File size: 22,769 Bytes
838b84c | 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 | CHAPTER 10 TRAPS, INTERCEPTORS AND SEPARATORS SECTION PC 1001 GENERAL 1001.1 Scope. This chapter shall govern the material and installation of traps, interceptors and separators. SECTION PC 1002 TRAP REQUIREMENTS 1002.1 Fixture traps. Each plumbing fixture shall be separately trapped by a liquid - seal trap, except as otherwise permitted by this code. The vertical distance from the fixture outlet to the trap weir shall not exceed 48 inches (1220 mm), and the horizontal distance shall not exceed 30 inches ( 762 mm) measured from the centerline of the fixture outlet to the centerline of the inlet of the trap. The height of a clothes washer standpipe above a trap shall conform to Section 802.3.3. A fixture shall not be double trapped. Exceptio ns: 1. This section shall not apply to fixtures with integral traps. 2. A combination plumbing fixture is permitted to be installed on one trap, provided that one compartment is not more than 6 inches (152 mm) deeper than the other compartment and the wast e outlets are not more than 30 inches (762 mm) apart. 3. A grease interceptor intended to serve as a fixture trap in accordance with the manufacturer’s installation instructions shall be permitted to serve as the trap for a single fixture or a combination sink of not more than three compartments where the vertical distance from the fixture outlet to the inlet of the interceptor does not exceed 30 inches (762 mm ) and the developed length of the waste pipe from the most upstream fixture outlet to the inlet of the interceptor does not exceed 60 inches (1524 mm). 4. Floor drains in multilevel parking structures that discharge to a building storm sewer shall not be required to be individually trapped. Where floor drains in multilevel parking structures are requir ed to discharge to a combined building sewer system, the floor drains shall not be required to be individually trapped provided that they are connected to a main trap in accordance with Section 1103.1. 5. This section shall not apply to outdoor drinking fo untains discharging to a drywell. 6. This section shall not apply where local acid neutralizing systems are utilized in accordance with the rules of the Department of Environmental Protection and Section 803.2 of this code. 1002.2 Design of traps. Fixture traps shall be self - scouring. Fixture traps shall not have interior partitions, except where such traps are integral with the fixture or where such traps are constructed of an approved material that is resistant to corrosion and degradation. Slip joints sh all be made with an approved elastomeric gasket and shall be installed only on the trap inlet, trap outlet and within the trap seal. 1002.3 Prohibited traps. The following types of traps are prohibited: 1. Traps that depend on moving parts to maintain the seal. 2. Bell , pot, bottle traps and traps with interior partitions . 3. Crown - vented traps. 4. Traps not integral with a fixture and that depend on interior partitions for the seal, except those traps constructed of an approved material that is resistant t o corrosion and degradation. 5. “S” traps. 6. Drum traps. TRAPS, INTERCEPTORS AND SEPARATORS Exception: Drum traps used as solids interceptors and drum traps serving chemical waste systems shall be permit- ted. 1002.4 Trap seals. Each fixture trap shall have a liquid seal of not less than 2 i nches (51 mm) and not more than 4 inches (102 mm), or deeper for special designs relating to accessible fixtures. 1002.4.1 Trap seal protection. Trap seals of emergency floor drain traps and trap seals subject to evaporation shall be protected by one of t he methods in Sections 1002.4.1.1 through 1002.4.1.3. 1002.4.1.1 Potable water - supplied trap seal primer valve. A potable water - supplied trap seal primer valve shall supply water to the trap. Water - supplied trap seal primer valves shall conform to ASSE 101 8. The dis- charge pipe from the trap seal primer valve shall connect to the trap above the trap seal on the inlet side of the trap. 1002.4.1.2 Reclaimed or gray water - supplied trap seal primer valve. A reclaimed or gray water - supplied trap seal primer valve shall supply water to the trap. Water - supplied trap seal primer valves shall conform to ASSE 1018. The quality of reclaimed or gray water supplied to trap seal primer valves shall be in accordance with the requirements of the manufacturer of the trap seal primer valve and this code. The discharge pipe from the trap seal primer valve shall connect to the trap above the trap seal, on the inlet side of the trap. 1002.4.1.3 Manual water - supplied trap priming. A hose bib or similar manually operated plumbing fixture shall be provided within the same room and within a horizontal distance not to exceed 25 feet (7620 mm) and not more than 3 feet (914 mm) above the floor. 1002.5 Size of fixture traps. Fixture trap size shall be sufficient to drain the fix ture rapidly and not less than the size indicated in Table 709.1. A trap shall not be larger than the drainage pipe into which the trap discharges. 1002.6 Building traps. Building (house) traps shall be installed on all building drains near the foundation wall of the structure, inside of the street line, and on the sewer side of all connections except the connection used to receive the discharge from a sewage ejector, oil separator or leader on combined systems. If such trap is placed outside of the foundation wall or below a cellar floor, it shall be made accessible in a manhole with a cover, or by extension of the two handholes that shall be provided with cleanouts at the cellar floor or grade. Handhold extensions shall be not more than 18 inche s (457 mm) above the centerline of the drain. Building (house) traps shall be the same size as the building drain connected thereto and shall be provided with a fresh air inlet in accordance with Section 703.7.1. 1002.7 Trap setting and protection. Traps s hall be set level with respect to the trap seal and, where necessary, shall be protected from freezing. 1002.8 Recess for trap connection. A recess provided for connection of the underground trap, such as one serving a bathtub in slab - type construction, sh all have sides and a bottom of corrosion - resistant, insect - and vermin - proof con- struction. 1002.9 Acid - resisting traps. Where a vitrified clay or other brittleware, acid - resisting trap is installed underground, such trap shall be embedded in concrete exten ding 6 inches (152 mm) beyond the bottom and sides of the trap. 1002.10 Plumbing in mental health centers. In mental health centers, pipes and traps shall not be exposed. SECTION PC 1003 INTERCEPTORS AND SEPARATORS 1003.1 Where required. Interceptors and s eparators shall be provided to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the building drainage system, the public sewer, the private sewage system or the sewage treatment plant or processes. 1003.2 Approval. Th e size, type and location of each interceptor and of each separator shall be designed and installed in accordance with the manufacturer’s instructions and the requirements of this section based on the anticipated con- ditions of use. Wastes that do not requi re treatment or separation shall not be discharged into any interceptor or sepa- rator. 1003.3 Grease interceptors. Grease interceptors shall comply with the requirements of Sections 1003.3.1 through 1003.3.6. CHAPTER 10 TRAPS, INTERCEPTORS AND SEPARATORS SECTION PC 1001 GENERAL 1001.1 Scope. This chapter shall govern the material and installation of traps, interceptors and separators. SECTION PC 1002 TRAP REQUIREMENTS 1002.1 Fixture traps. Each plumbing fixture shall be separately trapped by a liquid - seal trap, except as otherwise permitted by this code. The vertical distance from the fixture outlet to the trap weir shall not exceed 48 inches (1220 mm), and the horizontal distance shall not exceed 30 inches ( 762 mm) measured from the centerline of the fixture outlet to the centerline of the inlet of the trap. The height of a clothes washer standpipe above a trap shall conform to Section 802.3.3. A fixture shall not be double trapped. Exceptio ns: 1. This section shall not apply to fixtures with integral traps. 2. A combination plumbing fixture is permitted to be installed on one trap, provided that one compartment is not more than 6 inches (152 mm) deeper than the other compartment and the wast e outlets are not more than 30 inches (762 mm) apart. 3. A grease interceptor intended to serve as a fixture trap in accordance with the manufacturer’s installation instructions shall be permitted to serve as the trap for a single fixture or a combination sink of not more than three compartments where the vertical distance from the fixture outlet to the inlet of the interceptor does not exceed 30 inches (762 mm ) and the developed length of the waste pipe from the most upstream fixture outlet to the inlet of the interceptor does not exceed 60 inches (1524 mm). 4. Floor drains in multilevel parking structures that discharge to a building storm sewer shall not be required to be individually trapped. Where floor drains in multilevel parking structures are requir ed to discharge to a combined building sewer system, the floor drains shall not be required to be individually trapped provided that they are connected to a main trap in accordance with Section 1103.1. 5. This section shall not apply to outdoor drinking fo untains discharging to a drywell. 6. This section shall not apply where local acid neutralizing systems are utilized in accordance with the rules of the Department of Environmental Protection and Section 803.2 of this code. 1002.2 Design of traps. Fixture traps shall be self - scouring. Fixture traps shall not have interior partitions, except where such traps are integral with the fixture or where such traps are constructed of an approved material that is resistant to corrosion and degradation. Slip joints sh all be made with an approved elastomeric gasket and shall be installed only on the trap inlet, trap outlet and within the trap seal. 1002.3 Prohibited traps. The following types of traps are prohibited: 1. Traps that depend on moving parts to maintain the seal. 2. Bell , pot, bottle traps and traps with interior partitions . 3. Crown - vented traps. 4. Traps not integral with a fixture and that depend on interior partitions for the seal, except those traps constructed of an approved material that is resistant t o corrosion and degradation. 5. “S” traps. 6. Drum traps. TRAPS, INTERCEPTORS AND SEPARATORS Exception: Drum traps used as solids interceptors and drum traps serving chemical waste systems shall be permit- ted. 1002.4 Trap seals. Each fixture trap shall have a liquid seal of not less than 2 i nches (51 mm) and not more than 4 inches (102 mm), or deeper for special designs relating to accessible fixtures. 1002.4.1 Trap seal protection. Trap seals of emergency floor drain traps and trap seals subject to evaporation shall be protected by one of t he methods in Sections 1002.4.1.1 through 1002.4.1.3. 1002.4.1.1 Potable water - supplied trap seal primer valve. A potable water - supplied trap seal primer valve shall supply water to the trap. Water - supplied trap seal primer valves shall conform to ASSE 101 8. The dis- charge pipe from the trap seal primer valve shall connect to the trap above the trap seal on the inlet side of the trap. 1002.4.1.2 Reclaimed or gray water - supplied trap seal primer valve. A reclaimed or gray water - supplied trap seal primer valve shall supply water to the trap. Water - supplied trap seal primer valves shall conform to ASSE 1018. The quality of reclaimed or gray water supplied to trap seal primer valves shall be in accordance with the requirements of the manufacturer of the trap seal primer valve and this code. The discharge pipe from the trap seal primer valve shall connect to the trap above the trap seal, on the inlet side of the trap. 1002.4.1.3 Manual water - supplied trap priming. A hose bib or similar manually operated plumbing fixture shall be provided within the same room and within a horizontal distance not to exceed 25 feet (7620 mm) and not more than 3 feet (914 mm) above the floor. 1002.5 Size of fixture traps. Fixture trap size shall be sufficient to drain the fix ture rapidly and not less than the size indicated in Table 709.1. A trap shall not be larger than the drainage pipe into which the trap discharges. 1002.6 Building traps. Building (house) traps shall be installed on all building drains near the foundation wall of the structure, inside of the street line, and on the sewer side of all connections except the connection used to receive the discharge from a sewage ejector, oil separator or leader on combined systems. If such trap is placed outside of the foundation wall or below a cellar floor, it shall be made accessible in a manhole with a cover, or by extension of the two handholes that shall be provided with cleanouts at the cellar floor or grade. Handhold extensions shall be not more than 18 inche s (457 mm) above the centerline of the drain. Building (house) traps shall be the same size as the building drain connected thereto and shall be provided with a fresh air inlet in accordance with Section 703.7.1. 1002.7 Trap setting and protection. Traps s hall be set level with respect to the trap seal and, where necessary, shall be protected from freezing. 1002.8 Recess for trap connection. A recess provided for connection of the underground trap, such as one serving a bathtub in slab - type construction, sh all have sides and a bottom of corrosion - resistant, insect - and vermin - proof con- struction. 1002.9 Acid - resisting traps. Where a vitrified clay or other brittleware, acid - resisting trap is installed underground, such trap shall be embedded in concrete exten ding 6 inches (152 mm) beyond the bottom and sides of the trap. 1002.10 Plumbing in mental health centers. In mental health centers, pipes and traps shall not be exposed. SECTION PC 1003 INTERCEPTORS AND SEPARATORS 1003.1 Where required. Interceptors and s eparators shall be provided to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the building drainage system, the public sewer, the private sewage system or the sewage treatment plant or processes. 1003.2 Approval. Th e size, type and location of each interceptor and of each separator shall be designed and installed in accordance with the manufacturer’s instructions and the requirements of this section based on the anticipated con- ditions of use. Wastes that do not requi re treatment or separation shall not be discharged into any interceptor or sepa- rator. 1003.3 Grease interceptors. Grease interceptors shall comply with the requirements of Sections 1003.3.1 through 1003.3.6. TRAPS, INTERCEPTORS AND SEPARATORS 1003.3.1 Grease interceptors and automatic greas e removal devices required. A grease interceptor or auto- matic grease removal device shall be required to receive the drainage from fixtures and equipment with waste containing fats, oils, or grease located in food preparation areas and shall be in accordan ce with the requirements of the Department of Environmental Protection. Grease interceptors and automatic grease removal devices shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged. 1003.3.2 Reserved. 1003 .3.3 Grease interceptors and automatic grease removal devices not required. A grease interceptor or an automatic grease removal device shall not be required for individual dwelling units , any private living quarters , or non - culinary schools which only cont ain residential type stoves and sinks intended for teaching basic home cook- ing skills . 1003.3.4 Grease interceptor and automatic grease removal device sizing and standards. Grease interceptors and automatic grease removal devices shall be sized in accordance with the rules of the Department of Environ- mental Protection . Grease interceptors and automatic grease removal devices shall be designed and tested in ac- cordance with PDI G101, ASME A112.14.3 or ASME A112 .14.4 and shall be installed in accordance with the manufacturer’s instructions. 1003.3.4.1 Grease interceptor capacity. Grease interceptors shall have a grease retention capacity in accord- ance with the rules of the Depar tment of Environmental Protection. 1003.3.4.2 Rate of flow controls. Grease interceptors shall be equipped with devices to control the rate of water flow so that the water flow does not exceed the rated flow. The flow - control device shall be vented and ter minate not less than 6 inches (152 mm) above the flood rim level or be installed in accordance with the manufacturer’s instructions. 1003.3.5 Automatic grease removal devices. Where automatic grease removal devices are installed, such devices shall be loca ted downstream of each fixture or multiple fixtures in accordance with the manufacturer’s instructions. The automatic grease removal device shall be sized to pretreat the measured or calculated flows for all connected fixtures or equipment in accordance wi th the sizing requirements of the Department of Environmental Protection. Ready access shall be provided for inspection and maintenance. 1003.3.6 Direct connection. The discharge piping from a grease interceptor shall be directly connected to the sanitary drainage system. 1003.4 Oil separators required. At repair garages where floor or trench drains are provided, car washing facilities with engine or undercarriage cleaning capability, factories where oily and flammable liquid wastes are produced and hydraul ic elevator pits, oil separators shall be installed into which oil - bearing, grease - bearing or flammable wastes shall be discharged before emptying into the building drainage system or other point of disposal. Exception: An oil separator is not required in hydraulic elevator pits where an automatic shut - down system is installed for the prevention of accidental discharge of oil - laden waste water into the sanitary system . Such systems shall not terminate the operation of pumps utilized to maintain emergency op eration of the elevator by fire fighters. 1003.4.1 Separation of liquids. A mixture of treated or untreated light and heavy liquids with various specific gravities shall be separated in an approved receptacle. 1003.4.2 Oil separator design. Oil separators shall be listed and labeled, or designed in accordance with Sections 1003.4.2.1 and 1003.4.2.2. 1003.4.2.1 General design requirements. Oil separators shall have a depth of not less than 2 feet (610 mm) below the invert of the discharge drain. The outlet o pening of the separator shall have not less than an 18 - inch (457 mm) water seal. 1003.4.2.2 Garages and service stations. Where automobiles are serviced, greased, repaired or washed or where gasoline is dispensed, oil separators shall have a capacity of no t less than 6 cubic feet (0.168 m 3 ) for the first 100 square feet (9.3 m 2 ) of area to be drained, plus 1 cubic foot (0.028 m 3 ) for each additional 100 square feet (9.3 m 2 ) of area to be drained into the separator. Parking garages in which servicing, repair ing or washing is not conducted, and in which gasoline is not dispensed, shall not require a separator. Areas of commercial garages utilized only for storage of automobiles are not required to be drained through a separator. TRAPS, INTERCEPTORS AND SEPARATORS 1003.5 Sand interceptors in com mercial establishments. Sand and similar interceptors for heavy solids shall be designed and located so as to be provided with ready access for cleaning, and shall have a water seal of not less than 6 inches (152 mm). 1003.6 Clothes washer discharge interc eptor. Clothes washers shall discharge through an interceptor that is pro- vided with a wire basket or similar device, removable for cleaning, that prevents passage into the drainage system of solids 1 / 2 inch (12.7 mm) or larger in size, string, rags, buttons or other materials detrimental to the public sewage system. Exceptions: 1. Clothes washers in individual dwelling units shall not be required to discharge through an interceptor. 2. A single clothes washer designed for use in individual dwelling un its and installed in a location other than an individual dwelling unit shall not be required to discharge through an interceptor. 1003.7 Bottling establishments. Bottling plants shall discharge process wastes into an interceptor that will provide for the separation of broken glass or other solids before discharging waste into the drainage system. 1003.8 Slaughterhouses. Slaughtering room and dressing room drains shall be equipped with approved separators. The separator shall prevent the discharge into the drainage system of feathers, entrails and other materials that cause clogging. 1003.9 Venting of interceptors and separators. Interceptors and separators shall be designed so as not to become air bound . Interceptors and separators shall be vented in ac cordance with one of the methods in Chapter 9. 1003.10 Access and maintenance of interceptors and separators. Access shall be provided to each interceptor and separator for service and maintenance , and for inspection by the department and the Department of Environmental Protection . Interceptors and separators shall be maintained by periodic removal of accumulated grease, scum, oil, or other floating substances and solids deposited in the interceptor or separator. SECTION PC 1004 MATERIALS, JOINTS AND CONNEC TIONS 1004.1 General. The materials and methods utilized for the construction and installation of traps, interceptors and separators shall comply with this chapter and the applicable provisions of Chapters 4 and 7. The fittings shall not have ledges, shoul ders or reductions capable of retarding or obstructing flow of the piping. |