aedaf74 | 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 | # Copyright (c) Meta Platforms, Inc. and affiliates.
# All rights reserved.
#
# This source code is licensed under the BSD-style license found in the
# LICENSE file in the root directory of this source tree.
"""
Power subsystem simulation: UPS, PDU, Generator, ATS.
Models the electrical power chain from utility/generator through UPS and PDU
to IT loads. Tracks efficiency losses, battery state-of-charge, generator
fuel consumption, and automatic transfer switching.
Physics references:
- UPS quadratic loss model: APC White Paper 108
- PDU three-phase power: P = √3 × V_LL × I_L × PF
- Generator fuel: linear with load fraction + 10% idle
- ATS transfer: mechanical switch timing (50-200 ms)
"""
from __future__ import annotations
import math
from dataclasses import dataclass, field
from ..config import (
ATSConfig,
GeneratorConfig,
PDUConfig,
PowerConfig,
UPSConfig,
)
from .types import (
ATSPosition,
ATSState,
GeneratorState,
GensetState,
PDUState,
PowerState,
UPSMode,
UPSState,
)
# ---------------------------------------------------------------------------
# Power step result
# ---------------------------------------------------------------------------
@dataclass
class PowerAlarm:
"""A power subsystem alarm."""
component: str # e.g. "UPS-1", "PDU-A1", "GEN-1", "ATS-1"
alarm_type: str # e.g. "on_battery", "low_battery", "overload", "fuel_low"
severity: str # "warning", "critical"
message: str
value: float = 0.0 # Relevant numeric value (SOC, load%, fuel level, etc.)
@dataclass
class PowerStepResult:
"""Result of a single power simulation step."""
total_ups_loss_kw: float = 0.0
total_pdu_loss_kw: float = 0.0
total_power_overhead_kw: float = 0.0
generator_output_kw: float = 0.0
generator_fuel_remaining_liters: float = 0.0
utility_available: bool = True
on_generator: bool = False
power_available: bool = True
alarms: list[PowerAlarm] = field(default_factory=list)
# ---------------------------------------------------------------------------
# Power simulation
# ---------------------------------------------------------------------------
class PowerSimulation:
"""Simulates the datacenter power distribution chain.
Power flow:
Utility/Generator → ATS → UPS(es) → PDU(s) → IT Load
Each step():
1. ATS: detect utility loss/restoration, manage transfer
2. Generator: state machine (off → start_delay → cranking → warming → ready → loaded)
3. UPS: compute efficiency, manage battery SOC
4. PDU: compute losses, check phase currents
"""
def __init__(self, power_config: PowerConfig, it_load_kw: float = 160.0) -> None:
self._config = power_config
self._state = self._init_state(power_config)
self._it_load_kw = it_load_kw
@property
def state(self) -> PowerState:
return self._state
@staticmethod
def _init_state(config: PowerConfig) -> PowerState:
"""Initialize power state from configuration."""
ups_units = []
for uc in config.ups_units:
ups = UPSState(
unit_id=uc.unit_id,
mode=UPSMode(uc.initial_mode),
rated_capacity_kw=uc.rated_capacity_kw,
loss_c0=uc.loss_c0,
loss_c1=uc.loss_c1,
loss_c2=uc.loss_c2,
battery_capacity_kwh=uc.battery_capacity_kwh,
battery_discharge_efficiency=uc.battery_discharge_efficiency,
battery_aging_factor=uc.battery_aging_factor,
recharge_rate_kw=uc.recharge_rate_kw,
battery_soc=1.0,
)
ups_units.append(ups)
pdus = []
for pc in config.pdus:
pdu = PDUState(
pdu_id=pc.pdu_id,
voltage_ll_v=pc.voltage_ll_v,
max_current_per_phase_a=pc.max_current_per_phase_a,
num_phases=pc.num_phases,
breaker_rating_a=pc.breaker_rating_a,
efficiency=pc.efficiency,
continuous_derating=pc.continuous_derating,
)
pdus.append(pdu)
gen_cfg = config.generator
generator = GensetState(
gen_id=gen_cfg.gen_id,
rated_capacity_kw=gen_cfg.rated_capacity_kw,
start_delay_s=gen_cfg.start_delay_s,
crank_time_s=gen_cfg.crank_time_s,
warmup_time_s=gen_cfg.warmup_time_s,
cooldown_time_s=gen_cfg.cooldown_time_s,
fuel_tank_liters=gen_cfg.fuel_tank_liters,
fuel_level_liters=gen_cfg.fuel_tank_liters,
consumption_lph_full=gen_cfg.consumption_lph_full,
)
ats_cfg = config.ats
ats = ATSState(
ats_id=ats_cfg.ats_id,
transfer_time_ms=ats_cfg.transfer_time_ms,
retransfer_delay_s=ats_cfg.retransfer_delay_s,
)
return PowerState(
ups_units=ups_units,
pdus=pdus,
generator=generator,
ats=ats,
utility_available=config.utility_available,
utility_voltage_v=config.utility_voltage_v,
)
def step(self, dt_s: float, it_load_kw: float) -> PowerStepResult:
"""Advance the power simulation by dt_s seconds.
Args:
dt_s: Timestep in seconds.
it_load_kw: Total IT power demand in kW.
Returns:
PowerStepResult with losses, alarms, and status.
"""
self._it_load_kw = it_load_kw
alarms: list[PowerAlarm] = []
# 1. ATS logic: detect utility state changes
self._step_ats(dt_s, alarms)
# 2. Generator state machine
self._step_generator(dt_s, alarms)
# 3. Determine if load-side power is available
power_available = self._state.power_available
# 4. UPS: efficiency, battery, losses
total_ups_loss = self._step_ups_units(dt_s, it_load_kw, alarms)
# 5. PDU: losses, phase currents
total_pdu_loss = self._step_pdus(it_load_kw, alarms)
return PowerStepResult(
total_ups_loss_kw=total_ups_loss,
total_pdu_loss_kw=total_pdu_loss,
total_power_overhead_kw=total_ups_loss + total_pdu_loss,
generator_output_kw=self._state.generator.output_power_kw,
generator_fuel_remaining_liters=self._state.generator.fuel_level_liters,
utility_available=self._state.utility_available,
on_generator=self._state.on_generator,
power_available=power_available,
alarms=alarms,
)
# -------------------------------------------------------------------
# ATS
# -------------------------------------------------------------------
def _step_ats(self, dt_s: float, alarms: list[PowerAlarm]) -> None:
"""Handle ATS transfer logic."""
ats = self._state.ats
gen = self._state.generator
utility_ok = self._state.utility_available
if ats.position == ATSPosition.UTILITY:
if not utility_ok:
# Utility lost — initiate transfer to generator
ats.position = ATSPosition.TRANSFERRING
ats.transfer_elapsed_ms = 0.0
ats.retransfer_timer_s = 0.0
# Start generator if not already running
if gen.state == GeneratorState.OFF:
gen.state = GeneratorState.START_DELAY
gen.state_elapsed_s = 0.0
alarms.append(PowerAlarm(
component=ats.ats_id,
alarm_type="utility_lost",
severity="critical",
message="Utility power lost, initiating transfer to generator",
))
elif ats.position == ATSPosition.TRANSFERRING:
ats.transfer_elapsed_ms += dt_s * 1000.0
if ats.transfer_elapsed_ms >= ats.transfer_time_ms:
# Transfer complete
if utility_ok:
# Utility came back during transfer — go back to utility
ats.position = ATSPosition.UTILITY
ats.transfer_elapsed_ms = 0.0
elif gen.is_available:
ats.position = ATSPosition.GENERATOR
ats.transfer_elapsed_ms = 0.0
alarms.append(PowerAlarm(
component=ats.ats_id,
alarm_type="on_generator",
severity="warning",
message="Load transferred to generator",
))
# else: stay transferring until generator is ready
elif ats.position == ATSPosition.GENERATOR:
if utility_ok:
# Utility restored — wait retransfer delay before switching back
ats.retransfer_timer_s += dt_s
if ats.retransfer_timer_s >= ats.retransfer_delay_s:
ats.position = ATSPosition.TRANSFERRING
ats.transfer_elapsed_ms = 0.0
alarms.append(PowerAlarm(
component=ats.ats_id,
alarm_type="retransfer",
severity="warning",
message="Utility restored, initiating retransfer",
))
else:
ats.retransfer_timer_s = 0.0
# -------------------------------------------------------------------
# Generator
# -------------------------------------------------------------------
def _step_generator(self, dt_s: float, alarms: list[PowerAlarm]) -> None:
"""Advance generator state machine."""
gen = self._state.generator
if gen.state == GeneratorState.OFF:
gen.output_power_kw = 0.0
gen.load_fraction = 0.0
gen.fuel_consumption_lph = 0.0
return
gen.state_elapsed_s += dt_s
if gen.state == GeneratorState.START_DELAY:
if gen.state_elapsed_s >= gen.start_delay_s:
gen.state = GeneratorState.CRANKING
gen.state_elapsed_s = 0.0
elif gen.state == GeneratorState.CRANKING:
if gen.state_elapsed_s >= gen.crank_time_s:
gen.state = GeneratorState.WARMING
gen.state_elapsed_s = 0.0
alarms.append(PowerAlarm(
component=gen.gen_id,
alarm_type="engine_started",
severity="warning",
message="Generator engine started, warming up",
))
elif gen.state == GeneratorState.WARMING:
# Idle fuel consumption during warmup
gen.fuel_consumption_lph = gen.consumption_lph_full * 0.1
self._consume_fuel(gen, dt_s)
if gen.state_elapsed_s >= gen.warmup_time_s:
gen.state = GeneratorState.READY
gen.state_elapsed_s = 0.0
alarms.append(PowerAlarm(
component=gen.gen_id,
alarm_type="ready",
severity="warning",
message="Generator ready to accept load",
))
elif gen.state == GeneratorState.READY:
gen.fuel_consumption_lph = gen.consumption_lph_full * 0.1
self._consume_fuel(gen, dt_s)
# If ATS has switched to generator, transition to loaded
if self._state.ats.position == ATSPosition.GENERATOR:
gen.state = GeneratorState.LOADED
gen.state_elapsed_s = 0.0
elif gen.state == GeneratorState.LOADED:
gen.load_fraction = min(self._it_load_kw / gen.rated_capacity_kw, 1.0)
gen.output_power_kw = min(self._it_load_kw, gen.rated_capacity_kw)
gen.fuel_consumption_lph = gen.compute_fuel_consumption_lph()
self._consume_fuel(gen, dt_s)
# Check fuel level
if gen.fuel_level_liters <= 0:
gen.fuel_level_liters = 0.0
gen.state = GeneratorState.OFF
gen.output_power_kw = 0.0
alarms.append(PowerAlarm(
component=gen.gen_id,
alarm_type="fuel_exhausted",
severity="critical",
message="Generator fuel exhausted — engine shutdown",
))
elif gen.fuel_remaining_hours < 2.0:
alarms.append(PowerAlarm(
component=gen.gen_id,
alarm_type="fuel_low",
severity="warning",
message=f"Generator fuel low: {gen.fuel_level_liters:.0f}L "
f"(~{gen.fuel_remaining_hours:.1f}h remaining)",
value=gen.fuel_level_liters,
))
# If utility is back and ATS has switched away, go to cooldown
if self._state.ats.position != ATSPosition.GENERATOR:
gen.state = GeneratorState.COOLDOWN
gen.state_elapsed_s = 0.0
gen.output_power_kw = 0.0
gen.load_fraction = 0.0
elif gen.state == GeneratorState.COOLDOWN:
gen.output_power_kw = 0.0
gen.load_fraction = 0.0
gen.fuel_consumption_lph = gen.consumption_lph_full * 0.1
self._consume_fuel(gen, dt_s)
if gen.state_elapsed_s >= gen.cooldown_time_s:
gen.state = GeneratorState.OFF
gen.state_elapsed_s = 0.0
gen.fuel_consumption_lph = 0.0
alarms.append(PowerAlarm(
component=gen.gen_id,
alarm_type="shutdown",
severity="warning",
message="Generator cooldown complete, engine off",
))
@staticmethod
def _consume_fuel(gen: GensetState, dt_s: float) -> None:
"""Consume fuel for the given timestep."""
if gen.fuel_consumption_lph > 0:
consumed = gen.fuel_consumption_lph * dt_s / 3600.0 # hours → seconds
gen.fuel_level_liters = max(0.0, gen.fuel_level_liters - consumed)
# -------------------------------------------------------------------
# UPS
# -------------------------------------------------------------------
def _step_ups_units(
self, dt_s: float, it_load_kw: float, alarms: list[PowerAlarm]
) -> float:
"""Step all UPS units and return total UPS losses in kW."""
if not self._state.ups_units:
return 0.0
# Distribute IT load evenly across UPS units
load_per_ups = it_load_kw / len(self._state.ups_units)
total_loss = 0.0
for ups in self._state.ups_units:
loss = self._step_single_ups(ups, dt_s, load_per_ups, alarms)
total_loss += loss
return total_loss
def _step_single_ups(
self,
ups: UPSState,
dt_s: float,
load_kw: float,
alarms: list[PowerAlarm],
) -> float:
"""Step a single UPS unit. Returns loss in kW."""
ups.output_power_kw = load_kw
ups.load_fraction = load_kw / ups.rated_capacity_kw if ups.rated_capacity_kw > 0 else 0.0
utility_ok = self._state.utility_available
ats_ok = self._state.ats.load_powered
# Mode transitions
if ups.mode == UPSMode.FAULT:
# Fault state: no output, no charging
ups.efficiency = 0.0
ups.heat_output_kw = 0.0
ups.input_power_kw = 0.0
ups.battery_power_kw = 0.0
return 0.0
if ups.mode == UPSMode.BYPASS:
# Bypass: no UPS processing, minimal losses
ups.efficiency = 1.0
ups.heat_output_kw = 0.0
ups.input_power_kw = load_kw
ups.battery_power_kw = 0.0
return 0.0
# Check if we need to switch to battery
source_ok = utility_ok and ats_ok
if ups.mode == UPSMode.ON_BATTERY:
if source_ok:
# Source restored — switch back to normal mode
ups.mode = UPSMode.DOUBLE_CONVERSION
alarms.append(PowerAlarm(
component=ups.unit_id,
alarm_type="utility_restored",
severity="warning",
message=f"UPS {ups.unit_id} back on utility power",
))
elif not source_ok and ups.mode in (
UPSMode.DOUBLE_CONVERSION, UPSMode.LINE_INTERACTIVE, UPSMode.ECO
):
ups.mode = UPSMode.ON_BATTERY
alarms.append(PowerAlarm(
component=ups.unit_id,
alarm_type="on_battery",
severity="critical",
message=f"UPS {ups.unit_id} switched to battery",
value=ups.battery_soc,
))
# Compute efficiency based on mode
if ups.mode == UPSMode.ECO:
# Eco mode: ~99% efficiency (minimal processing)
ups.efficiency = 0.99
elif ups.mode == UPSMode.LINE_INTERACTIVE:
# Line interactive: ~97% (some processing)
ups.efficiency = min(0.97, ups.compute_efficiency() + 0.03)
else:
# Double conversion or on_battery: full quadratic model
ups.efficiency = ups.compute_efficiency()
# Compute losses
if ups.efficiency > 0:
ups_loss = load_kw * (1.0 / ups.efficiency - 1.0)
else:
ups_loss = ups.rated_capacity_kw * ups.loss_c0
ups.heat_output_kw = ups_loss
ups.input_power_kw = load_kw + ups_loss
# Battery management
if ups.mode == UPSMode.ON_BATTERY:
# Discharging: SOC decreases
# P_discharge = P_output / η_discharge (battery must supply more than output)
p_discharge = load_kw / ups.battery_discharge_efficiency if ups.battery_discharge_efficiency > 0 else load_kw
ups.battery_power_kw = p_discharge
energy_used_kwh = p_discharge * dt_s / 3600.0
effective_capacity = ups.battery_capacity_kwh * ups.battery_aging_factor
if effective_capacity > 0:
ups.battery_soc -= energy_used_kwh / effective_capacity
ups.battery_soc = max(0.0, ups.battery_soc)
ups.battery_time_remaining_s = ups.compute_battery_time_remaining_s()
ups.input_power_kw = 0.0 # Not drawing from mains
# Battery alarms
if ups.battery_soc <= 0.0:
ups.mode = UPSMode.FAULT
alarms.append(PowerAlarm(
component=ups.unit_id,
alarm_type="battery_exhausted",
severity="critical",
message=f"UPS {ups.unit_id} battery exhausted — load unprotected",
))
elif ups.battery_soc < 0.10:
alarms.append(PowerAlarm(
component=ups.unit_id,
alarm_type="battery_critical",
severity="critical",
message=f"UPS {ups.unit_id} battery critical: {ups.battery_soc*100:.0f}%",
value=ups.battery_soc,
))
elif ups.battery_soc < 0.25:
alarms.append(PowerAlarm(
component=ups.unit_id,
alarm_type="battery_low",
severity="warning",
message=f"UPS {ups.unit_id} battery low: {ups.battery_soc*100:.0f}%",
value=ups.battery_soc,
))
else:
# On mains — charge battery if not full
ups.battery_power_kw = 0.0
ups.battery_time_remaining_s = float("inf")
if ups.battery_soc < 1.0:
charge_kw = min(ups.recharge_rate_kw, ups.rated_capacity_kw * 0.1)
energy_charged_kwh = charge_kw * dt_s / 3600.0
effective_capacity = ups.battery_capacity_kwh * ups.battery_aging_factor
if effective_capacity > 0:
ups.battery_soc += energy_charged_kwh / effective_capacity
ups.battery_soc = min(1.0, ups.battery_soc)
ups.battery_power_kw = -charge_kw # Negative = charging
ups.input_power_kw += charge_kw # Charging draws additional power
# Overload alarm
if ups.load_fraction > 1.0:
alarms.append(PowerAlarm(
component=ups.unit_id,
alarm_type="overload",
severity="critical",
message=f"UPS {ups.unit_id} overloaded at {ups.load_fraction*100:.0f}%",
value=ups.load_fraction,
))
return ups_loss
# -------------------------------------------------------------------
# PDU
# -------------------------------------------------------------------
def _step_pdus(
self, it_load_kw: float, alarms: list[PowerAlarm]
) -> float:
"""Step all PDUs and return total PDU losses in kW."""
if not self._state.pdus:
return 0.0
# Distribute IT load evenly across PDUs
load_per_pdu = it_load_kw / len(self._state.pdus)
total_loss = 0.0
for pdu in self._state.pdus:
loss = self._step_single_pdu(pdu, load_per_pdu, alarms)
total_loss += loss
return total_loss
def _step_single_pdu(
self,
pdu: PDUState,
load_kw: float,
alarms: list[PowerAlarm],
) -> float:
"""Step a single PDU. Returns loss in kW."""
pdu.output_power_kw = load_kw
pdu.input_power_kw = load_kw / pdu.efficiency if pdu.efficiency > 0 else load_kw
pdu_loss = pdu.input_power_kw - pdu.output_power_kw
pdu.heat_output_kw = pdu_loss
# Compute per-phase currents (assume balanced load across phases)
# P = √3 × V_LL × I_L × PF (assume PF = 1.0 for IT loads with PFC)
if pdu.voltage_ll_v > 0:
total_current = (load_kw * 1000.0) / (math.sqrt(3) * pdu.voltage_ll_v)
per_phase = total_current / pdu.num_phases if pdu.num_phases > 0 else total_current
pdu.phase_currents_a = [per_phase] * pdu.num_phases
else:
pdu.phase_currents_a = [0.0] * pdu.num_phases
# Load fraction of derated capacity
derated = pdu.derated_capacity_kw
pdu.load_fraction = load_kw / derated if derated > 0 else 0.0
# Phase imbalance (0 for balanced load — will be nonzero when
# individual rack loads are modeled)
pdu.phase_imbalance_pct = pdu.compute_phase_imbalance()
# Check overload
max_phase_current = max(pdu.phase_currents_a) if pdu.phase_currents_a else 0.0
if max_phase_current > pdu.max_current_per_phase_a:
pdu.overload = True
alarms.append(PowerAlarm(
component=pdu.pdu_id,
alarm_type="phase_overcurrent",
severity="critical",
message=f"PDU {pdu.pdu_id} phase overcurrent: "
f"{max_phase_current:.1f}A > {pdu.max_current_per_phase_a:.0f}A",
value=max_phase_current,
))
else:
pdu.overload = False
# Breaker trip check (per-branch, simplified as aggregate)
if max_phase_current > pdu.breaker_rating_a / pdu.continuous_derating:
pdu.breaker_tripped = True
alarms.append(PowerAlarm(
component=pdu.pdu_id,
alarm_type="breaker_trip",
severity="critical",
message=f"PDU {pdu.pdu_id} breaker tripped",
value=max_phase_current,
))
# Warn on high utilization
if pdu.load_fraction > 0.80 and not pdu.overload:
alarms.append(PowerAlarm(
component=pdu.pdu_id,
alarm_type="high_utilization",
severity="warning",
message=f"PDU {pdu.pdu_id} at {pdu.load_fraction*100:.0f}% of derated capacity",
value=pdu.load_fraction,
))
return pdu_loss
# -------------------------------------------------------------------
# Mutation helpers (for agent actions)
# -------------------------------------------------------------------
def set_utility_available(self, available: bool) -> None:
"""Set utility power availability (for scenario injection)."""
self._state.utility_available = available
def set_ups_mode(self, unit_id: str, mode: UPSMode) -> bool:
"""Manually set UPS operating mode. Returns True if found."""
for ups in self._state.ups_units:
if ups.unit_id == unit_id:
ups.mode = mode
return True
return False
def inject_ups_fault(self, unit_id: str) -> bool:
"""Put a UPS into fault mode. Returns True if found."""
return self.set_ups_mode(unit_id, UPSMode.FAULT)
def clear_ups_fault(self, unit_id: str) -> bool:
"""Restore a faulted UPS to double conversion. Returns True if found."""
for ups in self._state.ups_units:
if ups.unit_id == unit_id and ups.mode == UPSMode.FAULT:
ups.mode = UPSMode.DOUBLE_CONVERSION
return True
return False
def start_generator(self) -> None:
"""Manually start the generator."""
gen = self._state.generator
if gen.state == GeneratorState.OFF:
gen.state = GeneratorState.START_DELAY
gen.state_elapsed_s = 0.0
def stop_generator(self) -> None:
"""Initiate generator cooldown/shutdown."""
gen = self._state.generator
if gen.state in (GeneratorState.READY, GeneratorState.LOADED):
gen.state = GeneratorState.COOLDOWN
gen.state_elapsed_s = 0.0
gen.output_power_kw = 0.0
gen.load_fraction = 0.0
def refuel_generator(self, liters: float | None = None) -> None:
"""Refuel the generator (default: full tank)."""
gen = self._state.generator
if liters is None:
gen.fuel_level_liters = gen.fuel_tank_liters
else:
gen.fuel_level_liters = min(
gen.fuel_level_liters + liters,
gen.fuel_tank_liters,
)
|