CHAPTER 7 COMBUSTION , VENTILATION, AND DILUTION AIR SECTION MC 701 GENERAL 701.1 Scope. The provisions of this chapter shall govern the requirements for combustion, ventilation, and dilution air for fuel - burning appliances other than gas - fired appliances. The requirements for combustion, ventilation, and dilution air for gas - fired appliances shal l be in accordance with the New York City Fuel Gas Code. 701.2 Combustion, ventilation, and dilution air required. Every room or space containing fuel - burning appliances shall be provided with combustion, ventilation, and dilution air as required by this c ode. Combustion, ventilation, and dilution air shall be provided in accordance with Section 702, 703, 704, 705, 706 or 707. Direct - vent appliances or equipment that do not draw combustion air from inside of the building are not required to be considered in the determination of the combustion and dilution air requirements and shall be installed in accordance with the equip- ment manufacturer’s instructions and listing. Combustion air requirements shall be determined based on the simul- taneous operation of all f uel - burning appliances drawing combustion, ventilation, and dilution air from the room or space. Combustion, ventilation, and dilution air shall be obtained solely from the outdoors for fuel - burning appli- ances with an input greater than 350,000 Btu/h (102. 6 kW). The room or space containing fuel - burning appliances shall comply with the requirements of Sections C402.5.3 and R402.4.4, as applicable, of the New York City Energy Conservation Code and Section 1012 of this code. 701.3 Circulation of air. The equi pment and appliances within every room containing fuel - burning appliances shall be installed so as to allow free circulation of air. Provisions shall be made to allow for the simultaneous operation of mechanical exhaust systems, fireplaces or other equipme nt and appliances operating in the same room or space from which combustion, ventilation, and dilution air is being drawn. Such provisions shall prevent the operation of such appliances, equipment and systems from affecting the supply of combustion, ventil ation, and dilution air. 701.3.1 Makeup air for fuel - burning devices. Where exhaust fans are installed, makeup air shall be provided to replace the exhausted air. Calculations shall be provided on the construction documents to validate the use of the exhaust fan(s) and compliance with this chapter. 701.3.2 Ventilation air f or fuel - burning devices. Where ventilation air is brought in by mechanical means for heat generation mitigation, provisions must be made for proper air balance to prevent a negative or positive pressure in the boiler and to discharge the ventilation air di rectly to the outside. 701.4 Crawl space and attic space. For the purposes of this chapter, an opening to a naturally ventilated crawl space or attic space shall be considered equivalent to an opening to the outdoors. 701.4.1 Crawl space. Where lower combu stion air openings connect with crawl spaces, such spaces shall have unobstructed openings to the outdoors at least twice that required for the combustion air openings . The height of the crawl space shall comply with the requirements of the New York City B uilding Code and shall be without obstruction to the free flow of air. 701.4.2 Attic space. Where combustion air is obtained from an attic area, the attic ventilating openings shall not be subject to ice or snow blockage, and the attic shall have not less than 30 inches (762 mm) vertical clear height at its maxi - mum point. Attic ventilation openings shall be sufficient to provide the required volume of combustion air and the attic ventilation required by the New York City Building Code. The combustion air o penings shall be provided with a sleeve of not less than 0.019 inch (0.48 mm) (No.26 Gage) galvanized steel or other approved material extending from the appliance enclosure to at least 6 inches ( 152.4 mm) above the top of the ceiling joists and insulation . 701.5 Prohibited sources. Openings and ducts shall not connect appliance enclosures with a space in which the operation of a fan will adversely affect the flow of the combustion, ventilation, and dilution air. Combustion, venti- lation, and dilution air sh all not be subject to ice or snow blockage. No combustion, ventilation, and dilution air inlet COMBUSTION, VENTILATION, AND DILUTION AIR shall be less than 30 inches (762 mm) above grade. Combustion, ventilation, and dilution air shall not be obtained from a hazardous location, except where the fu el - fired appliances are located within the hazardous location and are installed in accordance with this code. Combustion, ventilation, and dilution air shall not be taken from a refrigeration machinery room, except where a refrigerant vapor detector system is installed to automatically shut off the combus- tion process in the event of refrigerant leakage. For structures in flood hazard areas, air shall be obtained from a location complying with the additional requirements of Appendix G of the New York City Bu ilding Code. SECTION MC 702 INSIDE AIR 702.1 All air from indoors. Combustion, ventilation, and dilution air shall be permitted to be obtained entirely from the indoors in buildings that are not of unusually tight construction. In buildings of unusually tight construction, combustion air shall be obtained from the outdoors in accordance with Section 703, 705, 706 or 707. 702.2 Air from the same room or space. The room or space containing fuel - burning appliances shall be an uncon- fined space as de fined in Section 202. 702.3 Air from adjacent spaces. Where the volume of the room in which the fuel - burning appliances are located does not comply with Section 702.2, additional inside combustion, ventilation, and dilution air shall be obtained by opening the room to adjacent spaces so that the combined volume of all communicating spaces meets the volumetric requirement of Section 702.2. Openings connecting the spaces shall comply with Sections 702.3.1, 702.3.2 and Fig- ure A - 1 of Appendix A. 702.3.1 Number and location of openings. Two openings shall be provided, one within 1 foot ( 304.8 mm) of the ceiling of the room and one within 1 foot ( 304.8 mm) of the floor. 702.3.2 Size of openings. The net free area of each opening, calculated in accordance with Sect ion 708, shall be a minimum of 1 square inch per 1,000 Btu/h (2201 mm 2 /kW) of input rating of the fuel - burning appliances draw- ing combustion, ventilation, and dilution air from the communicating spaces and shall be not less than 100 square inches (64 516 m m 2 ). SECTION MC 703 OUTDOOR AIR 703.1 All air from the outdoors. Where all combustion, ventilation, and dilution air is to be provided by outdoor air, the required combustion, ventilation, and dilution air shall be obtained by direct opening by louver or a duct(s) from the boiler room to the outdoors. Openings connecting the room to the outdoor air shall comply with Sections 703.1.1 through 703.1.2 of this code, and Figures 304.6.1(1), 304.6.1(2), 304.6.1(3) and 304.6.2 of the New York City Fuel Gas Code . The size of the openings connecting the room to the outdoor air supply shall also comply with any applicable rules of the New York City Department of Environmental Protection. 703.1.1 Two - permanent - openings method. Two permanent openings, one commencing within 12 inches (304.8 mm) at the top and one commencing within 12 inches (304.8 mm) of the bottom of the room, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces th at freely communicate with the outdoors as follows: 1. Where directly communicating with the outdoors, or where communicating with the outdoors through verti- cal ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/h (550 mm 2 /kW ) of total input rating of all equipment in the room. 2. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2,000 Btu/H (1100 mm 2 /kW) of total input rating of all e quipment in the room. 703.1.2 One - permanent - opening method. One permanent opening, commencing within 12 inches (304.8 mm) of the top of the enclosure, shall be provided. The equipment shall have clearances of at least 1 inch (25.4 mm) from the sides and b ack and 6 inches (152.4 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or through a vertical or horizontal duct to the outdoors or spaces that freely communicate with mm) at the top and one commencing within 12 inches (304.8 mm) of the bottom of the room, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces th at freely communicate with the outdoors as follows: 1. Where directly communicating with the outdoors, or where communicating with the outdoors through verti- cal ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/h (550 mm 2 /kW ) of total input rating of all equipment in the room. 2. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2,000 Btu/H (1100 mm 2 /kW) of total input rating of all e quipment in the room. 703.1.2 One - permanent - opening method. One permanent opening, commencing within 12 inches (304.8 mm) of the top of the enclosure, shall be provided. The equipment shall have clearances of at least 1 inch (25.4 mm) from the sides and b ack and 6 inches (152.4 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or through a vertical or horizontal duct to the outdoors or spaces that freely communicate with COMBUSTION, VENTILATION, AND DILUTION AIR the outdoors and shall have a minimum free area of 1 square inch per 3,000 Btu/h (734 mm 2 /kW) of the total input rating of all equipment located in the enclosure, and not less than the sum of the areas of all vent connectors in the space. SECTION MC 704 COMBINED USE OF INSIDE AND OUTDOOR AIR (COND ITION 1) 704.1 Combination of air from inside and outdoors. This section shall apply only to appliances located in confined spaces in buildings not of unusually tight construction. Where the volumes of rooms and spaces are combined for the purpose of provi ding indoor combustion air, such rooms and spaces shall communicate through permanent open- ings in compliance with Sections 702.3.1 and 702.3.2. The required combustion, ventilation, and dilution air shall be obtained by opening the room to the outdoors usi ng a combination of inside and outdoor air, prorated in accord- ance with Section 704.1.6. The ratio of interior spaces shall comply with Section 704.1.5. The number, location and ratios of openings connecting the space with the outdoor air shall comply with Sections 704.1.1 through 704.1.4. 704.1.1 Number and location of openings. At least two openings shall be provided, one within 1 foot ( 304.8 mm) of the ceiling of the room and one within 1 foot ( 304.8 mm) of the floor. 704.1.2 Ratio of direct openings. Wh ere direct openings to the outdoors are provided in accordance with Section 703.1, the ratio of direct openings shall be the sum of the net free areas of both direct openings to the outdoors, divided by the sum of the required areas for both such openings as determined in accordance with Section 703.1.2. 704.1.3 Ratio of horizontal openings. Where openings connected to the outdoors through horizontal ducts are pro - vided in accordance with Section 703.1, the ratio of horizontal openings shall be the sum of the net free areas of both such openings, divided by the sum of the required areas for both such openings as determined in accord- ance with Section 703.1.3. 704.1.4 Ratio of vertical openings. Where openings connected to the outdoors through vertical ducts are provided in accordance with Section 703.1, the ratio of vertical openings shall be the sum of the net free areas of both such openings, divided by the sum of the required areas for both such openings as determined in accordance with Section 703.1.4. 70 4.1.5 Ratio of interior spaces. The ratio of interior spaces shall be the available volume of all communicating spaces, divided by the required volume as determined in accordance with Sections 702.2 and 702.3. 704.1.6 Prorating of inside and outdoor air. In spaces that utilize a combination of inside and outdoor air, the sum of the ratios of all direct openings, horizontal openings, vertical openings and interior spaces shall equal or exceed 1. SECTION MC 705 COMBINED USE OF INSIDE AND OUTDOOR AIR (CONDITI ON 2) 705.1 General. This section shall apply only to appliances located in unconfined spaces in buildings of unusually tight construction. Combustion air supplied by a combined use of indoor and outdoor air shall be supplied through openings and ducts ext ending to the appliance room or to the vicinity of the appliance. 705.1.1 Openings and supply ducts. Openings shall be provided, located and sized in accordance with Sections 702.3.1 and 702.3.2; additionally, there shall be one opening to the outdoors hav ing a free area of at least 1 square inch per 5,000 Btu/h (440 mm 2 /kW) of total input of all appliances in the space. SECTION MC 706 MECHANICAL COMBUSTION AIR SUPPLY 706.1 Rate of air supplied. Where all combustion air is provided by a mechanical air suppl y system, the combustion air shall be supplied from the outdoors at a rate of not less than 0.35 cubic feet per minute per 1,000 Btu/h (0.034 COMBUSTION, VENTILATION, AND DILUTION AIR m 3 /min per kW) of total input rating for all the fuel - burning appliances located within the space. Combustion air rates shall also comply with any applicable rules of the New York City Department of Environmental Protection. The mechanical air supply shall be sufficient to accommodate combustion air, ventilation air, and dilution air re- quirements of the installation. 706.1.1 Appliance interlock. Each of the appliances served shall be interlocked with the mechanical air supply system to prevent main burner operation when the mechanical air supply system is not in operation. The air flow and the damper operation shall be proven prior to burner operation. SECTION MC 707 DIRECT CONNECTION 707.1 General. Fuel - burning appliances that are listed and labeled for direct combustion air connection to the out- doors shall be installed in accordance with the manufacturer’s instruction s. SECTION MC 708 COMBUSTION AIR DUCTS 708.1 General. Combustion air ducts shall comply with all of the following: 1. Be of galvanized steel complying with Chapter 6 or of equivalent corrosion - resistant material approved for this application. Exception: Within dwelling units, unobstructed stud and joist spaces shall not be prohibited from conveying combustion air, provided that not more than one required fireblock is removed. 2. Have a minimum dimension of 3 inches ( 76.2 mm) in all directions. 3. Termin ate in an unobstructed space allowing free movement of combustion air to the appliances. 4. Have the same cross - sectional areas as the free area of the openings to which they connect. 5. Serve a single appliance enclosure. 6. Not serve both upper and lo wer combustion air openings where both such openings are used. The separation between ducts serving upper and lower combustion air openings shall be maintained to the source of combus- tion air. 7. Not be screened where terminating in an attic space. 8. No t slope downward toward the source of combustion air, where serving the upper required combustion air opening. 9. Be constructed so that the remaining space surrounding a chimney or chimney liner, installed within a masonry, metal or factory - built chimney cannot be used to supply combustion, ventilation and dilution air, except for direct vent appliances designed and installed in accordance with the equipment manufacturer’s instructions and listing. 10. Be insulated in accordance with Section C402.5.3 of t he New York City Energy Conservation Code . SECTION MC 709 OPENING OBSTRUCTIONS 709.1 General. The required size of openings for combustion, ventilation, and dilution air shall be based on the net free area of each opening. The net free area of an opening s hall be that specified by the manufacturer of the opening covering. In the absence of such information, openings covered with metal louvers shall be deemed to have a net free area of 60 percent of the area of the opening, and openings covered with wood lou vers shall be deemed to have a net free area of 10 percent of the area of the opening. Louvers and grills shall be fixed in the open position. Exception: Operable louvers shall be interlocked with the appliance so that they are proven to be in the full open position prior to main burner ignition and during main burner operation. Means shall be provided to prevent the COMBUSTION, VENTILATION, AND DILUTION AIR main burner from igniting if the louvers fail to open during burner startup and to shut down the main burner if the louvers close during operation. 709.2 Dampered openings. Where the combustion air openings are provided with automatic, smoke or fire dampers, the dampers shall be electrically interlocked with the appliances served, so as to prevent operation of any appliance that draws combustion and dilution air from the room when any of the dampers are closed. Manually operated damp- ers shall not be installed in combustion air ope nings. The damper opening shall be proven prior to burner operation . Dampers shall be provided in accordance with Chapter 6. 709.3 Caution sign. A sign stating, “Louvers, dampers and/or ventilation openings must not be blocked or disabled.” shall be perman ently affixed, in clear view, and adjacent to the opening(s) within the room containing the equipment. The letters used on the sign shall be at least 1 inch ( 25.4 mm) in height. SECTION MC 710 OPENING LOCATION AND PROTECTION 710.1 General. Combustion air o penings to the outdoors shall comply with the location and protection provisions applicable to outside air intake openings of Sections 401.5 and 401.6.