‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm).from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm).from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm). GENERAL REGULATIONS 308.4.2.2 Masonry chimneys. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry chimne ys as specified in the New York City Building Code and Chapter 8 of this code. 308.4.2.3 Chimney connector pass - throughs. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for chimney connect or pass - throughs as specified in Sec- tion 803.10.4. 308.4.2.4 Masonry fireplaces. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry fireplaces as specified in the New York City Bui lding Code and Chapter 8 of this code. 308.4.2.5 Kitchen exhaust ducts. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the minimum clearances required by Section 506.3.11 for kitchen exhaust ducts enclosed in a s haft. SECTION MC 309 TEMPERATURE CONTROL 309.1 Space - heating systems. Interior spaces intended for human occupancy shall be provided with active or passive space - heating systems capable of maintaining an indoor temperature of not less than 68°F (20°C) at a point 3 feet (914.4 mm) above floor on the design heating day. The installation of portable space heaters shall not be used to achieve compliance with this section . Refer to Section 1204 of the New York City Building Code . Exception: Interior s paces where the primary purpose is not associated with human comfort. SECTION MC 310 EXPLOSION CONTROL 310.1 Required. Structures occupied for purposes involving explosion hazards shall be provided with explosion control in compliance with rules of the Commissioner of the Fire Department. Explosion control systems shall be designed and installed in accordance with the New York City Fire Code . SECTION MC 311 SMOKE AND HEAT VENTS 311.1 Required. Approved smoke and heat vents shall be installed in the roofs of one - story buildings where required by the New York City Fire Code . Smoke and heat vents shall be designed and installe d in accordance with the New York City Fire Code . SECTION MC 312 HEATING AND COOLING LOAD CALCULATIONS 312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the procedures described in the ASHRAE ACCA Standard 183. Alternatively, design loads shall be determined by an appro ved equivalent computation procedure, using the design parameters specified in the New York City Energy Conservation Code . Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall also comply with the requir ements of Section 1204 of the New York City Building Code . SECTION MC 313 NOISE CONTROL AND VIBRATION ISOLATION REQUIREMENTS 313.1 General. Interior and exterior mechanical equipment and systems shall comply with the provisions of this sec- tion. GENERAL REGULATIONS 313.2 Noise from exterior mechanical equipment. Mechanical equipment located outside of the building in a yard or court or on a roof, or located inside a building but open to the exterior of the building, shall comply with the requirements of Sections 313.2.1 and 313 .2.2. 313.2.1 Design and installation. The applicant shall select and design any such exterior mechanical equipment in order to achieve compliance with the applicable requirements of Sections 24 - 218, 24 - 227, 24 - 228 and 24 - 232 of the Administrative Code , al so known as the New York City Noise Control Code , in accordance with generally acceptable engineering practices. 313.2.2 Operation. The operation of such exterior mechanical equipment shall comply with any applicable re- quirements of Sections 24 - 218, 24 - 227 , 24 - 228 and 24 - 232 of the New York City Noise Control Code , as enforced by the Department of Environmental Protection. 313.3 Minimum structure - borne noise and vibration isolation requirements. All isolators shall comply with the requirements of Sections 3 13.3.1 through 313.3.10. Where vibration isolation of equipment and appliances is em- ployed, supplemental restraint shall be used to accomplish the support and restraint. Exception: When specified by the registered design professional, the requirements of S ections 313.3.1 through 313.3.10 may be modified provided that the equipment, appliances, and supports shall be designed and installed so that continuous or intermittent vibration transmitted to structural slabs shall not exceed the following values be- twee n 8 Hz and 80 Hz on the structural slab in the affected occupancy space: 1. Group E, I or R occupancies: 5,600 microinches (142.4 um) per second. 2. All other occupancies: 16,000 microinches (406.4 um) per second. For the purposes of this exception, transmitted vibration shall be in accordance with the following parameters: 1. The peak third - octave band RMS velocity measurements. 2. The method shall be in accordance with ANSI/ASA S2.71. 313.3.1 Boiler rooms. Boilers, boiler breeching, and b oiler piping shall be isolated in accordance with the appli- cable requirements of Sections 313.3.1.1 and 313.3.1.2. 313.3.1.1 Boilers. All boilers supported on floors directly above a story having dwelling units shall be sup- ported on resilient isolators hav ing a minimum static deflection of 1 inch (25.4 mm). The isolators shall be installed directly under the structural frame of the boiler. 313.3.1.2 Boiler breeching and piping. When boilers are equipped with mechanical draft fans, the boiler breeching and p iping that are supported from or on slabs, floors or walls that are contiguous to the dwelling unit shall be supported for a distance of 50 pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of 1 inch (25.4 mm). 313.3.2 Refuse charging chutes. Metal chutes, chute supports, and chute bracing shall be installed in accordance with Section 313.3.2.1. Masonry chutes must comply with Section 313.3.2.2. 313.3.2.1 Metal chutes. Metal chutes, metal chute supports, and /or metal chute bracing shall be free of direct contact with the shaft enclosure and the openings provided in the floor construction. Metal chutes shall be resiliently supported at each structural support location. Isolators shall provide a minimum static deflection of 0.30 inches (7.62 mm). All chutes shall be plumb. 313.3.2.2 Masonry chutes. The interior chute wall shall be plumb and without obstructions for the full height of the shaft and shall have a smooth interior finish. 313.3.3 Piping. Equipment pi ping shall be installed as follows: 1. Metal piping connected to power driven equipment shall be resiliently supported from or on the building structure for a distance of 50 pipe diameters from the power driven equipment. The resilient isolators shall have a minimum static deflection of 1 inch (25.4 mm) for all piping with a 4 inch (101.6 mm) or larger in actual outside diameter and 1 / 2 inch (12.7 mm) for piping with less than 4 inches (101.6 mm) in actual outside diameter. Piping connected to fluid pressur e - reducing valves shall be resiliently isolated for a distance of 50 pipe diameters from pressure - reducing valves and isolators shall provide a minimum static deflection of 1 / 2 inch (12.7 mm). ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm). GENERAL REGULATIONS 308.4.2.2 Masonry chimneys. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry chimne ys as specified in the New York City Building Code and Chapter 8 of this code. 308.4.2.3 Chimney connector pass - throughs. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for chimney connect or pass - throughs as specified in Sec- tion 803.10.4. 308.4.2.4 Masonry fireplaces. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry fireplaces as specified in the New York City Bui lding Code and Chapter 8 of this code. 308.4.2.5 Kitchen exhaust ducts. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the minimum clearances required by Section 506.3.11 for kitchen exhaust ducts enclosed in a s haft. SECTION MC 309 TEMPERATURE CONTROL 309.1 Space - heating systems. Interior spaces intended for human occupancy shall be provided with active or passive space - heating systems capable of maintaining an indoor temperature of not less than 68°F (20°C) at a point 3 feet (914.4 mm) above floor on the design heating day. The installation of portable space heaters shall not be used to achieve compliance with this section . Refer to Section 1204 of the New York City Building Code . Exception: Interior s paces where the primary purpose is not associated with human comfort. SECTION MC 310 EXPLOSION CONTROL 310.1 Required. Structures occupied for purposes involving explosion hazards shall be provided with explosion control in compliance with rules of the Commissioner of the Fire Department. Explosion control systems shall be designed and installed in accordance with the New York City Fire Code . SECTION MC 311 SMOKE AND HEAT VENTS 311.1 Required. Approved smoke and heat vents shall be installed in the roofs of one - story buildings where required by the New York City Fire Code . Smoke and heat vents shall be designed and installe d in accordance with the New York City Fire Code . SECTION MC 312 HEATING AND COOLING LOAD CALCULATIONS 312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the procedures described in the ASHRAE ACCA Standard 183. Alternatively, design loads shall be determined by an appro ved equivalent computation procedure, using the design parameters specified in the New York City Energy Conservation Code . Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall also comply with the requir ements of Section 1204 of the New York City Building Code . SECTION MC 313 NOISE CONTROL AND VIBRATION ISOLATION REQUIREMENTS 313.1 General. Interior and exterior mechanical equipment and systems shall comply with the provisions of this sec- tion. GENERAL REGULATIONS 313.2 Noise from exterior mechanical equipment. Mechanical equipment located outside of the building in a yard or court or on a roof, or located inside a building but open to the exterior of the building, shall comply with the requirements of Sections 313.2.1 and 313 .2.2. 313.2.1 Design and installation. The applicant shall select and design any such exterior mechanical equipment in order to achieve compliance with the applicable requirements of Sections 24 - 218, 24 - 227, 24 - 228 and 24 - 232 of the Administrative Code , al so known as the New York City Noise Control Code , in accordance with generally acceptable engineering practices. 313.2.2 Operation. The operation of such exterior mechanical equipment shall comply with any applicable re- quirements of Sections 24 - 218, 24 - 227 , 24 - 228 and 24 - 232 of the New York City Noise Control Code , as enforced by the Department of Environmental Protection. 313.3 Minimum structure - borne noise and vibration isolation requirements. All isolators shall comply with the requirements of Sections 3 13.3.1 through 313.3.10. Where vibration isolation of equipment and appliances is em- ployed, supplemental restraint shall be used to accomplish the support and restraint. Exception: When specified by the registered design professional, the requirements of S ections 313.3.1 through 313.3.10 may be modified provided that the equipment, appliances, and supports shall be designed and installed so that continuous or intermittent vibration transmitted to structural slabs shall not exceed the following values be- twee n 8 Hz and 80 Hz on the structural slab in the affected occupancy space: 1. Group E, I or R occupancies: 5,600 microinches (142.4 um) per second. 2. All other occupancies: 16,000 microinches (406.4 um) per second. For the purposes of this exception, transmitted vibration shall be in accordance with the following parameters: 1. The peak third - octave band RMS velocity measurements. 2. The method shall be in accordance with ANSI/ASA S2.71. 313.3.1 Boiler rooms. Boilers, boiler breeching, and b oiler piping shall be isolated in accordance with the appli- cable requirements of Sections 313.3.1.1 and 313.3.1.2. 313.3.1.1 Boilers. All boilers supported on floors directly above a story having dwelling units shall be sup- ported on resilient isolators hav ing a minimum static deflection of 1 inch (25.4 mm). The isolators shall be installed directly under the structural frame of the boiler. 313.3.1.2 Boiler breeching and piping. When boilers are equipped with mechanical draft fans, the boiler breeching and p iping that are supported from or on slabs, floors or walls that are contiguous to the dwelling unit shall be supported for a distance of 50 pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of 1 inch (25.4 mm). 313.3.2 Refuse charging chutes. Metal chutes, chute supports, and chute bracing shall be installed in accordance with Section 313.3.2.1. Masonry chutes must comply with Section 313.3.2.2. 313.3.2.1 Metal chutes. Metal chutes, metal chute supports, and /or metal chute bracing shall be free of direct contact with the shaft enclosure and the openings provided in the floor construction. Metal chutes shall be resiliently supported at each structural support location. Isolators shall provide a minimum static deflection of 0.30 inches (7.62 mm). All chutes shall be plumb. 313.3.2.2 Masonry chutes. The interior chute wall shall be plumb and without obstructions for the full height of the shaft and shall have a smooth interior finish. 313.3.3 Piping. Equipment pi ping shall be installed as follows: 1. Metal piping connected to power driven equipment shall be resiliently supported from or on the building structure for a distance of 50 pipe diameters from the power driven equipment. The resilient isolators shall have a minimum static deflection of 1 inch (25.4 mm) for all piping with a 4 inch (101.6 mm) or larger in actual outside diameter and 1 / 2 inch (12.7 mm) for piping with less than 4 inches (101.6 mm) in actual outside diameter. Piping connected to fluid pressur e - reducing valves shall be resiliently isolated for a distance of 50 pipe diameters from pressure - reducing valves and isolators shall provide a minimum static deflection of 1 / 2 inch (12.7 mm). GENERAL REGULATIONS 2. Equipment such as heat exchangers, absorption refrigeration machines, or similar equipment, that is located on any floor or roof other than a floor on grade, and that is not power driven but is connected by metal piping to power driven equipment, shall be resiliently supported from or on the building structure, for a distance of 50 pipe diameters from the power driven equipment. The resilient supports shall be vibration isolators having a minimum static deflection of 1 inch (25.4 mm) and shall incorporate a pproved resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.4 Fans. All fan equipment with motors in excess of 1 / 2 horsepower (0.37 kW), located on any roof or floor other than a floor on grade shall be mounted on or from vibration isolat ors. Fan equipment with motor drives separated from the fan equipment shall be supported on an isolated integral rigid structural base supporting both the fan and motor. Fan equipment with motor drives supported from the fan equipment shall be mounted dire ctly on vibration isolators. Each isolator shall have provision for leveling. Isolators shall incorporate resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). The vibration isolators shall provide a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum deflection of 2 inches ( 50.8 mm). Fans and compressors assembled in unitary containers may meet this requirement with isolators internal to the container providing the isolators meet the above minimum isolator efficiencies. 313.3.5 Pumps. All pumps of 3 horsepower (2.24 kW) or more located on any floor other than a floor on grade shall be supported on vibration isolators having a minimum isolation efficiency of 90 percent at the lowest dis- turbing frequency. Each isolator shal l incorporate a leveling device and a resilient pad having a minimum thick- ness of 1 / 4 inch (6.4 mm). 313.3.6 Compressors. Compressors and drives located on a floor other than a floor on grade shall be mounted on vibration isolators having a minimum isolati on efficiency of 90 percent at the lowest disturbing frequency. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.7 Cooling towers and fluid coolers. All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided. ‡‡‡ 313.3.8 Evaporative condensers. Evaporative and air - cooled condensers located on a r oof or floor other than a floor on grade shall be mounted on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling dev ice and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided on evaporative condensers. 313.3.9 Duct connections to fans. Flexible connections shall be installed between fan equipment and connecting d uctwork. 313.3.10 Ceiling suspended packaged HVAC units with compressors. Equipment such as heat pumps, air - conditioning units, or similar equipment, that is suspended from a structure shall be resiliently supported from or on the building structure. Vibra tion isolators shall have a minimum isolation efficiency of 90 percent at the lowest disturbing frequency. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm). GENERAL REGULATIONS 308.4.2.2 Masonry chimneys. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry chimne ys as specified in the New York City Building Code and Chapter 8 of this code. 308.4.2.3 Chimney connector pass - throughs. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for chimney connect or pass - throughs as specified in Sec- tion 803.10.4. 308.4.2.4 Masonry fireplaces. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry fireplaces as specified in the New York City Bui lding Code and Chapter 8 of this code. 308.4.2.5 Kitchen exhaust ducts. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the minimum clearances required by Section 506.3.11 for kitchen exhaust ducts enclosed in a s haft. SECTION MC 309 TEMPERATURE CONTROL 309.1 Space - heating systems. Interior spaces intended for human occupancy shall be provided with active or passive space - heating systems capable of maintaining an indoor temperature of not less than 68°F (20°C) at a point 3 feet (914.4 mm) above floor on the design heating day. The installation of portable space heaters shall not be used to achieve compliance with this section . Refer to Section 1204 of the New York City Building Code . Exception: Interior s paces where the primary purpose is not associated with human comfort. SECTION MC 310 EXPLOSION CONTROL 310.1 Required. Structures occupied for purposes involving explosion hazards shall be provided with explosion control in compliance with rules of the Commissioner of the Fire Department. Explosion control systems shall be designed and installed in accordance with the New York City Fire Code . SECTION MC 311 SMOKE AND HEAT VENTS 311.1 Required. Approved smoke and heat vents shall be installed in the roofs of one - story buildings where required by the New York City Fire Code . Smoke and heat vents shall be designed and installe d in accordance with the New York City Fire Code . SECTION MC 312 HEATING AND COOLING LOAD CALCULATIONS 312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the procedures described in the ASHRAE ACCA Standard 183. Alternatively, design loads shall be determined by an appro ved equivalent computation procedure, using the design parameters specified in the New York City Energy Conservation Code . Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall also comply with the requir ements of Section 1204 of the New York City Building Code . SECTION MC 313 NOISE CONTROL AND VIBRATION ISOLATION REQUIREMENTS 313.1 General. Interior and exterior mechanical equipment and systems shall comply with the provisions of this sec- tion. GENERAL REGULATIONS 313.2 Noise from exterior mechanical equipment. Mechanical equipment located outside of the building in a yard or court or on a roof, or located inside a building but open to the exterior of the building, shall comply with the requirements of Sections 313.2.1 and 313 .2.2. 313.2.1 Design and installation. The applicant shall select and design any such exterior mechanical equipment in order to achieve compliance with the applicable requirements of Sections 24 - 218, 24 - 227, 24 - 228 and 24 - 232 of the Administrative Code , al so known as the New York City Noise Control Code , in accordance with generally acceptable engineering practices. 313.2.2 Operation. The operation of such exterior mechanical equipment shall comply with any applicable re- quirements of Sections 24 - 218, 24 - 227 , 24 - 228 and 24 - 232 of the New York City Noise Control Code , as enforced by the Department of Environmental Protection. 313.3 Minimum structure - borne noise and vibration isolation requirements. All isolators shall comply with the requirements of Sections 3 13.3.1 through 313.3.10. Where vibration isolation of equipment and appliances is em- ployed, supplemental restraint shall be used to accomplish the support and restraint. Exception: When specified by the registered design professional, the requirements of S ections 313.3.1 through 313.3.10 may be modified provided that the equipment, appliances, and supports shall be designed and installed so that continuous or intermittent vibration transmitted to structural slabs shall not exceed the following values be- twee n 8 Hz and 80 Hz on the structural slab in the affected occupancy space: 1. Group E, I or R occupancies: 5,600 microinches (142.4 um) per second. 2. All other occupancies: 16,000 microinches (406.4 um) per second. For the purposes of this exception, transmitted vibration shall be in accordance with the following parameters: 1. The peak third - octave band RMS velocity measurements. 2. The method shall be in accordance with ANSI/ASA S2.71. 313.3.1 Boiler rooms. Boilers, boiler breeching, and b oiler piping shall be isolated in accordance with the appli- cable requirements of Sections 313.3.1.1 and 313.3.1.2. 313.3.1.1 Boilers. All boilers supported on floors directly above a story having dwelling units shall be sup- ported on resilient isolators hav ing a minimum static deflection of 1 inch (25.4 mm). The isolators shall be installed directly under the structural frame of the boiler. 313.3.1.2 Boiler breeching and piping. When boilers are equipped with mechanical draft fans, the boiler breeching and p iping that are supported from or on slabs, floors or walls that are contiguous to the dwelling unit shall be supported for a distance of 50 pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of 1 inch (25.4 mm). 313.3.2 Refuse charging chutes. Metal chutes, chute supports, and chute bracing shall be installed in accordance with Section 313.3.2.1. Masonry chutes must comply with Section 313.3.2.2. 313.3.2.1 Metal chutes. Metal chutes, metal chute supports, and /or metal chute bracing shall be free of direct contact with the shaft enclosure and the openings provided in the floor construction. Metal chutes shall be resiliently supported at each structural support location. Isolators shall provide a minimum static deflection of 0.30 inches (7.62 mm). All chutes shall be plumb. 313.3.2.2 Masonry chutes. The interior chute wall shall be plumb and without obstructions for the full height of the shaft and shall have a smooth interior finish. 313.3.3 Piping. Equipment pi ping shall be installed as follows: 1. Metal piping connected to power driven equipment shall be resiliently supported from or on the building structure for a distance of 50 pipe diameters from the power driven equipment. The resilient isolators shall have a minimum static deflection of 1 inch (25.4 mm) for all piping with a 4 inch (101.6 mm) or larger in actual outside diameter and 1 / 2 inch (12.7 mm) for piping with less than 4 inches (101.6 mm) in actual outside diameter. Piping connected to fluid pressur e - reducing valves shall be resiliently isolated for a distance of 50 pipe diameters from pressure - reducing valves and isolators shall provide a minimum static deflection of 1 / 2 inch (12.7 mm). GENERAL REGULATIONS 2. Equipment such as heat exchangers, absorption refrigeration machines, or similar equipment, that is located on any floor or roof other than a floor on grade, and that is not power driven but is connected by metal piping to power driven equipment, shall be resiliently supported from or on the building structure, for a distance of 50 pipe diameters from the power driven equipment. The resilient supports shall be vibration isolators having a minimum static deflection of 1 inch (25.4 mm) and shall incorporate a pproved resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.4 Fans. All fan equipment with motors in excess of 1 / 2 horsepower (0.37 kW), located on any roof or floor other than a floor on grade shall be mounted on or from vibration isolat ors. Fan equipment with motor drives separated from the fan equipment shall be supported on an isolated integral rigid structural base supporting both the fan and motor. Fan equipment with motor drives supported from the fan equipment shall be mounted dire ctly on vibration isolators. Each isolator shall have provision for leveling. Isolators shall incorporate resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). The vibration isolators shall provide a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum deflection of 2 inches ( 50.8 mm). Fans and compressors assembled in unitary containers may meet this requirement with isolators internal to the container providing the isolators meet the above minimum isolator efficiencies. 313.3.5 Pumps. All pumps of 3 horsepower (2.24 kW) or more located on any floor other than a floor on grade shall be supported on vibration isolators having a minimum isolation efficiency of 90 percent at the lowest dis- turbing frequency. Each isolator shal l incorporate a leveling device and a resilient pad having a minimum thick- ness of 1 / 4 inch (6.4 mm). 313.3.6 Compressors. Compressors and drives located on a floor other than a floor on grade shall be mounted on vibration isolators having a minimum isolati on efficiency of 90 percent at the lowest disturbing frequency. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.7 Cooling towers and fluid coolers. All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided. ‡‡‡ 313.3.8 Evaporative condensers. Evaporative and air - cooled condensers located on a r oof or floor other than a floor on grade shall be mounted on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling dev ice and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided on evaporative condensers. 313.3.9 Duct connections to fans. Flexible connections shall be installed between fan equipment and connecting d uctwork. 313.3.10 Ceiling suspended packaged HVAC units with compressors. Equipment such as heat pumps, air - conditioning units, or similar equipment, that is suspended from a structure shall be resiliently supported from or on the building structure. Vibra tion isolators shall have a minimum isolation efficiency of 90 percent at the lowest disturbing frequency. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm). GENERAL REGULATIONS 308.4.2.2 Masonry chimneys. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry chimne ys as specified in the New York City Building Code and Chapter 8 of this code. 308.4.2.3 Chimney connector pass - throughs. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for chimney connect or pass - throughs as specified in Sec- tion 803.10.4. 308.4.2.4 Masonry fireplaces. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry fireplaces as specified in the New York City Bui lding Code and Chapter 8 of this code. 308.4.2.5 Kitchen exhaust ducts. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the minimum clearances required by Section 506.3.11 for kitchen exhaust ducts enclosed in a s haft. SECTION MC 309 TEMPERATURE CONTROL 309.1 Space - heating systems. Interior spaces intended for human occupancy shall be provided with active or passive space - heating systems capable of maintaining an indoor temperature of not less than 68°F (20°C) at a point 3 feet (914.4 mm) above floor on the design heating day. The installation of portable space heaters shall not be used to achieve compliance with this section . Refer to Section 1204 of the New York City Building Code . Exception: Interior s paces where the primary purpose is not associated with human comfort. SECTION MC 310 EXPLOSION CONTROL 310.1 Required. Structures occupied for purposes involving explosion hazards shall be provided with explosion control in compliance with rules of the Commissioner of the Fire Department. Explosion control systems shall be designed and installed in accordance with the New York City Fire Code . SECTION MC 311 SMOKE AND HEAT VENTS 311.1 Required. Approved smoke and heat vents shall be installed in the roofs of one - story buildings where required by the New York City Fire Code . Smoke and heat vents shall be designed and installe d in accordance with the New York City Fire Code . SECTION MC 312 HEATING AND COOLING LOAD CALCULATIONS 312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the procedures described in the ASHRAE ACCA Standard 183. Alternatively, design loads shall be determined by an appro ved equivalent computation procedure, using the design parameters specified in the New York City Energy Conservation Code . Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall also comply with the requir ements of Section 1204 of the New York City Building Code . SECTION MC 313 NOISE CONTROL AND VIBRATION ISOLATION REQUIREMENTS 313.1 General. Interior and exterior mechanical equipment and systems shall comply with the provisions of this sec- tion. GENERAL REGULATIONS 313.2 Noise from exterior mechanical equipment. Mechanical equipment located outside of the building in a yard or court or on a roof, or located inside a building but open to the exterior of the building, shall comply with the requirements of Sections 313.2.1 and 313 .2.2. 313.2.1 Design and installation. The applicant shall select and design any such exterior mechanical equipment in order to achieve compliance with the applicable requirements of Sections 24 - 218, 24 - 227, 24 - 228 and 24 - 232 of the Administrative Code , al so known as the New York City Noise Control Code , in accordance with generally acceptable engineering practices. 313.2.2 Operation. The operation of such exterior mechanical equipment shall comply with any applicable re- quirements of Sections 24 - 218, 24 - 227 , 24 - 228 and 24 - 232 of the New York City Noise Control Code , as enforced by the Department of Environmental Protection. 313.3 Minimum structure - borne noise and vibration isolation requirements. All isolators shall comply with the requirements of Sections 3 13.3.1 through 313.3.10. Where vibration isolation of equipment and appliances is em- ployed, supplemental restraint shall be used to accomplish the support and restraint. Exception: When specified by the registered design professional, the requirements of S ections 313.3.1 through 313.3.10 may be modified provided that the equipment, appliances, and supports shall be designed and installed so that continuous or intermittent vibration transmitted to structural slabs shall not exceed the following values be- twee n 8 Hz and 80 Hz on the structural slab in the affected occupancy space: 1. Group E, I or R occupancies: 5,600 microinches (142.4 um) per second. 2. All other occupancies: 16,000 microinches (406.4 um) per second. For the purposes of this exception, transmitted vibration shall be in accordance with the following parameters: 1. The peak third - octave band RMS velocity measurements. 2. The method shall be in accordance with ANSI/ASA S2.71. 313.3.1 Boiler rooms. Boilers, boiler breeching, and b oiler piping shall be isolated in accordance with the appli- cable requirements of Sections 313.3.1.1 and 313.3.1.2. 313.3.1.1 Boilers. All boilers supported on floors directly above a story having dwelling units shall be sup- ported on resilient isolators hav ing a minimum static deflection of 1 inch (25.4 mm). The isolators shall be installed directly under the structural frame of the boiler. 313.3.1.2 Boiler breeching and piping. When boilers are equipped with mechanical draft fans, the boiler breeching and p iping that are supported from or on slabs, floors or walls that are contiguous to the dwelling unit shall be supported for a distance of 50 pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of 1 inch (25.4 mm). 313.3.2 Refuse charging chutes. Metal chutes, chute supports, and chute bracing shall be installed in accordance with Section 313.3.2.1. Masonry chutes must comply with Section 313.3.2.2. 313.3.2.1 Metal chutes. Metal chutes, metal chute supports, and /or metal chute bracing shall be free of direct contact with the shaft enclosure and the openings provided in the floor construction. Metal chutes shall be resiliently supported at each structural support location. Isolators shall provide a minimum static deflection of 0.30 inches (7.62 mm). All chutes shall be plumb. 313.3.2.2 Masonry chutes. The interior chute wall shall be plumb and without obstructions for the full height of the shaft and shall have a smooth interior finish. 313.3.3 Piping. Equipment pi ping shall be installed as follows: 1. Metal piping connected to power driven equipment shall be resiliently supported from or on the building structure for a distance of 50 pipe diameters from the power driven equipment. The resilient isolators shall have a minimum static deflection of 1 inch (25.4 mm) for all piping with a 4 inch (101.6 mm) or larger in actual outside diameter and 1 / 2 inch (12.7 mm) for piping with less than 4 inches (101.6 mm) in actual outside diameter. Piping connected to fluid pressur e - reducing valves shall be resiliently isolated for a distance of 50 pipe diameters from pressure - reducing valves and isolators shall provide a minimum static deflection of 1 / 2 inch (12.7 mm). GENERAL REGULATIONS 2. Equipment such as heat exchangers, absorption refrigeration machines, or similar equipment, that is located on any floor or roof other than a floor on grade, and that is not power driven but is connected by metal piping to power driven equipment, shall be resiliently supported from or on the building structure, for a distance of 50 pipe diameters from the power driven equipment. The resilient supports shall be vibration isolators having a minimum static deflection of 1 inch (25.4 mm) and shall incorporate a pproved resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.4 Fans. All fan equipment with motors in excess of 1 / 2 horsepower (0.37 kW), located on any roof or floor other than a floor on grade shall be mounted on or from vibration isolat ors. Fan equipment with motor drives separated from the fan equipment shall be supported on an isolated integral rigid structural base supporting both the fan and motor. Fan equipment with motor drives supported from the fan equipment shall be mounted dire ctly on vibration isolators. Each isolator shall have provision for leveling. Isolators shall incorporate resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). The vibration isolators shall provide a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum deflection of 2 inches ( 50.8 mm). Fans and compressors assembled in unitary containers may meet this requirement with isolators internal to the container providing the isolators meet the above minimum isolator efficiencies. 313.3.5 Pumps. All pumps of 3 horsepower (2.24 kW) or more located on any floor other than a floor on grade shall be supported on vibration isolators having a minimum isolation efficiency of 90 percent at the lowest dis- turbing frequency. Each isolator shal l incorporate a leveling device and a resilient pad having a minimum thick- ness of 1 / 4 inch (6.4 mm). 313.3.6 Compressors. Compressors and drives located on a floor other than a floor on grade shall be mounted on vibration isolators having a minimum isolati on efficiency of 90 percent at the lowest disturbing frequency. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.7 Cooling towers and fluid coolers. All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided. ‡‡‡ 313.3.8 Evaporative condensers. Evaporative and air - cooled condensers located on a r oof or floor other than a floor on grade shall be mounted on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling dev ice and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided on evaporative condensers. 313.3.9 Duct connections to fans. Flexible connections shall be installed between fan equipment and connecting d uctwork. 313.3.10 Ceiling suspended packaged HVAC units with compressors. Equipment such as heat pumps, air - conditioning units, or similar equipment, that is suspended from a structure shall be resiliently supported from or on the building structure. Vibra tion isolators shall have a minimum isolation efficiency of 90 percent at the lowest disturbing frequency. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm). GENERAL REGULATIONS 308.4.2.2 Masonry chimneys. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry chimne ys as specified in the New York City Building Code and Chapter 8 of this code. 308.4.2.3 Chimney connector pass - throughs. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for chimney connect or pass - throughs as specified in Sec- tion 803.10.4. 308.4.2.4 Masonry fireplaces. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry fireplaces as specified in the New York City Bui lding Code and Chapter 8 of this code. 308.4.2.5 Kitchen exhaust ducts. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the minimum clearances required by Section 506.3.11 for kitchen exhaust ducts enclosed in a s haft. SECTION MC 309 TEMPERATURE CONTROL 309.1 Space - heating systems. Interior spaces intended for human occupancy shall be provided with active or passive space - heating systems capable of maintaining an indoor temperature of not less than 68°F (20°C) at a point 3 feet (914.4 mm) above floor on the design heating day. The installation of portable space heaters shall not be used to achieve compliance with this section . Refer to Section 1204 of the New York City Building Code . Exception: Interior s paces where the primary purpose is not associated with human comfort. SECTION MC 310 EXPLOSION CONTROL 310.1 Required. Structures occupied for purposes involving explosion hazards shall be provided with explosion control in compliance with rules of the Commissioner of the Fire Department. Explosion control systems shall be designed and installed in accordance with the New York City Fire Code . SECTION MC 311 SMOKE AND HEAT VENTS 311.1 Required. Approved smoke and heat vents shall be installed in the roofs of one - story buildings where required by the New York City Fire Code . Smoke and heat vents shall be designed and installe d in accordance with the New York City Fire Code . SECTION MC 312 HEATING AND COOLING LOAD CALCULATIONS 312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the procedures described in the ASHRAE ACCA Standard 183. Alternatively, design loads shall be determined by an appro ved equivalent computation procedure, using the design parameters specified in the New York City Energy Conservation Code . Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall also comply with the requir ements of Section 1204 of the New York City Building Code . SECTION MC 313 NOISE CONTROL AND VIBRATION ISOLATION REQUIREMENTS 313.1 General. Interior and exterior mechanical equipment and systems shall comply with the provisions of this sec- tion. GENERAL REGULATIONS 313.2 Noise from exterior mechanical equipment. Mechanical equipment located outside of the building in a yard or court or on a roof, or located inside a building but open to the exterior of the building, shall comply with the requirements of Sections 313.2.1 and 313 .2.2. 313.2.1 Design and installation. The applicant shall select and design any such exterior mechanical equipment in order to achieve compliance with the applicable requirements of Sections 24 - 218, 24 - 227, 24 - 228 and 24 - 232 of the Administrative Code , al so known as the New York City Noise Control Code , in accordance with generally acceptable engineering practices. 313.2.2 Operation. The operation of such exterior mechanical equipment shall comply with any applicable re- quirements of Sections 24 - 218, 24 - 227 , 24 - 228 and 24 - 232 of the New York City Noise Control Code , as enforced by the Department of Environmental Protection. 313.3 Minimum structure - borne noise and vibration isolation requirements. All isolators shall comply with the requirements of Sections 3 13.3.1 through 313.3.10. Where vibration isolation of equipment and appliances is em- ployed, supplemental restraint shall be used to accomplish the support and restraint. Exception: When specified by the registered design professional, the requirements of S ections 313.3.1 through 313.3.10 may be modified provided that the equipment, appliances, and supports shall be designed and installed so that continuous or intermittent vibration transmitted to structural slabs shall not exceed the following values be- twee n 8 Hz and 80 Hz on the structural slab in the affected occupancy space: 1. Group E, I or R occupancies: 5,600 microinches (142.4 um) per second. 2. All other occupancies: 16,000 microinches (406.4 um) per second. For the purposes of this exception, transmitted vibration shall be in accordance with the following parameters: 1. The peak third - octave band RMS velocity measurements. 2. The method shall be in accordance with ANSI/ASA S2.71. 313.3.1 Boiler rooms. Boilers, boiler breeching, and b oiler piping shall be isolated in accordance with the appli- cable requirements of Sections 313.3.1.1 and 313.3.1.2. 313.3.1.1 Boilers. All boilers supported on floors directly above a story having dwelling units shall be sup- ported on resilient isolators hav ing a minimum static deflection of 1 inch (25.4 mm). The isolators shall be installed directly under the structural frame of the boiler. 313.3.1.2 Boiler breeching and piping. When boilers are equipped with mechanical draft fans, the boiler breeching and p iping that are supported from or on slabs, floors or walls that are contiguous to the dwelling unit shall be supported for a distance of 50 pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of 1 inch (25.4 mm). 313.3.2 Refuse charging chutes. Metal chutes, chute supports, and chute bracing shall be installed in accordance with Section 313.3.2.1. Masonry chutes must comply with Section 313.3.2.2. 313.3.2.1 Metal chutes. Metal chutes, metal chute supports, and /or metal chute bracing shall be free of direct contact with the shaft enclosure and the openings provided in the floor construction. Metal chutes shall be resiliently supported at each structural support location. Isolators shall provide a minimum static deflection of 0.30 inches (7.62 mm). All chutes shall be plumb. 313.3.2.2 Masonry chutes. The interior chute wall shall be plumb and without obstructions for the full height of the shaft and shall have a smooth interior finish. 313.3.3 Piping. Equipment pi ping shall be installed as follows: 1. Metal piping connected to power driven equipment shall be resiliently supported from or on the building structure for a distance of 50 pipe diameters from the power driven equipment. The resilient isolators shall have a minimum static deflection of 1 inch (25.4 mm) for all piping with a 4 inch (101.6 mm) or larger in actual outside diameter and 1 / 2 inch (12.7 mm) for piping with less than 4 inches (101.6 mm) in actual outside diameter. Piping connected to fluid pressur e - reducing valves shall be resiliently isolated for a distance of 50 pipe diameters from pressure - reducing valves and isolators shall provide a minimum static deflection of 1 / 2 inch (12.7 mm). GENERAL REGULATIONS 2. Equipment such as heat exchangers, absorption refrigeration machines, or similar equipment, that is located on any floor or roof other than a floor on grade, and that is not power driven but is connected by metal piping to power driven equipment, shall be resiliently supported from or on the building structure, for a distance of 50 pipe diameters from the power driven equipment. The resilient supports shall be vibration isolators having a minimum static deflection of 1 inch (25.4 mm) and shall incorporate a pproved resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.4 Fans. All fan equipment with motors in excess of 1 / 2 horsepower (0.37 kW), located on any roof or floor other than a floor on grade shall be mounted on or from vibration isolat ors. Fan equipment with motor drives separated from the fan equipment shall be supported on an isolated integral rigid structural base supporting both the fan and motor. Fan equipment with motor drives supported from the fan equipment shall be mounted dire ctly on vibration isolators. Each isolator shall have provision for leveling. Isolators shall incorporate resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). The vibration isolators shall provide a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum deflection of 2 inches ( 50.8 mm). Fans and compressors assembled in unitary containers may meet this requirement with isolators internal to the container providing the isolators meet the above minimum isolator efficiencies. 313.3.5 Pumps. All pumps of 3 horsepower (2.24 kW) or more located on any floor other than a floor on grade shall be supported on vibration isolators having a minimum isolation efficiency of 90 percent at the lowest dis- turbing frequency. Each isolator shal l incorporate a leveling device and a resilient pad having a minimum thick- ness of 1 / 4 inch (6.4 mm). 313.3.6 Compressors. Compressors and drives located on a floor other than a floor on grade shall be mounted on vibration isolators having a minimum isolati on efficiency of 90 percent at the lowest disturbing frequency. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.7 Cooling towers and fluid coolers. All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided. ‡‡‡ 313.3.8 Evaporative condensers. Evaporative and air - cooled condensers located on a r oof or floor other than a floor on grade shall be mounted on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling dev ice and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided on evaporative condensers. 313.3.9 Duct connections to fans. Flexible connections shall be installed between fan equipment and connecting d uctwork. 313.3.10 Ceiling suspended packaged HVAC units with compressors. Equipment such as heat pumps, air - conditioning units, or similar equipment, that is suspended from a structure shall be resiliently supported from or on the building structure. Vibra tion isolators shall have a minimum isolation efficiency of 90 percent at the lowest disturbing frequency. ‡‡‡ Chapter 3 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 3 GENERAL REGULATIONS SECTION MC 301 GENERAL 301.1 Scope. This chapter shall govern the approval and installation of all equipment and appliances that comprise parts of the building mechanical systems regulated by this code in accordance with Section 101.2. 301.2 Energy utilization. Heating, ventilating, air - conditioning, and refrigeration systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the New York City Energy Conservation Code. 301.3 Identification. All pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identifi- cation of the manufacturer. 301.4 Plastic pipe, fittings and components. Plastic pipe, fittings a nd components shall be third - party certified. 301.5 Third - party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 301.3. Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. 301.6 Fuel gas appliances and equipment. The approval and installation of fuel gas distribution piping and equip- ment, fuel gas - fired appliances and fuel gas - fired appliance venting systems shall be in accordance with the New York City Fuel Gas Code. 301.7 Listed and labeled. Appliances regulated by this code shall be listed an d labeled for the application in which they are installed. Exception: Listing and labeling of equipment and appliances used for refrigeration shall be in accordance with Section 1101.2. 301.8 Testing of materials. Refer to Section 28 - 113 of the Administrative Code . 301.9 Label information. A permanent factory - applied name - plate (s) shall be affixed to appliances on which shall appear in legible lettering, the manufacturer’s name or trademark , the model number, serial number and the seal or mark of the approved agency. A label shall also include the following: 1. Electrical equipment and appliances: Electrical rating in volts, amperes and motor phase; identification of indi- vidual electrical components in volts, amperes or watts, motor phase; Btu/h ( W) output; and required clearances. 2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating for units having step or automatic modu- lating controls; type of fuel; type of refrigerant; cooling capacity in Btu/h (W); and required clearances. 3. Fuel - burning units: Hourly rating in Btu/h (W); type of fuel approved for use with the appliance; and required clearances. 4. Electric comfort heating appliances: Electric rating in volts, amperes and phase; Btu/h (W) output rating; indi- vidual marking for each electrical component in amperes or watts, volts and phase; and required clearances from combustibles . 301.10 Electrical. Electrical wiring, controls and connections to equipment and appliances regulated by this code shall be in accordance with the Ne w York City Electrical Code. GENERAL REGULATIONS 301.11 Plumbing connections. Potable water supply and building drainage system connections to equipment and appliances regulated by this code shall be in accordance with the New York City Plumbing Code. 301.12 Fuel types. Fuel - fired appliances shall be designed for use with the type of fuel to which they will be connected and the altitude at which they are installed. Appliances that comprise parts of the building mechanical system shall not be converted for the usage of a d ifferent fuel, except where approved and converted in accordance with the man- ufacturer’s instructions. The fuel input rate shall not be increased or decreased beyond the limit rating for the altitude at which the appliance is installed. 301.13 Reserved. 30 1.14 Repair. Defective material or parts shall be replaced or repaired in such a manner so as to preserve the original approval or listing. 301.15 Wind resistance. Mechanical equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the New York City Building Code. 301.16 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall comply with the additional requirem ents of Appendix G of the New York City Building Code. 301.16.1 High - velocity wave action. For buildings in coastal high - hazard areas and coastal A - zones as established in Section G102 of the New York City Building Code , mechanical systems and equipment shall not be mounted on or penetrate through breakaway walls. 301.17 Rodentproofing. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which persons live, sleep or work, or in which feed, food or foodstuffs are stored, prepared, processed, served or sold, shall be constructed to pro tect against the entrance of rodents in accordance with Appendix F of the New York City Building Code . 301.18 Seismic resistance. Where earthquake loads are applicable in accordance with the New York City Building Code , mechanical system supports shall be designed and installed for the seismic forces in accordance with the New York City Building Code . SECTION MC 302 STRUCTURAL SAFETY 302.1 Structural safety. The building or structure shall not be weakened by the installation of mechanical systems. Where flo ors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with th e New York City Building Code. 302.1.1 Loading. Alterations resulting in the addition of loads to any member , such as HVAC equipment and water heaters, shall not be permitted without verification that the members are capable of supporting such additional loading. 302.2 Penetrations of floor/ceiling assemblies and fire - resistance - rated assemblies. Penetrations of floor/ceiling assemblies and assemblies required to have a fire - resistance rating shall be protected in accordance with Chapter 7 of the New York City Building Code and Chapter 6 of this code. 302.3 Cutting, notching and boring in wood framing. The cutting , notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3.5. 302.3.1 Solid non - engineered joist notches and holes. Notches on the ends of the solid, non - engineered joists shall not exceed one - fourth the joist depth. Not ches in the top or bottom of joists shall not exceed one - sixth the depth, shall not be longer than one - third the depth and shall not be located in the middle third of the span. Holes bored in joists shall not be within 2 inches (50.8 mm) of the top or bott om of the joist, and the diameter of any such hole shall not exceed one - third the depth of the joist. Holes bored in the middle third of the span shall be located at the center of the joist depth. Clear distance between holes and notches shall be a minimum of 2 inches (50.8 mm). See Figure 2308.5.8 of the New York City Building Code . GENERAL REGULATIONS ‡‡‡ 302.3.2 Stud cutting and notching. In exterior walls and bearing partitions, wood studs are permitted to be cut or notched to a depth not exceeding 25 percent of the width of the stud. Cutting or notching of studs to a depth not greater than 40 percent of the width of the stud is permitted in nonbearing partitions supporting no loads other than the weight of the partition. See Figure 2308.5. 8 of the New York City Building Code . 302.3.3 Bored holes in studs. Bored holes not greater than 40 percent of the stud width are permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the stud width are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 5 / 8 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut or notch. See Figure 2308.5.8 of the New York City Building Code . 302.3.4 Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, struc- tural glue - laminated members or I - joists are prohibited except where permitted by the manufacturer’s recommen- dations or where the effects of such alterations are specifically considered in the design of the member by a regis- tered design professional. ‡‡‡ 302.3.5 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load - bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1 / 2 inches (38.1 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) nails having a minimum length of 1 1 / 2 inches (38.1 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches (152.4 mm) past the opening. See Figure 2308.5.8 of the New York City Building Code . Exception: When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing additional fastening is not required. 302.4 Trusses. Truss members of any material and components shall not be cut, drilled, notched, spliced or otherwise altered in any way without written concurrence and approval of a registered design p rofessional. 302.5 Cutting, notching and boring in steel framing. The cutting, notching and boring of steel framing members shall comply with Sections 302.5.1 through 302.5.4. 302.5.1 Structural steel framing. The cutting, notching and boring of holes in s tructural steel framing members shall be as prescribed by the registered design professional. 302.5.2 Cold - formed steel framing. Flanges and lips of load - bearing, cold - formed steel framing members shall not be cut or notched. Holes in webs of load - bearing, cold - formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, pene tration spacing or minimum hole edge distance as prescribed by the registered design professional. 302.5.3 Nonstructural cold - formed steel wall framing. Flanges and lips of nonstructural cold - formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1 1 / 2 inches (38.1 mm) in width or 4 inches (101.6 mm) in length, and the holes shall not be spaced less than 24 inches (609.6 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end. 302.5.4 Steel floor and roof decking. Cutting, notching and boring holes in steel floor and roof decking shall be as prescribed by the registered design professional. 302.6 Cutting, notching and coring into concrete. The cutting, notching or coring of concrete must comply with provisions of Chapter 19 of the New York City Building Code and is not permitted without prior approval of the registered design professional. 302.7 Protection of footings. Trenching installed parallel to footings and wa lls shall not extend into the bearing plane of a footing or wall. The upper boundary of the bearing plane is a line that extends downward, at an angle of 34 degrees (1:1.5 slope) from horizontal, from the outside bottom edge of the footing or wall. 302.8 P iping materials exposed within plenums. Piping materials exposed within plenums shall comply with this code. GENERAL REGULATIONS SECTION MC 303 EQUIPMENT AND APPLIANCE LOCATION 303.1 General. Equipment and appliances shall be located as required by this section, specific requ irements elsewhere in this code and the conditions of the equipment and appliance listing. 303.2 Hazardous locations. Appliances shall not be located in a hazardous location unless listed and approved for the specific installation. 303.3 Prohibited locations. Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following e xceptions: Exceptions: This section shall not apply to the following appliances: 1. In rooms other than those used for sleeping purposes, direct - vent appliances that obtain all combustion air directly from the outdoors and are installed in accordance with the conditions of the listing and manufac- turer’s instructions. 2. In rooms other than those used for sleeping purposes, vented room heaters, wall furnaces, vented decorative appliances, vented gas fireplaces, vented gas fireplace heaters and decorative appliances for installation in vented solid fuel - burning fireplaces that are installed in rooms that meet the required volume criteria of Sec- tion 702. 3. In rooms other than those used for sleeping purposes, appliances installed in a dedicated e nclosure in which all combustion air is taken directly from the outdoors, in accordance with Section 703. Access to such enclo- sure shall be through a solid door, weather - stripped in accordance with the exterior door air leakage require- ments of the New York City Energy Conservation Code and equipped with an approved self - closing device. 303.4 Protection from physical damage. Appliances shall not be installed in a location where subject to physical damage, including vehicular impact, unless protected by appro ved barriers meeting the requirements of the New York City Fire Code . 303.5 Indoor locations. Furnaces and boilers installed in closets and alcoves shall be listed for such installation. 303.6 Outdoor locations. Appliances installed in other than indoor locations shall be listed and labeled for outdoor installation. 303.7 Pit locations. Appliances installed in pits or excavations shall not come in direct contact with the surrounding soil. The sides of the pit or excavation shall be held back not le ss than 12 inches (304.8 mm) from the appliance. Where the depth exceeds 12 inches (304.8 mm) below adjoining grade, the walls of the pit or excavation shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (1 01.6 mm) above adjoining grade and shall have sufficient lateral load - bearing capacity to resist collapse. The appliance shall be protected from flooding. 303.8 Elevator shafts. Mechanical systems shall not be located in an elevator shaft. SECTION MC 304 I NSTALLATION 304.1 General. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s instructions and this code. Manufacturer’s instructions shall be availab le on the job site at the time of inspection. 304.2 Conflicts. Where conflicts between this code and the conditions of listing or the manufacturer’s instructions occur, the provisions of this code shall apply. Exception: Where a code provision is less rest rictive than the conditions of the listing of the equipment or appliance or the manufacturer’s instructions, the conditions of the listing and the manufacturer’s instructions shall apply. GENERAL REGULATIONS 304.3 Elevation of ignition source. Equipment and appliances having an ignition source and located in hazardous locations and public garages, private garages, repair garages, automotive motor fuel - dispensing facilities and parking garages shall be elevated such that the source of ignition is not less than 18 inches (457.2 mm) above the floor surface on which the equipment or appliance rests. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be c onsid- ered to be part of the private garage. Exception: Elevation of the ignition source is not required for appliances that are listed as flammable vapor ignition resistant. 304.3.1 Parking garages. Connection of a parking garage with any room in which the re is a fuel - fired appliance shall be by means of a vestibule providing a two - doorway separation, except that a single door is permitted where the sources of ignition in the appliance are elevated in accordance with Section 304.3. Exception: This section s hall not apply to appliance installations complying with Section 304.6. 304.4 Prohibited equipment and appliance location. Equipment and appliances having an ignition source shall not be installed in Group H occupancies or control areas where open use, han dling or dispensing of combustible, flamma- ble or explosive materials occurs. 304.5 Hydrogen generating and refueling operations. Hydrogen generating and refueling operations shall be pro- hibited except as permitted by the Commissioner of the Fire Department. 304.6 Public garages. Appliances located in public garages, motor fueling - dispensing facilities, repair garages or other areas frequented by motor vehicles, shall be installed not less than 8 feet (2438.4 mm) above the floor. Where motor vehicl es are capable of passing under an appliance, the appliance shall be installed at the clearances required by the appliance manufacturer and not less than 1 foot (304.8 mm) higher than the tallest vehicle garage door opening. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with NFPA 30A and Section 304.3 of this code . 304.7 Private garages. Appliances located in private garages and carports shall be installed with a minimum clearance of 6 feet (1828.8 mm) above the floor. Exception: The requirements of this section shall not apply where the appliances are protected from motor vehicle impact and installed in accordance with Section 304.3. 304.8 Construction and protection. Boiler rooms and furnace rooms shall be protected as required by the New York City Building Code. 304.9 Clearances to combustible construction. Heat - producing equipment and appliances shall be installed to main- tain the required clearances to c ombustible construction as specified in the listing and manufacturer’s instructions. Such clearances shall be reduced only in accordance with Section 308. Clearances to combustibles shall include such considerations as door swing, drawer pull, overhead pro jections or shelving and window swing, shutters, coverings and drapes. Devices such as doorstops or limits, closers, drapery ties or guards shall not be used to provide the required clearances. 304.10 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level con- crete slab or other approved material extending not less than 3 inches (76.2 mm) above adjoining grade or shall be suspended not less than 6 inches (152.4 mm) above adjoining grade. Such support shall be in accordance with the manufacturer’s instructions. 304.11 Guards. Guards shall be provided where appliances, equipment, fans or other components that require service and roof hatch openings are located within 10 feet (3048 mm) of a roof e dge or open side of a walking surface and such edge or open side is located more than 30 inches (762 mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762 mm) beyond each end of such appliances, equipment, fans, com ponents and roof hatch openings and the top of the guard shall be located not less than 42 inches (1066.8 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21 - inch - diameter (533.4 mm) sph ere and shall comply with the loading requirements for guards specified in the New York City Building Code . 304.12 Area served. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. GENERAL REGULATIONS 304.13 Rooftop access and obstructions. Equipment and appliances installed on rooftops of buildings shall be in- stalled in accordance with the requirements of the New York City Fire Code regarding rooftop access and obstructions, and shall not obstruct or interfere with firefighting operations or the operation of any doors, windows, fire escapes, or other means of egress or other building components requiring operation or access. SECTION M C 305 PIPING SUPPORT 305.1 General. Mechanical system piping shall be supported in accordance with this section. 305.2 Materials. Pipe hangers and supports shall have sufficient strength to withstand all anticipated static and spec- ified dynamic loading conditions associated with the intended use. Pipe hangers and supports that are in direct contact with piping shall be of materials that are compatible with the piping and that will not promote galvanic action. 305.3 Structural attachment. Hangers and anchors shall be attached to the building structure . Post - installed anchors shall be subject to special inspection in accordance with Section 1705.37 of the New York City Building Code . 305.4 Interval of support. Piping shall be sup ported at distances not exceeding the spacing specified in Table 305.4, or in accordance with ANSI/MSS SP - 58 . TABLE 305.4 PIPING SUPPORT SPACING a PIPING MATERIAL MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum pipe and tubing 10 15 Brass pipe 10 10 Brass tubing, 1 1 / 4 - inch diameter and smaller 6 10 Brass tubing, 1 1 / 2 - inch diameter and larger 10 10 Cast - iron pipe b 5 15 Copper or copper - alloy pipe 12 10 Copper or copper - alloy tubing, 1 1 / 4 - inch diameter and smaller 6 10 Copper or copper - alloy tubing, 1 1 / 2 - inch diameter and larger 10 10 CPVC pipe or tubing, 1 inch and smaller 3 10 c CPVC pipe or tubing, 1 1 / 4 - inch and larger 4 10 c Lead pipe Continuous 4 PB pipe or tubing 2 2 / 3 (32 inches) 4 PE - RT < 1 inches 2 2 / 3 (32 inches) 10 c PE - RT > 1 1 / 4 inches 4 10 c PEX tubing 2 2 / 3 (32 inches) 10 c GENERAL REGULATIONS Polypropylene (PP) pipe or tubing, 1 inch or smaller 2 2 / 3 (32 inches) 10 c Polypropylene (PP) pipe or tubing 1 1 / 4 inches or larger 4 10 c PVC pipe 4 10 c Steel tubing 8 10 Steel pipe 12 15 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. See Section 301.18. b. The maximum horizontal spacing of cast - iron pipe hangers shall be increased. c. Mid - story guide. 305.5 Protection against physical damage. In concealed locations where piping, other than cast - iron or steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches (38.1 mm) from the nearest edge of the me mber, the pipe shall be protected by shield plates. Protective steel shield plates having a mini- mum thickness of 0.0575 inch (1.463 mm) (No. 16 gage) shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 in ches (50.8 mm) above sole plates and below top plates. SECTION MC 306 ACCESS AND SERVICE SPACE 306.1 Access. Appliances, control devices, heat exchangers and HVAC system components that require maintenance shall be accessible for inspection, service, repair and replacement without disabling the function of a fire - resistance - rated assembly or removing permanent construction, other appliances, venting systems or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced. A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Clearance shall also be provided as required by the New York City Electri cal Code . 306.1.1 Central furnaces. Central furnaces within compartments or alcoves shall have a minimum working space clearance of 3 inches (76.2 mm) along the sides, back and top with a total width of the enclosing space being not less than 12 inches (304.8 mm) wider than the furnace. Furnaces having a firebox open to the at mosphere shall have not less than 6 inches (152.4 mm) working space along the front combustion chamber side. Combustion air openings at the rear or side of the compartment shall comply with the requirements of Chapter 7. Exception: This section shall not a pply to replacement appliances installed in existing compartments and al- coves where the working space clearances are in accordance with the equipment or appliance manufacturer’s instructions. 306.2 Appliances in rooms. Rooms containing appliances shall be provided with a door and an unobstructed pas- sageway measuring not less than 36 inches (914.4 mm) wide and 80 inches (2032 mm) high. Exception: Within a dwelling unit, appliances installed in a compartment, alcove, basement or similar space shall be accesse d by an opening or door and an unobstructed passageway measuring not less than 24 inches (609.6 mm) wide and large enough to allow removal of the largest appliance in the space, provided that a level service space of not less than 30 inches (762 mm) deep a nd the height of the appliance, but not less than 30 inches (762 mm), is present at the front or service side of the appliance with the door open. 306.3 Appliances in attics. Attics containing appliances shall be provided with an opening and unobstructed p assage- way large enough to allow removal of the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide and not more than 20 feet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. The passageway shall have continuous solid flooring not less than 24 inches (609.6 mm) wide. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service sid e of the appliance. The clear access opening dimensions shall be not less than 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. GENERAL REGULATIONS Exceptions: 1. The passageway and level service space are not required whe re the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less than 6 feet (1828.8 mm) high and 24 inches (609.6 mm) wide for its entire length, the passageway shall be not great er than 50 feet (15 250 mm) in length. 306.3.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with the New Yor k City Electrical Code . 306.4 Appliances under floors. Under - floor spaces containing appliances shall be provided with an access opening and unobstructed passageway large enough to remove the largest appliance. The passageway shall be not less than 30 inches (762 mm) high and 22 inches (558.8 mm) wide, nor more than 20 f eet (6096 mm) in length measured along the centerline of the passageway from the opening to the appliance. A level service space not less than 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present at the front or service side of the applianc e. If the depth of the passageway or the service space exceeds 12 inches (304.8 mm) below the adjoining grade, the walls of the pas- sageway shall be lined with concrete or masonry. Such concrete or masonry shall extend not less than 4 inches (101.6 mm) abov e the adjoining grade and shall have sufficient lateral - bearing capacity to resist collapse. The clear access opening dimensions shall be not less than 22 inches by 30 inches (558.8 mm by 762 mm), and large enough to allow removal of the largest appliance. Exceptions: 1. The passageway is not required where the level service space is present when the access is open and the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is unobstructed and not less th an 6 feet ( 1828.8 mm) high and 22 inches (558.8 mm) wide for its entire length, the passageway shall not be limited in length. 306.4.1 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle o utlet shall be provided at or near the appliance location in accordance with the New York City Electrical Code . 306.5 Equipment and appliances on roofs or elevated structures. Where equipment or appliances requiring access are located on an elevated struct ure or the roof of a building such that personnel will have to climb higher than 16 feet (4876.8 mm ) above grade, roof or floor level to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not r equire climbing over obstructions greater than 30 inches (762 mm) in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal (33 - percent slope). Such access to the roof or elevated structure and access from the roof o r elevated structure to equipment requiring mainte- nance shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide th e required access shall comply with the following minimum design crite- ria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches (762 mm). 2. Ladders shall have rung spacing not to exceed 12 inches (304.8 mm) on center. The uppermost rung shall be not more than 24 inches (609.6 mm) below the upper edge of the roof hatch, roof or parapet, or equipment access platform, as applicable. 3. Ladders shall have a toe spacing not less than 7 inches (177.8 mm) deep. 4. There shal l be not less than 18 inches (457.2 mm) between rails. 5. Rungs shall have a diameter not less than 0.75 - inch (19 mm) and be capable of withstanding a 300 - pound (136.1 kg) load. 6. Where a cage, well or ladder safety device is prohibited, ladders over 20 feet (6096 mm) in height shall be provided with landing platforms for each 30 feet (9144 mm) of height. Where a cage, well or ladder safety device is not provided, ladders over 20 fe et (6096 mm) in height shall be provided with landing platforms for GENERAL REGULATIONS each 20 feet (6096 mm) of height. Landings shall be capable of withstanding 100 pounds (488.2 kg/m 2 ) per square foot. A guard rail and toeboard shall be provided on all open sides of the l anding. 7. Climbing clearance. The distance from the centerline of the rungs to the nearest permanent object on the climb- ing side of the ladder shall be not less than 30 inches (762 mm) measured perpendicular to the rungs. This distance shall be maintaine d from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches (381 mm) shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed . 8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches (762 mm by 762 mm) centered in front of the ladder. 9. Ladders shall be protected against corrosion by approved means. 10. Service personnel shall have access to ladders at all times. 11. Where ladder extensions are installed, the side rails of through or side - step ladder extensions shall extend 3 1 / 2 feet (1066.8 mm) above the parapets and landings. For through ladder extensions, the rungs shall be omitted from the extensions and shall have not less than 18 inches (457.2 mm) nor more than 24 inches (609.6 mm) of clearance between rails. For side - step or offset fixed ladder sections, at landings, the side rails and rungs shall be carried to the next regular rung beyond or above the 3 1 / 2 feet (1066.8 mm) minimum. Catwalks installed to provide the required access shall be not less than 24 inches (609.6 mm) wide and shall have railings as required for service platforms. Exception: This section shall not apply to Group R - 3 occupancies. 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of three units vertical in 12 units horizontal (25 - percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a level platform shall be provided on each side of the appliance or equipment to which access is required for service , repair or maintenance . The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1066.8 mm) above the platform, shall be constructed so as to prevent the passage of a 21 - inch (533 .4 mm) diameter sphere and shall comply with the loading requirements for guards specified in the New York City Building Code . Access shall not require walking on roofs having a slope greater than four units vertical in 12 units horizontal (33 - percent slope). Where access involves obstructions greater than 30 inches (762 mm) in height, such obstructions shall be provided with la dders installed in accordance with Section 306.5 or stairways installed in accordance with the requirements specified in the New York City Building Code in the path of travel to and from appliances, fans or equipment requiring service. 306.5.2 Electrical r equirements. A receptacle outlet shall be provided at or near the equipment location in ac- cordance with the New York City Electrical Code . SECTION MC 307 CONDENSATE DISPOSAL 307.1 Fuel - burning appliances. Liquid combustion by - products of condensing applian ces shall be collected and dis- charged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s instructions. Con- densate piping shall be of approved corrosion - resistant material in accordance with Section 803 of the New York Ci ty Plumbing Code and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Pi ping shall be configured to permit clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.1.1 Condensate disposal. Condensate from all fuel - burning appliances and associated flues shall be neutral- ized to a pH o f at least 6 and no more than 8 prior to disposal to a sanitary system. 307.2 Evaporators and cooling coils. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.6. GENERAL REGULATIONS Exception: Evaporators and cooling coils that are designed to operate in sensible cooling only and not support condensation shall not be required to meet the requireme nts of this section. 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of disc harge of not less than one - eighth unit vertical in 12 units horizontal (1 - percent slope). Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. 307.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be cast iron, galva- nized steel, copper, cross - linked polyethylene, polyethylene , ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Com- ponents shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 of the New York City Plumbing Code relat ive to the material type. Condensate waste and drain line size shall be not less than 3 / 4 - inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more tha n one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 307.2.2. TABLE 307.2.2 CONDENSATE DRAIN SIZING EQUIPMENT CAPACITY MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration 3 / 4 inch Over 20 tons to 40 tons of refrigeration 1 inch Over 40 tons to 90 tons of refrigeration 1 1 / 4 inches Over 90 tons to 125 tons of re- frigeration 1 1 / 2 inches Over 125 tons to 250 tons of re- frigeration 2 inches For SI:1 inch = 25.4 mm, 1 ton = 3.517 kW. 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where dam- age to any building components could occur as a result of overflow from the equipment primary condensate re- moval system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel - fired appliance that produces condensate: 1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a depth of not less than 1 1 / 2 inches (38.1 mm), shall be not less than 3 inches (76.2 mm) larger than the unit, or the coil dimensions in width and length and shall be constructed of corrosion - resistant material. Metallic pans shall have a thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage ) for galvaniz ed sheet metal pans, 0.0179 inch (0.4546 mm) (No. 26 gage) for stainless steel pans, or 0.0320 inch (0.8128 mm) (No. 20 gage) for aluminum pans. Nonmetallic pans shall have a thickness of not less than 0.0625 inch (1.6 mm). 2. A separate overflow drain li ne shall be connected to the drain pan provided with the equipment. Such over- flow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drai n pan at a higher level than the primary drain connection. GENERAL REGULATIONS 3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a listed water - level detection device that will shut off the equip- ment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section. 4. A listed water - level detection device shall be provided that will shut off the equipment served in t he event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment - supplied drain pan, located at a point higher than the primary drain line connection and below the overflow ri m of such pan. Exceptions: 1. An auxiliary drain protection method shall not be required for fuel - fired appliances that automati- cally shut down operation in the event of a stoppage in the condensate drainage system. 2. An auxiliary drain protection method shall not be required where a suitably sized and located floor drain is provided. 307.2.3.1 Water - level monitoring devices. On down - flow units and all other coils that do not have a secondary drain or provisions to install a secondary or auxiliary drain pan, a water - level monitoring device shall be installed inside the primary drain pan. This device shall shut off the equipment served in the event that the primary drain becomes restricted. Devices installed in the drain line shall not be p ermitted. 307.2.3.2 Appliance, equipment or insulation in pans. Where an appliance, equipment or insulation is sub- ject to water damage when auxiliary drain pans fill, that portion of the appliance, equipment or insulation shall be installed above the rim o f the pans. Supports located inside of the pans to support the appliance or equipment or insulation shall be water resistant and approved. 307.2.4 Traps. Condensate drains shall be trapped as required by the equipment or appliance manufacturer. 307.2.5 Dra in line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut. 307.2.6 Condensate discharge. Where multiple evaporators and/or condensate pumps discharge into the same piping system, it shall be piped to prevent the discharge of condensate from one appliance to another. 307.3 Exceptions. This section applies to permanently installed equipment. Window units and through - the - wall air - conditioning uni ts are exempt from the requirements of this section. SECTION MC 308 CLEARANCE REDUCTION 308.1 Scope. This section shall govern the reduction in required clearances to gypsum board, combustible materials and combustible assemblies for chimneys, vents, kitchen exhaust equipment, mechanical appliances, and mechanical devices and equipment. 308.2 Listed appliances and equipment. The reduction of the required clearances to combustibles for listed and labeled appliances and equipment shall be in accordance w ith the requirements of this section except that such clear- ances shall not be reduced where reduction is specifically prohibited by the terms of the appliance or equipment listing. 308.3 Protective assembly construction and installation. Reduced clearance protective assemblies, including struc- tural and support elements, shall be constructed of noncombustible materials. Spacers utilized to maintain an airspace between the protective assembly and the protected material or assembly shall be noncombustible. Whe re a space between the protective assembly and protected combustible material or assembly is specified, the same space shall be provided around the edges of the protective assembly and the spacers shall be placed so as to allow air circulation by convectio n in such space. Protective assemblies shall not be placed less than 1 inch (25.4 mm) from the mechanical appliances, devices or equipment, regardless of the allowable reduced clearance. 308.4 Allowable reduction. The reduction of required clearances to co mbustible assemblies or combustible materials shall be based on the utilization of a reduced clearance protective assembly in accordance with Section 308.4.1 or 308.4.2. GENERAL REGULATIONS 308.4.1 Labeled assemblies. The allowable clearance reduction shall be based on a redu ced clearance protective assembly that has been tested and bears the label of an approved agency . 308.4.2 Reduction table. The allowable clearance reduction shall be based on one of the methods specified in Table 308.4.2. Where required clearances are not listed in Table 308.4.2, the reduced clearances shall be determined by linear interpolation between the distances listed in the table. Reduced clearances shall not be derived by extrap- olation below the range of the table. TABLE 308.4.2 CLEARANCE REDUCTION METHODS b TYPE OF PROTECTIVE ASSEMBLY a REDUCED CLEARANCE WITH PROTECTION (inches) a Horizontal combustible assemblies located above the heat source Horizontal combustible assemblies located beneath the heat source and all vertical combustible assemblies Required clearance to combustibles without protection (inches) a Required clearance to combustible without protection (inches) a 36 18 9 6 36 18 9 6 Galvanized sheet metal, minimum nominal thickness of 0.0296 inch (No. 22 Gage), mounted on 1 - inch glass fiber or mineral wool batt reinforced with wire on the back, 1 inch off the combustible as- sembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having a 1 - inch airspace between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 Two layers of galvanized sheet metal, minimum nominal thickness of 0.0240 inch (No. 24 Gage ), having 1 inch of fiberglass insulation between layers, spaced 1 inch off the combustible assembly 18 9 5 3 12 6 3 3 0.5 - inch inorganic insulating board, over 1 inch of fiberglass or mineral wool batt, against the combustible assembly 24 12 6 4 18 9 5 3 3.5 - inch brick wall, spaced 1 inch off the combustible wall — — — — 12 6 6 6 3.5 - inch brick wall, against the combustible wall — — — — 24 12 6 5 For SI: 1 inch = 25.4 mm, °C = (°F) - 32)/1.8, 1 pound per cubic foot = 16.02 kg/m 3 , 1.0 Btu • in./(ft 2 • h • °F) = 0.144 W/m 2 • K. a. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum m elting point of 1,500°F. Insulation material utilized as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu • in./(ft 2 • h • °F) or less. Insulation board shall be formed of noncombustible material. b. For limitations on clearance reduction for solid fuel - burning appliances, masonry ch imneys, connector pass - throughs, masonry fireplaces and kitchen ducts, see Sections 308.4.2.1 through 308.4.2.5. 308.4.2.1 Solid fuel - burning appliances. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearance required for solid fuel - burning appliances that are labeled for installation with clearances of 12 inches (304.8 mm) or less. Where appliances are labeled for installation with clearances of greater than 12 inches (304.8 mm), the clearance reduct ion methods of Table 308.4.2 shall not reduce the clear- ance to less than 12 inches (304.8 mm). GENERAL REGULATIONS 308.4.2.2 Masonry chimneys. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry chimne ys as specified in the New York City Building Code and Chapter 8 of this code. 308.4.2.3 Chimney connector pass - throughs. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for chimney connect or pass - throughs as specified in Sec- tion 803.10.4. 308.4.2.4 Masonry fireplaces. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the clearances required for masonry fireplaces as specified in the New York City Bui lding Code and Chapter 8 of this code. 308.4.2.5 Kitchen exhaust ducts. The clearance reduction methods specified in Table 308.4.2 shall not be utilized to reduce the minimum clearances required by Section 506.3.11 for kitchen exhaust ducts enclosed in a s haft. SECTION MC 309 TEMPERATURE CONTROL 309.1 Space - heating systems. Interior spaces intended for human occupancy shall be provided with active or passive space - heating systems capable of maintaining an indoor temperature of not less than 68°F (20°C) at a point 3 feet (914.4 mm) above floor on the design heating day. The installation of portable space heaters shall not be used to achieve compliance with this section . Refer to Section 1204 of the New York City Building Code . Exception: Interior s paces where the primary purpose is not associated with human comfort. SECTION MC 310 EXPLOSION CONTROL 310.1 Required. Structures occupied for purposes involving explosion hazards shall be provided with explosion control in compliance with rules of the Commissioner of the Fire Department. Explosion control systems shall be designed and installed in accordance with the New York City Fire Code . SECTION MC 311 SMOKE AND HEAT VENTS 311.1 Required. Approved smoke and heat vents shall be installed in the roofs of one - story buildings where required by the New York City Fire Code . Smoke and heat vents shall be designed and installe d in accordance with the New York City Fire Code . SECTION MC 312 HEATING AND COOLING LOAD CALCULATIONS 312.1 Load calculations. Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall be determined in accordance with the procedures described in the ASHRAE ACCA Standard 183. Alternatively, design loads shall be determined by an appro ved equivalent computation procedure, using the design parameters specified in the New York City Energy Conservation Code . Heating and cooling system design loads for the purpose of sizing systems, appliances and equipment shall also comply with the requir ements of Section 1204 of the New York City Building Code . SECTION MC 313 NOISE CONTROL AND VIBRATION ISOLATION REQUIREMENTS 313.1 General. Interior and exterior mechanical equipment and systems shall comply with the provisions of this sec- tion. GENERAL REGULATIONS 313.2 Noise from exterior mechanical equipment. Mechanical equipment located outside of the building in a yard or court or on a roof, or located inside a building but open to the exterior of the building, shall comply with the requirements of Sections 313.2.1 and 313 .2.2. 313.2.1 Design and installation. The applicant shall select and design any such exterior mechanical equipment in order to achieve compliance with the applicable requirements of Sections 24 - 218, 24 - 227, 24 - 228 and 24 - 232 of the Administrative Code , al so known as the New York City Noise Control Code , in accordance with generally acceptable engineering practices. 313.2.2 Operation. The operation of such exterior mechanical equipment shall comply with any applicable re- quirements of Sections 24 - 218, 24 - 227 , 24 - 228 and 24 - 232 of the New York City Noise Control Code , as enforced by the Department of Environmental Protection. 313.3 Minimum structure - borne noise and vibration isolation requirements. All isolators shall comply with the requirements of Sections 3 13.3.1 through 313.3.10. Where vibration isolation of equipment and appliances is em- ployed, supplemental restraint shall be used to accomplish the support and restraint. Exception: When specified by the registered design professional, the requirements of S ections 313.3.1 through 313.3.10 may be modified provided that the equipment, appliances, and supports shall be designed and installed so that continuous or intermittent vibration transmitted to structural slabs shall not exceed the following values be- twee n 8 Hz and 80 Hz on the structural slab in the affected occupancy space: 1. Group E, I or R occupancies: 5,600 microinches (142.4 um) per second. 2. All other occupancies: 16,000 microinches (406.4 um) per second. For the purposes of this exception, transmitted vibration shall be in accordance with the following parameters: 1. The peak third - octave band RMS velocity measurements. 2. The method shall be in accordance with ANSI/ASA S2.71. 313.3.1 Boiler rooms. Boilers, boiler breeching, and b oiler piping shall be isolated in accordance with the appli- cable requirements of Sections 313.3.1.1 and 313.3.1.2. 313.3.1.1 Boilers. All boilers supported on floors directly above a story having dwelling units shall be sup- ported on resilient isolators hav ing a minimum static deflection of 1 inch (25.4 mm). The isolators shall be installed directly under the structural frame of the boiler. 313.3.1.2 Boiler breeching and piping. When boilers are equipped with mechanical draft fans, the boiler breeching and p iping that are supported from or on slabs, floors or walls that are contiguous to the dwelling unit shall be supported for a distance of 50 pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of 1 inch (25.4 mm). 313.3.2 Refuse charging chutes. Metal chutes, chute supports, and chute bracing shall be installed in accordance with Section 313.3.2.1. Masonry chutes must comply with Section 313.3.2.2. 313.3.2.1 Metal chutes. Metal chutes, metal chute supports, and /or metal chute bracing shall be free of direct contact with the shaft enclosure and the openings provided in the floor construction. Metal chutes shall be resiliently supported at each structural support location. Isolators shall provide a minimum static deflection of 0.30 inches (7.62 mm). All chutes shall be plumb. 313.3.2.2 Masonry chutes. The interior chute wall shall be plumb and without obstructions for the full height of the shaft and shall have a smooth interior finish. 313.3.3 Piping. Equipment pi ping shall be installed as follows: 1. Metal piping connected to power driven equipment shall be resiliently supported from or on the building structure for a distance of 50 pipe diameters from the power driven equipment. The resilient isolators shall have a minimum static deflection of 1 inch (25.4 mm) for all piping with a 4 inch (101.6 mm) or larger in actual outside diameter and 1 / 2 inch (12.7 mm) for piping with less than 4 inches (101.6 mm) in actual outside diameter. Piping connected to fluid pressur e - reducing valves shall be resiliently isolated for a distance of 50 pipe diameters from pressure - reducing valves and isolators shall provide a minimum static deflection of 1 / 2 inch (12.7 mm). GENERAL REGULATIONS 2. Equipment such as heat exchangers, absorption refrigeration machines, or similar equipment, that is located on any floor or roof other than a floor on grade, and that is not power driven but is connected by metal piping to power driven equipment, shall be resiliently supported from or on the building structure, for a distance of 50 pipe diameters from the power driven equipment. The resilient supports shall be vibration isolators having a minimum static deflection of 1 inch (25.4 mm) and shall incorporate a pproved resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.4 Fans. All fan equipment with motors in excess of 1 / 2 horsepower (0.37 kW), located on any roof or floor other than a floor on grade shall be mounted on or from vibration isolat ors. Fan equipment with motor drives separated from the fan equipment shall be supported on an isolated integral rigid structural base supporting both the fan and motor. Fan equipment with motor drives supported from the fan equipment shall be mounted dire ctly on vibration isolators. Each isolator shall have provision for leveling. Isolators shall incorporate resilient pads having a minimum thickness of 1 / 4 inch (6.4 mm). The vibration isolators shall provide a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum deflection of 2 inches ( 50.8 mm). Fans and compressors assembled in unitary containers may meet this requirement with isolators internal to the container providing the isolators meet the above minimum isolator efficiencies. 313.3.5 Pumps. All pumps of 3 horsepower (2.24 kW) or more located on any floor other than a floor on grade shall be supported on vibration isolators having a minimum isolation efficiency of 90 percent at the lowest dis- turbing frequency. Each isolator shal l incorporate a leveling device and a resilient pad having a minimum thick- ness of 1 / 4 inch (6.4 mm). 313.3.6 Compressors. Compressors and drives located on a floor other than a floor on grade shall be mounted on vibration isolators having a minimum isolati on efficiency of 90 percent at the lowest disturbing frequency. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). 313.3.7 Cooling towers and fluid coolers. All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided. ‡‡‡ 313.3.8 Evaporative condensers. Evaporative and air - cooled condensers located on a r oof or floor other than a floor on grade shall be mounted on vibration isolators providing a minimum isolation efficiency of 90 percent at fan rotor rpm with a maximum static deflection of 4 inches (101.6 mm). Each isolator shall incorporate a leveling dev ice and a resilient pad having a minimum thickness of 1 / 4 inch (6.4 mm). Vibration cutoff switches shall be provided on evaporative condensers. 313.3.9 Duct connections to fans. Flexible connections shall be installed between fan equipment and connecting d uctwork. 313.3.10 Ceiling suspended packaged HVAC units with compressors. Equipment such as heat pumps, air - conditioning units, or similar equipment, that is suspended from a structure shall be resiliently supported from or on the building structure. Vibra tion isolators shall have a minimum isolation efficiency of 90 percent at the lowest disturbing frequency.