09ecf23 | 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683 684 685 686 687 688 689 690 691 692 693 694 695 696 697 698 699 700 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 738 739 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 | """
Data Centre Thermal Simulation β V2
Physics-based multi-zone server room model.
Responsibilities (pure physics only):
- ZoneState β per-zone thermal + sensor state
- FacilityState β facility-level state including chiller, carbon, load curves
- step_thermal(), apply_action_with_rate_limiting(), advance_time()
- Sensor drift, chiller fault injection, free-cooling, load/carbon advancement
No RL concepts. No reward logic. Just physics.
"""
import random
import math
from dataclasses import dataclass, field
from typing import Optional, List, Dict
# ββ Physical constants ββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
THERMAL_MASS_KJ_PER_K = 850.0
SECONDS_PER_STEP = 300 # 5-minute steps
IT_HEAT_FRACTION = 0.98
# Action rate limits (enforced by apply_action_with_rate_limiting)
MAX_FAN_DELTA_PER_STEP = 20.0 # Β± % per step
MAX_SUPPLY_TEMP_DELTA = 2.0 # Β± Β°C per step
MAX_CHILLER_SETPOINT_DELTA = 1.0 # Β± Β°C per step
# Chiller operating bounds
CHILLER_SETPOINT_MIN = 6.0
CHILLER_SETPOINT_MAX = 15.0
# Fan / supply air bounds
FAN_SPEED_MIN = 0.0
FAN_SPEED_MAX = 100.0
SUPPLY_AIR_TEMP_MIN = 16.0
SUPPLY_AIR_TEMP_MAX = 26.0
# Reference delta-T used in cooling-power scaling (Β°C).
# Must match the natural hot-aisle rise at design conditions:
# heat_in / (max_mass_flow Γ cp_air) = 441 / (50 Γ 1.006) β 8.77 Β°C
# At REF=15 effective cooling at equilibrium was only 280 kW < 441 kW heat-in,
# making the zone impossible to cool at any fan speed. REF=9 gives 468 kW.
COOLING_DELTA_T_REF = 9.0
# Mass-flow reference: easy zone (480 kW capacity) at 100% fan moves 50 kg/s.
# All other zones scale proportionally so every zone has the same 6% cooling
# headroom above heat-in: capacity / (mass_flow_max Γ 1.006 Γ REF) β 1.06.
MASS_FLOW_REF_CAPACITY_KW = 480.0 # easy zone cooling capacity (calibration reference)
MASS_FLOW_REF_KGS = 50.0 # mass flow at 100% fan for the reference zone
# Cube-law fan power coefficient (kW at 100 %)
FAN_POWER_MAX_KW = 8.0
# Envelope heat-transfer coefficient (kW / Β°C).
# Real data centres are extremely well insulated; at a 10 Β°C indoor-outdoor
# differential a 500 kW zone loses only ~0.5 kW through the fabric β
# negligible compared to IT heat. The previous value of 0.5 kW/Β°C was
# 10Γ too high and dominated zone-level thermal behaviour unrealistically.
ENVELOPE_CONDUCTANCE = 0.05
# Hot-aisle temperature rise coefficient
HOT_AISLE_RISE_COEFF = 5.0
# ββ Zone priority labels ββββββββββββββββββββββββββββββββββββββββββββββββββββββ
PRIORITY_LOW = 0
PRIORITY_MEDIUM = 1
PRIORITY_CRITICAL = 2
# ββ Dataclasses βββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
@dataclass
class ZoneState:
"""Per-zone thermal and sensor state (V2 β extended from V1)."""
# ββ Identity ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
zone_id: str
# ββ Thermal state βββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
temp_c: float # cold-aisle temperature (true value)
it_load_kw: float
fan_speed_pct: float
cooling_capacity_kw: float
# ββ V1 fields (kept) ββββββββββββββββββββββββββββββββββββββββββββββββββββββ
setpoint_c: float = 22.0 # legacy alias; use supply_air_temp_setpoint_c
humidity_pct: float = 45.0
sensor_faulty: bool = False
# ββ V2 new fields βββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
hot_aisle_temp_c: float = 0.0 # return-air temperature (computed)
supply_air_temp_c: float = 18.0 # actual delivered supply air temp
supply_air_temp_setpoint_c: float = 22.0 # agent-controlled setpoint
zone_priority: int = PRIORITY_MEDIUM # 0=low, 1=medium, 2=critical
sensor_drift_c: float = 0.0 # cumulative sensor drift (Β°C)
sensor_confidence: float = 1.0 # [0.0β1.0] reliability weight
base_it_load_kw: float = 0.0 # baseline load before diurnal variation
job_load_kw: float = 0.0 # cluster mode: IT load from admitted jobs (kW)
it_load_pct: float = 0.0 # normalised load [0β1]
thermal_mass_kj_per_k: float = 850.0 # room thermal mass (kJ/K); scale per zone size
def __post_init__(self):
if self.base_it_load_kw == 0.0:
self.base_it_load_kw = self.it_load_kw
if self.hot_aisle_temp_c == 0.0:
self.hot_aisle_temp_c = self.temp_c + 8.0
self.supply_air_temp_c = self.supply_air_temp_setpoint_c
# ββ Computed properties βββββββββββββββββββββββββββββββββββββββββββββββββββ
@property
def reported_temp_c(self) -> float:
"""Sensor reading β may be drifted if sensor_faulty is True."""
noise = random.gauss(0, 0.1)
if self.sensor_faulty:
return round(self.temp_c + self.sensor_drift_c + noise, 2)
return round(self.temp_c + noise, 2)
@property
def actual_cooling_kw(self) -> float:
"""Cooling power delivered (before delta-T scaling)."""
return self.cooling_capacity_kw * (self.fan_speed_pct / 100.0)
@property
def fan_power_kw(self) -> float:
"""Fan electrical power (cube law), scaled by zone cooling capacity."""
capacity_ratio = self.cooling_capacity_kw / MASS_FLOW_REF_CAPACITY_KW
return FAN_POWER_MAX_KW * capacity_ratio * (self.fan_speed_pct / 100.0) ** 3
# ββ Thermal step ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
def step_thermal(self, outside_temp_c: float, supply_air_temp_c: Optional[float] = None):
"""
Advance zone temperature by one time step.
V2 upgrade: cooling power is scaled by the delta-T between the hot aisle
and the delivered supply air temperature (not just fan speed alone).
"""
if supply_air_temp_c is None:
supply_air_temp_c = self.supply_air_temp_c
heat_in_kw = self.it_load_kw * IT_HEAT_FRACTION
# Effective cooling scales with temperature driving force
delta_t = max(self.hot_aisle_temp_c - supply_air_temp_c, 0.0)
scaling = delta_t / COOLING_DELTA_T_REF
effective_cooling_kw = self.actual_cooling_kw * scaling
effective_cooling_kw = min(effective_cooling_kw, heat_in_kw * 3.0)
# Envelope loss / gain (positive = heat flowing out when room is warm)
envelope_kw = ENVELOPE_CONDUCTANCE * (self.temp_c - outside_temp_c)
net_kw = heat_in_kw - effective_cooling_kw - envelope_kw
net_kj = net_kw * SECONDS_PER_STEP
delta_temp = net_kj / self.thermal_mass_kj_per_k # per-zone thermal mass
# delta_temp = max(-5.0, min(5.0, delta_temp))
delta_temp = max(-2.0, min(2.0, delta_temp))
self.temp_c = round(self.temp_c + delta_temp, 3)
# Derived temperatures
# denominator = max(effective_cooling_kw, 0.1)
# self.hot_aisle_temp_c = round(
# self.temp_c + (heat_in_kw / denominator) * HOT_AISLE_RISE_COEFF, 3
# )
# self.hot_aisle_temp_c = max(self.hot_aisle_temp_c, self.temp_c + 1.0)
# Mass flow scales with zone cooling capacity so every zone has the
# same ~6% cooling headroom above heat-in (fixes small-zone uncoolability).
mass_flow = (
(self.cooling_capacity_kw / MASS_FLOW_REF_CAPACITY_KW)
* MASS_FLOW_REF_KGS
* (self.fan_speed_pct / 100.0)
) # kg/s
if self.fan_speed_pct > 0.5:
self.hot_aisle_temp_c = round(
supply_air_temp_c + heat_in_kw / (mass_flow * 1.006), 3
)
else:
self.hot_aisle_temp_c = round(min(supply_air_temp_c + 50.0, 85.0), 3)
self.supply_air_temp_c = supply_air_temp_c
# Cold-aisle temperature floor: the zone cannot be colder than the
# supply air being delivered into it (physically impossible).
self.temp_c = round(max(self.temp_c, supply_air_temp_c), 3)
# Humidity heuristic
if self.temp_c > 26:
self.humidity_pct = min(70.0, self.humidity_pct + 0.5)
elif self.temp_c < 20:
self.humidity_pct = max(30.0, self.humidity_pct - 0.3)
# Normalised load
peak_load = max(self.base_it_load_kw, 1.0)
self.it_load_pct = round(min(self.it_load_kw / peak_load, 1.0), 4)
# ββ Facility state ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
@dataclass
class FacilityState:
"""Facility-level state (V2 β extended from V1)."""
# ββ Core ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
zones: List[ZoneState]
outside_temp_c: float
# ββ V1 fields (kept) ββββββββββββββββββββββββββββββββββββββββββββββββββββββ
chiller_active: bool = True
chiller_cop: float = 3.5
ups_efficiency: float = 0.96
step_number: int = 0
timestamp_hour: float = 14.0
grid_carbon_intensity: str = "medium"
maintenance_notes: List[str] = field(default_factory=list)
upcoming_events: List[str] = field(default_factory=list)
# ββ V2 new fields βββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
chiller_setpoint_c: float = 10.0 # agent-controlled, [6β15]Β°C
chiller_fault_level: float = 0.0 # 0 = healthy, 1 = full failure
chiller_fault_step: int = -1 # step when fault triggers (-1 = never)
wet_bulb_temp_c: float = 18.0 # enables free-cooling logic
grid_carbon_curve: List[float] = field(default_factory=list) # 24-hr normalised [0β1]
load_curve: List[float] = field(default_factory=list) # 24-hr normalised [0β1]
pid_baseline_pue: float = 1.55 # pre-computed PID reference PUE
grid_carbon_intensity_normalized: float = 0.5 # [0β1] numeric companion
minutes_per_step: float = 5.0 # sim minutes per env step; set by environment.py for timeline condensation
cluster_mode: bool = False # when True, bypass diurnal load curve; loads come from admitted jobs
# ββ Convenience constants βββββββββββββββββββββββββββββββββββββββββββββββββ
_BASE_CHILLER_COP: float = field(default=3.5, init=False, repr=False)
def __post_init__(self):
self._BASE_CHILLER_COP = self.chiller_cop
if not self.grid_carbon_curve:
self.grid_carbon_curve = _default_carbon_curve()
if not self.load_curve:
self.load_curve = _default_load_curve()
# ββ Computed properties βββββββββββββββββββββββββββββββββββββββββββββββββββ
@property
def total_it_load_kw(self) -> float:
return sum(z.it_load_kw for z in self.zones)
@property
def total_fan_power_kw(self) -> float:
return sum(z.fan_power_kw for z in self.zones)
@property
def effective_chiller_cop(self) -> float:
"""
COP adjusted for supply-water temperature and outdoor conditions.
Real-world behaviour:
- Higher leaving-water temp (chiller_setpoint_c) β less compression work β higher COP.
- Higher outdoor temp β harder heat rejection β lower COP.
Fault degradation overrides temperature adjustment: once inject_chiller_fault()
has modified self.chiller_cop, that modified value is used as-is.
"""
if self.chiller_fault_level > 0:
return self.chiller_cop # fault path; COP already degraded
cop = self._BASE_CHILLER_COP
cop *= (1.0 + 0.03 * (self.chiller_setpoint_c - 10.0)) # +3 % per Β°C higher setpoint
cop *= (1.0 - 0.02 * max(0.0, self.outside_temp_c - 20.0)) # β2 % per Β°C outdoor > 20
return max(1.0, min(6.0, cop))
@property
def chiller_power_kw(self) -> float:
if not self.chiller_active:
return 0.0
total_cooling = sum(z.actual_cooling_kw for z in self.zones)
cop = max(self.effective_chiller_cop, 0.01)
return total_cooling / cop
@property
def pue(self) -> float:
it = self.total_it_load_kw / max(self.ups_efficiency, 0.01)
cooling = self.total_fan_power_kw + self.chiller_power_kw
return round((it + cooling) / max(self.total_it_load_kw, 1.0), 4)
# ββ Time advancement ββββββββββββββββββββββββββββββββββββββββββββββββββββββ
def advance_time(self):
"""Tick clock forward by one step (minutes_per_step minutes)."""
self.timestamp_hour = (self.timestamp_hour + self.minutes_per_step / 60.0) % 24.0
self.step_number += 1
# ββ Load advancement ββββββββββββββββββββββββββββββββββββββββββββββββββββββ
def advance_load(self):
"""
Update IT load per zone.
Standard mode: diurnal curve Γ base_it_load_kw + random batch burst.
Cluster mode: base_it_load_kw (fixed baseline, e.g. inference always on)
+ job_load_kw (set each window by ClusterEnvironment from
EpisodeLedger.active_load_kw). No diurnal curve applied.
"""
if self.cluster_mode:
for zone in self.zones:
zone.it_load_kw = round(zone.base_it_load_kw + zone.job_load_kw, 2)
peak = max(zone.base_it_load_kw + zone.job_load_kw, zone.base_it_load_kw, 1.0)
zone.it_load_pct = round(min(zone.it_load_kw / peak, 1.5), 4)
return
if not self.load_curve:
return
hour_idx = int(self.timestamp_hour) % 24
normalised_load = self.load_curve[hour_idx]
for zone in self.zones:
# Scale load around the zone's base
batch_burst = 0.0
if random.random() < 0.05: # 5 % chance of batch arrival
batch_burst = random.uniform(0.03, 0.08)
zone.it_load_kw = round(
zone.base_it_load_kw * (normalised_load + batch_burst), 2
)
peak = max(zone.base_it_load_kw, 1.0)
zone.it_load_pct = round(min(zone.it_load_kw / peak, 1.0), 4)
# ββ Cluster mode: job load injection βββββββββββββββββββββββββββββββββββββ
def set_zone_job_load(self, zone_id: str, job_load_kw: float) -> None:
"""
Set the admitted-job IT load for a single zone.
Called by ClusterEnvironment when a job is admitted to or expires from a zone.
Only meaningful when cluster_mode=True.
"""
for zone in self.zones:
if zone.zone_id == zone_id:
zone.job_load_kw = max(0.0, round(job_load_kw, 2))
return
def set_all_job_loads(self, load_map: Dict[str, float]) -> None:
"""
Set admitted-job IT load for all zones in one call.
load_map: {zone_id: job_load_kw}. Zones absent from the map are set to 0.
Called by ClusterEnvironment at the start of each negotiation window.
Only meaningful when cluster_mode=True.
"""
for zone in self.zones:
zone.job_load_kw = max(0.0, round(load_map.get(zone.zone_id, 0.0), 2))
def total_job_load_kw(self) -> float:
"""Sum of all admitted job loads across zones (cluster mode)."""
return sum(z.job_load_kw for z in self.zones)
# ββ Carbon advancement ββββββββββββββββββββββββββββββββββββββββββββββββββββ
def advance_carbon(self):
"""Update grid carbon intensity from the 24-hr curve."""
if not self.grid_carbon_curve:
return
hour_idx = int(self.timestamp_hour) % 24
intensity = self.grid_carbon_curve[hour_idx]
self.grid_carbon_intensity_normalized = round(intensity, 4)
# Also update the human-readable label
if intensity < 0.25:
self.grid_carbon_intensity = "low"
elif intensity < 0.55:
self.grid_carbon_intensity = "medium"
elif intensity < 0.80:
self.grid_carbon_intensity = "high"
else:
self.grid_carbon_intensity = "critical_high"
# ββ Sensor drift ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
def apply_sensor_drift(self, step: int):
"""
Gradually drift faulty zone sensors over time.
Confidence decreases proportionally as drift grows.
Uses an effective step scaled by minutes_per_step so that drift
reaches its maximum at the same simulated time regardless of
whether the episode is condensed (larger minutes_per_step).
At 5 min/step the sensor stabilises at ~12 Β°C around step 50.
At 24 min/step (medium condensed) it stabilises around step 10.
"""
for zone in self.zones:
if not zone.sensor_faulty:
continue
# Scale step by how many 5-min periods this step represents
effective_step = int(step * self.minutes_per_step / 5.0)
target_drift = min(3.0 + effective_step * 0.18, 12.0)
zone.sensor_drift_c = round(target_drift, 2)
# Confidence shrinks from 1.0 β ~0.1 as drift grows from 0 β 12
zone.sensor_confidence = round(max(0.1, 1.0 - zone.sensor_drift_c / 13.0), 3)
# ββ Chiller fault injection βββββββββββββββββββββββββββββββββββββββββββββββ
def inject_chiller_fault(self, step: int):
"""
Degrade chiller COP based on fault progression.
Fault schedule (hard task):
step 15 β COP drops from 3.5 β 0.8 (partial failure)
step 20 β chiller goes fully offline
"""
if self.chiller_fault_step < 0:
return # no fault configured for this scenario
if step < self.chiller_fault_step:
return # fault not yet triggered
steps_since_fault = step - self.chiller_fault_step
if steps_since_fault < 5:
# Ramp COP down over 5 steps: 3.5 β 0.8
progress = steps_since_fault / 5.0
degraded_cop = self._BASE_CHILLER_COP + progress * (0.8 - self._BASE_CHILLER_COP)
self.chiller_cop = round(max(degraded_cop, 0.8), 3)
self.chiller_fault_level = round(progress, 3)
else:
# Full failure
self.chiller_active = False
self.chiller_cop = 0.0
self.chiller_fault_level = 1.0
# ββ Free-cooling potential ββββββββββββββββββββββββββββββββββββββββββββββββ
def compute_free_cooling_potential(self) -> float:
"""
Estimate how much cooling can come from outside air alone.
Returns a fraction [0.0β1.0] of the total required cooling that
could be met via economiser / free-air cooling, based on the
wet-bulb temperature vs. the average zone cold-aisle temperature.
Rule of thumb: free cooling is viable when wet-bulb < (zone_temp - 4Β°C).
"""
if not self.zones:
return 0.0
avg_zone_temp = sum(z.temp_c for z in self.zones) / len(self.zones)
headroom = avg_zone_temp - self.wet_bulb_temp_c - 4.0
if headroom <= 0.0:
return 0.0
# Scale linearly: full free cooling when headroom β₯ 10 Β°C
return round(min(headroom / 10.0, 1.0), 3)
# ββ Chiller setpoint β supply air temperature propagation βββββββββββββββββ
def propagate_chiller_setpoint(self):
"""
Translate the chiller setpoint into actual supply air temperature
for each zone, accounting for chiller COP and free-cooling potential.
When the chiller is offline, supply air approaches outdoor wet-bulb.
Free-cooling (economiser) blending is only applied when outdoor air
is actually cooler than what the chiller delivers. If the wet-bulb
temperature is above the chilled-supply setpoint β e.g. a hot summer
day with wet-bulb=22 Β°C and supply setpoint=18 Β°C β blending outdoor
air would *raise* the supply temperature and reduce cooling effectiveness.
In that case, the chilled supply is used as-is.
"""
free_cooling = self.compute_free_cooling_potential()
free_cooling_air_temp = self.wet_bulb_temp_c + 2.0
for zone in self.zones:
if self.chiller_active:
# Chiller can deliver down to chiller_setpoint + duct loss
# but zone setpoint is the agent's actual control lever
chiller_floor = self.chiller_setpoint_c + 0.5
# Agent setpoint is bounded below by what the chiller can deliver
chilled_supply = max(zone.supply_air_temp_setpoint_c, chiller_floor)
else:
chilled_supply = free_cooling_air_temp
# Only blend outdoor (free-cooling) air when it is colder than the
# chilled supply β otherwise free cooling would warm, not cool.
if free_cooling > 0.0 and free_cooling_air_temp < chilled_supply:
effective_supply = (
free_cooling * free_cooling_air_temp
+ (1.0 - free_cooling) * chilled_supply
)
else:
effective_supply = chilled_supply
zone.supply_air_temp_c = round(
max(SUPPLY_AIR_TEMP_MIN, min(effective_supply, SUPPLY_AIR_TEMP_MAX)), 2
)
# ββ Action application with rate-limiting βββββββββββββββββββββββββββββββββ
def apply_action_with_rate_limiting(
self,
action: "DCAction",
last_action: "DCAction",
) -> Dict[str, bool]:
"""
Apply agent action, enforcing per-step delta limits.
Rate limits scale with the step's simulated duration so they remain
physically consistent under timeline condensation. At 5 min/step
(easy task) the baseline limits apply; at 36 min/step (hard task)
limits are multiplied by 7.2, capped at the physical range.
Returns
-------
info : dict
{
"chiller_setpoint_clipped": bool,
"chiller_toggled": bool,
"zones": {zone_id: {"fan_clipped": bool, "supply_temp_clipped": bool}}
}
"""
# Scale limits proportionally to simulated minutes per step.
# minutes_per_step / 5.0 gives 1.0 for the reference (easy) task.
scale = self.minutes_per_step / 5.0
eff_fan_delta = min(MAX_FAN_DELTA_PER_STEP * scale, FAN_SPEED_MAX)
eff_supply_delta = min(MAX_SUPPLY_TEMP_DELTA * scale,
SUPPLY_AIR_TEMP_MAX - SUPPLY_AIR_TEMP_MIN)
eff_chiller_delta = min(MAX_CHILLER_SETPOINT_DELTA * scale,
CHILLER_SETPOINT_MAX - CHILLER_SETPOINT_MIN)
info: Dict = {
"chiller_setpoint_clipped": False,
"chiller_toggled": False,
"zones": {},
}
# ββ Facility-level levers βββββββββββββββββββββββββββββββββββββββββββββ
# Chiller setpoint
raw_delta = action.chiller_setpoint_c - last_action.chiller_setpoint_c
clipped_delta = _clip(raw_delta, eff_chiller_delta)
if abs(clipped_delta - raw_delta) > 1e-6:
info["chiller_setpoint_clipped"] = True
new_setpoint = last_action.chiller_setpoint_c + clipped_delta
self.chiller_setpoint_c = round(
_clip_bounds(new_setpoint, CHILLER_SETPOINT_MIN, CHILLER_SETPOINT_MAX), 2
)
# Chiller on/off β allowed freely (nuclear option, but costly).
# Once fully failed (fault_level == 1.0) the toggle is ignored and a
# maintenance_note is appended so the agent gets explicit feedback.
if self.chiller_fault_level < 1.0:
self.chiller_active = action.chiller_active
info["chiller_toggled"] = (action.chiller_active != last_action.chiller_active)
elif action.chiller_active and not self.chiller_active:
# Agent asked to re-enable a fully failed chiller β inform it.
note = (
"ACTION IGNORED: chiller_active=true submitted but chiller is "
"offline due to fault. Fans are the only available cooling."
)
if note not in self.maintenance_notes:
self.maintenance_notes.append(note)
# ββ Per-zone levers βββββββββββββββββββββββββββββββββββββββββββββββββββ
zone_map = {z.zone_id: z for z in self.zones}
last_zone_map = {za.zone_id: za for za in last_action.zone_adjustments}
for adj in action.zone_adjustments:
zone = zone_map.get(adj.zone_id)
if zone is None:
continue
last_adj = last_zone_map.get(adj.zone_id)
last_fan = last_adj.fan_speed_pct if last_adj else zone.fan_speed_pct
last_supply = (
last_adj.supply_air_temp_setpoint_c
if last_adj
else zone.supply_air_temp_setpoint_c
)
zone_info = {"fan_clipped": False, "supply_temp_clipped": False}
# Fan speed
fan_raw_delta = adj.fan_speed_pct - last_fan
fan_clipped_delta = _clip(fan_raw_delta, eff_fan_delta)
if abs(fan_clipped_delta - fan_raw_delta) > 1e-6:
zone_info["fan_clipped"] = True
zone.fan_speed_pct = round(
_clip_bounds(last_fan + fan_clipped_delta, FAN_SPEED_MIN, FAN_SPEED_MAX), 2
)
# Supply air temperature setpoint
supply_raw_delta = adj.supply_air_temp_setpoint_c - last_supply
supply_clipped_delta = _clip(supply_raw_delta, eff_supply_delta)
if abs(supply_clipped_delta - supply_raw_delta) > 1e-6:
zone_info["supply_temp_clipped"] = True
zone.supply_air_temp_setpoint_c = round(
_clip_bounds(
last_supply + supply_clipped_delta,
SUPPLY_AIR_TEMP_MIN,
SUPPLY_AIR_TEMP_MAX,
),
2,
)
info["zones"][adj.zone_id] = zone_info
return info
# ββ Full simulation step ββββββββββββββββββββββββββββββββββββββββββββββββββ
def step(
self,
action: "DCAction",
last_action: "DCAction",
) -> Dict:
"""
Advance simulation by one step.
Order of operations (per spec Β§4 Transition Dynamics):
1. Rate-limit and clip action
2. Apply supply air temp setpoint (propagate chiller β zones)
3. Update load and carbon from curves
4. Apply chiller fault (if scheduled)
5. Thermal step per zone
6. Sensor drift
7. Advance time
"""
# 1. Apply action (with clipping)
clip_info = self.apply_action_with_rate_limiting(action, last_action)
# 2. Propagate chiller setpoint β zone supply air temps
self.propagate_chiller_setpoint()
# 3. Update load and carbon
self.advance_load()
self.advance_carbon()
# 4. Chiller fault injection
self.inject_chiller_fault(self.step_number)
# 5. Thermal step per zone
for zone in self.zones:
zone.step_thermal(self.outside_temp_c, zone.supply_air_temp_c)
# 6. Sensor drift
self.apply_sensor_drift(self.step_number)
# 7. Advance time
self.advance_time()
return {"action_clipped": clip_info}
# ββ Observation serialisation βββββββββββββββββββββββββββββββββββββββββββββ
def to_observation_dict(self) -> dict:
"""Serialise full V2 observation (scalars + text fields)."""
hour = self.timestamp_hour
return {
"step": self.step_number,
"timestamp_hour": round(hour, 2),
"timestamp_day_sin": round(math.sin(2 * math.pi * hour / 24.0), 6),
"timestamp_day_cos": round(math.cos(2 * math.pi * hour / 24.0), 6),
"outside_temp_c": round(self.outside_temp_c, 1),
"wet_bulb_temp_c": round(self.wet_bulb_temp_c, 1),
"chiller_active": self.chiller_active,
"chiller_setpoint_c": round(self.chiller_setpoint_c, 2),
"chiller_cop": round(self.chiller_cop, 3),
"chiller_fault_level": round(self.chiller_fault_level, 3),
"ups_efficiency": round(self.ups_efficiency, 4),
"current_pue": self.pue,
"grid_carbon_intensity": self.grid_carbon_intensity,
"grid_carbon_intensity_normalized": self.grid_carbon_intensity_normalized,
"free_cooling_potential": self.compute_free_cooling_potential(),
"zones": [
{
"zone_id": z.zone_id,
# For faulty zones the cold-aisle sensor reading is degraded β expose the
# reported (potentially drifted) value so agents face a genuine inference
# challenge. The true internal temp_c is reserved for graders only.
"cold_aisle_temp_c": z.reported_temp_c if z.sensor_faulty else round(z.temp_c, 3),
"hot_aisle_temp_c": round(z.hot_aisle_temp_c, 3),
"reported_temp_c": z.reported_temp_c,
"it_load_kw": round(z.it_load_kw, 1),
"it_load_pct": round(z.it_load_pct, 4),
"fan_speed_pct": round(z.fan_speed_pct, 1),
"supply_air_temp_c": round(z.supply_air_temp_c, 2),
"supply_air_temp_setpoint_c": round(z.supply_air_temp_setpoint_c, 2),
"cooling_capacity_kw": z.cooling_capacity_kw,
"humidity_pct": round(z.humidity_pct, 1),
"sensor_confidence": round(z.sensor_confidence, 3),
"sensor_drift_c": round(z.sensor_drift_c, 2),
"zone_priority": z.zone_priority,
}
for z in self.zones
],
"maintenance_notes": self.maintenance_notes,
"upcoming_events": self.upcoming_events,
}
# ββ Default curves ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
def _default_carbon_curve() -> List[float]:
"""
Realistic 24-hour grid carbon intensity [0β1].
Low at night (wind/nuclear), peaks around midday (grid demand).
Indices correspond to hour-of-day (0β23).
"""
return [
0.20, 0.18, 0.17, 0.16, 0.17, 0.20, # 00β05 (night, renewables)
0.30, 0.45, 0.60, 0.72, 0.80, 0.85, # 06β11 (morning ramp)
0.88, 0.90, 0.87, 0.82, 0.75, 0.65, # 12β17 (midday peak)
0.55, 0.45, 0.38, 0.32, 0.27, 0.22, # 18β23 (evening wind)
]
def _default_load_curve() -> List[float]:
"""
Normalised IT load [0β1] across 24 hours.
Low at night, rises with business hours, peaks around 10β14h.
"""
return [
0.55, 0.52, 0.50, 0.50, 0.52, 0.58, # 00β05 (overnight batch)
0.65, 0.75, 0.88, 0.95, 0.98, 0.99, # 06β11 (morning surge)
1.00, 0.98, 0.96, 0.94, 0.90, 0.85, # 12β17 (business hours)
0.78, 0.72, 0.68, 0.64, 0.60, 0.57, # 18β23 (evening taper)
]
# ββ Action stubs (imported by modules that call apply_action_with_rate_limiting)
# Full Pydantic models live in models.py; these stubs are used here only for
# type-hint purposes and to keep simulation.py import-free of pydantic.
class _ZoneAdjustmentStub:
"""Minimal duck-type for ZoneAdjustment used in rate-limiting logic."""
def __init__(self, zone_id: str, fan_speed_pct: float, supply_air_temp_setpoint_c: float):
self.zone_id = zone_id
self.fan_speed_pct = fan_speed_pct
self.supply_air_temp_setpoint_c = supply_air_temp_setpoint_c
class _DCActionStub:
"""Minimal duck-type for DCAction used in rate-limiting logic."""
def __init__(
self,
zone_adjustments: List[_ZoneAdjustmentStub],
chiller_setpoint_c: float,
chiller_active: bool,
reasoning: Optional[str] = None,
):
self.zone_adjustments = zone_adjustments
self.chiller_setpoint_c = chiller_setpoint_c
self.chiller_active = chiller_active
self.reasoning = reasoning
# Re-export under the names used in type hints above
DCAction = _DCActionStub
ZoneAdjustment = _ZoneAdjustmentStub
# ββ Internal helpers ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ
def _clip(value: float, max_abs: float) -> float:
"""Clip value to [-max_abs, +max_abs]."""
return max(-max_abs, min(max_abs, value))
def _clip_bounds(value: float, lo: float, hi: float) -> float:
"""Clip value to [lo, hi]."""
return max(lo, min(hi, value)) |