| CHAPTER 12 | |
| SPECIAL PIPING AND STORAGE SYSTEMS | |
| SECTION | |
| PC | |
| 1201 | |
| GENERAL | |
| 1201.1 Scope. | |
| The provisions of this chapter shall govern the design and installation of piping and storage systems | |
| for nonflammable medical and nonmedical gas systems. | |
| 1201.2 Storage, handling, and use. | |
| The storage, handling, and use of medical and nonmedical gases s | |
| hall be in | |
| accordance with the | |
| New York City | |
| Fire Code. | |
| SECTION | |
| PC | |
| 1202 | |
| MEDICAL AND NONMEDICAL GASES | |
| 1202.1 Nonflammable medical and nonmedical gases. | |
| Nonflammable medical and nonmedical gas systems shall | |
| be designed and installed in accordance with NFPA 9 | |
| 9. | |
| Exceptions: | |
| 1. | |
| This section shall not apply to portable systems or cylinder storage. | |
| 2. | |
| Vacuum system exhaust terminations shall comply with the | |
| New York City | |
| Mechanical Code | |
| . | |
| SECTION | |
| PC | |
| 1203 | |
| NONMEDICAL OXYGEN SYSTEMS | |
| 1203.1 Design and installation. | |
| Non | |
| medical oxygen systems shall be designed and installed in accordance with | |
| NFPA 55 and NFPA 51. | |
| SECTION PC 1204 | |
| OTHER CRYOGENIC SYSTEMS | |
| 1204.1 Design and installation. | |
| Design and installation of cryogenic systems shall be in accordance with Sections | |
| 1202 an | |
| d 1203. | |
| 1204.2 Storage, handling, and use. | |
| Storage, handling, and use of cryogenic gases and fluids shall be in accordance | |
| with the | |
| New York City Fire Code | |
| . |