| ‡‡‡ Chapter 10 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 10 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| SECTION MC 1001 | |
| GENERAL | |
| 1001.1 Scope. | |
| This chapter | |
| shall establish the minimum safety requirements for and | |
| shall govern the installation, | |
| alteration and repair of boilers, wate | |
| r heaters and pressure vessels. | |
| Exceptions: | |
| 1. | |
| Pressure vessels used for unheated water supply. | |
| 2. | |
| Portable unfired pressure vessels and Interstate | |
| Commerce | |
| Commission containers. | |
| 3. | |
| Containers for bulk oxygen and medical gas. | |
| 4. | |
| Unfired pressure | |
| vessels having a volume of 5 cubic feet (0.14 m | |
| 3 | |
| ) or less operating at pressures not exceed- | |
| ing 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, | |
| S and U. | |
| 5. | |
| Pressure vessels used in refrigeration systems | |
| that are regulated by Chapter 11. | |
| 6. | |
| Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other | |
| similar | |
| humidity control systems. | |
| 7. | |
| Any boiler or pressure vessel subject to inspection by federal inspectors. | |
| 1001.2 The | |
| rmal safety (spill) switches. | |
| Thermal safety (spill) switches shall be installed in accordance with Section | |
| 801.23.3. | |
| 1001.3 Clearances. | |
| Minimum clearances at | |
| boilers, water heaters and pressure vessels shall be maintained in accord- | |
| ance with Chapter 3. | |
| SEC | |
| TION MC 1002 | |
| WATER HEATERS | |
| 1002.1 General. | |
| Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accord- | |
| ance with the manufacturer’s instructions, the | |
| New York City | |
| Plumbing Code | |
| and this code. All water heaters shal | |
| l be | |
| capable of being removed without first removing a permanent portion of the building structure. The potable water | |
| connections | |
| and relief valves for all water heaters shall conform to the requirements of the | |
| New York City | |
| Plumbing | |
| Code | |
| . Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall | |
| comply with UL 1453. Oil | |
| - | |
| fired water heaters shall comply with UL 732. Approval for oil | |
| - | |
| fired water heaters | |
| 350,000 | |
| Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. | |
| Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water | |
| heaters shall comply with UL 174 or UL 1995. | |
| 1002.2 Water heaters utilized for s | |
| pace heating. | |
| Water heaters utilized both to supply potable hot water and provide | |
| hot water for space | |
| - | |
| heating applications shall be listed and labeled for such applications by the manufacturer and shall | |
| be | |
| built in accordance with Section IV of the | |
| ASME | |
| Boiler and Pressure Vessel Code | |
| with an “H” code stamp. Water | |
| heaters shall be | |
| installed in accordance with the manufacturer’s instructions | |
| , the | |
| ASME Boiler and Pressure Vessel | |
| Code | |
| and the | |
| New York City | |
| Plumbing Code. | |
| Oil | |
| - | |
| fired heaters shall comply with U | |
| L 732 and shall have an “HW” | |
| stamp. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1002.2.1 Sizing. | |
| Water heaters utilized for both potable water heating and space | |
| - | |
| heating applications shall be sized | |
| to prevent the space | |
| - | |
| heating load from diminishing the required potable water | |
| - | |
| heating capacity. | |
| 1002.2. | |
| 2 Temperature limitation. | |
| Where a combination potable water | |
| - | |
| heating and space | |
| - | |
| heating system requires | |
| water for space heating, a temperature | |
| actuated mixing valve complying with ASSE 1017 shall be provided to | |
| temper the water supplied to the potable hot wa | |
| ter distribution system in accordance with Section 607 of the | |
| New | |
| York City Plumbing Code | |
| . | |
| 1002.2.3 Cross | |
| - | |
| connection. | |
| Water heaters utilized for both potable hot water and hot water for space | |
| - | |
| heating | |
| applications shall have separate heating sections and co | |
| nnections for distribution systems and shall not be cross | |
| - | |
| connected. The potability of the domestic water shall be maintained throughout the system in accordance with the | |
| New York City Plumbing Code. | |
| 1002.3 Supplemental water | |
| - | |
| heating devices. | |
| Potable | |
| water | |
| - | |
| heating devices that utilize refrigerant | |
| - | |
| to | |
| - | |
| water heat | |
| exchangers shall be approved and installed in accordance with the | |
| New York City | |
| Plumbing Code | |
| , the applicable | |
| provisions of the | |
| New York City Energy Conservation Code | |
| and the manufacturer’s | |
| instructions. | |
| SECTION MC 1003 | |
| PRESSURE VESSELS | |
| 1003.1 General. | |
| All pressure vessels shall be constructed and certified in accordance with the | |
| ASME Boiler and | |
| Pressure Vessel Code | |
| , and shall | |
| bear the label of an approved agency. Pressure vessels shall | |
| be in | |
| stalled in accordance | |
| with the manufacturer’s | |
| instructions and nationally recognized standards. Directly fired pressure vessels shall meet | |
| the requirements of Section 1004. | |
| 1003.2 Piping. | |
| All piping materials, fittings, joints, | |
| connections | |
| and devices asso | |
| ciated with systems utilized in | |
| con- | |
| junction | |
| with pressure vessels shall be designed for the specific application and shall | |
| comply with the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| and this code | |
| . | |
| 1003.3 Welding. | |
| Welding on pressure vessels shall be performed by | |
| welders | |
| certified in | |
| compliance with nationally | |
| recognized standards, including the | |
| National Board Inspection Code | |
| and | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| Section | |
| IX. Such welders shall also comply with 12 NYCRR 4 | |
| - | |
| 6.2, and 12 NYCRR 14 | |
| - | |
| 3.3 through 14 | |
| - | |
| 3.1 | |
| 8. | |
| SECTION | |
| MC | |
| 1004 | |
| BOILERS | |
| 1004.1 Standards. | |
| Boilers shall be designed, constructed and certified in accordance with the | |
| ASME Boiler and Pres- | |
| sure Vessel Code | |
| , Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with | |
| fuel | |
| input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD | |
| - | |
| 1. Controls and safety | |
| devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. | |
| Packaged oil | |
| - | |
| fired boile | |
| rs shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be | |
| listed and labeled in accordance with UL 834. | |
| Approval for oil | |
| - | |
| fired boilers 350,000 Btu/h input (102.6 kW) and | |
| above shall be obtained from the New York City Depa | |
| rtment of Environmental Protection. | |
| 1004.1.1 Field erected boilers requirements. | |
| Field erected boiler installations shall comply with the following | |
| : | |
| 1. | |
| The vessel erector shall hold the appropriate ASME stamp for vessel construction. | |
| 2. | |
| The licensed instal | |
| ler is responsible for the installation of all controls and burners which shall be designed | |
| and constructed in accordance with the requirements of ASME CSD | |
| - | |
| 1 and, as applicable, the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| , 12 NYCRR Parts 4 and 14, and NFPA 85 | |
| . | |
| 3. | |
| The New York City Department of Environmental Protection shall approve the installation of the boiler and | |
| burner for compatibility, controls and safety devices. | |
| 4. | |
| Boiler vessels shall comply with one of the following listings: | |
| 4.1. | |
| UL 726 or UL 795 a | |
| s applicable; or | |
| ‡‡‡ Chapter 10 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 10 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| SECTION MC 1001 | |
| GENERAL | |
| 1001.1 Scope. | |
| This chapter | |
| shall establish the minimum safety requirements for and | |
| shall govern the installation, | |
| alteration and repair of boilers, wate | |
| r heaters and pressure vessels. | |
| Exceptions: | |
| 1. | |
| Pressure vessels used for unheated water supply. | |
| 2. | |
| Portable unfired pressure vessels and Interstate | |
| Commerce | |
| Commission containers. | |
| 3. | |
| Containers for bulk oxygen and medical gas. | |
| 4. | |
| Unfired pressure | |
| vessels having a volume of 5 cubic feet (0.14 m | |
| 3 | |
| ) or less operating at pressures not exceed- | |
| ing 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, | |
| S and U. | |
| 5. | |
| Pressure vessels used in refrigeration systems | |
| that are regulated by Chapter 11. | |
| 6. | |
| Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other | |
| similar | |
| humidity control systems. | |
| 7. | |
| Any boiler or pressure vessel subject to inspection by federal inspectors. | |
| 1001.2 The | |
| rmal safety (spill) switches. | |
| Thermal safety (spill) switches shall be installed in accordance with Section | |
| 801.23.3. | |
| 1001.3 Clearances. | |
| Minimum clearances at | |
| boilers, water heaters and pressure vessels shall be maintained in accord- | |
| ance with Chapter 3. | |
| SEC | |
| TION MC 1002 | |
| WATER HEATERS | |
| 1002.1 General. | |
| Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accord- | |
| ance with the manufacturer’s instructions, the | |
| New York City | |
| Plumbing Code | |
| and this code. All water heaters shal | |
| l be | |
| capable of being removed without first removing a permanent portion of the building structure. The potable water | |
| connections | |
| and relief valves for all water heaters shall conform to the requirements of the | |
| New York City | |
| Plumbing | |
| Code | |
| . Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall | |
| comply with UL 1453. Oil | |
| - | |
| fired water heaters shall comply with UL 732. Approval for oil | |
| - | |
| fired water heaters | |
| 350,000 | |
| Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. | |
| Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water | |
| heaters shall comply with UL 174 or UL 1995. | |
| 1002.2 Water heaters utilized for s | |
| pace heating. | |
| Water heaters utilized both to supply potable hot water and provide | |
| hot water for space | |
| - | |
| heating applications shall be listed and labeled for such applications by the manufacturer and shall | |
| be | |
| built in accordance with Section IV of the | |
| ASME | |
| Boiler and Pressure Vessel Code | |
| with an “H” code stamp. Water | |
| heaters shall be | |
| installed in accordance with the manufacturer’s instructions | |
| , the | |
| ASME Boiler and Pressure Vessel | |
| Code | |
| and the | |
| New York City | |
| Plumbing Code. | |
| Oil | |
| - | |
| fired heaters shall comply with U | |
| L 732 and shall have an “HW” | |
| stamp. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1002.2.1 Sizing. | |
| Water heaters utilized for both potable water heating and space | |
| - | |
| heating applications shall be sized | |
| to prevent the space | |
| - | |
| heating load from diminishing the required potable water | |
| - | |
| heating capacity. | |
| 1002.2. | |
| 2 Temperature limitation. | |
| Where a combination potable water | |
| - | |
| heating and space | |
| - | |
| heating system requires | |
| water for space heating, a temperature | |
| actuated mixing valve complying with ASSE 1017 shall be provided to | |
| temper the water supplied to the potable hot wa | |
| ter distribution system in accordance with Section 607 of the | |
| New | |
| York City Plumbing Code | |
| . | |
| 1002.2.3 Cross | |
| - | |
| connection. | |
| Water heaters utilized for both potable hot water and hot water for space | |
| - | |
| heating | |
| applications shall have separate heating sections and co | |
| nnections for distribution systems and shall not be cross | |
| - | |
| connected. The potability of the domestic water shall be maintained throughout the system in accordance with the | |
| New York City Plumbing Code. | |
| 1002.3 Supplemental water | |
| - | |
| heating devices. | |
| Potable | |
| water | |
| - | |
| heating devices that utilize refrigerant | |
| - | |
| to | |
| - | |
| water heat | |
| exchangers shall be approved and installed in accordance with the | |
| New York City | |
| Plumbing Code | |
| , the applicable | |
| provisions of the | |
| New York City Energy Conservation Code | |
| and the manufacturer’s | |
| instructions. | |
| SECTION MC 1003 | |
| PRESSURE VESSELS | |
| 1003.1 General. | |
| All pressure vessels shall be constructed and certified in accordance with the | |
| ASME Boiler and | |
| Pressure Vessel Code | |
| , and shall | |
| bear the label of an approved agency. Pressure vessels shall | |
| be in | |
| stalled in accordance | |
| with the manufacturer’s | |
| instructions and nationally recognized standards. Directly fired pressure vessels shall meet | |
| the requirements of Section 1004. | |
| 1003.2 Piping. | |
| All piping materials, fittings, joints, | |
| connections | |
| and devices asso | |
| ciated with systems utilized in | |
| con- | |
| junction | |
| with pressure vessels shall be designed for the specific application and shall | |
| comply with the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| and this code | |
| . | |
| 1003.3 Welding. | |
| Welding on pressure vessels shall be performed by | |
| welders | |
| certified in | |
| compliance with nationally | |
| recognized standards, including the | |
| National Board Inspection Code | |
| and | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| Section | |
| IX. Such welders shall also comply with 12 NYCRR 4 | |
| - | |
| 6.2, and 12 NYCRR 14 | |
| - | |
| 3.3 through 14 | |
| - | |
| 3.1 | |
| 8. | |
| SECTION | |
| MC | |
| 1004 | |
| BOILERS | |
| 1004.1 Standards. | |
| Boilers shall be designed, constructed and certified in accordance with the | |
| ASME Boiler and Pres- | |
| sure Vessel Code | |
| , Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with | |
| fuel | |
| input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD | |
| - | |
| 1. Controls and safety | |
| devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. | |
| Packaged oil | |
| - | |
| fired boile | |
| rs shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be | |
| listed and labeled in accordance with UL 834. | |
| Approval for oil | |
| - | |
| fired boilers 350,000 Btu/h input (102.6 kW) and | |
| above shall be obtained from the New York City Depa | |
| rtment of Environmental Protection. | |
| 1004.1.1 Field erected boilers requirements. | |
| Field erected boiler installations shall comply with the following | |
| : | |
| 1. | |
| The vessel erector shall hold the appropriate ASME stamp for vessel construction. | |
| 2. | |
| The licensed instal | |
| ler is responsible for the installation of all controls and burners which shall be designed | |
| and constructed in accordance with the requirements of ASME CSD | |
| - | |
| 1 and, as applicable, the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| , 12 NYCRR Parts 4 and 14, and NFPA 85 | |
| . | |
| 3. | |
| The New York City Department of Environmental Protection shall approve the installation of the boiler and | |
| burner for compatibility, controls and safety devices. | |
| 4. | |
| Boiler vessels shall comply with one of the following listings: | |
| 4.1. | |
| UL 726 or UL 795 a | |
| s applicable; or | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 4.2. | |
| UL 2106. | |
| Exception: | |
| Unlisted equipment shall obtain approval from the department. | |
| 5. | |
| Controls and safety devices shall be tested and inspected in accordance with ASME CSD | |
| - | |
| 1 and, as applicable, | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| 12 NYCRR Parts 4 and 14, and NFPA 85. Testing and inspection | |
| shall be performed by the burner manufacturer’s authorized representative in the presence of the licensed | |
| installer. | |
| 6. | |
| Inspection of the installed boiler assembly shall be performed by the dep | |
| artment. | |
| 1004.2 Installation. | |
| In addition to the requirements of this code, the installation of boilers shall conform to the | |
| man- | |
| ufacturer’s | |
| instructions. Operating instructions of a permanent type shall be | |
| located in | |
| the boiler | |
| room and readily | |
| accessible | |
| . | |
| Boilers shall have all controls set, adjusted and tested by the installer. The manufacturer’s rating data and | |
| the nameplate shall be attached to the boiler. | |
| 1004.3 Working clearance. | |
| Clearances shall be maintained around boilers, generators, heaters, tanks and related | |
| equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When | |
| boilers are installed or replaced, clearance shall | |
| be provided to allow access for maintenance and repair | |
| per the boiler’s | |
| listing and manufacturer’s instructions. | |
| Passageways | |
| for inspection | |
| around all sides of boilers shall have an unob- | |
| structed width of not less than 18 inches | |
| ( | |
| 457.2 | |
| mm) | |
| unless | |
| the boiler | |
| ’s listing or department approval or manufac- | |
| turer’s instructions state | |
| otherwise. | |
| 1004.3.1 Top clearance. | |
| Clearances from the tops of boilers to the ceiling or other overhead obstruction shall be | |
| in accordance with Table 1004.3.1. | |
| TABLE 1004.3.1 | |
| BOILER TOP | |
| CLEARANCES | |
| BOILER TYPE | |
| MINIMUM | |
| CLEARANCES FROM | |
| TOP OF BOILER TO | |
| CEILING OR OTHER | |
| OVERHEAD | |
| OBSTRUCTION (feet) | |
| All boilers with manholes on top of the | |
| boiler except where a greater clearance is | |
| required in this table. | |
| 3 | |
| All boilers without | |
| manholes on top of | |
| the boiler except high | |
| - | |
| pressure steam | |
| boilers and where a greater clearance is | |
| required in this table. | |
| 2 | |
| High | |
| - | |
| pressure steam boilers with steam | |
| generating capacity not exceeding 5,000 | |
| pounds per hour. | |
| 3 | |
| High | |
| - | |
| pressure steam | |
| boilers with steam | |
| generating capacity exceeding 5,000 | |
| pounds per hour. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface not exceeding 1,000 square | |
| feet. | |
| 3 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface in excess of 1,000 square | |
| feet. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers with input | |
| not exceeding 5,000,000 Btu/h. | |
| 3 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| High | |
| - | |
| pressure steam boilers with input in | |
| excess of 5,000,000 Btu/h. | |
| 7 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers with input exceeding | |
| 5,000,000 Btu/h. | |
| 3 | |
| Steam | |
| - | |
| heating boilers exceeding 5,000 | |
| pounds of steam per hour. | |
| 3 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers having heating surface | |
| exceeding 1,000 square feet. | |
| 3 | |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m | |
| 2 | |
| , 1 pound per hour = 0.4536 | |
| kg/h, 1 Btu/hr = 0.293 W. | |
| 1004.4 Mounting. | |
| Equipment | |
| and appliances | |
| shall be set or mounted on a level base capable of supporting and dis- | |
| tributing the weight contained thereon. Boilers, tanks and equipment shall be | |
| securely anchored to the structure. | |
| Equ | |
| ipment and appliances requiring vibration isolation shall be installed as designed by a registered design profes- | |
| sional | |
| in accordance with the manufacturer’s instructions. | |
| 1004.5 Floors. | |
| Boilers shall be mounted on floors of noncombustible | |
| construction, unless listed for mounting on | |
| combustible flooring. Vibration isolation shall be in accordance with Section 313. In buildings with residential occu- | |
| pancies, boilers shall be installed in accordance with the requirements of Section 313. | |
| 1004.6 | |
| Boiler rooms and enclosures. | |
| Boiler rooms and enclosures and access thereto shall comply with Chapters 5 | |
| and 10 of the | |
| New York City | |
| Building Code | |
| and Chapter 3 of this code. Boiler rooms shall be equipped with a floor | |
| drain or other approved means for | |
| disposing | |
| of liquid waste | |
| in accordance with the | |
| New York City Plumbing Code | |
| . | |
| 1004.7 Operating adjustments and instructions. | |
| Hot water and steam boil | |
| ers shall have all operating and safety | |
| controls set and operationally tested by the installing contractor. A | |
| complete | |
| control diagram and boiler operating | |
| instructions shall be furnished by the installer for each installation. | |
| A complete control diagram o | |
| f a permanent type | |
| shall be located in the boiler room and shall be readily accessible. | |
| 1004.8 Burner controls. | |
| Gas and oil modulating burners shall be provided with burner controls (oil and gas equiv- | |
| alent ratings) in accordance with ASME CSD | |
| - | |
| 1 and NFPA 85 | |
| . | |
| 1004.9 Conversion burners. | |
| Conversion burners shall be installed in accordance with ANSI Z21.8. | |
| SECTION MC 1005 | |
| BOILER CONNECTIONS | |
| 1005.1 Valves. | |
| Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple | |
| boil | |
| er or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in | |
| the | |
| supply | |
| and return piping. | |
| Exception: | |
| Shutoff valves are not required in a system | |
| having | |
| a single low | |
| - | |
| pressure steam boiler | |
| of 350,000 Btu | |
| /h | |
| (103 kW) output or less | |
| . | |
| 1005.2 Potable water supply. | |
| The water supply to all boilers, including but not limited to backflow prevention, shall | |
| be connected in accordance with the | |
| New | |
| York City | |
| Plumbing Code | |
| . | |
| SECTION MC 1006 | |
| SAFETY AND PRESSURE | |
| RELIEF VALVES | |
| AND CONTROLS | |
| 1006.1 Safety valves for steam boilers. | |
| Steam boilers shall be protected with a safety valve | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| ‡‡‡ Chapter 10 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 10 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| SECTION MC 1001 | |
| GENERAL | |
| 1001.1 Scope. | |
| This chapter | |
| shall establish the minimum safety requirements for and | |
| shall govern the installation, | |
| alteration and repair of boilers, wate | |
| r heaters and pressure vessels. | |
| Exceptions: | |
| 1. | |
| Pressure vessels used for unheated water supply. | |
| 2. | |
| Portable unfired pressure vessels and Interstate | |
| Commerce | |
| Commission containers. | |
| 3. | |
| Containers for bulk oxygen and medical gas. | |
| 4. | |
| Unfired pressure | |
| vessels having a volume of 5 cubic feet (0.14 m | |
| 3 | |
| ) or less operating at pressures not exceed- | |
| ing 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, | |
| S and U. | |
| 5. | |
| Pressure vessels used in refrigeration systems | |
| that are regulated by Chapter 11. | |
| 6. | |
| Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other | |
| similar | |
| humidity control systems. | |
| 7. | |
| Any boiler or pressure vessel subject to inspection by federal inspectors. | |
| 1001.2 The | |
| rmal safety (spill) switches. | |
| Thermal safety (spill) switches shall be installed in accordance with Section | |
| 801.23.3. | |
| 1001.3 Clearances. | |
| Minimum clearances at | |
| boilers, water heaters and pressure vessels shall be maintained in accord- | |
| ance with Chapter 3. | |
| SEC | |
| TION MC 1002 | |
| WATER HEATERS | |
| 1002.1 General. | |
| Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accord- | |
| ance with the manufacturer’s instructions, the | |
| New York City | |
| Plumbing Code | |
| and this code. All water heaters shal | |
| l be | |
| capable of being removed without first removing a permanent portion of the building structure. The potable water | |
| connections | |
| and relief valves for all water heaters shall conform to the requirements of the | |
| New York City | |
| Plumbing | |
| Code | |
| . Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall | |
| comply with UL 1453. Oil | |
| - | |
| fired water heaters shall comply with UL 732. Approval for oil | |
| - | |
| fired water heaters | |
| 350,000 | |
| Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. | |
| Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water | |
| heaters shall comply with UL 174 or UL 1995. | |
| 1002.2 Water heaters utilized for s | |
| pace heating. | |
| Water heaters utilized both to supply potable hot water and provide | |
| hot water for space | |
| - | |
| heating applications shall be listed and labeled for such applications by the manufacturer and shall | |
| be | |
| built in accordance with Section IV of the | |
| ASME | |
| Boiler and Pressure Vessel Code | |
| with an “H” code stamp. Water | |
| heaters shall be | |
| installed in accordance with the manufacturer’s instructions | |
| , the | |
| ASME Boiler and Pressure Vessel | |
| Code | |
| and the | |
| New York City | |
| Plumbing Code. | |
| Oil | |
| - | |
| fired heaters shall comply with U | |
| L 732 and shall have an “HW” | |
| stamp. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1002.2.1 Sizing. | |
| Water heaters utilized for both potable water heating and space | |
| - | |
| heating applications shall be sized | |
| to prevent the space | |
| - | |
| heating load from diminishing the required potable water | |
| - | |
| heating capacity. | |
| 1002.2. | |
| 2 Temperature limitation. | |
| Where a combination potable water | |
| - | |
| heating and space | |
| - | |
| heating system requires | |
| water for space heating, a temperature | |
| actuated mixing valve complying with ASSE 1017 shall be provided to | |
| temper the water supplied to the potable hot wa | |
| ter distribution system in accordance with Section 607 of the | |
| New | |
| York City Plumbing Code | |
| . | |
| 1002.2.3 Cross | |
| - | |
| connection. | |
| Water heaters utilized for both potable hot water and hot water for space | |
| - | |
| heating | |
| applications shall have separate heating sections and co | |
| nnections for distribution systems and shall not be cross | |
| - | |
| connected. The potability of the domestic water shall be maintained throughout the system in accordance with the | |
| New York City Plumbing Code. | |
| 1002.3 Supplemental water | |
| - | |
| heating devices. | |
| Potable | |
| water | |
| - | |
| heating devices that utilize refrigerant | |
| - | |
| to | |
| - | |
| water heat | |
| exchangers shall be approved and installed in accordance with the | |
| New York City | |
| Plumbing Code | |
| , the applicable | |
| provisions of the | |
| New York City Energy Conservation Code | |
| and the manufacturer’s | |
| instructions. | |
| SECTION MC 1003 | |
| PRESSURE VESSELS | |
| 1003.1 General. | |
| All pressure vessels shall be constructed and certified in accordance with the | |
| ASME Boiler and | |
| Pressure Vessel Code | |
| , and shall | |
| bear the label of an approved agency. Pressure vessels shall | |
| be in | |
| stalled in accordance | |
| with the manufacturer’s | |
| instructions and nationally recognized standards. Directly fired pressure vessels shall meet | |
| the requirements of Section 1004. | |
| 1003.2 Piping. | |
| All piping materials, fittings, joints, | |
| connections | |
| and devices asso | |
| ciated with systems utilized in | |
| con- | |
| junction | |
| with pressure vessels shall be designed for the specific application and shall | |
| comply with the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| and this code | |
| . | |
| 1003.3 Welding. | |
| Welding on pressure vessels shall be performed by | |
| welders | |
| certified in | |
| compliance with nationally | |
| recognized standards, including the | |
| National Board Inspection Code | |
| and | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| Section | |
| IX. Such welders shall also comply with 12 NYCRR 4 | |
| - | |
| 6.2, and 12 NYCRR 14 | |
| - | |
| 3.3 through 14 | |
| - | |
| 3.1 | |
| 8. | |
| SECTION | |
| MC | |
| 1004 | |
| BOILERS | |
| 1004.1 Standards. | |
| Boilers shall be designed, constructed and certified in accordance with the | |
| ASME Boiler and Pres- | |
| sure Vessel Code | |
| , Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with | |
| fuel | |
| input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD | |
| - | |
| 1. Controls and safety | |
| devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. | |
| Packaged oil | |
| - | |
| fired boile | |
| rs shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be | |
| listed and labeled in accordance with UL 834. | |
| Approval for oil | |
| - | |
| fired boilers 350,000 Btu/h input (102.6 kW) and | |
| above shall be obtained from the New York City Depa | |
| rtment of Environmental Protection. | |
| 1004.1.1 Field erected boilers requirements. | |
| Field erected boiler installations shall comply with the following | |
| : | |
| 1. | |
| The vessel erector shall hold the appropriate ASME stamp for vessel construction. | |
| 2. | |
| The licensed instal | |
| ler is responsible for the installation of all controls and burners which shall be designed | |
| and constructed in accordance with the requirements of ASME CSD | |
| - | |
| 1 and, as applicable, the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| , 12 NYCRR Parts 4 and 14, and NFPA 85 | |
| . | |
| 3. | |
| The New York City Department of Environmental Protection shall approve the installation of the boiler and | |
| burner for compatibility, controls and safety devices. | |
| 4. | |
| Boiler vessels shall comply with one of the following listings: | |
| 4.1. | |
| UL 726 or UL 795 a | |
| s applicable; or | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 4.2. | |
| UL 2106. | |
| Exception: | |
| Unlisted equipment shall obtain approval from the department. | |
| 5. | |
| Controls and safety devices shall be tested and inspected in accordance with ASME CSD | |
| - | |
| 1 and, as applicable, | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| 12 NYCRR Parts 4 and 14, and NFPA 85. Testing and inspection | |
| shall be performed by the burner manufacturer’s authorized representative in the presence of the licensed | |
| installer. | |
| 6. | |
| Inspection of the installed boiler assembly shall be performed by the dep | |
| artment. | |
| 1004.2 Installation. | |
| In addition to the requirements of this code, the installation of boilers shall conform to the | |
| man- | |
| ufacturer’s | |
| instructions. Operating instructions of a permanent type shall be | |
| located in | |
| the boiler | |
| room and readily | |
| accessible | |
| . | |
| Boilers shall have all controls set, adjusted and tested by the installer. The manufacturer’s rating data and | |
| the nameplate shall be attached to the boiler. | |
| 1004.3 Working clearance. | |
| Clearances shall be maintained around boilers, generators, heaters, tanks and related | |
| equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When | |
| boilers are installed or replaced, clearance shall | |
| be provided to allow access for maintenance and repair | |
| per the boiler’s | |
| listing and manufacturer’s instructions. | |
| Passageways | |
| for inspection | |
| around all sides of boilers shall have an unob- | |
| structed width of not less than 18 inches | |
| ( | |
| 457.2 | |
| mm) | |
| unless | |
| the boiler | |
| ’s listing or department approval or manufac- | |
| turer’s instructions state | |
| otherwise. | |
| 1004.3.1 Top clearance. | |
| Clearances from the tops of boilers to the ceiling or other overhead obstruction shall be | |
| in accordance with Table 1004.3.1. | |
| TABLE 1004.3.1 | |
| BOILER TOP | |
| CLEARANCES | |
| BOILER TYPE | |
| MINIMUM | |
| CLEARANCES FROM | |
| TOP OF BOILER TO | |
| CEILING OR OTHER | |
| OVERHEAD | |
| OBSTRUCTION (feet) | |
| All boilers with manholes on top of the | |
| boiler except where a greater clearance is | |
| required in this table. | |
| 3 | |
| All boilers without | |
| manholes on top of | |
| the boiler except high | |
| - | |
| pressure steam | |
| boilers and where a greater clearance is | |
| required in this table. | |
| 2 | |
| High | |
| - | |
| pressure steam boilers with steam | |
| generating capacity not exceeding 5,000 | |
| pounds per hour. | |
| 3 | |
| High | |
| - | |
| pressure steam | |
| boilers with steam | |
| generating capacity exceeding 5,000 | |
| pounds per hour. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface not exceeding 1,000 square | |
| feet. | |
| 3 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface in excess of 1,000 square | |
| feet. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers with input | |
| not exceeding 5,000,000 Btu/h. | |
| 3 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| High | |
| - | |
| pressure steam boilers with input in | |
| excess of 5,000,000 Btu/h. | |
| 7 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers with input exceeding | |
| 5,000,000 Btu/h. | |
| 3 | |
| Steam | |
| - | |
| heating boilers exceeding 5,000 | |
| pounds of steam per hour. | |
| 3 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers having heating surface | |
| exceeding 1,000 square feet. | |
| 3 | |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m | |
| 2 | |
| , 1 pound per hour = 0.4536 | |
| kg/h, 1 Btu/hr = 0.293 W. | |
| 1004.4 Mounting. | |
| Equipment | |
| and appliances | |
| shall be set or mounted on a level base capable of supporting and dis- | |
| tributing the weight contained thereon. Boilers, tanks and equipment shall be | |
| securely anchored to the structure. | |
| Equ | |
| ipment and appliances requiring vibration isolation shall be installed as designed by a registered design profes- | |
| sional | |
| in accordance with the manufacturer’s instructions. | |
| 1004.5 Floors. | |
| Boilers shall be mounted on floors of noncombustible | |
| construction, unless listed for mounting on | |
| combustible flooring. Vibration isolation shall be in accordance with Section 313. In buildings with residential occu- | |
| pancies, boilers shall be installed in accordance with the requirements of Section 313. | |
| 1004.6 | |
| Boiler rooms and enclosures. | |
| Boiler rooms and enclosures and access thereto shall comply with Chapters 5 | |
| and 10 of the | |
| New York City | |
| Building Code | |
| and Chapter 3 of this code. Boiler rooms shall be equipped with a floor | |
| drain or other approved means for | |
| disposing | |
| of liquid waste | |
| in accordance with the | |
| New York City Plumbing Code | |
| . | |
| 1004.7 Operating adjustments and instructions. | |
| Hot water and steam boil | |
| ers shall have all operating and safety | |
| controls set and operationally tested by the installing contractor. A | |
| complete | |
| control diagram and boiler operating | |
| instructions shall be furnished by the installer for each installation. | |
| A complete control diagram o | |
| f a permanent type | |
| shall be located in the boiler room and shall be readily accessible. | |
| 1004.8 Burner controls. | |
| Gas and oil modulating burners shall be provided with burner controls (oil and gas equiv- | |
| alent ratings) in accordance with ASME CSD | |
| - | |
| 1 and NFPA 85 | |
| . | |
| 1004.9 Conversion burners. | |
| Conversion burners shall be installed in accordance with ANSI Z21.8. | |
| SECTION MC 1005 | |
| BOILER CONNECTIONS | |
| 1005.1 Valves. | |
| Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple | |
| boil | |
| er or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in | |
| the | |
| supply | |
| and return piping. | |
| Exception: | |
| Shutoff valves are not required in a system | |
| having | |
| a single low | |
| - | |
| pressure steam boiler | |
| of 350,000 Btu | |
| /h | |
| (103 kW) output or less | |
| . | |
| 1005.2 Potable water supply. | |
| The water supply to all boilers, including but not limited to backflow prevention, shall | |
| be connected in accordance with the | |
| New | |
| York City | |
| Plumbing Code | |
| . | |
| SECTION MC 1006 | |
| SAFETY AND PRESSURE | |
| RELIEF VALVES | |
| AND CONTROLS | |
| 1006.1 Safety valves for steam boilers. | |
| Steam boilers shall be protected with a safety valve | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| ‡‡‡ Chapter 10 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 10 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| SECTION MC 1001 | |
| GENERAL | |
| 1001.1 Scope. | |
| This chapter | |
| shall establish the minimum safety requirements for and | |
| shall govern the installation, | |
| alteration and repair of boilers, wate | |
| r heaters and pressure vessels. | |
| Exceptions: | |
| 1. | |
| Pressure vessels used for unheated water supply. | |
| 2. | |
| Portable unfired pressure vessels and Interstate | |
| Commerce | |
| Commission containers. | |
| 3. | |
| Containers for bulk oxygen and medical gas. | |
| 4. | |
| Unfired pressure | |
| vessels having a volume of 5 cubic feet (0.14 m | |
| 3 | |
| ) or less operating at pressures not exceed- | |
| ing 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, | |
| S and U. | |
| 5. | |
| Pressure vessels used in refrigeration systems | |
| that are regulated by Chapter 11. | |
| 6. | |
| Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other | |
| similar | |
| humidity control systems. | |
| 7. | |
| Any boiler or pressure vessel subject to inspection by federal inspectors. | |
| 1001.2 The | |
| rmal safety (spill) switches. | |
| Thermal safety (spill) switches shall be installed in accordance with Section | |
| 801.23.3. | |
| 1001.3 Clearances. | |
| Minimum clearances at | |
| boilers, water heaters and pressure vessels shall be maintained in accord- | |
| ance with Chapter 3. | |
| SEC | |
| TION MC 1002 | |
| WATER HEATERS | |
| 1002.1 General. | |
| Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accord- | |
| ance with the manufacturer’s instructions, the | |
| New York City | |
| Plumbing Code | |
| and this code. All water heaters shal | |
| l be | |
| capable of being removed without first removing a permanent portion of the building structure. The potable water | |
| connections | |
| and relief valves for all water heaters shall conform to the requirements of the | |
| New York City | |
| Plumbing | |
| Code | |
| . Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall | |
| comply with UL 1453. Oil | |
| - | |
| fired water heaters shall comply with UL 732. Approval for oil | |
| - | |
| fired water heaters | |
| 350,000 | |
| Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. | |
| Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water | |
| heaters shall comply with UL 174 or UL 1995. | |
| 1002.2 Water heaters utilized for s | |
| pace heating. | |
| Water heaters utilized both to supply potable hot water and provide | |
| hot water for space | |
| - | |
| heating applications shall be listed and labeled for such applications by the manufacturer and shall | |
| be | |
| built in accordance with Section IV of the | |
| ASME | |
| Boiler and Pressure Vessel Code | |
| with an “H” code stamp. Water | |
| heaters shall be | |
| installed in accordance with the manufacturer’s instructions | |
| , the | |
| ASME Boiler and Pressure Vessel | |
| Code | |
| and the | |
| New York City | |
| Plumbing Code. | |
| Oil | |
| - | |
| fired heaters shall comply with U | |
| L 732 and shall have an “HW” | |
| stamp. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1002.2.1 Sizing. | |
| Water heaters utilized for both potable water heating and space | |
| - | |
| heating applications shall be sized | |
| to prevent the space | |
| - | |
| heating load from diminishing the required potable water | |
| - | |
| heating capacity. | |
| 1002.2. | |
| 2 Temperature limitation. | |
| Where a combination potable water | |
| - | |
| heating and space | |
| - | |
| heating system requires | |
| water for space heating, a temperature | |
| actuated mixing valve complying with ASSE 1017 shall be provided to | |
| temper the water supplied to the potable hot wa | |
| ter distribution system in accordance with Section 607 of the | |
| New | |
| York City Plumbing Code | |
| . | |
| 1002.2.3 Cross | |
| - | |
| connection. | |
| Water heaters utilized for both potable hot water and hot water for space | |
| - | |
| heating | |
| applications shall have separate heating sections and co | |
| nnections for distribution systems and shall not be cross | |
| - | |
| connected. The potability of the domestic water shall be maintained throughout the system in accordance with the | |
| New York City Plumbing Code. | |
| 1002.3 Supplemental water | |
| - | |
| heating devices. | |
| Potable | |
| water | |
| - | |
| heating devices that utilize refrigerant | |
| - | |
| to | |
| - | |
| water heat | |
| exchangers shall be approved and installed in accordance with the | |
| New York City | |
| Plumbing Code | |
| , the applicable | |
| provisions of the | |
| New York City Energy Conservation Code | |
| and the manufacturer’s | |
| instructions. | |
| SECTION MC 1003 | |
| PRESSURE VESSELS | |
| 1003.1 General. | |
| All pressure vessels shall be constructed and certified in accordance with the | |
| ASME Boiler and | |
| Pressure Vessel Code | |
| , and shall | |
| bear the label of an approved agency. Pressure vessels shall | |
| be in | |
| stalled in accordance | |
| with the manufacturer’s | |
| instructions and nationally recognized standards. Directly fired pressure vessels shall meet | |
| the requirements of Section 1004. | |
| 1003.2 Piping. | |
| All piping materials, fittings, joints, | |
| connections | |
| and devices asso | |
| ciated with systems utilized in | |
| con- | |
| junction | |
| with pressure vessels shall be designed for the specific application and shall | |
| comply with the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| and this code | |
| . | |
| 1003.3 Welding. | |
| Welding on pressure vessels shall be performed by | |
| welders | |
| certified in | |
| compliance with nationally | |
| recognized standards, including the | |
| National Board Inspection Code | |
| and | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| Section | |
| IX. Such welders shall also comply with 12 NYCRR 4 | |
| - | |
| 6.2, and 12 NYCRR 14 | |
| - | |
| 3.3 through 14 | |
| - | |
| 3.1 | |
| 8. | |
| SECTION | |
| MC | |
| 1004 | |
| BOILERS | |
| 1004.1 Standards. | |
| Boilers shall be designed, constructed and certified in accordance with the | |
| ASME Boiler and Pres- | |
| sure Vessel Code | |
| , Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with | |
| fuel | |
| input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD | |
| - | |
| 1. Controls and safety | |
| devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. | |
| Packaged oil | |
| - | |
| fired boile | |
| rs shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be | |
| listed and labeled in accordance with UL 834. | |
| Approval for oil | |
| - | |
| fired boilers 350,000 Btu/h input (102.6 kW) and | |
| above shall be obtained from the New York City Depa | |
| rtment of Environmental Protection. | |
| 1004.1.1 Field erected boilers requirements. | |
| Field erected boiler installations shall comply with the following | |
| : | |
| 1. | |
| The vessel erector shall hold the appropriate ASME stamp for vessel construction. | |
| 2. | |
| The licensed instal | |
| ler is responsible for the installation of all controls and burners which shall be designed | |
| and constructed in accordance with the requirements of ASME CSD | |
| - | |
| 1 and, as applicable, the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| , 12 NYCRR Parts 4 and 14, and NFPA 85 | |
| . | |
| 3. | |
| The New York City Department of Environmental Protection shall approve the installation of the boiler and | |
| burner for compatibility, controls and safety devices. | |
| 4. | |
| Boiler vessels shall comply with one of the following listings: | |
| 4.1. | |
| UL 726 or UL 795 a | |
| s applicable; or | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 4.2. | |
| UL 2106. | |
| Exception: | |
| Unlisted equipment shall obtain approval from the department. | |
| 5. | |
| Controls and safety devices shall be tested and inspected in accordance with ASME CSD | |
| - | |
| 1 and, as applicable, | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| 12 NYCRR Parts 4 and 14, and NFPA 85. Testing and inspection | |
| shall be performed by the burner manufacturer’s authorized representative in the presence of the licensed | |
| installer. | |
| 6. | |
| Inspection of the installed boiler assembly shall be performed by the dep | |
| artment. | |
| 1004.2 Installation. | |
| In addition to the requirements of this code, the installation of boilers shall conform to the | |
| man- | |
| ufacturer’s | |
| instructions. Operating instructions of a permanent type shall be | |
| located in | |
| the boiler | |
| room and readily | |
| accessible | |
| . | |
| Boilers shall have all controls set, adjusted and tested by the installer. The manufacturer’s rating data and | |
| the nameplate shall be attached to the boiler. | |
| 1004.3 Working clearance. | |
| Clearances shall be maintained around boilers, generators, heaters, tanks and related | |
| equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When | |
| boilers are installed or replaced, clearance shall | |
| be provided to allow access for maintenance and repair | |
| per the boiler’s | |
| listing and manufacturer’s instructions. | |
| Passageways | |
| for inspection | |
| around all sides of boilers shall have an unob- | |
| structed width of not less than 18 inches | |
| ( | |
| 457.2 | |
| mm) | |
| unless | |
| the boiler | |
| ’s listing or department approval or manufac- | |
| turer’s instructions state | |
| otherwise. | |
| 1004.3.1 Top clearance. | |
| Clearances from the tops of boilers to the ceiling or other overhead obstruction shall be | |
| in accordance with Table 1004.3.1. | |
| TABLE 1004.3.1 | |
| BOILER TOP | |
| CLEARANCES | |
| BOILER TYPE | |
| MINIMUM | |
| CLEARANCES FROM | |
| TOP OF BOILER TO | |
| CEILING OR OTHER | |
| OVERHEAD | |
| OBSTRUCTION (feet) | |
| All boilers with manholes on top of the | |
| boiler except where a greater clearance is | |
| required in this table. | |
| 3 | |
| All boilers without | |
| manholes on top of | |
| the boiler except high | |
| - | |
| pressure steam | |
| boilers and where a greater clearance is | |
| required in this table. | |
| 2 | |
| High | |
| - | |
| pressure steam boilers with steam | |
| generating capacity not exceeding 5,000 | |
| pounds per hour. | |
| 3 | |
| High | |
| - | |
| pressure steam | |
| boilers with steam | |
| generating capacity exceeding 5,000 | |
| pounds per hour. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface not exceeding 1,000 square | |
| feet. | |
| 3 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface in excess of 1,000 square | |
| feet. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers with input | |
| not exceeding 5,000,000 Btu/h. | |
| 3 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| High | |
| - | |
| pressure steam boilers with input in | |
| excess of 5,000,000 Btu/h. | |
| 7 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers with input exceeding | |
| 5,000,000 Btu/h. | |
| 3 | |
| Steam | |
| - | |
| heating boilers exceeding 5,000 | |
| pounds of steam per hour. | |
| 3 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers having heating surface | |
| exceeding 1,000 square feet. | |
| 3 | |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m | |
| 2 | |
| , 1 pound per hour = 0.4536 | |
| kg/h, 1 Btu/hr = 0.293 W. | |
| 1004.4 Mounting. | |
| Equipment | |
| and appliances | |
| shall be set or mounted on a level base capable of supporting and dis- | |
| tributing the weight contained thereon. Boilers, tanks and equipment shall be | |
| securely anchored to the structure. | |
| Equ | |
| ipment and appliances requiring vibration isolation shall be installed as designed by a registered design profes- | |
| sional | |
| in accordance with the manufacturer’s instructions. | |
| 1004.5 Floors. | |
| Boilers shall be mounted on floors of noncombustible | |
| construction, unless listed for mounting on | |
| combustible flooring. Vibration isolation shall be in accordance with Section 313. In buildings with residential occu- | |
| pancies, boilers shall be installed in accordance with the requirements of Section 313. | |
| 1004.6 | |
| Boiler rooms and enclosures. | |
| Boiler rooms and enclosures and access thereto shall comply with Chapters 5 | |
| and 10 of the | |
| New York City | |
| Building Code | |
| and Chapter 3 of this code. Boiler rooms shall be equipped with a floor | |
| drain or other approved means for | |
| disposing | |
| of liquid waste | |
| in accordance with the | |
| New York City Plumbing Code | |
| . | |
| 1004.7 Operating adjustments and instructions. | |
| Hot water and steam boil | |
| ers shall have all operating and safety | |
| controls set and operationally tested by the installing contractor. A | |
| complete | |
| control diagram and boiler operating | |
| instructions shall be furnished by the installer for each installation. | |
| A complete control diagram o | |
| f a permanent type | |
| shall be located in the boiler room and shall be readily accessible. | |
| 1004.8 Burner controls. | |
| Gas and oil modulating burners shall be provided with burner controls (oil and gas equiv- | |
| alent ratings) in accordance with ASME CSD | |
| - | |
| 1 and NFPA 85 | |
| . | |
| 1004.9 Conversion burners. | |
| Conversion burners shall be installed in accordance with ANSI Z21.8. | |
| SECTION MC 1005 | |
| BOILER CONNECTIONS | |
| 1005.1 Valves. | |
| Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple | |
| boil | |
| er or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in | |
| the | |
| supply | |
| and return piping. | |
| Exception: | |
| Shutoff valves are not required in a system | |
| having | |
| a single low | |
| - | |
| pressure steam boiler | |
| of 350,000 Btu | |
| /h | |
| (103 kW) output or less | |
| . | |
| 1005.2 Potable water supply. | |
| The water supply to all boilers, including but not limited to backflow prevention, shall | |
| be connected in accordance with the | |
| New | |
| York City | |
| Plumbing Code | |
| . | |
| SECTION MC 1006 | |
| SAFETY AND PRESSURE | |
| RELIEF VALVES | |
| AND CONTROLS | |
| 1006.1 Safety valves for steam boilers. | |
| Steam boilers shall be protected with a safety valve | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1006.2 Safety relief valves for hot water boilers. | |
| Hot water | |
| boilers shall be protected with a safety relief valve | |
| in | |
| accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.3 Pressure relief for pressure vessels. | |
| Pressure vessels | |
| shall be protected with a pressure relief valve or | |
| pres- | |
| sure | |
| - | |
| limit | |
| ing device as required by the manufacturer’s instructions for the pressure vessel and | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| 1006.4 Standards of safety and safety relief valves. | |
| Safety and safety relief valves shall be l | |
| isted and labeled, and | |
| shall have a minimum rated capacity for the equipment or appliances served. Safety and safety relief valves shall be | |
| set at not greater than the nameplate pressure rating of the boiler or pressure vessel and shall be in accordance wi | |
| th | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| or the ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.5 Installation. | |
| Safety or relief valves shall be installed directly into the safety or relief valve opening on the | |
| boiler or pressure vessel. Valves shall not be located on either side of a safety or relief valve connection. The relief | |
| valve drain shall | |
| discharge by gravi | |
| ty to a nonhazardous point of discharge without obstruction.‡ | |
| 1006.6 Safety and relief valve discharge. | |
| Safety and relief valve discharge pipes shall be of rigid pipe that is approved | |
| for the temperature of the system. The discharge pipe shall | |
| , at a minimu | |
| m, | |
| be the same diameter as the safety or relief | |
| valve outlet. Safety and relief valve discharge pipes shall be properly supported to prevent stress on the valve and | |
| vessel. Safety and relief valves shall not discharge so as to be a hazard, a potential caus | |
| e of damage or otherwise a | |
| nuisance. | |
| Discharge of hazardous materials must be properly contained in a method approved by the department. | |
| High | |
| - | |
| pressure | |
| - | |
| steam safety valves shall be vented to the outside of the structure. Where a low | |
| - | |
| pressure safety valve | |
| or | |
| a relief valve discharges to the drainage system, the installation shall conform to the | |
| New York City | |
| Plumbing Code | |
| . | |
| 1006.7 Boiler safety devices. | |
| Boilers shall be equipped with controls and limit devices as required by the manufac- | |
| turer’s instructions and | |
| the conditions of the listing. | |
| 1006.8 Electrical requirements. | |
| The power supply to the electrical control system shall be from a two | |
| - | |
| wire branch | |
| circuit | |
| that has a grounded conductor, or from an isolation | |
| trans | |
| - | |
| former | |
| with a two | |
| - | |
| wire secondary. Where an i | |
| solation | |
| transformer is provided, one conductor of the secondary | |
| winding | |
| shall be grounded. Control voltage shall not exceed | |
| 150 volts nominal, line to line. Control and limit devices shall | |
| interrupt | |
| the ungrounded side of the circuit. A means | |
| of manually | |
| disconnecting the control circuit shall be provided and controls shall be arranged so that when deener- | |
| gized, the burner shall be inoperative. Such disconnecting means shall be capable of being locked in the off position | |
| and shall be provided with ready acc | |
| ess. | |
| 1006.8.1 Remote control (shutdown). | |
| A remote control shall be provided to stop the flow of oil and/or gas and | |
| combustion air to any burner or fuel | |
| - | |
| burning internal combustion equipment. Such a control shall be provided | |
| along every means of egress from | |
| the room in which the burner or equipment is located. Each remote control shall | |
| be located outside of, but as close as practicable to the burner or equipment room itself and shall be labeled: | |
| “REMOTE CONTROL FOR BURNER.” | |
| Exception: | |
| Where an outside locati | |
| on is impracticable, the remote control shutdown may be provided immedi- | |
| ately inside the room in which the burner or equipment is located. | |
| Such location must be accessible at all times. | |
| 1006.9 Carbon monoxide detectors. | |
| Carbon monoxide detectors shall be p | |
| rovided in all fuel | |
| - | |
| fired appliance rooms | |
| to detect the level of carbon monoxide in the room and signal an alarm. Such detectors shall be listed and installed | |
| in accordance with Chapter 9 of the | |
| New York City Building Code | |
| . | |
| SECTION | |
| MC | |
| 1007 | |
| BOILER | |
| LOW | |
| - | |
| WATER CUTOFF | |
| 1007.1 General. | |
| Steam and hot water boilers shall be protected with | |
| dual | |
| low | |
| - | |
| water cutoff control, with each control | |
| independently piped to the pressure vessel in accordance with ASME CSD | |
| - | |
| 1. For hydronic boilers, the low | |
| - | |
| water cut | |
| out may | |
| be located in the supply piping above the boiler before any intervening valve. A flow | |
| - | |
| sensing control installed | |
| in accordance with ASME CSD | |
| - | |
| 1 shall be considered a low | |
| - | |
| water cutoff for the purposes of this section. | |
| Exception: | |
| Hot water | |
| boilers | |
| located wit | |
| hin a dwelling unit supplying only | |
| that | |
| unit and having a total heat input | |
| of | |
| less than 400,000 Btu/h (117.2 kW) may be | |
| protected | |
| by only one low | |
| - | |
| water cutoff | |
| control. | |
| ‡‡‡ Chapter 10 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 10 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| SECTION MC 1001 | |
| GENERAL | |
| 1001.1 Scope. | |
| This chapter | |
| shall establish the minimum safety requirements for and | |
| shall govern the installation, | |
| alteration and repair of boilers, wate | |
| r heaters and pressure vessels. | |
| Exceptions: | |
| 1. | |
| Pressure vessels used for unheated water supply. | |
| 2. | |
| Portable unfired pressure vessels and Interstate | |
| Commerce | |
| Commission containers. | |
| 3. | |
| Containers for bulk oxygen and medical gas. | |
| 4. | |
| Unfired pressure | |
| vessels having a volume of 5 cubic feet (0.14 m | |
| 3 | |
| ) or less operating at pressures not exceed- | |
| ing 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, | |
| S and U. | |
| 5. | |
| Pressure vessels used in refrigeration systems | |
| that are regulated by Chapter 11. | |
| 6. | |
| Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other | |
| similar | |
| humidity control systems. | |
| 7. | |
| Any boiler or pressure vessel subject to inspection by federal inspectors. | |
| 1001.2 The | |
| rmal safety (spill) switches. | |
| Thermal safety (spill) switches shall be installed in accordance with Section | |
| 801.23.3. | |
| 1001.3 Clearances. | |
| Minimum clearances at | |
| boilers, water heaters and pressure vessels shall be maintained in accord- | |
| ance with Chapter 3. | |
| SEC | |
| TION MC 1002 | |
| WATER HEATERS | |
| 1002.1 General. | |
| Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accord- | |
| ance with the manufacturer’s instructions, the | |
| New York City | |
| Plumbing Code | |
| and this code. All water heaters shal | |
| l be | |
| capable of being removed without first removing a permanent portion of the building structure. The potable water | |
| connections | |
| and relief valves for all water heaters shall conform to the requirements of the | |
| New York City | |
| Plumbing | |
| Code | |
| . Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall | |
| comply with UL 1453. Oil | |
| - | |
| fired water heaters shall comply with UL 732. Approval for oil | |
| - | |
| fired water heaters | |
| 350,000 | |
| Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. | |
| Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water | |
| heaters shall comply with UL 174 or UL 1995. | |
| 1002.2 Water heaters utilized for s | |
| pace heating. | |
| Water heaters utilized both to supply potable hot water and provide | |
| hot water for space | |
| - | |
| heating applications shall be listed and labeled for such applications by the manufacturer and shall | |
| be | |
| built in accordance with Section IV of the | |
| ASME | |
| Boiler and Pressure Vessel Code | |
| with an “H” code stamp. Water | |
| heaters shall be | |
| installed in accordance with the manufacturer’s instructions | |
| , the | |
| ASME Boiler and Pressure Vessel | |
| Code | |
| and the | |
| New York City | |
| Plumbing Code. | |
| Oil | |
| - | |
| fired heaters shall comply with U | |
| L 732 and shall have an “HW” | |
| stamp. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1002.2.1 Sizing. | |
| Water heaters utilized for both potable water heating and space | |
| - | |
| heating applications shall be sized | |
| to prevent the space | |
| - | |
| heating load from diminishing the required potable water | |
| - | |
| heating capacity. | |
| 1002.2. | |
| 2 Temperature limitation. | |
| Where a combination potable water | |
| - | |
| heating and space | |
| - | |
| heating system requires | |
| water for space heating, a temperature | |
| actuated mixing valve complying with ASSE 1017 shall be provided to | |
| temper the water supplied to the potable hot wa | |
| ter distribution system in accordance with Section 607 of the | |
| New | |
| York City Plumbing Code | |
| . | |
| 1002.2.3 Cross | |
| - | |
| connection. | |
| Water heaters utilized for both potable hot water and hot water for space | |
| - | |
| heating | |
| applications shall have separate heating sections and co | |
| nnections for distribution systems and shall not be cross | |
| - | |
| connected. The potability of the domestic water shall be maintained throughout the system in accordance with the | |
| New York City Plumbing Code. | |
| 1002.3 Supplemental water | |
| - | |
| heating devices. | |
| Potable | |
| water | |
| - | |
| heating devices that utilize refrigerant | |
| - | |
| to | |
| - | |
| water heat | |
| exchangers shall be approved and installed in accordance with the | |
| New York City | |
| Plumbing Code | |
| , the applicable | |
| provisions of the | |
| New York City Energy Conservation Code | |
| and the manufacturer’s | |
| instructions. | |
| SECTION MC 1003 | |
| PRESSURE VESSELS | |
| 1003.1 General. | |
| All pressure vessels shall be constructed and certified in accordance with the | |
| ASME Boiler and | |
| Pressure Vessel Code | |
| , and shall | |
| bear the label of an approved agency. Pressure vessels shall | |
| be in | |
| stalled in accordance | |
| with the manufacturer’s | |
| instructions and nationally recognized standards. Directly fired pressure vessels shall meet | |
| the requirements of Section 1004. | |
| 1003.2 Piping. | |
| All piping materials, fittings, joints, | |
| connections | |
| and devices asso | |
| ciated with systems utilized in | |
| con- | |
| junction | |
| with pressure vessels shall be designed for the specific application and shall | |
| comply with the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| and this code | |
| . | |
| 1003.3 Welding. | |
| Welding on pressure vessels shall be performed by | |
| welders | |
| certified in | |
| compliance with nationally | |
| recognized standards, including the | |
| National Board Inspection Code | |
| and | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| Section | |
| IX. Such welders shall also comply with 12 NYCRR 4 | |
| - | |
| 6.2, and 12 NYCRR 14 | |
| - | |
| 3.3 through 14 | |
| - | |
| 3.1 | |
| 8. | |
| SECTION | |
| MC | |
| 1004 | |
| BOILERS | |
| 1004.1 Standards. | |
| Boilers shall be designed, constructed and certified in accordance with the | |
| ASME Boiler and Pres- | |
| sure Vessel Code | |
| , Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with | |
| fuel | |
| input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD | |
| - | |
| 1. Controls and safety | |
| devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. | |
| Packaged oil | |
| - | |
| fired boile | |
| rs shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be | |
| listed and labeled in accordance with UL 834. | |
| Approval for oil | |
| - | |
| fired boilers 350,000 Btu/h input (102.6 kW) and | |
| above shall be obtained from the New York City Depa | |
| rtment of Environmental Protection. | |
| 1004.1.1 Field erected boilers requirements. | |
| Field erected boiler installations shall comply with the following | |
| : | |
| 1. | |
| The vessel erector shall hold the appropriate ASME stamp for vessel construction. | |
| 2. | |
| The licensed instal | |
| ler is responsible for the installation of all controls and burners which shall be designed | |
| and constructed in accordance with the requirements of ASME CSD | |
| - | |
| 1 and, as applicable, the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| , 12 NYCRR Parts 4 and 14, and NFPA 85 | |
| . | |
| 3. | |
| The New York City Department of Environmental Protection shall approve the installation of the boiler and | |
| burner for compatibility, controls and safety devices. | |
| 4. | |
| Boiler vessels shall comply with one of the following listings: | |
| 4.1. | |
| UL 726 or UL 795 a | |
| s applicable; or | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 4.2. | |
| UL 2106. | |
| Exception: | |
| Unlisted equipment shall obtain approval from the department. | |
| 5. | |
| Controls and safety devices shall be tested and inspected in accordance with ASME CSD | |
| - | |
| 1 and, as applicable, | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| 12 NYCRR Parts 4 and 14, and NFPA 85. Testing and inspection | |
| shall be performed by the burner manufacturer’s authorized representative in the presence of the licensed | |
| installer. | |
| 6. | |
| Inspection of the installed boiler assembly shall be performed by the dep | |
| artment. | |
| 1004.2 Installation. | |
| In addition to the requirements of this code, the installation of boilers shall conform to the | |
| man- | |
| ufacturer’s | |
| instructions. Operating instructions of a permanent type shall be | |
| located in | |
| the boiler | |
| room and readily | |
| accessible | |
| . | |
| Boilers shall have all controls set, adjusted and tested by the installer. The manufacturer’s rating data and | |
| the nameplate shall be attached to the boiler. | |
| 1004.3 Working clearance. | |
| Clearances shall be maintained around boilers, generators, heaters, tanks and related | |
| equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When | |
| boilers are installed or replaced, clearance shall | |
| be provided to allow access for maintenance and repair | |
| per the boiler’s | |
| listing and manufacturer’s instructions. | |
| Passageways | |
| for inspection | |
| around all sides of boilers shall have an unob- | |
| structed width of not less than 18 inches | |
| ( | |
| 457.2 | |
| mm) | |
| unless | |
| the boiler | |
| ’s listing or department approval or manufac- | |
| turer’s instructions state | |
| otherwise. | |
| 1004.3.1 Top clearance. | |
| Clearances from the tops of boilers to the ceiling or other overhead obstruction shall be | |
| in accordance with Table 1004.3.1. | |
| TABLE 1004.3.1 | |
| BOILER TOP | |
| CLEARANCES | |
| BOILER TYPE | |
| MINIMUM | |
| CLEARANCES FROM | |
| TOP OF BOILER TO | |
| CEILING OR OTHER | |
| OVERHEAD | |
| OBSTRUCTION (feet) | |
| All boilers with manholes on top of the | |
| boiler except where a greater clearance is | |
| required in this table. | |
| 3 | |
| All boilers without | |
| manholes on top of | |
| the boiler except high | |
| - | |
| pressure steam | |
| boilers and where a greater clearance is | |
| required in this table. | |
| 2 | |
| High | |
| - | |
| pressure steam boilers with steam | |
| generating capacity not exceeding 5,000 | |
| pounds per hour. | |
| 3 | |
| High | |
| - | |
| pressure steam | |
| boilers with steam | |
| generating capacity exceeding 5,000 | |
| pounds per hour. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface not exceeding 1,000 square | |
| feet. | |
| 3 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface in excess of 1,000 square | |
| feet. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers with input | |
| not exceeding 5,000,000 Btu/h. | |
| 3 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| High | |
| - | |
| pressure steam boilers with input in | |
| excess of 5,000,000 Btu/h. | |
| 7 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers with input exceeding | |
| 5,000,000 Btu/h. | |
| 3 | |
| Steam | |
| - | |
| heating boilers exceeding 5,000 | |
| pounds of steam per hour. | |
| 3 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers having heating surface | |
| exceeding 1,000 square feet. | |
| 3 | |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m | |
| 2 | |
| , 1 pound per hour = 0.4536 | |
| kg/h, 1 Btu/hr = 0.293 W. | |
| 1004.4 Mounting. | |
| Equipment | |
| and appliances | |
| shall be set or mounted on a level base capable of supporting and dis- | |
| tributing the weight contained thereon. Boilers, tanks and equipment shall be | |
| securely anchored to the structure. | |
| Equ | |
| ipment and appliances requiring vibration isolation shall be installed as designed by a registered design profes- | |
| sional | |
| in accordance with the manufacturer’s instructions. | |
| 1004.5 Floors. | |
| Boilers shall be mounted on floors of noncombustible | |
| construction, unless listed for mounting on | |
| combustible flooring. Vibration isolation shall be in accordance with Section 313. In buildings with residential occu- | |
| pancies, boilers shall be installed in accordance with the requirements of Section 313. | |
| 1004.6 | |
| Boiler rooms and enclosures. | |
| Boiler rooms and enclosures and access thereto shall comply with Chapters 5 | |
| and 10 of the | |
| New York City | |
| Building Code | |
| and Chapter 3 of this code. Boiler rooms shall be equipped with a floor | |
| drain or other approved means for | |
| disposing | |
| of liquid waste | |
| in accordance with the | |
| New York City Plumbing Code | |
| . | |
| 1004.7 Operating adjustments and instructions. | |
| Hot water and steam boil | |
| ers shall have all operating and safety | |
| controls set and operationally tested by the installing contractor. A | |
| complete | |
| control diagram and boiler operating | |
| instructions shall be furnished by the installer for each installation. | |
| A complete control diagram o | |
| f a permanent type | |
| shall be located in the boiler room and shall be readily accessible. | |
| 1004.8 Burner controls. | |
| Gas and oil modulating burners shall be provided with burner controls (oil and gas equiv- | |
| alent ratings) in accordance with ASME CSD | |
| - | |
| 1 and NFPA 85 | |
| . | |
| 1004.9 Conversion burners. | |
| Conversion burners shall be installed in accordance with ANSI Z21.8. | |
| SECTION MC 1005 | |
| BOILER CONNECTIONS | |
| 1005.1 Valves. | |
| Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple | |
| boil | |
| er or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in | |
| the | |
| supply | |
| and return piping. | |
| Exception: | |
| Shutoff valves are not required in a system | |
| having | |
| a single low | |
| - | |
| pressure steam boiler | |
| of 350,000 Btu | |
| /h | |
| (103 kW) output or less | |
| . | |
| 1005.2 Potable water supply. | |
| The water supply to all boilers, including but not limited to backflow prevention, shall | |
| be connected in accordance with the | |
| New | |
| York City | |
| Plumbing Code | |
| . | |
| SECTION MC 1006 | |
| SAFETY AND PRESSURE | |
| RELIEF VALVES | |
| AND CONTROLS | |
| 1006.1 Safety valves for steam boilers. | |
| Steam boilers shall be protected with a safety valve | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1006.2 Safety relief valves for hot water boilers. | |
| Hot water | |
| boilers shall be protected with a safety relief valve | |
| in | |
| accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.3 Pressure relief for pressure vessels. | |
| Pressure vessels | |
| shall be protected with a pressure relief valve or | |
| pres- | |
| sure | |
| - | |
| limit | |
| ing device as required by the manufacturer’s instructions for the pressure vessel and | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| 1006.4 Standards of safety and safety relief valves. | |
| Safety and safety relief valves shall be l | |
| isted and labeled, and | |
| shall have a minimum rated capacity for the equipment or appliances served. Safety and safety relief valves shall be | |
| set at not greater than the nameplate pressure rating of the boiler or pressure vessel and shall be in accordance wi | |
| th | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| or the ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.5 Installation. | |
| Safety or relief valves shall be installed directly into the safety or relief valve opening on the | |
| boiler or pressure vessel. Valves shall not be located on either side of a safety or relief valve connection. The relief | |
| valve drain shall | |
| discharge by gravi | |
| ty to a nonhazardous point of discharge without obstruction.‡ | |
| 1006.6 Safety and relief valve discharge. | |
| Safety and relief valve discharge pipes shall be of rigid pipe that is approved | |
| for the temperature of the system. The discharge pipe shall | |
| , at a minimu | |
| m, | |
| be the same diameter as the safety or relief | |
| valve outlet. Safety and relief valve discharge pipes shall be properly supported to prevent stress on the valve and | |
| vessel. Safety and relief valves shall not discharge so as to be a hazard, a potential caus | |
| e of damage or otherwise a | |
| nuisance. | |
| Discharge of hazardous materials must be properly contained in a method approved by the department. | |
| High | |
| - | |
| pressure | |
| - | |
| steam safety valves shall be vented to the outside of the structure. Where a low | |
| - | |
| pressure safety valve | |
| or | |
| a relief valve discharges to the drainage system, the installation shall conform to the | |
| New York City | |
| Plumbing Code | |
| . | |
| 1006.7 Boiler safety devices. | |
| Boilers shall be equipped with controls and limit devices as required by the manufac- | |
| turer’s instructions and | |
| the conditions of the listing. | |
| 1006.8 Electrical requirements. | |
| The power supply to the electrical control system shall be from a two | |
| - | |
| wire branch | |
| circuit | |
| that has a grounded conductor, or from an isolation | |
| trans | |
| - | |
| former | |
| with a two | |
| - | |
| wire secondary. Where an i | |
| solation | |
| transformer is provided, one conductor of the secondary | |
| winding | |
| shall be grounded. Control voltage shall not exceed | |
| 150 volts nominal, line to line. Control and limit devices shall | |
| interrupt | |
| the ungrounded side of the circuit. A means | |
| of manually | |
| disconnecting the control circuit shall be provided and controls shall be arranged so that when deener- | |
| gized, the burner shall be inoperative. Such disconnecting means shall be capable of being locked in the off position | |
| and shall be provided with ready acc | |
| ess. | |
| 1006.8.1 Remote control (shutdown). | |
| A remote control shall be provided to stop the flow of oil and/or gas and | |
| combustion air to any burner or fuel | |
| - | |
| burning internal combustion equipment. Such a control shall be provided | |
| along every means of egress from | |
| the room in which the burner or equipment is located. Each remote control shall | |
| be located outside of, but as close as practicable to the burner or equipment room itself and shall be labeled: | |
| “REMOTE CONTROL FOR BURNER.” | |
| Exception: | |
| Where an outside locati | |
| on is impracticable, the remote control shutdown may be provided immedi- | |
| ately inside the room in which the burner or equipment is located. | |
| Such location must be accessible at all times. | |
| 1006.9 Carbon monoxide detectors. | |
| Carbon monoxide detectors shall be p | |
| rovided in all fuel | |
| - | |
| fired appliance rooms | |
| to detect the level of carbon monoxide in the room and signal an alarm. Such detectors shall be listed and installed | |
| in accordance with Chapter 9 of the | |
| New York City Building Code | |
| . | |
| SECTION | |
| MC | |
| 1007 | |
| BOILER | |
| LOW | |
| - | |
| WATER CUTOFF | |
| 1007.1 General. | |
| Steam and hot water boilers shall be protected with | |
| dual | |
| low | |
| - | |
| water cutoff control, with each control | |
| independently piped to the pressure vessel in accordance with ASME CSD | |
| - | |
| 1. For hydronic boilers, the low | |
| - | |
| water cut | |
| out may | |
| be located in the supply piping above the boiler before any intervening valve. A flow | |
| - | |
| sensing control installed | |
| in accordance with ASME CSD | |
| - | |
| 1 shall be considered a low | |
| - | |
| water cutoff for the purposes of this section. | |
| Exception: | |
| Hot water | |
| boilers | |
| located wit | |
| hin a dwelling unit supplying only | |
| that | |
| unit and having a total heat input | |
| of | |
| less than 400,000 Btu/h (117.2 kW) may be | |
| protected | |
| by only one low | |
| - | |
| water cutoff | |
| control. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1007.2 Operation. | |
| Low | |
| - | |
| water cutoff controls and flow | |
| - | |
| sensing controls required by Section 1007.1 shall automati- | |
| cally stop the combustion operation of the appliance when the water level drops below the lowest safe water level as | |
| established by the manufacturer | |
| and in accordance with ASME CSD | |
| - | |
| 1, | |
| or when water circulation stops, respectively. | |
| 10 | |
| 07.3 Low | |
| - | |
| water cut out maintenance and testing. | |
| Low | |
| - | |
| water cut outs shall be maintained in accordance with | |
| ASME CSD | |
| - | |
| 1 and the manufacturer’s specifications. An operator shall test low | |
| - | |
| water cut outs as follows: (1) high | |
| pressure steam boilers every shift, ( | |
| 2) low pressure steam boilers daily and (3) hot water boilers monthly. Slow drain | |
| tests shall be conducted for steam boilers every six months. | |
| Every year, low | |
| - | |
| water cut outs and associated piping for | |
| steam boilers shall be opened, cleaned and inspected. | |
| Re | |
| cords of all testing, cleaning, and inspection required by this | |
| section shall be maintained, and made available to the department upon request. | |
| SECTION MC 1008 | |
| BOILER BLOWOFF/BLOWDOWN VALVES | |
| 1008.1 General. | |
| Every boiler | |
| shall be equipped with blowoff | |
| /blow | |
| down | |
| valve(s). The valve(s) shall be installed in | |
| the | |
| openings | |
| provided on the boiler. The minimum | |
| quantity and | |
| size of the valve(s) and associated piping shall be the | |
| quantity and | |
| size specified by the boiler manufacturer or the | |
| quantity and size of the boiler blowoff | |
| /blowdown | |
| valve | |
| opening. Where the maximum allowable working pressure of the boiler exceeds 15 psig (103.4 kPa), two bottom | |
| blowoff valves shall be provided consisting | |
| of either two slow | |
| - | |
| opening valves in series or one quick | |
| - | |
| opening valve | |
| and one slow | |
| - | |
| opening valve in series, with the quick | |
| - | |
| opening valve installed closest to the boiler. | |
| 1008.2 Discharge. | |
| Blowoff | |
| /blowdown | |
| valves shall discharge to a safe place of disposal. Where discharging to the | |
| drainage system, the installation shall conform to the | |
| New York City | |
| Plumbing Code. | |
| 1008.3 Maintenance. | |
| Blowdown lines shall be inspected annually to verify they are free of deposits and in good | |
| working condition. | |
| SECTION MC 1009 | |
| HOT WATER BOILER EXPANSION TANK | |
| 1009.1 Where required. | |
| An expansion tank shall be installed in every hot water system. For multiple boiler installa- | |
| tions, not less than one expansion tank is required. Expansion tanks shall be of the closed or open type. Tanks shall | |
| be rated for the pressure of the hot water system. | |
| Lockable shutoff valves shall be installed at connections to all | |
| expansion tanks. Valves shall remain locked in the open position. | |
| 1009.2 Closed | |
| - | |
| type expansion tanks. | |
| Closed | |
| - | |
| type expansion tanks shall be installed in accordance with the manu- | |
| facturer’s instructions. Expansion tanks for systems designed to have an operating pressure in excess of 30 psi (205.8 | |
| kPa) shall be constructed and certified in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| . The size of the | |
| tank shall be based on the capacity of the hot | |
| - | |
| water | |
| - | |
| heating system. The minimum size of the tank shall be determined | |
| in accordance with the following equation where all necessary | |
| information is known: | |
| V | |
| t | |
| = | |
| ( | |
| 0 | |
| . | |
| 00041T | |
| −0 | |
| . | |
| 0466 | |
| ) | |
| V | |
| s | |
| � | |
| P | |
| a | |
| P | |
| f | |
| � | |
| −� | |
| P | |
| a | |
| P | |
| o | |
| � | |
| (Equation 10 | |
| - | |
| 1) | |
| For SI: | |
| V | |
| t | |
| = | |
| ( | |
| 0. | |
| 000738T | |
| − | |
| 0. | |
| 03348 | |
| ) | |
| V | |
| s | |
| � | |
| P | |
| a | |
| P | |
| f | |
| �−� | |
| P | |
| a | |
| P | |
| o | |
| � | |
| where: | |
| V | |
| t | |
| = | |
| Minimum volume of tanks (gallons) (L). | |
| V | |
| s | |
| = | |
| Volume of system, not including expansion tanks | |
| (gallons) (L). | |
| T | |
| = | |
| Average operating temperature ( | |
| ° | |
| F) ( | |
| ° | |
| C). | |
| P | |
| a | |
| = | |
| Atmospheric pressure (psi) (kPa). | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| P | |
| f | |
| = | |
| Fill pressure (psi) (kPa). | |
| P | |
| o | |
| = | |
| Maximum operating pressure (psi) (kPa). | |
| Where all necessary information is not known, the minimum size of the tank shall be | |
| determined from Table 1009.2. | |
| TABLE 1009.2 | |
| CLOSED | |
| - | |
| TYPE EXPANSION TANK SIZING | |
| SYSTEM VOLUME | |
| IN GALLONS | |
| TANK CAPACITIES IN GALLONS | |
| Pressurized | |
| Diaphragm Type | |
| Nonpressurized | |
| Type | |
| 100 | |
| 9 | |
| 15 | |
| 200 | |
| 17 | |
| 30 | |
| 300 | |
| 25 | |
| 45 | |
| 400 | |
| 33 | |
| 60 | |
| 500 | |
| 42 | |
| 75 | |
| 1,000 | |
| 83 | |
| 150 | |
| 2,000 | |
| 165 | |
| 300 | |
| For SI: 1 gallon = 3.795 L. | |
| 1009.3 Open | |
| - | |
| type expansion tanks. | |
| Open | |
| - | |
| type expansion tanks shall be located not less than 4 feet (1219.2 mm) | |
| above the highest heating element. The tank shall be adequately sized for the hot water system. An overflow with a | |
| minimum | |
| diameter | |
| of 1 inch (25.4 mm) shall be installed at the to | |
| p of the tank. The overflow shall discharge to the | |
| drainage system in | |
| accordance | |
| with the | |
| New York City | |
| Plumbing Code. | |
| SECTION MC 1010 | |
| GAUGES | |
| 1010.1 Hot water boiler gauges. | |
| Every hot water boiler shall have a pressure gauge and a temperature gauge, or a | |
| c | |
| ombination pressure and temperature gauge. The gauges shall indicate the temperature and pressure within the normal | |
| range of the system’s operation. | |
| 1010.2 Steam boiler gauges. | |
| Every steam boiler shall have a water | |
| - | |
| gauge glass and a pressure gauge with a s | |
| iphon. | |
| The pressure gauge shall indicate the pressure within the normal range of the system’s operation. | |
| 1010.2.1 Water | |
| - | |
| gauge glass. | |
| The gauge glass shall be installed in accordance with the | |
| ASME Boiler and Pressure | |
| Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| SECTION MC 1011 | |
| TESTS | |
| 1011.1 Tests. | |
| Upon completion of the assembly and | |
| installation | |
| of boilers and pressure vessels, acceptance tests shall | |
| be conducted in accordance with the requirements of the | |
| ASME Boiler and Pressure Vessel Code | |
| . Boilers shall not | |
| be placed in operation upon completion of construction until they have been inspected | |
| a | |
| nd | |
| tested and a certificate of | |
| compliance has been issued by the commissioner. All final inspections and | |
| tests | |
| for boilers shall be witnessed by a | |
| qualified boiler inspector in the employ of the department or a duly authorized insurance company as provided | |
| in | |
| Section 204 of the Labor Law of the State of New York. Equipment having an input of not more than 350,000 Btu/h | |
| (103 kW) shall be exempt from this requirement. Where field assembly of pressure vessels or boilers is required, a | |
| copy of | |
| the completed H | |
| - | |
| 2 | |
| , P | |
| - | |
| 2 or U | |
| - | |
| 1 Manufacturer’s Data Report and the completed Appendix C of ASME CSD | |
| - | |
| 1 | |
| required by the | |
| ASME Boiler and Pressure Vessel Code | |
| shall be submitted to the | |
| department | |
| . | |
| 1011.1.1 Fitness for service. | |
| When a boiler or pressure vessel has exceeded its us | |
| eful life or has been subjected to | |
| an event that may have impacted the integrity of the pressure vessel, the department may require that a fitness for | |
| service study be completed. The study shall be completed in accordance with the | |
| National Board Inspection | |
| Code | |
| Part 2, Section 4, and documented in accordance with the National Board 403 form. | |
| ‡‡‡ Chapter 10 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 10 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| SECTION MC 1001 | |
| GENERAL | |
| 1001.1 Scope. | |
| This chapter | |
| shall establish the minimum safety requirements for and | |
| shall govern the installation, | |
| alteration and repair of boilers, wate | |
| r heaters and pressure vessels. | |
| Exceptions: | |
| 1. | |
| Pressure vessels used for unheated water supply. | |
| 2. | |
| Portable unfired pressure vessels and Interstate | |
| Commerce | |
| Commission containers. | |
| 3. | |
| Containers for bulk oxygen and medical gas. | |
| 4. | |
| Unfired pressure | |
| vessels having a volume of 5 cubic feet (0.14 m | |
| 3 | |
| ) or less operating at pressures not exceed- | |
| ing 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, | |
| S and U. | |
| 5. | |
| Pressure vessels used in refrigeration systems | |
| that are regulated by Chapter 11. | |
| 6. | |
| Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other | |
| similar | |
| humidity control systems. | |
| 7. | |
| Any boiler or pressure vessel subject to inspection by federal inspectors. | |
| 1001.2 The | |
| rmal safety (spill) switches. | |
| Thermal safety (spill) switches shall be installed in accordance with Section | |
| 801.23.3. | |
| 1001.3 Clearances. | |
| Minimum clearances at | |
| boilers, water heaters and pressure vessels shall be maintained in accord- | |
| ance with Chapter 3. | |
| SEC | |
| TION MC 1002 | |
| WATER HEATERS | |
| 1002.1 General. | |
| Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accord- | |
| ance with the manufacturer’s instructions, the | |
| New York City | |
| Plumbing Code | |
| and this code. All water heaters shal | |
| l be | |
| capable of being removed without first removing a permanent portion of the building structure. The potable water | |
| connections | |
| and relief valves for all water heaters shall conform to the requirements of the | |
| New York City | |
| Plumbing | |
| Code | |
| . Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall | |
| comply with UL 1453. Oil | |
| - | |
| fired water heaters shall comply with UL 732. Approval for oil | |
| - | |
| fired water heaters | |
| 350,000 | |
| Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. | |
| Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water | |
| heaters shall comply with UL 174 or UL 1995. | |
| 1002.2 Water heaters utilized for s | |
| pace heating. | |
| Water heaters utilized both to supply potable hot water and provide | |
| hot water for space | |
| - | |
| heating applications shall be listed and labeled for such applications by the manufacturer and shall | |
| be | |
| built in accordance with Section IV of the | |
| ASME | |
| Boiler and Pressure Vessel Code | |
| with an “H” code stamp. Water | |
| heaters shall be | |
| installed in accordance with the manufacturer’s instructions | |
| , the | |
| ASME Boiler and Pressure Vessel | |
| Code | |
| and the | |
| New York City | |
| Plumbing Code. | |
| Oil | |
| - | |
| fired heaters shall comply with U | |
| L 732 and shall have an “HW” | |
| stamp. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1002.2.1 Sizing. | |
| Water heaters utilized for both potable water heating and space | |
| - | |
| heating applications shall be sized | |
| to prevent the space | |
| - | |
| heating load from diminishing the required potable water | |
| - | |
| heating capacity. | |
| 1002.2. | |
| 2 Temperature limitation. | |
| Where a combination potable water | |
| - | |
| heating and space | |
| - | |
| heating system requires | |
| water for space heating, a temperature | |
| actuated mixing valve complying with ASSE 1017 shall be provided to | |
| temper the water supplied to the potable hot wa | |
| ter distribution system in accordance with Section 607 of the | |
| New | |
| York City Plumbing Code | |
| . | |
| 1002.2.3 Cross | |
| - | |
| connection. | |
| Water heaters utilized for both potable hot water and hot water for space | |
| - | |
| heating | |
| applications shall have separate heating sections and co | |
| nnections for distribution systems and shall not be cross | |
| - | |
| connected. The potability of the domestic water shall be maintained throughout the system in accordance with the | |
| New York City Plumbing Code. | |
| 1002.3 Supplemental water | |
| - | |
| heating devices. | |
| Potable | |
| water | |
| - | |
| heating devices that utilize refrigerant | |
| - | |
| to | |
| - | |
| water heat | |
| exchangers shall be approved and installed in accordance with the | |
| New York City | |
| Plumbing Code | |
| , the applicable | |
| provisions of the | |
| New York City Energy Conservation Code | |
| and the manufacturer’s | |
| instructions. | |
| SECTION MC 1003 | |
| PRESSURE VESSELS | |
| 1003.1 General. | |
| All pressure vessels shall be constructed and certified in accordance with the | |
| ASME Boiler and | |
| Pressure Vessel Code | |
| , and shall | |
| bear the label of an approved agency. Pressure vessels shall | |
| be in | |
| stalled in accordance | |
| with the manufacturer’s | |
| instructions and nationally recognized standards. Directly fired pressure vessels shall meet | |
| the requirements of Section 1004. | |
| 1003.2 Piping. | |
| All piping materials, fittings, joints, | |
| connections | |
| and devices asso | |
| ciated with systems utilized in | |
| con- | |
| junction | |
| with pressure vessels shall be designed for the specific application and shall | |
| comply with the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| and this code | |
| . | |
| 1003.3 Welding. | |
| Welding on pressure vessels shall be performed by | |
| welders | |
| certified in | |
| compliance with nationally | |
| recognized standards, including the | |
| National Board Inspection Code | |
| and | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| Section | |
| IX. Such welders shall also comply with 12 NYCRR 4 | |
| - | |
| 6.2, and 12 NYCRR 14 | |
| - | |
| 3.3 through 14 | |
| - | |
| 3.1 | |
| 8. | |
| SECTION | |
| MC | |
| 1004 | |
| BOILERS | |
| 1004.1 Standards. | |
| Boilers shall be designed, constructed and certified in accordance with the | |
| ASME Boiler and Pres- | |
| sure Vessel Code | |
| , Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with | |
| fuel | |
| input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD | |
| - | |
| 1. Controls and safety | |
| devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. | |
| Packaged oil | |
| - | |
| fired boile | |
| rs shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be | |
| listed and labeled in accordance with UL 834. | |
| Approval for oil | |
| - | |
| fired boilers 350,000 Btu/h input (102.6 kW) and | |
| above shall be obtained from the New York City Depa | |
| rtment of Environmental Protection. | |
| 1004.1.1 Field erected boilers requirements. | |
| Field erected boiler installations shall comply with the following | |
| : | |
| 1. | |
| The vessel erector shall hold the appropriate ASME stamp for vessel construction. | |
| 2. | |
| The licensed instal | |
| ler is responsible for the installation of all controls and burners which shall be designed | |
| and constructed in accordance with the requirements of ASME CSD | |
| - | |
| 1 and, as applicable, the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| , 12 NYCRR Parts 4 and 14, and NFPA 85 | |
| . | |
| 3. | |
| The New York City Department of Environmental Protection shall approve the installation of the boiler and | |
| burner for compatibility, controls and safety devices. | |
| 4. | |
| Boiler vessels shall comply with one of the following listings: | |
| 4.1. | |
| UL 726 or UL 795 a | |
| s applicable; or | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 4.2. | |
| UL 2106. | |
| Exception: | |
| Unlisted equipment shall obtain approval from the department. | |
| 5. | |
| Controls and safety devices shall be tested and inspected in accordance with ASME CSD | |
| - | |
| 1 and, as applicable, | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| 12 NYCRR Parts 4 and 14, and NFPA 85. Testing and inspection | |
| shall be performed by the burner manufacturer’s authorized representative in the presence of the licensed | |
| installer. | |
| 6. | |
| Inspection of the installed boiler assembly shall be performed by the dep | |
| artment. | |
| 1004.2 Installation. | |
| In addition to the requirements of this code, the installation of boilers shall conform to the | |
| man- | |
| ufacturer’s | |
| instructions. Operating instructions of a permanent type shall be | |
| located in | |
| the boiler | |
| room and readily | |
| accessible | |
| . | |
| Boilers shall have all controls set, adjusted and tested by the installer. The manufacturer’s rating data and | |
| the nameplate shall be attached to the boiler. | |
| 1004.3 Working clearance. | |
| Clearances shall be maintained around boilers, generators, heaters, tanks and related | |
| equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When | |
| boilers are installed or replaced, clearance shall | |
| be provided to allow access for maintenance and repair | |
| per the boiler’s | |
| listing and manufacturer’s instructions. | |
| Passageways | |
| for inspection | |
| around all sides of boilers shall have an unob- | |
| structed width of not less than 18 inches | |
| ( | |
| 457.2 | |
| mm) | |
| unless | |
| the boiler | |
| ’s listing or department approval or manufac- | |
| turer’s instructions state | |
| otherwise. | |
| 1004.3.1 Top clearance. | |
| Clearances from the tops of boilers to the ceiling or other overhead obstruction shall be | |
| in accordance with Table 1004.3.1. | |
| TABLE 1004.3.1 | |
| BOILER TOP | |
| CLEARANCES | |
| BOILER TYPE | |
| MINIMUM | |
| CLEARANCES FROM | |
| TOP OF BOILER TO | |
| CEILING OR OTHER | |
| OVERHEAD | |
| OBSTRUCTION (feet) | |
| All boilers with manholes on top of the | |
| boiler except where a greater clearance is | |
| required in this table. | |
| 3 | |
| All boilers without | |
| manholes on top of | |
| the boiler except high | |
| - | |
| pressure steam | |
| boilers and where a greater clearance is | |
| required in this table. | |
| 2 | |
| High | |
| - | |
| pressure steam boilers with steam | |
| generating capacity not exceeding 5,000 | |
| pounds per hour. | |
| 3 | |
| High | |
| - | |
| pressure steam | |
| boilers with steam | |
| generating capacity exceeding 5,000 | |
| pounds per hour. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface not exceeding 1,000 square | |
| feet. | |
| 3 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface in excess of 1,000 square | |
| feet. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers with input | |
| not exceeding 5,000,000 Btu/h. | |
| 3 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| High | |
| - | |
| pressure steam boilers with input in | |
| excess of 5,000,000 Btu/h. | |
| 7 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers with input exceeding | |
| 5,000,000 Btu/h. | |
| 3 | |
| Steam | |
| - | |
| heating boilers exceeding 5,000 | |
| pounds of steam per hour. | |
| 3 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers having heating surface | |
| exceeding 1,000 square feet. | |
| 3 | |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m | |
| 2 | |
| , 1 pound per hour = 0.4536 | |
| kg/h, 1 Btu/hr = 0.293 W. | |
| 1004.4 Mounting. | |
| Equipment | |
| and appliances | |
| shall be set or mounted on a level base capable of supporting and dis- | |
| tributing the weight contained thereon. Boilers, tanks and equipment shall be | |
| securely anchored to the structure. | |
| Equ | |
| ipment and appliances requiring vibration isolation shall be installed as designed by a registered design profes- | |
| sional | |
| in accordance with the manufacturer’s instructions. | |
| 1004.5 Floors. | |
| Boilers shall be mounted on floors of noncombustible | |
| construction, unless listed for mounting on | |
| combustible flooring. Vibration isolation shall be in accordance with Section 313. In buildings with residential occu- | |
| pancies, boilers shall be installed in accordance with the requirements of Section 313. | |
| 1004.6 | |
| Boiler rooms and enclosures. | |
| Boiler rooms and enclosures and access thereto shall comply with Chapters 5 | |
| and 10 of the | |
| New York City | |
| Building Code | |
| and Chapter 3 of this code. Boiler rooms shall be equipped with a floor | |
| drain or other approved means for | |
| disposing | |
| of liquid waste | |
| in accordance with the | |
| New York City Plumbing Code | |
| . | |
| 1004.7 Operating adjustments and instructions. | |
| Hot water and steam boil | |
| ers shall have all operating and safety | |
| controls set and operationally tested by the installing contractor. A | |
| complete | |
| control diagram and boiler operating | |
| instructions shall be furnished by the installer for each installation. | |
| A complete control diagram o | |
| f a permanent type | |
| shall be located in the boiler room and shall be readily accessible. | |
| 1004.8 Burner controls. | |
| Gas and oil modulating burners shall be provided with burner controls (oil and gas equiv- | |
| alent ratings) in accordance with ASME CSD | |
| - | |
| 1 and NFPA 85 | |
| . | |
| 1004.9 Conversion burners. | |
| Conversion burners shall be installed in accordance with ANSI Z21.8. | |
| SECTION MC 1005 | |
| BOILER CONNECTIONS | |
| 1005.1 Valves. | |
| Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple | |
| boil | |
| er or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in | |
| the | |
| supply | |
| and return piping. | |
| Exception: | |
| Shutoff valves are not required in a system | |
| having | |
| a single low | |
| - | |
| pressure steam boiler | |
| of 350,000 Btu | |
| /h | |
| (103 kW) output or less | |
| . | |
| 1005.2 Potable water supply. | |
| The water supply to all boilers, including but not limited to backflow prevention, shall | |
| be connected in accordance with the | |
| New | |
| York City | |
| Plumbing Code | |
| . | |
| SECTION MC 1006 | |
| SAFETY AND PRESSURE | |
| RELIEF VALVES | |
| AND CONTROLS | |
| 1006.1 Safety valves for steam boilers. | |
| Steam boilers shall be protected with a safety valve | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1006.2 Safety relief valves for hot water boilers. | |
| Hot water | |
| boilers shall be protected with a safety relief valve | |
| in | |
| accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.3 Pressure relief for pressure vessels. | |
| Pressure vessels | |
| shall be protected with a pressure relief valve or | |
| pres- | |
| sure | |
| - | |
| limit | |
| ing device as required by the manufacturer’s instructions for the pressure vessel and | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| 1006.4 Standards of safety and safety relief valves. | |
| Safety and safety relief valves shall be l | |
| isted and labeled, and | |
| shall have a minimum rated capacity for the equipment or appliances served. Safety and safety relief valves shall be | |
| set at not greater than the nameplate pressure rating of the boiler or pressure vessel and shall be in accordance wi | |
| th | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| or the ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.5 Installation. | |
| Safety or relief valves shall be installed directly into the safety or relief valve opening on the | |
| boiler or pressure vessel. Valves shall not be located on either side of a safety or relief valve connection. The relief | |
| valve drain shall | |
| discharge by gravi | |
| ty to a nonhazardous point of discharge without obstruction.‡ | |
| 1006.6 Safety and relief valve discharge. | |
| Safety and relief valve discharge pipes shall be of rigid pipe that is approved | |
| for the temperature of the system. The discharge pipe shall | |
| , at a minimu | |
| m, | |
| be the same diameter as the safety or relief | |
| valve outlet. Safety and relief valve discharge pipes shall be properly supported to prevent stress on the valve and | |
| vessel. Safety and relief valves shall not discharge so as to be a hazard, a potential caus | |
| e of damage or otherwise a | |
| nuisance. | |
| Discharge of hazardous materials must be properly contained in a method approved by the department. | |
| High | |
| - | |
| pressure | |
| - | |
| steam safety valves shall be vented to the outside of the structure. Where a low | |
| - | |
| pressure safety valve | |
| or | |
| a relief valve discharges to the drainage system, the installation shall conform to the | |
| New York City | |
| Plumbing Code | |
| . | |
| 1006.7 Boiler safety devices. | |
| Boilers shall be equipped with controls and limit devices as required by the manufac- | |
| turer’s instructions and | |
| the conditions of the listing. | |
| 1006.8 Electrical requirements. | |
| The power supply to the electrical control system shall be from a two | |
| - | |
| wire branch | |
| circuit | |
| that has a grounded conductor, or from an isolation | |
| trans | |
| - | |
| former | |
| with a two | |
| - | |
| wire secondary. Where an i | |
| solation | |
| transformer is provided, one conductor of the secondary | |
| winding | |
| shall be grounded. Control voltage shall not exceed | |
| 150 volts nominal, line to line. Control and limit devices shall | |
| interrupt | |
| the ungrounded side of the circuit. A means | |
| of manually | |
| disconnecting the control circuit shall be provided and controls shall be arranged so that when deener- | |
| gized, the burner shall be inoperative. Such disconnecting means shall be capable of being locked in the off position | |
| and shall be provided with ready acc | |
| ess. | |
| 1006.8.1 Remote control (shutdown). | |
| A remote control shall be provided to stop the flow of oil and/or gas and | |
| combustion air to any burner or fuel | |
| - | |
| burning internal combustion equipment. Such a control shall be provided | |
| along every means of egress from | |
| the room in which the burner or equipment is located. Each remote control shall | |
| be located outside of, but as close as practicable to the burner or equipment room itself and shall be labeled: | |
| “REMOTE CONTROL FOR BURNER.” | |
| Exception: | |
| Where an outside locati | |
| on is impracticable, the remote control shutdown may be provided immedi- | |
| ately inside the room in which the burner or equipment is located. | |
| Such location must be accessible at all times. | |
| 1006.9 Carbon monoxide detectors. | |
| Carbon monoxide detectors shall be p | |
| rovided in all fuel | |
| - | |
| fired appliance rooms | |
| to detect the level of carbon monoxide in the room and signal an alarm. Such detectors shall be listed and installed | |
| in accordance with Chapter 9 of the | |
| New York City Building Code | |
| . | |
| SECTION | |
| MC | |
| 1007 | |
| BOILER | |
| LOW | |
| - | |
| WATER CUTOFF | |
| 1007.1 General. | |
| Steam and hot water boilers shall be protected with | |
| dual | |
| low | |
| - | |
| water cutoff control, with each control | |
| independently piped to the pressure vessel in accordance with ASME CSD | |
| - | |
| 1. For hydronic boilers, the low | |
| - | |
| water cut | |
| out may | |
| be located in the supply piping above the boiler before any intervening valve. A flow | |
| - | |
| sensing control installed | |
| in accordance with ASME CSD | |
| - | |
| 1 shall be considered a low | |
| - | |
| water cutoff for the purposes of this section. | |
| Exception: | |
| Hot water | |
| boilers | |
| located wit | |
| hin a dwelling unit supplying only | |
| that | |
| unit and having a total heat input | |
| of | |
| less than 400,000 Btu/h (117.2 kW) may be | |
| protected | |
| by only one low | |
| - | |
| water cutoff | |
| control. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1007.2 Operation. | |
| Low | |
| - | |
| water cutoff controls and flow | |
| - | |
| sensing controls required by Section 1007.1 shall automati- | |
| cally stop the combustion operation of the appliance when the water level drops below the lowest safe water level as | |
| established by the manufacturer | |
| and in accordance with ASME CSD | |
| - | |
| 1, | |
| or when water circulation stops, respectively. | |
| 10 | |
| 07.3 Low | |
| - | |
| water cut out maintenance and testing. | |
| Low | |
| - | |
| water cut outs shall be maintained in accordance with | |
| ASME CSD | |
| - | |
| 1 and the manufacturer’s specifications. An operator shall test low | |
| - | |
| water cut outs as follows: (1) high | |
| pressure steam boilers every shift, ( | |
| 2) low pressure steam boilers daily and (3) hot water boilers monthly. Slow drain | |
| tests shall be conducted for steam boilers every six months. | |
| Every year, low | |
| - | |
| water cut outs and associated piping for | |
| steam boilers shall be opened, cleaned and inspected. | |
| Re | |
| cords of all testing, cleaning, and inspection required by this | |
| section shall be maintained, and made available to the department upon request. | |
| SECTION MC 1008 | |
| BOILER BLOWOFF/BLOWDOWN VALVES | |
| 1008.1 General. | |
| Every boiler | |
| shall be equipped with blowoff | |
| /blow | |
| down | |
| valve(s). The valve(s) shall be installed in | |
| the | |
| openings | |
| provided on the boiler. The minimum | |
| quantity and | |
| size of the valve(s) and associated piping shall be the | |
| quantity and | |
| size specified by the boiler manufacturer or the | |
| quantity and size of the boiler blowoff | |
| /blowdown | |
| valve | |
| opening. Where the maximum allowable working pressure of the boiler exceeds 15 psig (103.4 kPa), two bottom | |
| blowoff valves shall be provided consisting | |
| of either two slow | |
| - | |
| opening valves in series or one quick | |
| - | |
| opening valve | |
| and one slow | |
| - | |
| opening valve in series, with the quick | |
| - | |
| opening valve installed closest to the boiler. | |
| 1008.2 Discharge. | |
| Blowoff | |
| /blowdown | |
| valves shall discharge to a safe place of disposal. Where discharging to the | |
| drainage system, the installation shall conform to the | |
| New York City | |
| Plumbing Code. | |
| 1008.3 Maintenance. | |
| Blowdown lines shall be inspected annually to verify they are free of deposits and in good | |
| working condition. | |
| SECTION MC 1009 | |
| HOT WATER BOILER EXPANSION TANK | |
| 1009.1 Where required. | |
| An expansion tank shall be installed in every hot water system. For multiple boiler installa- | |
| tions, not less than one expansion tank is required. Expansion tanks shall be of the closed or open type. Tanks shall | |
| be rated for the pressure of the hot water system. | |
| Lockable shutoff valves shall be installed at connections to all | |
| expansion tanks. Valves shall remain locked in the open position. | |
| 1009.2 Closed | |
| - | |
| type expansion tanks. | |
| Closed | |
| - | |
| type expansion tanks shall be installed in accordance with the manu- | |
| facturer’s instructions. Expansion tanks for systems designed to have an operating pressure in excess of 30 psi (205.8 | |
| kPa) shall be constructed and certified in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| . The size of the | |
| tank shall be based on the capacity of the hot | |
| - | |
| water | |
| - | |
| heating system. The minimum size of the tank shall be determined | |
| in accordance with the following equation where all necessary | |
| information is known: | |
| V | |
| t | |
| = | |
| ( | |
| 0 | |
| . | |
| 00041T | |
| −0 | |
| . | |
| 0466 | |
| ) | |
| V | |
| s | |
| � | |
| P | |
| a | |
| P | |
| f | |
| � | |
| −� | |
| P | |
| a | |
| P | |
| o | |
| � | |
| (Equation 10 | |
| - | |
| 1) | |
| For SI: | |
| V | |
| t | |
| = | |
| ( | |
| 0. | |
| 000738T | |
| − | |
| 0. | |
| 03348 | |
| ) | |
| V | |
| s | |
| � | |
| P | |
| a | |
| P | |
| f | |
| �−� | |
| P | |
| a | |
| P | |
| o | |
| � | |
| where: | |
| V | |
| t | |
| = | |
| Minimum volume of tanks (gallons) (L). | |
| V | |
| s | |
| = | |
| Volume of system, not including expansion tanks | |
| (gallons) (L). | |
| T | |
| = | |
| Average operating temperature ( | |
| ° | |
| F) ( | |
| ° | |
| C). | |
| P | |
| a | |
| = | |
| Atmospheric pressure (psi) (kPa). | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| P | |
| f | |
| = | |
| Fill pressure (psi) (kPa). | |
| P | |
| o | |
| = | |
| Maximum operating pressure (psi) (kPa). | |
| Where all necessary information is not known, the minimum size of the tank shall be | |
| determined from Table 1009.2. | |
| TABLE 1009.2 | |
| CLOSED | |
| - | |
| TYPE EXPANSION TANK SIZING | |
| SYSTEM VOLUME | |
| IN GALLONS | |
| TANK CAPACITIES IN GALLONS | |
| Pressurized | |
| Diaphragm Type | |
| Nonpressurized | |
| Type | |
| 100 | |
| 9 | |
| 15 | |
| 200 | |
| 17 | |
| 30 | |
| 300 | |
| 25 | |
| 45 | |
| 400 | |
| 33 | |
| 60 | |
| 500 | |
| 42 | |
| 75 | |
| 1,000 | |
| 83 | |
| 150 | |
| 2,000 | |
| 165 | |
| 300 | |
| For SI: 1 gallon = 3.795 L. | |
| 1009.3 Open | |
| - | |
| type expansion tanks. | |
| Open | |
| - | |
| type expansion tanks shall be located not less than 4 feet (1219.2 mm) | |
| above the highest heating element. The tank shall be adequately sized for the hot water system. An overflow with a | |
| minimum | |
| diameter | |
| of 1 inch (25.4 mm) shall be installed at the to | |
| p of the tank. The overflow shall discharge to the | |
| drainage system in | |
| accordance | |
| with the | |
| New York City | |
| Plumbing Code. | |
| SECTION MC 1010 | |
| GAUGES | |
| 1010.1 Hot water boiler gauges. | |
| Every hot water boiler shall have a pressure gauge and a temperature gauge, or a | |
| c | |
| ombination pressure and temperature gauge. The gauges shall indicate the temperature and pressure within the normal | |
| range of the system’s operation. | |
| 1010.2 Steam boiler gauges. | |
| Every steam boiler shall have a water | |
| - | |
| gauge glass and a pressure gauge with a s | |
| iphon. | |
| The pressure gauge shall indicate the pressure within the normal range of the system’s operation. | |
| 1010.2.1 Water | |
| - | |
| gauge glass. | |
| The gauge glass shall be installed in accordance with the | |
| ASME Boiler and Pressure | |
| Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| SECTION MC 1011 | |
| TESTS | |
| 1011.1 Tests. | |
| Upon completion of the assembly and | |
| installation | |
| of boilers and pressure vessels, acceptance tests shall | |
| be conducted in accordance with the requirements of the | |
| ASME Boiler and Pressure Vessel Code | |
| . Boilers shall not | |
| be placed in operation upon completion of construction until they have been inspected | |
| a | |
| nd | |
| tested and a certificate of | |
| compliance has been issued by the commissioner. All final inspections and | |
| tests | |
| for boilers shall be witnessed by a | |
| qualified boiler inspector in the employ of the department or a duly authorized insurance company as provided | |
| in | |
| Section 204 of the Labor Law of the State of New York. Equipment having an input of not more than 350,000 Btu/h | |
| (103 kW) shall be exempt from this requirement. Where field assembly of pressure vessels or boilers is required, a | |
| copy of | |
| the completed H | |
| - | |
| 2 | |
| , P | |
| - | |
| 2 or U | |
| - | |
| 1 Manufacturer’s Data Report and the completed Appendix C of ASME CSD | |
| - | |
| 1 | |
| required by the | |
| ASME Boiler and Pressure Vessel Code | |
| shall be submitted to the | |
| department | |
| . | |
| 1011.1.1 Fitness for service. | |
| When a boiler or pressure vessel has exceeded its us | |
| eful life or has been subjected to | |
| an event that may have impacted the integrity of the pressure vessel, the department may require that a fitness for | |
| service study be completed. The study shall be completed in accordance with the | |
| National Board Inspection | |
| Code | |
| Part 2, Section 4, and documented in accordance with the National Board 403 form. | |
| ‡‡‡ Chapter 10 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 10 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| SECTION MC 1001 | |
| GENERAL | |
| 1001.1 Scope. | |
| This chapter | |
| shall establish the minimum safety requirements for and | |
| shall govern the installation, | |
| alteration and repair of boilers, wate | |
| r heaters and pressure vessels. | |
| Exceptions: | |
| 1. | |
| Pressure vessels used for unheated water supply. | |
| 2. | |
| Portable unfired pressure vessels and Interstate | |
| Commerce | |
| Commission containers. | |
| 3. | |
| Containers for bulk oxygen and medical gas. | |
| 4. | |
| Unfired pressure | |
| vessels having a volume of 5 cubic feet (0.14 m | |
| 3 | |
| ) or less operating at pressures not exceed- | |
| ing 250 pounds per square inch (psi) (1723.7 kPa) and located within occupancies of Groups B, F, H, M, R, | |
| S and U. | |
| 5. | |
| Pressure vessels used in refrigeration systems | |
| that are regulated by Chapter 11. | |
| 6. | |
| Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other | |
| similar | |
| humidity control systems. | |
| 7. | |
| Any boiler or pressure vessel subject to inspection by federal inspectors. | |
| 1001.2 The | |
| rmal safety (spill) switches. | |
| Thermal safety (spill) switches shall be installed in accordance with Section | |
| 801.23.3. | |
| 1001.3 Clearances. | |
| Minimum clearances at | |
| boilers, water heaters and pressure vessels shall be maintained in accord- | |
| ance with Chapter 3. | |
| SEC | |
| TION MC 1002 | |
| WATER HEATERS | |
| 1002.1 General. | |
| Potable water heaters and hot water storage tanks shall be listed and labeled and installed in accord- | |
| ance with the manufacturer’s instructions, the | |
| New York City | |
| Plumbing Code | |
| and this code. All water heaters shal | |
| l be | |
| capable of being removed without first removing a permanent portion of the building structure. The potable water | |
| connections | |
| and relief valves for all water heaters shall conform to the requirements of the | |
| New York City | |
| Plumbing | |
| Code | |
| . Domestic electric water heaters shall comply with UL 174 or UL 1453. Commercial electric water heaters shall | |
| comply with UL 1453. Oil | |
| - | |
| fired water heaters shall comply with UL 732. Approval for oil | |
| - | |
| fired water heaters | |
| 350,000 | |
| Btu/h input (103 kW) and above shall be obtained from the New York City Department of Environmental Protection. | |
| Thermal solar water heaters shall comply with UL 174 or UL 1453, and Chapter 14 of this code. Heat pump water | |
| heaters shall comply with UL 174 or UL 1995. | |
| 1002.2 Water heaters utilized for s | |
| pace heating. | |
| Water heaters utilized both to supply potable hot water and provide | |
| hot water for space | |
| - | |
| heating applications shall be listed and labeled for such applications by the manufacturer and shall | |
| be | |
| built in accordance with Section IV of the | |
| ASME | |
| Boiler and Pressure Vessel Code | |
| with an “H” code stamp. Water | |
| heaters shall be | |
| installed in accordance with the manufacturer’s instructions | |
| , the | |
| ASME Boiler and Pressure Vessel | |
| Code | |
| and the | |
| New York City | |
| Plumbing Code. | |
| Oil | |
| - | |
| fired heaters shall comply with U | |
| L 732 and shall have an “HW” | |
| stamp. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1002.2.1 Sizing. | |
| Water heaters utilized for both potable water heating and space | |
| - | |
| heating applications shall be sized | |
| to prevent the space | |
| - | |
| heating load from diminishing the required potable water | |
| - | |
| heating capacity. | |
| 1002.2. | |
| 2 Temperature limitation. | |
| Where a combination potable water | |
| - | |
| heating and space | |
| - | |
| heating system requires | |
| water for space heating, a temperature | |
| actuated mixing valve complying with ASSE 1017 shall be provided to | |
| temper the water supplied to the potable hot wa | |
| ter distribution system in accordance with Section 607 of the | |
| New | |
| York City Plumbing Code | |
| . | |
| 1002.2.3 Cross | |
| - | |
| connection. | |
| Water heaters utilized for both potable hot water and hot water for space | |
| - | |
| heating | |
| applications shall have separate heating sections and co | |
| nnections for distribution systems and shall not be cross | |
| - | |
| connected. The potability of the domestic water shall be maintained throughout the system in accordance with the | |
| New York City Plumbing Code. | |
| 1002.3 Supplemental water | |
| - | |
| heating devices. | |
| Potable | |
| water | |
| - | |
| heating devices that utilize refrigerant | |
| - | |
| to | |
| - | |
| water heat | |
| exchangers shall be approved and installed in accordance with the | |
| New York City | |
| Plumbing Code | |
| , the applicable | |
| provisions of the | |
| New York City Energy Conservation Code | |
| and the manufacturer’s | |
| instructions. | |
| SECTION MC 1003 | |
| PRESSURE VESSELS | |
| 1003.1 General. | |
| All pressure vessels shall be constructed and certified in accordance with the | |
| ASME Boiler and | |
| Pressure Vessel Code | |
| , and shall | |
| bear the label of an approved agency. Pressure vessels shall | |
| be in | |
| stalled in accordance | |
| with the manufacturer’s | |
| instructions and nationally recognized standards. Directly fired pressure vessels shall meet | |
| the requirements of Section 1004. | |
| 1003.2 Piping. | |
| All piping materials, fittings, joints, | |
| connections | |
| and devices asso | |
| ciated with systems utilized in | |
| con- | |
| junction | |
| with pressure vessels shall be designed for the specific application and shall | |
| comply with the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| and this code | |
| . | |
| 1003.3 Welding. | |
| Welding on pressure vessels shall be performed by | |
| welders | |
| certified in | |
| compliance with nationally | |
| recognized standards, including the | |
| National Board Inspection Code | |
| and | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| Section | |
| IX. Such welders shall also comply with 12 NYCRR 4 | |
| - | |
| 6.2, and 12 NYCRR 14 | |
| - | |
| 3.3 through 14 | |
| - | |
| 3.1 | |
| 8. | |
| SECTION | |
| MC | |
| 1004 | |
| BOILERS | |
| 1004.1 Standards. | |
| Boilers shall be designed, constructed and certified in accordance with the | |
| ASME Boiler and Pres- | |
| sure Vessel Code | |
| , Section I or IV, and 12 NYCRR Parts 4 and 14. Controls and safety devices for boilers with | |
| fuel | |
| input ratings of 12,500,000 Btu/h (3663 kW) or less shall meet the requirements of ASME CSD | |
| - | |
| 1. Controls and safety | |
| devices for boilers with inputs greater than 12,500,000 Btu/h (3663 kW) shall meet the requirements of NFPA 85. | |
| Packaged oil | |
| - | |
| fired boile | |
| rs shall be listed and labeled in accordance with UL 726. Packaged electric boilers shall be | |
| listed and labeled in accordance with UL 834. | |
| Approval for oil | |
| - | |
| fired boilers 350,000 Btu/h input (102.6 kW) and | |
| above shall be obtained from the New York City Depa | |
| rtment of Environmental Protection. | |
| 1004.1.1 Field erected boilers requirements. | |
| Field erected boiler installations shall comply with the following | |
| : | |
| 1. | |
| The vessel erector shall hold the appropriate ASME stamp for vessel construction. | |
| 2. | |
| The licensed instal | |
| ler is responsible for the installation of all controls and burners which shall be designed | |
| and constructed in accordance with the requirements of ASME CSD | |
| - | |
| 1 and, as applicable, the | |
| ASME Boiler | |
| and Pressure Vessel Code | |
| , 12 NYCRR Parts 4 and 14, and NFPA 85 | |
| . | |
| 3. | |
| The New York City Department of Environmental Protection shall approve the installation of the boiler and | |
| burner for compatibility, controls and safety devices. | |
| 4. | |
| Boiler vessels shall comply with one of the following listings: | |
| 4.1. | |
| UL 726 or UL 795 a | |
| s applicable; or | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 4.2. | |
| UL 2106. | |
| Exception: | |
| Unlisted equipment shall obtain approval from the department. | |
| 5. | |
| Controls and safety devices shall be tested and inspected in accordance with ASME CSD | |
| - | |
| 1 and, as applicable, | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| , | |
| 12 NYCRR Parts 4 and 14, and NFPA 85. Testing and inspection | |
| shall be performed by the burner manufacturer’s authorized representative in the presence of the licensed | |
| installer. | |
| 6. | |
| Inspection of the installed boiler assembly shall be performed by the dep | |
| artment. | |
| 1004.2 Installation. | |
| In addition to the requirements of this code, the installation of boilers shall conform to the | |
| man- | |
| ufacturer’s | |
| instructions. Operating instructions of a permanent type shall be | |
| located in | |
| the boiler | |
| room and readily | |
| accessible | |
| . | |
| Boilers shall have all controls set, adjusted and tested by the installer. The manufacturer’s rating data and | |
| the nameplate shall be attached to the boiler. | |
| 1004.3 Working clearance. | |
| Clearances shall be maintained around boilers, generators, heaters, tanks and related | |
| equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. When | |
| boilers are installed or replaced, clearance shall | |
| be provided to allow access for maintenance and repair | |
| per the boiler’s | |
| listing and manufacturer’s instructions. | |
| Passageways | |
| for inspection | |
| around all sides of boilers shall have an unob- | |
| structed width of not less than 18 inches | |
| ( | |
| 457.2 | |
| mm) | |
| unless | |
| the boiler | |
| ’s listing or department approval or manufac- | |
| turer’s instructions state | |
| otherwise. | |
| 1004.3.1 Top clearance. | |
| Clearances from the tops of boilers to the ceiling or other overhead obstruction shall be | |
| in accordance with Table 1004.3.1. | |
| TABLE 1004.3.1 | |
| BOILER TOP | |
| CLEARANCES | |
| BOILER TYPE | |
| MINIMUM | |
| CLEARANCES FROM | |
| TOP OF BOILER TO | |
| CEILING OR OTHER | |
| OVERHEAD | |
| OBSTRUCTION (feet) | |
| All boilers with manholes on top of the | |
| boiler except where a greater clearance is | |
| required in this table. | |
| 3 | |
| All boilers without | |
| manholes on top of | |
| the boiler except high | |
| - | |
| pressure steam | |
| boilers and where a greater clearance is | |
| required in this table. | |
| 2 | |
| High | |
| - | |
| pressure steam boilers with steam | |
| generating capacity not exceeding 5,000 | |
| pounds per hour. | |
| 3 | |
| High | |
| - | |
| pressure steam | |
| boilers with steam | |
| generating capacity exceeding 5,000 | |
| pounds per hour. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface not exceeding 1,000 square | |
| feet. | |
| 3 | |
| High | |
| - | |
| pressure steam boilers having heat- | |
| ing surface in excess of 1,000 square | |
| feet. | |
| 7 | |
| High | |
| - | |
| pressure steam boilers with input | |
| not exceeding 5,000,000 Btu/h. | |
| 3 | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| High | |
| - | |
| pressure steam boilers with input in | |
| excess of 5,000,000 Btu/h. | |
| 7 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers with input exceeding | |
| 5,000,000 Btu/h. | |
| 3 | |
| Steam | |
| - | |
| heating boilers exceeding 5,000 | |
| pounds of steam per hour. | |
| 3 | |
| Steam | |
| - | |
| heating boilers and hot water | |
| - | |
| heating boilers having heating surface | |
| exceeding 1,000 square feet. | |
| 3 | |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m | |
| 2 | |
| , 1 pound per hour = 0.4536 | |
| kg/h, 1 Btu/hr = 0.293 W. | |
| 1004.4 Mounting. | |
| Equipment | |
| and appliances | |
| shall be set or mounted on a level base capable of supporting and dis- | |
| tributing the weight contained thereon. Boilers, tanks and equipment shall be | |
| securely anchored to the structure. | |
| Equ | |
| ipment and appliances requiring vibration isolation shall be installed as designed by a registered design profes- | |
| sional | |
| in accordance with the manufacturer’s instructions. | |
| 1004.5 Floors. | |
| Boilers shall be mounted on floors of noncombustible | |
| construction, unless listed for mounting on | |
| combustible flooring. Vibration isolation shall be in accordance with Section 313. In buildings with residential occu- | |
| pancies, boilers shall be installed in accordance with the requirements of Section 313. | |
| 1004.6 | |
| Boiler rooms and enclosures. | |
| Boiler rooms and enclosures and access thereto shall comply with Chapters 5 | |
| and 10 of the | |
| New York City | |
| Building Code | |
| and Chapter 3 of this code. Boiler rooms shall be equipped with a floor | |
| drain or other approved means for | |
| disposing | |
| of liquid waste | |
| in accordance with the | |
| New York City Plumbing Code | |
| . | |
| 1004.7 Operating adjustments and instructions. | |
| Hot water and steam boil | |
| ers shall have all operating and safety | |
| controls set and operationally tested by the installing contractor. A | |
| complete | |
| control diagram and boiler operating | |
| instructions shall be furnished by the installer for each installation. | |
| A complete control diagram o | |
| f a permanent type | |
| shall be located in the boiler room and shall be readily accessible. | |
| 1004.8 Burner controls. | |
| Gas and oil modulating burners shall be provided with burner controls (oil and gas equiv- | |
| alent ratings) in accordance with ASME CSD | |
| - | |
| 1 and NFPA 85 | |
| . | |
| 1004.9 Conversion burners. | |
| Conversion burners shall be installed in accordance with ANSI Z21.8. | |
| SECTION MC 1005 | |
| BOILER CONNECTIONS | |
| 1005.1 Valves. | |
| Every boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple | |
| boil | |
| er or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in | |
| the | |
| supply | |
| and return piping. | |
| Exception: | |
| Shutoff valves are not required in a system | |
| having | |
| a single low | |
| - | |
| pressure steam boiler | |
| of 350,000 Btu | |
| /h | |
| (103 kW) output or less | |
| . | |
| 1005.2 Potable water supply. | |
| The water supply to all boilers, including but not limited to backflow prevention, shall | |
| be connected in accordance with the | |
| New | |
| York City | |
| Plumbing Code | |
| . | |
| SECTION MC 1006 | |
| SAFETY AND PRESSURE | |
| RELIEF VALVES | |
| AND CONTROLS | |
| 1006.1 Safety valves for steam boilers. | |
| Steam boilers shall be protected with a safety valve | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1006.2 Safety relief valves for hot water boilers. | |
| Hot water | |
| boilers shall be protected with a safety relief valve | |
| in | |
| accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.3 Pressure relief for pressure vessels. | |
| Pressure vessels | |
| shall be protected with a pressure relief valve or | |
| pres- | |
| sure | |
| - | |
| limit | |
| ing device as required by the manufacturer’s instructions for the pressure vessel and | |
| in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| 1006.4 Standards of safety and safety relief valves. | |
| Safety and safety relief valves shall be l | |
| isted and labeled, and | |
| shall have a minimum rated capacity for the equipment or appliances served. Safety and safety relief valves shall be | |
| set at not greater than the nameplate pressure rating of the boiler or pressure vessel and shall be in accordance wi | |
| th | |
| the | |
| ASME Boiler and Pressure Vessel Code | |
| or the ASME CSD | |
| - | |
| 1 | |
| . | |
| 1006.5 Installation. | |
| Safety or relief valves shall be installed directly into the safety or relief valve opening on the | |
| boiler or pressure vessel. Valves shall not be located on either side of a safety or relief valve connection. The relief | |
| valve drain shall | |
| discharge by gravi | |
| ty to a nonhazardous point of discharge without obstruction.‡ | |
| 1006.6 Safety and relief valve discharge. | |
| Safety and relief valve discharge pipes shall be of rigid pipe that is approved | |
| for the temperature of the system. The discharge pipe shall | |
| , at a minimu | |
| m, | |
| be the same diameter as the safety or relief | |
| valve outlet. Safety and relief valve discharge pipes shall be properly supported to prevent stress on the valve and | |
| vessel. Safety and relief valves shall not discharge so as to be a hazard, a potential caus | |
| e of damage or otherwise a | |
| nuisance. | |
| Discharge of hazardous materials must be properly contained in a method approved by the department. | |
| High | |
| - | |
| pressure | |
| - | |
| steam safety valves shall be vented to the outside of the structure. Where a low | |
| - | |
| pressure safety valve | |
| or | |
| a relief valve discharges to the drainage system, the installation shall conform to the | |
| New York City | |
| Plumbing Code | |
| . | |
| 1006.7 Boiler safety devices. | |
| Boilers shall be equipped with controls and limit devices as required by the manufac- | |
| turer’s instructions and | |
| the conditions of the listing. | |
| 1006.8 Electrical requirements. | |
| The power supply to the electrical control system shall be from a two | |
| - | |
| wire branch | |
| circuit | |
| that has a grounded conductor, or from an isolation | |
| trans | |
| - | |
| former | |
| with a two | |
| - | |
| wire secondary. Where an i | |
| solation | |
| transformer is provided, one conductor of the secondary | |
| winding | |
| shall be grounded. Control voltage shall not exceed | |
| 150 volts nominal, line to line. Control and limit devices shall | |
| interrupt | |
| the ungrounded side of the circuit. A means | |
| of manually | |
| disconnecting the control circuit shall be provided and controls shall be arranged so that when deener- | |
| gized, the burner shall be inoperative. Such disconnecting means shall be capable of being locked in the off position | |
| and shall be provided with ready acc | |
| ess. | |
| 1006.8.1 Remote control (shutdown). | |
| A remote control shall be provided to stop the flow of oil and/or gas and | |
| combustion air to any burner or fuel | |
| - | |
| burning internal combustion equipment. Such a control shall be provided | |
| along every means of egress from | |
| the room in which the burner or equipment is located. Each remote control shall | |
| be located outside of, but as close as practicable to the burner or equipment room itself and shall be labeled: | |
| “REMOTE CONTROL FOR BURNER.” | |
| Exception: | |
| Where an outside locati | |
| on is impracticable, the remote control shutdown may be provided immedi- | |
| ately inside the room in which the burner or equipment is located. | |
| Such location must be accessible at all times. | |
| 1006.9 Carbon monoxide detectors. | |
| Carbon monoxide detectors shall be p | |
| rovided in all fuel | |
| - | |
| fired appliance rooms | |
| to detect the level of carbon monoxide in the room and signal an alarm. Such detectors shall be listed and installed | |
| in accordance with Chapter 9 of the | |
| New York City Building Code | |
| . | |
| SECTION | |
| MC | |
| 1007 | |
| BOILER | |
| LOW | |
| - | |
| WATER CUTOFF | |
| 1007.1 General. | |
| Steam and hot water boilers shall be protected with | |
| dual | |
| low | |
| - | |
| water cutoff control, with each control | |
| independently piped to the pressure vessel in accordance with ASME CSD | |
| - | |
| 1. For hydronic boilers, the low | |
| - | |
| water cut | |
| out may | |
| be located in the supply piping above the boiler before any intervening valve. A flow | |
| - | |
| sensing control installed | |
| in accordance with ASME CSD | |
| - | |
| 1 shall be considered a low | |
| - | |
| water cutoff for the purposes of this section. | |
| Exception: | |
| Hot water | |
| boilers | |
| located wit | |
| hin a dwelling unit supplying only | |
| that | |
| unit and having a total heat input | |
| of | |
| less than 400,000 Btu/h (117.2 kW) may be | |
| protected | |
| by only one low | |
| - | |
| water cutoff | |
| control. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1007.2 Operation. | |
| Low | |
| - | |
| water cutoff controls and flow | |
| - | |
| sensing controls required by Section 1007.1 shall automati- | |
| cally stop the combustion operation of the appliance when the water level drops below the lowest safe water level as | |
| established by the manufacturer | |
| and in accordance with ASME CSD | |
| - | |
| 1, | |
| or when water circulation stops, respectively. | |
| 10 | |
| 07.3 Low | |
| - | |
| water cut out maintenance and testing. | |
| Low | |
| - | |
| water cut outs shall be maintained in accordance with | |
| ASME CSD | |
| - | |
| 1 and the manufacturer’s specifications. An operator shall test low | |
| - | |
| water cut outs as follows: (1) high | |
| pressure steam boilers every shift, ( | |
| 2) low pressure steam boilers daily and (3) hot water boilers monthly. Slow drain | |
| tests shall be conducted for steam boilers every six months. | |
| Every year, low | |
| - | |
| water cut outs and associated piping for | |
| steam boilers shall be opened, cleaned and inspected. | |
| Re | |
| cords of all testing, cleaning, and inspection required by this | |
| section shall be maintained, and made available to the department upon request. | |
| SECTION MC 1008 | |
| BOILER BLOWOFF/BLOWDOWN VALVES | |
| 1008.1 General. | |
| Every boiler | |
| shall be equipped with blowoff | |
| /blow | |
| down | |
| valve(s). The valve(s) shall be installed in | |
| the | |
| openings | |
| provided on the boiler. The minimum | |
| quantity and | |
| size of the valve(s) and associated piping shall be the | |
| quantity and | |
| size specified by the boiler manufacturer or the | |
| quantity and size of the boiler blowoff | |
| /blowdown | |
| valve | |
| opening. Where the maximum allowable working pressure of the boiler exceeds 15 psig (103.4 kPa), two bottom | |
| blowoff valves shall be provided consisting | |
| of either two slow | |
| - | |
| opening valves in series or one quick | |
| - | |
| opening valve | |
| and one slow | |
| - | |
| opening valve in series, with the quick | |
| - | |
| opening valve installed closest to the boiler. | |
| 1008.2 Discharge. | |
| Blowoff | |
| /blowdown | |
| valves shall discharge to a safe place of disposal. Where discharging to the | |
| drainage system, the installation shall conform to the | |
| New York City | |
| Plumbing Code. | |
| 1008.3 Maintenance. | |
| Blowdown lines shall be inspected annually to verify they are free of deposits and in good | |
| working condition. | |
| SECTION MC 1009 | |
| HOT WATER BOILER EXPANSION TANK | |
| 1009.1 Where required. | |
| An expansion tank shall be installed in every hot water system. For multiple boiler installa- | |
| tions, not less than one expansion tank is required. Expansion tanks shall be of the closed or open type. Tanks shall | |
| be rated for the pressure of the hot water system. | |
| Lockable shutoff valves shall be installed at connections to all | |
| expansion tanks. Valves shall remain locked in the open position. | |
| 1009.2 Closed | |
| - | |
| type expansion tanks. | |
| Closed | |
| - | |
| type expansion tanks shall be installed in accordance with the manu- | |
| facturer’s instructions. Expansion tanks for systems designed to have an operating pressure in excess of 30 psi (205.8 | |
| kPa) shall be constructed and certified in accordance with the | |
| ASME Boiler and Pressure Vessel Code | |
| . The size of the | |
| tank shall be based on the capacity of the hot | |
| - | |
| water | |
| - | |
| heating system. The minimum size of the tank shall be determined | |
| in accordance with the following equation where all necessary | |
| information is known: | |
| V | |
| t | |
| = | |
| ( | |
| 0 | |
| . | |
| 00041T | |
| −0 | |
| . | |
| 0466 | |
| ) | |
| V | |
| s | |
| � | |
| P | |
| a | |
| P | |
| f | |
| � | |
| −� | |
| P | |
| a | |
| P | |
| o | |
| � | |
| (Equation 10 | |
| - | |
| 1) | |
| For SI: | |
| V | |
| t | |
| = | |
| ( | |
| 0. | |
| 000738T | |
| − | |
| 0. | |
| 03348 | |
| ) | |
| V | |
| s | |
| � | |
| P | |
| a | |
| P | |
| f | |
| �−� | |
| P | |
| a | |
| P | |
| o | |
| � | |
| where: | |
| V | |
| t | |
| = | |
| Minimum volume of tanks (gallons) (L). | |
| V | |
| s | |
| = | |
| Volume of system, not including expansion tanks | |
| (gallons) (L). | |
| T | |
| = | |
| Average operating temperature ( | |
| ° | |
| F) ( | |
| ° | |
| C). | |
| P | |
| a | |
| = | |
| Atmospheric pressure (psi) (kPa). | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| P | |
| f | |
| = | |
| Fill pressure (psi) (kPa). | |
| P | |
| o | |
| = | |
| Maximum operating pressure (psi) (kPa). | |
| Where all necessary information is not known, the minimum size of the tank shall be | |
| determined from Table 1009.2. | |
| TABLE 1009.2 | |
| CLOSED | |
| - | |
| TYPE EXPANSION TANK SIZING | |
| SYSTEM VOLUME | |
| IN GALLONS | |
| TANK CAPACITIES IN GALLONS | |
| Pressurized | |
| Diaphragm Type | |
| Nonpressurized | |
| Type | |
| 100 | |
| 9 | |
| 15 | |
| 200 | |
| 17 | |
| 30 | |
| 300 | |
| 25 | |
| 45 | |
| 400 | |
| 33 | |
| 60 | |
| 500 | |
| 42 | |
| 75 | |
| 1,000 | |
| 83 | |
| 150 | |
| 2,000 | |
| 165 | |
| 300 | |
| For SI: 1 gallon = 3.795 L. | |
| 1009.3 Open | |
| - | |
| type expansion tanks. | |
| Open | |
| - | |
| type expansion tanks shall be located not less than 4 feet (1219.2 mm) | |
| above the highest heating element. The tank shall be adequately sized for the hot water system. An overflow with a | |
| minimum | |
| diameter | |
| of 1 inch (25.4 mm) shall be installed at the to | |
| p of the tank. The overflow shall discharge to the | |
| drainage system in | |
| accordance | |
| with the | |
| New York City | |
| Plumbing Code. | |
| SECTION MC 1010 | |
| GAUGES | |
| 1010.1 Hot water boiler gauges. | |
| Every hot water boiler shall have a pressure gauge and a temperature gauge, or a | |
| c | |
| ombination pressure and temperature gauge. The gauges shall indicate the temperature and pressure within the normal | |
| range of the system’s operation. | |
| 1010.2 Steam boiler gauges. | |
| Every steam boiler shall have a water | |
| - | |
| gauge glass and a pressure gauge with a s | |
| iphon. | |
| The pressure gauge shall indicate the pressure within the normal range of the system’s operation. | |
| 1010.2.1 Water | |
| - | |
| gauge glass. | |
| The gauge glass shall be installed in accordance with the | |
| ASME Boiler and Pressure | |
| Vessel Code | |
| or ASME CSD | |
| - | |
| 1. | |
| SECTION MC 1011 | |
| TESTS | |
| 1011.1 Tests. | |
| Upon completion of the assembly and | |
| installation | |
| of boilers and pressure vessels, acceptance tests shall | |
| be conducted in accordance with the requirements of the | |
| ASME Boiler and Pressure Vessel Code | |
| . Boilers shall not | |
| be placed in operation upon completion of construction until they have been inspected | |
| a | |
| nd | |
| tested and a certificate of | |
| compliance has been issued by the commissioner. All final inspections and | |
| tests | |
| for boilers shall be witnessed by a | |
| qualified boiler inspector in the employ of the department or a duly authorized insurance company as provided | |
| in | |
| Section 204 of the Labor Law of the State of New York. Equipment having an input of not more than 350,000 Btu/h | |
| (103 kW) shall be exempt from this requirement. Where field assembly of pressure vessels or boilers is required, a | |
| copy of | |
| the completed H | |
| - | |
| 2 | |
| , P | |
| - | |
| 2 or U | |
| - | |
| 1 Manufacturer’s Data Report and the completed Appendix C of ASME CSD | |
| - | |
| 1 | |
| required by the | |
| ASME Boiler and Pressure Vessel Code | |
| shall be submitted to the | |
| department | |
| . | |
| 1011.1.1 Fitness for service. | |
| When a boiler or pressure vessel has exceeded its us | |
| eful life or has been subjected to | |
| an event that may have impacted the integrity of the pressure vessel, the department may require that a fitness for | |
| service study be completed. The study shall be completed in accordance with the | |
| National Board Inspection | |
| Code | |
| Part 2, Section 4, and documented in accordance with the National Board 403 form. | |
| BOILERS, WATER HEATERS AND PRESSURE VESSELS | |
| 1011.2 Test gauges. | |
| An indicating test gauge shall be | |
| connected | |
| directly to the boiler or pressure vessel where it is | |
| visible to the operator throughout the duration of | |
| the test. The pressure gauge scale shall be graduated over a range of | |
| not less than one and one | |
| - | |
| half times and not greater than four times the maximum test pressure. Gauges utilized for | |
| testing shall be calibrated and certified | |
| annually in accordance with | |
| ASME B40.100 | |
| by the test operator. | |
| ‡‡‡ | |
| 1011.3 Periodic boiler inspections. | |
| Periodic boiler inspections shall be performed in accordance with Article | |
| 303 | |
| of Chapter 3 | |
| of Title 28 | |
| of the | |
| Administrative Code | |
| and Section 1007.3 of this code. In | |
| addition, boiler inspec- | |
| tions shall: | |
| 1. | |
| Be completed in accordance with the | |
| National Board Inspection Code | |
| . | |
| 2. | |
| Include the review of testing documentation for all controls and safety devices. | |
| 3. | |
| Verify that the flue connection from the boiler to the chimney | |
| is properly sealed and in good working condition. | |
| 4. | |
| Verify that the combustion air system as originally designed is operational. | |
| 5. | |
| Verify that the High Pressure Operators’ licenses are current and that Low Pressure Operators are qualified per | |
| New York S | |
| tate requirements. | |
| 6. | |
| Include a permanent record of the visit. | |
| 7. | |
| Be subject to the quality control measures of the department. | |
| 1011.4 | |
| Pressurized systems containing hazardous materials. | |
| Any pressurized system that contains hazardous ma- | |
| terials or presents | |
| a physical hazard by release shall be pre | |
| - | |
| approved for installation, subject to testing, and subject to | |
| inspection by the department. | |
| 1011.5 Nondestructive examination. | |
| When required by the department, the nondestructive examination (NDE) re- | |
| quirements, in | |
| cluding technique, extent of coverage, procedures, personnel qualification, and acceptance criteria, shall | |
| be performed in accordance with the applicable provisions of the edition of the code of construction for the pressure | |
| - | |
| vessel in effect at the time of | |
| installation. Weld repairs and alterations shall be subject to the same nondestructive | |
| examination requirements. Where this is not possible or practicable, alternative NDE methods acceptable to the in- | |
| spector and the department may be used. | |
| SECTION MC 1012 | |
| MAXIMUM TEMPERATURE | |
| 1012.1 Maximum temperature. | |
| Maximum indoor temperature in spaces surrounding boilers, water heaters, and | |
| pressure vessels shall not exceed the operational temperature of the installed equipment or 104°F (40°C). |