"""Tests for the power subsystem simulation.
Validates:
- UPS quadratic efficiency model against published data
- UPS battery discharge/charge dynamics
- PDU loss calculations and three-phase current distribution
- Generator state machine and fuel consumption
- ATS transfer timing
- Full utility-loss → generator-takeover scenario
"""
from __future__ import annotations
import math
import pytest
from dc_ops_env.config import (
ATSConfig,
GeneratorConfig,
PDUConfig,
PowerConfig,
UPSConfig,
)
from dc_ops_env.simulation.power import PowerAlarm, PowerSimulation, PowerStepResult
from dc_ops_env.simulation.types import (
ATSPosition,
GeneratorState,
UPSMode,
)
# ---------------------------------------------------------------------------
# Helpers
# ---------------------------------------------------------------------------
def make_simple_power_config(
num_ups: int = 1,
num_pdus: int = 1,
ups_capacity_kw: float = 500.0,
) -> PowerConfig:
"""Create a minimal power config for testing."""
return PowerConfig(
ups_units=[
UPSConfig(unit_id=f"UPS-{i+1}", rated_capacity_kw=ups_capacity_kw)
for i in range(num_ups)
],
pdus=[
PDUConfig(pdu_id=f"PDU-{i+1}")
for i in range(num_pdus)
],
generator=GeneratorConfig(),
ats=ATSConfig(),
)
# ===========================================================================
# UPS Efficiency Tests
# ===========================================================================
class TestUPSEfficiency:
"""Validate UPS quadratic loss model against reference data.
APC WP-108 Table: 500 kVA double-conversion UPS efficiency
25% load → ~90.5%
50% load → ~93.6%
75% load → ~94.0%
100% load → ~93.9%
"""
def test_efficiency_at_25_percent(self) -> None:
"""Efficiency at 25% load: η = 0.25/(0.25+0.013+0.006×0.25+0.011×0.0625) ≈ 94.3%."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=125.0)
sim.step(1.0, 125.0) # 125/500 = 25%
ups = sim.state.ups_units[0]
assert 0.93 <= ups.efficiency <= 0.96, f"η={ups.efficiency:.3f}"
def test_efficiency_at_50_percent(self) -> None:
"""Efficiency at 50% load: η ≈ 96.4%."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=250.0)
sim.step(1.0, 250.0)
ups = sim.state.ups_units[0]
assert 0.95 <= ups.efficiency <= 0.97, f"η={ups.efficiency:.3f}"
def test_efficiency_at_75_percent(self) -> None:
"""Efficiency at 75% load: η ≈ 96.9%."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=375.0)
sim.step(1.0, 375.0)
ups = sim.state.ups_units[0]
assert 0.96 <= ups.efficiency <= 0.98, f"η={ups.efficiency:.3f}"
def test_efficiency_at_100_percent(self) -> None:
"""Efficiency at 100% load: η ≈ 97.1%."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=500.0)
sim.step(1.0, 500.0)
ups = sim.state.ups_units[0]
assert 0.96 <= ups.efficiency <= 0.98, f"η={ups.efficiency:.3f}"
def test_efficiency_peak_around_75_percent(self) -> None:
"""Peak efficiency should occur around 50-75% load, not at extremes."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=0.0)
efficiencies = {}
for load_pct in [10, 25, 50, 75, 100]:
load_kw = 500.0 * load_pct / 100.0
sim2 = PowerSimulation(make_simple_power_config(), it_load_kw=load_kw)
sim2.step(1.0, load_kw)
efficiencies[load_pct] = sim2.state.ups_units[0].efficiency
# Peak should be between 50-100%, not at 10%
peak_pct = max(efficiencies, key=efficiencies.get)
assert peak_pct >= 50, f"Peak at {peak_pct}%, efficiencies: {efficiencies}"
def test_losses_are_positive(self) -> None:
"""UPS losses should always be positive (waste heat)."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.step(1.0, 160.0)
ups = sim.state.ups_units[0]
assert ups.heat_output_kw > 0, "UPS must produce waste heat"
def test_eco_mode_higher_efficiency(self) -> None:
"""Eco mode should have higher efficiency than double conversion."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.step(1.0, 160.0)
eta_dc = sim.state.ups_units[0].efficiency
sim2 = PowerSimulation(make_simple_power_config(), it_load_kw=160.0)
sim2.set_ups_mode("UPS-1", UPSMode.ECO)
sim2.step(1.0, 160.0)
eta_eco = sim2.state.ups_units[0].efficiency
assert eta_eco > eta_dc, f"Eco {eta_eco:.3f} should > DC {eta_dc:.3f}"
# ===========================================================================
# UPS Battery Tests
# ===========================================================================
class TestUPSBattery:
"""Validate battery discharge and charge dynamics."""
def test_battery_discharge_on_utility_loss(self) -> None:
"""Battery SOC should decrease when utility is lost."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
# Verify initial SOC = 100%
assert sim.state.ups_units[0].battery_soc == 1.0
# Kill utility
sim.set_utility_available(False)
# Run for 60 seconds
for _ in range(60):
sim.step(1.0, 160.0)
ups = sim.state.ups_units[0]
assert ups.mode == UPSMode.ON_BATTERY
assert ups.battery_soc < 1.0, "SOC should decrease on battery"
assert ups.battery_soc > 0.5, "SOC shouldn't drop too fast in 60s"
def test_battery_runtime_estimation(self) -> None:
"""Battery time remaining estimate should be reasonable.
8.3 kWh battery, 0.9 discharge eff, 0.85 aging, 160 kW load:
usable = 8.3 × 0.9 × 0.85 = 6.35 kWh
At 160 kW: ~143 seconds (~2.4 min)
"""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.set_utility_available(False)
sim.step(1.0, 160.0)
ups = sim.state.ups_units[0]
assert ups.mode == UPSMode.ON_BATTERY
assert 60 < ups.battery_time_remaining_s < 300, \
f"Runtime {ups.battery_time_remaining_s:.0f}s should be 1-5 min for 160kW"
def test_battery_exhaustion(self) -> None:
"""Battery should eventually exhaust and UPS should fault."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.set_utility_available(False)
# Run until battery dies (should be ~2-3 min)
max_steps = 600 # 10 min max
exhausted = False
for _ in range(max_steps):
result = sim.step(1.0, 160.0)
if sim.state.ups_units[0].mode == UPSMode.FAULT:
exhausted = True
break
assert exhausted, "Battery should exhaust within 10 minutes at 160 kW"
assert sim.state.ups_units[0].battery_soc == 0.0
def test_battery_recharge_after_utility_restored(self) -> None:
"""Battery should recharge when utility is restored."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=80.0)
# Discharge for 30 seconds
sim.set_utility_available(False)
for _ in range(30):
sim.step(1.0, 80.0)
soc_after_discharge = sim.state.ups_units[0].battery_soc
# Restore utility
sim.set_utility_available(True)
for _ in range(300): # 5 min recharge
sim.step(1.0, 80.0)
soc_after_recharge = sim.state.ups_units[0].battery_soc
assert soc_after_recharge > soc_after_discharge, \
f"SOC should increase: {soc_after_discharge:.3f}{soc_after_recharge:.3f}"
def test_battery_low_alarm(self) -> None:
"""Should get low battery alarm when SOC drops below 25%."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.set_utility_available(False)
all_alarms: list[PowerAlarm] = []
for _ in range(600):
result = sim.step(1.0, 160.0)
all_alarms.extend(result.alarms)
if sim.state.ups_units[0].battery_soc < 0.10:
break
alarm_types = [a.alarm_type for a in all_alarms]
assert "battery_low" in alarm_types or "battery_critical" in alarm_types, \
f"Should have low battery alarm, got: {alarm_types}"
# ===========================================================================
# PDU Tests
# ===========================================================================
class TestPDU:
"""Validate PDU power distribution and loss calculations."""
def test_pdu_losses_at_nominal(self) -> None:
"""PDU losses should be ~2% of load (98% efficiency)."""
config = make_simple_power_config(num_pdus=1)
sim = PowerSimulation(config, it_load_kw=5.0)
result = sim.step(1.0, 5.0)
pdu = sim.state.pdus[0]
expected_loss = 5.0 * (1.0 / 0.98 - 1.0) # ~0.102 kW
assert abs(pdu.heat_output_kw - expected_loss) < 0.01, \
f"PDU loss {pdu.heat_output_kw:.3f} kW, expected {expected_loss:.3f}"
def test_phase_current_calculation(self) -> None:
"""Phase currents should match P = √3 × V_LL × I_L formula.
5 kW load at 208V: I_total = 5000 / (√3 × 208) = 13.88 A
Per phase (balanced): 13.88 / 3 = 4.63 A
"""
config = make_simple_power_config(num_pdus=1)
sim = PowerSimulation(config, it_load_kw=5.0)
sim.step(1.0, 5.0)
pdu = sim.state.pdus[0]
expected_total = 5000.0 / (math.sqrt(3) * 208.0)
expected_per_phase = expected_total / 3.0
for i, current in enumerate(pdu.phase_currents_a):
assert abs(current - expected_per_phase) < 0.1, \
f"Phase {i} current {current:.2f}A, expected {expected_per_phase:.2f}A"
def test_pdu_nameplate_capacity(self) -> None:
"""Nameplate capacity = √3 × 208V × 24A ≈ 8.65 kW."""
config = make_simple_power_config(num_pdus=1)
sim = PowerSimulation(config, it_load_kw=1.0)
sim.step(1.0, 1.0)
pdu = sim.state.pdus[0]
expected = math.sqrt(3) * 208.0 * 24.0 / 1000.0
assert abs(pdu.nameplate_capacity_kw - expected) < 0.01
def test_pdu_derated_capacity(self) -> None:
"""Derated capacity = nameplate × 0.80."""
config = make_simple_power_config(num_pdus=1)
sim = PowerSimulation(config, it_load_kw=1.0)
sim.step(1.0, 1.0)
pdu = sim.state.pdus[0]
expected = pdu.nameplate_capacity_kw * 0.80
assert abs(pdu.derated_capacity_kw - expected) < 0.01
def test_pdu_overcurrent_alarm(self) -> None:
"""Overloading a PDU beyond phase current limit should trigger alarm.
Phase current = P / (√3 × V_LL) / num_phases_factor
For total_current > 24A per-phase: need I_total > 72A
I_total = P / (√3 × 208) = P / 360.2
So P > 72 × 360.2 / 3 ≈ 8.65 kW won't do it because per_phase = I_total/3
Actually: per_phase = (P×1000)/(√3×208) / 3, need per_phase > 24A
per_phase > 24 → P > 24 × 3 × √3 × 208 / 1000 = 25.95 kW
"""
config = make_simple_power_config(num_pdus=1)
sim = PowerSimulation(config, it_load_kw=27.0)
result = sim.step(1.0, 27.0)
alarm_types = [a.alarm_type for a in result.alarms]
assert "phase_overcurrent" in alarm_types, f"Expected overcurrent alarm, got {alarm_types}"
def test_multiple_pdus_share_load(self) -> None:
"""Load should be distributed across PDUs."""
config = make_simple_power_config(num_pdus=4)
sim = PowerSimulation(config, it_load_kw=20.0)
sim.step(1.0, 20.0)
for pdu in sim.state.pdus:
assert abs(pdu.output_power_kw - 5.0) < 0.01
# ===========================================================================
# Generator Tests
# ===========================================================================
class TestGenerator:
"""Validate generator state machine and fuel consumption."""
def test_generator_startup_sequence(self) -> None:
"""Generator should progress: OFF → START_DELAY → CRANKING → WARMING → READY."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
gen = sim.state.generator
assert gen.state == GeneratorState.OFF
# Start generator
sim.start_generator()
assert gen.state == GeneratorState.START_DELAY
# Run through start delay (4s)
for _ in range(5):
sim.step(1.0, 160.0)
assert gen.state == GeneratorState.CRANKING
# Run through cranking (5s)
for _ in range(6):
sim.step(1.0, 160.0)
assert gen.state == GeneratorState.WARMING
# Run through warmup (8s)
for _ in range(9):
sim.step(1.0, 160.0)
assert gen.state == GeneratorState.READY
def test_generator_total_startup_time(self) -> None:
"""Total startup time should be ~17s (4 + 5 + 8)."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.start_generator()
# Run until ready
steps = 0
for steps in range(1, 100):
sim.step(1.0, 160.0)
if sim.state.generator.is_available:
break
# 4s delay + 5s crank + 8s warmup = 17s, allow ±2s
assert 15 <= steps <= 20, f"Startup took {steps}s, expected ~17s"
def test_fuel_consumption_under_load(self) -> None:
"""Fuel should be consumed when generator is loaded."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
gen = sim.state.generator
initial_fuel = gen.fuel_level_liters
# Trigger utility loss to get generator running and loaded
sim.set_utility_available(False)
# Run for 30 seconds (enough for startup + some loaded time)
for _ in range(30):
sim.step(1.0, 160.0)
assert gen.fuel_level_liters < initial_fuel, "Fuel should be consumed"
def test_fuel_consumption_rate(self) -> None:
"""Fuel rate = full_rate × (0.1 + 0.9 × load_fraction).
At 160kW / 750kW = 21.3% load:
rate = 180 × (0.1 + 0.9 × 0.213) = 180 × 0.292 = 52.6 L/hr
In 1 hour: ~52.6 liters consumed
"""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
# Must disable utility so ATS stays on generator for full hour
sim.set_utility_available(False)
# Manually put generator into loaded state for cleaner test
gen = sim.state.generator
gen.state = GeneratorState.LOADED
gen.load_fraction = 160.0 / 750.0
gen.output_power_kw = 160.0
sim.state.ats.position = ATSPosition.GENERATOR
initial_fuel = gen.fuel_level_liters
# Run for 1 hour
for _ in range(3600):
sim.step(1.0, 160.0)
consumed = initial_fuel - gen.fuel_level_liters
expected_rate = 180.0 * (0.1 + 0.9 * (160.0 / 750.0))
# Allow 10% tolerance
assert abs(consumed - expected_rate) < expected_rate * 0.15, \
f"Consumed {consumed:.1f}L/hr, expected ~{expected_rate:.1f}L/hr"
def test_generator_cooldown(self) -> None:
"""Generator should cool down for 5 minutes before shutdown."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
# Get generator running
gen = sim.state.generator
gen.state = GeneratorState.LOADED
gen.output_power_kw = 160.0
# Stop generator
sim.stop_generator()
assert gen.state == GeneratorState.COOLDOWN
# Run cooldown (300s)
for i in range(299):
sim.step(1.0, 160.0)
assert gen.state == GeneratorState.COOLDOWN, f"Still cooling at {i+1}s"
# Should transition to OFF after 300s
sim.step(1.0, 160.0)
assert gen.state == GeneratorState.OFF
def test_fuel_exhaustion(self) -> None:
"""Generator should shut down when fuel runs out."""
config = PowerConfig(
ups_units=[UPSConfig(unit_id="UPS-1")],
pdus=[PDUConfig(pdu_id="PDU-1")],
generator=GeneratorConfig(fuel_tank_liters=1.0), # Very small tank
ats=ATSConfig(),
)
sim = PowerSimulation(config, it_load_kw=160.0)
gen = sim.state.generator
gen.state = GeneratorState.LOADED
gen.load_fraction = 160.0 / 750.0
gen.output_power_kw = 160.0
sim.state.ats.position = ATSPosition.GENERATOR
sim.set_utility_available(False)
# Run until fuel runs out (1L / 52.6 L/hr ≈ 68 seconds)
all_alarms: list[PowerAlarm] = []
for _ in range(200):
result = sim.step(1.0, 160.0)
all_alarms.extend(result.alarms)
if gen.state == GeneratorState.OFF:
break
assert gen.state == GeneratorState.OFF
assert gen.fuel_level_liters == 0.0
alarm_types = [a.alarm_type for a in all_alarms]
assert "fuel_exhausted" in alarm_types
# ===========================================================================
# ATS Tests
# ===========================================================================
class TestATS:
"""Validate Automatic Transfer Switch behavior."""
def test_ats_starts_on_utility(self) -> None:
"""ATS should start in UTILITY position."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
assert sim.state.ats.position == ATSPosition.UTILITY
def test_ats_transfers_on_utility_loss(self) -> None:
"""ATS should begin transfer when utility is lost."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.set_utility_available(False)
sim.step(0.001, 160.0) # Tiny step to trigger detection
assert sim.state.ats.position == ATSPosition.TRANSFERRING
def test_ats_waits_for_generator(self) -> None:
"""ATS should stay TRANSFERRING until generator is ready."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.set_utility_available(False)
# Run for 5 seconds (generator still starting up)
for _ in range(5):
sim.step(1.0, 160.0)
# Should still be transferring because generator isn't ready yet
gen = sim.state.generator
assert not gen.is_available
assert sim.state.ats.position == ATSPosition.TRANSFERRING
def test_ats_completes_transfer_to_generator(self) -> None:
"""ATS should transfer to generator once it's ready."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.set_utility_available(False)
# Run long enough for generator startup (~17s) + transfer
for _ in range(25):
sim.step(1.0, 160.0)
assert sim.state.ats.position == ATSPosition.GENERATOR
assert sim.state.generator.state == GeneratorState.LOADED
def test_ats_retransfer_delay(self) -> None:
"""ATS should wait retransfer_delay (300s) before switching back to utility."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
# Lose utility and get on generator
sim.set_utility_available(False)
for _ in range(25):
sim.step(1.0, 160.0)
assert sim.state.ats.position == ATSPosition.GENERATOR
# Restore utility
sim.set_utility_available(True)
# Run for 200s — should still be on generator
for _ in range(200):
sim.step(1.0, 160.0)
assert sim.state.ats.position == ATSPosition.GENERATOR
# Run past 300s retransfer delay
for _ in range(150):
sim.step(1.0, 160.0)
# Should be transferring back or on utility
ats_pos = sim.state.ats.position
assert ats_pos in (ATSPosition.TRANSFERRING, ATSPosition.UTILITY), \
f"Expected transfer back, got {ats_pos}"
# ===========================================================================
# Full Scenario Tests
# ===========================================================================
class TestUtilityLossScenario:
"""End-to-end utility loss and recovery scenario."""
def test_full_utility_loss_and_recovery(self) -> None:
"""Complete scenario: utility loss → battery bridge → generator → recovery.
Timeline:
t=0: Utility fails
t=0-17s: UPS on battery, generator starting
t=17s: Generator ready, ATS transfers
t=17s+: On generator power
t=100s: Utility restored
t=400s: Retransfer to utility (after 300s delay)
"""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
# Phase 1: Utility loss
sim.set_utility_available(False)
# Run through startup sequence
ups_on_battery = False
gen_ready = False
on_generator = False
for t in range(1, 30):
result = sim.step(1.0, 160.0)
if sim.state.ups_units[0].mode == UPSMode.ON_BATTERY:
ups_on_battery = True
if sim.state.generator.is_available:
gen_ready = True
if sim.state.ats.position == ATSPosition.GENERATOR:
on_generator = True
assert ups_on_battery, "UPS should have been on battery"
assert gen_ready, "Generator should be ready by 30s"
assert on_generator, "Should be on generator by 30s"
# Phase 2: Running on generator
result = sim.step(1.0, 160.0)
assert result.on_generator
assert sim.state.generator.state == GeneratorState.LOADED
# Phase 3: Utility restored
sim.set_utility_available(True)
# Run past retransfer delay (300s)
for _ in range(350):
sim.step(1.0, 160.0)
# Should be back on utility (or transferring)
assert sim.state.ats.position in (ATSPosition.UTILITY, ATSPosition.TRANSFERRING)
def test_power_available_during_transfer(self) -> None:
"""UPS should bridge the gap during ATS transfer."""
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
# Initial: power available
result = sim.step(1.0, 160.0)
assert result.power_available
# During utility loss, UPS provides power
sim.set_utility_available(False)
for _ in range(5):
result = sim.step(1.0, 160.0)
# UPS is on battery, still providing power
assert sim.state.ups_units[0].mode == UPSMode.ON_BATTERY
# The IT load is still being served
assert sim.state.ups_units[0].output_power_kw > 0
# ===========================================================================
# Integration with DatacenterState Tests
# ===========================================================================
class TestPowerStateIntegration:
"""Test PowerState integration with DatacenterState."""
def test_datacenter_state_with_power(self) -> None:
"""DatacenterState should use PowerState for PUE when available."""
from dc_ops_env.simulation.types import DatacenterState, PowerState, UPSState, PDUState
ups = UPSState(unit_id="UPS-1", heat_output_kw=5.0)
pdu = PDUState(pdu_id="PDU-1", heat_output_kw=1.0)
power = PowerState(ups_units=[ups], pdus=[pdu])
state = DatacenterState(
power=power,
lighting_power_kw=5.0,
)
# With no zones (no IT load), PUE should be 1.0
assert state.pue == 1.0
def test_datacenter_state_without_power_uses_stubs(self) -> None:
"""DatacenterState without PowerState should use stub fractions."""
from dc_ops_env.simulation.types import DatacenterState
state = DatacenterState(
ups_loss_fraction=0.05,
pdu_loss_fraction=0.02,
)
# Should use the stub loss fractions (backward compat)
assert state.power is None
# ===========================================================================
# Performance Test
# ===========================================================================
class TestPerformance:
"""Ensure power simulation is fast enough for RL training."""
def test_steps_per_second(self) -> None:
"""Power sim should sustain >10,000 steps/sec."""
import time
config = make_simple_power_config(num_ups=2, num_pdus=20)
sim = PowerSimulation(config, it_load_kw=160.0)
n_steps = 5000
start = time.perf_counter()
for _ in range(n_steps):
sim.step(1.0, 160.0)
elapsed = time.perf_counter() - start
steps_per_sec = n_steps / elapsed
assert steps_per_sec > 10_000, \
f"Only {steps_per_sec:.0f} steps/sec, need >10,000"
# ===========================================================================
# Mutation Helper Tests
# ===========================================================================
class TestMutationHelpers:
"""Test convenience methods for scenario injection."""
def test_set_utility_available(self) -> None:
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
assert sim.state.utility_available is True
sim.set_utility_available(False)
assert sim.state.utility_available is False
def test_set_ups_mode(self) -> None:
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
assert sim.set_ups_mode("UPS-1", UPSMode.ECO)
assert sim.state.ups_units[0].mode == UPSMode.ECO
assert not sim.set_ups_mode("UPS-999", UPSMode.ECO)
def test_inject_and_clear_ups_fault(self) -> None:
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
assert sim.inject_ups_fault("UPS-1")
assert sim.state.ups_units[0].mode == UPSMode.FAULT
assert sim.clear_ups_fault("UPS-1")
assert sim.state.ups_units[0].mode == UPSMode.DOUBLE_CONVERSION
def test_start_stop_generator(self) -> None:
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
sim.start_generator()
assert sim.state.generator.state == GeneratorState.START_DELAY
# Run to READY
for _ in range(20):
sim.step(1.0, 160.0)
assert sim.state.generator.is_available
sim.stop_generator()
assert sim.state.generator.state == GeneratorState.COOLDOWN
def test_refuel_generator(self) -> None:
config = make_simple_power_config()
sim = PowerSimulation(config, it_load_kw=160.0)
gen = sim.state.generator
gen.fuel_level_liters = 500.0
sim.refuel_generator(200.0)
assert gen.fuel_level_liters == 700.0
sim.refuel_generator() # Full tank
assert gen.fuel_level_liters == gen.fuel_tank_liters