1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683 684 685 686 687 688 689 690 691 692 693 694 695 696 697 698 699 700 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 738 739 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 771 772 773 774 775 776 777 778 779 780 781 782 783 784 785 786 787 788 789 790 791 792 793 794 795 796 797 798 799 800 801 802 803 804 805 806 807 808 809 810 811 812 813 814 815 816 817 818 819 820 821 822 823 824 825 826 827 828 829 830 831 832 833 834 835 836 837 838 839 840 841 842 843 844 845 846 847 848 849 850 851 852 853 854 855 856 857 858 859 860 861 862 863 864 865 866 867 868 869 870 871 872 873 874 875 876 877 878 879 880 881 882 883 884 885 886 887 888 889 890 891 892 893 894 895 896 897 898 899 900 901 902 903 904 905 906 907 908 909 910 911 912 913 914 915 916 917 918 919 920 921 922 923 924 925 926 927 928 929 930 931 932 933 934 935 936 937 938 939 940 941 942 943 944 945 946 947 948 949 950 951 952 953 954 955 956 957 958 959 960 961 962 963 964 965 966 967 968 969 970 971 972 973 974 975 976 977 978 979 980 981 982 983 984 985 986 987 988 989 990 991 992 993 994 995 |
# FDAM: Fire Damage Assessment Methodology
## A Systematic Framework for Fire Restoration Industrial Hygiene Documentation
**Version 4.0.1 | January 2026**
**Developed in partnership:** IHC and GVO
**Empirical Validation Analysis:** January 2026 (QVC Distribution Center March 2023, Our Lady of Victory February 2025)
---
## Document Control
| Version | Date | Changes |
|---------|------|---------|
| 3.0 | January 2026 | Standards verification; ACH revised to 4 minimum per NADCA ACR 2021; metals aligned with BNL SOP IH75190; Public/Childcare lead updated to EPA/HUD October 2024 |
| 4.0 | January 2026 | Empirical validation integration; dual lab format support; regulatory justification blocks; ceiling deck protocols; reclean/retest procedures; deliverable consolidation; appendix restructure |
| 4.0.1 | January 2026 | EAA Method Guide integration: combustion particle definitions (soot/char/ash); qualitative observation checklist; unit conversion reference (cts/mm² to cts/cm²); EAA classification cross-reference |
---
## Executive Summary
FDAM is a systematic framework for assessing fire-damaged properties and generating scientifically defensible restoration documentation. The methodology synthesizes regulatory standards, industry guidance, and empirical field data from IHC fire restoration projects.
**FDAM produces three deliverables:**
1. **Cleaning Specification / Scope of Work** — Scope, methods, labor, equipment, and acceptance criteria
2. **Results Interpretation** — Threshold justification, regulatory basis, and pass/fail determination
3. **Executive Summary Report** — Completion verification and compliance documentation
**Standards Basis:**
- Metals clearance: BNL SOP IH75190 (Rev23, 06/23/17)
- Non-Operational alternative: Army/Air Force National Guard Indoor Firing Range Guidelines (200 µg/ft²)
- Air filtration: NADCA ACR 2021 (4 ACH minimum)
- Zone framework: IICRC/RIA/CIRI Technical Guide (December 2025)
- Particulate clearance: IHC professional judgment with empirical validation
---
## Part 1: Methodology Foundation
### 1.1 Scientific Basis
FDAM synthesizes:
- **Regulatory frameworks:** OSHA Technical Manual, NIOSH sampling methods, EPA clearance standards
- **Industry standards:** IICRC S700/S760, IICRC/RIA/CIRI Technical Guide, NADCA ACR, RIA Fire & Smoke Damage Repair
- **Published guidance:** BNL SOP IH75190, AIHA Technical Guide for Wildfire Impact Assessments
- **Empirical validation:** IHC field data from commercial fire restoration projects (see Appendix B)
### 1.2 Regulatory Framework
| Source | Application | Status |
|--------|-------------|--------|
| BNL SOP IH75190 (Rev23) | Surface wipe clearance for metals | **Primary - verified** |
| Army/Air Force National Guard Guidelines | Non-Operational lead alternative (200 µg/ft²) | **Primary - verified** |
| EPA/HUD Lead Dust Hazard Standards (October 2024) | Public/Childcare lead clearance | **Primary - verified** |
| OSHA Technical Manual, Section II Ch. 2 | Surface contaminant methodology, facility classification | Referenced |
| NIOSH Method 9100 | Surface wipe sampling procedures | Referenced |
| 29 CFR 1910.1025 | Lead housekeeping requirements | Referenced |
| 29 CFR 1910.1018 | Arsenic housekeeping requirements | Referenced |
| 29 CFR 1910.1027 | Cadmium housekeeping requirements | Referenced |
| NADCA ACR 2021 | Air filtration requirements | **Primary - verified** |
| IICRC/RIA/CIRI Technical Guide (Dec 2025) | Zone-based assessment | **Primary - verified** |
| IICRC S520 | Mold remediation (cross-reference for fungal co-occurrence) | Referenced |
### 1.3 Threshold Classification
**Standards-Based Thresholds:** Values from published, peer-reviewed, or regulatory sources with explicit citations.
**Professional Judgment Thresholds:** Values developed through field experience where no published standards exist. Explicitly labeled with empirical validation data where available.
### 1.4 Metals Clearance Thresholds
**Source:** BNL SOP IH75190, Attachment 9.3 (Rev23, 06/23/17)
| Metal | Non-Operational | Operational | Unit | Regulatory Basis |
|-------|-----------------|-------------|------|------------------|
| Lead (Pb) | 22 | 500 | µg/100cm² | 29 CFR 1910.1025 |
| Cadmium (Cd) | 3.3 | 50 | µg/100cm² | 29 CFR 1910.1027 |
| Arsenic (As) | 6.7 | 100 | µg/100cm² | 29 CFR 1910.1018 |
**Unit Conversions:**
- µg/100cm² × 9.29 = µg/ft²
- Lead Non-Op: 22 µg/100cm² ≈ 204 µg/ft²
**Alternative Non-Operational Reference:**
Army and Air Force National Guard "Guidelines and Procedures for Rehabilitation and Conversion of Indoor Firing Ranges" establishes 200 µg/ft² as acceptable surface contamination for spaces converted to general use. This is consistent with BNL Non-Operational threshold (22 µg/100cm² ≈ 204 µg/ft²).
**Public/Childcare Thresholds (EPA/HUD October 2024):**
| Surface | Threshold | Unit |
|---------|-----------|------|
| Floors | 0.54 | µg/100cm² |
| Window Sills | 4.3 | µg/100cm² |
| Window Troughs | 4.3 | µg/100cm² |
### 1.5 Combustion Particle Definitions
Fire/combustion residue particles are classified into three categories based on combustion process:
| Category | Definition | Morphology |
|----------|------------|------------|
| **Soot** | Residues from combustion of organic resins and compounds | Aciniform (grape-like clusters); fine spherical particles; optically opaque |
| **Char** | Incomplete combustion of cellulose/vegetation material | Irregular angular fragments; carbonized plant structure visible; variable size |
| **Ash** | Residual mineral elements remaining after complete combustion (Ca, Na, Mg, K salts) | Irregular crystalline; often white/gray; variable opacity |
Source: Environmental Analysis Associates, Air-O-Cell Method Guide & Particle Atlas (2018)
**Laboratory Reporting Note:** Some laboratories report "Ash and Char" as a combined category. When combined reporting is used, interpret results against the Ash/Char threshold. When separated, sum the values for threshold comparison unless laboratory provides specific guidance.
### 1.6 Particulate Clearance Thresholds
**Classification:** Professional Judgment with Empirical Validation
| Analyte | Clearance Threshold | Unit | Validation Status |
|---------|---------------------|------|-------------------|
| Ash and Char (combined) | < 150 | particles/cm² | Validated (97.8% pass rate, n=45) |
| Aciniform Soot | < 500 | particles/cm² | Validated (91.1% pass rate, n=45) |
| Cellulose/Synthetic Fibers | < 500 | particles/cm² | Professional judgment |
| Silicates | < 1,500 | particles/cm² | Professional judgment |
**Laboratory Reference Comparison:**
| Particle Type | Lab "Normal" Range | FDAM Clearance | Position |
|---------------|-------------------|----------------|----------|
| Ash/Char | 0-300/cm² | < 150/cm² | 50% of upper normal |
| Aciniform Soot | 0-800/cm² | < 500/cm² | 62.5% of upper normal |
Source: Hayes Microbial Consulting, Estimated Normal Ranges based on ASTM D6602
FDAM clearance thresholds are set below laboratory "normal" ranges to ensure post-restoration surfaces are demonstrably cleaner than typical unaffected environments.
**Empirical Validation Summary:**
- Dataset: 45 post-restoration samples (QVC Distribution Center, March 2023)
- Pass rate at current thresholds: 93.3%
- Typical achievable post-cleaning levels: 5-15/cm² (both particle types)
- See Appendix B for complete analysis
**Application:**
- Evaluate in conjunction with visual inspection and odor assessment
- Compare to control/background samples from unaffected areas
- Results interpreted by qualified industrial hygienist
---
## Part 2: Assessment Workflow
### 2.1 Project Phases
```
PHASE 1: PRE (Pre-Restoration Evaluation)
├── Site inspection and documentation
├── Contamination mapping
├── Material inventory
├── Zone classification (Burn/Near-Field/Far-Field)
└── Output: Preliminary findings, PRA recommendation
PHASE 2: PRA (Pre-Restoration Assessment)
├── Sampling plan development
├── Tape lift and surface wipe collection
├── Laboratory analysis
├── Results interpretation
└── Output: CLEANING SPECIFICATION / SCOPE OF WORK
PHASE 3: RESTORATION (Contractor Execution)
├── Work performed per specification
└── Output: Completion notification
PHASE 4: PRV (Post-Restoration Verification)
├── Verification sampling
├── Laboratory analysis
├── Pass/fail determination
├── Reclean/retest if required
└── Output: EXECUTIVE SUMMARY REPORT
```
### 2.2 Phase 1: Pre-Restoration Evaluation (PRE)
**Field Activities:**
| Activity | Method | Data Captured |
|----------|--------|---------------|
| Site walk-through | Visual inspection | Affected areas, impact severity by zone |
| Odor assessment | Sensory | Presence/intensity/location of smoke odor |
| White wipe test | Clean cloth on surfaces | Preliminary contamination indicator |
| Photo documentation | Camera/device | Conditions, damage, access constraints |
| Material inventory | Visual identification | Surface types, quantities, restorability |
| Dimensional survey | Manual measurement | Room dimensions, surface areas |
| Zone classification | Distance from fire origin | Burn Zone / Near-Field / Far-Field |
**PRE Decision Logic:**
```
IF visible contamination is widespread
OR odor is significant
OR white wipe test shows deposits
OR materials of concern present
OR property is in Burn Zone or Near-Field Zone
THEN → Recommend PRA (laboratory assessment)
IF contamination is superficial
AND limited to small area
AND no materials of concern
AND Far-Field Zone only
THEN → May proceed directly to cleaning specification
```
### 2.3 Phase 2: Pre-Restoration Assessment (PRA)
**Sampling Protocol:**
*Tape Lift Samples (Particulate Identification):*
- Minimum 1 per distinct surface type per zone
- Additional samples at contamination gradients
- Control samples from unaffected areas (recommended)
- Analysis: Polarized light microscopy (PLM)
*Surface Wipe Samples (Metals Quantification):*
- Per NIOSH Method 9100 / BNL SOP IH75190
- 100 cm² sample area (10cm × 10cm template)
- Ghost Wipes or equivalent pre-moistened media
- Analysis: ICP-MS or ICP-OES at AIHA-accredited laboratory
**Sample Density Guidelines:**
| Area Size | Tape Lifts | Surface Wipes |
|-----------|------------|---------------|
| < 5,000 SF | 3-5 per surface type | 3-5 per surface type |
| 5,000 - 25,000 SF | 5-10 per surface type | 5-10 per surface type |
| 25,000 - 100,000 SF | 10-20 per surface type | 10-15 per surface type |
| > 100,000 SF | 20+ per surface type | 15-25 per surface type |
**Ceiling Deck Sample Density (Enhanced):**
Empirical data indicates ceiling deck surfaces exhibit higher post-cleaning contamination rates (82.4% pass rate vs 95%+ for other structural surfaces). For ceiling decks:
- Increase sample density by 50% above standard guidelines
- Minimum 1 sample per 2,500 SF (vs standard 1 per 5,000 SF)
**Qualitative Observation Checklist:**
Document the following at each sample location:
| Observation | Response | Notes |
|-------------|----------|-------|
| Smoke/fire odor present? | Yes / No | Intensity if present |
| Visible soot deposits? | Yes / No | Describe pattern |
| Large char particles observed? | Yes / No | Estimated density |
| Ash-like residue present? | Yes / No | Color, texture |
| Surface discoloration? | Yes / No | Describe |
| Dust loading or interference? | Yes / No | May affect lab accuracy |
| Burned soil/pollen/vegetation indicators? | Yes / No | Wildfire indicator |
This checklist supports visual-to-lab correlation and identifies potential analytical interferences.
### 2.4 Phase 4: Post-Restoration Verification (PRV)
**Verification Protocol:**
1. Visual inspection for dust-free surfaces
2. Odor assessment (no detectable fire/smoke odor)
3. Verification sampling (same methods as PRA)
4. Laboratory analysis
5. Results comparison to clearance criteria
6. Pass/fail determination by area
**PRV Decision Logic:**
```
IF all samples pass clearance thresholds
AND visual inspection confirms dust-free
AND no detectable odor
THEN → Issue clearance, generate Executive Summary
IF any samples exceed thresholds
THEN → Execute Reclean/Retest Protocol (Section 5.4)
```
---
## Part 3: Facility Classification
### 3.1 Classification Categories
| Classification | Definition | Lead Threshold | Applicable Standards |
|----------------|------------|----------------|---------------------|
| Operational | OSHA regulated substance used; workers trained; hygiene controls in place | 500 µg/100cm² | BNL SOP IH75190 Operational |
| Non-Operational | No regulated substance use; workers not trained; eating/drinking permitted | 22 µg/100cm² | BNL SOP IH75190 Non-Operational |
| Public-Childcare | Schools, daycare, child-occupied facilities | 0.54 µg/100cm² (floors) | EPA/HUD October 2024 |
### 3.2 Classification Determination
Facility classification is a professional judgment decision documented in the Results Interpretation deliverable. The determination considers:
- Facility use and occupancy type
- Presence of OSHA regulated substances
- Worker training status
- Personal hygiene controls (eating/drinking restrictions, handwashing requirements)
- Occupant populations (children, general public, trained workers)
### 3.3 Regulatory Justification Blocks
**Non-Operational Commercial/Industrial:**
> The indoor environment within [FACILITY] is comparable to the definition of a "Non-Operational Area" per OSHA Technical Manual Section II Chapter 2: an area where an OSHA Regulated Substance is not used and where workers are not trained in hazards and controls. Personal hygiene control practices are not in place (hand washing is not expected on exiting the area) and eating & drinking are permitted.
>
> The applicable standard for measuring cleaning performance is derived from BNL SOP IH75190 "Surface Wipe Sampling for Metals" (Rev23, 06/23/17), which establishes 22 µg/100cm² (≈204 µg/ft²) for Non-Operational areas. This threshold is consistent with the Army and Air Force National Guard "Guidelines and Procedures for Rehabilitation and Conversion of Indoor Firing Ranges" which establishes 200 µg/ft² as acceptable for spaces converted to general use.
>
> OSHA housekeeping provisions (29 CFR 1910.1025, 1910.1018, 1910.1027) require surfaces be maintained "as free as practicable" of accumulations of regulated metals.
**Operational Industrial:**
> [FACILITY] meets the definition of an "Operational Area" per OSHA Technical Manual Section II Chapter 2: an area where workers are routinely in the presence of an OSHA Regulated Substance as part of their work activity. Workers who handle the substance have been trained in hazards and controls. Substances are routinely used, handled or stored and personal hygiene control practices are in place.
>
> The applicable standard is BNL SOP IH75190 Operational threshold of 500 µg/100cm² for lead.
**Public-Childcare:**
> [FACILITY] is classified as a child-occupied facility subject to EPA/HUD Lead Dust Hazard Standards (October 2024). These standards establish protective thresholds for environments where children may be present.
>
> Applicable thresholds: 0.54 µg/100cm² (floors), 4.3 µg/100cm² (window sills and troughs).
---
## Part 4: Surface Assessment
### 4.1 Zone Classification
**Source:** IICRC/RIA/CIRI Technical Guide for Wildfire Restoration (December 2025)
| Zone | Definition | Typical Characteristics |
|------|------------|------------------------|
| Burn Zone | Direct fire involvement | Structural damage, char, complete combustion |
| Near-Field | Adjacent to burn zone, heavy smoke/heat exposure | Heavy soot deposits, heat damage, strong odor |
| Far-Field | Smoke migration without direct heat exposure | Light to moderate deposits, odor, no structural damage |
### 4.2 Condition Scale
| Condition | Visual Indicators |
|-----------|-------------------|
| Background | No visible contamination; equivalent to unaffected areas |
| Light | Faint discoloration; minimal deposits visible on white wipe |
| Moderate | Visible film or deposits; clear contamination on white wipe |
| Heavy | Thick deposits; surface texture obscured; strong odor |
| Structural Damage | Physical damage requiring repair before cleaning |
### 4.3 Disposition Matrix
**Non-Porous Surfaces (Steel, Concrete, Glass, Metal):**
| Zone | Condition | Disposition | Protocol |
|------|-----------|-------------|----------|
| Any | Background | No action | Document only |
| Far-Field | Light | Clean | Standard protocol |
| Far-Field | Moderate | Clean | Full protocol |
| Near-Field | Light | Clean | Full protocol |
| Near-Field | Moderate | Clean | Aggressive protocol, multiple passes |
| Near-Field | Heavy | Clean | Aggressive protocol with verification sampling |
| Burn Zone | Any restorable | Clean | Post-structural repair; aggressive protocol |
| Any | Structural Damage | Remove/Repair | Beyond cleaning scope |
**Porous/Semi-Porous Surfaces (Drywall, Carpet, Insulation, Acoustic Tile):**
| Zone | Condition | Disposition | Rationale |
|------|-----------|-------------|-----------|
| Far-Field | Background | Evaluate | May clean if truly superficial |
| Far-Field | Light | Evaluate/Clean | Assessment determines restorability |
| Far-Field | Moderate+ | Remove | Porous materials absorb contaminants |
| Near-Field | Light+ | Remove | Porous materials absorb contaminants and VOCs |
| Burn Zone | Any | Remove | Cannot effectively decontaminate |
### 4.4 Material Disposition Categories
**Tier 1: Generally Replace When Fire/Smoke Affected**
| Material | Rationale |
|----------|-----------|
| Fiberglass insulation | Absorbs particulates and VOCs into fiber matrix |
| Flexible ductwork | Interior lining absorbs contaminants; cannot effectively clean |
| HVAC duct interior insulation | Porous material in air pathway; recontamination risk |
| Mattresses and bedding | Multi-layer foam construction; deep penetration |
**Tier 2: Assess Based on Condition**
| Material | Clean When | Remove When |
|----------|------------|-------------|
| Carpet and pad | Far-Field, Light | Near-Field, Moderate+ |
| Drop ceiling tile | Far-Field, Light, smooth | Near-Field, or textured/acoustic |
| Drywall (painted) | Far-Field, Light | Near-Field Moderate+, or unpainted |
| Upholstered furniture | Far-Field, Light, high value | Near-Field, or low value |
**Tier 3: Generally Cleanable**
| Material | Standard Protocol |
|----------|-------------------|
| Structural steel | HEPA vac → wet wipe → rinse |
| Concrete (sealed) | Scrubber or power wash |
| Metal doors/frames | Wet wipe → rinse |
| Glass/windows | Wet wipe → squeegee |
| Smooth rigid ductwork | Per NADCA ACR |
### 4.5 Ceiling Deck Protocol
Empirical data indicates ceiling deck surfaces require enhanced attention:
**Finding:** 82.4% pass rate for ceiling decks vs 95%+ for other structural surfaces (n=45, QVC dataset)
**Requirements:**
- Increase PRV sample density by 50%
- Consider additional cleaning pass before PRV
- Document access method and cleaning thoroughness
- Priority surface for reclean if failures occur
### 4.6 Secondary Contamination
If fungal/mold growth is identified during fire damage assessment:
- Document presence, type, and extent
- Cross-reference IICRC S520 for remediation protocols
- Address fire damage and biological contamination as separate scopes
- Sequential remediation may be required (mold first if active growth)
---
## Part 5: Cleaning Protocol Framework
### 5.1 Standard Cleaning Sequence
```
Step 1: HEPA Vacuum
└── Remove loose particulate from all surfaces
Step 2: Dry Sponge (if needed)
└── Chemical sponge for char/soot on non-porous surfaces
Step 3: Wet Wipe - Alkaline Detergent
└── pH 10-12 solution for chemical residue removal
Step 4: Rinse Wipe
└── Clean water to remove detergent residue
Step 5: Degreaser (if needed)
└── For stubborn residues not removed by standard protocol
```
**Sequencing Rule:** Clean top-down (roof deck → structure → walls → floor) to prevent recontamination.
### 5.2 Surface-Specific Methods
| Surface Type | Standard Method |
|--------------|-----------------|
| Steel roof deck | HEPA vac → Wet wipe → Rinse |
| Steel joists/beams | HEPA vac → Wet wipe → Rinse |
| Steel columns | HEPA vac → Wet wipe → Rinse |
| Concrete floor | Scrubber machine + alkaline |
| CMU walls | HEPA vac → Wet wipe OR power wash |
| Metal doors | Wet wipe → Rinse |
| Rigid ductwork | Per NADCA ACR |
### 5.3 Air Filtration Requirements
**Source:** NADCA ACR 2021 Edition, Section 3.6
**Minimum Requirement:** 4 air changes per hour (ACH)
**Calculation:**
```
Units Required = (Volume CF × 4 ACH) / (Unit CFM × 60)
Where:
Volume CF = Area SF × Ceiling Height FT
Unit CFM = Rated capacity of air scrubber
```
**Example:**
```
Work Area: 50,000 SF × 30 FT = 1,500,000 CF
Units = (1,500,000 × 4) / (2,000 CFM × 60) = 50 units
```
### 5.4 Reclean/Retest Protocol
When PRV samples exceed clearance thresholds:
**Step 1: Identify Deficient Areas**
- Map failed sample locations
- Determine surface types affected
- Assess pattern (localized vs widespread)
**Step 2: Reclean Specification**
```
Failed surfaces at [SAMPLE LOCATIONS] require additional cleaning:
- [SURFACE TYPE]: Execute [PROTOCOL] with additional pass
- Extend cleaning 10 feet beyond failed sample locations
- Document cleaning date, method, and personnel
```
**Step 3: Retest Protocol**
- Resample at original failed locations
- Add samples at adjacent locations if pattern suggests broader issue
- Same laboratory and analytical methods as original PRV
**Step 4: Documentation**
- Reference original sample numbers and results
- Document reclean activities
- Report retest results with comparison to original
**Iteration:** Repeat until all samples pass clearance thresholds.
---
## Part 6: Documentation Outputs
### 6.1 Deliverable 1: Cleaning Specification / Scope of Work
**Purpose:** Define scope, methods, labor, equipment, and acceptance criteria for contractor execution.
**Required Sections:**
| Section | Content |
|---------|---------|
| Project Identification | Facility, address, contact, dates |
| Scope Summary | Affected areas, zone classifications, total SF by disposition |
| Surface Inventory | Itemized surfaces by type, area, condition, disposition |
| Work Area Preparation | Containment, air filtration calculations (4 ACH minimum) |
| Surface-Specific Procedures | Cleaning methods by surface type |
| Removal Scope | Materials requiring removal with quantities |
| Labor Estimate | Hours by task, production rates applied |
| Equipment Requirements | Air scrubbers, lifts, supplies with quantities |
| Quality Assurance Criteria | Pass/fail thresholds for PRV |
| Worker Protection | PPE, safety protocols |
**Ceiling Deck Emphasis:** When ceiling decks are in scope, include:
- Note regarding enhanced sample density at PRV
- Recommendation for additional cleaning pass
- Access method requirements
### 6.2 Deliverable 2: Results Interpretation
**Purpose:** Establish applicable thresholds with regulatory justification and determine pass/fail status.
**Required Sections:**
| Section | Content |
|---------|---------|
| Purpose Statement | Why interpretation needed, specific questions addressed |
| Facility Classification | Operational / Non-Operational / Public-Childcare determination |
| Regulatory Framework | Applicable standards with citations |
| Regulatory Justification | Justification block per Section 3.3 |
| Recommended Thresholds | Specific values with source citations |
| Results Comparison | Actual data vs thresholds |
| Pass/Fail Determination | By sample, by area, overall |
| Reclean Requirements | If applicable, per Section 5.4 |
| Response to Inquiries | Address specific stakeholder questions if applicable |
**Standards Basis Statement (Required):**
> Metals thresholds are standards-based per BNL SOP IH75190. Particulate thresholds represent professional judgment with empirical validation (see FDAM Appendix B).
### 6.3 Deliverable 3: Executive Summary Report
**Purpose:** Document completion and compliance for closeout.
**Required Sections:**
| Section | Content |
|---------|---------|
| Project Summary | Identification, scope performed, conclusions |
| Clearance Confirmation | Statement that all areas passed clearance criteria |
| Discussion of Results | Testing summary, any reclean/retest activities |
| Threshold Reference | Thresholds applied with regulatory basis |
| Chronology | Timeline of assessment, cleaning, verification |
| Appendices | Lab reports, photos, field documentation |
| Standard of Care | Professional limitations |
| Standards Basis Statement | Per Section 6.2 |
---
## Part 7: Validation Requirements
### 7.1 Threshold Validation Status
| Category | Status | Source | Validation |
|----------|--------|--------|------------|
| Metals (Pb, Cd, As) | **Verified** | BNL SOP IH75190 | Standards-based |
| Particulates | **Validated** | IHC + empirical data | 93.3% pass rate (n=45) |
| ACH requirements | **Verified** | NADCA ACR 2021 | Standards-based |
| Sample density | Professional Judgment | Internal guidance | Ongoing refinement |
### 7.2 Validation Criteria
Thresholds are validated when:
- >90% first-pass clearance rate with proper cleaning
- <5% false negatives
- Correlation with absence of occupant complaints post-restoration
### 7.3 Ongoing Data Collection
For threshold refinement, collect:
- Condition assessment + lab result + clearance outcome (paired)
- Surface type performance data
- Reclean frequency by surface type
- Control/background sample baselines
---
## Part 8: System Architecture
### 8.1 SmokeScan Implementation
```
FIELD DEVICE
├── Project/building/zone/room hierarchy
├── Zone classification with distance documentation
├── Surface inventory (type, material, condition, area)
├── Photo capture with metadata
├── Sample location documentation
└── Offline capability with sync
CLOUD PLATFORM
├── Project data management
├── Lab result entry and threshold comparison
├── SOW calculations (quantities, labor, equipment)
├── Document generation
├── Pass/fail determination with threshold source flagging
└── Report export
```
### 8.2 Calculation Engine
**Surface Area Aggregation:**
```
Total by Type = Σ(Surface.area) WHERE Surface.type = [type]
Total by Disposition = Σ(Surface.area) WHERE Surface.disposition = [action]
```
**Equipment Sizing:**
```
Air Scrubbers = (Total Volume × 4 ACH) / (Unit CFM × 60)
```
**Pass/Fail Determination:**
```
FOR each Result:
Threshold = Lookup(Analyte, Classification)
ThresholdSource = Lookup(Analyte, Source)
IF Result < Threshold THEN Pass ELSE Fail
FLAG if ThresholdSource = "Professional Judgment"
```
---
## Part 9: Future Research
### 9.1 Field Screening Methods
**Optical Density Approach:**
Develop calibrated visual assessment correlating reflectance measurements to contamination levels.
**Research Questions:**
- Can OD measurements correlate with tape lift particle counts?
- What calibration protocol provides reliable results?
### 9.2 Control Sample Protocol
**Decision Required:** Determine whether control/background samples should be mandatory for relative comparison, or if absolute thresholds are sufficient.
**Options:**
- A: Mandatory control sample with relative pass/fail logic
- B: Control samples recommended but absolute thresholds authoritative
- C: Control samples required only for disputed results
### 9.3 Surface-Specific Threshold Refinement
With additional data collection, evaluate whether surface-specific thresholds are warranted (e.g., tighter thresholds for ceiling decks given higher failure rates).
---
## Appendix A: Lab Result Interpretation Framework
### A.1 Supported Laboratory Formats
FDAM supports two primary laboratory reporting formats:
**Format 1: Quantitative (particles/cm²)**
- Labs: Hayes Microbial, EMSL, others
- Direct comparison to FDAM thresholds
- Preferred format for pass/fail determination
**Format 2: Semi-Quantitative (% particles per field at 400x)**
- Labs: N.G. Carlson Analytical, EAA Baxter methodology
- Requires interpretation guidance
- Methodological differences from Format 1
### A.2 Format 1: Quantitative Interpretation
Direct threshold comparison:
| Analyte | Result | Threshold | Determination |
|---------|--------|-----------|---------------|
| Ash/Char | [value]/cm² | < 150/cm² | PASS if < 150 |
| Aciniform Soot | [value]/cm² | < 500/cm² | PASS if < 500 |
### A.3 Format 2: Semi-Quantitative Interpretation
**Source:** EAA Air-O-Cell Method Guide & Particle Atlas (2018); EMSL Fire & Smoke Damage Guide 2021
| % per Field (400x) | Lab Interpretation | FDAM Guidance |
|--------------------|-------------------|---------------|
| < 1% | Typical low | Presumed PASS - consistent with clearance |
| < 3% | Upper background | Presumed PASS - within acceptable range |
| 3-10% | Moderate impact | Professional judgment required |
| > 10% | Significant impact | Presumed FAIL - additional cleaning likely required |
**Methodological Caveat:**
Percentage-per-field and particles/cm² are fundamentally different analytical approaches. The guidance above represents professional correlation, not mathematical conversion. When results fall in the 3-10% range, consider:
- Visual condition at sample location
- Comparison to control samples
- Overall project context
- Retesting with quantitative methodology if determination is critical
### A.4 Decision Logic
```
INPUT: Lab Result + Format + Facility Classification
STEP 1: Identify Format
IF particles/cm² → Use A.2 direct comparison
IF % per field → Use A.3 interpretation guidance
STEP 2: Determine Threshold
Metals → Per Facility Classification (Section 3.1)
Particulates → Standard thresholds (Section 1.6)
STEP 3: Compare and Determine
IF Result < Threshold → PASS
IF Result > Threshold → FAIL
IF Semi-quantitative in judgment range → Flag for professional review
STEP 4: Document
Record result, threshold, source, determination
Flag professional judgment thresholds
```
### A.5 Laboratory Selection Guidance
When selecting laboratories:
- Confirm reporting format before submission
- Request particles/cm² format when available
- Ensure consistent methodology across PRA and PRV sampling
- Request differentiation notes if atypical particles observed
### A.6 Unit Conversion Reference
Laboratories may report surface particle concentrations in different units. Use the following conversions:
**Area Conversions:**
```
1 cm² = 100 mm²
cts/mm² × 100 = cts/cm²
cts/cm² ÷ 100 = cts/mm²
```
**Common Laboratory Unit Formats:**
| Lab Format | Unit | Conversion to FDAM (cts/cm²) |
|------------|------|------------------------------|
| Hayes Microbial | cts/cm² | Direct comparison |
| EAA | cts/mm² | Multiply by 100 |
| N.G. Carlson | % per field | Use Appendix A.3 guidance |
**Example Conversion:**
- EAA reports: 5.0 cts/mm² fire residue
- FDAM equivalent: 5.0 × 100 = 500 cts/cm²
- Threshold comparison: 500 cts/cm² vs <150 (Ash/Char) = FAIL
**EAA Classification to FDAM Threshold Comparison:**
| EAA Classification | EAA (cts/mm²) | Converted (cts/cm²) | FDAM Status |
|--------------------|---------------|---------------------|-------------|
| Low | <1.0 | <100 | PASS |
| Typical-low | 1.0-5.0 | 100-500 | Evaluate vs threshold |
| Low-moderate | 5.0-10 | 500-1,000 | Likely FAIL |
| Moderate | 10-50 | 1,000-5,000 | FAIL |
| High | >50 | >5,000 | FAIL |
FDAM clearance thresholds (150 cts/cm² ash/char, 500 cts/cm² aciniform) fall within or at the upper boundary of EAA's "Typical-low" classification (100-500 cts/cm²), confirming FDAM thresholds are appropriately conservative for post-restoration clearance.
---
## Appendix B: Empirical Validation Data
### B.1 QVC Distribution Center Dataset
**Project:** QVC Outbound Fire Loss Restoration
**Location:** Rocky Mount, NC
**Date:** March 2023
**Sample Type:** Post-Restoration Verification (PRV)
**Sample Count:** 45 Bio-Tape samples (1.00 cm²)
**Laboratory:** Hayes Microbial Consulting
**Facility Classification:** Non-Operational Commercial
### B.2 Results Summary
**Aciniform-like Soot:**
| Statistic | Value |
|-----------|-------|
| Non-Detect | 21 samples (46.7%) |
| Range (detected) | 1 - 2,200/cm² |
| Median (detected) | 4.5/cm² |
| 90th Percentile | 65/cm² |
| Pass Rate | 91.1% (41/45) |
**Ash and Char:**
| Statistic | Value |
|-----------|-------|
| Non-Detect | 2 samples (4.4%) |
| Range (detected) | 1 - 440/cm² |
| Median (detected) | 5/cm² |
| 90th Percentile | 60/cm² |
| Pass Rate | 97.8% (44/45) |
**Combined Pass/Fail:**
| Status | Count | Percentage |
|--------|-------|------------|
| Both Pass | 42 | 93.3% |
| Any Fail | 3 | 6.7% |
### B.3 Surface Type Analysis
| Surface Type | Samples | Pass Rate |
|--------------|---------|-----------|
| Ceiling Deck (CD) | 17 | 82.4% |
| Ceiling Joist (CJ) | 20 | 95.0% |
| Beam | 6 | 100% |
| Column | 1 | 100% |
| Pipe | 1 | 100% |
**Finding:** Ceiling decks exhibit significantly lower pass rates, driving the ceiling deck emphasis protocol in Section 4.5.
### B.4 Failed Sample Analysis
| Sample | Location | Aciniform | Ash/Char | Failure |
|--------|----------|-----------|----------|---------|
| 02 | B2-C2 Grid - Ceiling Deck | 2,200/cm² | 4/cm² | Aciniform |
| 06 | D2-E2 Grid - Ceiling Deck | 1,320/cm² | 15/cm² | Aciniform |
| 12 | E3-F3 Grid - CJ Horizontal | 8/cm² | 440/cm² | Ash/Char |
All failures were addressed through reclean/retest protocol and subsequently passed.
### B.5 Laboratory Reference Ranges
**Source:** Hayes Microbial Consulting, based on ASTM D6602
| Particle Type | Normal Surface Range |
|---------------|---------------------|
| Ash/Char | 0-300/cm² |
| Aciniform Soot | 0-800/cm² |
| Cellulose Fibers | 0-1,600/cm² |
| Synthetic Fibers | 0-1,600/cm² |
| Silicates | 0-2,800/cm² |
These ranges represent typical environments, not post-fire clearance criteria. FDAM thresholds are set below these ranges to ensure demonstrably clean post-restoration conditions.
### B.6 Our Lady of Victory Dataset
**Project:** Our Lady of Victory (Catholic School)
**Location:** Minnesota
**Date:** February 2025
**Sample Type:** Assessment
**Sample Count:** 55 tease-tape samples
**Laboratory:** N.G. Carlson Analytical
**Facility Classification:** Public-Childcare
**Methodology:** Semi-quantitative (% particles per field at 400x)
**Distribution by Impact Level:**
| Impact Level | Samples | Percentage |
|--------------|---------|------------|
| No Char/No Soot | 14 | 27% |
| Typical Low (<1%) | 25 | 48% |
| Upper Background (<3%) | 7 | 13% |
| Moderate (3-10%) | 5 | 10% |
| Significant (>10%) | 1 | 2% |
**Pattern Observation:** Basement and lower-level areas showed higher contamination, consistent with smoke stratification.
---
## Appendix C: Deliverable Templates
### C.1 Cleaning Specification / SOW - Key Language Blocks
**Scope Statement:**
> [FACILITY] sustained fire damage on [DATE]. Industrial Hygiene Consulting, Corp. (IHC) conducted Pre-Restoration Assessment on [DATE]. Based on laboratory analysis and field assessment, the following cleaning specification establishes scope, methods, and acceptance criteria for fire residue restoration.
**Zone Summary Table:**
```
| Zone | Area (SF) | Condition | Disposition |
|------|-----------|-----------|-------------|
| [Zone ID] | [SF] | [Condition] | Clean/Remove |
```
**Air Filtration Calculation:**
> Work area volume: [SF] × [Height] = [CF]
> Required ACH: 4 (NADCA ACR 2021)
> Air scrubber capacity: [CFM] per unit
> Units required: ([CF] × 4) / ([CFM] × 60) = [Units]
**Acceptance Criteria:**
> Post-restoration verification sampling will be conducted per FDAM methodology. Clearance thresholds:
> - Ash and Char: < 150 particles/cm²
> - Aciniform Soot: < 500 particles/cm²
> - Lead: [Threshold] µg/100cm² per [Classification] standards
>
> Surfaces exceeding thresholds require reclean and retest until passing.
### C.2 Results Interpretation - Key Language Blocks
**Purpose Statement:**
> IHC provides this results interpretation to establish applicable clearance thresholds for [FACILITY] based on facility classification and regulatory framework.
**Classification Determination:**
> [Insert applicable regulatory justification block from Section 3.3]
**Threshold Table:**
```
| Analyte | Threshold | Unit | Source |
|---------|-----------|------|--------|
| Lead | [value] | µg/100cm² | [BNL/EPA-HUD] |
| Ash/Char | 150 | particles/cm² | IHC/FDAM |
| Aciniform | 500 | particles/cm² | IHC/FDAM |
```
**Pass/Fail Summary:**
> Of [N] samples collected, [X] passed all clearance thresholds. [Y] samples exceeded thresholds and require reclean/retest per Section 5.4.
**Standards Basis Statement:**
> Metals thresholds are standards-based per BNL SOP IH75190 (Rev23, 06/23/17). Particulate thresholds represent professional judgment developed through IHC field experience with empirical validation (93.3% pass rate, n=45).
### C.3 Executive Summary - Key Language Blocks
**Clearance Statement:**
> Based on post-restoration verification testing conducted [DATE], all tested surfaces within [FACILITY] meet applicable clearance criteria. The fire residue restoration is complete and the facility is cleared for reoccupancy.
**Testing Summary:**
> [N] tape lift samples and [N] surface wipe samples were collected from [AREAS]. All results were below applicable thresholds.
**Threshold Reference:**
> Clearance thresholds applied:
> - Lead: [value] µg/100cm² (BNL SOP IH75190, Non-Operational)
> - Particulates: < 150/cm² ash/char, < 500/cm² aciniform (IHC/FDAM professional judgment with empirical validation)
---
## Appendix D: Reference Standards Compendium
### D.1 Primary Standards (Verified)
| Standard | Title | Version | Application |
|----------|-------|---------|-------------|
| BNL SOP IH75190 | Surface Wipe Sampling for Metals | Rev23, 06/23/17 | Metals clearance thresholds |
| EPA/HUD Lead Dust Hazard Standards | Lead Dust Hazard Standards | October 2024 | Public-Childcare lead thresholds |
| NADCA ACR | Assessment, Cleaning and Restoration of HVAC Systems | 2021 Edition | Air filtration requirements |
| IICRC/RIA/CIRI Technical Guide | Technical Guide for Wildfire Restoration | December 2025 | Zone framework |
| Army/Air Force National Guard | Guidelines for Indoor Firing Range Rehabilitation | Current | Non-Operational lead alternative |
### D.2 Referenced Standards
| Standard | Application |
|----------|-------------|
| OSHA 29 CFR 1910.1025 | Lead housekeeping requirements |
| OSHA 29 CFR 1910.1018 | Arsenic housekeeping requirements |
| OSHA 29 CFR 1910.1027 | Cadmium housekeeping requirements |
| OSHA Technical Manual Section II Ch. 2 | Surface contaminant methodology |
| NIOSH Method 9100 | Surface wipe sampling procedures |
| IICRC S700 | Standard for Fire and Smoke Damage Restoration |
| IICRC S520 | Standard for Mold Remediation |
| ASTM D6602 | Sampling and Testing of Carbon Black |
### D.3 Laboratory References
| Reference | Application |
|-----------|-------------|
| Environmental Analysis Associates (EAA) Air-O-Cell Method Guide & Particle Atlas (2018) | Combustion particle definitions; classification ranges; unit conversion reference; semi-quantitative interpretation |
| EMSL Fire & Smoke Damage Guide 2021 | Sampling procedures |
| Hayes Microbial Normal Ranges | Reference comparison (ASTM D6602 based) |
**Note on EAA:** Environmental Analysis Associates, founded by Daniel Baxter (inventor of the Air-O-Cell sampler), maintains 30+ years of indoor air quality data. Their classification system provides independent validation of FDAM threshold positioning. EAA reports in cts/mm² (convert to cts/cm² by multiplying by 100).
---
*FDAM v4.0.1 — End of Document*
|