‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. CHIMNEYS AND VENTS 804.3.7 Exhauster sizing. Mechanical flue or power exhausters and the chimney or vent system served shall be sized and installed in accordance with the manufacturer’s instructions. 804.3.8 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such sy stem complies with all of the following requirements: 1. The mechanical draft device shall be listed and labeled in accordance with UL 378, and shall be installed in accordance with the manufacturer’s instructions. 2. A device shall be installed in the roo m with the appliance or fireplace that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power, at any time that the mechan- ical draft device is turned on. This device shall be equipped with a battery bac kup if it receives power from the building wiring. 3. A smoke detector or alarm, and a carbon monoxide detector or alarm, shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives pow er from the building wiring. SECTION MC 805 FACTORY - BUILT CHIMNEYS 805.1 Listing. Factory - built chimneys shall be listed and labeled and shall be installed and terminated in accordance with this code and the manufacturer’s instructions. 805.2 Solid fuel - bu rning appliances. Factory - built chimneys installed in dwelling units with solid fuel - burning ap- pliances shall comply with the Type HT requirements of UL 103 and shall be marked “Type HT” and “Residential Type and Building Heating Appliance Chimney.” Exceptions: 1. Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked “Residential Type and Building Heating Appliance Chimney.” 2. Chimneys for use with open combustion chamber appliances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be marked “Building Heating Appliance Chimney” or “Residential Type and Building Heating Appliance Chimney.” 805.3 Factory - built chimney offsets. Where a factory - built chimney serving a solid fuel - burning appliance or fire- place incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not i nclude more than four elbows. Exception: Factory - built chimneys listed to UL103 Type HT serving a solid fuel - burning appliance or fireplace may offset at angles greater than 30 degrees from vertical if listed for such angles and installed in accordance with manufacturer’s instructions. Cleanouts shall be installed in accordance with Section 801.13. 805.4 Support. Where factory - built chimneys are supported by structural members, such as joists and rafters, such members shall be designed to supp ort the additional load. 805.5 Medium - heat appliances. Factory - built chimneys for medium - heat appliances producing flue gases having a temperature above 1,000 ° F ( 537.8° C ), measured at the entrance to the chimney shall comply with UL 959. 805.6 Decorative s hrouds. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are in- stalled in accordance with Section 304.1. 805.7 Factory - built fireplaces. Chimneys for use with factory - built fireplaces shall comply with the requirements of UL 127. CHIMNEYS AND VENTS SECTION MC 806 METAL CHIMNEYS 806.1 General. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 806.2 Exteri or metal chimneys. Exterior metal chimneys shall be stainless steel. SECTION MC 807 CHANGES IN APPLIANCE FUELS 807.1 Changes in appliance fuels. Conversion of appliances from solid or liquid fuel to, or the addition of, natural gas shall be installed per t he New York City Fuel Gas Code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if: 1. The chimney design meets the requirements of this chapter for the conversion fuel, and the chimney is test run and smoke tested in accordance with Section 810. 2. The chimney is sized to provide adequate draft and vent the combustion products for the new fuel. 3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits. SECTION MC 808 REDUCTION OF FLUE SIZE 808.1 Reduction of flue size. Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood - burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this chapter. SECTION MC 809 CHIMNEY SUPPORTED FROM EQUIPMENT 809.1 Chimney support. Chimneys shall not be supported by the equipment they serve, unless such eq uipment has been specifically designed for such loads. SECTION MC 810 TEST RUN AND SMOKE TEST ‡‡‡ 810.1 Test run. All new and altered chimneys, and chimneys to which a new appliance has been connected, shall be test run under operating conditions to demonst rate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The test run shall be conducted by a registered design professional or special inspector responsible for the test, and the results of such test run shall be certified as correct by such professional or special inspector and submitted in writing to the department. Refer to Section 1705.32 of the New York City Building Code for additional requirements. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. CHIMNEYS AND VENTS Such test shall not be required to be witnessed by the depar tment, registered design professional or special inspector. 810.3 Smoke test. To determine the tightness of chimney construction , a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirements of t his chapter, and the test shall be repeated until the results are satisfactory. 3. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the st ack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 - inch (13 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspect ion of the chimney. 4. Refer to Section 170 5 .32 ‡ of the New York City Building Code for requirements for existing and new negative pressure chimneys and vents. SECTION MC 811 EXHAUST GASES FROM INTERNAL COMBUSTION ENGINES AND TURBINES 811.1 Exhaust system construction. The exhaust system from internal combustion engines shall be constructed in accordance with NFPA 211, NFPA 37, and based on the temperature of the flue gas entering the exhaust system, and in accordance with the following: 1. The exhau st system, if factory built, shall be installed in accordance with its listing and manufacturer’s instruc- tions. 1.1. Exhaust systems with flue gas temperatures greater than 300°F (148.9°C) shall be listed to UL 103 or UL 2561 and be rated for a minimum of 60 inch w.c. (14 934.3 Pa). 1.2. Exhaust systems with flue gas temperatures not more than 300°F (148.9°C) and that are capable of causing excessive condensate production in the exhaust system shall be listed to UL 103 or UL 2561 and UL 1738 and be rated fo r a pressure suitable for the operating conditions. 2. The exhaust system, if field fabricated, shall be constructed of at least 3 / 16 - inch (4.8 mm) steel, or of other equiv- alent metal of similar strength and resistance to the temperature and corrosive acti on of the exhaust gases. No lining shall be required. 3. Where the exhaust system runs inside a building, it shall be insulated adequately for the equipment operating temperature, so that the surface temperature shall be not more than 200°F (93.3°C). 4. Wh ere the exhaust system runs inside a building outside of the room containing the equipment, it shall be en- closed in fire - rated construction with a fire rating equal to the fire rating of the construction of the room. 5. All joints shall be constructed so a s to be gas tight under all operating conditions and tested in accordance with Section 810. 811.2 Emergency and standby generator discharge opening termination requirements. The location of discharge outlets for emergency and standby internal combustion en gines shall comply with the requirements of NFPA 37 so that the flue gases are not directed to jeopardize the health or safety of people, overheat combustible structures, nor enter building openings in the vicinity of the outlet, nor shall the location of such openings cause the condensate leaving the outlet to come into contact with people. 811.2.1 Interference. No discharge opening shall be located and constructed so as to interfere with the proper functioning of other openings in the same building or adjoining buildings, to interfere unreasonably with the occupants of the same building or adjoining buildings, or with the general public, or to create a fire or health hazard . ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. CHIMNEYS AND VENTS 804.3.7 Exhauster sizing. Mechanical flue or power exhausters and the chimney or vent system served shall be sized and installed in accordance with the manufacturer’s instructions. 804.3.8 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such sy stem complies with all of the following requirements: 1. The mechanical draft device shall be listed and labeled in accordance with UL 378, and shall be installed in accordance with the manufacturer’s instructions. 2. A device shall be installed in the roo m with the appliance or fireplace that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power, at any time that the mechan- ical draft device is turned on. This device shall be equipped with a battery bac kup if it receives power from the building wiring. 3. A smoke detector or alarm, and a carbon monoxide detector or alarm, shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives pow er from the building wiring. SECTION MC 805 FACTORY - BUILT CHIMNEYS 805.1 Listing. Factory - built chimneys shall be listed and labeled and shall be installed and terminated in accordance with this code and the manufacturer’s instructions. 805.2 Solid fuel - bu rning appliances. Factory - built chimneys installed in dwelling units with solid fuel - burning ap- pliances shall comply with the Type HT requirements of UL 103 and shall be marked “Type HT” and “Residential Type and Building Heating Appliance Chimney.” Exceptions: 1. Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked “Residential Type and Building Heating Appliance Chimney.” 2. Chimneys for use with open combustion chamber appliances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be marked “Building Heating Appliance Chimney” or “Residential Type and Building Heating Appliance Chimney.” 805.3 Factory - built chimney offsets. Where a factory - built chimney serving a solid fuel - burning appliance or fire- place incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not i nclude more than four elbows. Exception: Factory - built chimneys listed to UL103 Type HT serving a solid fuel - burning appliance or fireplace may offset at angles greater than 30 degrees from vertical if listed for such angles and installed in accordance with manufacturer’s instructions. Cleanouts shall be installed in accordance with Section 801.13. 805.4 Support. Where factory - built chimneys are supported by structural members, such as joists and rafters, such members shall be designed to supp ort the additional load. 805.5 Medium - heat appliances. Factory - built chimneys for medium - heat appliances producing flue gases having a temperature above 1,000 ° F ( 537.8° C ), measured at the entrance to the chimney shall comply with UL 959. 805.6 Decorative s hrouds. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are in- stalled in accordance with Section 304.1. 805.7 Factory - built fireplaces. Chimneys for use with factory - built fireplaces shall comply with the requirements of UL 127. CHIMNEYS AND VENTS SECTION MC 806 METAL CHIMNEYS 806.1 General. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 806.2 Exteri or metal chimneys. Exterior metal chimneys shall be stainless steel. SECTION MC 807 CHANGES IN APPLIANCE FUELS 807.1 Changes in appliance fuels. Conversion of appliances from solid or liquid fuel to, or the addition of, natural gas shall be installed per t he New York City Fuel Gas Code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if: 1. The chimney design meets the requirements of this chapter for the conversion fuel, and the chimney is test run and smoke tested in accordance with Section 810. 2. The chimney is sized to provide adequate draft and vent the combustion products for the new fuel. 3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits. SECTION MC 808 REDUCTION OF FLUE SIZE 808.1 Reduction of flue size. Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood - burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this chapter. SECTION MC 809 CHIMNEY SUPPORTED FROM EQUIPMENT 809.1 Chimney support. Chimneys shall not be supported by the equipment they serve, unless such eq uipment has been specifically designed for such loads. SECTION MC 810 TEST RUN AND SMOKE TEST ‡‡‡ 810.1 Test run. All new and altered chimneys, and chimneys to which a new appliance has been connected, shall be test run under operating conditions to demonst rate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The test run shall be conducted by a registered design professional or special inspector responsible for the test, and the results of such test run shall be certified as correct by such professional or special inspector and submitted in writing to the department. Refer to Section 1705.32 of the New York City Building Code for additional requirements. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. CHIMNEYS AND VENTS Such test shall not be required to be witnessed by the depar tment, registered design professional or special inspector. 810.3 Smoke test. To determine the tightness of chimney construction , a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirements of t his chapter, and the test shall be repeated until the results are satisfactory. 3. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the st ack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 - inch (13 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspect ion of the chimney. 4. Refer to Section 170 5 .32 ‡ of the New York City Building Code for requirements for existing and new negative pressure chimneys and vents. SECTION MC 811 EXHAUST GASES FROM INTERNAL COMBUSTION ENGINES AND TURBINES 811.1 Exhaust system construction. The exhaust system from internal combustion engines shall be constructed in accordance with NFPA 211, NFPA 37, and based on the temperature of the flue gas entering the exhaust system, and in accordance with the following: 1. The exhau st system, if factory built, shall be installed in accordance with its listing and manufacturer’s instruc- tions. 1.1. Exhaust systems with flue gas temperatures greater than 300°F (148.9°C) shall be listed to UL 103 or UL 2561 and be rated for a minimum of 60 inch w.c. (14 934.3 Pa). 1.2. Exhaust systems with flue gas temperatures not more than 300°F (148.9°C) and that are capable of causing excessive condensate production in the exhaust system shall be listed to UL 103 or UL 2561 and UL 1738 and be rated fo r a pressure suitable for the operating conditions. 2. The exhaust system, if field fabricated, shall be constructed of at least 3 / 16 - inch (4.8 mm) steel, or of other equiv- alent metal of similar strength and resistance to the temperature and corrosive acti on of the exhaust gases. No lining shall be required. 3. Where the exhaust system runs inside a building, it shall be insulated adequately for the equipment operating temperature, so that the surface temperature shall be not more than 200°F (93.3°C). 4. Wh ere the exhaust system runs inside a building outside of the room containing the equipment, it shall be en- closed in fire - rated construction with a fire rating equal to the fire rating of the construction of the room. 5. All joints shall be constructed so a s to be gas tight under all operating conditions and tested in accordance with Section 810. 811.2 Emergency and standby generator discharge opening termination requirements. The location of discharge outlets for emergency and standby internal combustion en gines shall comply with the requirements of NFPA 37 so that the flue gases are not directed to jeopardize the health or safety of people, overheat combustible structures, nor enter building openings in the vicinity of the outlet, nor shall the location of such openings cause the condensate leaving the outlet to come into contact with people. 811.2.1 Interference. No discharge opening shall be located and constructed so as to interfere with the proper functioning of other openings in the same building or adjoining buildings, to interfere unreasonably with the occupants of the same building or adjoining buildings, or with the general public, or to create a fire or health hazard . ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. CHIMNEYS AND VENTS 804.3.7 Exhauster sizing. Mechanical flue or power exhausters and the chimney or vent system served shall be sized and installed in accordance with the manufacturer’s instructions. 804.3.8 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such sy stem complies with all of the following requirements: 1. The mechanical draft device shall be listed and labeled in accordance with UL 378, and shall be installed in accordance with the manufacturer’s instructions. 2. A device shall be installed in the roo m with the appliance or fireplace that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power, at any time that the mechan- ical draft device is turned on. This device shall be equipped with a battery bac kup if it receives power from the building wiring. 3. A smoke detector or alarm, and a carbon monoxide detector or alarm, shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives pow er from the building wiring. SECTION MC 805 FACTORY - BUILT CHIMNEYS 805.1 Listing. Factory - built chimneys shall be listed and labeled and shall be installed and terminated in accordance with this code and the manufacturer’s instructions. 805.2 Solid fuel - bu rning appliances. Factory - built chimneys installed in dwelling units with solid fuel - burning ap- pliances shall comply with the Type HT requirements of UL 103 and shall be marked “Type HT” and “Residential Type and Building Heating Appliance Chimney.” Exceptions: 1. Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked “Residential Type and Building Heating Appliance Chimney.” 2. Chimneys for use with open combustion chamber appliances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be marked “Building Heating Appliance Chimney” or “Residential Type and Building Heating Appliance Chimney.” 805.3 Factory - built chimney offsets. Where a factory - built chimney serving a solid fuel - burning appliance or fire- place incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not i nclude more than four elbows. Exception: Factory - built chimneys listed to UL103 Type HT serving a solid fuel - burning appliance or fireplace may offset at angles greater than 30 degrees from vertical if listed for such angles and installed in accordance with manufacturer’s instructions. Cleanouts shall be installed in accordance with Section 801.13. 805.4 Support. Where factory - built chimneys are supported by structural members, such as joists and rafters, such members shall be designed to supp ort the additional load. 805.5 Medium - heat appliances. Factory - built chimneys for medium - heat appliances producing flue gases having a temperature above 1,000 ° F ( 537.8° C ), measured at the entrance to the chimney shall comply with UL 959. 805.6 Decorative s hrouds. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are in- stalled in accordance with Section 304.1. 805.7 Factory - built fireplaces. Chimneys for use with factory - built fireplaces shall comply with the requirements of UL 127. CHIMNEYS AND VENTS SECTION MC 806 METAL CHIMNEYS 806.1 General. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 806.2 Exteri or metal chimneys. Exterior metal chimneys shall be stainless steel. SECTION MC 807 CHANGES IN APPLIANCE FUELS 807.1 Changes in appliance fuels. Conversion of appliances from solid or liquid fuel to, or the addition of, natural gas shall be installed per t he New York City Fuel Gas Code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if: 1. The chimney design meets the requirements of this chapter for the conversion fuel, and the chimney is test run and smoke tested in accordance with Section 810. 2. The chimney is sized to provide adequate draft and vent the combustion products for the new fuel. 3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits. SECTION MC 808 REDUCTION OF FLUE SIZE 808.1 Reduction of flue size. Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood - burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this chapter. SECTION MC 809 CHIMNEY SUPPORTED FROM EQUIPMENT 809.1 Chimney support. Chimneys shall not be supported by the equipment they serve, unless such eq uipment has been specifically designed for such loads. SECTION MC 810 TEST RUN AND SMOKE TEST ‡‡‡ 810.1 Test run. All new and altered chimneys, and chimneys to which a new appliance has been connected, shall be test run under operating conditions to demonst rate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The test run shall be conducted by a registered design professional or special inspector responsible for the test, and the results of such test run shall be certified as correct by such professional or special inspector and submitted in writing to the department. Refer to Section 1705.32 of the New York City Building Code for additional requirements. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. CHIMNEYS AND VENTS Such test shall not be required to be witnessed by the depar tment, registered design professional or special inspector. 810.3 Smoke test. To determine the tightness of chimney construction , a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirements of t his chapter, and the test shall be repeated until the results are satisfactory. 3. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the st ack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 - inch (13 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspect ion of the chimney. 4. Refer to Section 170 5 .32 ‡ of the New York City Building Code for requirements for existing and new negative pressure chimneys and vents. SECTION MC 811 EXHAUST GASES FROM INTERNAL COMBUSTION ENGINES AND TURBINES 811.1 Exhaust system construction. The exhaust system from internal combustion engines shall be constructed in accordance with NFPA 211, NFPA 37, and based on the temperature of the flue gas entering the exhaust system, and in accordance with the following: 1. The exhau st system, if factory built, shall be installed in accordance with its listing and manufacturer’s instruc- tions. 1.1. Exhaust systems with flue gas temperatures greater than 300°F (148.9°C) shall be listed to UL 103 or UL 2561 and be rated for a minimum of 60 inch w.c. (14 934.3 Pa). 1.2. Exhaust systems with flue gas temperatures not more than 300°F (148.9°C) and that are capable of causing excessive condensate production in the exhaust system shall be listed to UL 103 or UL 2561 and UL 1738 and be rated fo r a pressure suitable for the operating conditions. 2. The exhaust system, if field fabricated, shall be constructed of at least 3 / 16 - inch (4.8 mm) steel, or of other equiv- alent metal of similar strength and resistance to the temperature and corrosive acti on of the exhaust gases. No lining shall be required. 3. Where the exhaust system runs inside a building, it shall be insulated adequately for the equipment operating temperature, so that the surface temperature shall be not more than 200°F (93.3°C). 4. Wh ere the exhaust system runs inside a building outside of the room containing the equipment, it shall be en- closed in fire - rated construction with a fire rating equal to the fire rating of the construction of the room. 5. All joints shall be constructed so a s to be gas tight under all operating conditions and tested in accordance with Section 810. 811.2 Emergency and standby generator discharge opening termination requirements. The location of discharge outlets for emergency and standby internal combustion en gines shall comply with the requirements of NFPA 37 so that the flue gases are not directed to jeopardize the health or safety of people, overheat combustible structures, nor enter building openings in the vicinity of the outlet, nor shall the location of such openings cause the condensate leaving the outlet to come into contact with people. 811.2.1 Interference. No discharge opening shall be located and constructed so as to interfere with the proper functioning of other openings in the same building or adjoining buildings, to interfere unreasonably with the occupants of the same building or adjoining buildings, or with the general public, or to create a fire or health hazard . CHIMNEYS AND VENTS 811.2.2 Chimneys. The exhaust pipe may be connected to a chimney used for other equipment, provided that the operation of the engine does not adversely affect the operation of the other equipment so that it is in violation of the New York City Air Pollut ion Control Code. 811.3 All other engine and turbine discharge opening termination requirements. The location of the discharge outlet from all other engines and turbines shall comply with the termination requirements of Section 801.21, Item 2 or Section 80 1.21, Item 3 based on the temperature of the flue gas entering the exhaust system. 811.4 Chimneys. The exhaust system may be connected to a chimney used for other appliances, provided that the chimney complies with Section 811.1, Item 1 or Section 811.1, I tem 2 and the operation of the engine does not adversely affect the operation of the other appliances and is in accordance with the New York City Air Pollution Control Code. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. CHIMNEYS AND VENTS 804.3.7 Exhauster sizing. Mechanical flue or power exhausters and the chimney or vent system served shall be sized and installed in accordance with the manufacturer’s instructions. 804.3.8 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such sy stem complies with all of the following requirements: 1. The mechanical draft device shall be listed and labeled in accordance with UL 378, and shall be installed in accordance with the manufacturer’s instructions. 2. A device shall be installed in the roo m with the appliance or fireplace that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power, at any time that the mechan- ical draft device is turned on. This device shall be equipped with a battery bac kup if it receives power from the building wiring. 3. A smoke detector or alarm, and a carbon monoxide detector or alarm, shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives pow er from the building wiring. SECTION MC 805 FACTORY - BUILT CHIMNEYS 805.1 Listing. Factory - built chimneys shall be listed and labeled and shall be installed and terminated in accordance with this code and the manufacturer’s instructions. 805.2 Solid fuel - bu rning appliances. Factory - built chimneys installed in dwelling units with solid fuel - burning ap- pliances shall comply with the Type HT requirements of UL 103 and shall be marked “Type HT” and “Residential Type and Building Heating Appliance Chimney.” Exceptions: 1. Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked “Residential Type and Building Heating Appliance Chimney.” 2. Chimneys for use with open combustion chamber appliances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be marked “Building Heating Appliance Chimney” or “Residential Type and Building Heating Appliance Chimney.” 805.3 Factory - built chimney offsets. Where a factory - built chimney serving a solid fuel - burning appliance or fire- place incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not i nclude more than four elbows. Exception: Factory - built chimneys listed to UL103 Type HT serving a solid fuel - burning appliance or fireplace may offset at angles greater than 30 degrees from vertical if listed for such angles and installed in accordance with manufacturer’s instructions. Cleanouts shall be installed in accordance with Section 801.13. 805.4 Support. Where factory - built chimneys are supported by structural members, such as joists and rafters, such members shall be designed to supp ort the additional load. 805.5 Medium - heat appliances. Factory - built chimneys for medium - heat appliances producing flue gases having a temperature above 1,000 ° F ( 537.8° C ), measured at the entrance to the chimney shall comply with UL 959. 805.6 Decorative s hrouds. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are in- stalled in accordance with Section 304.1. 805.7 Factory - built fireplaces. Chimneys for use with factory - built fireplaces shall comply with the requirements of UL 127. CHIMNEYS AND VENTS SECTION MC 806 METAL CHIMNEYS 806.1 General. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 806.2 Exteri or metal chimneys. Exterior metal chimneys shall be stainless steel. SECTION MC 807 CHANGES IN APPLIANCE FUELS 807.1 Changes in appliance fuels. Conversion of appliances from solid or liquid fuel to, or the addition of, natural gas shall be installed per t he New York City Fuel Gas Code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if: 1. The chimney design meets the requirements of this chapter for the conversion fuel, and the chimney is test run and smoke tested in accordance with Section 810. 2. The chimney is sized to provide adequate draft and vent the combustion products for the new fuel. 3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits. SECTION MC 808 REDUCTION OF FLUE SIZE 808.1 Reduction of flue size. Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood - burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this chapter. SECTION MC 809 CHIMNEY SUPPORTED FROM EQUIPMENT 809.1 Chimney support. Chimneys shall not be supported by the equipment they serve, unless such eq uipment has been specifically designed for such loads. SECTION MC 810 TEST RUN AND SMOKE TEST ‡‡‡ 810.1 Test run. All new and altered chimneys, and chimneys to which a new appliance has been connected, shall be test run under operating conditions to demonst rate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The test run shall be conducted by a registered design professional or special inspector responsible for the test, and the results of such test run shall be certified as correct by such professional or special inspector and submitted in writing to the department. Refer to Section 1705.32 of the New York City Building Code for additional requirements. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. CHIMNEYS AND VENTS Such test shall not be required to be witnessed by the depar tment, registered design professional or special inspector. 810.3 Smoke test. To determine the tightness of chimney construction , a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirements of t his chapter, and the test shall be repeated until the results are satisfactory. 3. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the st ack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 - inch (13 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspect ion of the chimney. 4. Refer to Section 170 5 .32 ‡ of the New York City Building Code for requirements for existing and new negative pressure chimneys and vents. SECTION MC 811 EXHAUST GASES FROM INTERNAL COMBUSTION ENGINES AND TURBINES 811.1 Exhaust system construction. The exhaust system from internal combustion engines shall be constructed in accordance with NFPA 211, NFPA 37, and based on the temperature of the flue gas entering the exhaust system, and in accordance with the following: 1. The exhau st system, if factory built, shall be installed in accordance with its listing and manufacturer’s instruc- tions. 1.1. Exhaust systems with flue gas temperatures greater than 300°F (148.9°C) shall be listed to UL 103 or UL 2561 and be rated for a minimum of 60 inch w.c. (14 934.3 Pa). 1.2. Exhaust systems with flue gas temperatures not more than 300°F (148.9°C) and that are capable of causing excessive condensate production in the exhaust system shall be listed to UL 103 or UL 2561 and UL 1738 and be rated fo r a pressure suitable for the operating conditions. 2. The exhaust system, if field fabricated, shall be constructed of at least 3 / 16 - inch (4.8 mm) steel, or of other equiv- alent metal of similar strength and resistance to the temperature and corrosive acti on of the exhaust gases. No lining shall be required. 3. Where the exhaust system runs inside a building, it shall be insulated adequately for the equipment operating temperature, so that the surface temperature shall be not more than 200°F (93.3°C). 4. Wh ere the exhaust system runs inside a building outside of the room containing the equipment, it shall be en- closed in fire - rated construction with a fire rating equal to the fire rating of the construction of the room. 5. All joints shall be constructed so a s to be gas tight under all operating conditions and tested in accordance with Section 810. 811.2 Emergency and standby generator discharge opening termination requirements. The location of discharge outlets for emergency and standby internal combustion en gines shall comply with the requirements of NFPA 37 so that the flue gases are not directed to jeopardize the health or safety of people, overheat combustible structures, nor enter building openings in the vicinity of the outlet, nor shall the location of such openings cause the condensate leaving the outlet to come into contact with people. 811.2.1 Interference. No discharge opening shall be located and constructed so as to interfere with the proper functioning of other openings in the same building or adjoining buildings, to interfere unreasonably with the occupants of the same building or adjoining buildings, or with the general public, or to create a fire or health hazard . CHIMNEYS AND VENTS 811.2.2 Chimneys. The exhaust pipe may be connected to a chimney used for other equipment, provided that the operation of the engine does not adversely affect the operation of the other equipment so that it is in violation of the New York City Air Pollut ion Control Code. 811.3 All other engine and turbine discharge opening termination requirements. The location of the discharge outlet from all other engines and turbines shall comply with the termination requirements of Section 801.21, Item 2 or Section 80 1.21, Item 3 based on the temperature of the flue gas entering the exhaust system. 811.4 Chimneys. The exhaust system may be connected to a chimney used for other appliances, provided that the chimney complies with Section 811.1, Item 1 or Section 811.1, I tem 2 and the operation of the engine does not adversely affect the operation of the other appliances and is in accordance with the New York City Air Pollution Control Code. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. CHIMNEYS AND VENTS 804.3.7 Exhauster sizing. Mechanical flue or power exhausters and the chimney or vent system served shall be sized and installed in accordance with the manufacturer’s instructions. 804.3.8 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such sy stem complies with all of the following requirements: 1. The mechanical draft device shall be listed and labeled in accordance with UL 378, and shall be installed in accordance with the manufacturer’s instructions. 2. A device shall be installed in the roo m with the appliance or fireplace that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power, at any time that the mechan- ical draft device is turned on. This device shall be equipped with a battery bac kup if it receives power from the building wiring. 3. A smoke detector or alarm, and a carbon monoxide detector or alarm, shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives pow er from the building wiring. SECTION MC 805 FACTORY - BUILT CHIMNEYS 805.1 Listing. Factory - built chimneys shall be listed and labeled and shall be installed and terminated in accordance with this code and the manufacturer’s instructions. 805.2 Solid fuel - bu rning appliances. Factory - built chimneys installed in dwelling units with solid fuel - burning ap- pliances shall comply with the Type HT requirements of UL 103 and shall be marked “Type HT” and “Residential Type and Building Heating Appliance Chimney.” Exceptions: 1. Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked “Residential Type and Building Heating Appliance Chimney.” 2. Chimneys for use with open combustion chamber appliances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be marked “Building Heating Appliance Chimney” or “Residential Type and Building Heating Appliance Chimney.” 805.3 Factory - built chimney offsets. Where a factory - built chimney serving a solid fuel - burning appliance or fire- place incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not i nclude more than four elbows. Exception: Factory - built chimneys listed to UL103 Type HT serving a solid fuel - burning appliance or fireplace may offset at angles greater than 30 degrees from vertical if listed for such angles and installed in accordance with manufacturer’s instructions. Cleanouts shall be installed in accordance with Section 801.13. 805.4 Support. Where factory - built chimneys are supported by structural members, such as joists and rafters, such members shall be designed to supp ort the additional load. 805.5 Medium - heat appliances. Factory - built chimneys for medium - heat appliances producing flue gases having a temperature above 1,000 ° F ( 537.8° C ), measured at the entrance to the chimney shall comply with UL 959. 805.6 Decorative s hrouds. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are in- stalled in accordance with Section 304.1. 805.7 Factory - built fireplaces. Chimneys for use with factory - built fireplaces shall comply with the requirements of UL 127. CHIMNEYS AND VENTS SECTION MC 806 METAL CHIMNEYS 806.1 General. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 806.2 Exteri or metal chimneys. Exterior metal chimneys shall be stainless steel. SECTION MC 807 CHANGES IN APPLIANCE FUELS 807.1 Changes in appliance fuels. Conversion of appliances from solid or liquid fuel to, or the addition of, natural gas shall be installed per t he New York City Fuel Gas Code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if: 1. The chimney design meets the requirements of this chapter for the conversion fuel, and the chimney is test run and smoke tested in accordance with Section 810. 2. The chimney is sized to provide adequate draft and vent the combustion products for the new fuel. 3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits. SECTION MC 808 REDUCTION OF FLUE SIZE 808.1 Reduction of flue size. Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood - burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this chapter. SECTION MC 809 CHIMNEY SUPPORTED FROM EQUIPMENT 809.1 Chimney support. Chimneys shall not be supported by the equipment they serve, unless such eq uipment has been specifically designed for such loads. SECTION MC 810 TEST RUN AND SMOKE TEST ‡‡‡ 810.1 Test run. All new and altered chimneys, and chimneys to which a new appliance has been connected, shall be test run under operating conditions to demonst rate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The test run shall be conducted by a registered design professional or special inspector responsible for the test, and the results of such test run shall be certified as correct by such professional or special inspector and submitted in writing to the department. Refer to Section 1705.32 of the New York City Building Code for additional requirements. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. CHIMNEYS AND VENTS Such test shall not be required to be witnessed by the depar tment, registered design professional or special inspector. 810.3 Smoke test. To determine the tightness of chimney construction , a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirements of t his chapter, and the test shall be repeated until the results are satisfactory. 3. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the st ack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 - inch (13 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspect ion of the chimney. 4. Refer to Section 170 5 .32 ‡ of the New York City Building Code for requirements for existing and new negative pressure chimneys and vents. SECTION MC 811 EXHAUST GASES FROM INTERNAL COMBUSTION ENGINES AND TURBINES 811.1 Exhaust system construction. The exhaust system from internal combustion engines shall be constructed in accordance with NFPA 211, NFPA 37, and based on the temperature of the flue gas entering the exhaust system, and in accordance with the following: 1. The exhau st system, if factory built, shall be installed in accordance with its listing and manufacturer’s instruc- tions. 1.1. Exhaust systems with flue gas temperatures greater than 300°F (148.9°C) shall be listed to UL 103 or UL 2561 and be rated for a minimum of 60 inch w.c. (14 934.3 Pa). 1.2. Exhaust systems with flue gas temperatures not more than 300°F (148.9°C) and that are capable of causing excessive condensate production in the exhaust system shall be listed to UL 103 or UL 2561 and UL 1738 and be rated fo r a pressure suitable for the operating conditions. 2. The exhaust system, if field fabricated, shall be constructed of at least 3 / 16 - inch (4.8 mm) steel, or of other equiv- alent metal of similar strength and resistance to the temperature and corrosive acti on of the exhaust gases. No lining shall be required. 3. Where the exhaust system runs inside a building, it shall be insulated adequately for the equipment operating temperature, so that the surface temperature shall be not more than 200°F (93.3°C). 4. Wh ere the exhaust system runs inside a building outside of the room containing the equipment, it shall be en- closed in fire - rated construction with a fire rating equal to the fire rating of the construction of the room. 5. All joints shall be constructed so a s to be gas tight under all operating conditions and tested in accordance with Section 810. 811.2 Emergency and standby generator discharge opening termination requirements. The location of discharge outlets for emergency and standby internal combustion en gines shall comply with the requirements of NFPA 37 so that the flue gases are not directed to jeopardize the health or safety of people, overheat combustible structures, nor enter building openings in the vicinity of the outlet, nor shall the location of such openings cause the condensate leaving the outlet to come into contact with people. 811.2.1 Interference. No discharge opening shall be located and constructed so as to interfere with the proper functioning of other openings in the same building or adjoining buildings, to interfere unreasonably with the occupants of the same building or adjoining buildings, or with the general public, or to create a fire or health hazard . CHIMNEYS AND VENTS 811.2.2 Chimneys. The exhaust pipe may be connected to a chimney used for other equipment, provided that the operation of the engine does not adversely affect the operation of the other equipment so that it is in violation of the New York City Air Pollut ion Control Code. 811.3 All other engine and turbine discharge opening termination requirements. The location of the discharge outlet from all other engines and turbines shall comply with the termination requirements of Section 801.21, Item 2 or Section 80 1.21, Item 3 based on the temperature of the flue gas entering the exhaust system. 811.4 Chimneys. The exhaust system may be connected to a chimney used for other appliances, provided that the chimney complies with Section 811.1, Item 1 or Section 811.1, I tem 2 and the operation of the engine does not adversely affect the operation of the other appliances and is in accordance with the New York City Air Pollution Control Code. ‡‡‡ Chapter 8 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 8 CHIMNEYS AND VENTS SECTION MC 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, design, minimum safety requirements , repair and approval of factory - built chimneys, chimney liners, vents and connectors , and field - built chimneys and connect- ors for all nongas - fired appliances. This chapter shall also govern the utilization of masonry chimneys. Gas - fired appliances shall be vented in accordance with the New Yor k City Fuel Gas Code. The construction, repair, mainte- nance and approval of masonry chimneys shall be regulated by the New York City Building Code. Venting systems shall be designed in accordance with this chapter and comply with the requirements of the Ne w York City Air Pollu- tion Control Code . 801.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply with the requirements of Section 28 - 104.13 of the New York City Administrative Code and Sections 801.1.1.1 through 801.1.1.8 of this code. 801.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any portion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to make them conform with the requirements of this chapter. A chimney or ve nt that is no longer connected with a fireplace or combustion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be accom- plished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required in this chapter from the new or altered building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapter. Such requirements shall not dispense with or modify any additional requirements that may be applicable pursuant to rules of the New York City Department of Environmental Prote ction. 801.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 801.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 801.1.1.3 Written notification, pl ans and required documents. The owner of the new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 801.1.1. 3.1 through 801.1.1.3.3. 801.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such noti ce shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be file d with the department. 801.1.1.3.2 Second notice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered build ing. Such notice shall include a request for access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and CHIMNEYS AND VENTS certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at the public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result i n a determination that chimney or vent alteration is not required and a revised chimney and vent plan is submitted to the department. 801.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and con- ditions are observed that result in a determination that chimney or vent alteration is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 801.1.1.4 Approval. The construction documents for the proposed chimney extension, alteration or reloca- tion shall be submitted to the department pursuant to Section 28 - 104 of the New York City Administrative Code . No certificate of occupancy shall b e issued for the new building pursuant to Section 28 - 118.23 of the New York City Administrative Code until the work associated with such construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the departme nt. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determination that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Sect ion 107.18 of the New York City Building Code documenting such. 2. A certificate of occupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the New York City Administrative Code . 801.1.1.5 Refusal of consent. If consent is not gr anted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to the commissioner; and the owner of the new or altered building having provided the notices required by Section 801.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any health hazard or nuisance that may occur as a result of the ne w or altered building. Such responsibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refus al, he or she shall then assume all responsibil- ities as prescribed above. ‡‡‡ 801.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Building Code ; 2. Provide required notification pursuant to Section 801.1.1.3 of this code; 3. Provide plans pursuant to Section 801.1.1.3.3 of this code; 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the New York City Administrative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain pe rmit(s) for the proposed work in accordance with Section 28 - 105 of the New York City Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chimneys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; CHIMNEYS AND VENTS 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same material as the original chimney or vent so as to maintain the same quality and appearance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthetics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner ma y permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the New York City Admin- istrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the New York City Admin is- trative Code . 801.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or alte red building. 801.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 801.2 General. Every fuel - burning appliance shall discharge the products of combustion to a vent, factory - built chim- ney or masonry chim ney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being vented. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507. 801.2 .1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combustible surfaces shall not be raised above 160°F (71.1°C). Chimneys and vents shall be designed to resist the effects of condensation that would cause deterioration of the chimney or vent. 801.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. 801.2.3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifically designed for such loads. 801.2.4 Oil - fired appliances. Oil - fired ap pliances shall be vented in accordance with this code and NFPA 31. 801.2.5 Gas - fired appliances. Gas - fired appliances shall be vented in accordance with the New York City Fuel Gas Code . 801.3 Masonry chimneys. Masonry chimneys shall be constructed in accor dance with the New York City Building Code. 801.4 Positive flow. Venting systems shall be designed and constructed so as to develop a positive flow adequate to convey all combustion products to the outside atmosphere. 801.5 Design. Venting systems shall b e designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 801.6 Minimum size of chimney or vent. Except as otherwise provided for in this chapter, the size of the chimney or vent, serving a single appliance, except engineered systems, shall have a minimum area equal to the area of the appliance connection. 801.7 Solid fuel - burning appliance flues. The cross - sectional area of a flue serving a solid fuel - burning appliance shall be not greate r than three times the cross - sectional area of the appliance flue collar or flue outlet. 801.8 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method , sealed air - tight and permanently labeled as abandoned . 801.9 Positive pressure. Where an appliance equipped with a forced or induced draft system creates a positive pres- sure in the venting system, the venting system shall be designed and listed for positive pressure applications. CHIMNEYS AND VENTS 801.10 Connection to fireplace. Connection of appliances to chimney flues serving fireplaces shall be in accordance with Sections 801.10.1 through 801.10.3. 801.10.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 801.10.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a fac- tory - built fireplace unl ess the appliance is specifically listed for such installation. The connection shall be made in accordance with the appliance manufacturer’s instructions. 801.10.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flu e serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be provided with access or shall be removable for inspection and cleaning of both the connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 801.11 Multiple solid fuel - burning appliances prohibited. A solid fuel - burning appliance or fireplace shall not connect to a chimney passageway venting another appliance. 801.12 Chimney entrance. Connect ors shall connect to a chimney flue at a point not less than 12 inches (304.8 mm) above the lowest portion of the interior of the chimney flue. 801.13 Cleanouts. Factory - built chimneys and vents shall be provided with a cleanout opening or access door at t he base of the chimney or vent installed in accordance with the manufacturer’s instructions. Masonry and metal chim- neys shall be provided with a cleanout opening having a minimum height of 6 inches (152.4 mm). The upper edge of the opening shall be located not less than 6 inches (152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches (203.2 mm by 203.2 mm). Cleanouts shall comply with the requireme nts of the New York City Air Pollution Control Code. Exception: Cleanouts shall not be required for chimney flues serving masonry fireplaces, if such flues are provided with access through the fireplace opening. 801.14 Connections to exhauster. Appliance c onnections to a chimney or vent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and piping on the positive pressure side of the exhauster shall be listed for positive pressure applications as specified by the manufa cturer’s instructions for the exhauster or in accord- ance with this code . 801.15 Fuel - fired appliances. Masonry chimneys utilized to vent fuel - fired appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented. 801.16 Flue lining. Masonry chimneys shall be lined. The lining material shall be compatible with the type of appli- ance connected, in accordance with the appliance listing and manufacturer’s instructions. Listed materials used as flue linings shall be installed in accordance with their listings and the manufacturer’s instructions. 8 01.16.1 Residential and low - heat appliances (general). Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue l ining shall be installed in accordance with the New York City Building Code. 2. Listed and labeled chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved mater ials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800 ° F (982.2 ° C). 4. Existing firebrick chimneys may be used to vent appliances if the firebrick is acid resistant and lab tested. The brick a nd mortar must be inspected in accordance with Section 1705.32 of the New York City Building Code. 801.17 Space around lining. The space surrounding a flue lining system or other vent installed within a masonry chimney shall not be used to vent any other a ppliance. This shall not prevent the installation of a separate flue lining in accordance with the manufacturer’s instructions and this code. CHIMNEYS AND VENTS 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or ven t, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney or vent shall comply with Sections 801.18.1 through 801.18.4. 801.18.1 Size. The chimney or vent shall be resized as necessary to con trol flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For the venting of oil - fired appliances to masonry chimneys, the resizing shall be in accordance with NFPA 31. 801. 18.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inne r wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration which would allow the escape of combustion products, including gases, moisture and creosote. Where an oil - fired appliance is connected to an existin g masonry chimney, such chimney flue shall be repaired or relined in accordance with NFPA 31. 801.18.3 Cleanout. Masonry chimneys shall be provided with a cleanout opening complying with Section 801.13. 801.18.4 Clearances. Chimneys and vents shall have ai rspace clearance to combustibles in accordance with the New York City Building Code and the chimney or vent manufacturer’s instructions. Exception: Masonry chimneys without the required airspace clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in accordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 80 1.18.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance with the New York City Building Code. 801.19 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 801.20 Reserved. 801.21 Termination requirements. Terminations shall comply with the appliance listing and manufacturer’s instruc- tions, and the following: 1. Chimneys, vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F (315.6°C) shall extend at least 3 feet (914.4 m m) above the highest construction, such as a roof ridge, parapet wall or penthouse within 10 feet (3048 mm) of the chimney vent or flue outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys, vents or f lues located in an area that is more than 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required heig ht of a chimney, such construction shall not include other chimneys, vents or open structural framing. 2. Chimneys serving appliances or fireplaces with outlet temperatures between 600°F (315.6°C) and 1000°F ( 537.8 °C) shall extend at least 10 feet (3048 m m) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. Any chimneys located in an area mo re than 20 feet (6096 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction in such area. For purposes of determining the required height of the chimney, such construc tion does not include other chimneys, vents or open structural framing. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend at least 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another building. Any chimneys located in an area that is more than 50 feet (15 24 0 mm) from such construction, but not more than the distance determined from Equation 8 - 1, shall be at least as high as the highest construction located in such area. For purposes of determining the required height of the chimney, such construction does no t include other chimneys, vents, or open structural framing. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 . A positive means shall be provided to prevent water from entering the appliance. CHIMNEYS AND VENTS Exceptio n: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are installed in ac- cordance with the manufacturers’ instructions. 6. The following formula shall be used in order to determine the distance referred to in Items 1, 2 and 3 of this section: D = F × √ A (Equation 8 - 1) where: D = Distance, in feet, measured from the center of the chimney, vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from Table 801.21. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. TABLE 801.21 “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES TYPE OF FUEL “F” FACTOR 600°F (315.6°C) and less 600°F (315.6°C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) No. 2 Fuel Oil 2.5 2.5 3 No. 4, 6 Fuel Oil, Solid Fuels 3 3 3 801.22 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch (25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements. The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys and gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accordance with the listing and installation in- structions. On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 801.23 Draft controls. The installation of draft controls shall comply with Sections 801.23.1 through 801.23.5. 801.23.1 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturers’ instructions. In the absence of manufac- turers’ instructions, the device shall be attached to the flue collar of the applia nce or as near to the appliance as practical. 801. 23.2 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed barometric draft regulator or automatic damper installed and adjusted in accordance w ith the manu- facturers’ instructions. Automatic dampers shall be installed in accordance with Section 803.6. 801.23.3 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric draft regulators and all other appurtenan ces that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or vent. CHIMNEYS AND VENTS 801.23.4 Location. Barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the regulator and the combustion air supply. 801. 23.5 Positioning. Barometric draft regulators shall be installed in the position for which they were designed wit h reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance, adjacent construction or installation hardware. 801.24 Obstructions. Devices or items that protrude into, impe de or restrict the flow of vent gases shall not be in- stalled in a vent connector, chimney, or vent. 801.25 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). SECTION MC 802 VENTS 802.1 General. Vent systems shall be listed and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance wit h UL 641. 802.2 Vent application. The application of vents shall be in accordance with Table 802.2. TABLE 802.2 VENT APPLICATION VENT TYPES APPLIANCE TYPES Type L oil vents Oil - burning appliances listed and labeled for venting with Type L vents; gas appliances listed and labeled for venting with Type B vents. 802.3 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions. 802.4 Vent termination caps. Vent termination caps shall not be permitted and a drain installed to receive condensed or rain water shall be required. A positive means, such as offsets, shall be provided to prevent water from entering the appliance. Exception: Termination caps shall be permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 802.5 Type L vent terminations. Type L vents shall terminate in accordance with Section 801.21 . 802.6 Minimum vent heights. Vents shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance flue collar. Exceptions: 1. Venting systems of direct vent appliances shall be installed in accordance with the appliance and the vent manufacturer’s in structions. 2. Appliances listed for outdoor installations incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. 802.7 Support of vents. All portions of vents shall be installed in ac cordance with the manufacturer’s instructions and shall be adequately supported for the design and weight of the materials employed. 802.8 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of not less than N o. 26 gage sheet metal shall be installed to provide clearance between the vent and the insulation material. The CHIMNEYS AND VENTS clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions. Where vents pass through atti c space, the shield shall terminate not less than 2 inches (50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance with the manufacturer’s instructions. 802.9 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches (304.8 mm) horizontally of the vent terminals. Doorstops or closers shall not be installed to obtain this clear- ance. SECTION MC 803 CONNECTORS 803.1 Connectors required. Connectors shall be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. 803.2 Location. Connectors shall be loca ted entirely within the room in which the connecting appliance is located, except as provided for in Section 803.10.4. Where passing through an unheated space, a connector shall not be con- structed of single - wall pipe. 803.3 Size. The connector shall not be smaller than the size of the flue collar supplied by the manufacturer of the appliance. Where the appliance has more than one flue outlet, and in the absence of the manufacturer’s specific in- structions, the connector area shall be not less than the combin ed area of the flue outlets for which it acts as a common connector. 803.4 Branch connections. Branch connections to the vent connector shall be made in accordance with the vent manufacturer’s instructions. 803.5 Manual dampers. Manual dampers shall not be installed in connectors except in chimney connectors serving solid fuel - burning appliances. 803.6 Automatic dampers. Automatically operated dampers shall be equipped with safety controls and shall be of a listed type. Such safety controls shall be capable of demonstrating operation of the damper and appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be installed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 803.7 Connectors serving two or more appliances. Where two or more connectors enter a common vent or chimney, the smaller connector shall enter at the highest level consistent with available headroom or clearance to combustible material. 803.8 Vent connect or construction. A vent connector for a nonresidential, low - heat appliance shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 803.8. Factory - built chimney sections shall be joined together in accordance with the chimney manufacturer’s instructions. TABLE 803.8 MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 (No. 28 gage) 6 to less than 10 0.023 (No. 26 gage) 10 to 12 inclusive 0.029 (No.24 gage) 14 to 16 inclusive 0.034 (No. 22 gage) Over 16 0.056 (No. 16 gage) CHIMNEYS AND VENTS For SI: 1 inch = 25.4 mm. 803.9 Chimney connector construction. Chimney connectors for low - heat appliances shall be of sheet steel pipe having resistance to corrosion and heat not less than that of galvanized steel specified in Table 803.9(1). Connectors for medium - heat appliances and high - heat appliances shall be of sheet steel not less than the thickness specified in Table 803.9(2). TABL E 803.9(1) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM NOMINAL THICKNESS (galvanized) (inches) 5 and smaller 0.022 (No. 26 gage) Larger than 5 and up to 10 0.028 (No. 24 gage) Larger than 10 and up to 16 0.034 (No. 22 gage) Larger than 16 0.064 (No. 16 gage) For SI: 1 inch = 25.4 mm. TABLE 803.9(2) MINIMUM CHIMNEY CONNECTOR THICKNESS FOR MEDIUM - AND HIGH - HEAT APPLIANCES AREA (square inches) EQUIVALENT ROUND DIAMETER (inches) MINIMUM THICKNESS (inches) 0 – 154 0 – 14 0.0575 (No. 16 gage) 155 – 201 15 – 16 0.075 (No. 14 gage) 202 – 254 17 – 18 0.0994 (No. 12 gage) Greater than 254 Greater than 18 0.1292 (No. 10 gage) For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 803.10 Installation. Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6. 803.10.1 Supports and joints. Connectors shall be supported in an approved manner, and overlapping joints shall be tight - fitting and fastened with she et metal screws, rivets, welds or other approved means. 803.10.2 Length. The maximum horizontal length of a single - wall connector shall not affect the capability of the system to produce adequate draft . 803.10.3 Connection. The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently ce- mented in place with high - temperature cement. ‡‡‡ 803.10.4 Connector pass - through. Chimney connectors shall not pass through any floor or ceiling, nor through a fire - resistance - rated wall assembly. Chimney connectors shall not pass through walls or partitions con- structed of combustible material to reach a chimney or vent, except where s uch chimney connector complies with Section 803.10.4.1 or 803.10.4.2. ‡‡‡ 803.10.4.1 Manufactured insulated chimney connectors. Manufactured insulated chimney connectors that pass through walls or partitions of combustible construction must comply with the following: CHIMNEYS AND VENTS 1. The connector is labeled for wall pass - through and is installed in accordance with the manufacturer’s instructions ; or 2. The connector is put through a device labeled for wall pass - through ; or 3. The connector has a diameter not larger than 10 inches (254 mm) and is installed in accordance with one of the methods in Table 803.10.4. Concealed metal parts of the pass - through system in contact with flue gases shall be of stainless steel or equivalent material that resists corrosion, softening or cracking up to 1,800 ° F (982 ° C). 803.10.4.2 Field - applied insulation for chimney connectors. Chimney connectors of appliances with flue gas temperatures less than 500 ° F (260 ° C) that pass through walls or partitions of combustible construction shall be insu lated with a field - applied flexible wrap assembly tested in accordance with either ASTM E2816 or ASTM E2336. The connector shall comply with all of the following: 1. The insulated vent connectors pass - through assemblies and through penetration assemblies s hall be tested for F and T ratings in accordance with ASTM E 814. The F and T rating of the assembly shall be equal to or exceed the fire - resistance rating of the mechanical/boiler room. 2. Bracing and supports shall be of noncombustible material securely attached to the structure and designed to carry gravity and seismic loads within the stress limitations of Chapter 16 of the New York City Building Code . Bolts, screws, rivets and other mechanical fasteners shall not penetrate connector walls. 3. Insulat ed vent connector pass - through assemblies shall not pass through ceilings or floors. 4. Insulated vent connector pass - through assemblies shall not run through occupied spaces, corridors, sleep- ing rooms and spaces with hazardous materials. 5. Insulated vent connector pass - through assemblies material shall meet the requirements for minimum chimney connector thicknesses for medium and high - heat appliances in accordance with Table 803.9(2). 6. Insulated vent connector pass - through assemblies fittings shall be w elded or shall be factory fabricated UL listed construction suitable for external flexible wrap insulation. 7. The draft calculations shall account for the insulating value of the field - applied flexible wrap insulation. ‡‡‡ TABLE 803.10.4 CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES TO COMBUSTIBLE WALL MATERIALS FOR HEATING APPLIANCES a, b, c, d System A (12 - inch clearance) A 3.5 - inch - thick brick wall shall be framed into the combustible wall. A 0.625 - inch - thick fire - clay liner (ASTM C 315 or equivalent) e shall be firmly cemented in the center of the brick wall maintaining a 12 - inch clearance to combustibles. The clay liner s hall run from the outer surface of the bricks to the inner surface of the chimney liner. System B (9 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) the same inside diameter as the connector shall be utilized. Sheet steel supports cut to maintain a 9 - inch clearance to combustibles shall be fastened to the wall surface and to the chimney section . Fasteners shall not penetrate the chimney flue liner. The chimney length shall be flush with the masonry chimney liner and sealed to the masonry with water - insoluble refractory cement. Chimney manufacturers’ parts shall be utilized to securely fasten the chimney connector to the chimney section. CHIMNEYS AND VENTS System C (6 - inch clear- ance) A sheet metal (minimum No. 24 gage) ventilated thimble having a minimum thickness of 0.0236 inch (No. 24 gage) having two 1 - inch air channels shall be installed. Steel supports shall be cut to maintain a 6 - inch clearance with a sheet steel chimney connector between the thimble and combustibles. The chimney connector and steel supports shall have a minimum thickness of 0.0236 inch (No. 24 gage). One side of the support shall be fastened to the wall on all sides. Glass - fiber insulation shall fill the 6 - inch spa ce between the thimble and the supports. System D (2 - inch clear- ance) A labeled solid - insulated factory - built chimney section (1 - inch insulation) with a diameter 2 inches larger than the chimney connector shall be installed with a steel chimney connector having a minimum thickness of 0.0236 inch ( No. 24 gage). Sheet steel supports shall be positioned to maintain a 2 - inch clearance to combustibles and to hold the chimney connector to ensure that a 1 - inch airspace surrounds the chimney connector through the chimney section. The steel support shall be fastened to the wall on all sides and the chimney section shall be fastened to the supports. Fasteners shall not penetrate the liner of the chimney section. For SI: 1 inch = 25.4 mm, 1.0 Btu × in/ft 2 • h • ° F = 0.144 W/m 2 • K. a. Insulation material that is part of the wall pass - through system shall be noncombustible and shall have a thermal conductivity of 1.0 Btu × in/ft 2 • h • ° F or less. b. All clearances and thicknesses are minimums. c. Materials utilized to seal penetrations for the connector shall be non - combustible . d. Connectors for all systems except System B shall extend through the wall pass - through system to the inner face of the flue li ner. e. ASTM C 315. 803.10.5 Pitch. Connectors shall rise vertically to the chimney or vent with a minimum pitch equal to one - fourth unit vertical in 12 units horizontal (2 - percent slope). 803.10.6 Clearances. Connectors shall have a minimum clearance to c ombustibles in accordance with Table 803.10.6. The clearances specified in Table 803.10.6 apply, except where the listing and labeling of an appliance specifies a different clearance, in which case the labeled clearance shall apply. The clearance to combus tibles for connectors shall be reduced only in accordance with Section 308 or via the use of a listed chimney or vent con- nector system . CHIMNEYS AND VENTS TABLE 803.10.6 CONNECTOR CLEARANCES TO COMBUSTIBLES TYPE OF APPLIANCE MINIMUM CLEARANCE (inches) Domestic - type appliances Chimney and vent connectors Electric and oil incinerators 18 Oil and solid fuel - burning appliances 18 Oil appliances labeled for venting with Type L vents 9 Commercial, industrial - type appliances Low - heat appliances Chimney connectors Oil and solid fuel boilers, furnaces and water heaters 18 Oil unit heaters 18 Other low - heat industrial appliances 18 Medium - heat appliances Chimney connectors All oil and solid fuel - burning appliances 36 High - heat appliances In accordance with NFPA 211 Masonry or metal connectors All oil and solid fuel - burning appliances For SI: 1 inch = 25.4 mm. SECTION MC 804 DIRECT - VENT, INTEGRAL VENT AND MECHANICAL DRAFT SYSTEMS 804.1 Direct - vent terminations. Vent terminals for direct - vent appliances shall be installed in accordance with the manufacturer’s instructions. In addition, direct vent terminations shall comply with the following requirements: 1. Where located adjacent t o walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent appliance, loc ated within 10 feet (3048 mm). 3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent termination point shal l not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. CHIMNEYS AND VENTS 5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, re gulating, venting relief equipment or other building opening. 6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwi se approved by the commissioner. 9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2 Appli ances with integral vents. Appliances incorporating integral venting means shall be installed in accord- ance with their listings and the manufacturer’s instructions. In addition, integral vent terminals shall comply with the following requirements: 1. Where located adjacent to walkways, the vent terminal shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 2. The vent terminal shall be at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject integral vent appliance, located within 10 feet (3048 mm). 3. The vent terminal shall be at least 4 feet (1219.2 mm) below, 4 feet ( 1219.2 mm) horizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 4. The vent terminal shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 5. The vent terminal shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 6. The bottom of the vent terminal shall be located at least 36 i nches (914.4 mm) above finished grade. 7. The maximum heat input of an appliance served by single horizontal vent terminal shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 8. The maximum heat input of all appliances served by horizontal vent terminals located within a 10 foot (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 9. The vent terminal shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacen t build- ings. The termination shall be installed in accordance with the vent manufacturer’s instructions. 804.2.1 Reserved. 804.3 Mechanical draft systems. Mechanical draft systems of either forced or induced draft design shall be listed and labeled in acc ordance with UL 378 and shall comply with Sections 804.3.1 through 804.3.8. 804.3.1 Forced draft systems. Forced draft systems and all portions of induced draft systems under positive pres- sure during operation shall be designed and installed so as to be ga s tight to prevent leakage of combustion products into a building. 804.3.2 Automatic shutoff. Power exhausters serving automatically fired appliances shall be electrically connected to each appliance to prevent operation of the appliance when the power exh auster is not in operation. 804.3.3 Termination. The termination of chimneys or vents equipped with power exhausters shall be located not less than 10 feet (3048 mm) from the lot line or from adjacent buildings, unless otherwise approved by the com- missione r. The exhaust shall be directed vertically away from the building. 804.3.4 Horizontal terminations. Horizontal terminations and discharges, including any horizontal direct vent terminations subject to Section 804.1 and horizontal integral vent terminals s ubject to Section 804.2, shall not be permitted, unless otherwise authorized by the commissioner. 804.3.5 Vertical terminations. Vertical terminations and discharges shall comply with Section 801.21. 804.3.6 Exhauster connections. An appliance vented by na tural draft shall not be connected into a vent, chimney or vent connector on the discharge side of a mechanical flue or power exhauster. CHIMNEYS AND VENTS 804.3.7 Exhauster sizing. Mechanical flue or power exhausters and the chimney or vent system served shall be sized and installed in accordance with the manufacturer’s instructions. 804.3.8 Mechanical draft systems for manually fired appliances and fireplaces. A mechanical draft system shall be permitted to be used with manually fired appliances and fireplaces where such sy stem complies with all of the following requirements: 1. The mechanical draft device shall be listed and labeled in accordance with UL 378, and shall be installed in accordance with the manufacturer’s instructions. 2. A device shall be installed in the roo m with the appliance or fireplace that produces visible and audible warning upon failure of the mechanical draft device or loss of electrical power, at any time that the mechan- ical draft device is turned on. This device shall be equipped with a battery bac kup if it receives power from the building wiring. 3. A smoke detector or alarm, and a carbon monoxide detector or alarm, shall be installed in the room with the appliance or fireplace. This device shall be equipped with a battery backup if it receives pow er from the building wiring. SECTION MC 805 FACTORY - BUILT CHIMNEYS 805.1 Listing. Factory - built chimneys shall be listed and labeled and shall be installed and terminated in accordance with this code and the manufacturer’s instructions. 805.2 Solid fuel - bu rning appliances. Factory - built chimneys installed in dwelling units with solid fuel - burning ap- pliances shall comply with the Type HT requirements of UL 103 and shall be marked “Type HT” and “Residential Type and Building Heating Appliance Chimney.” Exceptions: 1. Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked “Residential Type and Building Heating Appliance Chimney.” 2. Chimneys for use with open combustion chamber appliances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be marked “Building Heating Appliance Chimney” or “Residential Type and Building Heating Appliance Chimney.” 805.3 Factory - built chimney offsets. Where a factory - built chimney serving a solid fuel - burning appliance or fire- place incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not i nclude more than four elbows. Exception: Factory - built chimneys listed to UL103 Type HT serving a solid fuel - burning appliance or fireplace may offset at angles greater than 30 degrees from vertical if listed for such angles and installed in accordance with manufacturer’s instructions. Cleanouts shall be installed in accordance with Section 801.13. 805.4 Support. Where factory - built chimneys are supported by structural members, such as joists and rafters, such members shall be designed to supp ort the additional load. 805.5 Medium - heat appliances. Factory - built chimneys for medium - heat appliances producing flue gases having a temperature above 1,000 ° F ( 537.8° C ), measured at the entrance to the chimney shall comply with UL 959. 805.6 Decorative s hrouds. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and labeled for use with the specific factory - built chimney system and are in- stalled in accordance with Section 304.1. 805.7 Factory - built fireplaces. Chimneys for use with factory - built fireplaces shall comply with the requirements of UL 127. CHIMNEYS AND VENTS SECTION MC 806 METAL CHIMNEYS 806.1 General. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 806.2 Exteri or metal chimneys. Exterior metal chimneys shall be stainless steel. SECTION MC 807 CHANGES IN APPLIANCE FUELS 807.1 Changes in appliance fuels. Conversion of appliances from solid or liquid fuel to, or the addition of, natural gas shall be installed per t he New York City Fuel Gas Code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if: 1. The chimney design meets the requirements of this chapter for the conversion fuel, and the chimney is test run and smoke tested in accordance with Section 810. 2. The chimney is sized to provide adequate draft and vent the combustion products for the new fuel. 3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits. SECTION MC 808 REDUCTION OF FLUE SIZE 808.1 Reduction of flue size. Conversion from one fuel to another or the use of an existing chimney to service a fireplace or wood - burning appliance may require a flue size change for proper operation. This may be done if the redesigned flue meets the criteria for the fuel and chimney type to be used as set forth in this chapter. SECTION MC 809 CHIMNEY SUPPORTED FROM EQUIPMENT 809.1 Chimney support. Chimneys shall not be supported by the equipment they serve, unless such eq uipment has been specifically designed for such loads. SECTION MC 810 TEST RUN AND SMOKE TEST ‡‡‡ 810.1 Test run. All new and altered chimneys, and chimneys to which a new appliance has been connected, shall be test run under operating conditions to demonst rate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The test run shall be conducted by a registered design professional or special inspector responsible for the test, and the results of such test run shall be certified as correct by such professional or special inspector and submitted in writing to the department. Refer to Section 1705.32 of the New York City Building Code for additional requirements. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test ru n shall not require a registered design professional or special in- spector. ‡‡‡ 810.2 Requirement of a smoke test. A smoke test shall be made as outlined in Section 810.3. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In lieu thereof, the commissioner may accept the test report of a registered design professional or special inspector respon- sible for the test that shall be submitted in writing to the department. Exception: A smoke test may be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. CHIMNEYS AND VENTS Such test shall not be required to be witnessed by the depar tment, registered design professional or special inspector. 810.3 Smoke test. To determine the tightness of chimney construction , a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the requirements of t his chapter, and the test shall be repeated until the results are satisfactory. 3. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the st ack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 - inch (13 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspect ion of the chimney. 4. Refer to Section 170 5 .32 ‡ of the New York City Building Code for requirements for existing and new negative pressure chimneys and vents. SECTION MC 811 EXHAUST GASES FROM INTERNAL COMBUSTION ENGINES AND TURBINES 811.1 Exhaust system construction. The exhaust system from internal combustion engines shall be constructed in accordance with NFPA 211, NFPA 37, and based on the temperature of the flue gas entering the exhaust system, and in accordance with the following: 1. The exhau st system, if factory built, shall be installed in accordance with its listing and manufacturer’s instruc- tions. 1.1. Exhaust systems with flue gas temperatures greater than 300°F (148.9°C) shall be listed to UL 103 or UL 2561 and be rated for a minimum of 60 inch w.c. (14 934.3 Pa). 1.2. Exhaust systems with flue gas temperatures not more than 300°F (148.9°C) and that are capable of causing excessive condensate production in the exhaust system shall be listed to UL 103 or UL 2561 and UL 1738 and be rated fo r a pressure suitable for the operating conditions. 2. The exhaust system, if field fabricated, shall be constructed of at least 3 / 16 - inch (4.8 mm) steel, or of other equiv- alent metal of similar strength and resistance to the temperature and corrosive acti on of the exhaust gases. No lining shall be required. 3. Where the exhaust system runs inside a building, it shall be insulated adequately for the equipment operating temperature, so that the surface temperature shall be not more than 200°F (93.3°C). 4. Wh ere the exhaust system runs inside a building outside of the room containing the equipment, it shall be en- closed in fire - rated construction with a fire rating equal to the fire rating of the construction of the room. 5. All joints shall be constructed so a s to be gas tight under all operating conditions and tested in accordance with Section 810. 811.2 Emergency and standby generator discharge opening termination requirements. The location of discharge outlets for emergency and standby internal combustion en gines shall comply with the requirements of NFPA 37 so that the flue gases are not directed to jeopardize the health or safety of people, overheat combustible structures, nor enter building openings in the vicinity of the outlet, nor shall the location of such openings cause the condensate leaving the outlet to come into contact with people. 811.2.1 Interference. No discharge opening shall be located and constructed so as to interfere with the proper functioning of other openings in the same building or adjoining buildings, to interfere unreasonably with the occupants of the same building or adjoining buildings, or with the general public, or to create a fire or health hazard . CHIMNEYS AND VENTS 811.2.2 Chimneys. The exhaust pipe may be connected to a chimney used for other equipment, provided that the operation of the engine does not adversely affect the operation of the other equipment so that it is in violation of the New York City Air Pollut ion Control Code. 811.3 All other engine and turbine discharge opening termination requirements. The location of the discharge outlet from all other engines and turbines shall comply with the termination requirements of Section 801.21, Item 2 or Section 80 1.21, Item 3 based on the temperature of the flue gas entering the exhaust system. 811.4 Chimneys. The exhaust system may be connected to a chimney used for other appliances, provided that the chimney complies with Section 811.1, Item 1 or Section 811.1, I tem 2 and the operation of the engine does not adversely affect the operation of the other appliances and is in accordance with the New York City Air Pollution Control Code.