| Data Centre Thermal Simulation β V2 | |
| Physics-based multi-zone server room model. | |
| Responsibilities (pure physics only): | |
| - ZoneState β per-zone thermal + sensor state | |
| - FacilityState β facility-level state including chiller, carbon, load curves | |
| - step_thermal(), apply_action_with_rate_limiting(), advance_time() | |
| - Sensor drift, chiller fault injection, free-cooling, load/carbon advancement | |
| No RL concepts. No reward logic. Just physics. | |
| """ | |
| import random | |
| import math | |
| from dataclasses import dataclass, field | |
| from typing import Optional, List, Dict | |
| # ββ Physical constants ββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| THERMAL_MASS_KJ_PER_K = 850.0 | |
| SECONDS_PER_STEP = 300 # 5-minute steps | |
| IT_HEAT_FRACTION = 0.98 | |
| # Action rate limits (enforced by apply_action_with_rate_limiting) | |
| MAX_FAN_DELTA_PER_STEP = 20.0 # Β± % per step | |
| MAX_SUPPLY_TEMP_DELTA = 2.0 # Β± Β°C per step | |
| MAX_CHILLER_SETPOINT_DELTA = 1.0 # Β± Β°C per step | |
| # Chiller operating bounds | |
| CHILLER_SETPOINT_MIN = 6.0 | |
| CHILLER_SETPOINT_MAX = 15.0 | |
| # Fan / supply air bounds | |
| FAN_SPEED_MIN = 0.0 | |
| FAN_SPEED_MAX = 100.0 | |
| SUPPLY_AIR_TEMP_MIN = 16.0 | |
| SUPPLY_AIR_TEMP_MAX = 26.0 | |
| # Reference delta-T used in cooling-power scaling (Β°C). | |
| # Must match the natural hot-aisle rise at design conditions: | |
| # heat_in / (max_mass_flow Γ cp_air) = 441 / (50 Γ 1.006) β 8.77 Β°C | |
| # At REF=15 effective cooling at equilibrium was only 280 kW < 441 kW heat-in, | |
| # making the zone impossible to cool at any fan speed. REF=9 gives 468 kW. | |
| COOLING_DELTA_T_REF = 9.0 | |
| # Mass-flow reference: easy zone (480 kW capacity) at 100% fan moves 50 kg/s. | |
| # All other zones scale proportionally so every zone has the same 6% cooling | |
| # headroom above heat-in: capacity / (mass_flow_max Γ 1.006 Γ REF) β 1.06. | |
| MASS_FLOW_REF_CAPACITY_KW = 480.0 # easy zone cooling capacity (calibration reference) | |
| MASS_FLOW_REF_KGS = 50.0 # mass flow at 100% fan for the reference zone | |
| # Cube-law fan power coefficient (kW at 100 %) | |
| FAN_POWER_MAX_KW = 8.0 | |
| # Envelope heat-transfer coefficient (kW / Β°C). | |
| # Real data centres are extremely well insulated; at a 10 Β°C indoor-outdoor | |
| # differential a 500 kW zone loses only ~0.5 kW through the fabric β | |
| # negligible compared to IT heat. The previous value of 0.5 kW/Β°C was | |
| # 10Γ too high and dominated zone-level thermal behaviour unrealistically. | |
| ENVELOPE_CONDUCTANCE = 0.05 | |
| # Hot-aisle temperature rise coefficient | |
| HOT_AISLE_RISE_COEFF = 5.0 | |
| # ββ Zone priority labels ββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| PRIORITY_LOW = 0 | |
| PRIORITY_MEDIUM = 1 | |
| PRIORITY_CRITICAL = 2 | |
| # ββ Dataclasses βββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| class ZoneState: | |
| """Per-zone thermal and sensor state (V2 β extended from V1).""" | |
| # ββ Identity ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| zone_id: str | |
| # ββ Thermal state βββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| temp_c: float # cold-aisle temperature (true value) | |
| it_load_kw: float | |
| fan_speed_pct: float | |
| cooling_capacity_kw: float | |
| # ββ V1 fields (kept) ββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| setpoint_c: float = 22.0 # legacy alias; use supply_air_temp_setpoint_c | |
| humidity_pct: float = 45.0 | |
| sensor_faulty: bool = False | |
| # ββ V2 new fields βββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| hot_aisle_temp_c: float = 0.0 # return-air temperature (computed) | |
| supply_air_temp_c: float = 18.0 # actual delivered supply air temp | |
| supply_air_temp_setpoint_c: float = 22.0 # agent-controlled setpoint | |
| zone_priority: int = PRIORITY_MEDIUM # 0=low, 1=medium, 2=critical | |
| sensor_drift_c: float = 0.0 # cumulative sensor drift (Β°C) | |
| sensor_confidence: float = 1.0 # [0.0β1.0] reliability weight | |
| base_it_load_kw: float = 0.0 # baseline load before diurnal variation | |
| job_load_kw: float = 0.0 # cluster mode: IT load from admitted jobs (kW) | |
| it_load_pct: float = 0.0 # normalised load [0β1] | |
| thermal_mass_kj_per_k: float = 850.0 # room thermal mass (kJ/K); scale per zone size | |
| def __post_init__(self): | |
| if self.base_it_load_kw == 0.0: | |
| self.base_it_load_kw = self.it_load_kw | |
| if self.hot_aisle_temp_c == 0.0: | |
| self.hot_aisle_temp_c = self.temp_c + 8.0 | |
| self.supply_air_temp_c = self.supply_air_temp_setpoint_c | |
| # ββ Computed properties βββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def reported_temp_c(self) -> float: | |
| """Sensor reading β may be drifted if sensor_faulty is True.""" | |
| noise = random.gauss(0, 0.1) | |
| if self.sensor_faulty: | |
| return round(self.temp_c + self.sensor_drift_c + noise, 2) | |
| return round(self.temp_c + noise, 2) | |
| def actual_cooling_kw(self) -> float: | |
| """Cooling power delivered (before delta-T scaling).""" | |
| return self.cooling_capacity_kw * (self.fan_speed_pct / 100.0) | |
| def fan_power_kw(self) -> float: | |
| """Fan electrical power (cube law), scaled by zone cooling capacity.""" | |
| capacity_ratio = self.cooling_capacity_kw / MASS_FLOW_REF_CAPACITY_KW | |
| return FAN_POWER_MAX_KW * capacity_ratio * (self.fan_speed_pct / 100.0) ** 3 | |
| # ββ Thermal step ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def step_thermal(self, outside_temp_c: float, supply_air_temp_c: Optional[float] = None): | |
| """ | |
| Advance zone temperature by one time step. | |
| V2 upgrade: cooling power is scaled by the delta-T between the hot aisle | |
| and the delivered supply air temperature (not just fan speed alone). | |
| """ | |
| if supply_air_temp_c is None: | |
| supply_air_temp_c = self.supply_air_temp_c | |
| heat_in_kw = self.it_load_kw * IT_HEAT_FRACTION | |
| # Effective cooling scales with temperature driving force | |
| delta_t = max(self.hot_aisle_temp_c - supply_air_temp_c, 0.0) | |
| scaling = delta_t / COOLING_DELTA_T_REF | |
| effective_cooling_kw = self.actual_cooling_kw * scaling | |
| effective_cooling_kw = min(effective_cooling_kw, heat_in_kw * 3.0) | |
| # Envelope loss / gain (positive = heat flowing out when room is warm) | |
| envelope_kw = ENVELOPE_CONDUCTANCE * (self.temp_c - outside_temp_c) | |
| net_kw = heat_in_kw - effective_cooling_kw - envelope_kw | |
| net_kj = net_kw * SECONDS_PER_STEP | |
| delta_temp = net_kj / self.thermal_mass_kj_per_k # per-zone thermal mass | |
| # delta_temp = max(-5.0, min(5.0, delta_temp)) | |
| delta_temp = max(-2.0, min(2.0, delta_temp)) | |
| self.temp_c = round(self.temp_c + delta_temp, 3) | |
| # Derived temperatures | |
| # denominator = max(effective_cooling_kw, 0.1) | |
| # self.hot_aisle_temp_c = round( | |
| # self.temp_c + (heat_in_kw / denominator) * HOT_AISLE_RISE_COEFF, 3 | |
| # ) | |
| # self.hot_aisle_temp_c = max(self.hot_aisle_temp_c, self.temp_c + 1.0) | |
| # Mass flow scales with zone cooling capacity so every zone has the | |
| # same ~6% cooling headroom above heat-in (fixes small-zone uncoolability). | |
| mass_flow = ( | |
| (self.cooling_capacity_kw / MASS_FLOW_REF_CAPACITY_KW) | |
| * MASS_FLOW_REF_KGS | |
| * (self.fan_speed_pct / 100.0) | |
| ) # kg/s | |
| if self.fan_speed_pct > 0.5: | |
| self.hot_aisle_temp_c = round( | |
| supply_air_temp_c + heat_in_kw / (mass_flow * 1.006), 3 | |
| ) | |
| else: | |
| self.hot_aisle_temp_c = round(min(supply_air_temp_c + 50.0, 85.0), 3) | |
| self.supply_air_temp_c = supply_air_temp_c | |
| # Cold-aisle temperature floor: the zone cannot be colder than the | |
| # supply air being delivered into it (physically impossible). | |
| self.temp_c = round(max(self.temp_c, supply_air_temp_c), 3) | |
| # Humidity heuristic | |
| if self.temp_c > 26: | |
| self.humidity_pct = min(70.0, self.humidity_pct + 0.5) | |
| elif self.temp_c < 20: | |
| self.humidity_pct = max(30.0, self.humidity_pct - 0.3) | |
| # Normalised load | |
| peak_load = max(self.base_it_load_kw, 1.0) | |
| self.it_load_pct = round(min(self.it_load_kw / peak_load, 1.0), 4) | |
| # ββ Facility state ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| class FacilityState: | |
| """Facility-level state (V2 β extended from V1).""" | |
| # ββ Core ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| zones: List[ZoneState] | |
| outside_temp_c: float | |
| # ββ V1 fields (kept) ββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| chiller_active: bool = True | |
| chiller_cop: float = 3.5 | |
| ups_efficiency: float = 0.96 | |
| step_number: int = 0 | |
| timestamp_hour: float = 14.0 | |
| grid_carbon_intensity: str = "medium" | |
| maintenance_notes: List[str] = field(default_factory=list) | |
| upcoming_events: List[str] = field(default_factory=list) | |
| # ββ V2 new fields βββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| chiller_setpoint_c: float = 10.0 # agent-controlled, [6β15]Β°C | |
| chiller_fault_level: float = 0.0 # 0 = healthy, 1 = full failure | |
| chiller_fault_step: int = -1 # step when fault triggers (-1 = never) | |
| wet_bulb_temp_c: float = 18.0 # enables free-cooling logic | |
| grid_carbon_curve: List[float] = field(default_factory=list) # 24-hr normalised [0β1] | |
| load_curve: List[float] = field(default_factory=list) # 24-hr normalised [0β1] | |
| pid_baseline_pue: float = 1.55 # pre-computed PID reference PUE | |
| grid_carbon_intensity_normalized: float = 0.5 # [0β1] numeric companion | |
| minutes_per_step: float = 5.0 # sim minutes per env step; set by environment.py for timeline condensation | |
| cluster_mode: bool = False # when True, bypass diurnal load curve; loads come from admitted jobs | |
| # ββ Convenience constants βββββββββββββββββββββββββββββββββββββββββββββββββ | |
| _BASE_CHILLER_COP: float = field(default=3.5, init=False, repr=False) | |
| def __post_init__(self): | |
| self._BASE_CHILLER_COP = self.chiller_cop | |
| if not self.grid_carbon_curve: | |
| self.grid_carbon_curve = _default_carbon_curve() | |
| if not self.load_curve: | |
| self.load_curve = _default_load_curve() | |
| # ββ Computed properties βββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def total_it_load_kw(self) -> float: | |
| return sum(z.it_load_kw for z in self.zones) | |
| def total_fan_power_kw(self) -> float: | |
| return sum(z.fan_power_kw for z in self.zones) | |
| def effective_chiller_cop(self) -> float: | |
| """ | |
| COP adjusted for supply-water temperature and outdoor conditions. | |
| Real-world behaviour: | |
| - Higher leaving-water temp (chiller_setpoint_c) β less compression work β higher COP. | |
| - Higher outdoor temp β harder heat rejection β lower COP. | |
| Fault degradation overrides temperature adjustment: once inject_chiller_fault() | |
| has modified self.chiller_cop, that modified value is used as-is. | |
| """ | |
| if self.chiller_fault_level > 0: | |
| return self.chiller_cop # fault path; COP already degraded | |
| cop = self._BASE_CHILLER_COP | |
| cop *= (1.0 + 0.03 * (self.chiller_setpoint_c - 10.0)) # +3 % per Β°C higher setpoint | |
| cop *= (1.0 - 0.02 * max(0.0, self.outside_temp_c - 20.0)) # β2 % per Β°C outdoor > 20 | |
| return max(1.0, min(6.0, cop)) | |
| def chiller_power_kw(self) -> float: | |
| if not self.chiller_active: | |
| return 0.0 | |
| total_cooling = sum(z.actual_cooling_kw for z in self.zones) | |
| cop = max(self.effective_chiller_cop, 0.01) | |
| return total_cooling / cop | |
| def pue(self) -> float: | |
| it = self.total_it_load_kw / max(self.ups_efficiency, 0.01) | |
| cooling = self.total_fan_power_kw + self.chiller_power_kw | |
| return round((it + cooling) / max(self.total_it_load_kw, 1.0), 4) | |
| # ββ Time advancement ββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def advance_time(self): | |
| """Tick clock forward by one step (minutes_per_step minutes).""" | |
| self.timestamp_hour = (self.timestamp_hour + self.minutes_per_step / 60.0) % 24.0 | |
| self.step_number += 1 | |
| # ββ Load advancement ββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def advance_load(self): | |
| """ | |
| Update IT load per zone. | |
| Standard mode: diurnal curve Γ base_it_load_kw + random batch burst. | |
| Cluster mode: base_it_load_kw (fixed baseline, e.g. inference always on) | |
| + job_load_kw (set each window by ClusterEnvironment from | |
| EpisodeLedger.active_load_kw). No diurnal curve applied. | |
| """ | |
| if self.cluster_mode: | |
| for zone in self.zones: | |
| zone.it_load_kw = round(zone.base_it_load_kw + zone.job_load_kw, 2) | |
| peak = max(zone.base_it_load_kw + zone.job_load_kw, zone.base_it_load_kw, 1.0) | |
| zone.it_load_pct = round(min(zone.it_load_kw / peak, 1.5), 4) | |
| return | |
| if not self.load_curve: | |
| return | |
| hour_idx = int(self.timestamp_hour) % 24 | |
| normalised_load = self.load_curve[hour_idx] | |
| for zone in self.zones: | |
| # Scale load around the zone's base | |
| batch_burst = 0.0 | |
| if random.random() < 0.05: # 5 % chance of batch arrival | |
| batch_burst = random.uniform(0.03, 0.08) | |
| zone.it_load_kw = round( | |
| zone.base_it_load_kw * (normalised_load + batch_burst), 2 | |
| ) | |
| peak = max(zone.base_it_load_kw, 1.0) | |
| zone.it_load_pct = round(min(zone.it_load_kw / peak, 1.0), 4) | |
| # ββ Cluster mode: job load injection βββββββββββββββββββββββββββββββββββββ | |
| def set_zone_job_load(self, zone_id: str, job_load_kw: float) -> None: | |
| """ | |
| Set the admitted-job IT load for a single zone. | |
| Called by ClusterEnvironment when a job is admitted to or expires from a zone. | |
| Only meaningful when cluster_mode=True. | |
| """ | |
| for zone in self.zones: | |
| if zone.zone_id == zone_id: | |
| zone.job_load_kw = max(0.0, round(job_load_kw, 2)) | |
| return | |
| def set_all_job_loads(self, load_map: Dict[str, float]) -> None: | |
| """ | |
| Set admitted-job IT load for all zones in one call. | |
| load_map: {zone_id: job_load_kw}. Zones absent from the map are set to 0. | |
| Called by ClusterEnvironment at the start of each negotiation window. | |
| Only meaningful when cluster_mode=True. | |
| """ | |
| for zone in self.zones: | |
| zone.job_load_kw = max(0.0, round(load_map.get(zone.zone_id, 0.0), 2)) | |
| def total_job_load_kw(self) -> float: | |
| """Sum of all admitted job loads across zones (cluster mode).""" | |
| return sum(z.job_load_kw for z in self.zones) | |
| # ββ Carbon advancement ββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def advance_carbon(self): | |
| """Update grid carbon intensity from the 24-hr curve.""" | |
| if not self.grid_carbon_curve: | |
| return | |
| hour_idx = int(self.timestamp_hour) % 24 | |
| intensity = self.grid_carbon_curve[hour_idx] | |
| self.grid_carbon_intensity_normalized = round(intensity, 4) | |
| # Also update the human-readable label | |
| if intensity < 0.25: | |
| self.grid_carbon_intensity = "low" | |
| elif intensity < 0.55: | |
| self.grid_carbon_intensity = "medium" | |
| elif intensity < 0.80: | |
| self.grid_carbon_intensity = "high" | |
| else: | |
| self.grid_carbon_intensity = "critical_high" | |
| # ββ Sensor drift ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def apply_sensor_drift(self, step: int): | |
| """ | |
| Gradually drift faulty zone sensors over time. | |
| Confidence decreases proportionally as drift grows. | |
| Uses an effective step scaled by minutes_per_step so that drift | |
| reaches its maximum at the same simulated time regardless of | |
| whether the episode is condensed (larger minutes_per_step). | |
| At 5 min/step the sensor stabilises at ~12 Β°C around step 50. | |
| At 24 min/step (medium condensed) it stabilises around step 10. | |
| """ | |
| for zone in self.zones: | |
| if not zone.sensor_faulty: | |
| continue | |
| # Scale step by how many 5-min periods this step represents | |
| effective_step = int(step * self.minutes_per_step / 5.0) | |
| target_drift = min(3.0 + effective_step * 0.18, 12.0) | |
| zone.sensor_drift_c = round(target_drift, 2) | |
| # Confidence shrinks from 1.0 β ~0.1 as drift grows from 0 β 12 | |
| zone.sensor_confidence = round(max(0.1, 1.0 - zone.sensor_drift_c / 13.0), 3) | |
| # ββ Chiller fault injection βββββββββββββββββββββββββββββββββββββββββββββββ | |
| def inject_chiller_fault(self, step: int): | |
| """ | |
| Degrade chiller COP based on fault progression. | |
| Fault schedule (hard task): | |
| step 15 β COP drops from 3.5 β 0.8 (partial failure) | |
| step 20 β chiller goes fully offline | |
| """ | |
| if self.chiller_fault_step < 0: | |
| return # no fault configured for this scenario | |
| if step < self.chiller_fault_step: | |
| return # fault not yet triggered | |
| steps_since_fault = step - self.chiller_fault_step | |
| if steps_since_fault < 5: | |
| # Ramp COP down over 5 steps: 3.5 β 0.8 | |
| progress = steps_since_fault / 5.0 | |
| degraded_cop = self._BASE_CHILLER_COP + progress * (0.8 - self._BASE_CHILLER_COP) | |
| self.chiller_cop = round(max(degraded_cop, 0.8), 3) | |
| self.chiller_fault_level = round(progress, 3) | |
| else: | |
| # Full failure | |
| self.chiller_active = False | |
| self.chiller_cop = 0.0 | |
| self.chiller_fault_level = 1.0 | |
| # ββ Free-cooling potential ββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def compute_free_cooling_potential(self) -> float: | |
| """ | |
| Estimate how much cooling can come from outside air alone. | |
| Returns a fraction [0.0β1.0] of the total required cooling that | |
| could be met via economiser / free-air cooling, based on the | |
| wet-bulb temperature vs. the average zone cold-aisle temperature. | |
| Rule of thumb: free cooling is viable when wet-bulb < (zone_temp - 4Β°C). | |
| """ | |
| if not self.zones: | |
| return 0.0 | |
| avg_zone_temp = sum(z.temp_c for z in self.zones) / len(self.zones) | |
| headroom = avg_zone_temp - self.wet_bulb_temp_c - 4.0 | |
| if headroom <= 0.0: | |
| return 0.0 | |
| # Scale linearly: full free cooling when headroom β₯ 10 Β°C | |
| return round(min(headroom / 10.0, 1.0), 3) | |
| # ββ Chiller setpoint β supply air temperature propagation βββββββββββββββββ | |
| def propagate_chiller_setpoint(self): | |
| """ | |
| Translate the chiller setpoint into actual supply air temperature | |
| for each zone, accounting for chiller COP and free-cooling potential. | |
| When the chiller is offline, supply air approaches outdoor wet-bulb. | |
| Free-cooling (economiser) blending is only applied when outdoor air | |
| is actually cooler than what the chiller delivers. If the wet-bulb | |
| temperature is above the chilled-supply setpoint β e.g. a hot summer | |
| day with wet-bulb=22 Β°C and supply setpoint=18 Β°C β blending outdoor | |
| air would *raise* the supply temperature and reduce cooling effectiveness. | |
| In that case, the chilled supply is used as-is. | |
| """ | |
| free_cooling = self.compute_free_cooling_potential() | |
| free_cooling_air_temp = self.wet_bulb_temp_c + 2.0 | |
| for zone in self.zones: | |
| if self.chiller_active: | |
| # Chiller can deliver down to chiller_setpoint + duct loss | |
| # but zone setpoint is the agent's actual control lever | |
| chiller_floor = self.chiller_setpoint_c + 0.5 | |
| # Agent setpoint is bounded below by what the chiller can deliver | |
| chilled_supply = max(zone.supply_air_temp_setpoint_c, chiller_floor) | |
| else: | |
| chilled_supply = free_cooling_air_temp | |
| # Only blend outdoor (free-cooling) air when it is colder than the | |
| # chilled supply β otherwise free cooling would warm, not cool. | |
| if free_cooling > 0.0 and free_cooling_air_temp < chilled_supply: | |
| effective_supply = ( | |
| free_cooling * free_cooling_air_temp | |
| + (1.0 - free_cooling) * chilled_supply | |
| ) | |
| else: | |
| effective_supply = chilled_supply | |
| zone.supply_air_temp_c = round( | |
| max(SUPPLY_AIR_TEMP_MIN, min(effective_supply, SUPPLY_AIR_TEMP_MAX)), 2 | |
| ) | |
| # ββ Action application with rate-limiting βββββββββββββββββββββββββββββββββ | |
| def apply_action_with_rate_limiting( | |
| self, | |
| action: "DCAction", | |
| last_action: "DCAction", | |
| ) -> Dict[str, bool]: | |
| """ | |
| Apply agent action, enforcing per-step delta limits. | |
| Rate limits scale with the step's simulated duration so they remain | |
| physically consistent under timeline condensation. At 5 min/step | |
| (easy task) the baseline limits apply; at 36 min/step (hard task) | |
| limits are multiplied by 7.2, capped at the physical range. | |
| Returns | |
| ------- | |
| info : dict | |
| { | |
| "chiller_setpoint_clipped": bool, | |
| "chiller_toggled": bool, | |
| "zones": {zone_id: {"fan_clipped": bool, "supply_temp_clipped": bool}} | |
| } | |
| """ | |
| # Scale limits proportionally to simulated minutes per step. | |
| # minutes_per_step / 5.0 gives 1.0 for the reference (easy) task. | |
| scale = self.minutes_per_step / 5.0 | |
| eff_fan_delta = min(MAX_FAN_DELTA_PER_STEP * scale, FAN_SPEED_MAX) | |
| eff_supply_delta = min(MAX_SUPPLY_TEMP_DELTA * scale, | |
| SUPPLY_AIR_TEMP_MAX - SUPPLY_AIR_TEMP_MIN) | |
| eff_chiller_delta = min(MAX_CHILLER_SETPOINT_DELTA * scale, | |
| CHILLER_SETPOINT_MAX - CHILLER_SETPOINT_MIN) | |
| info: Dict = { | |
| "chiller_setpoint_clipped": False, | |
| "chiller_toggled": False, | |
| "zones": {}, | |
| } | |
| # ββ Facility-level levers βββββββββββββββββββββββββββββββββββββββββββββ | |
| # Chiller setpoint | |
| raw_delta = action.chiller_setpoint_c - last_action.chiller_setpoint_c | |
| clipped_delta = _clip(raw_delta, eff_chiller_delta) | |
| if abs(clipped_delta - raw_delta) > 1e-6: | |
| info["chiller_setpoint_clipped"] = True | |
| new_setpoint = last_action.chiller_setpoint_c + clipped_delta | |
| self.chiller_setpoint_c = round( | |
| _clip_bounds(new_setpoint, CHILLER_SETPOINT_MIN, CHILLER_SETPOINT_MAX), 2 | |
| ) | |
| # Chiller on/off β allowed freely (nuclear option, but costly). | |
| # Once fully failed (fault_level == 1.0) the toggle is ignored and a | |
| # maintenance_note is appended so the agent gets explicit feedback. | |
| if self.chiller_fault_level < 1.0: | |
| self.chiller_active = action.chiller_active | |
| info["chiller_toggled"] = (action.chiller_active != last_action.chiller_active) | |
| elif action.chiller_active and not self.chiller_active: | |
| # Agent asked to re-enable a fully failed chiller β inform it. | |
| note = ( | |
| "ACTION IGNORED: chiller_active=true submitted but chiller is " | |
| "offline due to fault. Fans are the only available cooling." | |
| ) | |
| if note not in self.maintenance_notes: | |
| self.maintenance_notes.append(note) | |
| # ββ Per-zone levers βββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| zone_map = {z.zone_id: z for z in self.zones} | |
| last_zone_map = {za.zone_id: za for za in last_action.zone_adjustments} | |
| for adj in action.zone_adjustments: | |
| zone = zone_map.get(adj.zone_id) | |
| if zone is None: | |
| continue | |
| last_adj = last_zone_map.get(adj.zone_id) | |
| last_fan = last_adj.fan_speed_pct if last_adj else zone.fan_speed_pct | |
| last_supply = ( | |
| last_adj.supply_air_temp_setpoint_c | |
| if last_adj | |
| else zone.supply_air_temp_setpoint_c | |
| ) | |
| zone_info = {"fan_clipped": False, "supply_temp_clipped": False} | |
| # Fan speed | |
| fan_raw_delta = adj.fan_speed_pct - last_fan | |
| fan_clipped_delta = _clip(fan_raw_delta, eff_fan_delta) | |
| if abs(fan_clipped_delta - fan_raw_delta) > 1e-6: | |
| zone_info["fan_clipped"] = True | |
| zone.fan_speed_pct = round( | |
| _clip_bounds(last_fan + fan_clipped_delta, FAN_SPEED_MIN, FAN_SPEED_MAX), 2 | |
| ) | |
| # Supply air temperature setpoint | |
| supply_raw_delta = adj.supply_air_temp_setpoint_c - last_supply | |
| supply_clipped_delta = _clip(supply_raw_delta, eff_supply_delta) | |
| if abs(supply_clipped_delta - supply_raw_delta) > 1e-6: | |
| zone_info["supply_temp_clipped"] = True | |
| zone.supply_air_temp_setpoint_c = round( | |
| _clip_bounds( | |
| last_supply + supply_clipped_delta, | |
| SUPPLY_AIR_TEMP_MIN, | |
| SUPPLY_AIR_TEMP_MAX, | |
| ), | |
| 2, | |
| ) | |
| info["zones"][adj.zone_id] = zone_info | |
| return info | |
| # ββ Full simulation step ββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def step( | |
| self, | |
| action: "DCAction", | |
| last_action: "DCAction", | |
| ) -> Dict: | |
| """ | |
| Advance simulation by one step. | |
| Order of operations (per spec Β§4 Transition Dynamics): | |
| 1. Rate-limit and clip action | |
| 2. Apply supply air temp setpoint (propagate chiller β zones) | |
| 3. Update load and carbon from curves | |
| 4. Apply chiller fault (if scheduled) | |
| 5. Thermal step per zone | |
| 6. Sensor drift | |
| 7. Advance time | |
| """ | |
| # 1. Apply action (with clipping) | |
| clip_info = self.apply_action_with_rate_limiting(action, last_action) | |
| # 2. Propagate chiller setpoint β zone supply air temps | |
| self.propagate_chiller_setpoint() | |
| # 3. Update load and carbon | |
| self.advance_load() | |
| self.advance_carbon() | |
| # 4. Chiller fault injection | |
| self.inject_chiller_fault(self.step_number) | |
| # 5. Thermal step per zone | |
| for zone in self.zones: | |
| zone.step_thermal(self.outside_temp_c, zone.supply_air_temp_c) | |
| # 6. Sensor drift | |
| self.apply_sensor_drift(self.step_number) | |
| # 7. Advance time | |
| self.advance_time() | |
| return {"action_clipped": clip_info} | |
| # ββ Observation serialisation βββββββββββββββββββββββββββββββββββββββββββββ | |
| def to_observation_dict(self) -> dict: | |
| """Serialise full V2 observation (scalars + text fields).""" | |
| hour = self.timestamp_hour | |
| return { | |
| "step": self.step_number, | |
| "timestamp_hour": round(hour, 2), | |
| "timestamp_day_sin": round(math.sin(2 * math.pi * hour / 24.0), 6), | |
| "timestamp_day_cos": round(math.cos(2 * math.pi * hour / 24.0), 6), | |
| "outside_temp_c": round(self.outside_temp_c, 1), | |
| "wet_bulb_temp_c": round(self.wet_bulb_temp_c, 1), | |
| "chiller_active": self.chiller_active, | |
| "chiller_setpoint_c": round(self.chiller_setpoint_c, 2), | |
| "chiller_cop": round(self.chiller_cop, 3), | |
| "chiller_fault_level": round(self.chiller_fault_level, 3), | |
| "ups_efficiency": round(self.ups_efficiency, 4), | |
| "current_pue": self.pue, | |
| "grid_carbon_intensity": self.grid_carbon_intensity, | |
| "grid_carbon_intensity_normalized": self.grid_carbon_intensity_normalized, | |
| "free_cooling_potential": self.compute_free_cooling_potential(), | |
| "zones": [ | |
| { | |
| "zone_id": z.zone_id, | |
| # For faulty zones the cold-aisle sensor reading is degraded β expose the | |
| # reported (potentially drifted) value so agents face a genuine inference | |
| # challenge. The true internal temp_c is reserved for graders only. | |
| "cold_aisle_temp_c": z.reported_temp_c if z.sensor_faulty else round(z.temp_c, 3), | |
| "hot_aisle_temp_c": round(z.hot_aisle_temp_c, 3), | |
| "reported_temp_c": z.reported_temp_c, | |
| "it_load_kw": round(z.it_load_kw, 1), | |
| "it_load_pct": round(z.it_load_pct, 4), | |
| "fan_speed_pct": round(z.fan_speed_pct, 1), | |
| "supply_air_temp_c": round(z.supply_air_temp_c, 2), | |
| "supply_air_temp_setpoint_c": round(z.supply_air_temp_setpoint_c, 2), | |
| "cooling_capacity_kw": z.cooling_capacity_kw, | |
| "humidity_pct": round(z.humidity_pct, 1), | |
| "sensor_confidence": round(z.sensor_confidence, 3), | |
| "sensor_drift_c": round(z.sensor_drift_c, 2), | |
| "zone_priority": z.zone_priority, | |
| } | |
| for z in self.zones | |
| ], | |
| "maintenance_notes": self.maintenance_notes, | |
| "upcoming_events": self.upcoming_events, | |
| } | |
| # ββ Default curves ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def _default_carbon_curve() -> List[float]: | |
| """ | |
| Realistic 24-hour grid carbon intensity [0β1]. | |
| Low at night (wind/nuclear), peaks around midday (grid demand). | |
| Indices correspond to hour-of-day (0β23). | |
| """ | |
| return [ | |
| 0.20, 0.18, 0.17, 0.16, 0.17, 0.20, # 00β05 (night, renewables) | |
| 0.30, 0.45, 0.60, 0.72, 0.80, 0.85, # 06β11 (morning ramp) | |
| 0.88, 0.90, 0.87, 0.82, 0.75, 0.65, # 12β17 (midday peak) | |
| 0.55, 0.45, 0.38, 0.32, 0.27, 0.22, # 18β23 (evening wind) | |
| ] | |
| def _default_load_curve() -> List[float]: | |
| """ | |
| Normalised IT load [0β1] across 24 hours. | |
| Low at night, rises with business hours, peaks around 10β14h. | |
| """ | |
| return [ | |
| 0.55, 0.52, 0.50, 0.50, 0.52, 0.58, # 00β05 (overnight batch) | |
| 0.65, 0.75, 0.88, 0.95, 0.98, 0.99, # 06β11 (morning surge) | |
| 1.00, 0.98, 0.96, 0.94, 0.90, 0.85, # 12β17 (business hours) | |
| 0.78, 0.72, 0.68, 0.64, 0.60, 0.57, # 18β23 (evening taper) | |
| ] | |
| # ββ Action stubs (imported by modules that call apply_action_with_rate_limiting) | |
| # Full Pydantic models live in models.py; these stubs are used here only for | |
| # type-hint purposes and to keep simulation.py import-free of pydantic. | |
| class _ZoneAdjustmentStub: | |
| """Minimal duck-type for ZoneAdjustment used in rate-limiting logic.""" | |
| def __init__(self, zone_id: str, fan_speed_pct: float, supply_air_temp_setpoint_c: float): | |
| self.zone_id = zone_id | |
| self.fan_speed_pct = fan_speed_pct | |
| self.supply_air_temp_setpoint_c = supply_air_temp_setpoint_c | |
| class _DCActionStub: | |
| """Minimal duck-type for DCAction used in rate-limiting logic.""" | |
| def __init__( | |
| self, | |
| zone_adjustments: List[_ZoneAdjustmentStub], | |
| chiller_setpoint_c: float, | |
| chiller_active: bool, | |
| reasoning: Optional[str] = None, | |
| ): | |
| self.zone_adjustments = zone_adjustments | |
| self.chiller_setpoint_c = chiller_setpoint_c | |
| self.chiller_active = chiller_active | |
| self.reasoning = reasoning | |
| # Re-export under the names used in type hints above | |
| DCAction = _DCActionStub | |
| ZoneAdjustment = _ZoneAdjustmentStub | |
| # ββ Internal helpers ββββββββββββββββββββββββββββββββββββββββββββββββββββββββββ | |
| def _clip(value: float, max_abs: float) -> float: | |
| """Clip value to [-max_abs, +max_abs].""" | |
| return max(-max_abs, min(max_abs, value)) | |
| def _clip_bounds(value: float, lo: float, hi: float) -> float: | |
| """Clip value to [lo, hi].""" | |
| return max(lo, min(hi, value)) |