‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi).1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,9005.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,30031 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,30031 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,0005 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping ‡‡‡ Chapter 4 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 4 GAS PIPING INSTALLATIONS SECTION FGC 401 GENERAL 401.1 Scope. This chapter shall govern the design, installation, modification and maintenance of fuel - gas piping sys- tems. The scope covered by this chapter includes piping systems from the point of delivery to the connections with the appliances and includes the design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance of such piping systems. 401.1.1 Meters and service piping. Service piping includes the fuel - gas piping up to the point of delivery. Meters and service piping shall comply with the requirements of Appendix E . In addition, service piping located within buildings shall be designed and installed in accordance with the structural integrity, firestopping, and fire protection provisions of the New York City Building Code . 401.1.2 Meters for gas consumption monitoring. Approved gas meters shall be permitted to be installed for gas consumpti on monitoring, energy measurement, verification and analysis. Gas meters shall be listed in accordance with ANSI B109.1, ANSI B109.2, or ANSI B109.3 and installed in accordance with the manufacturer’s instruc- tions. A full size valve bypass shall be provide d around gas meters for maintenance and repair. 401.2 Reserved. 401.3 Modifications to existing systems. In modifying or adding to existing piping systems, sizes shall be maintained in accordance with this chapter. 401.4 Additional appliances. Where an add itional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity for all appliances served. If inadequate, the existing system shall be enlarged as required or separate piping of adequate capacity shall be pr ovided. 401.5 Identification. All piping installed in new construction and all new piping installed in existing buildings, whether or not the piping is intended to be enclosed when construction is completed, shall be identified by a yellow label marked “Gas” in black letters. Where the installation requires a gas test, such labeling shall be completed prior to such test. Labels shall be provided in accordance with ASME A13.1 and the marking shall be spaced at intervals not exceeding 5 feet (1524 mm). The marking shall not be required on pipe located in the same room as the appliance served. 401.6 Interconnections. Where two or more meters are installed on the same premises but supply separate consumers, the pi ping systems shall not be interconnected on the outlet side of the meters. 401.7 Piping meter identification. Piping from multiple meter installations shall be marked with an approved per- manent identification by the installer so that the piping system supp lied by each meter is readily identifiable. Such marking shall be in accordance with ASME A13.1. 401.8 Minimum sizes. Pipe utilized for the installation, extension and alteration of any piping system shall be sized to supply the full number of outlets for the intended purpose and shall be sized in accordance with Section 402. 401.9 Identification. Each length of pipe and each pipe fitting, utilized in a fuel gas system, shall bear the identifica- tion of the manufacturer. 401.10 Third - party testing and certif ication. Piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code and shall be identified in accordance with Section 401.9. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS Piping, tubing and fittings shall either be tested by an approved third - party testing agency or certified by an approved third - party certification agency. SECTION FGC 402 PIPE SIZING 402.1 General considerations. Piping systems shall be of such size and so installed as to provide a supply of gas sufficient t o meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance. 402.2 Maximum gas demand. The volumetric flow rate of gas to be provided shall be the sum of the maximum input of the a ppliances served. The total connected hourly load shall be used as the basis for pipe sizing, assuming that all appliances could be operating at full capacity simultaneously. Where a diversity of load can be established, pipe sizing shall be permitted to b e based on such loads. The volumetric flow rate of gas to be provided shall be adjusted for altitude where the installation is above 2,000 feet (610 m) in elevation. 402.3 Sizing. Gas piping shall be sized in accordance with one of the following: 1. Pipe s izing tables or sizing equations in accordance with Section 402.4. 2. The sizing tables included in a listed piping system’s manufacturer’s instructions . 3. Other approved engineering methods. 4. Individual outlets to gas ranges shall not be less than 3 / 4 inches ( 19.1 mm) NPS. 402.4 Sizing tables and equations. Where Tables 402.4(1) through 402.4( 7) are used to size piping or tubing, the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. Where Equations 4 - 1 and 4 - 2 are used to size piping or tubing, the pipe or tubing shall have smooth inside walls and the pipe length shall be determined in accordance with Section 402.4.1, 402.4.2 or 402.4.3. 1. Low - pressure gas equation (Less than 1 1 / 2 pounds per square inch (psi) (10.3 kPa )) : D = Q 0 . 381 19 . 17 � ∆H C r × L � 0 . 206 (Equation 4 - 1) 2. High - pressure gas equation (1 1 / 2 psi (10.3 kPa) and above ): D = Q 0 . 381 18 . 93 � �P 1 2 − P 2 2 � × Y C r × L � 0 . 206 (Equation 4 - 2) where: D = Inside diameter of pipe, inches (mm). Q = Input rate appliance(s), cubic feet per hour at 60°F ( 15.6 °C) and 30 - inch mercury column. P 1 = Upstream pressure, psia ( P 1 + 14.7 ). P 2 = Downstream pressure, psia ( P 2 + 14.7 ). L = Equivalent length of pipe, feet. ∆ H = Pressure drop, inch water column (27.7 inch water col umn = 1 psi). GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS TABLE 402.4 C r AND Y VALUES FOR NATURAL GAS AT STANDARD CONDITIONS GAS EQUATION FACTORS C r Y Natural gas 0.6094 0.9992 For SI: 1 cubic foot = 0.028 m 3 , 1 foot = 305 mm, 1 - inch water column = 0.2488 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal unit per hour = 0.293 W. 402.4.1 Longest length method. The pipe size of each section of gas piping shall be determined using the longest length of piping from the point of delivery to the most remote outlet and the load of the section. 402.4.2 Branch length method. Pipe shall be sized as follows: 1. Pipe size of each section of the longest pipe run from the point of delivery to the most remote outlet shall be determined using the longest run of piping and the load of the section. 2. The pipe size of each section of branch piping not previously sized shall be determined using the length of piping from the point of delivery to the most remote outlet in each branch and the load of the section. 402.4.3 Hybrid pressure. The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery to the most remote line pressure regulator. The pipe size from the line pressure regulator to each outlet shall be determined using the length of piping from the regulator to the most remote outlet served by the regulator. TABLE 402.4(1) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.3 in. w. c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 31,700 51,300 105,000 191,000 303,000 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 21,800 35,300 72,400 132,000 208,000 30 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 40 62 129 243 499 747 1,440 2,290 4,050 8,270 15,000 24,200 49,800 90,400 143,000 50 55 114 215 442 662 1,280 2,030 3,590 7,330 13,300 21,500 44,100 80,100 127,000 60 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 70 46 95 179 368 552 1,060 1,690 3,000 6,110 11,100 17,900 36,800 66,800 106,000 80 42 89 167 343 514 989 1,580 2,790 5,680 10,300 16,700 34,200 62,100 98,400 90 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 100 38 79 148 304 455 877 1,400 2,470 5,040 9,110 14,800 30,300 55,100 87,200 125 33 70 131 269 403 777 1,240 2,190 4,460 8,080 13,100 26,900 48,800 77,300 150 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 175 28 58 109 224 336 648 1,030 1,820 3,720 6,730 10,900 22,400 40,700 64,400 200 26 54 102 209 313 602 960 1,700 3,460 6,260 10,100 20,800 37,900 59,900 250 23 48 90 185 277 534 851 1,500 3,070 5,550 8,990 18,500 33,500 53,100 300 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 350 19 40 75 154 231 445 709 1,250 2,560 4,630 7,490 15,400 28,000 44,300 GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 400 18 37 70 143 215 414 660 1,170 2,380 4,310 6,970 14,300 26,000 41,200 450 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 500 16 33 62 127 191 367 585 1,030 2,110 3,820 6,180 12,700 23,100 36,500 550 15 31 59 121 181 349 556 982 2,000 3,620 5,870 12,100 21,900 34,700 600 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 650 14 29 54 110 165 318 508 897 1,830 3,310 5,360 11,000 20,000 31,700 700 13 27 52 106 159 306 488 862 1,760 3,180 5,150 10,600 19,200 30,400 750 13 26 50 102 153 295 470 830 1,690 3,060 4,960 10,200 18,500 29,300 800 12 26 48 99 148 285 454 802 1,640 2,960 4,790 9,840 17,900 28,300 850 12 25 46 95 143 275 439 776 1,580 2,860 4,640 9,530 17,300 27,400 900 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 950 11 23 44 90 135 259 413 731 1,490 2,700 4,370 8,970 16,300 25,800 1,000 11 23 43 87 131 252 402 711 1,450 2,620 4,250 8,720 15,800 25,100 1,100 10 21 40 83 124 240 382 675 1,380 2,490 4,030 8,290 15,100 23,800 1,200 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 1,300 NA 20 37 76 114 219 349 617 1,260 2,280 3,680 7,570 13,700 21,800 1,400 NA 19 35 73 109 210 335 592 1,210 2,190 3,540 7,270 13,200 20,900 1,500 NA 18 34 70 105 203 323 571 1,160 2,110 3,410 7,010 12,700 20,100 1,600 NA 18 33 68 102 196 312 551 1,120 2,030 3,290 6,770 12,300 19,500 1,700 NA 17 32 66 98 189 302 533 1,090 1,970 3,190 6,550 11,900 18,800 1,800 NA 16 31 64 95 184 293 517 1,050 1,910 3,090 6,350 11,500 18,300 1,900 NA 16 30 62 93 178 284 502 1,020 1,850 3,000 6,170 11,200 17,700 2,000 NA 16 29 60 90 173 276 488 1,000 1,800 2,920 6,000 10,900 17,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2 psi Pressure Drop 0.5 in w.c. Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 5 6 8 10 12 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 41,800 67,600 139,000 252,000 399,000 20 118 247 466 957 1,430 2,760 4,400 7,780 15,900 28,700 46,500 95,500 173,000 275,000 30 95 199 374 768 1,150 2,220 3,530 6,250 12,700 23,000 37,300 76,700 139,000 220,000 40 81 170 320 657 985 1,900 3,020 5,350 10,900 19,700 31,900 65,600 119,000 189,000 50 72 151 284 583 873 1,680 2,680 4,740 9,660 17,500 28,300 58,200 106,000 167,000 60 65 137 257 528 791 1,520 2,430 4,290 8,760 15,800 25,600 52,700 95,700 152,000 70 60 126 237 486 728 1,400 2,230 3,950 8,050 14,600 23,600 48,500 88,100 139,000 80 56 117 220 452 677 1,300 2,080 3,670 7,490 13,600 22,000 45,100 81,900 130,000 90 52 110 207 424 635 1,220 1,950 3,450 7,030 12,700 20,600 42,300 76,900 122,000 100 50 104 195 400 600 1,160 1,840 3,260 6,640 12,000 19,500 40,000 72,600 115,000 125 44 92 173 355 532 1,020 1,630 2,890 5,890 10,600 17,200 35,400 64,300 102,000 150 40 83 157 322 482 928 1,480 2,610 5,330 9,650 15,600 32,100 58,300 92,300 175 37 77 144 296 443 854 1,360 2,410 4,910 8,880 14,400 29,500 53,600 84,900 GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS 200 34 71 134 275 412 794 1,270 2,240 4,560 8,260 13,400 27,500 49,900 79,000 250 30 63 119 244 366 704 1,120 1,980 4,050 7,320 11,900 24,300 44,200 70,000 300 27 57 108 221 331 638 1,020 1,800 3,670 6,630 10,700 22,100 40,100 63,400 350 25 53 99 203 305 587 935 1,650 3,370 6,100 9,880 20,300 36,900 58,400 400 23 49 92 189 283 546 870 1,540 3,140 5,680 9,190 18,900 34,300 54,300 450 22 46 86 177 266 512 816 1,440 2,940 5,330 8,620 17,700 32,200 50,900 500 21 43 82 168 251 484 771 1,360 2,780 5,030 8,150 16,700 30,400 48,100 550 20 41 78 159 239 459 732 1,290 2,640 4,780 7,740 15,900 28,900 45,700 600 19 39 74 152 228 438 699 1,240 2,520 4,560 7,380 15,200 27,500 43,600 650 18 38 71 145 218 420 669 1,180 2,410 4,360 7,070 14,500 26,400 41,800 700 17 36 68 140 209 403 643 1,140 2,320 4,190 6,790 14,000 25,300 40,100 750 17 35 66 135 202 389 619 1,090 2,230 4,040 6,540 13,400 24,400 38,600 800 16 34 63 130 195 375 598 1,060 2,160 3,900 6,320 13,000 23,600 37,300 850 16 33 61 126 189 363 579 1,020 2,090 3,780 6,110 12,600 22,800 36,100 900 15 32 59 122 183 352 561 992 2,020 3,660 5,930 12,200 22,100 35,000 950 15 31 58 118 178 342 545 963 1,960 3,550 5,760 11,800 21,500 34,000 1,000 14 30 56 115 173 333 530 937 1,910 3,460 5,600 11,500 20,900 33,100 1,100 14 28 53 109 164 316 503 890 1,810 3,280 5,320 10,900 19,800 31,400 1,200 13 27 51 104 156 301 480 849 1,730 3,130 5,070 10,400 18,900 30,000 1,300 12 26 49 100 150 289 460 813 1,660 3,000 4,860 9,980 18,100 28,700 1,400 12 25 47 96 144 277 442 781 1,590 2,880 4,670 9,590 17,400 27,600 1,500 11 24 45 93 139 267 426 752 1,530 2,780 4,500 9,240 16,800 26,600 1,600 11 23 44 89 134 258 411 727 1,480 2,680 4,340 8,920 16,200 25,600 1,700 11 22 42 86 130 250 398 703 1,430 2,590 4,200 8,630 15,700 24,800 1,800 10 22 41 84 126 242 386 682 1,390 2,520 4,070 8,370 15,200 24,100 1,900 10 21 40 81 122 235 375 662 1,350 2,440 3,960 8,130 14,800 23,400 2,000 NA 20 39 79 119 229 364 644 1,310 2,380 3,850 7,910 14,400 22,700 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Notes: 1. NA means a flow of less than 10 cfh. 2. All table entries have been rounded to three significant digits. TABLE 402.4(3) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 3.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 8.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 454 949 1,790 3,670 5,500 10,600 16,900 29,800 60,800 20 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 30 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 40 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 50 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 60 172 360 678 1,390 2,090 4,020 6,400 11,300 23,100 70 158 331 624 1,280 1,920 3,700 5,890 10,400 21,200 80 147 308 580 1,190 1,790 3,440 5,480 9.690 19,800 90 138 289 544 1,120 1,680 3,230 5,140 9,090 18,500 GAS PIPING INSTALLATIONS 100 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 125 116 242 456 936 1,400 2,700 4,300 7,610 15,500 150 105 219 413 848 1,270 2,450 3,900 6,890 14,100 175 96 202 380 780 1,170 2,250 3,590 6,340 12,900 200 90 188 353 726 1,090 2,090 3,340 5,900 12,000 250 80 166 313 643 964 1,860 2,960 5,230 10,700 300 72 151 284 583 873 1,680 2,680 4,740 9,700 350 66 139 261 536 803 1,550 2,470 4,360 8,900 400 62 129 243 499 747 1,440 2,290 4,060 8,300 450 58 121 228 468 701 1.350 2,150 3,800 7,800 500 55 114 215 442 662 1,280 2,030 3,590 7,300 550 52 109 204 420 629 1,210 1,930 3,410 7,000 600 50 104 195 400 600 1,160 1,840 3,260 6,640 650 47 99 187 384 575 1,110 1,760 3,120 6,360 700 46 95 179 368 552 1,060 1,700 3,000 6,110 750 44 92 173 355 532 1,020 1,630 2,890 5,890 800 42 89 167 343 514 989 1,580 2,790 5,680 850 41 86 162 332 497 957 1,530 2,700 5,500 900 40 83 157 322 482 928 1,480 2,620 5,330 950 39 81 152 312 468 901 1,440 2,540 5,180 1,000 38 79 148 304 455 877 1,400 2,470 5,040 1,100 36 75 141 289 432 833 1,330 2,350 4,780 1,200 34 71 134 275 412 794 1,270 2,240 4,560 1,300 33 68 128 264 395 761 1,210 2,140 4,370 1,400 31 65 123 253 379 731 1,170 2,060 4,200 1,500 30 63 119 244 366 704 1,120 1,980 4,050 1,600 29 61 115 236 353 680 1,080 1,920 3,910 1,700 28 59 111 228 342 658 1,050 1,850 3,780 1,800 27 57 108 221 331 638 1,020 1,800 3,670 1,900 27 56 105 215 322 619 987 1,750 3,560 2,000 26 54 102 209 313 602 960 1,700 3,460 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(4) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure Less than 2.0 psi Pressure Drop 6.0 in. w.c. Specific Gravity 0.60 INTENDED USE: Initial supply pressure of 11.0 inches w.c. or greater PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 660 1,380 2,600 5,340 8,000 15,400 24,600 43,400 88,500 20 454 949 1,790 3,670 5,500 10.600 16,900 29,900 60,800 30 364 762 1,440 2,950 4,420 8.500 13,600 24,000 48,900 40 312 652 1,230 2,520 3,780 7,280 11,600 20,500 41,800 50 276 578 1,090 2,240 3,350 6,450 10,300 18,200 37,100 60 250 524 986 2,030 3,030 5,840 9,310 16,500 33,600 70 230 482 907 1,860 2,790 5,380 8,570 15,100 30,900 GAS PIPING INSTALLATIONS 80 214 448 844 1,730 2,600 5,000 7,970 14,100 28,700 90 201 420 792 1,630 2,440 4,690 7,480 13,200 27,000 100 190 397 748 1,540 2,300 4,430 7,070 12,500 25,500 125 168 352 663 1,360 2,040 3,930 6,260 11,100 22,600 150 153 319 601 1,230 1,850 3,560 5,670 10,000 20,500 175 140 293 553 1,140 1,700 3,280 5,220 9,230 18,800 200 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 250 116 242 456 936 1,400 2,700 4,300 7,610 15,500 300 105 219 413 848 1,270 2,450 3,900 6,890 14,100 350 96 202 380 780 1,170 2,250 3,590 6,340 12,900 400 90 188 353 726 1,090 2,090 3,340 5,900 12,000 450 84 176 332 681 1,020 1,970 3,130 5,540 11,300 500 80 166 313 643 964 1,860 2,960 5,230 10,700 550 76 158 297 611 915 1,760 2,810 4,970 10,100 600 72 151 284 583 873 1,680 2,680 4,740 9,660 650 69 144 272 558 836 1,610 2,570 4,540 9,250 700 66 139 261 536 803 1,550 2,470 4,360 8.890 750 64 134 252 516 774 1,490 2,380 4,200 8,560 800 62 129 243 499 747 1,440 2,290 4,060 8,270 850 60 125 235 483 723 1,390 2,220 3,920 8,000 900 58 121 228 468 701 1,350 2,150 3,800 7,760 950 56 118 221 454 681 1,310 2,090 3,700 7,540 1,000 55 114 215 442 662 1,280 2,030 3,590 7,330 1,100 52 109 204 420 629 1,210 1,930 3,410 6,960 1,200 50 104 195 400 600 1,160 1,840 3,260 6,640 1,300 47 99 187 384 575 1,100 1,760 3,120 6,360 1,400 46 95 179 368 552 1,060 1,700 3,000 6,110 1,500 44 92 173 355 532 1,020 1,630 2,890 5,890 1,600 42 89 167 343 514 989 1,580 2,790 5,680 1,700 41 86 162 332 497 957 1,530 2,700 5,500 1,800 40 83 157 322 482 928 1,480 2,620 5,330 1,900 39 81 152 312 468 901 1,440 2,540 5,180 2,000 38 79 148 304 455 877 1,400 2,470 5,040 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0. 01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(5) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 2.0 psi Pressure Drop 1.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92,800 189,000 20 1,070 2,150 3,930 8,070 12,100 23,300 37,100 65,600 134,000 30 869 1,760 3,210 6,590 9,880 19,000 30,300 53,600 109,000 40 753 1,520 2,780 5,710 8,550 16,500 26,300 46,400 94,700 50 673 1,360 2,490 5,110 7,650 14,700 23,500 41,500 84,700 60 615 1,240 2,270 4,660 6,980 13,500 21,400 37,900 77,300 GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS FIGURE 408.4 METHOD O F INSTALLING A TEE FITTING SEDIMENT TRAP SECTION FGC 409 SHUTOFF VALVES 409.1 General. Piping systems shall be provided with shutoff valves in accordance with this section. 409.1.1 Valve approval. Shutoff valves shall be of an approved type; shall be const ructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1. TABLE 409.1.1 MANUAL GAS VALVE STANDARDS VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1 / 2 psig PRESSURE OTHER VALVE APPLICATIONS UP TO 1 / 2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE ANSI Z21.15 / CGA 9.1 X — — — — ASME B16.44 X X X a X b — ASME B16.33 X X X X X For SI: 1 pound per square inch gauge = 6.895 kPa. a. If labeled 2G. b. If labeled 5G. GAS PIPING INSTALLATIONS 409.1.2 Prohibited locations. Shutoff valves shall be prohibited in concealed locations and furnace plenums. 409.1.3 Access to shutoff valves. Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage. 409.2 Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter. Meter valves shall be of a type approved b y the utility company. 409.3 Shutoff valves for multiple - house line systems. Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant. 409.3.1 Multiple tenant buildings. In multiple tenant buildings, where a common piping system is installed to supply other than individual dwelling units, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tena nt’s space. 409.3.2 Individual buildings. In a common system serving more than one building, shutoff valves shall be installed outdoors at each building. 409.3.3 Identification of shutoff valves. Each house line shutoff valve shall be plainly marked with a n iden- tification tag attached by the installer so that the piping systems supplied by such valves are readily identified. Identification shall be provided in compliance with ASME A13.1. 409.4 MP regulator valves. An approved shutoff valve shall be installe d immediately ahead of each MP regulator. 409.5 Appliance shutoff valve. Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1 or 409.5. 2 . 409.5.1 Located within the same room. The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet ( 1828.8 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access and located not more than 60 inches (1524 mm) above the finished floor . Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions. Where the shutoff valve is located in the firebox , a remote shutoff valve shall also be provided. Exception: Shutoff valves may be located more than 60 inches (1524 mm) above the finished floor where the gas connection to the appliance is more than 60 inches (1524 m m) above the finished floor. 409.5.2 Vented decorative appliances and room heaters. Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet ( 1828.8 mm) of the appliance shall be designe d, sized and installed in accordance with Sections 401 through 408. 409.6 Shutoff valve for laboratories. Where provided with two or more fuel gas outlets, including table - , bench - and hood - mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through whic h all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shuto ff.” 409.7 Outside gas cut - off. An outside gas service line valve or other outside shutoff device or method acceptable to the commissioner shall be provided in accordance with Section E.2 of Appendix E. 409.8 Riser shutoff valves. Risers shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. 409.9 Branch shutoff valves. Branches serving more than one appliance shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. SECTION FGC 410 FLOW CONTROLS GAS PIPING INSTALLATIONS 410.1 Pressure regulators. A line pressure regulator shall be i nstalled where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80 /CSA 6.22 . Access shall be provided to pressure regulators. Pressure regulators shal l be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. 410.2 MP regulators. Medium pressure (MP) regulators shall comply with the following: 1. The MP regulator shall be approve d and shall be suitable for the inlet and outlet gas pressures for the application. 2. The MP regulator shall maintain a reduced outlet pressure under lockup (no - flow) conditions. 3. The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served. 4. The MP regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak - limiting device, in either case comply ing with Section 410.3. 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument and to serve as a sediment trap. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. A pressure gauge with an isolation valve may also be installed in addition to the fitting. 7. At least one union shall be installed within 1 foot (304.8 mm) of either side of the MP regulator. 410.3 Venting of regulators. Pressure regulators that require a vent shall be vented directly to the outdoors. The vent terminal shall be a minimum of 18 inches ( 457.2 mm) above grade, not under a building - opening or overhang, and shall be installed so as to prevent the entrance of water and insects. Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent - limiting device installed in accordanc e with ANSI Z21.18 and the manufacturer’s instructions. The vent - limiting device shall be installed in a location sufficiently ventilated to dissipate any gas discharged from the device. 410.3.1 Vent piping. Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pres- sure - regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes back pres sure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions . 410.4 Excess flow valves. Where automatic excess flow valves are installed, they shall be listed for the application and shall be sized and installed in accordance with the manufacturer’s instructions. 410.5 Flashback arrestor check valve. Where fuel gas is used with oxygen in any hot work operation, a listed pro- tective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an ap- proved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas suppl y is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appli- ance that increases pressure to the level required for such safe operation. SECTION FGC 411 APPLIANCE AND MANUFACTURED HOME CONNECTIO NS 411.1 Connecting appliances. Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: GAS PIPING INSTALLATIONS 1. Rigid metallic pipe and fittings. Space heaters and water heaters shall be connected using rigid piping an d fittings only. Use of semirigid (flexible) metallic tubing, fittings , appliance connectors or quick - disconnect devices is not permitted for this application. 2. Listed and labeled appliance connectors in compliance with ANSI Z21.24 /CGA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance. Connectors shall have an overall length not to exceed 6 feet (1828.8 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance. 3. Listed and labeled quick - disconnect devices used in conjunction with listed and labeled appliance connectors. 4. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance con nectors. 5. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 6. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect porta ble outdoor appli- ances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick - disconnect device or listed gas convenience outlet. 411. 1.1 Commercial cooking appliances. Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.6 9 /CSA 6.16 and NSF/ANSI 169 or in accordance with Item 1 of Section 411.1. The commercial cooking appliance connector installation shall be configured in accordance with the manu- facturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions. 411.1.2 Protection against damage. Connectors and tubing shall be installed so as to be protected against physical damage. 411.1.3 Connector installation. Fuel connectors shall be installed in accordance with the manufacturer’s instruc- tions and Sections 411.1.3.1 through 411.1.3.4. 411.1.3 .1 Maximum length. Connectors shall have an overall length not to exceed 6 feet ( 1828.8 mm). Meas- urement shall be made along the centerline of the connector. Only one connector shall be used for each appli- ance. 411.1.3.2 Minimum size. Connectors shall have the capacity for the total demand of the connected appliance. 411.1.3.3 Prohibited locations and penetrations. Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings. Exceptions: 1. Connect ors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2. 2. Rigid steel pipe connectors shall be per mitted to extend through openings in appliance housings. 3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in ac- cordance with the listing of the appliance. 4. Listed connectors shall be permitted to extend t hrough an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage. 411.1.3.4 Shutoff valve. A shutoff valve not less than the nominal size of the piping system shall be installed ahead of the connector i n accordance with Section 409.5. 411.1.4 Movable appliances. Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69 /CSA 6.16 or by means of Item 1 of Section 411.1 of this code . Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions . GAS PIPING INSTALLATIONS 70 569 1,150 2,100 4,320 6,470 12,500 19,900 35,100 71,600 80 532 1,080 1,970 4,040 6,050 11,700 18,600 32,800 67,000 90 502 1,010 1,850 3,810 5,700 11,000 17,500 30,900 63,100 100 462 934 1,710 3,510 5,260 10,100 16,100 28,500 58,200 125 414 836 1,530 3,140 4,700 9,060 14,400 25,500 52,100 150 372 751 1,370 2,820 4,220 8,130 13,000 22,900 46,700 175 344 695 1,270 2,601 3,910 7,530 12,000 21,200 43,300 200 318 642 1,170 2,410 3,610 6,960 11,100 19,600 40,000 250 279 583 1,040 2,140 3,210 6,180 9,850 17,400 35,500 300 253 528 945 1,940 2,910 5,600 8,920 15,800 32,200 350 232 486 869 1,790 2,670 5,150 8,210 14,500 29,600 400 216 452 809 1,660 2,490 4,790 7,640 13,500 27,500 450 203 424 759 1,560 2,330 4,500 7,170 12,700 25,800 500 192 401 717 1,470 2,210 4,250 6,770 12,000 24,400 550 182 381 681 1,400 2,090 4,030 6,430 11,400 23,200 600 174 363 650 1,330 2,000 3,850 6,130 10,800 22,100 650 166 348 622 1,280 1,910 3,680 5,870 10,400 21,200 700 160 334 598 1,230 1,840 3,540 5,640 9,970 20,300 750 154 322 576 1,180 1,770 3,410 5,440 9,610 19,600 800 149 311 556 1,140 1,710 3,290 5,250 9,280 18,900 850 144 301 538 1,100 1,650 3,190 5,080 8,980 18,300 900 139 292 522 1,070 1,600 3,090 4,930 8,710 17,800 950 135 283 507 1,040 1,560 3,000 4,780 8,460 17,200 1,000 132 275 493 1,010 1,520 2,920 4,650 8,220 16,800 1,100 125 262 468 960 1,440 2,770 4,420 7,810 15,900 1,200 119 250 446 917 1,370 2,640 4,220 7,450 15,200 1,300 114 239 427 878 1,320 2,530 4,040 7,140 14,600 1,400 110 230 411 843 1,260 2,430 3,880 6,860 14,000 1,500 106 221 396 812 1,220 2,340 3,740 6,600 13,500 1,600 102 214 382 784 1,180 2,260 3,610 6,380 13,000 1,700 99 207 370 759 1,140 2,190 3,490 6,170 12,600 1,800 96 200 358 736 1,100 2,120 3,390 5,980 12,200 1,900 93 195 348 715 1,070 2,060 3,290 5,810 11,900 2,000 91 189 339 695 1,040 2,010 3,200 5,650 11,500 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(6) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 3.0 psi Pressure Drop 2.0 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87,500 155,000 316,000 20 1,620 3,380 6,370 13,100 19,600 37,700 60,100 106,000 217,000 30 1,300 2,720 5,110 10,500 15,700 30,300 48,300 85,400 174,000 40 1,110 2,320 4,380 8,990 13,500 25,900 41,300 73,100 149,000 50 985 2,060 3,880 7,970 11,900 23,000 36,600 64,800 132,000 GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS FIGURE 408.4 METHOD O F INSTALLING A TEE FITTING SEDIMENT TRAP SECTION FGC 409 SHUTOFF VALVES 409.1 General. Piping systems shall be provided with shutoff valves in accordance with this section. 409.1.1 Valve approval. Shutoff valves shall be of an approved type; shall be const ructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1. TABLE 409.1.1 MANUAL GAS VALVE STANDARDS VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1 / 2 psig PRESSURE OTHER VALVE APPLICATIONS UP TO 1 / 2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE ANSI Z21.15 / CGA 9.1 X — — — — ASME B16.44 X X X a X b — ASME B16.33 X X X X X For SI: 1 pound per square inch gauge = 6.895 kPa. a. If labeled 2G. b. If labeled 5G. GAS PIPING INSTALLATIONS 409.1.2 Prohibited locations. Shutoff valves shall be prohibited in concealed locations and furnace plenums. 409.1.3 Access to shutoff valves. Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage. 409.2 Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter. Meter valves shall be of a type approved b y the utility company. 409.3 Shutoff valves for multiple - house line systems. Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant. 409.3.1 Multiple tenant buildings. In multiple tenant buildings, where a common piping system is installed to supply other than individual dwelling units, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tena nt’s space. 409.3.2 Individual buildings. In a common system serving more than one building, shutoff valves shall be installed outdoors at each building. 409.3.3 Identification of shutoff valves. Each house line shutoff valve shall be plainly marked with a n iden- tification tag attached by the installer so that the piping systems supplied by such valves are readily identified. Identification shall be provided in compliance with ASME A13.1. 409.4 MP regulator valves. An approved shutoff valve shall be installe d immediately ahead of each MP regulator. 409.5 Appliance shutoff valve. Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1 or 409.5. 2 . 409.5.1 Located within the same room. The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet ( 1828.8 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access and located not more than 60 inches (1524 mm) above the finished floor . Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions. Where the shutoff valve is located in the firebox , a remote shutoff valve shall also be provided. Exception: Shutoff valves may be located more than 60 inches (1524 mm) above the finished floor where the gas connection to the appliance is more than 60 inches (1524 m m) above the finished floor. 409.5.2 Vented decorative appliances and room heaters. Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet ( 1828.8 mm) of the appliance shall be designe d, sized and installed in accordance with Sections 401 through 408. 409.6 Shutoff valve for laboratories. Where provided with two or more fuel gas outlets, including table - , bench - and hood - mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through whic h all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shuto ff.” 409.7 Outside gas cut - off. An outside gas service line valve or other outside shutoff device or method acceptable to the commissioner shall be provided in accordance with Section E.2 of Appendix E. 409.8 Riser shutoff valves. Risers shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. 409.9 Branch shutoff valves. Branches serving more than one appliance shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. SECTION FGC 410 FLOW CONTROLS GAS PIPING INSTALLATIONS 410.1 Pressure regulators. A line pressure regulator shall be i nstalled where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80 /CSA 6.22 . Access shall be provided to pressure regulators. Pressure regulators shal l be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. 410.2 MP regulators. Medium pressure (MP) regulators shall comply with the following: 1. The MP regulator shall be approve d and shall be suitable for the inlet and outlet gas pressures for the application. 2. The MP regulator shall maintain a reduced outlet pressure under lockup (no - flow) conditions. 3. The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served. 4. The MP regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak - limiting device, in either case comply ing with Section 410.3. 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument and to serve as a sediment trap. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. A pressure gauge with an isolation valve may also be installed in addition to the fitting. 7. At least one union shall be installed within 1 foot (304.8 mm) of either side of the MP regulator. 410.3 Venting of regulators. Pressure regulators that require a vent shall be vented directly to the outdoors. The vent terminal shall be a minimum of 18 inches ( 457.2 mm) above grade, not under a building - opening or overhang, and shall be installed so as to prevent the entrance of water and insects. Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent - limiting device installed in accordanc e with ANSI Z21.18 and the manufacturer’s instructions. The vent - limiting device shall be installed in a location sufficiently ventilated to dissipate any gas discharged from the device. 410.3.1 Vent piping. Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pres- sure - regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes back pres sure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions . 410.4 Excess flow valves. Where automatic excess flow valves are installed, they shall be listed for the application and shall be sized and installed in accordance with the manufacturer’s instructions. 410.5 Flashback arrestor check valve. Where fuel gas is used with oxygen in any hot work operation, a listed pro- tective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an ap- proved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas suppl y is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appli- ance that increases pressure to the level required for such safe operation. SECTION FGC 411 APPLIANCE AND MANUFACTURED HOME CONNECTIO NS 411.1 Connecting appliances. Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: GAS PIPING INSTALLATIONS 1. Rigid metallic pipe and fittings. Space heaters and water heaters shall be connected using rigid piping an d fittings only. Use of semirigid (flexible) metallic tubing, fittings , appliance connectors or quick - disconnect devices is not permitted for this application. 2. Listed and labeled appliance connectors in compliance with ANSI Z21.24 /CGA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance. Connectors shall have an overall length not to exceed 6 feet (1828.8 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance. 3. Listed and labeled quick - disconnect devices used in conjunction with listed and labeled appliance connectors. 4. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance con nectors. 5. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 6. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect porta ble outdoor appli- ances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick - disconnect device or listed gas convenience outlet. 411. 1.1 Commercial cooking appliances. Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.6 9 /CSA 6.16 and NSF/ANSI 169 or in accordance with Item 1 of Section 411.1. The commercial cooking appliance connector installation shall be configured in accordance with the manu- facturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions. 411.1.2 Protection against damage. Connectors and tubing shall be installed so as to be protected against physical damage. 411.1.3 Connector installation. Fuel connectors shall be installed in accordance with the manufacturer’s instruc- tions and Sections 411.1.3.1 through 411.1.3.4. 411.1.3 .1 Maximum length. Connectors shall have an overall length not to exceed 6 feet ( 1828.8 mm). Meas- urement shall be made along the centerline of the connector. Only one connector shall be used for each appli- ance. 411.1.3.2 Minimum size. Connectors shall have the capacity for the total demand of the connected appliance. 411.1.3.3 Prohibited locations and penetrations. Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings. Exceptions: 1. Connect ors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2. 2. Rigid steel pipe connectors shall be per mitted to extend through openings in appliance housings. 3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in ac- cordance with the listing of the appliance. 4. Listed connectors shall be permitted to extend t hrough an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage. 411.1.3.4 Shutoff valve. A shutoff valve not less than the nominal size of the piping system shall be installed ahead of the connector i n accordance with Section 409.5. 411.1.4 Movable appliances. Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69 /CSA 6.16 or by means of Item 1 of Section 411.1 of this code . Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions . GAS PIPING INSTALLATIONS 60 892 1,870 3,520 7,220 10,800 20,800 33,200 58,700 120,000 70 821 1,720 3,230 6,640 9,950 19,200 30,500 54,000 110,000 80 764 1,600 3,010 6,180 9,260 17,800 28,400 50,200 102,000 90 717 1,500 2,820 5,800 8,680 16,700 26,700 47,100 96,100 100 677 1,420 2,670 5,470 8,200 15,800 25,200 44,500 90,800 125 600 1,250 2,360 4,850 7,270 14,000 22,300 39,500 80,500 150 544 1,140 2,140 4,400 6,590 12,700 20,200 35,700 72,900 175 500 1,050 1,970 4,040 6,060 11,700 18,600 32,900 67,100 200 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 250 412 862 1,620 3,330 5,000 9,620 15,300 27,100 55,300 300 374 781 1,470 3,020 4,530 8,720 13,900 24,600 50,100 350 344 719 1,350 2,780 4,170 8,020 12,800 22,600 46,100 400 320 669 1,260 2,590 3,870 7,460 11,900 21,000 42,900 450 300 627 1,180 2,430 3,640 7,000 11,200 19,700 40,200 500 283 593 1,120 2,290 3,430 6,610 10,500 18,600 38,000 550 269 563 1,060 2,180 3,260 6,280 10,000 17,700 36,100 600 257 537 1,010 2,080 3,110 5,990 9,550 16,900 34,400 650 246 514 969 1,990 2,980 5,740 9,150 16,200 33,000 700 236 494 931 1,910 2,860 5,510 8,790 15,500 31,700 750 228 476 897 1,840 2,760 5,310 8,470 15,000 30,500 800 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 850 213 445 838 1,720 2,580 4,960 7,910 14,000 28,500 900 206 431 812 1,670 2,500 4,810 7,670 13,600 27,700 950 200 419 789 1,620 2,430 4,670 7,450 13,200 26,900 1,000 195 407 767 1,580 2,360 4,550 7,240 12,800 26,100 1,100 185 387 729 1,500 2,240 4,320 6,890 12,200 24,800 1,200 177 369 695 1,430 2,140 4,120 6,570 11,600 23,700 1,300 169 353 666 1,370 2,050 3,940 6,290 11,100 22,700 1,400 162 340 640 1,310 1,970 3,790 6,040 10,700 21,800 1,500 156 327 616 1,270 1,900 3,650 5,820 10,300 21,000 1,600 151 316 595 1,220 1,830 3,530 5,620 10,000 20,300 1,700 146 306 576 1,180 1,770 3,410 5,440 9,610 19,600 1,800 142 296 558 1,150 1,720 3,310 5,270 9,320 19,000 1,900 138 288 542 1,110 1,670 3,210 5,120 9,050 18,400 2,000 134 280 527 1,080 1,620 3,120 4,980 8,800 18,000 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. TABLE 402.4(7) SCHEDULE 40 METALLIC PIPE Gas Natural Inlet Pressure 5.0 psi Pressure Drop 3.5 psi Specific Gravity 0.60 PIPE SIZE (inch) Nominal 1 / 2 3 / 4 1 1 1 / 4 1 1 / 2 2 2 1 / 2 3 4 Actual ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Cubic Feet of Gas Per Hour 10 3,190 6,430 11,800 24,200 36,200 69,700 111,000 196,000 401,000 20 2,250 4,550 8,320 17,100 25,600 49,300 78,600 139,000 283,000 30 1,840 3,720 6,790 14,000 20,900 40,300 64,200 113,000 231,000 40 1,590 3,220 5,880 12,100 18,100 34,900 55,600 98,200 200,000 GAS PIPING INSTALLATIONS 50 1,430 2,880 5,260 10,800 16,200 31,200 49,700 87,900 179,000 60 1,300 2,630 4,800 9,860 14,800 28,500 45,400 80,200 164,000 70 1,200 2,430 4,450 9,130 13,700 26,400 42,000 74,300 151,000 80 1,150 2,330 4,260 8,540 12,800 24,700 39,300 69,500 142,000 90 1,060 2,150 3,920 8,050 12,100 23,200 37,000 65,500 134,000 100 979 1,980 3,620 7,430 11,100 21,400 34,200 60,400 123,000 125 876 1,770 3,240 6,640 9,950 19,200 30,600 54,000 110,000 150 786 1,590 2,910 5,960 8,940 17,200 27,400 48,500 98,900 175 728 1,470 2,690 5,520 8,270 15,900 25,400 44,900 91,600 200 673 1,360 2,490 5,100 7,650 14,700 23,500 41,500 84,700 250 558 1,170 2,200 4,510 6,760 13,000 20,800 36,700 74,900 300 506 1,060 1,990 4,090 6,130 11,800 18,800 33,300 67,800 350 465 973 1,830 3,760 5,640 10,900 17,300 30,600 62,400 400 433 905 1,710 3,500 5,250 10,100 16,100 28,500 58,100 450 406 849 1,600 3,290 4,920 9,480 15,100 26,700 54,500 500 384 802 1,510 3,100 4,650 8,950 14,300 25,200 51,500 550 364 762 1,440 2,950 4,420 8,500 13,600 24,000 48,900 600 348 727 1,370 2,810 4,210 8,110 12,900 22,900 46,600 650 333 696 1,310 2,690 4,030 7,770 12,400 21,900 44,600 700 320 669 1,260 2,590 3,880 7,460 11,900 21,000 42,900 750 308 644 1,210 2,490 3,730 7,190 11,500 20,300 41,300 800 298 622 1,170 2,410 3,610 6,940 11,100 19,600 39,900 850 288 602 1,130 2,330 3,490 6,720 10,700 18,900 38,600 900 279 584 1,100 2,260 3,380 6,520 10,400 18,400 37,400 950 271 567 1,070 2,190 3,290 6,330 10,100 17,800 36,400 1,000 264 551 1,040 2,130 3,200 6,150 9,810 17,300 35,400 1,100 250 524 987 2,030 3,030 5,840 9,320 16,500 33,600 1,200 239 500 941 1,930 2,900 5,580 8,890 15,700 32,000 1,300 229 478 901 1,850 2,770 5,340 8,510 15,000 30,700 1,400 220 460 866 1,780 2,660 5,130 8,180 14,500 29,500 1,500 212 443 834 1,710 2,570 4,940 7,880 13,900 28,400 1,600 205 428 806 1,650 2,480 4,770 7,610 13,400 27,400 1,700 198 414 780 1,600 2,400 4,620 7,360 13,000 26,500 1,800 192 401 756 1,550 2,330 4,480 7,140 12,600 25,700 1,900 186 390 734 1,510 2,260 4,350 6,930 12,300 25,000 2,000 181 379 714 1,470 2,200 4,230 6,740 11,900 24,300 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 - inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m 3 /h, 1 degree = 0.01745 rad. Note: All table entries have been rounded to three significant digits. 402.5 Allowable pressure drop. The design pressure loss in any piping system under maximum probable flow con- ditions, from the point of delivery to the inlet connection of the appliance, shall be such that the supply pressure at the appl iance is greater than or equal to the minimum pressure required by the appliance. 402.6 Gas distribution pressures. The maximum design operating pressure for piping systems located inside build- ings shall not exceed 1 / 2 pounds per square inch gauge (psig) ( 3.5 kPa gauge). Exceptions: 1. Pressure not exceeding 5 psig (34.5 kPa gauge) is permitted where a system supplies o ne or more appliances that require gas pressure in excess of 1 / 2 psig (3.5 kPa gauge) . 2. Gas pressure not exceeding 15 psig ( 103.4 kPa gauge) is permitted for appliances in excess of 100,000 cubic feet per hour (2830 m 3 /h) provided the gas distribution piping is installed as provided for in Section 404. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS FIGURE 408.4 METHOD O F INSTALLING A TEE FITTING SEDIMENT TRAP SECTION FGC 409 SHUTOFF VALVES 409.1 General. Piping systems shall be provided with shutoff valves in accordance with this section. 409.1.1 Valve approval. Shutoff valves shall be of an approved type; shall be const ructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1. TABLE 409.1.1 MANUAL GAS VALVE STANDARDS VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1 / 2 psig PRESSURE OTHER VALVE APPLICATIONS UP TO 1 / 2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE ANSI Z21.15 / CGA 9.1 X — — — — ASME B16.44 X X X a X b — ASME B16.33 X X X X X For SI: 1 pound per square inch gauge = 6.895 kPa. a. If labeled 2G. b. If labeled 5G. GAS PIPING INSTALLATIONS 409.1.2 Prohibited locations. Shutoff valves shall be prohibited in concealed locations and furnace plenums. 409.1.3 Access to shutoff valves. Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage. 409.2 Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter. Meter valves shall be of a type approved b y the utility company. 409.3 Shutoff valves for multiple - house line systems. Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant. 409.3.1 Multiple tenant buildings. In multiple tenant buildings, where a common piping system is installed to supply other than individual dwelling units, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tena nt’s space. 409.3.2 Individual buildings. In a common system serving more than one building, shutoff valves shall be installed outdoors at each building. 409.3.3 Identification of shutoff valves. Each house line shutoff valve shall be plainly marked with a n iden- tification tag attached by the installer so that the piping systems supplied by such valves are readily identified. Identification shall be provided in compliance with ASME A13.1. 409.4 MP regulator valves. An approved shutoff valve shall be installe d immediately ahead of each MP regulator. 409.5 Appliance shutoff valve. Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1 or 409.5. 2 . 409.5.1 Located within the same room. The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet ( 1828.8 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access and located not more than 60 inches (1524 mm) above the finished floor . Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions. Where the shutoff valve is located in the firebox , a remote shutoff valve shall also be provided. Exception: Shutoff valves may be located more than 60 inches (1524 mm) above the finished floor where the gas connection to the appliance is more than 60 inches (1524 m m) above the finished floor. 409.5.2 Vented decorative appliances and room heaters. Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet ( 1828.8 mm) of the appliance shall be designe d, sized and installed in accordance with Sections 401 through 408. 409.6 Shutoff valve for laboratories. Where provided with two or more fuel gas outlets, including table - , bench - and hood - mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through whic h all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shuto ff.” 409.7 Outside gas cut - off. An outside gas service line valve or other outside shutoff device or method acceptable to the commissioner shall be provided in accordance with Section E.2 of Appendix E. 409.8 Riser shutoff valves. Risers shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. 409.9 Branch shutoff valves. Branches serving more than one appliance shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. SECTION FGC 410 FLOW CONTROLS GAS PIPING INSTALLATIONS 410.1 Pressure regulators. A line pressure regulator shall be i nstalled where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80 /CSA 6.22 . Access shall be provided to pressure regulators. Pressure regulators shal l be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. 410.2 MP regulators. Medium pressure (MP) regulators shall comply with the following: 1. The MP regulator shall be approve d and shall be suitable for the inlet and outlet gas pressures for the application. 2. The MP regulator shall maintain a reduced outlet pressure under lockup (no - flow) conditions. 3. The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served. 4. The MP regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak - limiting device, in either case comply ing with Section 410.3. 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument and to serve as a sediment trap. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. A pressure gauge with an isolation valve may also be installed in addition to the fitting. 7. At least one union shall be installed within 1 foot (304.8 mm) of either side of the MP regulator. 410.3 Venting of regulators. Pressure regulators that require a vent shall be vented directly to the outdoors. The vent terminal shall be a minimum of 18 inches ( 457.2 mm) above grade, not under a building - opening or overhang, and shall be installed so as to prevent the entrance of water and insects. Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent - limiting device installed in accordanc e with ANSI Z21.18 and the manufacturer’s instructions. The vent - limiting device shall be installed in a location sufficiently ventilated to dissipate any gas discharged from the device. 410.3.1 Vent piping. Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pres- sure - regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes back pres sure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions . 410.4 Excess flow valves. Where automatic excess flow valves are installed, they shall be listed for the application and shall be sized and installed in accordance with the manufacturer’s instructions. 410.5 Flashback arrestor check valve. Where fuel gas is used with oxygen in any hot work operation, a listed pro- tective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an ap- proved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas suppl y is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appli- ance that increases pressure to the level required for such safe operation. SECTION FGC 411 APPLIANCE AND MANUFACTURED HOME CONNECTIO NS 411.1 Connecting appliances. Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: GAS PIPING INSTALLATIONS 1. Rigid metallic pipe and fittings. Space heaters and water heaters shall be connected using rigid piping an d fittings only. Use of semirigid (flexible) metallic tubing, fittings , appliance connectors or quick - disconnect devices is not permitted for this application. 2. Listed and labeled appliance connectors in compliance with ANSI Z21.24 /CGA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance. Connectors shall have an overall length not to exceed 6 feet (1828.8 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance. 3. Listed and labeled quick - disconnect devices used in conjunction with listed and labeled appliance connectors. 4. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance con nectors. 5. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 6. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect porta ble outdoor appli- ances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick - disconnect device or listed gas convenience outlet. 411. 1.1 Commercial cooking appliances. Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.6 9 /CSA 6.16 and NSF/ANSI 169 or in accordance with Item 1 of Section 411.1. The commercial cooking appliance connector installation shall be configured in accordance with the manu- facturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions. 411.1.2 Protection against damage. Connectors and tubing shall be installed so as to be protected against physical damage. 411.1.3 Connector installation. Fuel connectors shall be installed in accordance with the manufacturer’s instruc- tions and Sections 411.1.3.1 through 411.1.3.4. 411.1.3 .1 Maximum length. Connectors shall have an overall length not to exceed 6 feet ( 1828.8 mm). Meas- urement shall be made along the centerline of the connector. Only one connector shall be used for each appli- ance. 411.1.3.2 Minimum size. Connectors shall have the capacity for the total demand of the connected appliance. 411.1.3.3 Prohibited locations and penetrations. Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings. Exceptions: 1. Connect ors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2. 2. Rigid steel pipe connectors shall be per mitted to extend through openings in appliance housings. 3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in ac- cordance with the listing of the appliance. 4. Listed connectors shall be permitted to extend t hrough an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage. 411.1.3.4 Shutoff valve. A shutoff valve not less than the nominal size of the piping system shall be installed ahead of the connector i n accordance with Section 409.5. 411.1.4 Movable appliances. Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69 /CSA 6.16 or by means of Item 1 of Section 411.1 of this code . Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions . GAS PIPING INSTALLATIONS 411.1.5 Connection of gas engine - powered air conditioners. Internal combustion engines shall not be rigidly connected to the gas supply piping. 411.1.6 Unions. A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall be accessible and located within 6 feet ( 1828.8 mm) of the appliance. 411.2 Manufactured home connections. Manufactured homes shall be connected to the distribution piping system by one of the following materials: 1. Metallic pipe in accordance with Section 403.4. 2. Listed and labeled connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 411.3 Suspended low - intensity infrared tube heaters. Suspended lo w - intensity infrared tube heaters shall be con- nected to the building piping system with a connector listed for the application complying with ANSI Z21.24/CGA 6.10. The connector shall be installed as specified by the tube heater manufacturer’s instructions . SECTION FGC 412 LIQUEFIED PETROLEUM GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 412.1 Applicability. Motor fuel - dispensing facilities for LP - gas fuel shall be designed and operated in accordance with the New York City Fire Code . 412.2 Reserved. 412.3 Reserved. 412.4 Reserved. 412.5 Reserved. 412.6 Reserved. 412.7 Reserved. 412.8 Reserved. SECTION FGC 413 COMPRESSED NATURAL GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 413.1 Applicability. Motor fuel - dispensing facilities for CNG fuel shall be designed and operated in accordance with the New York City Fire Code . 413.2 Reserved. 413.3 Reserved. 413.4 Reserved. 413.5 Reserved. 413.6 Reserved. 413.7 Reserved. 413.8 Reserved. SECTION FGC 414 RE SERVED GAS PIPING INSTALLATIONS SECTION FGC 415 PIPING SUPPORT INTERVALS 415.1 Interval of support. Piping shall be supported at intervals not exceeding the spacing specified in Table 415.1. TABLE 415.1 SUPPORT OF PIPING STEEL PIPE, NOMINAL SIZE OF PIPE (inches) SPACING OF SUPPORTS (feet) 1 / 2 6 3 / 4 or 1 8 1 1 / 4 or larger (horizontal) 12 All vertical piping Every floor level For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. SECTION FGC 416 OVERPRESSURE PROTECTION DEVICES 416.1 Where required. Where the serving gas supplier delivers gas at a pressure greater than 2 psi (13.79 kPa) for piping systems serving appliances designed to operate at a gas pressure of 14 inches w.c. (3.49 kPa) or less, overpres- sure protection devices shall be installed. Piping systems serving appliances designed to operate at inlet pressures greater than 14 inches w.c. (3.49 kPa) shall be equipped with overpressure protection devices as required by the ap- pliance manufacturer’s instructions. 416.2 Pressure limitation requi rements. The requirements for pressure limitation shall be in accordance with Sec- tions 416.2.1 through 416.2.5. 416.2.1 Pressure under 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches w.c. (3.49 kPa) or less are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi or less upon a failure of the line pressure regulator. 416.2.2 Pressure over 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches w.c. (3.49 kPa) are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s instru ctions. 416.2.3 Device capability. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by Section 416.2.1, independently of any other pr essure control equipment in the piping system. 416.2.4 Failure detection. Each gas piping system for which an overpressure protection device is required by Section 416 shall be designed and installed so that a failure of the primary pressure control device (s) is detectable. 416.2.5 Relief valve. Where a pressure relief valve is used to meet the requirements of Section 416, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 416.2.1 under all of the following conditions: 1. The line pressure regulator for which the relief valve is providing overpressure protection has failed wide open. 2. The gas pressure at the inlet of the line pressure regulator for which the relief valve i s providing overpressure protection is not less than the regulator’s normal operating inlet pressure. GAS PIPING INSTALLATIONS 3. The use of pressure in excess of 15 psig ( 103.4 kPa gauge) shall be permitted for distribution piping provided all of the requirements of Section 406 and Appendix G are met. SECTION FGC 403 PIPING MATERIALS 403.1 General. Materials used for piping systems shall be new and comply with the requirements of this chapter or shall be approved. 403.1.1 Pipe size and pressure limitations. 1. All requirements for installation of gas distribution p iping shall be in accordance with Chapter 4. Gas distri- bution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS FIGURE 408.4 METHOD O F INSTALLING A TEE FITTING SEDIMENT TRAP SECTION FGC 409 SHUTOFF VALVES 409.1 General. Piping systems shall be provided with shutoff valves in accordance with this section. 409.1.1 Valve approval. Shutoff valves shall be of an approved type; shall be const ructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1. TABLE 409.1.1 MANUAL GAS VALVE STANDARDS VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1 / 2 psig PRESSURE OTHER VALVE APPLICATIONS UP TO 1 / 2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE ANSI Z21.15 / CGA 9.1 X — — — — ASME B16.44 X X X a X b — ASME B16.33 X X X X X For SI: 1 pound per square inch gauge = 6.895 kPa. a. If labeled 2G. b. If labeled 5G. GAS PIPING INSTALLATIONS 409.1.2 Prohibited locations. Shutoff valves shall be prohibited in concealed locations and furnace plenums. 409.1.3 Access to shutoff valves. Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage. 409.2 Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter. Meter valves shall be of a type approved b y the utility company. 409.3 Shutoff valves for multiple - house line systems. Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant. 409.3.1 Multiple tenant buildings. In multiple tenant buildings, where a common piping system is installed to supply other than individual dwelling units, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tena nt’s space. 409.3.2 Individual buildings. In a common system serving more than one building, shutoff valves shall be installed outdoors at each building. 409.3.3 Identification of shutoff valves. Each house line shutoff valve shall be plainly marked with a n iden- tification tag attached by the installer so that the piping systems supplied by such valves are readily identified. Identification shall be provided in compliance with ASME A13.1. 409.4 MP regulator valves. An approved shutoff valve shall be installe d immediately ahead of each MP regulator. 409.5 Appliance shutoff valve. Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1 or 409.5. 2 . 409.5.1 Located within the same room. The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet ( 1828.8 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access and located not more than 60 inches (1524 mm) above the finished floor . Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions. Where the shutoff valve is located in the firebox , a remote shutoff valve shall also be provided. Exception: Shutoff valves may be located more than 60 inches (1524 mm) above the finished floor where the gas connection to the appliance is more than 60 inches (1524 m m) above the finished floor. 409.5.2 Vented decorative appliances and room heaters. Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet ( 1828.8 mm) of the appliance shall be designe d, sized and installed in accordance with Sections 401 through 408. 409.6 Shutoff valve for laboratories. Where provided with two or more fuel gas outlets, including table - , bench - and hood - mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through whic h all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shuto ff.” 409.7 Outside gas cut - off. An outside gas service line valve or other outside shutoff device or method acceptable to the commissioner shall be provided in accordance with Section E.2 of Appendix E. 409.8 Riser shutoff valves. Risers shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. 409.9 Branch shutoff valves. Branches serving more than one appliance shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. SECTION FGC 410 FLOW CONTROLS GAS PIPING INSTALLATIONS 410.1 Pressure regulators. A line pressure regulator shall be i nstalled where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80 /CSA 6.22 . Access shall be provided to pressure regulators. Pressure regulators shal l be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. 410.2 MP regulators. Medium pressure (MP) regulators shall comply with the following: 1. The MP regulator shall be approve d and shall be suitable for the inlet and outlet gas pressures for the application. 2. The MP regulator shall maintain a reduced outlet pressure under lockup (no - flow) conditions. 3. The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served. 4. The MP regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak - limiting device, in either case comply ing with Section 410.3. 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument and to serve as a sediment trap. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. A pressure gauge with an isolation valve may also be installed in addition to the fitting. 7. At least one union shall be installed within 1 foot (304.8 mm) of either side of the MP regulator. 410.3 Venting of regulators. Pressure regulators that require a vent shall be vented directly to the outdoors. The vent terminal shall be a minimum of 18 inches ( 457.2 mm) above grade, not under a building - opening or overhang, and shall be installed so as to prevent the entrance of water and insects. Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent - limiting device installed in accordanc e with ANSI Z21.18 and the manufacturer’s instructions. The vent - limiting device shall be installed in a location sufficiently ventilated to dissipate any gas discharged from the device. 410.3.1 Vent piping. Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pres- sure - regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes back pres sure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions . 410.4 Excess flow valves. Where automatic excess flow valves are installed, they shall be listed for the application and shall be sized and installed in accordance with the manufacturer’s instructions. 410.5 Flashback arrestor check valve. Where fuel gas is used with oxygen in any hot work operation, a listed pro- tective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an ap- proved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas suppl y is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appli- ance that increases pressure to the level required for such safe operation. SECTION FGC 411 APPLIANCE AND MANUFACTURED HOME CONNECTIO NS 411.1 Connecting appliances. Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: GAS PIPING INSTALLATIONS 1. Rigid metallic pipe and fittings. Space heaters and water heaters shall be connected using rigid piping an d fittings only. Use of semirigid (flexible) metallic tubing, fittings , appliance connectors or quick - disconnect devices is not permitted for this application. 2. Listed and labeled appliance connectors in compliance with ANSI Z21.24 /CGA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance. Connectors shall have an overall length not to exceed 6 feet (1828.8 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance. 3. Listed and labeled quick - disconnect devices used in conjunction with listed and labeled appliance connectors. 4. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance con nectors. 5. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 6. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect porta ble outdoor appli- ances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick - disconnect device or listed gas convenience outlet. 411. 1.1 Commercial cooking appliances. Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.6 9 /CSA 6.16 and NSF/ANSI 169 or in accordance with Item 1 of Section 411.1. The commercial cooking appliance connector installation shall be configured in accordance with the manu- facturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions. 411.1.2 Protection against damage. Connectors and tubing shall be installed so as to be protected against physical damage. 411.1.3 Connector installation. Fuel connectors shall be installed in accordance with the manufacturer’s instruc- tions and Sections 411.1.3.1 through 411.1.3.4. 411.1.3 .1 Maximum length. Connectors shall have an overall length not to exceed 6 feet ( 1828.8 mm). Meas- urement shall be made along the centerline of the connector. Only one connector shall be used for each appli- ance. 411.1.3.2 Minimum size. Connectors shall have the capacity for the total demand of the connected appliance. 411.1.3.3 Prohibited locations and penetrations. Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings. Exceptions: 1. Connect ors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2. 2. Rigid steel pipe connectors shall be per mitted to extend through openings in appliance housings. 3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in ac- cordance with the listing of the appliance. 4. Listed connectors shall be permitted to extend t hrough an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage. 411.1.3.4 Shutoff valve. A shutoff valve not less than the nominal size of the piping system shall be installed ahead of the connector i n accordance with Section 409.5. 411.1.4 Movable appliances. Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69 /CSA 6.16 or by means of Item 1 of Section 411.1 of this code . Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions . GAS PIPING INSTALLATIONS 411.1.5 Connection of gas engine - powered air conditioners. Internal combustion engines shall not be rigidly connected to the gas supply piping. 411.1.6 Unions. A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall be accessible and located within 6 feet ( 1828.8 mm) of the appliance. 411.2 Manufactured home connections. Manufactured homes shall be connected to the distribution piping system by one of the following materials: 1. Metallic pipe in accordance with Section 403.4. 2. Listed and labeled connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 411.3 Suspended low - intensity infrared tube heaters. Suspended lo w - intensity infrared tube heaters shall be con- nected to the building piping system with a connector listed for the application complying with ANSI Z21.24/CGA 6.10. The connector shall be installed as specified by the tube heater manufacturer’s instructions . SECTION FGC 412 LIQUEFIED PETROLEUM GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 412.1 Applicability. Motor fuel - dispensing facilities for LP - gas fuel shall be designed and operated in accordance with the New York City Fire Code . 412.2 Reserved. 412.3 Reserved. 412.4 Reserved. 412.5 Reserved. 412.6 Reserved. 412.7 Reserved. 412.8 Reserved. SECTION FGC 413 COMPRESSED NATURAL GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 413.1 Applicability. Motor fuel - dispensing facilities for CNG fuel shall be designed and operated in accordance with the New York City Fire Code . 413.2 Reserved. 413.3 Reserved. 413.4 Reserved. 413.5 Reserved. 413.6 Reserved. 413.7 Reserved. 413.8 Reserved. SECTION FGC 414 RE SERVED GAS PIPING INSTALLATIONS SECTION FGC 415 PIPING SUPPORT INTERVALS 415.1 Interval of support. Piping shall be supported at intervals not exceeding the spacing specified in Table 415.1. TABLE 415.1 SUPPORT OF PIPING STEEL PIPE, NOMINAL SIZE OF PIPE (inches) SPACING OF SUPPORTS (feet) 1 / 2 6 3 / 4 or 1 8 1 1 / 4 or larger (horizontal) 12 All vertical piping Every floor level For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. SECTION FGC 416 OVERPRESSURE PROTECTION DEVICES 416.1 Where required. Where the serving gas supplier delivers gas at a pressure greater than 2 psi (13.79 kPa) for piping systems serving appliances designed to operate at a gas pressure of 14 inches w.c. (3.49 kPa) or less, overpres- sure protection devices shall be installed. Piping systems serving appliances designed to operate at inlet pressures greater than 14 inches w.c. (3.49 kPa) shall be equipped with overpressure protection devices as required by the ap- pliance manufacturer’s instructions. 416.2 Pressure limitation requi rements. The requirements for pressure limitation shall be in accordance with Sec- tions 416.2.1 through 416.2.5. 416.2.1 Pressure under 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches w.c. (3.49 kPa) or less are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi or less upon a failure of the line pressure regulator. 416.2.2 Pressure over 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches w.c. (3.49 kPa) are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s instru ctions. 416.2.3 Device capability. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by Section 416.2.1, independently of any other pr essure control equipment in the piping system. 416.2.4 Failure detection. Each gas piping system for which an overpressure protection device is required by Section 416 shall be designed and installed so that a failure of the primary pressure control device (s) is detectable. 416.2.5 Relief valve. Where a pressure relief valve is used to meet the requirements of Section 416, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 416.2.1 under all of the following conditions: 1. The line pressure regulator for which the relief valve is providing overpressure protection has failed wide open. 2. The gas pressure at the inlet of the line pressure regulator for which the relief valve i s providing overpressure protection is not less than the regulator’s normal operating inlet pressure. GAS PIPING INSTALLATIONS 416.3 Devices. Pressure - relieving or pressure - limiting devices shall be one of the following: 1. Pressure relief valve. 2. Monitoring regulator. 3. Series regulator installed upstream from the line regulator and set to continuously limit the pressure on the inlet of the line regulator to the maximum values specified by Section 416.2.1. 4. Automatic shutoff device installed in series with the line pressure r egulator and set to shut off when the pressure on the downstream piping system reaches the maximum values specified by Section 416.2.1. This device shall be designed so that it will remain closed until manually reset. The devices specified in this section shall be installed either as an integral part of the service or line pressure regulator or as separate units. Where separate pressure - relieving or pressure - limiting devices are installed, they shall comply with Sections 416.3.1 through 416.3.6 . 416.3.1 Con struction and installation. Pressure - relieving and pressure - limiting devices shall be constructed of materials so that the operation of the devices will not be impaired by corrosion of external parts by the atmosphere or of internal parts by the gas. Press ure - relieving and pressure - limiting devices shall be designed and installed so that they can be operated to determine whether the valve is free. The devices shall be designed and installed so that they can be tested to determine the pressure at which they will operate and examined for leakage when in the closed position. The devices shall be maintained and inspected in accordance with Section 416.3.7. 416.3.2 External control piping. External control piping shall be designed and installed so that damage to the control piping of one device will not render both the regulator and the overpressure protection device inoperative. 416.3.3 Setting. Each pressure - relieving or pressure - limiting device shall be set so that the gas pressure supplied to the connected appliances does not exceed the limits specified in Section 416.2.1 . 416.3.4 Unauthorized operation. Precautions shall be taken to prevent u nauthorized operation of any shutoff valve that will make a pressure - relieving valve or pressure - limiting device inoperative. The valve shall be locked or continuously monitored in the open position. 416.3.5 Vents. The discharge stacks, vents and outlet pa rts of all pressure - relieving and pressure - limiting devices shall be located so that gas is safely discharged to the outdoors. Discharge stacks and vents shall be designed to prevent the entry of water, insects and other foreign material that could cause b lockage. The discharge stack or vent line shall be not less than the same size as the outlet of the pressure - relieving device. 416.3.6 Size of fittings, pipe and openings. The fittings, pipe and openings located between the system to be protected and the p ressure - relieving device shall be sized to prevent hammering of the valve and to prevent impair- ment of relief capacity. 416.3.7 Device maintenance. The overpressure protection device: (i) shall be properly maintained and inspected every two years by a lice nsed master plumber; (ii) inspection records shall be maintained by the owner and made available to the department; (iii) inspection procedures shall be in accordance with the commissioner; and (iv) replacements or repairs shall be promptly made. Exception : Where the gas pressure is 15 psig (103.4 kPa gauge) or above, the overpressure protection device shall be inspected annually.more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS FIGURE 408.4 METHOD O F INSTALLING A TEE FITTING SEDIMENT TRAP SECTION FGC 409 SHUTOFF VALVES 409.1 General. Piping systems shall be provided with shutoff valves in accordance with this section. 409.1.1 Valve approval. Shutoff valves shall be of an approved type; shall be const ructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1. TABLE 409.1.1 MANUAL GAS VALVE STANDARDS VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1 / 2 psig PRESSURE OTHER VALVE APPLICATIONS UP TO 1 / 2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE ANSI Z21.15 / CGA 9.1 X — — — — ASME B16.44 X X X a X b — ASME B16.33 X X X X X For SI: 1 pound per square inch gauge = 6.895 kPa. a. If labeled 2G. b. If labeled 5G. GAS PIPING INSTALLATIONS 409.1.2 Prohibited locations. Shutoff valves shall be prohibited in concealed locations and furnace plenums. 409.1.3 Access to shutoff valves. Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage. 409.2 Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter. Meter valves shall be of a type approved b y the utility company. 409.3 Shutoff valves for multiple - house line systems. Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant. 409.3.1 Multiple tenant buildings. In multiple tenant buildings, where a common piping system is installed to supply other than individual dwelling units, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tena nt’s space. 409.3.2 Individual buildings. In a common system serving more than one building, shutoff valves shall be installed outdoors at each building. 409.3.3 Identification of shutoff valves. Each house line shutoff valve shall be plainly marked with a n iden- tification tag attached by the installer so that the piping systems supplied by such valves are readily identified. Identification shall be provided in compliance with ASME A13.1. 409.4 MP regulator valves. An approved shutoff valve shall be installe d immediately ahead of each MP regulator. 409.5 Appliance shutoff valve. Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1 or 409.5. 2 . 409.5.1 Located within the same room. The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet ( 1828.8 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access and located not more than 60 inches (1524 mm) above the finished floor . Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions. Where the shutoff valve is located in the firebox , a remote shutoff valve shall also be provided. Exception: Shutoff valves may be located more than 60 inches (1524 mm) above the finished floor where the gas connection to the appliance is more than 60 inches (1524 m m) above the finished floor. 409.5.2 Vented decorative appliances and room heaters. Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet ( 1828.8 mm) of the appliance shall be designe d, sized and installed in accordance with Sections 401 through 408. 409.6 Shutoff valve for laboratories. Where provided with two or more fuel gas outlets, including table - , bench - and hood - mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through whic h all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shuto ff.” 409.7 Outside gas cut - off. An outside gas service line valve or other outside shutoff device or method acceptable to the commissioner shall be provided in accordance with Section E.2 of Appendix E. 409.8 Riser shutoff valves. Risers shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. 409.9 Branch shutoff valves. Branches serving more than one appliance shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. SECTION FGC 410 FLOW CONTROLS GAS PIPING INSTALLATIONS 410.1 Pressure regulators. A line pressure regulator shall be i nstalled where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80 /CSA 6.22 . Access shall be provided to pressure regulators. Pressure regulators shal l be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. 410.2 MP regulators. Medium pressure (MP) regulators shall comply with the following: 1. The MP regulator shall be approve d and shall be suitable for the inlet and outlet gas pressures for the application. 2. The MP regulator shall maintain a reduced outlet pressure under lockup (no - flow) conditions. 3. The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served. 4. The MP regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak - limiting device, in either case comply ing with Section 410.3. 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument and to serve as a sediment trap. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. A pressure gauge with an isolation valve may also be installed in addition to the fitting. 7. At least one union shall be installed within 1 foot (304.8 mm) of either side of the MP regulator. 410.3 Venting of regulators. Pressure regulators that require a vent shall be vented directly to the outdoors. The vent terminal shall be a minimum of 18 inches ( 457.2 mm) above grade, not under a building - opening or overhang, and shall be installed so as to prevent the entrance of water and insects. Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent - limiting device installed in accordanc e with ANSI Z21.18 and the manufacturer’s instructions. The vent - limiting device shall be installed in a location sufficiently ventilated to dissipate any gas discharged from the device. 410.3.1 Vent piping. Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pres- sure - regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes back pres sure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions . 410.4 Excess flow valves. Where automatic excess flow valves are installed, they shall be listed for the application and shall be sized and installed in accordance with the manufacturer’s instructions. 410.5 Flashback arrestor check valve. Where fuel gas is used with oxygen in any hot work operation, a listed pro- tective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an ap- proved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas suppl y is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appli- ance that increases pressure to the level required for such safe operation. SECTION FGC 411 APPLIANCE AND MANUFACTURED HOME CONNECTIO NS 411.1 Connecting appliances. Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: GAS PIPING INSTALLATIONS 1. Rigid metallic pipe and fittings. Space heaters and water heaters shall be connected using rigid piping an d fittings only. Use of semirigid (flexible) metallic tubing, fittings , appliance connectors or quick - disconnect devices is not permitted for this application. 2. Listed and labeled appliance connectors in compliance with ANSI Z21.24 /CGA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance. Connectors shall have an overall length not to exceed 6 feet (1828.8 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance. 3. Listed and labeled quick - disconnect devices used in conjunction with listed and labeled appliance connectors. 4. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance con nectors. 5. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 6. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect porta ble outdoor appli- ances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick - disconnect device or listed gas convenience outlet. 411. 1.1 Commercial cooking appliances. Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.6 9 /CSA 6.16 and NSF/ANSI 169 or in accordance with Item 1 of Section 411.1. The commercial cooking appliance connector installation shall be configured in accordance with the manu- facturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions. 411.1.2 Protection against damage. Connectors and tubing shall be installed so as to be protected against physical damage. 411.1.3 Connector installation. Fuel connectors shall be installed in accordance with the manufacturer’s instruc- tions and Sections 411.1.3.1 through 411.1.3.4. 411.1.3 .1 Maximum length. Connectors shall have an overall length not to exceed 6 feet ( 1828.8 mm). Meas- urement shall be made along the centerline of the connector. Only one connector shall be used for each appli- ance. 411.1.3.2 Minimum size. Connectors shall have the capacity for the total demand of the connected appliance. 411.1.3.3 Prohibited locations and penetrations. Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings. Exceptions: 1. Connect ors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2. 2. Rigid steel pipe connectors shall be per mitted to extend through openings in appliance housings. 3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in ac- cordance with the listing of the appliance. 4. Listed connectors shall be permitted to extend t hrough an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage. 411.1.3.4 Shutoff valve. A shutoff valve not less than the nominal size of the piping system shall be installed ahead of the connector i n accordance with Section 409.5. 411.1.4 Movable appliances. Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69 /CSA 6.16 or by means of Item 1 of Section 411.1 of this code . Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions . GAS PIPING INSTALLATIONS 411.1.5 Connection of gas engine - powered air conditioners. Internal combustion engines shall not be rigidly connected to the gas supply piping. 411.1.6 Unions. A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall be accessible and located within 6 feet ( 1828.8 mm) of the appliance. 411.2 Manufactured home connections. Manufactured homes shall be connected to the distribution piping system by one of the following materials: 1. Metallic pipe in accordance with Section 403.4. 2. Listed and labeled connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 411.3 Suspended low - intensity infrared tube heaters. Suspended lo w - intensity infrared tube heaters shall be con- nected to the building piping system with a connector listed for the application complying with ANSI Z21.24/CGA 6.10. The connector shall be installed as specified by the tube heater manufacturer’s instructions . SECTION FGC 412 LIQUEFIED PETROLEUM GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 412.1 Applicability. Motor fuel - dispensing facilities for LP - gas fuel shall be designed and operated in accordance with the New York City Fire Code . 412.2 Reserved. 412.3 Reserved. 412.4 Reserved. 412.5 Reserved. 412.6 Reserved. 412.7 Reserved. 412.8 Reserved. SECTION FGC 413 COMPRESSED NATURAL GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 413.1 Applicability. Motor fuel - dispensing facilities for CNG fuel shall be designed and operated in accordance with the New York City Fire Code . 413.2 Reserved. 413.3 Reserved. 413.4 Reserved. 413.5 Reserved. 413.6 Reserved. 413.7 Reserved. 413.8 Reserved. SECTION FGC 414 RE SERVED GAS PIPING INSTALLATIONS SECTION FGC 415 PIPING SUPPORT INTERVALS 415.1 Interval of support. Piping shall be supported at intervals not exceeding the spacing specified in Table 415.1. TABLE 415.1 SUPPORT OF PIPING STEEL PIPE, NOMINAL SIZE OF PIPE (inches) SPACING OF SUPPORTS (feet) 1 / 2 6 3 / 4 or 1 8 1 1 / 4 or larger (horizontal) 12 All vertical piping Every floor level For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. SECTION FGC 416 OVERPRESSURE PROTECTION DEVICES 416.1 Where required. Where the serving gas supplier delivers gas at a pressure greater than 2 psi (13.79 kPa) for piping systems serving appliances designed to operate at a gas pressure of 14 inches w.c. (3.49 kPa) or less, overpres- sure protection devices shall be installed. Piping systems serving appliances designed to operate at inlet pressures greater than 14 inches w.c. (3.49 kPa) shall be equipped with overpressure protection devices as required by the ap- pliance manufacturer’s instructions. 416.2 Pressure limitation requi rements. The requirements for pressure limitation shall be in accordance with Sec- tions 416.2.1 through 416.2.5. 416.2.1 Pressure under 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches w.c. (3.49 kPa) or less are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi or less upon a failure of the line pressure regulator. 416.2.2 Pressure over 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches w.c. (3.49 kPa) are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s instru ctions. 416.2.3 Device capability. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by Section 416.2.1, independently of any other pr essure control equipment in the piping system. 416.2.4 Failure detection. Each gas piping system for which an overpressure protection device is required by Section 416 shall be designed and installed so that a failure of the primary pressure control device (s) is detectable. 416.2.5 Relief valve. Where a pressure relief valve is used to meet the requirements of Section 416, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 416.2.1 under all of the following conditions: 1. The line pressure regulator for which the relief valve is providing overpressure protection has failed wide open. 2. The gas pressure at the inlet of the line pressure regulator for which the relief valve i s providing overpressure protection is not less than the regulator’s normal operating inlet pressure. GAS PIPING INSTALLATIONS 416.3 Devices. Pressure - relieving or pressure - limiting devices shall be one of the following: 1. Pressure relief valve. 2. Monitoring regulator. 3. Series regulator installed upstream from the line regulator and set to continuously limit the pressure on the inlet of the line regulator to the maximum values specified by Section 416.2.1. 4. Automatic shutoff device installed in series with the line pressure r egulator and set to shut off when the pressure on the downstream piping system reaches the maximum values specified by Section 416.2.1. This device shall be designed so that it will remain closed until manually reset. The devices specified in this section shall be installed either as an integral part of the service or line pressure regulator or as separate units. Where separate pressure - relieving or pressure - limiting devices are installed, they shall comply with Sections 416.3.1 through 416.3.6 . 416.3.1 Con struction and installation. Pressure - relieving and pressure - limiting devices shall be constructed of materials so that the operation of the devices will not be impaired by corrosion of external parts by the atmosphere or of internal parts by the gas. Press ure - relieving and pressure - limiting devices shall be designed and installed so that they can be operated to determine whether the valve is free. The devices shall be designed and installed so that they can be tested to determine the pressure at which they will operate and examined for leakage when in the closed position. The devices shall be maintained and inspected in accordance with Section 416.3.7. 416.3.2 External control piping. External control piping shall be designed and installed so that damage to the control piping of one device will not render both the regulator and the overpressure protection device inoperative. 416.3.3 Setting. Each pressure - relieving or pressure - limiting device shall be set so that the gas pressure supplied to the connected appliances does not exceed the limits specified in Section 416.2.1 . 416.3.4 Unauthorized operation. Precautions shall be taken to prevent u nauthorized operation of any shutoff valve that will make a pressure - relieving valve or pressure - limiting device inoperative. The valve shall be locked or continuously monitored in the open position. 416.3.5 Vents. The discharge stacks, vents and outlet pa rts of all pressure - relieving and pressure - limiting devices shall be located so that gas is safely discharged to the outdoors. Discharge stacks and vents shall be designed to prevent the entry of water, insects and other foreign material that could cause b lockage. The discharge stack or vent line shall be not less than the same size as the outlet of the pressure - relieving device. 416.3.6 Size of fittings, pipe and openings. The fittings, pipe and openings located between the system to be protected and the p ressure - relieving device shall be sized to prevent hammering of the valve and to prevent impair- ment of relief capacity. 416.3.7 Device maintenance. The overpressure protection device: (i) shall be properly maintained and inspected every two years by a lice nsed master plumber; (ii) inspection records shall be maintained by the owner and made available to the department; (iii) inspection procedures shall be in accordance with the commissioner; and (iv) replacements or repairs shall be promptly made. Exception : Where the gas pressure is 15 psig (103.4 kPa gauge) or above, the overpressure protection device shall be inspected annually.more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS FIGURE 408.4 METHOD O F INSTALLING A TEE FITTING SEDIMENT TRAP SECTION FGC 409 SHUTOFF VALVES 409.1 General. Piping systems shall be provided with shutoff valves in accordance with this section. 409.1.1 Valve approval. Shutoff valves shall be of an approved type; shall be const ructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1. TABLE 409.1.1 MANUAL GAS VALVE STANDARDS VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1 / 2 psig PRESSURE OTHER VALVE APPLICATIONS UP TO 1 / 2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE ANSI Z21.15 / CGA 9.1 X — — — — ASME B16.44 X X X a X b — ASME B16.33 X X X X X For SI: 1 pound per square inch gauge = 6.895 kPa. a. If labeled 2G. b. If labeled 5G. GAS PIPING INSTALLATIONS 409.1.2 Prohibited locations. Shutoff valves shall be prohibited in concealed locations and furnace plenums. 409.1.3 Access to shutoff valves. Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage. 409.2 Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter. Meter valves shall be of a type approved b y the utility company. 409.3 Shutoff valves for multiple - house line systems. Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant. 409.3.1 Multiple tenant buildings. In multiple tenant buildings, where a common piping system is installed to supply other than individual dwelling units, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tena nt’s space. 409.3.2 Individual buildings. In a common system serving more than one building, shutoff valves shall be installed outdoors at each building. 409.3.3 Identification of shutoff valves. Each house line shutoff valve shall be plainly marked with a n iden- tification tag attached by the installer so that the piping systems supplied by such valves are readily identified. Identification shall be provided in compliance with ASME A13.1. 409.4 MP regulator valves. An approved shutoff valve shall be installe d immediately ahead of each MP regulator. 409.5 Appliance shutoff valve. Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1 or 409.5. 2 . 409.5.1 Located within the same room. The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet ( 1828.8 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access and located not more than 60 inches (1524 mm) above the finished floor . Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions. Where the shutoff valve is located in the firebox , a remote shutoff valve shall also be provided. Exception: Shutoff valves may be located more than 60 inches (1524 mm) above the finished floor where the gas connection to the appliance is more than 60 inches (1524 m m) above the finished floor. 409.5.2 Vented decorative appliances and room heaters. Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet ( 1828.8 mm) of the appliance shall be designe d, sized and installed in accordance with Sections 401 through 408. 409.6 Shutoff valve for laboratories. Where provided with two or more fuel gas outlets, including table - , bench - and hood - mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through whic h all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shuto ff.” 409.7 Outside gas cut - off. An outside gas service line valve or other outside shutoff device or method acceptable to the commissioner shall be provided in accordance with Section E.2 of Appendix E. 409.8 Riser shutoff valves. Risers shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. 409.9 Branch shutoff valves. Branches serving more than one appliance shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. SECTION FGC 410 FLOW CONTROLS GAS PIPING INSTALLATIONS 410.1 Pressure regulators. A line pressure regulator shall be i nstalled where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80 /CSA 6.22 . Access shall be provided to pressure regulators. Pressure regulators shal l be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. 410.2 MP regulators. Medium pressure (MP) regulators shall comply with the following: 1. The MP regulator shall be approve d and shall be suitable for the inlet and outlet gas pressures for the application. 2. The MP regulator shall maintain a reduced outlet pressure under lockup (no - flow) conditions. 3. The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served. 4. The MP regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak - limiting device, in either case comply ing with Section 410.3. 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument and to serve as a sediment trap. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. A pressure gauge with an isolation valve may also be installed in addition to the fitting. 7. At least one union shall be installed within 1 foot (304.8 mm) of either side of the MP regulator. 410.3 Venting of regulators. Pressure regulators that require a vent shall be vented directly to the outdoors. The vent terminal shall be a minimum of 18 inches ( 457.2 mm) above grade, not under a building - opening or overhang, and shall be installed so as to prevent the entrance of water and insects. Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent - limiting device installed in accordanc e with ANSI Z21.18 and the manufacturer’s instructions. The vent - limiting device shall be installed in a location sufficiently ventilated to dissipate any gas discharged from the device. 410.3.1 Vent piping. Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pres- sure - regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes back pres sure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions . 410.4 Excess flow valves. Where automatic excess flow valves are installed, they shall be listed for the application and shall be sized and installed in accordance with the manufacturer’s instructions. 410.5 Flashback arrestor check valve. Where fuel gas is used with oxygen in any hot work operation, a listed pro- tective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an ap- proved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas suppl y is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appli- ance that increases pressure to the level required for such safe operation. SECTION FGC 411 APPLIANCE AND MANUFACTURED HOME CONNECTIO NS 411.1 Connecting appliances. Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: GAS PIPING INSTALLATIONS 1. Rigid metallic pipe and fittings. Space heaters and water heaters shall be connected using rigid piping an d fittings only. Use of semirigid (flexible) metallic tubing, fittings , appliance connectors or quick - disconnect devices is not permitted for this application. 2. Listed and labeled appliance connectors in compliance with ANSI Z21.24 /CGA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance. Connectors shall have an overall length not to exceed 6 feet (1828.8 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance. 3. Listed and labeled quick - disconnect devices used in conjunction with listed and labeled appliance connectors. 4. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance con nectors. 5. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 6. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect porta ble outdoor appli- ances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick - disconnect device or listed gas convenience outlet. 411. 1.1 Commercial cooking appliances. Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.6 9 /CSA 6.16 and NSF/ANSI 169 or in accordance with Item 1 of Section 411.1. The commercial cooking appliance connector installation shall be configured in accordance with the manu- facturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions. 411.1.2 Protection against damage. Connectors and tubing shall be installed so as to be protected against physical damage. 411.1.3 Connector installation. Fuel connectors shall be installed in accordance with the manufacturer’s instruc- tions and Sections 411.1.3.1 through 411.1.3.4. 411.1.3 .1 Maximum length. Connectors shall have an overall length not to exceed 6 feet ( 1828.8 mm). Meas- urement shall be made along the centerline of the connector. Only one connector shall be used for each appli- ance. 411.1.3.2 Minimum size. Connectors shall have the capacity for the total demand of the connected appliance. 411.1.3.3 Prohibited locations and penetrations. Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings. Exceptions: 1. Connect ors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2. 2. Rigid steel pipe connectors shall be per mitted to extend through openings in appliance housings. 3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in ac- cordance with the listing of the appliance. 4. Listed connectors shall be permitted to extend t hrough an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage. 411.1.3.4 Shutoff valve. A shutoff valve not less than the nominal size of the piping system shall be installed ahead of the connector i n accordance with Section 409.5. 411.1.4 Movable appliances. Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69 /CSA 6.16 or by means of Item 1 of Section 411.1 of this code . Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions . GAS PIPING INSTALLATIONS 411.1.5 Connection of gas engine - powered air conditioners. Internal combustion engines shall not be rigidly connected to the gas supply piping. 411.1.6 Unions. A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall be accessible and located within 6 feet ( 1828.8 mm) of the appliance. 411.2 Manufactured home connections. Manufactured homes shall be connected to the distribution piping system by one of the following materials: 1. Metallic pipe in accordance with Section 403.4. 2. Listed and labeled connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 411.3 Suspended low - intensity infrared tube heaters. Suspended lo w - intensity infrared tube heaters shall be con- nected to the building piping system with a connector listed for the application complying with ANSI Z21.24/CGA 6.10. The connector shall be installed as specified by the tube heater manufacturer’s instructions . SECTION FGC 412 LIQUEFIED PETROLEUM GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 412.1 Applicability. Motor fuel - dispensing facilities for LP - gas fuel shall be designed and operated in accordance with the New York City Fire Code . 412.2 Reserved. 412.3 Reserved. 412.4 Reserved. 412.5 Reserved. 412.6 Reserved. 412.7 Reserved. 412.8 Reserved. SECTION FGC 413 COMPRESSED NATURAL GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 413.1 Applicability. Motor fuel - dispensing facilities for CNG fuel shall be designed and operated in accordance with the New York City Fire Code . 413.2 Reserved. 413.3 Reserved. 413.4 Reserved. 413.5 Reserved. 413.6 Reserved. 413.7 Reserved. 413.8 Reserved. SECTION FGC 414 RE SERVED GAS PIPING INSTALLATIONS SECTION FGC 415 PIPING SUPPORT INTERVALS 415.1 Interval of support. Piping shall be supported at intervals not exceeding the spacing specified in Table 415.1. TABLE 415.1 SUPPORT OF PIPING STEEL PIPE, NOMINAL SIZE OF PIPE (inches) SPACING OF SUPPORTS (feet) 1 / 2 6 3 / 4 or 1 8 1 1 / 4 or larger (horizontal) 12 All vertical piping Every floor level For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. SECTION FGC 416 OVERPRESSURE PROTECTION DEVICES 416.1 Where required. Where the serving gas supplier delivers gas at a pressure greater than 2 psi (13.79 kPa) for piping systems serving appliances designed to operate at a gas pressure of 14 inches w.c. (3.49 kPa) or less, overpres- sure protection devices shall be installed. Piping systems serving appliances designed to operate at inlet pressures greater than 14 inches w.c. (3.49 kPa) shall be equipped with overpressure protection devices as required by the ap- pliance manufacturer’s instructions. 416.2 Pressure limitation requi rements. The requirements for pressure limitation shall be in accordance with Sec- tions 416.2.1 through 416.2.5. 416.2.1 Pressure under 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches w.c. (3.49 kPa) or less are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi or less upon a failure of the line pressure regulator. 416.2.2 Pressure over 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches w.c. (3.49 kPa) are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s instru ctions. 416.2.3 Device capability. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by Section 416.2.1, independently of any other pr essure control equipment in the piping system. 416.2.4 Failure detection. Each gas piping system for which an overpressure protection device is required by Section 416 shall be designed and installed so that a failure of the primary pressure control device (s) is detectable. 416.2.5 Relief valve. Where a pressure relief valve is used to meet the requirements of Section 416, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 416.2.1 under all of the following conditions: 1. The line pressure regulator for which the relief valve is providing overpressure protection has failed wide open. 2. The gas pressure at the inlet of the line pressure regulator for which the relief valve i s providing overpressure protection is not less than the regulator’s normal operating inlet pressure. GAS PIPING INSTALLATIONS 416.3 Devices. Pressure - relieving or pressure - limiting devices shall be one of the following: 1. Pressure relief valve. 2. Monitoring regulator. 3. Series regulator installed upstream from the line regulator and set to continuously limit the pressure on the inlet of the line regulator to the maximum values specified by Section 416.2.1. 4. Automatic shutoff device installed in series with the line pressure r egulator and set to shut off when the pressure on the downstream piping system reaches the maximum values specified by Section 416.2.1. This device shall be designed so that it will remain closed until manually reset. The devices specified in this section shall be installed either as an integral part of the service or line pressure regulator or as separate units. Where separate pressure - relieving or pressure - limiting devices are installed, they shall comply with Sections 416.3.1 through 416.3.6 . 416.3.1 Con struction and installation. Pressure - relieving and pressure - limiting devices shall be constructed of materials so that the operation of the devices will not be impaired by corrosion of external parts by the atmosphere or of internal parts by the gas. Press ure - relieving and pressure - limiting devices shall be designed and installed so that they can be operated to determine whether the valve is free. The devices shall be designed and installed so that they can be tested to determine the pressure at which they will operate and examined for leakage when in the closed position. The devices shall be maintained and inspected in accordance with Section 416.3.7. 416.3.2 External control piping. External control piping shall be designed and installed so that damage to the control piping of one device will not render both the regulator and the overpressure protection device inoperative. 416.3.3 Setting. Each pressure - relieving or pressure - limiting device shall be set so that the gas pressure supplied to the connected appliances does not exceed the limits specified in Section 416.2.1 . 416.3.4 Unauthorized operation. Precautions shall be taken to prevent u nauthorized operation of any shutoff valve that will make a pressure - relieving valve or pressure - limiting device inoperative. The valve shall be locked or continuously monitored in the open position. 416.3.5 Vents. The discharge stacks, vents and outlet pa rts of all pressure - relieving and pressure - limiting devices shall be located so that gas is safely discharged to the outdoors. Discharge stacks and vents shall be designed to prevent the entry of water, insects and other foreign material that could cause b lockage. The discharge stack or vent line shall be not less than the same size as the outlet of the pressure - relieving device. 416.3.6 Size of fittings, pipe and openings. The fittings, pipe and openings located between the system to be protected and the p ressure - relieving device shall be sized to prevent hammering of the valve and to prevent impair- ment of relief capacity. 416.3.7 Device maintenance. The overpressure protection device: (i) shall be properly maintained and inspected every two years by a lice nsed master plumber; (ii) inspection records shall be maintained by the owner and made available to the department; (iii) inspection procedures shall be in accordance with the commissioner; and (iv) replacements or repairs shall be promptly made. Exception : Where the gas pressure is 15 psig (103.4 kPa gauge) or above, the overpressure protection device shall be inspected annually.more shall be in accordance with Appendix G. 2. Gas distribution piping operating at a pressure of over 1 / 2 psig (3.5 kPa gauge) s hall be welded. Exception: Manufactured and listed gas trains provided with the appliance may be threaded. 3. All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406. 4. Threaded piping may b e used up to 4 inches ( 101.6 mm) in diameter at pressure no greater than 1 / 2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure. 5. All welded piping 2 1 / 2 inches (63.5 mm) or greater in diameter shall be butt - welded, and welded piping less than 2 1 / 2 inches (63.5 mm) in diameter may be socket - welded or butt - welded. 403.2 Used materials. Used pipe , fittings, valves and other materials shall not be reused . 403 .3 Other materials. Material not covered by the standards specifications listed herein shall be investigated and tested to determine that it is safe and suitable for the proposed service, and, in addition, shall be recommended for that service by the manuf acturer subject to approval by the commissioner . 403.4 Metallic pipe. Metallic pipe shall comply with Sections 403.4.1 through 403.4.4. 403.4.1 Cast iron. Cast - iron pipe shall not be used. 403.4.2 Steel. Carbon steel and wrought - iron pipe shall be not less than standard weight and shall comply with one of the following standards: 1. ASME B36.10M. 2. ASTM A 53/ A 53M . 3. ASTM A106/A106M . 403.4.3 Copper and brass. Copper and brass pipe shall not be used. 403.4.4 Aluminum. Aluminum - alloy pipe shall not be used. 403.5 Metallic tubing. Metallic tubing shall not be used except as provided in Section 404.2 . 403.5.1 Standards. Stainless steel flexible multiple leg hose assemblies shall be listed and labeled in accordance with UL 536 and designed in accordance with the manufacturer’s recommendation . 403.5.2 Seismic requirements. Stainless steel flexible multiple leg hose assemblies shall be designed to withstand seismic force and displacement in accordance with Section 1613 of the New York City Building Code . 403.5.3 Special inspection required. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspection in accordance with Section 1705.12.3 of the New York City Building Code and Section 406 of this code. 403.6 Reserved. GAS PIPING INSTALLATIONS 403.7 Workmanship and defects. Pipe and fittings shall be clear and free from cutting burrs and defects in structure or threading, and shall be thoroughly brushed, and chip and scale blown. Defects in pipe and fittings shall not be repaired. Defective pipe and fittings shall be replaced (see Section 406.1.2). 403.8 Protective coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion - r esistant material shall be used. External coatings or linings used on piping or components shall not be considered as adding strength. 403.9 Metallic pipe threads. Metallic pipe and fitting threads shall be taper pipe threads and shall comply with ASME B1. 20.1. 403.9.1 Damaged threads. Pipe with threads that are stripped, chipped, corroded or otherwise damaged shall not be used. Where a weld opens during the operation of cutting or threading, that portion of the pipe shall not be used. 403.9.2 Number of threads. Field threading of metal lic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON PIPE SIZE (inches) APPROXIMATE LENGTH OF THREADED PORTION (inches) APPROXIMATE NUMBER OF THREADS TO BE CUT 1 / 2 3 / 4 10 3 / 4 3 / 4 10 1 7 / 8 10 1 1 / 4 1 11 1 1 / 2 1 11 2 1 11 2 1 / 2 1 1 / 2 12 3 1 1 / 2 12 4 1 5 / 8 13 For SI: 1 inch = 25.4 mm 403.9.3 Thread joint compounds. Thread joint compounds shall be in non - hardening paste or tape form and shall be resistant to the action of liquefied petroleum gas or to any other chemical constituents of the gases to be con- ducted through the piping. Use of cotton thread (lamp wick) is prohibited. Threaded joint compound in tape form is prohibited for use at pressure regulator connections. 403.10 Metallic piping joints and fittings. The type of piping joint used shall be suitable for the pressure - temperature conditions and shall be selected giving consideration to joint tightness and mechanical strength under the service conditions. The joint shall be able to sustain the maximum end force caused by the internal pressure and any additional forces caused by temperature expansion or contraction, vibration, fatigue or the weight of the pipe and its contents. 403.10.1 Pipe joints. Pipe joints shall be threaded, flanged, or welded. 403.10.1.1 Prohibited joints and fittings. Unions and threaded close nipples shall be prohibited. Exception: Unions shall be permitted to be installed downstream of the appliance val ve in accordance with Section 411.1.6. 403.10.2 Tubing joints. Tubing joints shall not be used . 403.10.3 Flared joints. Flared joints shall not be used . 403.10.4 Metallic fittings. Metallic fittings shall comply with the following: 1. Threaded fittings in sizes larger than 4 inches ( 101.6 mm) shall not be used. 2. Fittings used with steel or wrought - iron pipe shall be steel or malleable iron. GAS PIPING INSTALLATIONS 3. Bushings shall not be used. 403.11 Reserved. 403.12 Flanges. Flanges and flange gaskets shall comply with Sections 403.12.1 through 403.12.7 . 403.12.1 Cast - iron. Cast - iron flanges shall not be used . 403.12.2 Steel. Steel flanges shall be in accordance with ASME B16 .5 or ASME B16 .47. 403.12.3 Nonferrous. Nonferrous flanges shall not be used . 403.12.4 Ductile iron. Ductile - iron flanges shall be in accordance with ASME B16 .42. 403.12.5 Raised face. Raised face flanges shall not be joined to flat faced cast - iron, ductile - iron or nonferrous material flanges. 403.12.6 Flange facings. Standard facin gs shall be permitted for use under this code. Where 150 pound (1034 kPa) pressure - rated steel flanges are bolted to Class 125 cast - iron flanges, the raised face on the steel flange shall be removed. 403.12.7 Lapped flanges. Lapped flanges shall be used on ly above ground or in exposed locations accessible for inspection. 403.13 Flange gaskets. Material for gaskets shall be capable of withstanding the design temperature and pressure of the piping system, and the chemical constituents of the gas being conducted, without change to its chemical and physical properties. The effects of fire exposure to the joint shall be considered in choosing material. Acceptable materials include metal (plain or corrugated), non - asbestos fiber , and spiral wound metal gaskets. Where a flanged joint is opened, the gasket shall be replaced. Full - face flange gaskets sha ll be used with all non - steel flanges. Rubber - faced phenolic and elastomeric gaskets shall be prohibited. 403.13.1 Metallic gaskets. Metallic flange gaskets shall be in accordance with ASME B16 .20. 403.13.2 Nonmetallic gaskets. Nonmetallic flange gaskets s hall be in accordance with ASME B16 .21. 403.14 Flange bolts. Flange bolts and associated hardware shall be manufactured from corrosion - resistant materials. SECTION FGC 404 PIPING SYSTEM INSTALLATION 404.1 Installation of materials. Materials used shall be installed in strict accordance with the standards under which the materials are accepted and approved. In the absence of such installation procedures, the manufacturer’s instructions shall be followed. Where the requirements of referenced standards or manu facturer’s instructions do not conform to minimum provisions of this code, the provisions of this code shall apply. 404.2 Pipe movement. Flammable or combustible gas piping systems shall be designed to account for pipe movement resulting from thermal chang es or seismic forces. 404.2.1 Seismic requirements. Gas piping shall be designed and installed to withstand seismic forces in accord- ance with Section 1613 of the New York City Building Code . 404.2.1.1 Stainless steel flexible multiple leg hose assemblies. Stainless steel flexible multiple leg hose as- semblies may be installed where pipe movement resulting from seismic forces may occur. Such assemblies shall be listed and labeled in accordance with UL 536 and shall be installed in accordance with the manufacturer’s instructions. 404.2.1.2 Inspection. The installation of stainless steel flexible multiple leg hose assemblies shall be subject to special inspections in accordance with Chapter 17 of the New York City Building Code . 404.3 Prohibited loca tions. Piping shall not be installed in or through a ducted supply, return or exhaust duct , or a trash or clothes chute, chimney or gas vent , ventilating duct , dumbwaiter or elevator shaft. Piping installed downstream of the point of delivery shall not ext end through any townhouse unit other than the unit served by such piping. Piping, GAS PIPING INSTALLATIONS fixtures, or equipment shall be located so as not to interfere with the normal operation of windows or doors and other exit openings. The following installation limitations s hall apply: 1. Stair enclosures. Gas piping shall not be installed within a stair enclosure or required exit or exit way. 2. Fire standpipe riser. Gas piping shall not be installed in any shaft containing standpipe risers. 3. Fire pump and fire pump rooms. Gas piping, gas consumption devices , appliances or any other gas equipment shall not be installed within any space housing a fire pump. Access to gas meter rooms shall not be permitted through rooms housing a fire pump. 4. Fire - rated construction. Gas piping shall not be installed within a wall or assembly required to have a fire - resistance rating. Through penetrations of fire - resistance - rated assemblies shall be in accordance with Chapter 7 of the New York City Building Code . 5. Publi c corridor. Gas piping shall not be installed in public corridors and exit enclosures. Exceptions: 1. Gas piping may be installed in public corridors or exit enclosures where separated by a fire - resistance - rated assembly meeting the hour rating and, if app licable, the impact - resistance rating required for the corridor or exit enclosure. Such assembly shall be rated for exposure to fire from both sides. 2. In residential buildings that do not have floors below grade, or in multi - use buildings that have a res i- dential occupancy, gas piping may be installed in public corridors in accordance with the following: 2.1. Gas piping shall be permitted to be installed within a public corridor at the lowest level of the building or the lowest residential level of the bui lding. 2.2. All gas valves located within the public corridor shall be accessible for maintenance and inspec- tion. 2.3. Gas pressure within the public corridor piping shall not exceed 1 / 2 psi (14 inch w.c.). 2.4. The public corridor shall be ventilated in accordance with the New York City Mechanical Code . The pipe shall not be installed in a return air plenum. 2.5. Pipes must be welded. 404.4 Piping in solid partitions and walls. Concealed piping shall not be locat ed in solid partitions and solid walls, unless installed in a ventilated chase or casing. 404.5 Fittings in concealed locations. Fittings installed in concealed locations shall be limited to the following types: 1. Threaded elbows, tees and couplings. 2. Welded fittings. 404.6 Piping through foundation wall. Underground piping , where installed below grade through the outer founda- tion or basement wall of a building, shall be encased in a protective pipe sleeve. Such sleeve shall extend a minim um of 1 inch (25.4 mm) beyond the inside of the foundation wall and a minimum of 4 inches (101.6 mm) beyond the outside of the foundation wall, or as otherwise required by the gas provider. The annular space between the gas piping and the sleeve shall be waterproofed and sealed. 404.7 Branch take - off. Branches shall be taken off the riser with not less than a two - elbow swing. 404.8 Piping in solid floors. Piping in solid floors shall be laid in channels in the floor and covered in a manner that will allow access to the piping with a minimum amount of damage to the building. Where such piping is subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner. As an alternative to installation in channels , the piping shall be installed in a conduit of Schedule 40 steel or wrought iron pipe installed in accordance with Section 404.8.1 or 404.8.2 . 404.8.1 Conduit with one end terminating outdoors. The conduit shall extend into an occupiable portion of the bu ilding and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond th e point where the pipe emerges from the floor. If the end sealing is capable of with- standing the full pressure of the gas pipe, the conduit shall be designed for the same pressure as the pipe. Such GAS PIPING INSTALLATIONS conduit shall extend not less than 4 inches ( 101.6 mm) out side the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404.8.2 Conduit with both ends terminating indoors. Where the conduit originates and terminates within the same buildi ng, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.9 Above - ground outdoor pip ing. Piping installed outdoors shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above ground and where installed across roof surfaces, shall be elevated not less than 3 1 / 2 inches ( 88.9 mm) above the roof surface , identified in accordance with Section 401.5, and shall not be concealed . Piping installed above ground, outdoors, and installed across the surface of roofs shall be securely supported to the structure and located where it will be protected from physical damage. Where passing through an outside wall, the piping shall be protected against corrosion in accordance with Sectio n 404.11 . Where piping is encased in a protective pipe sleeve, the annular space between the piping and the sleeve shall be sealed. At least one end shall have a vented outlet piped to a safe location outdoors. The vent terminal shall be outdoors, minimum 18 inches ( 457.2 mm) above grade, not under an opening to building or overhang, and shall be installed so as to prevent the entrance of water and insects. 404.10 Reserved. 404.11 Protection against corrosion. Metallic pipe, fittings , and joints susceptible to corrosive action, such as soil condition or moisture, shall be protected in an approved manner as set forth in Sections 404.11.1 through 404.11.6. 404.11.1 Prohibited use. Threaded or uncoated welded joints shall not be used in piping in con tact with soil. Uncoated piping, fittings, and joints shall be prohibited where internal or external corrosion is known to occur. 404.11.2 Protection of exposed pipe. Ferrous metal exposed in exterior locations shall be protected from corrosion by one of t he following methods: 1. Zinc coatings (galvanizing ). 2. Bonded coatings in accordance with Section 404.11.4. 3. Protective coatings in accordance with Section 404.11.5. 4. Protective wrappings in accordance with Section 404.11.6. 404.11.3 Protection of buried pipe. Ferrous metal installed in buried locations shall be protected from corrosion by one of the following methods: 1. Bonded coatings in accordance with Section 404.11.4. 2. Protective wrappings in accordance with Section 404.11.6. W here dissimilar metals are joined underground, an insulating coupling or fitting shall be used. Piping shall not be laid in contact with cinders. 404.11.4 . Protective bonded coatings. Pipe protective bonded coatings shall be approved for the application an d shall be factory applied. Exception: Where installed in accordance with the manufacturer’s instructions , field application of bonded coatings shall be permitted for pipe, fittings and locations where the factory coating or wrapping has been dam- aged or ne cessarily removed at joints. 404.11.5 Protective coatings. Pipe protective coatings shall be approved for the application and shall be factory applied or field applied in accordance with the manufacturer’s instructions. Exception: Where installed in accord ance with the manufacturer’s instructions, field application of coatings shall be permitted for pipe, fittings and locations where the factory coating has been damaged or necessarily removed at joints. 404.11.6 Protective wrappings. Pipe protective wrappin gs shall be approved for the application and shall be field applied in accordance with the manufacturer’s instructions. GAS PIPING INSTALLATIONS 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 24 inches ( 609.6 mm) below grade , measured to the top of the pipe . Exception: Burial depth less than 24 inches (609.6 mm) is permissible when the underground piping system is protected by steel protective plates not less than 1 / 4 - inch thick (6.36 mm) and with joints tack welded and over- lap ped a minimum of 3 inches (76.2 mm). The pipe shall be not less than 4 inches (101.6 mm) below the protective steel plate. 404.13 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench . 404.13.1 Backfilling. Material used under and beside pipes shall be clean backfill, free of discarded construction material and debris. Loose earth free from rocks, broken concrete and frozen chunks shall be placed in the trench in 6 - inch (152.4 mm) laye rs and tamped in place until the crown of the pipe is covered by 12 inches (304.8 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pip e remains aligned. In instances where the manufacturer’s installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement. Backfilling is sub ject to progress inspection in ac- cordance with Section 108. 404.14 Piping underground beneath buildings. Piping installed underground beneath buildings is prohibited except where the piping is encased in a conduit of wrought iron or steel pipe designed to withstand the superimposed loads. The conduit shall be protected from corrosion in accordance with Section 404.11 and shall be installed in accordance with Section 404.14.1 , 404.14.2 or 404.14. 3 . 404.14.1 Conduit with one end terminating outdoors. The cond uit shall extend into an occupiable portion of the building and, at the point where the conduit terminates in the building, the space between the conduit and the gas piping shall be permanently sealed to prevent the possible entrance of any gas leakage. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. The end sealing shall be capable of withstanding the full pressure of the gas pipe, and the conduit shall be designed for the same pressure a s the pipe. Such conduit shall extend not less than 4 inches ( 101.6 mm) outside of the building, shall be vented above grade to the outdoors and shall be installed so as to prevent the entrance of water and insects. 404. 14.2 Conduit with both ends terminat ing indoors. Where the conduit originates and terminates within the same building, the conduit shall originate and terminate in an accessible portion of the building and shall not be sealed. The conduit shall extend not less than 2 inches ( 50.8 mm) beyond the point where the pipe emerges from the floor. 404.14.3 Conduit with both ends terminating indoors within different buildings. Where the conduit originates indoors in a building and terminates indoors within a different building, the conduit shall comply with Section 404.14.2. ‡‡‡ 404.15 Outlet closures. Gas outlets shall be permitted only under the following conditions: 1. Valved and capped gas tight outlets for appliance outlets listed on approved applications . 2. Valved and capped outlets on each floor in nonproduction laboratory buildings for future laboratories. 3. Listed and labeled flush - mounted - type quick disconnect devices and listed and labeled gas convenience outlets installed in accordance with the manufacturer’s instructions . Exceptions: 1. Test ports for gas riser valves installed downstream of a riser control valve. 2. Outlets for pressure sensors and gauges installed in conjunction with gas appliances or equipment in- stalled in accordance with the manufacturer’s instructions. 404.16 Loca tion of outlets. The unthreaded portion of piping outlets shall extend not less than 1 inch ( 25 .4 mm) through finished ceilings and walls and where extending through floors or outdoor patios and slabs, shall be not less than 2 inches ( 50.8 mm) above them. The outlet fitting or piping shall be securely supported. Outlets shall not be placed behind doors. Outlets shall be located in the room or space where the appliance is installed. GAS PIPING INSTALLATIONS Exception: Listed and labeled flush - mounted - type quick - disconnect devices an d listed and labeled gas conven- ience outlets shall be installed in accordance with the manufacturer’s instructions . 404.17 Reserved. 404.18 Pipe cleaning. The use of a flammable or combustible gas to clean or remove debris from the interior of a piping system shall be prohibited. 404.19 Prohibited devices. A device shall not be placed inside the piping or fittings that will reduce the cross - sectional area or otherwise obstruct the free flow of gas. Exceptions: 1. Approved gas filters. 2. An approved fitting or device where the gas piping system has been siz ed to accommodate the pressure drop of the fitting or device . 3. Approved gas meters for monitoring and analysis of gas usage. 404.20 Testing of piping. Before any system of piping is put in service, it shall be tested to ensure that it is gas tight. Testi ng, inspection and purging of piping systems shall comply with Section 406. 404.21 Qualifications for gas work. Gas work shall be performed by individuals possessing the qualifications set forth in Article 28 - 423 of the Administrative Code . Welders must be qualified in accordance with Section 404.21.1. 404.21.1 Welder’s qualifications. Welders installing gas piping within buildings at any pressure shall comply with the following: 1. Welders shall be qualified for all pipe sizes, wall thicknesses and all pos itions in accordance with the ASME Boiler and Pressure Vessel Code , Section IX. Requalification of welders is required on an annual basis and when requested by the commissioner. 2. Welder qualification testing shall be performed by an approved agency and t he inspector witnessing the test shall be an authorized AWS Certified Welding Inspector. Radiographic test specimens shall be evaluated by a radiographic inspector having a minimum radiography qualification of Level II in accordance with the ASNT, Document No. SNT - TC - 1A, Supplement A. 3. Copies of the certified welder qualification reports shall be maintained by both the approved agency and the licensed master plumber employing the welder(s) for at least six years and shall be made available to the department upon request. 4. The approved agency shall submit certified welder qualification reports to the department upon successful qualification of a welder and when requested by the commissioner. 5. The licensed master plumber employing the welder(s) s hall submit a statement to the department including who welded the gas piping along with a copy(s) of the certified welder qualification report(s) witnessed by a representative of the licensed master plumber, at the time of the first roughing inspection. 6 . Requalification of a welder is required should the welder fail to maintain welder’s continuity every six months. The licensed master plumber employing the welder shall maintain a welder continuity log and the log shall be made available to the department upon request. 404.21.2 Welding requirements. All gas distribution piping to customer appliances operating in excess of 1 / 2 psig (3.5 kPa gauge) shall be welded. 404.21.3 Welding records. The licensed master plumber employing the welder(s) shall assign to each welder an identification symbol or number to identify the welds performed by that particular welder. The welder shall identify all welds with his or her symbol or number. The licensed master plumber shall maintain records identifying the weld(s) made by each welder for at least six years and shall make such records available to the department upon request. GAS PIPING INSTALLATIONS ‡‡‡ SECTION FGC 405 PIPING BENDS AND CHANGES IN DIRECTION 405.1 General. Changes in direction of pipe shall be permitted to be made by the use of fi ttings , factory bends, or field bends. 405.2 Metallic pipe. Metallic pipe bends shall comply with the following: 1. Bends shall be made only with bending tools and procedures intended for that purpose. 2. All bends shall be smooth and free from buckling, cracks or other evidence of mechanical damage. 3. Bends shall be made only with seamless pipe . 4. Pipe shall not be bent through an arc of more than 90 degrees (1.6 rad). 5. The inside radius of a bend shall be not less than six times the outside diameter of the pipe. 405.3 Reserved. 405.4 Elbows. Factory - made welding elbows or transverse segments cut therefrom shall have an arc length measured along the crotch of not less than 1 inch ( 25 .4 mm) in pipe sizes 2 inches ( 50.8 mm) and larger. SECTION FGC 406 INSPECTION, TESTING AND PURGING 406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 406.1.1 Inspections. Inspection shall consist of visual examination during or after manufacture, fabrication, as- sembly or pressure tests as appropriate. Supplementary types of nondestructive inspection techniques, such as mag- netic - particle, radiographic, ultrasonic, etc., shall not be required unless specifically listed herein or in the engi- neering design. All inspections shall be performed in accordance with Section 108. 406.1.1.1 Welding inspections and testing. Welded gas piping shall be subject to special inspection in accord- ance with Chapter 17 of the New York City Building Code . Radiographic testing shall be performed on all butt welds in gas meter and gas distribution piping operating at pressures ex ceeding 5 psig (34.5 kPa gauge) within buildings, in accordance with ASME Boiler and Pressure Vessel Code , Section IX. 406.1.2 Repairs and additions. In the event repairs or additions are made after the pressure test, the affected piping shall be tested. A ll sections of de - energized piping shall be pressure tested in accordance with Section 406.4. 406.1.3 New branches. Where new branches are installed, the new branches shall be pressure tested. Connections between the new piping and the existing piping shal l be pressure tested. 406.1.4 Section testing. A piping system shall be permitted to be tested as a complete unit or in sections. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, except where a double block and bleed val ve system or flange is installed. A valve shall not be subjected to the test pressure unless the piping system upstream of the valve has been deener- gized. The section of piping not subjected to the pressure test shall be checked with a noncorrosive leak - de tecting fluid or other approved leak - detecting methods. Sections may be tested at different pressures in accordance with Section 406.4. 406.1.5 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping system in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Such regulators and valve assemblies shall not be subjected to the testing requirements of Section 406.4. Spool pieces shall be installed in p lace for the test. The regulators and valve assemblies not subjected to the pressure test shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods. GAS PIPING INSTALLATIONS 406.1.6 Pipe clearing. Prior to testing, the interior of the pipe shall be purged with air or an inert gas to clear foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations or piping installation. 406.2 Test medium. The test medium shall be air, nitrogen, carb on dioxide or an inert gas. Oxygen shall not be used. 406.3 Test preparation. Pipe joints and piping including welds, shall be left exposed for examination during the test. Exception: Covered or concealed pipe end joints that have been previously inspected in accordance with this code. 406.3.1 Expansion joints. Expansion joints shall be provided with temporary restraints, if required, for the addi- tional thrust load under test. 406.3.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods when gas is energized. 406.3.3 Appliance and equipment disconnection. Where the piping system is connected to appliances or equip- ment desig ned for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). The affected piping and joints shall be checked with a noncorrosive leak - dete cting fluid or other approved leak - detecting methods when gas is energized. 406.3.4 Valve isolation. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliance s or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). The affected piping and joints shall be checked with a noncorrosive leak - detecting fluid or other approved leak - detecting methods whe n gas is energized. 406.3.5 Testing precautions. Testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. Bulkheads, anchorage, and bracing suitably designed to resist test pres- sures shall be installed if necessary. Prior to testing, the interior of the pipe shall be purged to flush out all foreign material, including weld splatter, dirt, rags, and other debris left inside the pipe during welding operations and piping install ation. 406.4 Test pressure measurement. Upon completion of the installation of a section of a gas system or of the entire gas system, and before appliances are connected thereto, the completed section or system shall be verified as to mate- rials, and tested and proven tight . Test pressure shall be measured with a manometer or with a pressure - measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be i solated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than two times the test pressure . Gauges shall comply with the requirements of Section 406 .4.3 or 406.4.4. 406.4.1 Test pressure. The test pressure to be used shall be not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20 .9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 ps ig ( 861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. Exceptions: 1. Gas piping with distribution pressures above 5 psig ( 34.5 kPa gauge) shall be tested to twice the maximum allowable operating pressure, but not less than 100 psig ( 689.5 kPa gauge), for a minimum of 1 hour. 2. Gas piping installed in public corridors in accordance with Section 404 sh all be tested and proven tight at a pressure of 10 psig (68.9 kPa gauge) for a minimum of 30 minutes. 3. Meter piping shall be pressure tested in accordance with the requirements of the serving utility. These requirements shall be either the same as those for testing distribution piping in this section or, if different, the piping shall be certified by the utility company as being tested in compliance with their requirements. 4. Notwithstanding the above, all field applied or factory applied coated and wra pped pipe shall be pressure tested at a minimum of 100 psig ( 689.5 kPa gauge) for a minimum of 60 minutes . For testing, the piping GAS PIPING INSTALLATIONS shall be filled with air or an inert gas, and the source of pressure shall be isolated before the pressure readings are made. All test duration time periods are to be measured after stabilization of testing medium. 406.4.1.1 Factory applied coatings. Gas piping with factory applied coatings intended to protect against cor- rosion during material shipping and storage shall be teste d at not less than 1 1 / 2 times the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that pro duces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.1.2 Field applied paint. Gas piping with field applied paint intended to protect against corrosion shall be tested at not less than 1 1 / 2 ti mes the proposed maximum working pressure, but not less than 3 psig (20.9 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (861.8 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 406.4.2 Test duration. Test duration shall be not less than 1 / 2 hour, unless a greater duration is required by Section 406.4.1. 406.4.3 Minimum standards for gauges . This section establishes minimum standards for gauges used to test gas piping. Each gauge shall meet the following requirements: 1. The gauge shall be manufactured and used in accordance with ASME B40.100 , which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standa rd; 2. The gauge shall be labeled with the name of the manufacturer; 3. The units of measurement “psig” shall appear on the face of the gauge; and 4. The gauge shall be kept in good working order. 406.4.4 Digital gauges used to measure pressure in the magn itude of 3 psig ( 20.9 kPa gauge) and higher. Each digital gauge used to measure pressure in the magnitude of 3 psig ( 20.9 kPa gauge) and higher shall meet the following requirements in addition to satisfying the minimum requirements set forth in Section 40 6.4.3 : 1. The gauge shall have a minimum reading of 1 / 100 of a psig (69 Pa), and 2. An extra charged battery shall be readily available for immediate use with the gauge. ‡‡‡ 406.4.5 Witnessing tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be witnessed by department plumbing inspectors. ‡‡‡ 406.4.6 Conducting tests of gas piping systems. Tests of gas piping systems in accordance with this code shall be conducted by an individual with not less than five years’ experience in gas work. 406.4.7 Notification. The holder of the plumbing permit shall give at least two days prior notice to the commis- sioner that the plumbing work covered by the permit is ready for inspections and test. 406 .5 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak unless such reductio n can be readily attributed to some other cause. 406.5.1 Detection methods. The leakage shall be located by means of an approved gas detector, a noncorrosive leak detection fluid or other approved leak detection methods. 406.5.2 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 406.6 Piping system and equipment leakage check. Leakage checking of systems and equipment shall be in accord- ance with Sections 406.6.1 thro ugh 406.6.4. 406.6.1 Check gases. Leak checks using fuel gas shall be permitted in piping systems that have been pressure tested in accordance with Section 406. GAS PIPING INSTALLATIONS 406.6.2 Before turning gas on. During the process of turning gas on into a system of new gas pi ping, the entire system shall be inspected to determine that there are no open fittings or ends and that all valves at unused outlets are closed and plugged or capped. 406.6.2.1 Gas authorization required. A gas piping system shall not be energized prior t o authorization. Such authorization is demonstrated by issuance of a certificate of approval of gas installation by the department. The certificate shall not be issued prior to the completion of the required inspections and tests. The certificate shall not expire. Exception: Gas authorization shall not be required when gas is reestablished by a utility company as permit- ted under Section 28 - 105.4.3 of Chapter 1 of Title 28 of the Administrative Code . 406.6.2.1.1 Existing gas piping. Any gas piping system or part thereof that has been previously energized and has been shut down shall be required to obtain a certificate of approval of gas installation for all appli- ances served by the affected gas meter(s) prior to the reestablishment of gas into such system. Ex ception: When an existing gas appliance is replaced and no gas piping is replaced upstream of the existing appliance shutoff valve and not more than 6 feet (1828.8 mm) of pipe is installed or replaced downstream of the existing appliance shutoff valve, a c ertificate of approval of gas installation shall not be required to energize such pipe or replacement appliance. 406.6.2.1.2 Partial gas authorization. A certificate of approval of gas installation may be issued for a por- tion of a gas piping system provide d the remainder of the system is locked - off by the gas service provider. 406.6.2.2 Establishing gas supply. It shall be unlawful for any utility company to supply or restore gas to a building, place or premises in which new meters other than replacement ga s meters are required until a certificate of approval of gas installation is issued in accordance with Section 406.6.2.1 . When new gas service piping has been installed, it shall be locked - off by the utility either by locking the gas service line valve or by installing a locking device on the outside gas service line valve. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected and certified as required by the depart- ment as being re ady for service. When an existing gas service piping has been taken out of service, it shall be locked - off by the utility. The lock shall not be removed until the gas meter piping (other than utility - owned) and gas distribution piping has been inspected an d certified as required by the department as being ready for service. 406.6.2.3 Alterations to gas piping systems. When alterations, extensions or repairs to existing gas meter pip- ing or gas distribution piping requires the operation of a service head valve, regulator valve or meter valve that would interrupt the flow of gas to a building , the utility shall be notified by the owner or his or her authorized representative. 406.6.2.4 Emergency service head valve, regulator valve or gas meter valve operati on. It is permissible for a licensed plumber or his or her employee to operate a valve in an emergency to alleviate a hazardous condition. The utility shall be notified by the licensee or his or her authorized representative. Such licensee or authorized re presentative shall wait on location for utility company operators to arrive and lock the affected valve. 406.6.3 Leak check. Immediately after the gas is turned on into a new system or into a system that has been initially restored after an interruption of service, the piping system shall be checked for abnormal operating conditions and leakage. The leakage check shall be performed by means of a combustible gas indicator complying with Section 406.7.1.4, or a noncorrosive leak detection fluid. Where leakage is indicated, or where an abnormal operating condition presents a hazard , the gas supply shall be shut off until the necessary repairs have been made. 406.6.4 Placing appliances and equipment in operation. Appliances and equipment shall not be placed in o per- ation until after the piping system has been checked in accordance with Section 406.6.3 , the piping system has been purged in accordance with Section 406.7 and the connections to the appliances have been checked for leakage. 406.6.4.1 Requirements for p lacing appliances in operation. The following will be required prior to placing appliances in operation as applicable: 1. Required fire protection system (sprinkler or standpipe) are completed, inspected and ready for service. 2. Such appliance and related equipment and gas piping are inspected by the department . 3. Associated fire suppression system is inspected and approved by the Fire Department. Exception: Appliances may be used as temporary sources of heat during construction as needed and in ac- cordance with requirements of the department. GAS PIPING INSTALLATIONS 406.7 Purging. The purging of piping shall be in accordance with Sections 406.7.1 through 406.7.3. 406.7.1 Piping systems required to be purged outdoors. The purging of piping systems shall be in accordanc e with the provisions of Sections 406.7.1.1 through 406.7.1.4 where the piping system meets either of the following: 1. The design operating gas pressure is greater than 2 psig ( 13. 8 kPa). 2. The piping being purged contains one or more sections of pipe me eting the size and length criteria of Table 406.7.1.1. 406.7.1.1 Removal from service. Where existing gas piping is opened, the section that is opened shall be iso- lated from the gas supply and the line pressure vented in accordance with Section 406.7.1.3. Where gas piping meeting the criteria of Table 406.7.1.1 is removed from service, the residual fuel gas in the piping shall be displaced with an inert gas. TABLE 406.7.1.1 SIZE AND LENGTH OF PIPING NOMINAL PIPE SIZE (inches) LENGTH OF PIPING (feet) ≥ 2 1 / 2 < 3 ≥ 50 ≥ 3 < 4 ≥ 30 ≥ 4 < 6 ≥ 15 ≥ 6 < 8 ≥ 10 ≥ 8 Any length For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 406.7.1.2 Placing in operation. Where gas piping containing air and meeting the criteria of Table 406.7.1.1 is placed in operation, the air in the piping shall first be displaced with an inert gas. The inert gas shall then be displaced with fuel gas in accordance with Section 406.7.1.3. 406.7.1.3 Outdoor discharge of purged gases. The open end of a piping system being pressure vented or purged shall discharge directly to an outdoor location. Purging operations shall comply with all of the following requirements: 1. The point of discharge shall be controlled with a shutoff valve. 2. The point of discharge shall be located not less than 10 feet (3048 mm) from sources of ignition, not less than 10 feet (3048 mm) from building openings and not less than 25 feet (7620 mm) from mechanical air i ntake openings. 3. During discharge, the open point of discharge shall be continuously attended and monitored with a com- bustible gas indicator that complies with Section 406.7.1.4. 4. Purging operations introducing fuel gas shall be stopped when at least 95 percent fuel gas by volume is detected within the pipe. 5. Persons not involved in the purging operations shall be evacuated from all areas within 10 feet (3048 mm) of the point of d ischarge. 406.7.1.4 Combustible gas indicator. Combustible gas indicators shall be listed and shall be calibrated in ac- cordance with the manufacturer’s instructions. Combustible gas indicators shall numerically display a volume scale from zero percent to 1 00 percent in 1 percent or smaller increments. 406.7.2 Piping systems allowed to be purged indoors or outdoors. The purging of piping systems shall be in accordance with the provisions of Section 406.7.2.1 where the piping system meets both of the followin g: 1. The design operating gas pressure is 2 psig (13.79 kPa) or less. 2. The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 406.7.1.1. 406.7.2.1 Purging procedure. The piping system shall be purged in accordance with one or more of the fol- lowing: GAS PIPING INSTALLATIONS 1. The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Se ction 406.7.2.2. Purging shall be stopped when fuel gas is detected. 2. The piping shall be purged in accordance with written procedures of the utility company . 406.7.2.2 Combustible gas detector. Combustible gas detectors shall be listed and shall be cal ibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. 406.7.3 Purging appliances and equipment. After the piping system has been placed in operation, applian ces and equipment subsequently installed shall be purged before being placed into operation. SECTION FGC 407 PIPING SUPPORT 407.1 General. Piping shall be provided with support in accordance with Section 407.2. In addition, when earth- quake loads are applicable in accordance with the New York City Building Code , a detailed piping system stress analysis including seismic analysis shall be performed. The pipe supports and restraints shall be designed and installed t o accommodate the resultant seismic forces, moments and displacements from this stress analysis in accordance with the New York City Building Code . 407.2 Design and installation. Piping shall be supported with metal pipe hooks, metal pipe straps, metal ban ds, metal brackets, metal hangers or building structural components, suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue str ains on connected appliances and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements of MSS SP - 58 and shall be spaced in accordance with Section 415. Supports, hangers and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment shall be designed and installed so that they will not be disengaged by movement of the supported piping. SECTION FGC 408 DRIPS AND SL OPED PIPING 408.1 Slopes. Piping for other than dry gas conditions shall be sloped not less than 1 / 4 inch in 15 feet (6.3 mm in 4572 mm) to prevent traps. The local gas supplier/utility company should be consulted to determine the type of fuel gas available for the intended service . 408.2 Drips. Drips are not permitted. 408.3 Test fittings. A manufactured test fitting shall be installed where required by the gas supplier. Such fitting shall be downstream of a lockable supply or riser valve in accord ance with the requirements of the gas supplier and the manufacturer’s instructions. The outlet of the test fitting shall be the smallest commercially available. The installation of manufactured test fittings in other locations shall be prohibited. 408.4 Se diment trap. Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the appliance shutoff valve as close to the inlet of the appliance as practical. The sediment trap shall be either a tee fitti ng having a capped nipple of any length installed vertically in the bottom most opening of the tee as illustrated in Figure 408.4 or other device approved as an effective sediment trap. Illuminating appli- ances, ranges, clothes dryers, decorative vented appliances for installation in vented fireplaces, gas fireplaces and outdoor grills need not be so equipped. GAS PIPING INSTALLATIONS FIGURE 408.4 METHOD O F INSTALLING A TEE FITTING SEDIMENT TRAP SECTION FGC 409 SHUTOFF VALVES 409.1 General. Piping systems shall be provided with shutoff valves in accordance with this section. 409.1.1 Valve approval. Shutoff valves shall be of an approved type; shall be const ructed of materials compatible with the piping; and shall comply with the standard that is applicable for the pressure and application, in accordance with Table 409.1.1. TABLE 409.1.1 MANUAL GAS VALVE STANDARDS VALVE STANDARDS APPLIANCE SHUTOFF VALVE APPLICATION UP TO 1 / 2 psig PRESSURE OTHER VALVE APPLICATIONS UP TO 1 / 2 psig PRESSURE UP TO 2 psig PRESSURE UP TO 5 psig PRESSURE UP TO 125 psig PRESSURE ANSI Z21.15 / CGA 9.1 X — — — — ASME B16.44 X X X a X b — ASME B16.33 X X X X X For SI: 1 pound per square inch gauge = 6.895 kPa. a. If labeled 2G. b. If labeled 5G. GAS PIPING INSTALLATIONS 409.1.2 Prohibited locations. Shutoff valves shall be prohibited in concealed locations and furnace plenums. 409.1.3 Access to shutoff valves. Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage. 409.2 Meter valve. Every meter shall be equipped with a shutoff valve located on the supply side of the meter. Meter valves shall be of a type approved b y the utility company. 409.3 Shutoff valves for multiple - house line systems. Where a single meter is used to supply gas to more than one building or tenant, a separate shutoff valve shall be provided for each building or tenant. 409.3.1 Multiple tenant buildings. In multiple tenant buildings, where a common piping system is installed to supply other than individual dwelling units, shutoff valves shall be provided for each tenant. Each tenant shall have access to the shutoff valve serving that tena nt’s space. 409.3.2 Individual buildings. In a common system serving more than one building, shutoff valves shall be installed outdoors at each building. 409.3.3 Identification of shutoff valves. Each house line shutoff valve shall be plainly marked with a n iden- tification tag attached by the installer so that the piping systems supplied by such valves are readily identified. Identification shall be provided in compliance with ASME A13.1. 409.4 MP regulator valves. An approved shutoff valve shall be installe d immediately ahead of each MP regulator. 409.5 Appliance shutoff valve. Each appliance shall be provided with a shutoff valve in accordance with Section 409.5.1 or 409.5. 2 . 409.5.1 Located within the same room. The shutoff valve shall be located in the same room as the appliance. The shutoff valve shall be within 6 feet ( 1828.8 mm) of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves. Such shutoff valves shall be provided with access and located not more than 60 inches (1524 mm) above the finished floor . Appliance shutoff valves located in the firebox of a fireplace shall be installed in accordance with the appliance manufacturer’s instructions. Where the shutoff valve is located in the firebox , a remote shutoff valve shall also be provided. Exception: Shutoff valves may be located more than 60 inches (1524 mm) above the finished floor where the gas connection to the appliance is more than 60 inches (1524 m m) above the finished floor. 409.5.2 Vented decorative appliances and room heaters. Shutoff valves for vented decorative appliances, room heaters and decorative appliances for installation in vented fireplaces shall be permitted to be installed in an area remote from the appliances where such valves are provided with ready access. Such valves shall be permanently identified and shall not serve another appliance. The piping from the shutoff valve to within 6 feet ( 1828.8 mm) of the appliance shall be designe d, sized and installed in accordance with Sections 401 through 408. 409.6 Shutoff valve for laboratories. Where provided with two or more fuel gas outlets, including table - , bench - and hood - mounted outlets, each laboratory space in educational, research, commercial and industrial occupancies shall be provided with a single dedicated shutoff valve through whic h all such gas outlets shall be supplied. The dedicated shutoff valve shall be readily accessible, located within the laboratory space served, located adjacent to the egress door from the space and shall be identified by approved signage stating “Gas Shuto ff.” 409.7 Outside gas cut - off. An outside gas service line valve or other outside shutoff device or method acceptable to the commissioner shall be provided in accordance with Section E.2 of Appendix E. 409.8 Riser shutoff valves. Risers shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. 409.9 Branch shutoff valves. Branches serving more than one appliance shall be equipped with an approved lockable shutoff valve. There shall be a test port installed downstream of the valve. SECTION FGC 410 FLOW CONTROLS GAS PIPING INSTALLATIONS 410.1 Pressure regulators. A line pressure regulator shall be i nstalled where the appliance is designed to operate at a lower pressure than the supply pressure. Line gas pressure regulators shall be listed as complying with ANSI Z21.80 /CSA 6.22 . Access shall be provided to pressure regulators. Pressure regulators shal l be protected from physical damage. Regulators installed on the exterior of the building shall be approved for outdoor installation. 410.2 MP regulators. Medium pressure (MP) regulators shall comply with the following: 1. The MP regulator shall be approve d and shall be suitable for the inlet and outlet gas pressures for the application. 2. The MP regulator shall maintain a reduced outlet pressure under lockup (no - flow) conditions. 3. The capacity of the MP regulator, determined by published ratings of its manufacturer, shall be adequate to supply the appliances served. 4. The MP regulator shall be provided with access. Where located indoors, the regulator shall be vented to the outdoors or shall be equipped with a leak - limiting device, in either case comply ing with Section 410.3. 5. A tee fitting with one opening capped or plugged shall be installed between the MP regulator and its upstream shutoff valve. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument and to serve as a sediment trap. 6. A tee fitting with one opening capped or plugged shall be installed not less than 10 pipe diameters downstream of the MP regulator outlet. Such tee fitting shall be positioned to allow connection of a pressure - measuring instrument. A pressure gauge with an isolation valve may also be installed in addition to the fitting. 7. At least one union shall be installed within 1 foot (304.8 mm) of either side of the MP regulator. 410.3 Venting of regulators. Pressure regulators that require a vent shall be vented directly to the outdoors. The vent terminal shall be a minimum of 18 inches ( 457.2 mm) above grade, not under a building - opening or overhang, and shall be installed so as to prevent the entrance of water and insects. Exception: A vent to the outdoors is not required for regulators equipped with and labeled for utilization with an approved vent - limiting device installed in accordanc e with ANSI Z21.18 and the manufacturer’s instructions. The vent - limiting device shall be installed in a location sufficiently ventilated to dissipate any gas discharged from the device. 410.3.1 Vent piping. Vent piping for relief vents and breather vents shall be constructed of materials allowed for gas piping in accordance with Section 403. Vent piping shall be not smaller than the vent connection on the pres- sure - regulating device. Vent piping serving relief vents and combination relief and breather vents shall be run independently to the outdoors and shall serve only a single device vent. Vent piping serving only breather vents is permitted to be connected in a manifold arrangement where sized in accordance with an approved design that minimizes back pres sure in the event of diaphragm rupture. Regulator vent piping shall not exceed the length specified in the regulator manufacturer’s instructions . 410.4 Excess flow valves. Where automatic excess flow valves are installed, they shall be listed for the application and shall be sized and installed in accordance with the manufacturer’s instructions. 410.5 Flashback arrestor check valve. Where fuel gas is used with oxygen in any hot work operation, a listed pro- tective device that serves as a combination flashback arrestor and backflow check valve shall be installed at an ap- proved location on both the fuel gas and oxygen supply lines. Where the pressure of the piped fuel gas suppl y is insufficient to ensure such safe operation, approved equipment shall be installed between the gas meter and the appli- ance that increases pressure to the level required for such safe operation. SECTION FGC 411 APPLIANCE AND MANUFACTURED HOME CONNECTIO NS 411.1 Connecting appliances. Except as required by Section 411.1.1, appliances shall be connected to the piping system by one of the following: GAS PIPING INSTALLATIONS 1. Rigid metallic pipe and fittings. Space heaters and water heaters shall be connected using rigid piping an d fittings only. Use of semirigid (flexible) metallic tubing, fittings , appliance connectors or quick - disconnect devices is not permitted for this application. 2. Listed and labeled appliance connectors in compliance with ANSI Z21.24 /CGA 6.10 and installed in accordance with the manufacturer’s instructions and located entirely in the same room as the appliance. Connectors shall have an overall length not to exceed 6 feet (1828.8 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance. 3. Listed and labeled quick - disconnect devices used in conjunction with listed and labeled appliance connectors. 4. Listed and labeled convenience outlets used in conjunction with listed and labeled appliance con nectors. 5. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 6. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect porta ble outdoor appli- ances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick - disconnect device or listed gas convenience outlet. 411. 1.1 Commercial cooking appliances. Commercial cooking appliances installed on casters and appliances that are moved for cleaning and sanitation purposes shall be connected to the piping system with an appliance connector listed as complying with ANSI Z21.6 9 /CSA 6.16 and NSF/ANSI 169 or in accordance with Item 1 of Section 411.1. The commercial cooking appliance connector installation shall be configured in accordance with the manu- facturer’s instructions. Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer’s instructions. 411.1.2 Protection against damage. Connectors and tubing shall be installed so as to be protected against physical damage. 411.1.3 Connector installation. Fuel connectors shall be installed in accordance with the manufacturer’s instruc- tions and Sections 411.1.3.1 through 411.1.3.4. 411.1.3 .1 Maximum length. Connectors shall have an overall length not to exceed 6 feet ( 1828.8 mm). Meas- urement shall be made along the centerline of the connector. Only one connector shall be used for each appli- ance. 411.1.3.2 Minimum size. Connectors shall have the capacity for the total demand of the connected appliance. 411.1.3.3 Prohibited locations and penetrations. Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings. Exceptions: 1. Connect ors constructed of materials allowed for piping systems in accordance with Section 403 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section 409.5.2. 2. Rigid steel pipe connectors shall be per mitted to extend through openings in appliance housings. 3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in ac- cordance with the listing of the appliance. 4. Listed connectors shall be permitted to extend t hrough an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage. 411.1.3.4 Shutoff valve. A shutoff valve not less than the nominal size of the piping system shall be installed ahead of the connector i n accordance with Section 409.5. 411.1.4 Movable appliances. Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69 /CSA 6.16 or by means of Item 1 of Section 411.1 of this code . Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer’s instructions . GAS PIPING INSTALLATIONS 411.1.5 Connection of gas engine - powered air conditioners. Internal combustion engines shall not be rigidly connected to the gas supply piping. 411.1.6 Unions. A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall be accessible and located within 6 feet ( 1828.8 mm) of the appliance. 411.2 Manufactured home connections. Manufactured homes shall be connected to the distribution piping system by one of the following materials: 1. Metallic pipe in accordance with Section 403.4. 2. Listed and labeled connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer’s instructions . 411.3 Suspended low - intensity infrared tube heaters. Suspended lo w - intensity infrared tube heaters shall be con- nected to the building piping system with a connector listed for the application complying with ANSI Z21.24/CGA 6.10. The connector shall be installed as specified by the tube heater manufacturer’s instructions . SECTION FGC 412 LIQUEFIED PETROLEUM GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 412.1 Applicability. Motor fuel - dispensing facilities for LP - gas fuel shall be designed and operated in accordance with the New York City Fire Code . 412.2 Reserved. 412.3 Reserved. 412.4 Reserved. 412.5 Reserved. 412.6 Reserved. 412.7 Reserved. 412.8 Reserved. SECTION FGC 413 COMPRESSED NATURAL GAS MOTOR VEHICLE FUEL - DISPENSING FACILITIES 413.1 Applicability. Motor fuel - dispensing facilities for CNG fuel shall be designed and operated in accordance with the New York City Fire Code . 413.2 Reserved. 413.3 Reserved. 413.4 Reserved. 413.5 Reserved. 413.6 Reserved. 413.7 Reserved. 413.8 Reserved. SECTION FGC 414 RE SERVED GAS PIPING INSTALLATIONS SECTION FGC 415 PIPING SUPPORT INTERVALS 415.1 Interval of support. Piping shall be supported at intervals not exceeding the spacing specified in Table 415.1. TABLE 415.1 SUPPORT OF PIPING STEEL PIPE, NOMINAL SIZE OF PIPE (inches) SPACING OF SUPPORTS (feet) 1 / 2 6 3 / 4 or 1 8 1 1 / 4 or larger (horizontal) 12 All vertical piping Every floor level For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. SECTION FGC 416 OVERPRESSURE PROTECTION DEVICES 416.1 Where required. Where the serving gas supplier delivers gas at a pressure greater than 2 psi (13.79 kPa) for piping systems serving appliances designed to operate at a gas pressure of 14 inches w.c. (3.49 kPa) or less, overpres- sure protection devices shall be installed. Piping systems serving appliances designed to operate at inlet pressures greater than 14 inches w.c. (3.49 kPa) shall be equipped with overpressure protection devices as required by the ap- pliance manufacturer’s instructions. 416.2 Pressure limitation requi rements. The requirements for pressure limitation shall be in accordance with Sec- tions 416.2.1 through 416.2.5. 416.2.1 Pressure under 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches w.c. (3.49 kPa) or less are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi or less upon a failure of the line pressure regulator. 416.2.2 Pressure over 14 inches w.c. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches w.c. (3.49 kPa) are required to be equipped with overpressure protection by Section 416.1, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s instru ctions. 416.2.3 Device capability. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by Section 416.2.1, independently of any other pr essure control equipment in the piping system. 416.2.4 Failure detection. Each gas piping system for which an overpressure protection device is required by Section 416 shall be designed and installed so that a failure of the primary pressure control device (s) is detectable. 416.2.5 Relief valve. Where a pressure relief valve is used to meet the requirements of Section 416, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 416.2.1 under all of the following conditions: 1. The line pressure regulator for which the relief valve is providing overpressure protection has failed wide open. 2. The gas pressure at the inlet of the line pressure regulator for which the relief valve i s providing overpressure protection is not less than the regulator’s normal operating inlet pressure. GAS PIPING INSTALLATIONS 416.3 Devices. Pressure - relieving or pressure - limiting devices shall be one of the following: 1. Pressure relief valve. 2. Monitoring regulator. 3. Series regulator installed upstream from the line regulator and set to continuously limit the pressure on the inlet of the line regulator to the maximum values specified by Section 416.2.1. 4. Automatic shutoff device installed in series with the line pressure r egulator and set to shut off when the pressure on the downstream piping system reaches the maximum values specified by Section 416.2.1. This device shall be designed so that it will remain closed until manually reset. The devices specified in this section shall be installed either as an integral part of the service or line pressure regulator or as separate units. Where separate pressure - relieving or pressure - limiting devices are installed, they shall comply with Sections 416.3.1 through 416.3.6 . 416.3.1 Con struction and installation. Pressure - relieving and pressure - limiting devices shall be constructed of materials so that the operation of the devices will not be impaired by corrosion of external parts by the atmosphere or of internal parts by the gas. Press ure - relieving and pressure - limiting devices shall be designed and installed so that they can be operated to determine whether the valve is free. The devices shall be designed and installed so that they can be tested to determine the pressure at which they will operate and examined for leakage when in the closed position. The devices shall be maintained and inspected in accordance with Section 416.3.7. 416.3.2 External control piping. External control piping shall be designed and installed so that damage to the control piping of one device will not render both the regulator and the overpressure protection device inoperative. 416.3.3 Setting. Each pressure - relieving or pressure - limiting device shall be set so that the gas pressure supplied to the connected appliances does not exceed the limits specified in Section 416.2.1 . 416.3.4 Unauthorized operation. Precautions shall be taken to prevent u nauthorized operation of any shutoff valve that will make a pressure - relieving valve or pressure - limiting device inoperative. The valve shall be locked or continuously monitored in the open position. 416.3.5 Vents. The discharge stacks, vents and outlet pa rts of all pressure - relieving and pressure - limiting devices shall be located so that gas is safely discharged to the outdoors. Discharge stacks and vents shall be designed to prevent the entry of water, insects and other foreign material that could cause b lockage. The discharge stack or vent line shall be not less than the same size as the outlet of the pressure - relieving device. 416.3.6 Size of fittings, pipe and openings. The fittings, pipe and openings located between the system to be protected and the p ressure - relieving device shall be sized to prevent hammering of the valve and to prevent impair- ment of relief capacity. 416.3.7 Device maintenance. The overpressure protection device: (i) shall be properly maintained and inspected every two years by a lice nsed master plumber; (ii) inspection records shall be maintained by the owner and made available to the department; (iii) inspection procedures shall be in accordance with the commissioner; and (iv) replacements or repairs shall be promptly made. Exception : Where the gas pressure is 15 psig (103.4 kPa gauge) or above, the overpressure protection device shall be inspected annually.