2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code ., as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 5 4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire - extinguishing systems. 5. Seismic protection and restraint details for piping and applian ces as required by Chapter 16 of the New York City Building Code . 6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and t he clearances from combustible walls, partitions and ceiling; and the fire - resistive ratings of rooms and spaces containing the appliances. 7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and stru c- tures for chimneys and gas vents. 8. Details show ing structural supports for fuel - gas - burning equipment where required. 9. In flood hazard areas , construction documents shall comply with Appendix G of the New York City Building Code . 107.6 Heating systems. Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source. 107.7 Boilers. Construction documents for boiler installations shall indicate the output capacity in BTU per hou r (W) , the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required b y this code. 107.8 Energy efficiency. Construction documents shall include compliance documentation as required by the N ew York City Energy Conservation Code . 107.9 Retention of construction and submittal documents. Refer to Section 28 - 104.12 of the Administrative Code . SECTION FGC 108 INSPECTIONS AND TESTING 108.1 General. Except as otherwise specified in Section 28 - 116.2.4.3 of the Administrative Code , inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such in- spections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. 108.2 Required inspections and testing. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be require d: 1. Progress inspections: 1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti - corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling . 1.2. Rough - in inspe ction shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be conce aled are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections. Exceptions: 1. A rough - in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A rough - in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28 - 105.4.1 of the Administrative Code . 1.3. Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable. 1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspect ions shall include, but not be limited to, an inspection of components 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 5 4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire - extinguishing systems. 5. Seismic protection and restraint details for piping and applian ces as required by Chapter 16 of the New York City Building Code . 6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and t he clearances from combustible walls, partitions and ceiling; and the fire - resistive ratings of rooms and spaces containing the appliances. 7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and stru c- tures for chimneys and gas vents. 8. Details show ing structural supports for fuel - gas - burning equipment where required. 9. In flood hazard areas , construction documents shall comply with Appendix G of the New York City Building Code . 107.6 Heating systems. Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source. 107.7 Boilers. Construction documents for boiler installations shall indicate the output capacity in BTU per hou r (W) , the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required b y this code. 107.8 Energy efficiency. Construction documents shall include compliance documentation as required by the N ew York City Energy Conservation Code . 107.9 Retention of construction and submittal documents. Refer to Section 28 - 104.12 of the Administrative Code . SECTION FGC 108 INSPECTIONS AND TESTING 108.1 General. Except as otherwise specified in Section 28 - 116.2.4.3 of the Administrative Code , inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such in- spections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. 108.2 Required inspections and testing. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be require d: 1. Progress inspections: 1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti - corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling . 1.2. Rough - in inspe ction shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be conce aled are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections. Exceptions: 1. A rough - in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A rough - in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28 - 105.4.1 of the Administrative Code . 1.3. Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable. 1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspect ions shall include, but not be limited to, an inspection of components ADMINISTRATION 1 - 6 2022 NEW YORK CITY FUEL GAS CODE downstream of the appliance shutoff valve including gas piping, appliances, vents, accessory piping and make up air. Gas final inspections may be completed in sections. 2. Special inspe ctions. Special inspections shall be performed in accordance with this code and Chapter 17 of the New York City Building Code . 3. Periodic inspections. Periodic inspections of gas piping systems shall be conducted in accordance with Article 318 of Chapter 3 of Title 28 of the Administrative Code . 4. Final inspection: Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 5. Issuance of certificate of compliance: Upon satisfactory inspection of service equipment and the satisfaction of all the requirements for sign - off, the department shall issue a certificate of compliance as applicable for the following service equipment: 5.1. Fuel - gas - burning equipment, 5.2. Heating systems, and 5.3. Boilers. The requirements of Section 108.2 shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and all required inspections are performed before any portion of such equipment or appliances is concealed by any permanent portion of the structure. 108.2.1 Approved inspection agencies. Refer to Articles 114 and 115 of Chapter 1 of Title 28 of the Administrative Code . 108.2.2 Inspection of prefabricated construction assemblies. Prior to the approval of a prefabricated construction assem- bly having concealed work and the issuance of a permi t, the department shall require the submittal of an evaluation report by an approved agency on each prefabricated construction assembly, indicating the complete details of the installation, including a description of the system and its components, the basi s upon which the system is being evaluated, test results and similar information and other data as necessary for the commissioner to determine conformance to this code. 108.2.2.1 Test and inspection records. Required test and inspection records shall be av ailable to the commissioner at all times during the fabrication of the installation and the erection of the building; or such records as the commissioner designates shall be filed. 108.2.3 Exposure of work. The work shall remain accessible and exposed for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection. 108.3 Testing. Installations shall be tested as required in this code an d in accordance with Sections 108.3.1 through 108.3.3 . Tests shall be made by the permit holder and witnessed by the department . 108.3.1 New, altered, extended or repaired installations. New installations and parts of existing installations that have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects. Exceptions: 1. A gas test shall not be required when an existing gas applianc e is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A gas test shall n ot be required when gas is reestablished by a utility company as permitted under section 28 - 105.4.1 of the Administrative Code . 108.3.2 Apparatus, instruments, material and labor for tests. Apparatus, instruments, material and labor required for test- ing an installation or part thereof shall be furnished by the permit holder. 108.3.3 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made t o comply with this code. The work or installation shall then be resubmitted to the department for inspection and testing. 108.3.4 Test validity. A gas test that is accepted by the department shall be valid for a period of one year from the date of the test . 108.4 Sign - off of completed work. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 5 4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire - extinguishing systems. 5. Seismic protection and restraint details for piping and applian ces as required by Chapter 16 of the New York City Building Code . 6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and t he clearances from combustible walls, partitions and ceiling; and the fire - resistive ratings of rooms and spaces containing the appliances. 7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and stru c- tures for chimneys and gas vents. 8. Details show ing structural supports for fuel - gas - burning equipment where required. 9. In flood hazard areas , construction documents shall comply with Appendix G of the New York City Building Code . 107.6 Heating systems. Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source. 107.7 Boilers. Construction documents for boiler installations shall indicate the output capacity in BTU per hou r (W) , the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required b y this code. 107.8 Energy efficiency. Construction documents shall include compliance documentation as required by the N ew York City Energy Conservation Code . 107.9 Retention of construction and submittal documents. Refer to Section 28 - 104.12 of the Administrative Code . SECTION FGC 108 INSPECTIONS AND TESTING 108.1 General. Except as otherwise specified in Section 28 - 116.2.4.3 of the Administrative Code , inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such in- spections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. 108.2 Required inspections and testing. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be require d: 1. Progress inspections: 1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti - corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling . 1.2. Rough - in inspe ction shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be conce aled are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections. Exceptions: 1. A rough - in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A rough - in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28 - 105.4.1 of the Administrative Code . 1.3. Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable. 1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspect ions shall include, but not be limited to, an inspection of components ADMINISTRATION 1 - 6 2022 NEW YORK CITY FUEL GAS CODE downstream of the appliance shutoff valve including gas piping, appliances, vents, accessory piping and make up air. Gas final inspections may be completed in sections. 2. Special inspe ctions. Special inspections shall be performed in accordance with this code and Chapter 17 of the New York City Building Code . 3. Periodic inspections. Periodic inspections of gas piping systems shall be conducted in accordance with Article 318 of Chapter 3 of Title 28 of the Administrative Code . 4. Final inspection: Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 5. Issuance of certificate of compliance: Upon satisfactory inspection of service equipment and the satisfaction of all the requirements for sign - off, the department shall issue a certificate of compliance as applicable for the following service equipment: 5.1. Fuel - gas - burning equipment, 5.2. Heating systems, and 5.3. Boilers. The requirements of Section 108.2 shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and all required inspections are performed before any portion of such equipment or appliances is concealed by any permanent portion of the structure. 108.2.1 Approved inspection agencies. Refer to Articles 114 and 115 of Chapter 1 of Title 28 of the Administrative Code . 108.2.2 Inspection of prefabricated construction assemblies. Prior to the approval of a prefabricated construction assem- bly having concealed work and the issuance of a permi t, the department shall require the submittal of an evaluation report by an approved agency on each prefabricated construction assembly, indicating the complete details of the installation, including a description of the system and its components, the basi s upon which the system is being evaluated, test results and similar information and other data as necessary for the commissioner to determine conformance to this code. 108.2.2.1 Test and inspection records. Required test and inspection records shall be av ailable to the commissioner at all times during the fabrication of the installation and the erection of the building; or such records as the commissioner designates shall be filed. 108.2.3 Exposure of work. The work shall remain accessible and exposed for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection. 108.3 Testing. Installations shall be tested as required in this code an d in accordance with Sections 108.3.1 through 108.3.3 . Tests shall be made by the permit holder and witnessed by the department . 108.3.1 New, altered, extended or repaired installations. New installations and parts of existing installations that have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects. Exceptions: 1. A gas test shall not be required when an existing gas applianc e is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A gas test shall n ot be required when gas is reestablished by a utility company as permitted under section 28 - 105.4.1 of the Administrative Code . 108.3.2 Apparatus, instruments, material and labor for tests. Apparatus, instruments, material and labor required for test- ing an installation or part thereof shall be furnished by the permit holder. 108.3.3 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made t o comply with this code. The work or installation shall then be resubmitted to the department for inspection and testing. 108.3.4 Test validity. A gas test that is accepted by the department shall be valid for a period of one year from the date of the test . 108.4 Sign - off of completed work. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 5 4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire - extinguishing systems. 5. Seismic protection and restraint details for piping and applian ces as required by Chapter 16 of the New York City Building Code . 6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and t he clearances from combustible walls, partitions and ceiling; and the fire - resistive ratings of rooms and spaces containing the appliances. 7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and stru c- tures for chimneys and gas vents. 8. Details show ing structural supports for fuel - gas - burning equipment where required. 9. In flood hazard areas , construction documents shall comply with Appendix G of the New York City Building Code . 107.6 Heating systems. Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source. 107.7 Boilers. Construction documents for boiler installations shall indicate the output capacity in BTU per hou r (W) , the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required b y this code. 107.8 Energy efficiency. Construction documents shall include compliance documentation as required by the N ew York City Energy Conservation Code . 107.9 Retention of construction and submittal documents. Refer to Section 28 - 104.12 of the Administrative Code . SECTION FGC 108 INSPECTIONS AND TESTING 108.1 General. Except as otherwise specified in Section 28 - 116.2.4.3 of the Administrative Code , inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such in- spections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. 108.2 Required inspections and testing. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be require d: 1. Progress inspections: 1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti - corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling . 1.2. Rough - in inspe ction shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be conce aled are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections. Exceptions: 1. A rough - in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A rough - in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28 - 105.4.1 of the Administrative Code . 1.3. Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable. 1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspect ions shall include, but not be limited to, an inspection of components ADMINISTRATION 1 - 6 2022 NEW YORK CITY FUEL GAS CODE downstream of the appliance shutoff valve including gas piping, appliances, vents, accessory piping and make up air. Gas final inspections may be completed in sections. 2. Special inspe ctions. Special inspections shall be performed in accordance with this code and Chapter 17 of the New York City Building Code . 3. Periodic inspections. Periodic inspections of gas piping systems shall be conducted in accordance with Article 318 of Chapter 3 of Title 28 of the Administrative Code . 4. Final inspection: Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 5. Issuance of certificate of compliance: Upon satisfactory inspection of service equipment and the satisfaction of all the requirements for sign - off, the department shall issue a certificate of compliance as applicable for the following service equipment: 5.1. Fuel - gas - burning equipment, 5.2. Heating systems, and 5.3. Boilers. The requirements of Section 108.2 shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and all required inspections are performed before any portion of such equipment or appliances is concealed by any permanent portion of the structure. 108.2.1 Approved inspection agencies. Refer to Articles 114 and 115 of Chapter 1 of Title 28 of the Administrative Code . 108.2.2 Inspection of prefabricated construction assemblies. Prior to the approval of a prefabricated construction assem- bly having concealed work and the issuance of a permi t, the department shall require the submittal of an evaluation report by an approved agency on each prefabricated construction assembly, indicating the complete details of the installation, including a description of the system and its components, the basi s upon which the system is being evaluated, test results and similar information and other data as necessary for the commissioner to determine conformance to this code. 108.2.2.1 Test and inspection records. Required test and inspection records shall be av ailable to the commissioner at all times during the fabrication of the installation and the erection of the building; or such records as the commissioner designates shall be filed. 108.2.3 Exposure of work. The work shall remain accessible and exposed for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection. 108.3 Testing. Installations shall be tested as required in this code an d in accordance with Sections 108.3.1 through 108.3.3 . Tests shall be made by the permit holder and witnessed by the department . 108.3.1 New, altered, extended or repaired installations. New installations and parts of existing installations that have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects. Exceptions: 1. A gas test shall not be required when an existing gas applianc e is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A gas test shall n ot be required when gas is reestablished by a utility company as permitted under section 28 - 105.4.1 of the Administrative Code . 108.3.2 Apparatus, instruments, material and labor for tests. Apparatus, instruments, material and labor required for test- ing an installation or part thereof shall be furnished by the permit holder. 108.3.3 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made t o comply with this code. The work or installation shall then be resubmitted to the department for inspection and testing. 108.3.4 Test validity. A gas test that is accepted by the department shall be valid for a period of one year from the date of the test . 108.4 Sign - off of completed work. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 7 108.5 Temporary connection. The commissioner shall have the authority to allow the temporary connection of an installation to the sources of energy for the purpose of testing the installation or for use under a temporary certificate of occupancy. SECTION FGC 109 VIOLATIONS 109.1 General. Refer to Chapters 2 and 3 of Title 28 of the Administrative Code . 109.2 Authority to disconnect service utilities. The commissioner shall have the authority to require disconnection of utility service to the building, structure or system regulated by the t echnical codes in case of emergency where necessary to eliminate an immediate hazard to life or property. The commissioner shall notify the serving utility, and wherever possible, the owner and occupant of the building, structure or service system of the d ecision to disconnect prior to taking such action. If not notified prior to disconnection, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as prac- ticable thereafter. 109.3 Connection after order to d isconnect. A person shall not make energy source connections to installations regulated by this code that have been disconnected or ordered to be disconnected by the commissioner , or the use of which has been ordered to be discontinued by the commissioner until the commissioner authorizes the reconnection and use of such installations. When an installation is maintained in violation of this code, and in violation of a notice issue d pursuant to the provisions of this section, the commissioner shall institute appropriate action to prevent, restrain, correct or abate the violation. 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 5 4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire - extinguishing systems. 5. Seismic protection and restraint details for piping and applian ces as required by Chapter 16 of the New York City Building Code . 6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and t he clearances from combustible walls, partitions and ceiling; and the fire - resistive ratings of rooms and spaces containing the appliances. 7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and stru c- tures for chimneys and gas vents. 8. Details show ing structural supports for fuel - gas - burning equipment where required. 9. In flood hazard areas , construction documents shall comply with Appendix G of the New York City Building Code . 107.6 Heating systems. Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source. 107.7 Boilers. Construction documents for boiler installations shall indicate the output capacity in BTU per hou r (W) , the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required b y this code. 107.8 Energy efficiency. Construction documents shall include compliance documentation as required by the N ew York City Energy Conservation Code . 107.9 Retention of construction and submittal documents. Refer to Section 28 - 104.12 of the Administrative Code . SECTION FGC 108 INSPECTIONS AND TESTING 108.1 General. Except as otherwise specified in Section 28 - 116.2.4.3 of the Administrative Code , inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such in- spections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. 108.2 Required inspections and testing. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be require d: 1. Progress inspections: 1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti - corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling . 1.2. Rough - in inspe ction shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be conce aled are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections. Exceptions: 1. A rough - in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A rough - in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28 - 105.4.1 of the Administrative Code . 1.3. Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable. 1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspect ions shall include, but not be limited to, an inspection of components ADMINISTRATION 1 - 6 2022 NEW YORK CITY FUEL GAS CODE downstream of the appliance shutoff valve including gas piping, appliances, vents, accessory piping and make up air. Gas final inspections may be completed in sections. 2. Special inspe ctions. Special inspections shall be performed in accordance with this code and Chapter 17 of the New York City Building Code . 3. Periodic inspections. Periodic inspections of gas piping systems shall be conducted in accordance with Article 318 of Chapter 3 of Title 28 of the Administrative Code . 4. Final inspection: Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 5. Issuance of certificate of compliance: Upon satisfactory inspection of service equipment and the satisfaction of all the requirements for sign - off, the department shall issue a certificate of compliance as applicable for the following service equipment: 5.1. Fuel - gas - burning equipment, 5.2. Heating systems, and 5.3. Boilers. The requirements of Section 108.2 shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and all required inspections are performed before any portion of such equipment or appliances is concealed by any permanent portion of the structure. 108.2.1 Approved inspection agencies. Refer to Articles 114 and 115 of Chapter 1 of Title 28 of the Administrative Code . 108.2.2 Inspection of prefabricated construction assemblies. Prior to the approval of a prefabricated construction assem- bly having concealed work and the issuance of a permi t, the department shall require the submittal of an evaluation report by an approved agency on each prefabricated construction assembly, indicating the complete details of the installation, including a description of the system and its components, the basi s upon which the system is being evaluated, test results and similar information and other data as necessary for the commissioner to determine conformance to this code. 108.2.2.1 Test and inspection records. Required test and inspection records shall be av ailable to the commissioner at all times during the fabrication of the installation and the erection of the building; or such records as the commissioner designates shall be filed. 108.2.3 Exposure of work. The work shall remain accessible and exposed for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection. 108.3 Testing. Installations shall be tested as required in this code an d in accordance with Sections 108.3.1 through 108.3.3 . Tests shall be made by the permit holder and witnessed by the department . 108.3.1 New, altered, extended or repaired installations. New installations and parts of existing installations that have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects. Exceptions: 1. A gas test shall not be required when an existing gas applianc e is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A gas test shall n ot be required when gas is reestablished by a utility company as permitted under section 28 - 105.4.1 of the Administrative Code . 108.3.2 Apparatus, instruments, material and labor for tests. Apparatus, instruments, material and labor required for test- ing an installation or part thereof shall be furnished by the permit holder. 108.3.3 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made t o comply with this code. The work or installation shall then be resubmitted to the department for inspection and testing. 108.3.4 Test validity. A gas test that is accepted by the department shall be valid for a period of one year from the date of the test . 108.4 Sign - off of completed work. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 7 108.5 Temporary connection. The commissioner shall have the authority to allow the temporary connection of an installation to the sources of energy for the purpose of testing the installation or for use under a temporary certificate of occupancy. SECTION FGC 109 VIOLATIONS 109.1 General. Refer to Chapters 2 and 3 of Title 28 of the Administrative Code . 109.2 Authority to disconnect service utilities. The commissioner shall have the authority to require disconnection of utility service to the building, structure or system regulated by the t echnical codes in case of emergency where necessary to eliminate an immediate hazard to life or property. The commissioner shall notify the serving utility, and wherever possible, the owner and occupant of the building, structure or service system of the d ecision to disconnect prior to taking such action. If not notified prior to disconnection, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as prac- ticable thereafter. 109.3 Connection after order to d isconnect. A person shall not make energy source connections to installations regulated by this code that have been disconnected or ordered to be disconnected by the commissioner , or the use of which has been ordered to be discontinued by the commissioner until the commissioner authorizes the reconnection and use of such installations. When an installation is maintained in violation of this code, and in violation of a notice issue d pursuant to the provisions of this section, the commissioner shall institute appropriate action to prevent, restrain, correct or abate the violation. 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 5 4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire - extinguishing systems. 5. Seismic protection and restraint details for piping and applian ces as required by Chapter 16 of the New York City Building Code . 6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and t he clearances from combustible walls, partitions and ceiling; and the fire - resistive ratings of rooms and spaces containing the appliances. 7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and stru c- tures for chimneys and gas vents. 8. Details show ing structural supports for fuel - gas - burning equipment where required. 9. In flood hazard areas , construction documents shall comply with Appendix G of the New York City Building Code . 107.6 Heating systems. Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source. 107.7 Boilers. Construction documents for boiler installations shall indicate the output capacity in BTU per hou r (W) , the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required b y this code. 107.8 Energy efficiency. Construction documents shall include compliance documentation as required by the N ew York City Energy Conservation Code . 107.9 Retention of construction and submittal documents. Refer to Section 28 - 104.12 of the Administrative Code . SECTION FGC 108 INSPECTIONS AND TESTING 108.1 General. Except as otherwise specified in Section 28 - 116.2.4.3 of the Administrative Code , inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such in- spections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. 108.2 Required inspections and testing. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be require d: 1. Progress inspections: 1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti - corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling . 1.2. Rough - in inspe ction shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be conce aled are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections. Exceptions: 1. A rough - in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A rough - in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28 - 105.4.1 of the Administrative Code . 1.3. Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable. 1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspect ions shall include, but not be limited to, an inspection of components ADMINISTRATION 1 - 6 2022 NEW YORK CITY FUEL GAS CODE downstream of the appliance shutoff valve including gas piping, appliances, vents, accessory piping and make up air. Gas final inspections may be completed in sections. 2. Special inspe ctions. Special inspections shall be performed in accordance with this code and Chapter 17 of the New York City Building Code . 3. Periodic inspections. Periodic inspections of gas piping systems shall be conducted in accordance with Article 318 of Chapter 3 of Title 28 of the Administrative Code . 4. Final inspection: Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 5. Issuance of certificate of compliance: Upon satisfactory inspection of service equipment and the satisfaction of all the requirements for sign - off, the department shall issue a certificate of compliance as applicable for the following service equipment: 5.1. Fuel - gas - burning equipment, 5.2. Heating systems, and 5.3. Boilers. The requirements of Section 108.2 shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and all required inspections are performed before any portion of such equipment or appliances is concealed by any permanent portion of the structure. 108.2.1 Approved inspection agencies. Refer to Articles 114 and 115 of Chapter 1 of Title 28 of the Administrative Code . 108.2.2 Inspection of prefabricated construction assemblies. Prior to the approval of a prefabricated construction assem- bly having concealed work and the issuance of a permi t, the department shall require the submittal of an evaluation report by an approved agency on each prefabricated construction assembly, indicating the complete details of the installation, including a description of the system and its components, the basi s upon which the system is being evaluated, test results and similar information and other data as necessary for the commissioner to determine conformance to this code. 108.2.2.1 Test and inspection records. Required test and inspection records shall be av ailable to the commissioner at all times during the fabrication of the installation and the erection of the building; or such records as the commissioner designates shall be filed. 108.2.3 Exposure of work. The work shall remain accessible and exposed for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection. 108.3 Testing. Installations shall be tested as required in this code an d in accordance with Sections 108.3.1 through 108.3.3 . Tests shall be made by the permit holder and witnessed by the department . 108.3.1 New, altered, extended or repaired installations. New installations and parts of existing installations that have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects. Exceptions: 1. A gas test shall not be required when an existing gas applianc e is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A gas test shall n ot be required when gas is reestablished by a utility company as permitted under section 28 - 105.4.1 of the Administrative Code . 108.3.2 Apparatus, instruments, material and labor for tests. Apparatus, instruments, material and labor required for test- ing an installation or part thereof shall be furnished by the permit holder. 108.3.3 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made t o comply with this code. The work or installation shall then be resubmitted to the department for inspection and testing. 108.3.4 Test validity. A gas test that is accepted by the department shall be valid for a period of one year from the date of the test . 108.4 Sign - off of completed work. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 7 108.5 Temporary connection. The commissioner shall have the authority to allow the temporary connection of an installation to the sources of energy for the purpose of testing the installation or for use under a temporary certificate of occupancy. SECTION FGC 109 VIOLATIONS 109.1 General. Refer to Chapters 2 and 3 of Title 28 of the Administrative Code . 109.2 Authority to disconnect service utilities. The commissioner shall have the authority to require disconnection of utility service to the building, structure or system regulated by the t echnical codes in case of emergency where necessary to eliminate an immediate hazard to life or property. The commissioner shall notify the serving utility, and wherever possible, the owner and occupant of the building, structure or service system of the d ecision to disconnect prior to taking such action. If not notified prior to disconnection, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as prac- ticable thereafter. 109.3 Connection after order to d isconnect. A person shall not make energy source connections to installations regulated by this code that have been disconnected or ordered to be disconnected by the commissioner , or the use of which has been ordered to be discontinued by the commissioner until the commissioner authorizes the reconnection and use of such installations. When an installation is maintained in violation of this code, and in violation of a notice issue d pursuant to the provisions of this section, the commissioner shall institute appropriate action to prevent, restrain, correct or abate the violation. 2022 NEW YORK CITY FUEL GAS CODE 1 - 1 CHAPTER 1 ADMINISTRATION SECTION FGC 101 GENERAL 101.1 Title. This code shall be known and may be cited as the “ New York City Fuel Gas Code ,” “NYCFGC” or “FGC.” All section numbers in this code shall be deemed to be preceded by the designation “FGC.” 101.2 Scope. This code shall apply to the installation of fuel - gas piping systems, fuel - gas appliances and related accessories in accordance with Sections 101.2 .2 through 101.2.5. 101.2.1 Reserved. 101.2.2 Piping systems. These regulations cover piping systems for natural gas. High pressure natural gas installations at pressures of 15 psig ( 103.4 kPa gauge) or above shall also comply with the requirements of Appendix G of this code. Coverage shall extend to the outlet of th e appliance shutoff valves . Piping system requirements shall include design, materials, compo- nents, fabrication, assembly, installation, testing, inspection, operation and maintenance. 101.2.3 Gas utilization appliances. Requirements for gas appliances and related accessories shall include installation, com- bustion and ventilation air and venting and connections to piping systems. 101.2.4 Systems and equipment outside the scope. This code shall not apply to the following: 1. Portable LP - gas appliances and e quipment of all types that are not connected to a fixed fuel piping system. 2. Oxygen - fuel gas cutting and welding systems. 3. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia, carbon mon- oxide, oxygen and nitrogen. 4. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants. 5. Integrated chemical plants or portions of such plants where flammable or comb ustible liquids or gases are produced by, or used in, chemical reactions. 6. LP - gas installations at utility gas plants. 7. Liquefied natural gas (LNG) installations. 8. Fuel gas piping in public utility power plants and atomic energy plants. 9. Components within proprietary items of equipment, apparatus or instruments such as gas - generating sets, compressors and calorimeters. 10. LP - gas equipment for vaporization, gas mixing and gas manufacturing. 11. Temporary LP - gas piping for buildings under c onstruction or renovation that is not to become part of the permanent piping system. 12. Installation of LP - gas systems for railroad switch heating. 13. Installation of hydrogen gas, LP - gas and compressed natural gas (CNG) systems on vehicles. 14. Except a s provided in Section 401.1.1 and Appendices E and G, gas piping, meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP - gas. 15. Building design and construction, except as specified herein. 16. Piping systems for mixtures of gas and air within the flammable range with an operating pressure greater than 10 psig ( 68.9 kPa gauge). 17. Portable fuel cell appliances that are neither connected to a fixed piping system nor inte rconnected to a power grid. 101.2.5 Other fuels. The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the New York City Mechanical Code . ADMINISTRATION 1 - 2 2022 NEW YORK CITY FUEL GAS CODE 1 01.3 Reserved. 101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb , health, property , public welfare and the environment by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of fuel gas systems. 101.5 Severability. If a section, subsection, sentence, clause or phrase of this code is, for any r eason, held to be unconstitu- tional, such decision shall not affect the validity of the remaining portions of this code. SECTION FGC 102 APPLICABILITY 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the s pecific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. 102.2 Existing installations. Except as otherwise pr ovided for in this chapter or elsewhere in this code , a provision in this code shall not require the removal, alteration or abandonment of, nor prevent the continued utilization and maintenance of, existi ng installations lawfully in existence on the effect ive date of this code. 102.2.1 Existing buildings. Additions, alterations, renovations or repairs related to building or structural issues shall be governed by Chapter 1 of Title 28 of the Administrative Code , the New York City Building Code and the 1968 Building Code , as applicable . 102.3 Maintenance. Installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accordance with the original design and in a safe condition. Devices or safeguards th at are required by this code shall be main- tained in compliance with the applicable provisions under which they were installed. 102.3.1 Owner responsibility. The owner or the owner’s designated agent shall be responsible for maintenance of instal- lations. To determine compliance with this provision, the commissioner shall have the authority to require an existing installation to be inspected . 102.4 Additions, alterations or repairs. Additions, alterations, renovations or repairs to installations shall conform to that required for new installations without requiring the existing installation to comply with all of the requirements of this cod e. Additions, alterations or repairs shall not cause an existing installation to become unsafe, hazardous or overloaded . 102.4.1 Minor additions, alterations, renovations and repairs. Minor additions, alterations, renovations and repairs to ex- isting installations shall meet the provisions for new construction, unless such work is done in the same manner and arrange- ment as wa s in the existing system, is not hazardous and is approved. 102.4.2 Special provisions for prior code buildings. In addition to the requirements of Sections 102.4 and 102.4.1, the provisions of Sections 102.4.2.1 through 102.4.2.4 shall apply to prior code buildings. 102.4.2.1 Fuel gas piping in prohibited locations . For prior code buildings, the replacement of existing fuel gas piping in the same locations shall not be subject to Section 404.3 when approved by the commissioner. 102.4.2.2 Guards and access to roofs and elevated structures. The provisions of Section 306.6 relating to guards and Section 306.5 relating to permanent means of access shall not apply where the equipment or appliances replace existing equipment or appliances in the same location. 10 2.4.2.3 Seismic supports. For prior code buildings, the determination as to whether seismic requirements apply to an alteration shall be made in accordance with the 1968 Building Code and interpretations by the department relating to such determinations. A ny applicable seismic loads and requirements shall be permitted to be determined in accordance with Chapter 16 of the New York City Building Code or the 1968 Building Code and Reference Standard RS 9 - 6 of such code. 102.4.2.4 Wind resistance. For prior cod e buildings, equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with Chapter 16 of the New York City Building Code . 102.5 Change in occupancy. Refer to Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 3 102.6 Reserved. 102.7 Reserved. 102 .8 Referenced standards. The standards referenced in this code shall be those that are listed in Chapter 8 and in the rules of the department and such standards s hall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Refer to Article 103 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to referenced standards. 102.8.1 Editions of referenced standards. References to standards in this code shall be to the editions of those standards provided for in Chapter 8 of this code, or as otherwise provided by rule. 102.9 Requirements not covered by code. Requirements necessary for the strength, stability or proper operation of an existing or proposed installation, or for the public safety, health and general welfare, not specifically covered by this code, shall be determined by the commissioner . 102.10 Application of references. Reference to chapter secti on numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code. SECTION FGC 103 DEPARTMENT OF BUILDINGS 103.1 Enforcement agency. Refer to the New York City Charter and Cha pter 1 of Title 28 of the Administrative Code . 103.2 Reserved. 103.3 Reserved. 103.4 Reserved. SECTION FGC 104 DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS 104.1 General. The commissioner shall have the authority to render interpretations of this code, adopt rules, and establish policies and procedures in order to clarify and implement its provisions. Such interpretations, policies , procedures , and rules shall be in compliance with the int ent and purpose of this code. See the New York City Charter and Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to the authority of commissioner . SECTION FGC 105 APPROVALS 105.1 Approvals. Refer to Chapter 1 of Title 28 of the Administrative Code . SECTION FGC 106 PERMITS 106.1 General. Permits shall comply with this section, with Article 105 of Chapter 1 of Title 28 of the Administrative Code , and with requirements found elsewhere in this code. 106.2 Required. Any owner or authorized agent who intends to construct, add to, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install, add to, alter, repair, remove, convert or replace any gas, m e- chanical or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done , shall first make application for construction document approval in accordance with Chapter 1 of Title 28 of the Administrative Code and this chapter and obtain the required permit. ADMINISTRATION 1 - 4 2022 NEW YORK CITY FUEL GAS CODE 106. 3 Work exempt from permit. Exemptions from permit requirements of this code as authorized in Chapter 1 of Title 28 of the Administrative Code and the rules of the department shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisio ns of this code or any o ther laws or rules . 106.4 Validity of permit. The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other law. Permits presuming to give authority to violate or cancel the provisions of this code or other law shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the commissioner from requiring the correction of error s in the construction documents and other data. The commissioner is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other la w. 106.5 Other permits. In addition to any permits required by the provisions o f this code, permits for sidewalk and street openings shall be obtained from the Department of Transportation. 106.6 Permits with respect to limited alteration applications. For permits with respect to limited alteration applications, refer to Sections 28 - 101.5 and 28 - 104.6, Exception 1, of the Administrative Code . SECTION FGC 107 CONSTRUCTION DOCUMENTS 107.1 General. Construction documents shall comply with Article 104 of Chapter 1 of Title 28 of the Administrative Code and other applicable provisions of this code and its referenced standards. Such construction documents shall be coordinated with architectural, structural and means of egress plans. 107.2 Required documents. The applicant shall submit all of the documents specified in Sections 107.3 through 107.8 as appropriate to the nature and extent of the work proposed. Construction documents shall indicate the heating, ventilation, refrig eration, and other mechanical work to be performed, so drawn as to conform to the architectural and structural aspects of the building and to show in detail compliance with this code. 107.2.1 Composite plans. Composite plans showing compliance of architectural, structural, and mechanical parts of a building may be submitted provided that a clear understanding of each part is not impaired. 107.3 Lot diagram. The lot diagram shall be provided where applicable to the work proposed, including but not l imited to the installation of exterior or rooftop equipment. 107.4 Building classification statement. Where applicable to the proposed work, the statement shall identify: 1. The occupancy group or groups that apply to parts of the building code in accordan ce with Section 302 of the New York City Building Code ; 2. The occupancy group of the main use or dominant occupancy of the building; 3. The construction type of the building in accordance with Section 602 of the New York City Building Code ; 4. The structu ral occupancy/risk category in accordance with Table 1604.5 of the New York City Building Code ; 5. The height of the building as defined in Section 202 of the New York City Building Code ; 6. The applicable measurements to the highest and lowest level of Fire Department access; 7. Whether the building is inside or outside of the fire districts ; and 8. Whether the building is inside or outside a flood hazard area as such term is defined in Chapt er 2 of the New York City Building Code . 107.5 Fuel - gas - burning appliance and fuel - gas piping plans. Construction documents for fuel - gas - burning appliances and fuel - gas piping shall contain plans that include the following data and information: 1. Riser di agrams showing the story heights, the gas riser diameter, operating pressure, gas meter piping and related appli- ances. 2. Diagrammatic floor plans showing the size, location, and material for all gas distribution piping and related appliances. 3. Floor plans or partial floor plans showing the location, operating pressure, layout, size, and listing information for all gas meter piping, gas distribution piping, fuel - gas burning appliances, gas vents, and chimneys, with the riser numbers coordi- nated w ith other plans and diagrams. The floor plans shall indicate locations of meters and shutoff valves, including the outside gas cut - off required by Appendix E, Section E6. The plans shall also indicate the method or means of providing air to the appliance s pace, including duct and opening sizes , or means of direct venting . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 5 4. Plans indicating the location and type of any relevant smoke and heat detectors, alarm and fire - extinguishing systems. 5. Seismic protection and restraint details for piping and applian ces as required by Chapter 16 of the New York City Building Code . 6. Details indicating the location, size and materials for all breechings; the thickness and type of insulation materials; and t he clearances from combustible walls, partitions and ceiling; and the fire - resistive ratings of rooms and spaces containing the appliances. 7. Details describing the type, material, listing information, height, and termination distances to adjacent properties and stru c- tures for chimneys and gas vents. 8. Details show ing structural supports for fuel - gas - burning equipment where required. 9. In flood hazard areas , construction documents shall comply with Appendix G of the New York City Building Code . 107.6 Heating systems. Construction documents for heating systems shall include the temperature to be maintained in every room and the output capacity in BTU per hour (W) of the central heating source. 107.7 Boilers. Construction documents for boiler installations shall indicate the output capacity in BTU per hou r (W) , the operating weight of each boiler, the pressure setting of the relief valves, and such other data and information as required b y this code. 107.8 Energy efficiency. Construction documents shall include compliance documentation as required by the N ew York City Energy Conservation Code . 107.9 Retention of construction and submittal documents. Refer to Section 28 - 104.12 of the Administrative Code . SECTION FGC 108 INSPECTIONS AND TESTING 108.1 General. Except as otherwise specified in Section 28 - 116.2.4.3 of the Administrative Code , inspections required by this code or by the department during the progress of work may be performed on behalf of the owner by approved agencies or, if applicable, by special inspectors. However, in the interest of public safety, the commissioner may direct that any of such in- spections be performed by the department. All inspections shall be performed at the sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code for additional provisions relating to inspections. 108.2 Required inspections and testing. In addition to any inspections otherwise required by this code or applicable rules, the following inspections shall be require d: 1. Progress inspections: 1.1. Underground inspection and/or testing of installed piping, valves, fittings, support structures, anti - corrosion equipment and associated underground components shall be made before backfill is put in place. When excavated soil contains rocks, broken concrete, frozen chunks and other rubble that would damage or break the piping or cause corrosive action, clean backfill shall be on the job site ready for use in backfilling . 1.2. Rough - in inspe ction shall be made to determine that the materials, design, fabrication and installation comply with all requirements of this code. The inspection shall be conducted after the roof, framing, fireblocking and bracing are in place and components to be conce aled are complete, and prior to the installation of wall or ceiling membranes. The inspection shall be conducted prior to or in conjunction with the gas pressure test. This inspection may be completed in sections. Exceptions: 1. A rough - in inspection shall not be required when an existing gas appliance is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve, and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A rough - in inspection shall not be required when gas is reestablished by a utility company as permitted under Section 28 - 105.4.1 of the Administrative Code . 1.3. Inspections required by the New York City Energy Conservation Code shall be made in accordance with rules of the department, as applicable. 1.4. Gas final inspections shall be conducted after all appliances are installed, vented, wired and ready to operate with the establishment of gas. Gas final inspect ions shall include, but not be limited to, an inspection of components ADMINISTRATION 1 - 6 2022 NEW YORK CITY FUEL GAS CODE downstream of the appliance shutoff valve including gas piping, appliances, vents, accessory piping and make up air. Gas final inspections may be completed in sections. 2. Special inspe ctions. Special inspections shall be performed in accordance with this code and Chapter 17 of the New York City Building Code . 3. Periodic inspections. Periodic inspections of gas piping systems shall be conducted in accordance with Article 318 of Chapter 3 of Title 28 of the Administrative Code . 4. Final inspection: Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . 5. Issuance of certificate of compliance: Upon satisfactory inspection of service equipment and the satisfaction of all the requirements for sign - off, the department shall issue a certificate of compliance as applicable for the following service equipment: 5.1. Fuel - gas - burning equipment, 5.2. Heating systems, and 5.3. Boilers. The requirements of Section 108.2 shall not be considered to prohibit the operation of any heating equipment or appliances installed to replace existing heating equipment or appliances serving an occupied portion of a structure provided that a request for inspection of such heating equipment or appliances has been filed with the department not more than 48 hours after such replacement work is completed, and all required inspections are performed before any portion of such equipment or appliances is concealed by any permanent portion of the structure. 108.2.1 Approved inspection agencies. Refer to Articles 114 and 115 of Chapter 1 of Title 28 of the Administrative Code . 108.2.2 Inspection of prefabricated construction assemblies. Prior to the approval of a prefabricated construction assem- bly having concealed work and the issuance of a permi t, the department shall require the submittal of an evaluation report by an approved agency on each prefabricated construction assembly, indicating the complete details of the installation, including a description of the system and its components, the basi s upon which the system is being evaluated, test results and similar information and other data as necessary for the commissioner to determine conformance to this code. 108.2.2.1 Test and inspection records. Required test and inspection records shall be av ailable to the commissioner at all times during the fabrication of the installation and the erection of the building; or such records as the commissioner designates shall be filed. 108.2.3 Exposure of work. The work shall remain accessible and exposed for inspection purposes. Neither the commissioner nor the city shall be liable for expense entailed in the removal or replacement of any material required to allow inspection. 108.3 Testing. Installations shall be tested as required in this code an d in accordance with Sections 108.3.1 through 108.3.3 . Tests shall be made by the permit holder and witnessed by the department . 108.3.1 New, altered, extended or repaired installations. New installations and parts of existing installations that have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects. Exceptions: 1. A gas test shall not be required when an existing gas applianc e is replaced, provided that (i) no gas piping is replaced upstream of the existing appliance shutoff valve and (ii) not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve. 2. A gas test shall n ot be required when gas is reestablished by a utility company as permitted under section 28 - 105.4.1 of the Administrative Code . 108.3.2 Apparatus, instruments, material and labor for tests. Apparatus, instruments, material and labor required for test- ing an installation or part thereof shall be furnished by the permit holder. 108.3.3 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made t o comply with this code. The work or installation shall then be resubmitted to the department for inspection and testing. 108.3.4 Test validity. A gas test that is accepted by the department shall be valid for a period of one year from the date of the test . 108.4 Sign - off of completed work. Refer to Article 116 of Chapter 1 of Title 28 of the Administrative Code . ADMINISTRATION 2022 NEW YORK CITY FUEL GAS CODE 1 - 7 108.5 Temporary connection. The commissioner shall have the authority to allow the temporary connection of an installation to the sources of energy for the purpose of testing the installation or for use under a temporary certificate of occupancy. SECTION FGC 109 VIOLATIONS 109.1 General. Refer to Chapters 2 and 3 of Title 28 of the Administrative Code . 109.2 Authority to disconnect service utilities. The commissioner shall have the authority to require disconnection of utility service to the building, structure or system regulated by the t echnical codes in case of emergency where necessary to eliminate an immediate hazard to life or property. The commissioner shall notify the serving utility, and wherever possible, the owner and occupant of the building, structure or service system of the d ecision to disconnect prior to taking such action. If not notified prior to disconnection, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as prac- ticable thereafter. 109.3 Connection after order to d isconnect. A person shall not make energy source connections to installations regulated by this code that have been disconnected or ordered to be disconnected by the commissioner , or the use of which has been ordered to be discontinued by the commissioner until the commissioner authorizes the reconnection and use of such installations. When an installation is maintained in violation of this code, and in violation of a notice issue d pursuant to the provisions of this section, the commissioner shall institute appropriate action to prevent, restrain, correct or abate the violation.