Ryan2219's picture
Upload 3258 files
838b84c verified
CHAPTER 14
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
SECTION PC 1401
GENERAL
1401.1 Scope.
The provisions of Chapter 14 shall govern the materials, design, construction and installation of sub-
surface landscape irrigation systems connected to nonpotable water from on
-
site water reuse systems.
1401.2 Materials.
Above
-
ground drain, waste and vent p
iping for subsurface landscape irrigation systems shall con-
form to one of the standards listed in Table 702.1. Subsurface landscape irrigation, underground building drainage
and vent pipe shall conform to one of the standards listed in Table 702.2.
1401.3
Tests.
Drain, waste and vent piping for subsurface landscape irrigation systems shall be tested in accordance
with Section 312.
1401.4 Inspections.
Subsurface landscape irrigation systems shall be inspected in accordance with Section 107.
1401.5 Disinfecti
on.
Disinfection shall not be required for on
-
site nonpotable water reuse for subsurface landscape
irrigation systems.
1401.6 Coloring.
On
-
site nonpotable water reuse for subsurface landscape irrigation systems shall not be required to
be dyed.
SECTION PC
1402
SYSTEM DESIGN AND SIZING
1402.1 Sizing.
The system shall be sized in accordance with the sum of the output of all water sources connected to
the subsurface irrigation system. Where gray water collection piping is connected to subsurface landscape irri
gation
systems, gray water output shall be calculated according to the gallons
-
per
-
day
-
per
-
occupant number based on the
type of fixtures connected. The gray water discharge shall be calculated by the following equation:
C = A
×
B
(Equation
14
-
1)
where:
A
= Number of occupants:
Residential
Number of occupants shall be determined by the actual number of occupants, but not less than two
occupants for one bedroom and one occupant for each additional bedroom.
Commercial
Number of occupants s
hall be determined by the
New York City Building Code
.
B
= Estimated flow demands for each occupant*:
Residential
25 gallons per day (94.6 lpd) per occupant for showers, bathtubs and lavatories and 15 gallons per day
(56.7 lpd) per occupant for clothes w
ashers or laundry trays.
Commercial
Based on type of fixture or water use records minus the discharge of fixtures other than those discharg-
ing gray water.
*Alternative estimated flow demands for each occupant shall be permitted based on actual calculate
d water usage for
the building.
C
= Estimated gray water discharge based on the total number of occupants.
1402.2 Percolation tests.
The permeability of the soil in the proposed absorption system shall be determined by
percolation tests or
permeability evaluation.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1402.2.1 Percolation tests and procedures.
At least three percolation tests in each system area shall be conducted.
The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption system. More per-
cola
tion tests shall be made where necessary, depending on system design.
1402.2.1.1 Percolation test hole.
The test hole shall be dug or bored. The test hole shall have vertical sides and
a horizontal dimension of 4 inches to 8 inches (102 mm to 203 mm). The
bottom and sides of the hole shall be
scratched with a sharp
-
pointed instrument to expose the natural soil. All loose material shall be removed from
the hole and the bottom shall be covered with 2 inches (51 mm) of gravel or coarse sand.
1402.2.1.2 Test pr
ocedure, sandy soils.
The hole shall be filled with clear water to a minimum of 12 inches
(305 mm) above the bottom of the hole for tests in sandy soils. The time for this amount of water to seep away
shall be determined, and this procedure shall be repeat
ed if the water from the second filling of the hole seeps
away in 10 minutes or less. The test shall proceed as follows: Water shall be added to a point not more than 6
inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference poin
t, water levels shall be
measured at 10
-
minute intervals for a period of 1 hour. Where 6 inches (152 mm) of water seeps away in less
than 10 minutes, a shorter interval between measurements shall be used, but in no case shall the water depth
exceed 6 inche
s (152 mm). Where 6 inches (152 mm) of water seeps away in less than 2 minutes, the test shall
be stopped and a rate of less than 1 minute per inch (2.4 s/mm) shall be reported. The final water level drop shall
be used to calculate the percolation rate. So
ils not meeting the above requirements shall be tested in accordance
with Section 1402.2.1.3.
1402.2.1.3 Test procedure, other soils.
The hole shall be filled with clear water, and a minimum water depth
of 12 inches (305 mm) shall be maintained above the b
ottom of the hole for a 4
-
hour period by refilling whenever
necessary or by use of an automatic siphon. Water remaining in the hole after 4 hours shall not be removed.
Thereafter, the soil shall be allowed to swell not less than 16 hours or more than 30 ho
urs. Immediately after the
soil swelling period, the measurements for determining the percolation rate shall be made as follows: any soil
sloughed into the hole shall be removed and the water level shall be adjusted to 6 inches (152 mm) above the
gravel or
coarse sand. Thereupon, from a fixed reference point, the water level shall be measured at 30
-
minute
intervals for a period of 4 hours, unless two successive water level drops do not vary by more than
1
/
16
inch (1.59
mm). At least three water level drops
shall be observed and recorded. The hole shall be filled with clear water
to a point not more than 6 inches (152 mm) above the gravel or coarse sand whenever it becomes nearly empty.
Adjustments of the water level shall not be made during the three measure
ment periods except to the limits of
the last measured water level drop. When the first 6 inches (152 mm) of water seeps away in less than 30
minutes, the time interval between measurements shall be 10 minutes and the test run for 1 hour. The water
depth s
hall not exceed 5 inches (127 mm) at any time during the measurement period. The drop that occurs
during the final measurement period shall be used in calculating the percolation rate.
1402.2.1.4 Mechanical test equipment.
Mechanical percolation test equip
ment shall be of an approved
type.
1402.2.2 Permeability evaluation.
Soil shall be evaluated for estimated percolation based on structure and texture
in accordance with accepted soil evaluation practices. Borings shall be made in accordance with
Section 1402.2.1.1
for evaluating the soil.
1402.3 Subsurface landscape irrigation site location.
The surface grade of all soil absorption systems shall be lo-
cated at a point lower than the surface grade of any water well or reservoir on the same or adjoin
ing lot. Where this is
not possible, the site shall be located so surface water drainage from the site is not directed toward a well or reservoir.
The soil absorption system shall be located with a minimum horizontal distance between various elements as in
dicated
in Table 1402.3. Private sewage disposal systems in compacted areas, such as parking lots and driveways, are prohib-
ited. Surface water shall be diverted away from any soil absorption site on the same or neighboring lots.
TABLE 1402.3
LOCATION OF S
UBSURFACE IRRIGATION SYSTEM
ELEMENT
MINIMUM HORIZONTAL DISTANCE
Storage tank (feet)
Irrigation disposal field
(feet)
Buildings
5
10
CHAPTER 14
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
SECTION PC 1401
GENERAL
1401.1 Scope.
The provisions of Chapter 14 shall govern the materials, design, construction and installation of sub-
surface landscape irrigation systems connected to nonpotable water from on
-
site water reuse systems.
1401.2 Materials.
Above
-
ground drain, waste and vent p
iping for subsurface landscape irrigation systems shall con-
form to one of the standards listed in Table 702.1. Subsurface landscape irrigation, underground building drainage
and vent pipe shall conform to one of the standards listed in Table 702.2.
1401.3
Tests.
Drain, waste and vent piping for subsurface landscape irrigation systems shall be tested in accordance
with Section 312.
1401.4 Inspections.
Subsurface landscape irrigation systems shall be inspected in accordance with Section 107.
1401.5 Disinfecti
on.
Disinfection shall not be required for on
-
site nonpotable water reuse for subsurface landscape
irrigation systems.
1401.6 Coloring.
On
-
site nonpotable water reuse for subsurface landscape irrigation systems shall not be required to
be dyed.
SECTION PC
1402
SYSTEM DESIGN AND SIZING
1402.1 Sizing.
The system shall be sized in accordance with the sum of the output of all water sources connected to
the subsurface irrigation system. Where gray water collection piping is connected to subsurface landscape irri
gation
systems, gray water output shall be calculated according to the gallons
-
per
-
day
-
per
-
occupant number based on the
type of fixtures connected. The gray water discharge shall be calculated by the following equation:
C = A
×
B
(Equation
14
-
1)
where:
A
= Number of occupants:
Residential
Number of occupants shall be determined by the actual number of occupants, but not less than two
occupants for one bedroom and one occupant for each additional bedroom.
Commercial
Number of occupants s
hall be determined by the
New York City Building Code
.
B
= Estimated flow demands for each occupant*:
Residential
25 gallons per day (94.6 lpd) per occupant for showers, bathtubs and lavatories and 15 gallons per day
(56.7 lpd) per occupant for clothes w
ashers or laundry trays.
Commercial
Based on type of fixture or water use records minus the discharge of fixtures other than those discharg-
ing gray water.
*Alternative estimated flow demands for each occupant shall be permitted based on actual calculate
d water usage for
the building.
C
= Estimated gray water discharge based on the total number of occupants.
1402.2 Percolation tests.
The permeability of the soil in the proposed absorption system shall be determined by
percolation tests or
permeability evaluation.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1402.2.1 Percolation tests and procedures.
At least three percolation tests in each system area shall be conducted.
The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption system. More per-
cola
tion tests shall be made where necessary, depending on system design.
1402.2.1.1 Percolation test hole.
The test hole shall be dug or bored. The test hole shall have vertical sides and
a horizontal dimension of 4 inches to 8 inches (102 mm to 203 mm). The
bottom and sides of the hole shall be
scratched with a sharp
-
pointed instrument to expose the natural soil. All loose material shall be removed from
the hole and the bottom shall be covered with 2 inches (51 mm) of gravel or coarse sand.
1402.2.1.2 Test pr
ocedure, sandy soils.
The hole shall be filled with clear water to a minimum of 12 inches
(305 mm) above the bottom of the hole for tests in sandy soils. The time for this amount of water to seep away
shall be determined, and this procedure shall be repeat
ed if the water from the second filling of the hole seeps
away in 10 minutes or less. The test shall proceed as follows: Water shall be added to a point not more than 6
inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference poin
t, water levels shall be
measured at 10
-
minute intervals for a period of 1 hour. Where 6 inches (152 mm) of water seeps away in less
than 10 minutes, a shorter interval between measurements shall be used, but in no case shall the water depth
exceed 6 inche
s (152 mm). Where 6 inches (152 mm) of water seeps away in less than 2 minutes, the test shall
be stopped and a rate of less than 1 minute per inch (2.4 s/mm) shall be reported. The final water level drop shall
be used to calculate the percolation rate. So
ils not meeting the above requirements shall be tested in accordance
with Section 1402.2.1.3.
1402.2.1.3 Test procedure, other soils.
The hole shall be filled with clear water, and a minimum water depth
of 12 inches (305 mm) shall be maintained above the b
ottom of the hole for a 4
-
hour period by refilling whenever
necessary or by use of an automatic siphon. Water remaining in the hole after 4 hours shall not be removed.
Thereafter, the soil shall be allowed to swell not less than 16 hours or more than 30 ho
urs. Immediately after the
soil swelling period, the measurements for determining the percolation rate shall be made as follows: any soil
sloughed into the hole shall be removed and the water level shall be adjusted to 6 inches (152 mm) above the
gravel or
coarse sand. Thereupon, from a fixed reference point, the water level shall be measured at 30
-
minute
intervals for a period of 4 hours, unless two successive water level drops do not vary by more than
1
/
16
inch (1.59
mm). At least three water level drops
shall be observed and recorded. The hole shall be filled with clear water
to a point not more than 6 inches (152 mm) above the gravel or coarse sand whenever it becomes nearly empty.
Adjustments of the water level shall not be made during the three measure
ment periods except to the limits of
the last measured water level drop. When the first 6 inches (152 mm) of water seeps away in less than 30
minutes, the time interval between measurements shall be 10 minutes and the test run for 1 hour. The water
depth s
hall not exceed 5 inches (127 mm) at any time during the measurement period. The drop that occurs
during the final measurement period shall be used in calculating the percolation rate.
1402.2.1.4 Mechanical test equipment.
Mechanical percolation test equip
ment shall be of an approved
type.
1402.2.2 Permeability evaluation.
Soil shall be evaluated for estimated percolation based on structure and texture
in accordance with accepted soil evaluation practices. Borings shall be made in accordance with
Section 1402.2.1.1
for evaluating the soil.
1402.3 Subsurface landscape irrigation site location.
The surface grade of all soil absorption systems shall be lo-
cated at a point lower than the surface grade of any water well or reservoir on the same or adjoin
ing lot. Where this is
not possible, the site shall be located so surface water drainage from the site is not directed toward a well or reservoir.
The soil absorption system shall be located with a minimum horizontal distance between various elements as in
dicated
in Table 1402.3. Private sewage disposal systems in compacted areas, such as parking lots and driveways, are prohib-
ited. Surface water shall be diverted away from any soil absorption site on the same or neighboring lots.
TABLE 1402.3
LOCATION OF S
UBSURFACE IRRIGATION SYSTEM
ELEMENT
MINIMUM HORIZONTAL DISTANCE
Storage tank (feet)
Irrigation disposal field
(feet)
Buildings
5
10
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Lot line adjoining
private property
5
5
Water wells
50
100
Streams and lakes
50
50
Seepage pits
5
20
Septic
tanks
0
5
Water service
5
5
Public water main
10
10
For SI: 1 foot = 304.8 mm.
SECTION PC 1403
INSTALLATION
1403.1 Installation.
Absorption systems shall be installed in accordance with Sections 1403.1.1 through 1403.1.5 to
provide landscape
irrigation without surfacing of water.
1403.1.1 Absorption area.
The total absorption area required shall be computed from the estimated daily gray
water discharge and the design
-
loading rate based on the percolation rate for the site. The required absorpt
ion area
equals the estimated gray water discharge divided by the design
-
loading rate from Table 1403.1.1.
TABLE 1403.1.1
DESIGN LOADING RATE
PERCOLATION RATE
(minutes per inch)
DESIGN LOADING FACTOR
(gallons per square foot per day)
< 1
Not suitable
1
5
1.20
6
7
1.00
8
10
0.90
11
15
0.80
16
20
0.70
21
30
0.60
31
45
0.50
46
60
0.45
61
120
0.20
> 120
Not Suitable
For SI: 1 minute per inch = min/25.4 mm,
1 gallon per square foot = 40.7 L/m
2
.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1403.1.2 Seepage trench excavations.
Seepage trench excavations shall be not less than 1 foot (304 mm) in width
and not greater than 5 feet (1524 mm) in width. Trench excavations shall be spaced not less than 2 feet (610 mm)
apart. The soil absorption area
of a seepage trench shall be computed by using the bottom of the trench area (width)
multiplied by the length of pipe. Individual seepage trenches shall be not greater than 100 feet (30 480 mm) in
developed length.
1403.1.3 Seepage bed excavations.
Seepa
ge bed excavations shall be not less than 5 feet (1524 mm) in width and
have more than one distribution pipe. The absorption area of a seepage bed shall be computed by using the bottom
of the trench area. Distribution piping in a seepage bed shall be unifo
rmly spaced not greater than 5 feet (1524 mm)
and not less than 3 feet (914 mm) apart, and greater than 3 feet (914 mm) and not less than 1 foot (305 mm) from
the sidewall or headwall.
1403.1.4 Excavation and construction.
The bottom of a trench or bed exc
avation shall be level. Seepage trenches
or beds shall not be excavated where the soil is so wet that such material rolled between the hands forms a soil
wire. All smeared or compacted soil surfaces in the sidewalls or bottom of seepage trench or bed excav
ations shall
be scarified to the depth of smearing or compaction and the loose material removed. Where rain falls on an open
excavation, the soil shall be left until sufficiently dry so a soil wire will not form when soil from the excavation
bottom is roll
ed between the hands. The bottom area shall then be scarified and loose material removed.
1403.1.5 Aggregate and backfill.
Not less than 6 inches in depth of aggregate, ranging in size from
1
/
2
to 2
1
/
2
inches (12.7 mm to 64 mm), shall be laid into the tren
ch below the distribution piping elevation. The aggregate
shall be evenly distributed not less than 2 inches (51 mm) in depth over the top of the distribution pipe. The aggre-
gate shall be covered with approved synthetic materials or 9 inches (229 mm) of un
compacted marsh hay or straw.
Building paper shall not be used to cover the aggregate. Not less than 9 inches (229 mm) of soil backfill shall be
provided above the covering.
1403.2 Distribution piping.
Distribution piping shall be not less than 3 inches (7
6 mm) in diameter. Materials shall
comply with Table 1403.2. The top of the distribution pipe shall be not less than 4 inches (100 mm) or greater than 12
inches (300 mm) below the original surface. The slope of the distribution pipes shall be not less than
2 inches (51 mm)
and not greater than 4 inches (102 mm) per 100 feet (30 480 mm).
TABLE 1403.2
DISTRIBUTION PIPE
MATERIAL
STANDARD
Polypropylene (PP) pipe
ASTM F
2389
Polyethylene (PE) plastic pipe
ASTM F
405
Polyvinyl chloride (PVC) plastic pipe
a
ASTM D
2729
Polyvinyl chloride (PVC) plastic pipe with a 3.5
-
inch O.D. and solid cellular core or composite wall
a
ASTM F
1488
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in
height.
1403.2.1 Joints and fittings.
Joints and fittings in distribution pipe shall be made in accordance with Table
1403.2.1.
TABLE 1403.2.1
JOINTS AND FITTINGS
MATERIAL
STANDARD
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Polyethylene (PE) plastic pipe
ASTM F 405
Polypropylene (PP) pipe
ASTM F 2389
Polyvinyl chloride (PVC) plastic in IPS
diameters
a
ASTM D 2665; ASTM
F 1866
Polyvinyl chloride (PVC) plastic pipe in
sewer and drain diameters
a
ASTM D 3034
Polyvinyl chloride (PVC) plastic pipe
with a 3.25
-
inch O.D.
a
ASTM D 2949
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
1403.2.2 Diversion valves.
Systems shall include a diversion valve to divert gray water
to the building sanitary
system when soils are saturated or frozen, there is a blockage or backup in the system, the maximum allowed
gallons per day is reached, or when system maintenance is necessary.
1403.2.3 Overflow connection.
Systems shall have a pi
ped connection to the building drainage system to accom-
modate tank overflow.
CHAPTER 14
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
SECTION PC 1401
GENERAL
1401.1 Scope.
The provisions of Chapter 14 shall govern the materials, design, construction and installation of sub-
surface landscape irrigation systems connected to nonpotable water from on
-
site water reuse systems.
1401.2 Materials.
Above
-
ground drain, waste and vent p
iping for subsurface landscape irrigation systems shall con-
form to one of the standards listed in Table 702.1. Subsurface landscape irrigation, underground building drainage
and vent pipe shall conform to one of the standards listed in Table 702.2.
1401.3
Tests.
Drain, waste and vent piping for subsurface landscape irrigation systems shall be tested in accordance
with Section 312.
1401.4 Inspections.
Subsurface landscape irrigation systems shall be inspected in accordance with Section 107.
1401.5 Disinfecti
on.
Disinfection shall not be required for on
-
site nonpotable water reuse for subsurface landscape
irrigation systems.
1401.6 Coloring.
On
-
site nonpotable water reuse for subsurface landscape irrigation systems shall not be required to
be dyed.
SECTION PC
1402
SYSTEM DESIGN AND SIZING
1402.1 Sizing.
The system shall be sized in accordance with the sum of the output of all water sources connected to
the subsurface irrigation system. Where gray water collection piping is connected to subsurface landscape irri
gation
systems, gray water output shall be calculated according to the gallons
-
per
-
day
-
per
-
occupant number based on the
type of fixtures connected. The gray water discharge shall be calculated by the following equation:
C = A
×
B
(Equation
14
-
1)
where:
A
= Number of occupants:
Residential
Number of occupants shall be determined by the actual number of occupants, but not less than two
occupants for one bedroom and one occupant for each additional bedroom.
Commercial
Number of occupants s
hall be determined by the
New York City Building Code
.
B
= Estimated flow demands for each occupant*:
Residential
25 gallons per day (94.6 lpd) per occupant for showers, bathtubs and lavatories and 15 gallons per day
(56.7 lpd) per occupant for clothes w
ashers or laundry trays.
Commercial
Based on type of fixture or water use records minus the discharge of fixtures other than those discharg-
ing gray water.
*Alternative estimated flow demands for each occupant shall be permitted based on actual calculate
d water usage for
the building.
C
= Estimated gray water discharge based on the total number of occupants.
1402.2 Percolation tests.
The permeability of the soil in the proposed absorption system shall be determined by
percolation tests or
permeability evaluation.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1402.2.1 Percolation tests and procedures.
At least three percolation tests in each system area shall be conducted.
The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption system. More per-
cola
tion tests shall be made where necessary, depending on system design.
1402.2.1.1 Percolation test hole.
The test hole shall be dug or bored. The test hole shall have vertical sides and
a horizontal dimension of 4 inches to 8 inches (102 mm to 203 mm). The
bottom and sides of the hole shall be
scratched with a sharp
-
pointed instrument to expose the natural soil. All loose material shall be removed from
the hole and the bottom shall be covered with 2 inches (51 mm) of gravel or coarse sand.
1402.2.1.2 Test pr
ocedure, sandy soils.
The hole shall be filled with clear water to a minimum of 12 inches
(305 mm) above the bottom of the hole for tests in sandy soils. The time for this amount of water to seep away
shall be determined, and this procedure shall be repeat
ed if the water from the second filling of the hole seeps
away in 10 minutes or less. The test shall proceed as follows: Water shall be added to a point not more than 6
inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference poin
t, water levels shall be
measured at 10
-
minute intervals for a period of 1 hour. Where 6 inches (152 mm) of water seeps away in less
than 10 minutes, a shorter interval between measurements shall be used, but in no case shall the water depth
exceed 6 inche
s (152 mm). Where 6 inches (152 mm) of water seeps away in less than 2 minutes, the test shall
be stopped and a rate of less than 1 minute per inch (2.4 s/mm) shall be reported. The final water level drop shall
be used to calculate the percolation rate. So
ils not meeting the above requirements shall be tested in accordance
with Section 1402.2.1.3.
1402.2.1.3 Test procedure, other soils.
The hole shall be filled with clear water, and a minimum water depth
of 12 inches (305 mm) shall be maintained above the b
ottom of the hole for a 4
-
hour period by refilling whenever
necessary or by use of an automatic siphon. Water remaining in the hole after 4 hours shall not be removed.
Thereafter, the soil shall be allowed to swell not less than 16 hours or more than 30 ho
urs. Immediately after the
soil swelling period, the measurements for determining the percolation rate shall be made as follows: any soil
sloughed into the hole shall be removed and the water level shall be adjusted to 6 inches (152 mm) above the
gravel or
coarse sand. Thereupon, from a fixed reference point, the water level shall be measured at 30
-
minute
intervals for a period of 4 hours, unless two successive water level drops do not vary by more than
1
/
16
inch (1.59
mm). At least three water level drops
shall be observed and recorded. The hole shall be filled with clear water
to a point not more than 6 inches (152 mm) above the gravel or coarse sand whenever it becomes nearly empty.
Adjustments of the water level shall not be made during the three measure
ment periods except to the limits of
the last measured water level drop. When the first 6 inches (152 mm) of water seeps away in less than 30
minutes, the time interval between measurements shall be 10 minutes and the test run for 1 hour. The water
depth s
hall not exceed 5 inches (127 mm) at any time during the measurement period. The drop that occurs
during the final measurement period shall be used in calculating the percolation rate.
1402.2.1.4 Mechanical test equipment.
Mechanical percolation test equip
ment shall be of an approved
type.
1402.2.2 Permeability evaluation.
Soil shall be evaluated for estimated percolation based on structure and texture
in accordance with accepted soil evaluation practices. Borings shall be made in accordance with
Section 1402.2.1.1
for evaluating the soil.
1402.3 Subsurface landscape irrigation site location.
The surface grade of all soil absorption systems shall be lo-
cated at a point lower than the surface grade of any water well or reservoir on the same or adjoin
ing lot. Where this is
not possible, the site shall be located so surface water drainage from the site is not directed toward a well or reservoir.
The soil absorption system shall be located with a minimum horizontal distance between various elements as in
dicated
in Table 1402.3. Private sewage disposal systems in compacted areas, such as parking lots and driveways, are prohib-
ited. Surface water shall be diverted away from any soil absorption site on the same or neighboring lots.
TABLE 1402.3
LOCATION OF S
UBSURFACE IRRIGATION SYSTEM
ELEMENT
MINIMUM HORIZONTAL DISTANCE
Storage tank (feet)
Irrigation disposal field
(feet)
Buildings
5
10
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Lot line adjoining
private property
5
5
Water wells
50
100
Streams and lakes
50
50
Seepage pits
5
20
Septic
tanks
0
5
Water service
5
5
Public water main
10
10
For SI: 1 foot = 304.8 mm.
SECTION PC 1403
INSTALLATION
1403.1 Installation.
Absorption systems shall be installed in accordance with Sections 1403.1.1 through 1403.1.5 to
provide landscape
irrigation without surfacing of water.
1403.1.1 Absorption area.
The total absorption area required shall be computed from the estimated daily gray
water discharge and the design
-
loading rate based on the percolation rate for the site. The required absorpt
ion area
equals the estimated gray water discharge divided by the design
-
loading rate from Table 1403.1.1.
TABLE 1403.1.1
DESIGN LOADING RATE
PERCOLATION RATE
(minutes per inch)
DESIGN LOADING FACTOR
(gallons per square foot per day)
< 1
Not suitable
1
5
1.20
6
7
1.00
8
10
0.90
11
15
0.80
16
20
0.70
21
30
0.60
31
45
0.50
46
60
0.45
61
120
0.20
> 120
Not Suitable
For SI: 1 minute per inch = min/25.4 mm,
1 gallon per square foot = 40.7 L/m
2
.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1403.1.2 Seepage trench excavations.
Seepage trench excavations shall be not less than 1 foot (304 mm) in width
and not greater than 5 feet (1524 mm) in width. Trench excavations shall be spaced not less than 2 feet (610 mm)
apart. The soil absorption area
of a seepage trench shall be computed by using the bottom of the trench area (width)
multiplied by the length of pipe. Individual seepage trenches shall be not greater than 100 feet (30 480 mm) in
developed length.
1403.1.3 Seepage bed excavations.
Seepa
ge bed excavations shall be not less than 5 feet (1524 mm) in width and
have more than one distribution pipe. The absorption area of a seepage bed shall be computed by using the bottom
of the trench area. Distribution piping in a seepage bed shall be unifo
rmly spaced not greater than 5 feet (1524 mm)
and not less than 3 feet (914 mm) apart, and greater than 3 feet (914 mm) and not less than 1 foot (305 mm) from
the sidewall or headwall.
1403.1.4 Excavation and construction.
The bottom of a trench or bed exc
avation shall be level. Seepage trenches
or beds shall not be excavated where the soil is so wet that such material rolled between the hands forms a soil
wire. All smeared or compacted soil surfaces in the sidewalls or bottom of seepage trench or bed excav
ations shall
be scarified to the depth of smearing or compaction and the loose material removed. Where rain falls on an open
excavation, the soil shall be left until sufficiently dry so a soil wire will not form when soil from the excavation
bottom is roll
ed between the hands. The bottom area shall then be scarified and loose material removed.
1403.1.5 Aggregate and backfill.
Not less than 6 inches in depth of aggregate, ranging in size from
1
/
2
to 2
1
/
2
inches (12.7 mm to 64 mm), shall be laid into the tren
ch below the distribution piping elevation. The aggregate
shall be evenly distributed not less than 2 inches (51 mm) in depth over the top of the distribution pipe. The aggre-
gate shall be covered with approved synthetic materials or 9 inches (229 mm) of un
compacted marsh hay or straw.
Building paper shall not be used to cover the aggregate. Not less than 9 inches (229 mm) of soil backfill shall be
provided above the covering.
1403.2 Distribution piping.
Distribution piping shall be not less than 3 inches (7
6 mm) in diameter. Materials shall
comply with Table 1403.2. The top of the distribution pipe shall be not less than 4 inches (100 mm) or greater than 12
inches (300 mm) below the original surface. The slope of the distribution pipes shall be not less than
2 inches (51 mm)
and not greater than 4 inches (102 mm) per 100 feet (30 480 mm).
TABLE 1403.2
DISTRIBUTION PIPE
MATERIAL
STANDARD
Polypropylene (PP) pipe
ASTM F
2389
Polyethylene (PE) plastic pipe
ASTM F
405
Polyvinyl chloride (PVC) plastic pipe
a
ASTM D
2729
Polyvinyl chloride (PVC) plastic pipe with a 3.5
-
inch O.D. and solid cellular core or composite wall
a
ASTM F
1488
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in
height.
1403.2.1 Joints and fittings.
Joints and fittings in distribution pipe shall be made in accordance with Table
1403.2.1.
TABLE 1403.2.1
JOINTS AND FITTINGS
MATERIAL
STANDARD
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Polyethylene (PE) plastic pipe
ASTM F 405
Polypropylene (PP) pipe
ASTM F 2389
Polyvinyl chloride (PVC) plastic in IPS
diameters
a
ASTM D 2665; ASTM
F 1866
Polyvinyl chloride (PVC) plastic pipe in
sewer and drain diameters
a
ASTM D 3034
Polyvinyl chloride (PVC) plastic pipe
with a 3.25
-
inch O.D.
a
ASTM D 2949
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
1403.2.2 Diversion valves.
Systems shall include a diversion valve to divert gray water
to the building sanitary
system when soils are saturated or frozen, there is a blockage or backup in the system, the maximum allowed
gallons per day is reached, or when system maintenance is necessary.
1403.2.3 Overflow connection.
Systems shall have a pi
ped connection to the building drainage system to accom-
modate tank overflow.
CHAPTER 14
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
SECTION PC 1401
GENERAL
1401.1 Scope.
The provisions of Chapter 14 shall govern the materials, design, construction and installation of sub-
surface landscape irrigation systems connected to nonpotable water from on
-
site water reuse systems.
1401.2 Materials.
Above
-
ground drain, waste and vent p
iping for subsurface landscape irrigation systems shall con-
form to one of the standards listed in Table 702.1. Subsurface landscape irrigation, underground building drainage
and vent pipe shall conform to one of the standards listed in Table 702.2.
1401.3
Tests.
Drain, waste and vent piping for subsurface landscape irrigation systems shall be tested in accordance
with Section 312.
1401.4 Inspections.
Subsurface landscape irrigation systems shall be inspected in accordance with Section 107.
1401.5 Disinfecti
on.
Disinfection shall not be required for on
-
site nonpotable water reuse for subsurface landscape
irrigation systems.
1401.6 Coloring.
On
-
site nonpotable water reuse for subsurface landscape irrigation systems shall not be required to
be dyed.
SECTION PC
1402
SYSTEM DESIGN AND SIZING
1402.1 Sizing.
The system shall be sized in accordance with the sum of the output of all water sources connected to
the subsurface irrigation system. Where gray water collection piping is connected to subsurface landscape irri
gation
systems, gray water output shall be calculated according to the gallons
-
per
-
day
-
per
-
occupant number based on the
type of fixtures connected. The gray water discharge shall be calculated by the following equation:
C = A
×
B
(Equation
14
-
1)
where:
A
= Number of occupants:
Residential
Number of occupants shall be determined by the actual number of occupants, but not less than two
occupants for one bedroom and one occupant for each additional bedroom.
Commercial
Number of occupants s
hall be determined by the
New York City Building Code
.
B
= Estimated flow demands for each occupant*:
Residential
25 gallons per day (94.6 lpd) per occupant for showers, bathtubs and lavatories and 15 gallons per day
(56.7 lpd) per occupant for clothes w
ashers or laundry trays.
Commercial
Based on type of fixture or water use records minus the discharge of fixtures other than those discharg-
ing gray water.
*Alternative estimated flow demands for each occupant shall be permitted based on actual calculate
d water usage for
the building.
C
= Estimated gray water discharge based on the total number of occupants.
1402.2 Percolation tests.
The permeability of the soil in the proposed absorption system shall be determined by
percolation tests or
permeability evaluation.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1402.2.1 Percolation tests and procedures.
At least three percolation tests in each system area shall be conducted.
The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption system. More per-
cola
tion tests shall be made where necessary, depending on system design.
1402.2.1.1 Percolation test hole.
The test hole shall be dug or bored. The test hole shall have vertical sides and
a horizontal dimension of 4 inches to 8 inches (102 mm to 203 mm). The
bottom and sides of the hole shall be
scratched with a sharp
-
pointed instrument to expose the natural soil. All loose material shall be removed from
the hole and the bottom shall be covered with 2 inches (51 mm) of gravel or coarse sand.
1402.2.1.2 Test pr
ocedure, sandy soils.
The hole shall be filled with clear water to a minimum of 12 inches
(305 mm) above the bottom of the hole for tests in sandy soils. The time for this amount of water to seep away
shall be determined, and this procedure shall be repeat
ed if the water from the second filling of the hole seeps
away in 10 minutes or less. The test shall proceed as follows: Water shall be added to a point not more than 6
inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference poin
t, water levels shall be
measured at 10
-
minute intervals for a period of 1 hour. Where 6 inches (152 mm) of water seeps away in less
than 10 minutes, a shorter interval between measurements shall be used, but in no case shall the water depth
exceed 6 inche
s (152 mm). Where 6 inches (152 mm) of water seeps away in less than 2 minutes, the test shall
be stopped and a rate of less than 1 minute per inch (2.4 s/mm) shall be reported. The final water level drop shall
be used to calculate the percolation rate. So
ils not meeting the above requirements shall be tested in accordance
with Section 1402.2.1.3.
1402.2.1.3 Test procedure, other soils.
The hole shall be filled with clear water, and a minimum water depth
of 12 inches (305 mm) shall be maintained above the b
ottom of the hole for a 4
-
hour period by refilling whenever
necessary or by use of an automatic siphon. Water remaining in the hole after 4 hours shall not be removed.
Thereafter, the soil shall be allowed to swell not less than 16 hours or more than 30 ho
urs. Immediately after the
soil swelling period, the measurements for determining the percolation rate shall be made as follows: any soil
sloughed into the hole shall be removed and the water level shall be adjusted to 6 inches (152 mm) above the
gravel or
coarse sand. Thereupon, from a fixed reference point, the water level shall be measured at 30
-
minute
intervals for a period of 4 hours, unless two successive water level drops do not vary by more than
1
/
16
inch (1.59
mm). At least three water level drops
shall be observed and recorded. The hole shall be filled with clear water
to a point not more than 6 inches (152 mm) above the gravel or coarse sand whenever it becomes nearly empty.
Adjustments of the water level shall not be made during the three measure
ment periods except to the limits of
the last measured water level drop. When the first 6 inches (152 mm) of water seeps away in less than 30
minutes, the time interval between measurements shall be 10 minutes and the test run for 1 hour. The water
depth s
hall not exceed 5 inches (127 mm) at any time during the measurement period. The drop that occurs
during the final measurement period shall be used in calculating the percolation rate.
1402.2.1.4 Mechanical test equipment.
Mechanical percolation test equip
ment shall be of an approved
type.
1402.2.2 Permeability evaluation.
Soil shall be evaluated for estimated percolation based on structure and texture
in accordance with accepted soil evaluation practices. Borings shall be made in accordance with
Section 1402.2.1.1
for evaluating the soil.
1402.3 Subsurface landscape irrigation site location.
The surface grade of all soil absorption systems shall be lo-
cated at a point lower than the surface grade of any water well or reservoir on the same or adjoin
ing lot. Where this is
not possible, the site shall be located so surface water drainage from the site is not directed toward a well or reservoir.
The soil absorption system shall be located with a minimum horizontal distance between various elements as in
dicated
in Table 1402.3. Private sewage disposal systems in compacted areas, such as parking lots and driveways, are prohib-
ited. Surface water shall be diverted away from any soil absorption site on the same or neighboring lots.
TABLE 1402.3
LOCATION OF S
UBSURFACE IRRIGATION SYSTEM
ELEMENT
MINIMUM HORIZONTAL DISTANCE
Storage tank (feet)
Irrigation disposal field
(feet)
Buildings
5
10
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Lot line adjoining
private property
5
5
Water wells
50
100
Streams and lakes
50
50
Seepage pits
5
20
Septic
tanks
0
5
Water service
5
5
Public water main
10
10
For SI: 1 foot = 304.8 mm.
SECTION PC 1403
INSTALLATION
1403.1 Installation.
Absorption systems shall be installed in accordance with Sections 1403.1.1 through 1403.1.5 to
provide landscape
irrigation without surfacing of water.
1403.1.1 Absorption area.
The total absorption area required shall be computed from the estimated daily gray
water discharge and the design
-
loading rate based on the percolation rate for the site. The required absorpt
ion area
equals the estimated gray water discharge divided by the design
-
loading rate from Table 1403.1.1.
TABLE 1403.1.1
DESIGN LOADING RATE
PERCOLATION RATE
(minutes per inch)
DESIGN LOADING FACTOR
(gallons per square foot per day)
< 1
Not suitable
1
5
1.20
6
7
1.00
8
10
0.90
11
15
0.80
16
20
0.70
21
30
0.60
31
45
0.50
46
60
0.45
61
120
0.20
> 120
Not Suitable
For SI: 1 minute per inch = min/25.4 mm,
1 gallon per square foot = 40.7 L/m
2
.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1403.1.2 Seepage trench excavations.
Seepage trench excavations shall be not less than 1 foot (304 mm) in width
and not greater than 5 feet (1524 mm) in width. Trench excavations shall be spaced not less than 2 feet (610 mm)
apart. The soil absorption area
of a seepage trench shall be computed by using the bottom of the trench area (width)
multiplied by the length of pipe. Individual seepage trenches shall be not greater than 100 feet (30 480 mm) in
developed length.
1403.1.3 Seepage bed excavations.
Seepa
ge bed excavations shall be not less than 5 feet (1524 mm) in width and
have more than one distribution pipe. The absorption area of a seepage bed shall be computed by using the bottom
of the trench area. Distribution piping in a seepage bed shall be unifo
rmly spaced not greater than 5 feet (1524 mm)
and not less than 3 feet (914 mm) apart, and greater than 3 feet (914 mm) and not less than 1 foot (305 mm) from
the sidewall or headwall.
1403.1.4 Excavation and construction.
The bottom of a trench or bed exc
avation shall be level. Seepage trenches
or beds shall not be excavated where the soil is so wet that such material rolled between the hands forms a soil
wire. All smeared or compacted soil surfaces in the sidewalls or bottom of seepage trench or bed excav
ations shall
be scarified to the depth of smearing or compaction and the loose material removed. Where rain falls on an open
excavation, the soil shall be left until sufficiently dry so a soil wire will not form when soil from the excavation
bottom is roll
ed between the hands. The bottom area shall then be scarified and loose material removed.
1403.1.5 Aggregate and backfill.
Not less than 6 inches in depth of aggregate, ranging in size from
1
/
2
to 2
1
/
2
inches (12.7 mm to 64 mm), shall be laid into the tren
ch below the distribution piping elevation. The aggregate
shall be evenly distributed not less than 2 inches (51 mm) in depth over the top of the distribution pipe. The aggre-
gate shall be covered with approved synthetic materials or 9 inches (229 mm) of un
compacted marsh hay or straw.
Building paper shall not be used to cover the aggregate. Not less than 9 inches (229 mm) of soil backfill shall be
provided above the covering.
1403.2 Distribution piping.
Distribution piping shall be not less than 3 inches (7
6 mm) in diameter. Materials shall
comply with Table 1403.2. The top of the distribution pipe shall be not less than 4 inches (100 mm) or greater than 12
inches (300 mm) below the original surface. The slope of the distribution pipes shall be not less than
2 inches (51 mm)
and not greater than 4 inches (102 mm) per 100 feet (30 480 mm).
TABLE 1403.2
DISTRIBUTION PIPE
MATERIAL
STANDARD
Polypropylene (PP) pipe
ASTM F
2389
Polyethylene (PE) plastic pipe
ASTM F
405
Polyvinyl chloride (PVC) plastic pipe
a
ASTM D
2729
Polyvinyl chloride (PVC) plastic pipe with a 3.5
-
inch O.D. and solid cellular core or composite wall
a
ASTM F
1488
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in
height.
1403.2.1 Joints and fittings.
Joints and fittings in distribution pipe shall be made in accordance with Table
1403.2.1.
TABLE 1403.2.1
JOINTS AND FITTINGS
MATERIAL
STANDARD
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Polyethylene (PE) plastic pipe
ASTM F 405
Polypropylene (PP) pipe
ASTM F 2389
Polyvinyl chloride (PVC) plastic in IPS
diameters
a
ASTM D 2665; ASTM
F 1866
Polyvinyl chloride (PVC) plastic pipe in
sewer and drain diameters
a
ASTM D 3034
Polyvinyl chloride (PVC) plastic pipe
with a 3.25
-
inch O.D.
a
ASTM D 2949
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
1403.2.2 Diversion valves.
Systems shall include a diversion valve to divert gray water
to the building sanitary
system when soils are saturated or frozen, there is a blockage or backup in the system, the maximum allowed
gallons per day is reached, or when system maintenance is necessary.
1403.2.3 Overflow connection.
Systems shall have a pi
ped connection to the building drainage system to accom-
modate tank overflow.
CHAPTER 14
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
SECTION PC 1401
GENERAL
1401.1 Scope.
The provisions of Chapter 14 shall govern the materials, design, construction and installation of sub-
surface landscape irrigation systems connected to nonpotable water from on
-
site water reuse systems.
1401.2 Materials.
Above
-
ground drain, waste and vent p
iping for subsurface landscape irrigation systems shall con-
form to one of the standards listed in Table 702.1. Subsurface landscape irrigation, underground building drainage
and vent pipe shall conform to one of the standards listed in Table 702.2.
1401.3
Tests.
Drain, waste and vent piping for subsurface landscape irrigation systems shall be tested in accordance
with Section 312.
1401.4 Inspections.
Subsurface landscape irrigation systems shall be inspected in accordance with Section 107.
1401.5 Disinfecti
on.
Disinfection shall not be required for on
-
site nonpotable water reuse for subsurface landscape
irrigation systems.
1401.6 Coloring.
On
-
site nonpotable water reuse for subsurface landscape irrigation systems shall not be required to
be dyed.
SECTION PC
1402
SYSTEM DESIGN AND SIZING
1402.1 Sizing.
The system shall be sized in accordance with the sum of the output of all water sources connected to
the subsurface irrigation system. Where gray water collection piping is connected to subsurface landscape irri
gation
systems, gray water output shall be calculated according to the gallons
-
per
-
day
-
per
-
occupant number based on the
type of fixtures connected. The gray water discharge shall be calculated by the following equation:
C = A
×
B
(Equation
14
-
1)
where:
A
= Number of occupants:
Residential
Number of occupants shall be determined by the actual number of occupants, but not less than two
occupants for one bedroom and one occupant for each additional bedroom.
Commercial
Number of occupants s
hall be determined by the
New York City Building Code
.
B
= Estimated flow demands for each occupant*:
Residential
25 gallons per day (94.6 lpd) per occupant for showers, bathtubs and lavatories and 15 gallons per day
(56.7 lpd) per occupant for clothes w
ashers or laundry trays.
Commercial
Based on type of fixture or water use records minus the discharge of fixtures other than those discharg-
ing gray water.
*Alternative estimated flow demands for each occupant shall be permitted based on actual calculate
d water usage for
the building.
C
= Estimated gray water discharge based on the total number of occupants.
1402.2 Percolation tests.
The permeability of the soil in the proposed absorption system shall be determined by
percolation tests or
permeability evaluation.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1402.2.1 Percolation tests and procedures.
At least three percolation tests in each system area shall be conducted.
The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption system. More per-
cola
tion tests shall be made where necessary, depending on system design.
1402.2.1.1 Percolation test hole.
The test hole shall be dug or bored. The test hole shall have vertical sides and
a horizontal dimension of 4 inches to 8 inches (102 mm to 203 mm). The
bottom and sides of the hole shall be
scratched with a sharp
-
pointed instrument to expose the natural soil. All loose material shall be removed from
the hole and the bottom shall be covered with 2 inches (51 mm) of gravel or coarse sand.
1402.2.1.2 Test pr
ocedure, sandy soils.
The hole shall be filled with clear water to a minimum of 12 inches
(305 mm) above the bottom of the hole for tests in sandy soils. The time for this amount of water to seep away
shall be determined, and this procedure shall be repeat
ed if the water from the second filling of the hole seeps
away in 10 minutes or less. The test shall proceed as follows: Water shall be added to a point not more than 6
inches (152 mm) above the gravel or coarse sand. Thereupon, from a fixed reference poin
t, water levels shall be
measured at 10
-
minute intervals for a period of 1 hour. Where 6 inches (152 mm) of water seeps away in less
than 10 minutes, a shorter interval between measurements shall be used, but in no case shall the water depth
exceed 6 inche
s (152 mm). Where 6 inches (152 mm) of water seeps away in less than 2 minutes, the test shall
be stopped and a rate of less than 1 minute per inch (2.4 s/mm) shall be reported. The final water level drop shall
be used to calculate the percolation rate. So
ils not meeting the above requirements shall be tested in accordance
with Section 1402.2.1.3.
1402.2.1.3 Test procedure, other soils.
The hole shall be filled with clear water, and a minimum water depth
of 12 inches (305 mm) shall be maintained above the b
ottom of the hole for a 4
-
hour period by refilling whenever
necessary or by use of an automatic siphon. Water remaining in the hole after 4 hours shall not be removed.
Thereafter, the soil shall be allowed to swell not less than 16 hours or more than 30 ho
urs. Immediately after the
soil swelling period, the measurements for determining the percolation rate shall be made as follows: any soil
sloughed into the hole shall be removed and the water level shall be adjusted to 6 inches (152 mm) above the
gravel or
coarse sand. Thereupon, from a fixed reference point, the water level shall be measured at 30
-
minute
intervals for a period of 4 hours, unless two successive water level drops do not vary by more than
1
/
16
inch (1.59
mm). At least three water level drops
shall be observed and recorded. The hole shall be filled with clear water
to a point not more than 6 inches (152 mm) above the gravel or coarse sand whenever it becomes nearly empty.
Adjustments of the water level shall not be made during the three measure
ment periods except to the limits of
the last measured water level drop. When the first 6 inches (152 mm) of water seeps away in less than 30
minutes, the time interval between measurements shall be 10 minutes and the test run for 1 hour. The water
depth s
hall not exceed 5 inches (127 mm) at any time during the measurement period. The drop that occurs
during the final measurement period shall be used in calculating the percolation rate.
1402.2.1.4 Mechanical test equipment.
Mechanical percolation test equip
ment shall be of an approved
type.
1402.2.2 Permeability evaluation.
Soil shall be evaluated for estimated percolation based on structure and texture
in accordance with accepted soil evaluation practices. Borings shall be made in accordance with
Section 1402.2.1.1
for evaluating the soil.
1402.3 Subsurface landscape irrigation site location.
The surface grade of all soil absorption systems shall be lo-
cated at a point lower than the surface grade of any water well or reservoir on the same or adjoin
ing lot. Where this is
not possible, the site shall be located so surface water drainage from the site is not directed toward a well or reservoir.
The soil absorption system shall be located with a minimum horizontal distance between various elements as in
dicated
in Table 1402.3. Private sewage disposal systems in compacted areas, such as parking lots and driveways, are prohib-
ited. Surface water shall be diverted away from any soil absorption site on the same or neighboring lots.
TABLE 1402.3
LOCATION OF S
UBSURFACE IRRIGATION SYSTEM
ELEMENT
MINIMUM HORIZONTAL DISTANCE
Storage tank (feet)
Irrigation disposal field
(feet)
Buildings
5
10
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Lot line adjoining
private property
5
5
Water wells
50
100
Streams and lakes
50
50
Seepage pits
5
20
Septic
tanks
0
5
Water service
5
5
Public water main
10
10
For SI: 1 foot = 304.8 mm.
SECTION PC 1403
INSTALLATION
1403.1 Installation.
Absorption systems shall be installed in accordance with Sections 1403.1.1 through 1403.1.5 to
provide landscape
irrigation without surfacing of water.
1403.1.1 Absorption area.
The total absorption area required shall be computed from the estimated daily gray
water discharge and the design
-
loading rate based on the percolation rate for the site. The required absorpt
ion area
equals the estimated gray water discharge divided by the design
-
loading rate from Table 1403.1.1.
TABLE 1403.1.1
DESIGN LOADING RATE
PERCOLATION RATE
(minutes per inch)
DESIGN LOADING FACTOR
(gallons per square foot per day)
< 1
Not suitable
1
5
1.20
6
7
1.00
8
10
0.90
11
15
0.80
16
20
0.70
21
30
0.60
31
45
0.50
46
60
0.45
61
120
0.20
> 120
Not Suitable
For SI: 1 minute per inch = min/25.4 mm,
1 gallon per square foot = 40.7 L/m
2
.
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1403.1.2 Seepage trench excavations.
Seepage trench excavations shall be not less than 1 foot (304 mm) in width
and not greater than 5 feet (1524 mm) in width. Trench excavations shall be spaced not less than 2 feet (610 mm)
apart. The soil absorption area
of a seepage trench shall be computed by using the bottom of the trench area (width)
multiplied by the length of pipe. Individual seepage trenches shall be not greater than 100 feet (30 480 mm) in
developed length.
1403.1.3 Seepage bed excavations.
Seepa
ge bed excavations shall be not less than 5 feet (1524 mm) in width and
have more than one distribution pipe. The absorption area of a seepage bed shall be computed by using the bottom
of the trench area. Distribution piping in a seepage bed shall be unifo
rmly spaced not greater than 5 feet (1524 mm)
and not less than 3 feet (914 mm) apart, and greater than 3 feet (914 mm) and not less than 1 foot (305 mm) from
the sidewall or headwall.
1403.1.4 Excavation and construction.
The bottom of a trench or bed exc
avation shall be level. Seepage trenches
or beds shall not be excavated where the soil is so wet that such material rolled between the hands forms a soil
wire. All smeared or compacted soil surfaces in the sidewalls or bottom of seepage trench or bed excav
ations shall
be scarified to the depth of smearing or compaction and the loose material removed. Where rain falls on an open
excavation, the soil shall be left until sufficiently dry so a soil wire will not form when soil from the excavation
bottom is roll
ed between the hands. The bottom area shall then be scarified and loose material removed.
1403.1.5 Aggregate and backfill.
Not less than 6 inches in depth of aggregate, ranging in size from
1
/
2
to 2
1
/
2
inches (12.7 mm to 64 mm), shall be laid into the tren
ch below the distribution piping elevation. The aggregate
shall be evenly distributed not less than 2 inches (51 mm) in depth over the top of the distribution pipe. The aggre-
gate shall be covered with approved synthetic materials or 9 inches (229 mm) of un
compacted marsh hay or straw.
Building paper shall not be used to cover the aggregate. Not less than 9 inches (229 mm) of soil backfill shall be
provided above the covering.
1403.2 Distribution piping.
Distribution piping shall be not less than 3 inches (7
6 mm) in diameter. Materials shall
comply with Table 1403.2. The top of the distribution pipe shall be not less than 4 inches (100 mm) or greater than 12
inches (300 mm) below the original surface. The slope of the distribution pipes shall be not less than
2 inches (51 mm)
and not greater than 4 inches (102 mm) per 100 feet (30 480 mm).
TABLE 1403.2
DISTRIBUTION PIPE
MATERIAL
STANDARD
Polypropylene (PP) pipe
ASTM F
2389
Polyethylene (PE) plastic pipe
ASTM F
405
Polyvinyl chloride (PVC) plastic pipe
a
ASTM D
2729
Polyvinyl chloride (PVC) plastic pipe with a 3.5
-
inch O.D. and solid cellular core or composite wall
a
ASTM F
1488
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in
height.
1403.2.1 Joints and fittings.
Joints and fittings in distribution pipe shall be made in accordance with Table
1403.2.1.
TABLE 1403.2.1
JOINTS AND FITTINGS
MATERIAL
STANDARD
SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
Polyethylene (PE) plastic pipe
ASTM F 405
Polypropylene (PP) pipe
ASTM F 2389
Polyvinyl chloride (PVC) plastic in IPS
diameters
a
ASTM D 2665; ASTM
F 1866
Polyvinyl chloride (PVC) plastic pipe in
sewer and drain diameters
a
ASTM D 3034
Polyvinyl chloride (PVC) plastic pipe
with a 3.25
-
inch O.D.
a
ASTM D 2949
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
1403.2.2 Diversion valves.
Systems shall include a diversion valve to divert gray water
to the building sanitary
system when soils are saturated or frozen, there is a blockage or backup in the system, the maximum allowed
gallons per day is reached, or when system maintenance is necessary.
1403.2.3 Overflow connection.
Systems shall have a pi
ped connection to the building drainage system to accom-
modate tank overflow.