
return max(0, load)
|
| 108 |
|
| 109 |
def calculate_roof_heating_load(self, roof: Roof, outdoor_temp: float, indoor_temp: float) -> float:
|
|
|
|
| 127 |
adjusted_delta_t = delta_t * lag_factor
|
| 128 |
|
| 129 |
load = self.heat_transfer.conduction_heat_transfer(roof.u_value, roof.area, adjusted_delta_t)
|
| 130 |
+
|
| 131 |
+
# ENHANCEMENT: Log detailed information in debug mode
|
| 132 |
+
if self.debug_mode:
|
| 133 |
+
logger.debug(f"Roof {roof.name} heating load: u_value={roof.u_value}, area={roof.area}, delta_t={adjusted_delta_t}, load={load:.2f} W")
|
| 134 |
+
|
| 135 |
return max(0, load)
|
| 136 |
|
| 137 |
def calculate_floor_heating_load(self, floor: Floor, ground_temp: float, indoor_temp: float) -> float:
|
|
|
|
| 151 |
if delta_t <= 1:
|
| 152 |
return 0.0
|
| 153 |
|
| 154 |
+
# ENHANCEMENT: Check if floor has ground_contact attribute
|
| 155 |
+
is_ground_contact = floor.ground_contact if hasattr(floor, 'ground_contact') else False
|
| 156 |
+
|
| 157 |
+
if is_ground_contact:
|
| 158 |
# Dynamic F-factor based on insulation
|
| 159 |
+
# ENHANCEMENT: Check if floor has insulated attribute
|
| 160 |
+
is_insulated = floor.insulated if hasattr(floor, 'insulated') else False
|
| 161 |
+
f_factor = 0.3 if is_insulated else 0.73 # W/m·K
|
| 162 |
+
|
| 163 |
+
# ENHANCEMENT: Check if floor has perimeter attribute
|
| 164 |
+
perimeter = floor.perimeter if hasattr(floor, 'perimeter') else (
|
| 165 |
+
floor.perimeter_length if hasattr(floor, 'perimeter_length') else
|
| 166 |
+
math.sqrt(4 * floor.area) # Estimate perimeter if not provided
|
| 167 |
+
)
|
| 168 |
+
|
| 169 |
+
load = f_factor * perimeter * delta_t
|
| 170 |
else:
|
| 171 |
load = self.heat_transfer.conduction_heat_transfer(floor.u_value, floor.area, delta_t)
|
| 172 |
|
|
|
|
| 192 |
if delta_t <= 1:
|
| 193 |
return 0.0
|
| 194 |
|
| 195 |
+
# ENHANCEMENT: Adjust U-value if window has drapery
|
| 196 |
+
adjusted_u_value = window.u_value
|
| 197 |
+
if hasattr(window, 'has_drapery') and window.has_drapery:
|
| 198 |
+
# Simple U-value adjustment for drapery (typically reduces U-value by 10-20%)
|
| 199 |
+
drapery_reduction = 0.15 # 15% reduction as a default
|
| 200 |
+
|
| 201 |
+
# More detailed adjustment if drapery properties are available
|
| 202 |
+
if hasattr(window, 'drapery_type'):
|
| 203 |
+
drapery_reductions = {
|
| 204 |
+
'None': 0.0,
|
| 205 |
+
'Sheer': 0.05,
|
| 206 |
+
'Light': 0.10,
|
| 207 |
+
'Medium': 0.15,
|
| 208 |
+
'Heavy': 0.20,
|
| 209 |
+
'Blackout': 0.25
|
| 210 |
+
}
|
| 211 |
+
drapery_reduction = drapery_reductions.get(window.drapery_type, 0.15)
|
| 212 |
+
|
| 213 |
+
adjusted_u_value = window.u_value * (1 - drapery_reduction)
|
| 214 |
+
|
| 215 |
+
load = self.heat_transfer.conduction_heat_transfer(adjusted_u_value, window.area, delta_t)
|
| 216 |
+
|
| 217 |
+
# ENHANCEMENT: Log detailed information in debug mode
|
| 218 |
+
if self.debug_mode:
|
| 219 |
+
logger.debug(f"Window {window.name} heating load: u_value={adjusted_u_value}, area={window.area}, delta_t={delta_t}, load={load:.2f} W")
|
| 220 |
+
|
| 221 |
return max(0, load)
|
| 222 |
|
| 223 |
def calculate_door_heating_load(self, door: Door, outdoor_temp: float, indoor_temp: float) -> float:
|
|
|
|
| 237 |
if delta_t <= 1:
|
| 238 |
return 0.0
|
| 239 |
|
| 240 |
+
# ENHANCEMENT: Adjust U-value if door has weatherstripping
|
| 241 |
+
adjusted_u_value = door.u_value
|
| 242 |
+
if hasattr(door, 'has_weatherstripping') and door.has_weatherstripping:
|
| 243 |
+
# Simple U-value adjustment for weatherstripping (typically reduces U-value by 5-10%)
|
| 244 |
+
adjusted_u_value = door.u_value * 0.95 # 5% reduction
|
| 245 |
+
|
| 246 |
+
load = self.heat_transfer.conduction_heat_transfer(adjusted_u_value, door.area, delta_t)
|
| 247 |
+
|
| 248 |
+
# ENHANCEMENT: Log detailed information in debug mode
|
| 249 |
+
if self.debug_mode:
|
| 250 |
+
logger.debug(f"Door {wall.name} heating load: u_value={adjusted_u_value}, area={door.area}, delta_t={delta_t}, load={load:.2f} W")
|
| 251 |
+
|
| 252 |
+
return max(0, load)
|
| 253 |
+
|
| 254 |
+
# ENHANCEMENT: Added skylight heating load calculation
|
| 255 |
+
def calculate_skylight_heating_load(self, skylight: Skylight, outdoor_temp: float, indoor_temp: float) -> float:
|
| 256 |
+
"""
|
| 257 |
+
Calculate heating load for a skylight.
|
| 258 |
+
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Equation 18.1.
|
| 259 |
+
|
| 260 |
+
Args:
|
| 261 |
+
skylight: Skylight component
|
| 262 |
+
outdoor_temp: Outdoor temperature in °C
|
| 263 |
+
indoor_temp: Indoor temperature in °C
|
| 264 |
+
|
| 265 |
+
Returns:
|
| 266 |
+
Heating load in W
|
| 267 |
+
"""
|
| 268 |
+
delta_t = indoor_temp - outdoor_temp
|
| 269 |
+
if delta_t <= 1:
|
| 270 |
+
return 0.0
|
| 271 |
+
|
| 272 |
+
# Skylights typically have higher U-values due to their horizontal orientation
|
| 273 |
+
# Apply a 10% increase to account for this
|
| 274 |
+
adjusted_u_value = skylight.u_value * 1.1
|
| 275 |
+
|
| 276 |
+
load = self.heat_transfer.conduction_heat_transfer(adjusted_u_value, skylight.area, delta_t)
|
| 277 |
+
|
| 278 |
+
# Log detailed information in debug mode
|
| 279 |
+
if self.debug_mode:
|
| 280 |
+
logger.debug(f"Skylight {skylight.name} heating load: u_value={adjusted_u_value}, area={skylight.area}, delta_t={delta_t}, load={load:.2f} W")
|
| 281 |
+
|
| 282 |
return max(0, load)
|
| 283 |
|
| 284 |
def calculate_infiltration_heating_load(self, indoor_conditions: Dict[str, float],
|
|
|
|
| 313 |
)
|
| 314 |
total_pd = self.heat_transfer.combined_pressure_difference(wind_pd, stack_pd)
|
| 315 |
|
| 316 |
+
# ENHANCEMENT: Use crack dimensions if available for more accurate infiltration calculation
|
| 317 |
+
if 'crack_length' in infiltration and 'crack_width' in infiltration:
|
| 318 |
+
crack_length = infiltration['crack_length']
|
| 319 |
+
crack_width = infiltration['crack_width'] / 1000.0 # Convert from mm to m
|
| 320 |
+
flow_rate = self.heat_transfer.crack_method_infiltration(crack_length, crack_width, total_pd)
|
| 321 |
+
else:
|
| 322 |
+
# Use provided flow rate or default
|
| 323 |
+
flow_rate = infiltration.get('flow_rate', 0.05) # m³/s
|
| 324 |
|
| 325 |
# Calculate humidity ratio difference
|
| 326 |
w_indoor = self.psychrometrics.humidity_ratio(
|
|
|
|
| 408 |
|
| 409 |
return max(0, sensible_load), max(0, latent_load)
|
| 410 |
|
| 411 |
+
# ENHANCEMENT: Modified to include equipment and internal loads as heating sources
|
| 412 |
+
def calculate_internal_gains(self, internal_loads: Dict[str, Any], include_as_heating_source: bool = True) -> float:
|
| 413 |
"""
|
| 414 |
Calculate internal heat gains from people, lighting, and equipment.
|
| 415 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.4.
|
| 416 |
|
| 417 |
Args:
|
| 418 |
internal_loads: Internal loads (people, lights, equipment)
|
| 419 |
+
include_as_heating_source: Whether to include internal gains as heating sources (positive value)
|
| 420 |
+
or as load reductions (negative value)
|
| 421 |
|
| 422 |
Returns:
|
| 423 |
+
Total internal gains in W (positive if heating source, negative if load reduction)
|
| 424 |
"""
|
| 425 |
total_gains = 0.0
|
| 426 |
|
|
|
|
| 440 |
if equipment.get('power', 0) > 0:
|
| 441 |
total_gains += equipment['power'] * equipment.get('use_factor', 0.7)
|
| 442 |
|
| 443 |
+
# ENHANCEMENT: Return positive value if including as heating source, negative if reducing load
|
| 444 |
+
return total_gains if include_as_heating_source else -total_gains
|
| 445 |
|
| 446 |
def calculate_design_heating_load(self, building_components: Dict[str, List[Any]],
|
| 447 |
outdoor_conditions: Dict[str, float],
|
| 448 |
indoor_conditions: Dict[str, float],
|
| 449 |
internal_loads: Dict[str, Any],
|
| 450 |
+
p_atm: float = 101325,
|
| 451 |
+
include_internal_gains_as_heating_source: bool = False) -> Dict[str, float]:
|
| 452 |
"""
|
| 453 |
Calculate design heating loads for all components.
|
| 454 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.
|
|
|
|
| 459 |
indoor_conditions: Indoor conditions (temperature, relative_humidity)
|
| 460 |
internal_loads: Internal loads (people, lights, equipment, infiltration, ventilation)
|
| 461 |
p_atm: Atmospheric pressure in Pa (default: 101325 Pa)
|
| 462 |
+
include_internal_gains_as_heating_source: Whether to include internal gains as heating sources
|
| 463 |
|
| 464 |
Returns:
|
| 465 |
Dictionary of design loads in W
|
|
|
|
| 475 |
'floors': 0.0,
|
| 476 |
'windows': 0.0,
|
| 477 |
'doors': 0.0,
|
| 478 |
+
'skylights': 0.0, # ENHANCEMENT: Added skylights
|
| 479 |
'infiltration_sensible': 0.0,
|
| 480 |
'infiltration_latent': 0.0,
|
| 481 |
'ventilation_sensible': 0.0,
|
|
|
|
| 499 |
for door in building_components.get('doors', []):
|
| 500 |
loads['doors'] += self.calculate_door_heating_load(door, outdoor_conditions['design_temperature'], indoor_conditions['temperature'])
|
| 501 |
|
| 502 |
+
# ENHANCEMENT: Added skylights
|
| 503 |
+
for skylight in building_components.get('skylights', []):
|
| 504 |
+
loads['skylights'] += self.calculate_skylight_heating_load(skylight, outdoor_conditions['design_temperature'], indoor_conditions['temperature'])
|
| 505 |
+
|
| 506 |
# Calculate infiltration and ventilation loads
|
| 507 |
building_height = internal_loads.get('infiltration', {}).get('height', 3.0)
|
| 508 |
infiltration_sensible, infiltration_latent = self.calculate_infiltration_heating_load(
|
|
|
|
| 517 |
loads['ventilation_sensible'] = ventilation_sensible
|
| 518 |
loads['ventilation_latent'] = ventilation_latent
|
| 519 |
|
| 520 |
+
# ENHANCEMENT: Calculate internal gains (positive or negative based on parameter)
|
| 521 |
+
loads['internal_gains'] = self.calculate_internal_gains(
|
| 522 |
+
internal_loads, include_as_heating_source=include_internal_gains_as_heating_source
|
| 523 |
+
)
|
| 524 |
|
| 525 |
return loads
|
| 526 |
|
|
|
|
| 535 |
Returns:
|
| 536 |
Summary dictionary with total, subtotal, and safety factor
|
| 537 |
"""
|
| 538 |
+
# ENHANCEMENT: Include skylights in subtotal
|
| 539 |
subtotal = sum(
|
| 540 |
load for key, load in design_loads.items()
|
| 541 |
if key not in ['internal_gains'] and load > 0
|
| 542 |
)
|
| 543 |
internal_gains = design_loads.get('internal_gains', 0)
|
| 544 |
|
| 545 |
+
# ENHANCEMENT: If internal gains are positive (heating source), add them to subtotal
|
| 546 |
+
# If negative (load reduction), subtract them from subtotal
|
| 547 |
+
if internal_gains >= 0:
|
| 548 |
+
adjusted_subtotal = subtotal + internal_gains
|
| 549 |
+
else:
|
| 550 |
+
adjusted_subtotal = subtotal + internal_gains # internal_gains is negative, so this is subtraction
|
| 551 |
+
|
| 552 |
+
total = max(0, adjusted_subtotal) * self.safety_factor
|
| 553 |
|
| 554 |
return {
|
| 555 |
'subtotal': subtotal,
|
| 556 |
'internal_gains': internal_gains,
|
| 557 |
+
'adjusted_subtotal': adjusted_subtotal,
|
| 558 |
'total': total,
|
| 559 |
'safety_factor': self.safety_factor
|
| 560 |
}
|
|
|
|
| 625 |
indoor_conditions: Dict[str, float],
|
| 626 |
internal_loads: Dict[str, Any],
|
| 627 |
monthly_temps: Dict[str, float],
|
| 628 |
+
p_atm: float = 101325,
|
| 629 |
+
include_internal_gains_as_heating_source: bool = False) -> Dict[str, float]:
|
| 630 |
"""
|
| 631 |
Calculate monthly heating loads.
|
| 632 |
Reference: ASHRAE Handbook—Fundamentals (2017), Chapter 18, Section 18.4.
|
|
|
|
| 638 |
internal_loads: Internal loads
|
| 639 |
monthly_temps: Dictionary of monthly average temperatures
|
| 640 |
p_atm: Atmospheric pressure in Pa (default: 101325 Pa)
|
| 641 |
+
include_internal_gains_as_heating_source: Whether to include internal gains as heating sources
|
| 642 |
|
| 643 |
Returns:
|
| 644 |
Dictionary of monthly heating loads in kW
|
|
|
|
| 656 |
|
| 657 |
try:
|
| 658 |
design_loads = self.calculate_design_heating_load(
|
| 659 |
+
building_components, modified_outdoor, indoor_conditions, internal_loads, p_atm,
|
| 660 |
+
include_internal_gains_as_heating_source
|
| 661 |
)
|
| 662 |
summary = self.calculate_heating_load_summary(design_loads)
|
| 663 |
monthly_loads[month] = summary['total'] / 1000 # kW
|
|
|
|
| 678 |
is_ground_contact=True, insulated=True, ground_temperature_c=10.0)],
|
| 679 |
'windows': [Window(id="win1", name="South Window", area=10.0, u_value=2.8, orientation=Orientation.SOUTH,
|
| 680 |
shgc=0.7, shading_coefficient=0.8)],
|
| 681 |
+
'doors': [Door(id="d1", name="Main Door", area=2.0, u_value=2.0, orientation=Orientation.NORTH)],
|
| 682 |
+
'skylights': [Skylight(id="s1", name="Main Skylight", area=5.0, u_value=3.0, orientation=Orientation.HORIZONTAL)]
|
| 683 |
}
|
| 684 |
|
| 685 |
outdoor_conditions = {
|
|
|
|
| 696 |
'people': {'number': 10, 'sensible_gain': 70.0, 'operating_hours': '8:00-18:00'},
|
| 697 |
'lights': {'power': 1000.0, 'use_factor': 0.8, 'hours_operation': '8h'},
|
| 698 |
'equipment': {'power': 500.0, 'use_factor': 0.7, 'hours_operation': '8h'},
|
| 699 |
+
'infiltration': {'flow_rate': 0.05, 'height': 3.0, 'crack_length': 20.0, 'crack_width': 2.0},
|
| 700 |
'ventilation': {'flow_rate': 0.1},
|
| 701 |
'operating_hours': '8:00-18:00'
|
| 702 |
}
|
|
|
|
| 706 |
}
|
| 707 |
|
| 708 |
# Calculate design loads
|
| 709 |
+
design_loads = calculator.calculate_design_heating_load(
|
| 710 |
+
components, outdoor_conditions, indoor_conditions, internal_loads,
|
| 711 |
+
include_internal_gains_as_heating_source=True # ENHANCEMENT: Include internal gains as heating sources
|
| 712 |
+
)
|
| 713 |
summary = calculator.calculate_heating_load_summary(design_loads)
|
| 714 |
|
| 715 |
# Log results
|
|
|
|
| 719 |
logger.info(f"Floor Load: {design_loads['floors']:.2f} W")
|
| 720 |
logger.info(f"Window Load: {design_loads['windows']:.2f} W")
|
| 721 |
logger.info(f"Door Load: {design_loads['doors']:.2f} W")
|
| 722 |
+
logger.info(f"Skylight Load: {design_loads['skylights']:.2f} W") # ENHANCEMENT: Added skylight load
|
| 723 |
logger.info(f"Infiltration Sensible Load: {design_loads['infiltration_sensible']:.2f} W")
|
| 724 |
logger.info(f"Infiltration Latent Load: {design_loads['infiltration_latent']:.2f} W")
|
| 725 |
logger.info(f"Ventilation Sensible Load: {design_loads['ventilation_sensible']:.2f} W")
|
|
|
|
| 734 |
|
| 735 |
# Calculate monthly loads
|
| 736 |
monthly_loads = calculator.calculate_monthly_heating_loads(
|
| 737 |
+
components, outdoor_conditions, indoor_conditions, internal_loads, monthly_temps,
|
| 738 |
+
include_internal_gains_as_heating_source=True # ENHANCEMENT: Include internal gains as heating sources
|
| 739 |
)
|
| 740 |
logger.info("Monthly Heating Loads (kW):")
|
| 741 |
for month, load in monthly_loads.items():
|