‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure; such pressures shall not r esult in door opening forces in excess of those indicated in the New York City Building Code and shall not prevent doors from closing as required by the New York City Building Code . The method to convey ventilation air shall be designed and installed in ac cordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. Exception: The minimum required rate of outdoor air may be reduced where the registered design professional demo nstrates that an engineered ventilation system is designed in accordance with ASHRAE 62.1 Indoor Air Quality Procedure . 403.2.1 Recirculation of air. The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that required by Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling unit to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other uses or occupancies . 3. Where mech anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- culation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1. 4. Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation is prohibited. Recircula tion of air that is contained completely within such spaces shall not be prohibited. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving a s makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The requir ed outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor air and local exhaust airflow rates. Buildings that are no t more than three stories in height above grade plane, and that (i) are within Occupancy Group R - 2 or Occupancy Group R - 3, (ii) are adult homes or enriched living housing as described in Section 308.3.1 of the New York City Building Code, within Occupancy Group I - 1 and have 16 occupants or fewer, or (iii) are community residences or intermediate - care facilities as described in Section 308.3.2 of the New York City Building Code, shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.1.2. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. 403.3.1 Reserved. 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed t o have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each habitable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1 . Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ven tilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of non - tobacco hookah establishments, t he ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non - tobacco hookah establishment, the ventilation system serving the space shall be designed to provide v entilation over and above that re- quired by Table 403.3.1.1 in accordance with accepted engineering practice. Exceptions: 1. The occupant load is not required to be determined based on the estimated maximum occupant load rate indi- cated in Table 403.3 .1.1 wh ere approved statistical data documents the accuracy of an alternate anticipated occupant load. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure; such pressures shall not r esult in door opening forces in excess of those indicated in the New York City Building Code and shall not prevent doors from closing as required by the New York City Building Code . The method to convey ventilation air shall be designed and installed in ac cordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. Exception: The minimum required rate of outdoor air may be reduced where the registered design professional demo nstrates that an engineered ventilation system is designed in accordance with ASHRAE 62.1 Indoor Air Quality Procedure . 403.2.1 Recirculation of air. The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that required by Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling unit to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other uses or occupancies . 3. Where mech anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- culation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1. 4. Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation is prohibited. Recircula tion of air that is contained completely within such spaces shall not be prohibited. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving a s makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The requir ed outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor air and local exhaust airflow rates. Buildings that are no t more than three stories in height above grade plane, and that (i) are within Occupancy Group R - 2 or Occupancy Group R - 3, (ii) are adult homes or enriched living housing as described in Section 308.3.1 of the New York City Building Code, within Occupancy Group I - 1 and have 16 occupants or fewer, or (iii) are community residences or intermediate - care facilities as described in Section 308.3.2 of the New York City Building Code, shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.1.2. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. 403.3.1 Reserved. 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed t o have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each habitable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1 . Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ven tilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of non - tobacco hookah establishments, t he ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non - tobacco hookah establishment, the ventilation system serving the space shall be designed to provide v entilation over and above that re- quired by Table 403.3.1.1 in accordance with accepted engineering practice. Exceptions: 1. The occupant load is not required to be determined based on the estimated maximum occupant load rate indi- cated in Table 403.3 .1.1 wh ere approved statistical data documents the accuracy of an alternate anticipated occupant load. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure; such pressures shall not r esult in door opening forces in excess of those indicated in the New York City Building Code and shall not prevent doors from closing as required by the New York City Building Code . The method to convey ventilation air shall be designed and installed in ac cordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. Exception: The minimum required rate of outdoor air may be reduced where the registered design professional demo nstrates that an engineered ventilation system is designed in accordance with ASHRAE 62.1 Indoor Air Quality Procedure . 403.2.1 Recirculation of air. The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that required by Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling unit to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other uses or occupancies . 3. Where mech anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- culation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1. 4. Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation is prohibited. Recircula tion of air that is contained completely within such spaces shall not be prohibited. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving a s makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The requir ed outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor air and local exhaust airflow rates. Buildings that are no t more than three stories in height above grade plane, and that (i) are within Occupancy Group R - 2 or Occupancy Group R - 3, (ii) are adult homes or enriched living housing as described in Section 308.3.1 of the New York City Building Code, within Occupancy Group I - 1 and have 16 occupants or fewer, or (iii) are community residences or intermediate - care facilities as described in Section 308.3.2 of the New York City Building Code, shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.1.2. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. 403.3.1 Reserved. 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed t o have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each habitable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1 . Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ven tilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of non - tobacco hookah establishments, t he ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non - tobacco hookah establishment, the ventilation system serving the space shall be designed to provide v entilation over and above that re- quired by Table 403.3.1.1 in accordance with accepted engineering practice. Exceptions: 1. The occupant load is not required to be determined based on the estimated maximum occupant load rate indi- cated in Table 403.3 .1.1 wh ere approved statistical data documents the accuracy of an alternate anticipated occupant load. VENTILATION 2. The occupant load used in computing the required ventilation shall be the maximum number who will occupy the room or space simultaneously during any 2 - hour p eriod. 3. Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in accordance with ASHRAE 62.1 a nd comply with footnote k of Table 403.3.1.1. These conditions include, but are not limited to: 3.1. Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow requirements will be reset. Note: Examples of measures for estimating such variations include: occupancy scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per person using occupancy sensors such as those based on indoor CO 2 concentrations. 3.2. Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation system airflows and temperatures. 3.3. A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli ng or exhaust air makeup. TABLE 403.3.1.1 MINIMUM VENTILATION RATES OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #/1000 FT 2a PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING ZONE, R p CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE R a CFM/FT 2a EXHAUST AIRFLOW RATE CFM/FT 2a Correctional facilities Booking/waiting 50 7.5 0.06 — Cells without plumbing fixtures 25 5 0.12 — with plumbing fixtures g 25 5 0.12 1.0 Day room 30 5 0.06 — Correctional facilities Dining halls (see food and beverage service) — — — — Guard stations 15 5 0.06 — Dry cleaners, laundries Coin - operated dry cleaner 20 15 — — Coin - operated laundries 20 7.5 0.06 — Commercial dry cleaner l 30 30 — — Commercial laundry 10 25 — — Storage, pick up 30 7.5 0.12 — Education Art classroom g 20 10 0.18 0.7 VENTILATION Auditoriums 150 5 0.06 — Classrooms (ages 5 - 8) 25 10 0.12 — Classrooms (age 9 plus) 35 10 0.12 — Computer lab 25 10 0.12 — Corridors (see public spaces) — — — — Day care (through age 4) 25 10 0.18 — Lecture classroom 65 7.5 0.06 — Lecture hall (fixed seats) 150 7.5 0.06 — Locker/dressing rooms g — — — 0.25 Media center 25 10 0.12 — Multiuse assembly 100 7.5 0.06 — Music/theater/dance 35 10 0.06 — Science laboratories g, k 25 10 0.18 1.0 Sports locker rooms g — — — 0.5 Wood/metal shops g 20 10 0.18 0.5 Food and beverage service Bars, cocktail lounges 100 7.5 0.18 — Cafeteria, fast food 100 7.5 0.18 — Dining rooms 70 7.5 0.18 — Kitchens (cooking) b — — — 0.7 Non - tobacco smoking establishments b 70 60 — — Hotels, motels, resorts and dormitories Bathrooms/toilet — private g — — — 25/50 f Bedroom/living room 10 5 0.06 — Conference/meeting 50 5 0.06 — Dormitory sleeping areas 20 5 0.06 — Gambling casinos 120 7.5 0.18 — Lobbies/prefunction 30 7.5 0.06 — Multipurpose assembly 120 5 0.06 — Laboratories j Biological — — 1.0 1.0 VENTILATION Chemical — — 1.0 1.0 Industrial and nonteaching — — 1.0 1.0 Nonproduction chemical labs — — 1.0 1.0 Offices Conference rooms 50 5 0.06 — Main entry lobbies 10 5 0.06 — Office spaces 5 5 0.06 — Reception areas 30 5 0.06 — Telephone/data entry 60 5 0.06 — Private dwellings, single and multiple Garages, common for multiple units b — — — 0.75 Kitchens and Kitchenettes b , m — — — 25/100 f Living areas c, i Based upon number of bedrooms. First bed- room, 2; each additional bedroom, 1 0.35 ACH but not less than 15 cfm/person — — Toilet rooms and bathrooms g — — — 20/50 f Public spaces Corridors — — 0.06 — Courtrooms 70 5 0.06 — Elevator car — — — 1.0 Legislative chambers 50 5 0.06 — Libraries 10 5 0.12 — Museums (children’s) 40 7.5 0.12 — Museums/galleries 40 7.5 0.06 — Places of religious worship 120 5 0.06 — Public spaces Shower room (per shower head) g — — — 50/20 f Toilet rooms – public g — — — 50/70 e VENTILATION Retail stores, sales floors and showroom floors Dressing rooms — — — 0.25 Mall common areas 40 7.5 0.06 — Sales 15 7.5 0.12 — Shipping and receiving — — 0.12 — Smoking lounges and non - tobacco smoking establishments b 70 60 — — Storage rooms — — 0.12 — Warehouses (see storage) — — — — Specialty shops Automotive motor - fuel dispensing stations b — — — 1.5 Barber 25 7.5 0.06 0.5 Beauty salons (without nail salon services) b 25 20 0.12 0.6 Nail salons b, h 25 20 0.12 0.6 Embalming room b — — — 2.0 Pet shops (animal areas) b 10 7.5 0.18 0.9 Supermarkets 8 7.5 0.06 — Sports and amusement Bowling alleys (seating areas) 40 10 0.12 — Disco/dance floors 100 20 0.06 — Game arcades 20 7.5 0.18 — Gym, stadium, arena (play area) — — 0.30 — Heath club/aerobics room 40 20 0.06 — Health club/weight room 10 20 0.06 — Ice arenas without combustion engines — — 0.30 0.5 Spectator areas 150 7.5 0.06 — ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure; such pressures shall not r esult in door opening forces in excess of those indicated in the New York City Building Code and shall not prevent doors from closing as required by the New York City Building Code . The method to convey ventilation air shall be designed and installed in ac cordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. Exception: The minimum required rate of outdoor air may be reduced where the registered design professional demo nstrates that an engineered ventilation system is designed in accordance with ASHRAE 62.1 Indoor Air Quality Procedure . 403.2.1 Recirculation of air. The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that required by Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling unit to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other uses or occupancies . 3. Where mech anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- culation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1. 4. Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation is prohibited. Recircula tion of air that is contained completely within such spaces shall not be prohibited. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving a s makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The requir ed outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor air and local exhaust airflow rates. Buildings that are no t more than three stories in height above grade plane, and that (i) are within Occupancy Group R - 2 or Occupancy Group R - 3, (ii) are adult homes or enriched living housing as described in Section 308.3.1 of the New York City Building Code, within Occupancy Group I - 1 and have 16 occupants or fewer, or (iii) are community residences or intermediate - care facilities as described in Section 308.3.2 of the New York City Building Code, shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.1.2. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. 403.3.1 Reserved. 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed t o have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each habitable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1 . Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ven tilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of non - tobacco hookah establishments, t he ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non - tobacco hookah establishment, the ventilation system serving the space shall be designed to provide v entilation over and above that re- quired by Table 403.3.1.1 in accordance with accepted engineering practice. Exceptions: 1. The occupant load is not required to be determined based on the estimated maximum occupant load rate indi- cated in Table 403.3 .1.1 wh ere approved statistical data documents the accuracy of an alternate anticipated occupant load. VENTILATION 2. The occupant load used in computing the required ventilation shall be the maximum number who will occupy the room or space simultaneously during any 2 - hour p eriod. 3. Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in accordance with ASHRAE 62.1 a nd comply with footnote k of Table 403.3.1.1. These conditions include, but are not limited to: 3.1. Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow requirements will be reset. Note: Examples of measures for estimating such variations include: occupancy scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per person using occupancy sensors such as those based on indoor CO 2 concentrations. 3.2. Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation system airflows and temperatures. 3.3. A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli ng or exhaust air makeup. TABLE 403.3.1.1 MINIMUM VENTILATION RATES OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #/1000 FT 2a PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING ZONE, R p CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE R a CFM/FT 2a EXHAUST AIRFLOW RATE CFM/FT 2a Correctional facilities Booking/waiting 50 7.5 0.06 — Cells without plumbing fixtures 25 5 0.12 — with plumbing fixtures g 25 5 0.12 1.0 Day room 30 5 0.06 — Correctional facilities Dining halls (see food and beverage service) — — — — Guard stations 15 5 0.06 — Dry cleaners, laundries Coin - operated dry cleaner 20 15 — — Coin - operated laundries 20 7.5 0.06 — Commercial dry cleaner l 30 30 — — Commercial laundry 10 25 — — Storage, pick up 30 7.5 0.12 — Education Art classroom g 20 10 0.18 0.7 VENTILATION Auditoriums 150 5 0.06 — Classrooms (ages 5 - 8) 25 10 0.12 — Classrooms (age 9 plus) 35 10 0.12 — Computer lab 25 10 0.12 — Corridors (see public spaces) — — — — Day care (through age 4) 25 10 0.18 — Lecture classroom 65 7.5 0.06 — Lecture hall (fixed seats) 150 7.5 0.06 — Locker/dressing rooms g — — — 0.25 Media center 25 10 0.12 — Multiuse assembly 100 7.5 0.06 — Music/theater/dance 35 10 0.06 — Science laboratories g, k 25 10 0.18 1.0 Sports locker rooms g — — — 0.5 Wood/metal shops g 20 10 0.18 0.5 Food and beverage service Bars, cocktail lounges 100 7.5 0.18 — Cafeteria, fast food 100 7.5 0.18 — Dining rooms 70 7.5 0.18 — Kitchens (cooking) b — — — 0.7 Non - tobacco smoking establishments b 70 60 — — Hotels, motels, resorts and dormitories Bathrooms/toilet — private g — — — 25/50 f Bedroom/living room 10 5 0.06 — Conference/meeting 50 5 0.06 — Dormitory sleeping areas 20 5 0.06 — Gambling casinos 120 7.5 0.18 — Lobbies/prefunction 30 7.5 0.06 — Multipurpose assembly 120 5 0.06 — Laboratories j Biological — — 1.0 1.0 VENTILATION Chemical — — 1.0 1.0 Industrial and nonteaching — — 1.0 1.0 Nonproduction chemical labs — — 1.0 1.0 Offices Conference rooms 50 5 0.06 — Main entry lobbies 10 5 0.06 — Office spaces 5 5 0.06 — Reception areas 30 5 0.06 — Telephone/data entry 60 5 0.06 — Private dwellings, single and multiple Garages, common for multiple units b — — — 0.75 Kitchens and Kitchenettes b , m — — — 25/100 f Living areas c, i Based upon number of bedrooms. First bed- room, 2; each additional bedroom, 1 0.35 ACH but not less than 15 cfm/person — — Toilet rooms and bathrooms g — — — 20/50 f Public spaces Corridors — — 0.06 — Courtrooms 70 5 0.06 — Elevator car — — — 1.0 Legislative chambers 50 5 0.06 — Libraries 10 5 0.12 — Museums (children’s) 40 7.5 0.12 — Museums/galleries 40 7.5 0.06 — Places of religious worship 120 5 0.06 — Public spaces Shower room (per shower head) g — — — 50/20 f Toilet rooms – public g — — — 50/70 e VENTILATION Retail stores, sales floors and showroom floors Dressing rooms — — — 0.25 Mall common areas 40 7.5 0.06 — Sales 15 7.5 0.12 — Shipping and receiving — — 0.12 — Smoking lounges and non - tobacco smoking establishments b 70 60 — — Storage rooms — — 0.12 — Warehouses (see storage) — — — — Specialty shops Automotive motor - fuel dispensing stations b — — — 1.5 Barber 25 7.5 0.06 0.5 Beauty salons (without nail salon services) b 25 20 0.12 0.6 Nail salons b, h 25 20 0.12 0.6 Embalming room b — — — 2.0 Pet shops (animal areas) b 10 7.5 0.18 0.9 Supermarkets 8 7.5 0.06 — Sports and amusement Bowling alleys (seating areas) 40 10 0.12 — Disco/dance floors 100 20 0.06 — Game arcades 20 7.5 0.18 — Gym, stadium, arena (play area) — — 0.30 — Heath club/aerobics room 40 20 0.06 — Health club/weight room 10 20 0.06 — Ice arenas without combustion engines — — 0.30 0.5 Spectator areas 150 7.5 0.06 — ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure; such pressures shall not r esult in door opening forces in excess of those indicated in the New York City Building Code and shall not prevent doors from closing as required by the New York City Building Code . The method to convey ventilation air shall be designed and installed in ac cordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. Exception: The minimum required rate of outdoor air may be reduced where the registered design professional demo nstrates that an engineered ventilation system is designed in accordance with ASHRAE 62.1 Indoor Air Quality Procedure . 403.2.1 Recirculation of air. The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that required by Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling unit to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other uses or occupancies . 3. Where mech anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- culation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1. 4. Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation is prohibited. Recircula tion of air that is contained completely within such spaces shall not be prohibited. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving a s makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The requir ed outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor air and local exhaust airflow rates. Buildings that are no t more than three stories in height above grade plane, and that (i) are within Occupancy Group R - 2 or Occupancy Group R - 3, (ii) are adult homes or enriched living housing as described in Section 308.3.1 of the New York City Building Code, within Occupancy Group I - 1 and have 16 occupants or fewer, or (iii) are community residences or intermediate - care facilities as described in Section 308.3.2 of the New York City Building Code, shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.1.2. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. 403.3.1 Reserved. 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed t o have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each habitable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1 . Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ven tilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of non - tobacco hookah establishments, t he ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non - tobacco hookah establishment, the ventilation system serving the space shall be designed to provide v entilation over and above that re- quired by Table 403.3.1.1 in accordance with accepted engineering practice. Exceptions: 1. The occupant load is not required to be determined based on the estimated maximum occupant load rate indi- cated in Table 403.3 .1.1 wh ere approved statistical data documents the accuracy of an alternate anticipated occupant load. VENTILATION 2. The occupant load used in computing the required ventilation shall be the maximum number who will occupy the room or space simultaneously during any 2 - hour p eriod. 3. Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in accordance with ASHRAE 62.1 a nd comply with footnote k of Table 403.3.1.1. These conditions include, but are not limited to: 3.1. Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow requirements will be reset. Note: Examples of measures for estimating such variations include: occupancy scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per person using occupancy sensors such as those based on indoor CO 2 concentrations. 3.2. Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation system airflows and temperatures. 3.3. A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli ng or exhaust air makeup. TABLE 403.3.1.1 MINIMUM VENTILATION RATES OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #/1000 FT 2a PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING ZONE, R p CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE R a CFM/FT 2a EXHAUST AIRFLOW RATE CFM/FT 2a Correctional facilities Booking/waiting 50 7.5 0.06 — Cells without plumbing fixtures 25 5 0.12 — with plumbing fixtures g 25 5 0.12 1.0 Day room 30 5 0.06 — Correctional facilities Dining halls (see food and beverage service) — — — — Guard stations 15 5 0.06 — Dry cleaners, laundries Coin - operated dry cleaner 20 15 — — Coin - operated laundries 20 7.5 0.06 — Commercial dry cleaner l 30 30 — — Commercial laundry 10 25 — — Storage, pick up 30 7.5 0.12 — Education Art classroom g 20 10 0.18 0.7 VENTILATION Auditoriums 150 5 0.06 — Classrooms (ages 5 - 8) 25 10 0.12 — Classrooms (age 9 plus) 35 10 0.12 — Computer lab 25 10 0.12 — Corridors (see public spaces) — — — — Day care (through age 4) 25 10 0.18 — Lecture classroom 65 7.5 0.06 — Lecture hall (fixed seats) 150 7.5 0.06 — Locker/dressing rooms g — — — 0.25 Media center 25 10 0.12 — Multiuse assembly 100 7.5 0.06 — Music/theater/dance 35 10 0.06 — Science laboratories g, k 25 10 0.18 1.0 Sports locker rooms g — — — 0.5 Wood/metal shops g 20 10 0.18 0.5 Food and beverage service Bars, cocktail lounges 100 7.5 0.18 — Cafeteria, fast food 100 7.5 0.18 — Dining rooms 70 7.5 0.18 — Kitchens (cooking) b — — — 0.7 Non - tobacco smoking establishments b 70 60 — — Hotels, motels, resorts and dormitories Bathrooms/toilet — private g — — — 25/50 f Bedroom/living room 10 5 0.06 — Conference/meeting 50 5 0.06 — Dormitory sleeping areas 20 5 0.06 — Gambling casinos 120 7.5 0.18 — Lobbies/prefunction 30 7.5 0.06 — Multipurpose assembly 120 5 0.06 — Laboratories j Biological — — 1.0 1.0 VENTILATION Chemical — — 1.0 1.0 Industrial and nonteaching — — 1.0 1.0 Nonproduction chemical labs — — 1.0 1.0 Offices Conference rooms 50 5 0.06 — Main entry lobbies 10 5 0.06 — Office spaces 5 5 0.06 — Reception areas 30 5 0.06 — Telephone/data entry 60 5 0.06 — Private dwellings, single and multiple Garages, common for multiple units b — — — 0.75 Kitchens and Kitchenettes b , m — — — 25/100 f Living areas c, i Based upon number of bedrooms. First bed- room, 2; each additional bedroom, 1 0.35 ACH but not less than 15 cfm/person — — Toilet rooms and bathrooms g — — — 20/50 f Public spaces Corridors — — 0.06 — Courtrooms 70 5 0.06 — Elevator car — — — 1.0 Legislative chambers 50 5 0.06 — Libraries 10 5 0.12 — Museums (children’s) 40 7.5 0.12 — Museums/galleries 40 7.5 0.06 — Places of religious worship 120 5 0.06 — Public spaces Shower room (per shower head) g — — — 50/20 f Toilet rooms – public g — — — 50/70 e VENTILATION Retail stores, sales floors and showroom floors Dressing rooms — — — 0.25 Mall common areas 40 7.5 0.06 — Sales 15 7.5 0.12 — Shipping and receiving — — 0.12 — Smoking lounges and non - tobacco smoking establishments b 70 60 — — Storage rooms — — 0.12 — Warehouses (see storage) — — — — Specialty shops Automotive motor - fuel dispensing stations b — — — 1.5 Barber 25 7.5 0.06 0.5 Beauty salons (without nail salon services) b 25 20 0.12 0.6 Nail salons b, h 25 20 0.12 0.6 Embalming room b — — — 2.0 Pet shops (animal areas) b 10 7.5 0.18 0.9 Supermarkets 8 7.5 0.06 — Sports and amusement Bowling alleys (seating areas) 40 10 0.12 — Disco/dance floors 100 20 0.06 — Game arcades 20 7.5 0.18 — Gym, stadium, arena (play area) — — 0.30 — Heath club/aerobics room 40 20 0.06 — Health club/weight room 10 20 0.06 — Ice arenas without combustion engines — — 0.30 0.5 Spectator areas 150 7.5 0.06 — VENTILATION Swimming pools (pool and deck area) — — 0.48 — Storage Repair garages, enclosed parking garages b, d — — — 0.75 Warehouses — — 0.06 — Theaters Auditoriums (see education) — — — — Lobbies 150 5 0.06 — Stages, studios 70 10 0.06 — Ticket booths 60 5 0.06 — Transportation Platforms 100 7.5 0.06 — Transportation waiting 100 7.5 0.06 — Workrooms Bank vaults/safe deposit 5 5 0.06 — Computer (without printing) 4 5 0.06 — Copy, printing rooms 4 5 0.06 0.5 Darkrooms — — — 1.0 Meat processing c 10 15 — — Pharmacy (prep. area) 10 5 0.18 — Photo studios 10 5 0.12 — For SI: 1 cubic foot per minute = 0.0004719 m 3 /s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508m 3 /(s • m 2 ), °C = ((°F) - 32) / 1.8, 1 square foot = 0.0929 m 2 . a. Based upon net occupiable floor area. b. Mechanical exhaust required and the recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3). c. Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous. d. Ventilation systems in enclosed parking garages sh all comply with Section 404. e. Rates are per water closet or urinal. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while the space served by the toilet facilities is occupied. f. Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to oper ate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while the dwelling unit or sleeping unit served by the toilet facility is occupied. g. Mechanical exhaust is required and recirculation from such spaces is prohibited (see Section 403.2.1, Item 4). h. For nail salons, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more re quired source capture systems operate ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure; such pressures shall not r esult in door opening forces in excess of those indicated in the New York City Building Code and shall not prevent doors from closing as required by the New York City Building Code . The method to convey ventilation air shall be designed and installed in ac cordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. Exception: The minimum required rate of outdoor air may be reduced where the registered design professional demo nstrates that an engineered ventilation system is designed in accordance with ASHRAE 62.1 Indoor Air Quality Procedure . 403.2.1 Recirculation of air. The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that required by Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling unit to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other uses or occupancies . 3. Where mech anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- culation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1. 4. Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation is prohibited. Recircula tion of air that is contained completely within such spaces shall not be prohibited. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving a s makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The requir ed outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor air and local exhaust airflow rates. Buildings that are no t more than three stories in height above grade plane, and that (i) are within Occupancy Group R - 2 or Occupancy Group R - 3, (ii) are adult homes or enriched living housing as described in Section 308.3.1 of the New York City Building Code, within Occupancy Group I - 1 and have 16 occupants or fewer, or (iii) are community residences or intermediate - care facilities as described in Section 308.3.2 of the New York City Building Code, shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.1.2. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. 403.3.1 Reserved. 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed t o have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each habitable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1 . Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ven tilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of non - tobacco hookah establishments, t he ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non - tobacco hookah establishment, the ventilation system serving the space shall be designed to provide v entilation over and above that re- quired by Table 403.3.1.1 in accordance with accepted engineering practice. Exceptions: 1. The occupant load is not required to be determined based on the estimated maximum occupant load rate indi- cated in Table 403.3 .1.1 wh ere approved statistical data documents the accuracy of an alternate anticipated occupant load. VENTILATION 2. The occupant load used in computing the required ventilation shall be the maximum number who will occupy the room or space simultaneously during any 2 - hour p eriod. 3. Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in accordance with ASHRAE 62.1 a nd comply with footnote k of Table 403.3.1.1. These conditions include, but are not limited to: 3.1. Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow requirements will be reset. Note: Examples of measures for estimating such variations include: occupancy scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per person using occupancy sensors such as those based on indoor CO 2 concentrations. 3.2. Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation system airflows and temperatures. 3.3. A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli ng or exhaust air makeup. TABLE 403.3.1.1 MINIMUM VENTILATION RATES OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #/1000 FT 2a PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING ZONE, R p CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE R a CFM/FT 2a EXHAUST AIRFLOW RATE CFM/FT 2a Correctional facilities Booking/waiting 50 7.5 0.06 — Cells without plumbing fixtures 25 5 0.12 — with plumbing fixtures g 25 5 0.12 1.0 Day room 30 5 0.06 — Correctional facilities Dining halls (see food and beverage service) — — — — Guard stations 15 5 0.06 — Dry cleaners, laundries Coin - operated dry cleaner 20 15 — — Coin - operated laundries 20 7.5 0.06 — Commercial dry cleaner l 30 30 — — Commercial laundry 10 25 — — Storage, pick up 30 7.5 0.12 — Education Art classroom g 20 10 0.18 0.7 VENTILATION Auditoriums 150 5 0.06 — Classrooms (ages 5 - 8) 25 10 0.12 — Classrooms (age 9 plus) 35 10 0.12 — Computer lab 25 10 0.12 — Corridors (see public spaces) — — — — Day care (through age 4) 25 10 0.18 — Lecture classroom 65 7.5 0.06 — Lecture hall (fixed seats) 150 7.5 0.06 — Locker/dressing rooms g — — — 0.25 Media center 25 10 0.12 — Multiuse assembly 100 7.5 0.06 — Music/theater/dance 35 10 0.06 — Science laboratories g, k 25 10 0.18 1.0 Sports locker rooms g — — — 0.5 Wood/metal shops g 20 10 0.18 0.5 Food and beverage service Bars, cocktail lounges 100 7.5 0.18 — Cafeteria, fast food 100 7.5 0.18 — Dining rooms 70 7.5 0.18 — Kitchens (cooking) b — — — 0.7 Non - tobacco smoking establishments b 70 60 — — Hotels, motels, resorts and dormitories Bathrooms/toilet — private g — — — 25/50 f Bedroom/living room 10 5 0.06 — Conference/meeting 50 5 0.06 — Dormitory sleeping areas 20 5 0.06 — Gambling casinos 120 7.5 0.18 — Lobbies/prefunction 30 7.5 0.06 — Multipurpose assembly 120 5 0.06 — Laboratories j Biological — — 1.0 1.0 VENTILATION Chemical — — 1.0 1.0 Industrial and nonteaching — — 1.0 1.0 Nonproduction chemical labs — — 1.0 1.0 Offices Conference rooms 50 5 0.06 — Main entry lobbies 10 5 0.06 — Office spaces 5 5 0.06 — Reception areas 30 5 0.06 — Telephone/data entry 60 5 0.06 — Private dwellings, single and multiple Garages, common for multiple units b — — — 0.75 Kitchens and Kitchenettes b , m — — — 25/100 f Living areas c, i Based upon number of bedrooms. First bed- room, 2; each additional bedroom, 1 0.35 ACH but not less than 15 cfm/person — — Toilet rooms and bathrooms g — — — 20/50 f Public spaces Corridors — — 0.06 — Courtrooms 70 5 0.06 — Elevator car — — — 1.0 Legislative chambers 50 5 0.06 — Libraries 10 5 0.12 — Museums (children’s) 40 7.5 0.12 — Museums/galleries 40 7.5 0.06 — Places of religious worship 120 5 0.06 — Public spaces Shower room (per shower head) g — — — 50/20 f Toilet rooms – public g — — — 50/70 e VENTILATION Retail stores, sales floors and showroom floors Dressing rooms — — — 0.25 Mall common areas 40 7.5 0.06 — Sales 15 7.5 0.12 — Shipping and receiving — — 0.12 — Smoking lounges and non - tobacco smoking establishments b 70 60 — — Storage rooms — — 0.12 — Warehouses (see storage) — — — — Specialty shops Automotive motor - fuel dispensing stations b — — — 1.5 Barber 25 7.5 0.06 0.5 Beauty salons (without nail salon services) b 25 20 0.12 0.6 Nail salons b, h 25 20 0.12 0.6 Embalming room b — — — 2.0 Pet shops (animal areas) b 10 7.5 0.18 0.9 Supermarkets 8 7.5 0.06 — Sports and amusement Bowling alleys (seating areas) 40 10 0.12 — Disco/dance floors 100 20 0.06 — Game arcades 20 7.5 0.18 — Gym, stadium, arena (play area) — — 0.30 — Heath club/aerobics room 40 20 0.06 — Health club/weight room 10 20 0.06 — Ice arenas without combustion engines — — 0.30 0.5 Spectator areas 150 7.5 0.06 — VENTILATION Swimming pools (pool and deck area) — — 0.48 — Storage Repair garages, enclosed parking garages b, d — — — 0.75 Warehouses — — 0.06 — Theaters Auditoriums (see education) — — — — Lobbies 150 5 0.06 — Stages, studios 70 10 0.06 — Ticket booths 60 5 0.06 — Transportation Platforms 100 7.5 0.06 — Transportation waiting 100 7.5 0.06 — Workrooms Bank vaults/safe deposit 5 5 0.06 — Computer (without printing) 4 5 0.06 — Copy, printing rooms 4 5 0.06 0.5 Darkrooms — — — 1.0 Meat processing c 10 15 — — Pharmacy (prep. area) 10 5 0.18 — Photo studios 10 5 0.12 — For SI: 1 cubic foot per minute = 0.0004719 m 3 /s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508m 3 /(s • m 2 ), °C = ((°F) - 32) / 1.8, 1 square foot = 0.0929 m 2 . a. Based upon net occupiable floor area. b. Mechanical exhaust required and the recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3). c. Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous. d. Ventilation systems in enclosed parking garages sh all comply with Section 404. e. Rates are per water closet or urinal. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while the space served by the toilet facilities is occupied. f. Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to oper ate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while the dwelling unit or sleeping unit served by the toilet facility is occupied. g. Mechanical exhaust is required and recirculation from such spaces is prohibited (see Section 403.2.1, Item 4). h. For nail salons, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more re quired source capture systems operate VENTILATION continuously during occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon. i. For each dwelling unit within R - 2 occupancies, outdoor ventilation air shall be provided by mechanical means when the sum of all exhaust air flow rates, whether continuous or intermittent, is designed to exceed 75 cfm. When provided, mechanical ventilation air flow rate shall be approximately equal to the exhaust air flow rate in accordance with Section 403.1 and shall not be less than that required by the air flow rates prescribed in Table 403.3.1.1. For such dwelling units, manually operated openable exte rior wall openings shall not be used to provide required mechanical ventilation air. j. During unoccupied hours the ventilation rate and exhaust rates may be reduced to 0.5 cfm/ft 2 . k. When an educational science laboratory is occupied and hoods are not in use and hazardous materials are not present, then ventilation rates shall be consistent with actual use of the space, but not less than 0.5 cfm/ft 2 . l. See Section 502.6 for additional requirements. m. Exception: kitchens and kitchenettes in dwelli ng units of R - 2 occupancy may be naturally ventilated in accordance with Section 402. 403.3.1.1.1 Zone outdoor airflow. The minimum outdoor airflow required to be supplied to each zone shall be de- termined as a function of occupancy classification and space air distribution effectiveness in accordance with Sections 403.3.1.1.1.1 through 403.3.1.1.1.3. 403.3.1.1.1.1 Breathing zone outdoor airflow. The outdoor airflow rate required in the breathing zone V bz of the occupiable space or spaces in a zone shall be determined in accordance with Equation 4 - 1. V bz = R p P z + R a A z (Equation 4 - 1) where: A z = Zone floor area: the net occupiable floor area of the space or spaces in the zone. p z = Zone population: the number of people in the space or spaces in the zone. R p = People outdoor air rate: the outdoor airflow rate required per person from Table 403.3.1.1. R a = Area outdoor air rate: the outdoor airflow rate required per unit area from Table 403.3.1.1. 403.3.1.1.1.2 Zone air distribution effectiveness . The zone air distribution effectiveness (E z ) shall be determined using Table 403.3.1.1.1.2. TABLE 403.3.1.1.1.2 ZONE AIR DISTRIBUTION EFFECTIVENESS a, b, c, d AIR DISTRIBUTION CONFIGURATION E z Ceiling or floor supply of cool air 1.0 e Ceiling or floor supply of warm air and floor return 1.0 Ceiling supply of warm air and ceiling return 0.8 f Floor supply of warm air and ceiling return 0.7 Makeup air drawn in on the opposite side of the room from the exhaust and/or return 0.8 Makeup air drawn in near to the exhaust and/or re- turn location 0.5 For SI: 1 foot = 304.8 mm, 1 foot per minute = 0.00506 m/s, °C = ((°F) – 32) /1.8 . a. “Cool air” is air cooler than space temperature. b. “Warm air” is air warmer than space temperature. c. “Ceiling” includes any point above the breathing zone. d. “Floor” includes any point below the breathing zone. e. Zone air distribution effectiveness of 1.2 shall be permitted for systems with a floor supply of cool air and ceiling return, provided that lo w- velocity dis - placement ventilation achieves unidirectional flow and thermal stratification. f. Zone air distribution effectiveness of 1.0 shall be permitted for systems with a ceiling supply of warm air, provided that su pply air temperature is less than 15°F above space temperature and provided that the 150 foot - per - minute supply air jet reaches to within 4 1 / 2 feet of floor level. 403.3.1.1.1.3 Zone outdoor airflow. The zone outdoor airflow rate (V oz ), shall be determined in accordance with Equation 4- 2. V oz = V bz E z (Equation 4 - 2) VENTILATION 403.3.1.1.2 System outdoor airflow. The outdoor air required to be supplied by each ventilation system shall be determined in accordance with Sections 403.3.1.1.2.1 through 403.3.1.1.2.3 as a function of system type and zone outdoor airflow rates. 403.3.1.1.2.1 Single zone systems. Where one air handler supplies a mixture of outdoor air and recirculated return air to only one zone, the system outdoor air intake flow rate (V ot ) shall be determined in accordance wi th Equation 4 - 3. V ot = V oz (Equation 4 - 3) 403.3.1.1.2.2 100 - percent outdoor air systems. Where one air handler supplies only outdoor air to one or more zones, the system outdoor air intake flow rate (V ot ) shall be determined using Equation 4 - 4. V ot = ∑ V oz all zones (Equation 4 - 4) 403.3.1.1.2.3 Multiple zone recirculating systems. Where one air handler supplies a mixture of outdoor air and recirculated return air to more than one zone, the system outdoor air intake flow rate (V ot ) shall be determined in accordance with Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4. 403.3.1.1.2.3.1 Primary outdoor air fraction. The primary outdoor air fraction (Z p ) shall be determined for each zone in accordance with Equation 4 - 5. Z p = V oz /V pz (Eq uation 4 - 5) where: V pz = Primary airflow: The airflow rate supplied to the zone from the air - handling unit at which the outdoor air intake is located. It includes outdoor intake air and recirculated air from that air - handling unit but does not include a ir transferred or air recirculated to the zone by other means. For design purposes, V pz shall be the zone design primary airflow rate, except for zones with variable air volume supply and V pz shall be the lowest expected primary air - flow rate to the zone w hen it is fully occupied. 403.3.1.1.2.3.2 System ventilation efficiency. The system ventilation efficiency (E v ) shall be determined using Table 403.3.1.1.2.3.2 or Appendix A of ASHRAE 62.1. TABLE 403.3.1.1.2.3.2 SYSTEM VENTILATION EFFICIENCY a, b Max (Z p ) E v ≤ 0.15 1 ≤  ⸀(特)  ⸹ ≤  ⸀㌵  ⸸ ≤  ⸀㐵  ⸷ ≤  ⸀㔵  ⸶ ≤  ⸀㘵  ⸵ ≤  ⸀㜵  ⸴ 㸀‰⸀㜵  ⸳ 愮⁍愀砀  ⠀ 娀 瀀 ⤀⁩猀⁴栀攠氀慲最敳琀⁶慬甀攠漀昀  娀 瀀 挀愀氀挀甀氀愀琀攀搀⁵猀椀渀最⁅焀甀愀琀椀漀渀′′′ ⴀ 㔀⁡洀漀渀最⁡氀氀  琀栀攀⁺潮攀猀⁳攀爀瘀攀搀⁢礀 琀栀攀⁳礀猀琀攀洀⸀ 戀⸠䤀渀琀敲瀀漀氀慴椀渀最 戀攀琀眀攀敮⁴愀戀氀攠 瘀愀汵攀猀⁳栀愀汬⁢攀 瀀攀爀洀椀瑴攀搀⸀ 403.3.1.1.2.3.3 Uncorrected outdoor air intake. The uncorrected outdoor air intake flow rate (V ou ) shall be determined in accordance with Equation 4 - 6. V ou = D ∑ R p P z all zones + ∑ R a A z all zones (Equation 4 - 6) where: D = Occupant diversity: the ratio of the system population to the sum of the zone populations, determined in accordance with Equation 4 - 7. VENTILATION D = P s ∑ P z all zones (Equation 4 - 7) where: P a = System population: The total number of occupants in the area served by the system. For design purposes, P s shall be the maximum number of occupants expected to be concurrently in all zones served by the system. 403.3.1.1.2.3.4 Outdoor air intake flow ra te. The outdoor air intake flow rate ( V ot ) shall be determined in accordance with Equation 4 - 8. V ot = V ou /E v (Equation 4 - 8) 403.3.1.2 Short - term conditions. If it is known that peak occupancy will be of short duration and/or ventilation will be varied or interrupted for a short period of time, the design may be based on the average conditions over a time period T determined by Equation 4 - 9. T = 3V/V bz (Equation 4 - 9) (US) T = 50V/V bz (Equation 4 - 9) (SI) where: T = averaging time period, minutes V = the volume of the zone of which averaging is being applied, cubic feet V bz = the breathing zone outdoor airflow calculated using Equation 4 - 1 and design valve of the zone pop- ulation P z , cfm Acceptable design adjustments based on this optional provision include the following: 1. Zone with fluctuating occupancy: the zone population ( P z ) may be averaged over time, T. 2. Zone with intermittent interruption of supply air: the average outdoor airflow supplied to breathing zone over time, T, shall be no less than the breathing zone outdoor airflow ( V bz ) calculated using Equation 4 - 1. 3. A system with intermittent closure of outdoor air intake: the average outdoor air intake over time, T, shall be no less than the minimum outdoor air intake ( V ot ) calculated using Equation 4 - 3, 4 - 4 or 4 - 8, as appropriate. 403.3.1.3 Exhaust ventilation. Exhaust airflow rate shall be provided in accordance with the requirements of Table 403.3.1.1. Exhaust makeup air shall be permitted to be any combination of outdo or air, recirculated air and transfer air, except as limited in accordance with Section 403.2. 403.3.1.4 System operation. The minimum flow rate of outdoor air that the ventilation system must be capable of sup- plying during its operation shall be permitted to be based on the rate per person indicated in Table 403.3.1.1 and the actual number of occupants present. 403.3.1.5 Variable air volume system control. Variable air volume air distribution systems, other than those designed to supply only 100 - percent ou tdoor air, shall be provided with controls to regulate the flow of outdoor air. Such control system shall be designed to maintain the flow rate of outdoor air at a rate of not less than that required by Section 403.3.1 .1 over the entire range of supply air operating rates. 403.3.1.6 Balancing. The ventilation air distribution system shall be provided with means to adjust the system to achieve not less than the minimum ventilation airflow rate as required by Sections 403.3.1.1 and 403.3.1.2. Ventilation syst ems shall be balanced by an approved method. Such balancing shall verify that the ventilation system is capable of supplying and exhausting the airflow rates required by Sections 403.3.1.1 and 403.3.1.2. SECTION MC 404 ENCLOSED PARKING GARAGES 404.1 Enclosed parking garages. Where mechanical ventilation systems for enclosed parking garages operate intermittently , such operation shall be automatic by means of carbon monoxide detectors applied in conjunction with nitrogen dioxide detec- tors. Such detectors sha ll be installed in accordance with their manufacturers’ instructions. Such systems shall operate auto- matically upon detection of a concentration of carbon monoxide of 25 parts per million (ppm) or nitrogen dioxide of 500 parts per billion (ppb). ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5. 401 .2 Ventilation required. Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. 1. Every occupiable space shall be: 1.1. Naturally ventilated in accordance with Section 402 and mechanically exhausted in accordance with Table 403.3.1.1; or 1.2. Mechanically ventilated in accordance with Section 403. 2. All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance with Section 403. 3. Every habitabl e space shall be naturally ventilated in accordance with Section 402. 4. Every habitable space shall be mechanically ventilated if required by Section 403 . Ambulatory care facilities (Group B) and Group I - 2 occupancies shall be ventilated by mechanical means in accordance with Section 407. 401.3 When required. Ventilation shall be provided during the periods that the room or space is occupied or during operation of gas appliances. ‡‡‡ 401.4 Intake opening location. Ventilation air intake openings shall compl y with all of the following: 1. Intake openings shall be located not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent erline between lot lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than 10,000 square feet (929 m 2 ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet (91 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect vehicular exhaust, such as off street loading bays. 3. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock s, except as specified in Item 3 of Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 4. Where the requirements of Item 3 above cannot be achieved, intake openings shall be located not less than 3 feet (914.4 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. 5. Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require d. VENTILATION 6. Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the New York City Building Code. Exception: Group R - 3 occupancies are not required to comply with Section 401.4. 401.4.1 Required damp ers in intake openings. Outdoor air intakes shall be provided with dampers in accordance with Chapter 6. 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion - resistant screens, louvers or grilles. O penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f or exterior wall opening protec tives in accordance with Section 705 of the New York City Building Code. TABLE 401.5 OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR EXHAUST AND AIR INTAKE OPENINGS OUTDOOR OPENING TYPE MINIMUM AND MAXIMUM OPENING SIZES IN LOUVERS, GRILLES AND SCREENS MEASURED IN ANY DIRECTION Intake openings in residential oc- cupancies Not < 1 / 4 inch and not > 1 / 2 inch Intake openings in other than resi- dential occupancies > 1 / 4 inch and not > 1 inch For SI: 1 inch = 25.4 mm. 401.6 Contaminant sources. Stationary local sources producing air - borne particulates, heat, odors, fumes, spray, vapors, smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in accordance with Chap ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved location at the exterior of the building. 401.6.1 Wind - driven rain. All exterior louvers for building ventilation systems shall conform to the requirements of Chap- ter 16 of the New York City Building Code , where applicable, and the following: 1. Comply with the requirements of AMCA 550. Louvers shall comply with the intru sion requirements of wind - driven rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with Chapter 16 of the New York City Building Code ; or 2. Be installed on a plenum configured to intercept any wind - driven rain penetrating the louver and to prevent the rain from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system to convey water penetrat ing the louver directly to the outdoors or in accordance with the New York City Plumbing Code . SECTION MC 402 NATURAL VENTILATION 402.1 General. Natural ventilation of occupiable and habitable spaces shall comply with Chapter 12 of the New York City Build ing Code. 402.2 Reserved. 402.3 Reserved. 402.4 Reserved. SECTION MC 403 MECHANICAL VENTILATION VENTILATION 403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure; such pressures shall not r esult in door opening forces in excess of those indicated in the New York City Building Code and shall not prevent doors from closing as required by the New York City Building Code . The method to convey ventilation air shall be designed and installed in ac cordance with Chapter 6. 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. Exception: The minimum required rate of outdoor air may be reduced where the registered design professional demo nstrates that an engineered ventilation system is designed in accordance with ASHRAE 62.1 Indoor Air Quality Procedure . 403.2.1 Recirculation of air. The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that required by Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that: 1. Ventilation air shall not be recirculated from one dwelling unit to another or to dissimilar occupancies. 2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other uses or occupancies . 3. Where mech anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- culation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1. 4. Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation is prohibited. Recircula tion of air that is contained completely within such spaces shall not be prohibited. 403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving a s makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The requir ed outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. 403.3 Outdoor air and local exhaust airflow rates. Buildings that are no t more than three stories in height above grade plane, and that (i) are within Occupancy Group R - 2 or Occupancy Group R - 3, (ii) are adult homes or enriched living housing as described in Section 308.3.1 of the New York City Building Code, within Occupancy Group I - 1 and have 16 occupants or fewer, or (iii) are community residences or intermediate - care facilities as described in Section 308.3.2 of the New York City Building Code, shall be provided with outdoor air and local exhaust in accordance with Section 403.3.1.1.2. All other buildings intended to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. 403.3.1 Reserved. 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed t o have the capacity to supply the minimum outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each habitable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1 . Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ven tilation system shall be designed to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. With the exception of non - tobacco hookah establishments, t he ventilation rates in Table 403.3.1.1 are based on the absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non - tobacco hookah establishment, the ventilation system serving the space shall be designed to provide v entilation over and above that re- quired by Table 403.3.1.1 in accordance with accepted engineering practice. Exceptions: 1. The occupant load is not required to be determined based on the estimated maximum occupant load rate indi- cated in Table 403.3 .1.1 wh ere approved statistical data documents the accuracy of an alternate anticipated occupant load. VENTILATION 2. The occupant load used in computing the required ventilation shall be the maximum number who will occupy the room or space simultaneously during any 2 - hour p eriod. 3. Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in accordance with ASHRAE 62.1 a nd comply with footnote k of Table 403.3.1.1. These conditions include, but are not limited to: 3.1. Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow requirements will be reset. Note: Examples of measures for estimating such variations include: occupancy scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per person using occupancy sensors such as those based on indoor CO 2 concentrations. 3.2. Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation system airflows and temperatures. 3.3. A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli ng or exhaust air makeup. TABLE 403.3.1.1 MINIMUM VENTILATION RATES OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #/1000 FT 2a PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING ZONE, R p CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE R a CFM/FT 2a EXHAUST AIRFLOW RATE CFM/FT 2a Correctional facilities Booking/waiting 50 7.5 0.06 — Cells without plumbing fixtures 25 5 0.12 — with plumbing fixtures g 25 5 0.12 1.0 Day room 30 5 0.06 — Correctional facilities Dining halls (see food and beverage service) — — — — Guard stations 15 5 0.06 — Dry cleaners, laundries Coin - operated dry cleaner 20 15 — — Coin - operated laundries 20 7.5 0.06 — Commercial dry cleaner l 30 30 — — Commercial laundry 10 25 — — Storage, pick up 30 7.5 0.12 — Education Art classroom g 20 10 0.18 0.7 VENTILATION Auditoriums 150 5 0.06 — Classrooms (ages 5 - 8) 25 10 0.12 — Classrooms (age 9 plus) 35 10 0.12 — Computer lab 25 10 0.12 — Corridors (see public spaces) — — — — Day care (through age 4) 25 10 0.18 — Lecture classroom 65 7.5 0.06 — Lecture hall (fixed seats) 150 7.5 0.06 — Locker/dressing rooms g — — — 0.25 Media center 25 10 0.12 — Multiuse assembly 100 7.5 0.06 — Music/theater/dance 35 10 0.06 — Science laboratories g, k 25 10 0.18 1.0 Sports locker rooms g — — — 0.5 Wood/metal shops g 20 10 0.18 0.5 Food and beverage service Bars, cocktail lounges 100 7.5 0.18 — Cafeteria, fast food 100 7.5 0.18 — Dining rooms 70 7.5 0.18 — Kitchens (cooking) b — — — 0.7 Non - tobacco smoking establishments b 70 60 — — Hotels, motels, resorts and dormitories Bathrooms/toilet — private g — — — 25/50 f Bedroom/living room 10 5 0.06 — Conference/meeting 50 5 0.06 — Dormitory sleeping areas 20 5 0.06 — Gambling casinos 120 7.5 0.18 — Lobbies/prefunction 30 7.5 0.06 — Multipurpose assembly 120 5 0.06 — Laboratories j Biological — — 1.0 1.0 VENTILATION Chemical — — 1.0 1.0 Industrial and nonteaching — — 1.0 1.0 Nonproduction chemical labs — — 1.0 1.0 Offices Conference rooms 50 5 0.06 — Main entry lobbies 10 5 0.06 — Office spaces 5 5 0.06 — Reception areas 30 5 0.06 — Telephone/data entry 60 5 0.06 — Private dwellings, single and multiple Garages, common for multiple units b — — — 0.75 Kitchens and Kitchenettes b , m — — — 25/100 f Living areas c, i Based upon number of bedrooms. First bed- room, 2; each additional bedroom, 1 0.35 ACH but not less than 15 cfm/person — — Toilet rooms and bathrooms g — — — 20/50 f Public spaces Corridors — — 0.06 — Courtrooms 70 5 0.06 — Elevator car — — — 1.0 Legislative chambers 50 5 0.06 — Libraries 10 5 0.12 — Museums (children’s) 40 7.5 0.12 — Museums/galleries 40 7.5 0.06 — Places of religious worship 120 5 0.06 — Public spaces Shower room (per shower head) g — — — 50/20 f Toilet rooms – public g — — — 50/70 e VENTILATION Retail stores, sales floors and showroom floors Dressing rooms — — — 0.25 Mall common areas 40 7.5 0.06 — Sales 15 7.5 0.12 — Shipping and receiving — — 0.12 — Smoking lounges and non - tobacco smoking establishments b 70 60 — — Storage rooms — — 0.12 — Warehouses (see storage) — — — — Specialty shops Automotive motor - fuel dispensing stations b — — — 1.5 Barber 25 7.5 0.06 0.5 Beauty salons (without nail salon services) b 25 20 0.12 0.6 Nail salons b, h 25 20 0.12 0.6 Embalming room b — — — 2.0 Pet shops (animal areas) b 10 7.5 0.18 0.9 Supermarkets 8 7.5 0.06 — Sports and amusement Bowling alleys (seating areas) 40 10 0.12 — Disco/dance floors 100 20 0.06 — Game arcades 20 7.5 0.18 — Gym, stadium, arena (play area) — — 0.30 — Heath club/aerobics room 40 20 0.06 — Health club/weight room 10 20 0.06 — Ice arenas without combustion engines — — 0.30 0.5 Spectator areas 150 7.5 0.06 — VENTILATION Swimming pools (pool and deck area) — — 0.48 — Storage Repair garages, enclosed parking garages b, d — — — 0.75 Warehouses — — 0.06 — Theaters Auditoriums (see education) — — — — Lobbies 150 5 0.06 — Stages, studios 70 10 0.06 — Ticket booths 60 5 0.06 — Transportation Platforms 100 7.5 0.06 — Transportation waiting 100 7.5 0.06 — Workrooms Bank vaults/safe deposit 5 5 0.06 — Computer (without printing) 4 5 0.06 — Copy, printing rooms 4 5 0.06 0.5 Darkrooms — — — 1.0 Meat processing c 10 15 — — Pharmacy (prep. area) 10 5 0.18 — Photo studios 10 5 0.12 — For SI: 1 cubic foot per minute = 0.0004719 m 3 /s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508m 3 /(s • m 2 ), °C = ((°F) - 32) / 1.8, 1 square foot = 0.0929 m 2 . a. Based upon net occupiable floor area. b. Mechanical exhaust required and the recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3). c. Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous. d. Ventilation systems in enclosed parking garages sh all comply with Section 404. e. Rates are per water closet or urinal. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while the space served by the toilet facilities is occupied. f. Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to oper ate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while the dwelling unit or sleeping unit served by the toilet facility is occupied. g. Mechanical exhaust is required and recirculation from such spaces is prohibited (see Section 403.2.1, Item 4). h. For nail salons, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more re quired source capture systems operate VENTILATION continuously during occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon. i. For each dwelling unit within R - 2 occupancies, outdoor ventilation air shall be provided by mechanical means when the sum of all exhaust air flow rates, whether continuous or intermittent, is designed to exceed 75 cfm. When provided, mechanical ventilation air flow rate shall be approximately equal to the exhaust air flow rate in accordance with Section 403.1 and shall not be less than that required by the air flow rates prescribed in Table 403.3.1.1. For such dwelling units, manually operated openable exte rior wall openings shall not be used to provide required mechanical ventilation air. j. During unoccupied hours the ventilation rate and exhaust rates may be reduced to 0.5 cfm/ft 2 . k. When an educational science laboratory is occupied and hoods are not in use and hazardous materials are not present, then ventilation rates shall be consistent with actual use of the space, but not less than 0.5 cfm/ft 2 . l. See Section 502.6 for additional requirements. m. Exception: kitchens and kitchenettes in dwelli ng units of R - 2 occupancy may be naturally ventilated in accordance with Section 402. 403.3.1.1.1 Zone outdoor airflow. The minimum outdoor airflow required to be supplied to each zone shall be de- termined as a function of occupancy classification and space air distribution effectiveness in accordance with Sections 403.3.1.1.1.1 through 403.3.1.1.1.3. 403.3.1.1.1.1 Breathing zone outdoor airflow. The outdoor airflow rate required in the breathing zone V bz of the occupiable space or spaces in a zone shall be determined in accordance with Equation 4 - 1. V bz = R p P z + R a A z (Equation 4 - 1) where: A z = Zone floor area: the net occupiable floor area of the space or spaces in the zone. p z = Zone population: the number of people in the space or spaces in the zone. R p = People outdoor air rate: the outdoor airflow rate required per person from Table 403.3.1.1. R a = Area outdoor air rate: the outdoor airflow rate required per unit area from Table 403.3.1.1. 403.3.1.1.1.2 Zone air distribution effectiveness . The zone air distribution effectiveness (E z ) shall be determined using Table 403.3.1.1.1.2. TABLE 403.3.1.1.1.2 ZONE AIR DISTRIBUTION EFFECTIVENESS a, b, c, d AIR DISTRIBUTION CONFIGURATION E z Ceiling or floor supply of cool air 1.0 e Ceiling or floor supply of warm air and floor return 1.0 Ceiling supply of warm air and ceiling return 0.8 f Floor supply of warm air and ceiling return 0.7 Makeup air drawn in on the opposite side of the room from the exhaust and/or return 0.8 Makeup air drawn in near to the exhaust and/or re- turn location 0.5 For SI: 1 foot = 304.8 mm, 1 foot per minute = 0.00506 m/s, °C = ((°F) – 32) /1.8 . a. “Cool air” is air cooler than space temperature. b. “Warm air” is air warmer than space temperature. c. “Ceiling” includes any point above the breathing zone. d. “Floor” includes any point below the breathing zone. e. Zone air distribution effectiveness of 1.2 shall be permitted for systems with a floor supply of cool air and ceiling return, provided that lo w- velocity dis - placement ventilation achieves unidirectional flow and thermal stratification. f. Zone air distribution effectiveness of 1.0 shall be permitted for systems with a ceiling supply of warm air, provided that su pply air temperature is less than 15°F above space temperature and provided that the 150 foot - per - minute supply air jet reaches to within 4 1 / 2 feet of floor level. 403.3.1.1.1.3 Zone outdoor airflow. The zone outdoor airflow rate (V oz ), shall be determined in accordance with Equation 4- 2. V oz = V bz E z (Equation 4 - 2) VENTILATION 403.3.1.1.2 System outdoor airflow. The outdoor air required to be supplied by each ventilation system shall be determined in accordance with Sections 403.3.1.1.2.1 through 403.3.1.1.2.3 as a function of system type and zone outdoor airflow rates. 403.3.1.1.2.1 Single zone systems. Where one air handler supplies a mixture of outdoor air and recirculated return air to only one zone, the system outdoor air intake flow rate (V ot ) shall be determined in accordance wi th Equation 4 - 3. V ot = V oz (Equation 4 - 3) 403.3.1.1.2.2 100 - percent outdoor air systems. Where one air handler supplies only outdoor air to one or more zones, the system outdoor air intake flow rate (V ot ) shall be determined using Equation 4 - 4. V ot = ∑ V oz all zones (Equation 4 - 4) 403.3.1.1.2.3 Multiple zone recirculating systems. Where one air handler supplies a mixture of outdoor air and recirculated return air to more than one zone, the system outdoor air intake flow rate (V ot ) shall be determined in accordance with Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4. 403.3.1.1.2.3.1 Primary outdoor air fraction. The primary outdoor air fraction (Z p ) shall be determined for each zone in accordance with Equation 4 - 5. Z p = V oz /V pz (Eq uation 4 - 5) where: V pz = Primary airflow: The airflow rate supplied to the zone from the air - handling unit at which the outdoor air intake is located. It includes outdoor intake air and recirculated air from that air - handling unit but does not include a ir transferred or air recirculated to the zone by other means. For design purposes, V pz shall be the zone design primary airflow rate, except for zones with variable air volume supply and V pz shall be the lowest expected primary air - flow rate to the zone w hen it is fully occupied. 403.3.1.1.2.3.2 System ventilation efficiency. The system ventilation efficiency (E v ) shall be determined using Table 403.3.1.1.2.3.2 or Appendix A of ASHRAE 62.1. TABLE 403.3.1.1.2.3.2 SYSTEM VENTILATION EFFICIENCY a, b Max (Z p ) E v ≤ 0.15 1 ≤  ⸀(特)  ⸹ ≤  ⸀㌵  ⸸ ≤  ⸀㐵  ⸷ ≤  ⸀㔵  ⸶ ≤  ⸀㘵  ⸵ ≤  ⸀㜵  ⸴ 㸀‰⸀㜵  ⸳ 愮⁍愀砀  ⠀ 娀 瀀 ⤀⁩猀⁴栀攠氀慲最敳琀⁶慬甀攠漀昀  娀 瀀 挀愀氀挀甀氀愀琀攀搀⁵猀椀渀最⁅焀甀愀琀椀漀渀′′′ ⴀ 㔀⁡洀漀渀最⁡氀氀  琀栀攀⁺潮攀猀⁳攀爀瘀攀搀⁢礀 琀栀攀⁳礀猀琀攀洀⸀ 戀⸠䤀渀琀敲瀀漀氀慴椀渀最 戀攀琀眀攀敮⁴愀戀氀攠 瘀愀汵攀猀⁳栀愀汬⁢攀 瀀攀爀洀椀瑴攀搀⸀ 403.3.1.1.2.3.3 Uncorrected outdoor air intake. The uncorrected outdoor air intake flow rate (V ou ) shall be determined in accordance with Equation 4 - 6. V ou = D ∑ R p P z all zones + ∑ R a A z all zones (Equation 4 - 6) where: D = Occupant diversity: the ratio of the system population to the sum of the zone populations, determined in accordance with Equation 4 - 7. VENTILATION D = P s ∑ P z all zones (Equation 4 - 7) where: P a = System population: The total number of occupants in the area served by the system. For design purposes, P s shall be the maximum number of occupants expected to be concurrently in all zones served by the system. 403.3.1.1.2.3.4 Outdoor air intake flow ra te. The outdoor air intake flow rate ( V ot ) shall be determined in accordance with Equation 4 - 8. V ot = V ou /E v (Equation 4 - 8) 403.3.1.2 Short - term conditions. If it is known that peak occupancy will be of short duration and/or ventilation will be varied or interrupted for a short period of time, the design may be based on the average conditions over a time period T determined by Equation 4 - 9. T = 3V/V bz (Equation 4 - 9) (US) T = 50V/V bz (Equation 4 - 9) (SI) where: T = averaging time period, minutes V = the volume of the zone of which averaging is being applied, cubic feet V bz = the breathing zone outdoor airflow calculated using Equation 4 - 1 and design valve of the zone pop- ulation P z , cfm Acceptable design adjustments based on this optional provision include the following: 1. Zone with fluctuating occupancy: the zone population ( P z ) may be averaged over time, T. 2. Zone with intermittent interruption of supply air: the average outdoor airflow supplied to breathing zone over time, T, shall be no less than the breathing zone outdoor airflow ( V bz ) calculated using Equation 4 - 1. 3. A system with intermittent closure of outdoor air intake: the average outdoor air intake over time, T, shall be no less than the minimum outdoor air intake ( V ot ) calculated using Equation 4 - 3, 4 - 4 or 4 - 8, as appropriate. 403.3.1.3 Exhaust ventilation. Exhaust airflow rate shall be provided in accordance with the requirements of Table 403.3.1.1. Exhaust makeup air shall be permitted to be any combination of outdo or air, recirculated air and transfer air, except as limited in accordance with Section 403.2. 403.3.1.4 System operation. The minimum flow rate of outdoor air that the ventilation system must be capable of sup- plying during its operation shall be permitted to be based on the rate per person indicated in Table 403.3.1.1 and the actual number of occupants present. 403.3.1.5 Variable air volume system control. Variable air volume air distribution systems, other than those designed to supply only 100 - percent ou tdoor air, shall be provided with controls to regulate the flow of outdoor air. Such control system shall be designed to maintain the flow rate of outdoor air at a rate of not less than that required by Section 403.3.1 .1 over the entire range of supply air operating rates. 403.3.1.6 Balancing. The ventilation air distribution system shall be provided with means to adjust the system to achieve not less than the minimum ventilation airflow rate as required by Sections 403.3.1.1 and 403.3.1.2. Ventilation syst ems shall be balanced by an approved method. Such balancing shall verify that the ventilation system is capable of supplying and exhausting the airflow rates required by Sections 403.3.1.1 and 403.3.1.2. SECTION MC 404 ENCLOSED PARKING GARAGES 404.1 Enclosed parking garages. Where mechanical ventilation systems for enclosed parking garages operate intermittently , such operation shall be automatic by means of carbon monoxide detectors applied in conjunction with nitrogen dioxide detec- tors. Such detectors sha ll be installed in accordance with their manufacturers’ instructions. Such systems shall operate auto- matically upon detection of a concentration of carbon monoxide of 25 parts per million (ppm) or nitrogen dioxide of 500 parts per billion (ppb). VENTILATION 404.2 Mini mum ventilation. Automatic operation of the system shall not reduce the ventilation airflow rate below 0.05 cfm per square foot (0.00025 m 3 /s • m 2 ) of the floor area and the system shall be capable of producing a ventilation airflow rate of 0.75 cfm per square foot (0.0038 m 3 /s • m 2 ) of floor area. 404.3 Occupied spaces accessory to public garages. Connecting offices, waiting rooms, ticket booths and similar uses that are accessory to a public garage shall be maintained at a positive pressure and shall be provided with ventilation in accordance with Section 403.3. SECTION MC 405 SYSTEMS CONTROL 405.1 General. Mechanical ventilation systems shall be provided with manual or automatic controls that will operate such systems whenever the spaces are occupied. A ir - conditioning systems that supply required ventilation air shall be provided with controls designed to automatically maintain the required outdoor air supply rate during occupancy. 405.2 Manual control. Each air distribution system shall be provided with not less than one manual control to stop the operation of the supply, return, and exhaust fans(s) in an emergency. The manual control shall be provided at an approved location. A disconnect switch shall not be considered a manual control. 405.2.1 Office b uildings. Any building where the main use or dominant occupancy is classified in Occupancy Group B having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, where a system serves a floor or floor s other than the floor on which the equipment is located, shall be provided with the following controls, in addition to the controls required by this chapter: 1. Manual controls for operating individually each air supply and each exhaust or return fan in t he system located as follows: 1.1. At the Fire Command Center, and 1.2. In the room containing the affected air - handling fans. 2. Manual controls for operating individually or in groups each remote control reversible fire shutter, when such shutters are provided in accordance with the provisions of the New York City Building Code , or each smoke damper provided in accordance with the provisions of the New York City Building Code . Such controls shall be located at the Fire Command Center. SECTION MC 406 VENTILATION OF UNINHABITED SPACES 406.1 General. Uninhabited spaces, such as crawl spaces and attics, shall be provided with natural ventilation openings as required by the New York City Building Code or shall be pro - vided with a mechanical exhaust and supply air system. The mechanical exhaust rate shall be not less than 0.02 cfm per square foot (0.00001 m 3 /s • m 2 ) of horizontal area and shall be automatically controlled to operate when the relative humidity in the space served exceeds 60 percent. 406.1.1 Methane and radon venting. The design and material s used in the installation of the methane and radon vent systems shall be approved by the commissioner and shall comply with all applicable rules of the Fire Department. SECTION MC 407 AMBULATORY CARE FACILITIES AND GROUP I - 2 OCCUPANCIES 407.1 General. Mec hanical ventilation for ambulatory care facilities (Group B) and Group I - 2 occupancies shall be designed and installed in accordance with all applicable federal, state and local regulations. SECTION MC 408 VENTILATION OF NONPRODUCTION CHEMICAL LABORATORIES VENTILATION 408 .1 General. Nonproduction chemical laboratories complying with the hazardous materials quantity limitations of Section 427 of the New York City Building Code shall provide a mechanical ventilation system in accordance with NFPA 45 and Table 403.3.1.1 o f this code, except that ducts constructed of combustible materials shall not be permitted.