aedaf74 91495a2 aedaf74 91495a2 aedaf74 91495a2 aedaf74 91495a2 aedaf74 | 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 | # Copyright (c) Meta Platforms, Inc. and affiliates.
# All rights reserved.
#
# This source code is licensed under the BSD-style license found in the
# LICENSE file in the root directory of this source tree.
"""
RC thermal network simulation for datacenter zones.
Physics model (lumped-capacitance, per zone):
C_zone × dT_zone/dt = Q_IT - Q_cooling + Q_envelope + Q_internal
Where:
C_zone = C_air + C_equipment [J/K]
Q_IT = sum of rack IT loads × 1000 [W]
Q_cool = sum of CRAC cooling outputs × 1000 [W]
Q_env = (T_outside - T_zone) / R_envelope [W]
Q_int = UPS losses + PDU losses + lighting [W]
Cold aisle temperature accounts for hot-air recirculation:
T_cold_effective = (1-r) × T_supply_weighted + r × T_hot_aisle
where r is the recirculation factor (0 = perfect containment).
Hot aisle temperature from server energy balance:
T_hot = T_cold + Q_IT / (m_dot_rack × c_p)
Integration: Forward Euler with configurable dt (default 1.0 s).
Target: <1 ms per step for a 20-rack, 4-CRAC datacenter.
"""
from __future__ import annotations
from dataclasses import dataclass, field
from ..config import (
AIR_DENSITY_KG_M3,
AIR_SPECIFIC_HEAT_J_KGK,
ASHRAE_CLASSES,
DatacenterConfig,
RackConfig,
CRACConfig,
ZoneConfig,
cfm_to_m3s,
make_default_datacenter_config,
)
from .types import (
CRACFaultType,
CRACState,
CRACStatus,
DatacenterState,
RackState,
ZoneState,
)
@dataclass
class ThermalAlarm:
"""An active thermal alarm."""
rack_id: str
zone_id: str
inlet_temp_c: float
threshold_c: float
severity: str # "warning" (recommended exceeded) or "critical" (allowable exceeded)
@dataclass
class ThermalStepResult:
"""Result of a single simulation step."""
state: DatacenterState
alarms: list[ThermalAlarm] = field(default_factory=list)
total_cooling_output_kw: float = 0.0
total_cooling_power_kw: float = 0.0
energy_consumed_kwh: float = 0.0 # Energy consumed in this step
class ThermalSimulation:
"""Multi-zone RC thermal network simulation.
Owns the DatacenterState and advances it forward in time.
Each call to step() integrates the thermal ODEs by dt seconds.
"""
def __init__(self, config: DatacenterConfig | None = None):
if config is None:
config = make_default_datacenter_config()
self._config = config
self._state = self._build_initial_state(config)
self._dt = config.simulation_dt_s
@property
def state(self) -> DatacenterState:
return self._state
@property
def config(self) -> DatacenterConfig:
return self._config
@property
def dt(self) -> float:
return self._dt
# ------------------------------------------------------------------
# Initialization
# ------------------------------------------------------------------
@staticmethod
def _build_initial_state(config: DatacenterConfig) -> DatacenterState:
"""Construct the initial DatacenterState from configuration."""
zones: list[ZoneState] = []
for zc in config.zones:
racks = ThermalSimulation._build_racks(zc, zc.initial_cold_aisle_temp_c)
cracs = ThermalSimulation._build_cracs(zc)
zone = ZoneState(
zone_id=zc.zone_id,
cold_aisle_temp_c=zc.initial_cold_aisle_temp_c,
hot_aisle_temp_c=zc.initial_cold_aisle_temp_c + 15.0, # Initial estimate
humidity_rh=zc.initial_humidity_rh,
recirculation_factor=zc.recirculation_factor,
racks=racks,
crac_units=cracs,
air_volume_m3=zc.air_volume_m3,
envelope_r_kw=zc.envelope_r_kw,
ashrae_class=zc.ashrae_class,
)
zones.append(zone)
state = DatacenterState(
zones=zones,
outside_temp_c=config.outside_temp_c,
outside_humidity_rh=config.outside_humidity_rh,
lighting_power_kw=config.lighting_w_per_m2 * config.floor_area_m2 / 1000.0,
ups_loss_fraction=config.ups_loss_fraction,
pdu_loss_fraction=config.pdu_loss_fraction,
sim_time_s=0.0,
)
# Run a few settling steps so initial temps are physically consistent
sim = ThermalSimulation.__new__(ThermalSimulation)
sim._state = state
sim._config = make_default_datacenter_config()
sim._dt = 1.0
for _ in range(300):
sim._integrate_step(1.0)
return state
@staticmethod
def _build_racks(zone_config: ZoneConfig, initial_temp_c: float) -> list[RackState]:
racks: list[RackState] = []
for rc in zone_config.racks:
airflow_cfm = rc.airflow_cfm_per_kw * rc.it_load_kw
airflow_m3s = cfm_to_m3s(airflow_cfm)
thermal_mass = rc.num_servers_2u * rc.server_thermal_mass_jk
rack = RackState(
rack_id=rc.rack_id,
row=rc.row,
position=rc.position,
it_load_kw=rc.it_load_kw,
inlet_temp_c=initial_temp_c,
outlet_temp_c=initial_temp_c + 15.0, # Will be corrected by settling
airflow_m3s=airflow_m3s,
thermal_mass_jk=thermal_mass,
)
racks.append(rack)
return racks
@staticmethod
def _build_cracs(zone_config: ZoneConfig) -> list[CRACState]:
cracs: list[CRACState] = []
for cc in zone_config.crac_units:
crac = CRACState(
unit_id=cc.unit_id,
setpoint_c=cc.initial_setpoint_c,
supply_temp_c=cc.initial_setpoint_c,
fan_speed_pct=cc.initial_fan_speed_pct,
max_airflow_m3s=cfm_to_m3s(cc.max_airflow_cfm),
rated_capacity_kw=cc.rated_capacity_kw,
rated_return_temp_c=cc.rated_return_temp_c,
capacity_slope_per_c=cc.capacity_slope_per_c,
fan_rated_power_kw=cc.fan_rated_power_kw,
cop_rated=cc.cop_rated,
cop_degradation_per_c=cc.cop_degradation_per_c,
supply_temp_lag_s=cc.supply_temp_lag_s,
)
cracs.append(crac)
return cracs
# ------------------------------------------------------------------
# Simulation step
# ------------------------------------------------------------------
def step(self, dt: float | None = None) -> ThermalStepResult:
"""Advance the simulation by dt seconds.
Returns a ThermalStepResult with updated state, alarms, and energy metrics.
"""
if dt is None:
dt = self._dt
result = self._integrate_step(dt)
self._state.sim_time_s += dt
return result
def step_n(self, n: int, dt: float | None = None) -> ThermalStepResult:
"""Advance simulation by n steps. Returns result of the last step."""
result = ThermalStepResult(state=self._state)
for _ in range(n):
result = self.step(dt)
return result
def _integrate_step(self, dt: float) -> ThermalStepResult:
"""Core integration: one Forward Euler step across all zones.
Physics model — **cold aisle energy balance** (not total-zone):
The cold aisle is a mixing volume. Heat flows into/out of it:
q_crac = m_dot_crac × c_p × (T_supply − T_cold) [cooling from CRACs]
q_recirc = r × m_dot_crac × c_p × (T_hot − T_cold) [recirculated hot air]
q_env = (T_outside − T_cold) / R_envelope [building heat gain]
q_int = UPS losses + PDU losses + lighting [internal gains]
IT heat does NOT appear directly — servers move cold air to the hot
aisle, raising T_hot. IT heat affects the cold aisle only through
recirculation (hot air leaking back) and indirectly via CRAC return
temperature.
Hot aisle temperature (algebraic, not ODE):
T_hot = T_cold + Q_IT / (m_dot_rack × c_p)
CRAC return air temperature accounts for bypass airflow:
When CRAC airflow > rack airflow, excess cold air bypasses servers
and returns directly to the CRAC at T_cold, lowering the effective
return air temperature and thus CRAC cooling output.
T_return = (1 − bypass) × T_hot + bypass × T_cold
"""
state = self._state
alarms: list[ThermalAlarm] = []
total_cooling_output_kw = 0.0
total_cooling_power_kw = 0.0
total_power_kw = 0.0
for zone in state.zones:
# 1. Update CRAC supply temperatures (first-order lag toward setpoint)
for crac in zone.crac_units:
crac.update_supply_temp(dt)
# 2. Airflow quantities
q_it_w = zone.total_it_load_kw * 1000.0
m_dot_rack = zone.total_rack_airflow_m3s * AIR_DENSITY_KG_M3 # kg/s
m_dot_crac = zone.total_crac_airflow_m3s * AIR_DENSITY_KG_M3 # kg/s
# Server temperature rise [°C]
if m_dot_rack > 0:
dt_server = q_it_w / (m_dot_rack * AIR_SPECIFIC_HEAT_J_KGK)
else:
dt_server = 50.0 # No airflow → extreme rise
t_hot = zone.cold_aisle_temp_c + dt_server
# 3. Bypass fraction: excess CRAC airflow that bypasses servers
if m_dot_crac > 0 and m_dot_rack > 0:
bypass_frac = max(0.0, 1.0 - m_dot_rack / m_dot_crac)
else:
bypass_frac = 0.0
# CRAC return air temp (mixed hot exhaust + bypassed cold air)
t_return = (1.0 - bypass_frac) * t_hot + bypass_frac * zone.cold_aisle_temp_c
# 4. CRAC cooling output (based on bypass-corrected return temp)
q_cooling_extracted_w = 0.0
zone_cooling_power_kw = 0.0
for crac in zone.crac_units:
q_crac_kw = crac.compute_cooling_output_kw(t_return)
q_cooling_extracted_w += q_crac_kw * 1000.0
total_cooling_output_kw += q_crac_kw
p_crac_kw = crac.compute_power_consumption_kw(q_crac_kw, state.outside_temp_c)
zone_cooling_power_kw += p_crac_kw
total_cooling_power_kw += p_crac_kw
# 5. Cold aisle energy balance [all in Watts]
# CRAC supply mixing: each CRAC injects air into the cold aisle.
# Running CRACs inject air at their supply temp (near setpoint).
# Compressor-faulted CRACs with fans running inject air at the
# return air temp (air passes through the inactive coil unconditioned).
q_crac_mixing_w = 0.0
for crac in zone.crac_units:
crac_flow = crac.current_airflow_m3s * AIR_DENSITY_KG_M3
if crac_flow <= 0:
continue
if crac.fault_type in (CRACFaultType.COMPRESSOR, CRACFaultType.REFRIGERANT_LEAK):
effective_supply = t_return # No cooling — just recirculating
else:
effective_supply = crac.supply_temp_c
q_crac_mixing_w += crac_flow * AIR_SPECIFIC_HEAT_J_KGK * (
effective_supply - zone.cold_aisle_temp_c
)
# Hot air entering cold aisle from two mechanisms:
#
# (a) Containment recirculation: fraction r of air leaks through
# containment gaps regardless of CRAC flow balance.
# Uses max(m_dot_rack, m_dot_crac) — recirculation is driven
# by pressure differentials from whichever airflow is dominant.
# When CRACs are off, server fans still drive leakage.
r = zone.recirculation_factor
m_dot_dominant = max(m_dot_rack, m_dot_crac)
q_recirc_w = r * m_dot_dominant * AIR_SPECIFIC_HEAT_J_KGK * dt_server
# (b) Natural return: when CRAC airflow < rack airflow, servers
# exhaust more hot air than CRACs can capture. The uncaptured
# fraction returns to the cold aisle via natural convection.
# When CRACs are completely off, ALL server exhaust returns
# (= Q_IT returns to cold aisle as heat).
if m_dot_rack > 0 and m_dot_crac < m_dot_rack:
natural_return_frac = 1.0 - m_dot_crac / m_dot_rack
q_natural_return_w = (
natural_return_frac * m_dot_rack * AIR_SPECIFIC_HEAT_J_KGK * dt_server
)
else:
q_natural_return_w = 0.0
# Envelope heat gain
if zone.envelope_r_kw > 0:
q_envelope_w = (state.outside_temp_c - zone.cold_aisle_temp_c) / zone.envelope_r_kw
else:
q_envelope_w = 0.0
# Internal gains (UPS/PDU losses + lighting)
q_ups_w = zone.total_it_load_kw * state.ups_loss_fraction * 1000.0
q_pdu_w = zone.total_it_load_kw * state.pdu_loss_fraction * 1000.0
num_zones = len(state.zones) if state.zones else 1
q_lighting_w = state.lighting_power_kw * 1000.0 / num_zones
q_internal_w = q_ups_w + q_pdu_w + q_lighting_w
# 6. Net heat into cold aisle [W]
q_net_w = (
q_crac_mixing_w + q_recirc_w + q_natural_return_w
+ q_envelope_w + q_internal_w
)
# 7. Forward Euler integration
c_total = zone.compute_thermal_capacitance_jk()
if c_total > 0:
dT = q_net_w * dt / c_total
zone.cold_aisle_temp_c += dT
# 8. Update hot aisle (algebraic: T_hot = T_cold + server ΔT)
if m_dot_rack > 0:
zone.hot_aisle_temp_c = (
zone.cold_aisle_temp_c
+ q_it_w / (m_dot_rack * AIR_SPECIFIC_HEAT_J_KGK)
)
else:
zone.hot_aisle_temp_c = zone.cold_aisle_temp_c + 50.0
# 9. Update individual rack inlet/outlet temperatures
for rack in zone.racks:
rack.inlet_temp_c = zone.cold_aisle_temp_c
rack.outlet_temp_c = rack.compute_outlet_temp()
# 10. Check ASHRAE alarms
ashrae = ASHRAE_CLASSES.get(zone.ashrae_class)
if ashrae:
for rack in zone.racks:
if rack.inlet_temp_c > ashrae.allowable_max_c:
alarms.append(ThermalAlarm(
rack_id=rack.rack_id,
zone_id=zone.zone_id,
inlet_temp_c=rack.inlet_temp_c,
threshold_c=ashrae.allowable_max_c,
severity="critical",
))
elif rack.inlet_temp_c > ashrae.recommended_max_c:
alarms.append(ThermalAlarm(
rack_id=rack.rack_id,
zone_id=zone.zone_id,
inlet_temp_c=rack.inlet_temp_c,
threshold_c=ashrae.recommended_max_c,
severity="warning",
))
total_power_kw += zone.total_it_load_kw
# Energy consumed in this step [kWh]
total_facility_kw = total_power_kw + total_cooling_power_kw + (
total_power_kw * (state.ups_loss_fraction + state.pdu_loss_fraction)
+ state.lighting_power_kw
)
energy_kwh = total_facility_kw * dt / 3600.0
return ThermalStepResult(
state=state,
alarms=alarms,
total_cooling_output_kw=total_cooling_output_kw,
total_cooling_power_kw=total_cooling_power_kw,
energy_consumed_kwh=energy_kwh,
)
@staticmethod
def _compute_weighted_supply_temp(zone: ZoneState) -> float | None:
"""Flow-weighted average of CRAC supply temperatures.
T_supply_weighted = Σ(T_supply_i × m_dot_i) / Σ(m_dot_i)
Returns None if no CRACs are producing airflow.
"""
total_flow = 0.0
weighted_temp = 0.0
for crac in zone.crac_units:
flow = crac.current_airflow_m3s
if flow > 0:
weighted_temp += crac.supply_temp_c * flow
total_flow += flow
if total_flow <= 0:
return None
return weighted_temp / total_flow
# ------------------------------------------------------------------
# Mutation helpers (used by action parser in later phases)
# ------------------------------------------------------------------
def set_crac_setpoint(self, unit_id: str, setpoint_c: float) -> bool:
"""Adjust a CRAC unit's supply air temperature setpoint. Returns success."""
crac = self._find_crac(unit_id)
if crac is None:
return False
crac.setpoint_c = setpoint_c
return True
def set_crac_fan_speed(self, unit_id: str, speed_pct: float) -> bool:
"""Set CRAC fan speed (0-100%). Returns success."""
crac = self._find_crac(unit_id)
if crac is None:
return False
crac.fan_speed_pct = max(0.0, min(100.0, speed_pct))
return True
def set_crac_status(self, unit_id: str, status: CRACStatus) -> bool:
"""Change CRAC operating status. Returns success."""
crac = self._find_crac(unit_id)
if crac is None:
return False
crac.status = status
return True
def inject_crac_fault(
self, unit_id: str, fault_type: CRACFaultType
) -> bool:
"""Inject a fault into a CRAC unit. Returns success."""
crac = self._find_crac(unit_id)
if crac is None:
return False
crac.status = CRACStatus.FAULT
crac.fault_type = fault_type
return True
def clear_crac_fault(self, unit_id: str) -> bool:
"""Clear a CRAC fault and return to running. Returns success."""
crac = self._find_crac(unit_id)
if crac is None:
return False
crac.status = CRACStatus.RUNNING
crac.fault_type = CRACFaultType.NONE
return True
def set_rack_load(self, rack_id: str, load_kw: float) -> bool:
"""Change a rack's IT load. Returns success."""
rack = self._find_rack(rack_id)
if rack is None:
return False
rack.it_load_kw = max(0.0, load_kw)
# Update airflow proportionally (servers spin fans with load)
from ..config import RackConfig
default_cfm_per_kw = RackConfig().airflow_cfm_per_kw
rack.airflow_m3s = cfm_to_m3s(default_cfm_per_kw * rack.it_load_kw)
return True
def set_outside_temp(self, temp_c: float) -> None:
"""Set outside temperature."""
self._state.outside_temp_c = temp_c
def _find_crac(self, unit_id: str) -> CRACState | None:
target = unit_id.lower()
for zone in self._state.zones:
for crac in zone.crac_units:
if crac.unit_id.lower() == target:
return crac
return None
def _find_rack(self, rack_id: str) -> RackState | None:
target = rack_id.lower()
for zone in self._state.zones:
for rack in zone.racks:
if rack.rack_id.lower() == target:
return rack
return None
def find_zone_for_crac(self, unit_id: str) -> ZoneState | None:
"""Find the zone containing a given CRAC unit."""
for zone in self._state.zones:
for crac in zone.crac_units:
if crac.unit_id == unit_id:
return zone
return None
def find_zone_for_rack(self, rack_id: str) -> ZoneState | None:
"""Find the zone containing a given rack."""
for zone in self._state.zones:
for rack in zone.racks:
if rack.rack_id == rack_id:
return zone
return None
|