‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. ‡‡‡ Chapter 5 was amended by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. CHAPTER 5 CHIMNEYS AND VENTS SECTION FGC 501 GENERAL 501.1 Scope. This chapter shall govern the installation, alteration, maintenance, design, minimum safety requirements, repair and ap- proval of fa ctory - built chimneys, chimney liners, vents and connectors, field - built chimneys and connectors and the utilization of ma- sonry chimneys serving gas - fired appliances. The requirements for the installation, maintenance, repair and approval of factory - built c himneys, chimney liners, vents and connectors serving appliances burning fuels other than fuel gas shall be regulated by the New York City Mechanical Code . The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the New York City Building Code . Venting systems shall be designed in accordance with this chapter and comply with the requirements of the New York City Air Pollution Control Code . 501.1.1 Existing chimneys and vents. Existing chimneys and vents shall comply w ith the requirements of Section 28 - 104.13 of the Administrative Code and Sections 501.1.1.1 through 501.1.1.8 of this code . 501.1.1.1 Responsibility of owner of taller building. Whenever a building is erected, enlarged, or increased in height so that any p ortion of such building, except chimneys or vents, extends higher than the top of any existing chimneys or vents within 100 feet (30 480 mm), the owner of such new or altered building shall have the responsibility of altering such chimneys or vents to ma ke them conform with the requirements of this chapter. A chimney or vent that is no longer connected with a fireplace or combust ion or other equipment for which a chimney or vent was required shall be exempt from this requirement. Such alterations shall be a ccomplished by one of the following means or a combination thereof: 1. Carry up the existing chimneys or vents to the height required in this chapter. 2. Offset such chimneys or vents to a distance beyond that required by this chapter from the new or alter ed building provided that the new location of the outlet of the offset chimney or vent shall otherwise comply with the requirements of this chapte r. Such requirements shall not dispense with or modify any additional requirements that may be applicable purs uant to rules of the New York City Department of Environmental Protection . 501.1.1.1.1 Chimney and vent plan. Applications for a new or altered building shall include a chimney and vent plan submitted pursuant to Section 107.18 of the New York City Building Code . 501.1.1.2 Protection of draft. After the alteration of a chimney or vent as required by this section, it shall be the responsibility of the owner of the new or altered building to provide any mechanical equipment or devices necessary to maintain the proper draft in the equipment. 501.1.1.3 Written notification , plans and required documents . The owner of t he new or altered building shall notify the owner of any building that may require a chimney or vent to be altered. Notification, plans and required documents shall comply with the requirements of Sections 501.1.1.3.1 through 501.1.1.3.3. 501.1.1.3.1 First notice. Written notice in a form acceptable to the department shall be provided to the building owner not less than 60 days prior to a request for permit for construction on the new or altered building. Such notice shall include a reque st for access to de termine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. A copy of such return receipt shall be filed with the department. 501.1.1.3.2 Second n otice. Written notice in a form acceptable to the department shall be provided to the building owner not more than 45 days following commencement of work after a permit has been issued for the new or altered building. Such notice shall include a request fo r access to determine the need to alter the existing chimney or vent and a description of such work. Notice shall be sent by regular mail and certified mail, return receipt requested. The second notice shall also be posted by a licensed process server at t he public entrance of the building requiring a chimney or vent to be altered. A copy of such return receipt and proof of service by the licensed process server shall be filed with the department. Exceptions: 1. A second notice shall not be required where an application to alter the affected chimney or vent has been filed with the department. 2. A second notice shall not be required where access is granted and conditions are observed that result in a determination that chimney or vent alteration is no t required and a revised chimney and vent plan is submitted to the department. 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 501.1.1.3.3 Plans and required documentation for alteration work. Where access is granted and conditions are observed that result in a determination that chimney or vent alterat ion is required, plans for such alteration work shall be provided to the owner of the existing building and a request for written consent to submit construction documents and perform such work shall be made. 501.1.1.4 Approval. The construction documents f or the proposed chimney extension, alteration or relocation shall be submitted to the department pursuant to Section 28 - 104 of the Administrative Code . No certificate of occupancy shall be issued for the new build- ing pursuant to Section 28 - 118.23 of the Ad ministrative Code until the work associated with the construction documents for the proposed chimney extension, alteration or relocation has been signed - off by the department. Exceptions: 1. A certificate of occupancy may be issued where access is granted and conditions are observed that result in a determina- tion that chimney or vent alteration is not required and a revised chimney or vent plan is submitted pursuant to Section 107.18 of the New York City Building Code documenting such. 2. A certificate of o ccupancy may be issued in accordance with Section 28 - 118.23, Exception 2 of the Administrative Code . 501.1.1.5 Refusal of consent. If consent is not granted by the owner of the affected building to do the alteration work required by this section, such owner shall signify his or her refusal in writing to the owner of the new or altered building and to th e commissioner; and the owner of the new or altered building having provided the notic es required by Section 501.1.1.3 shall thereupon be released from any responsibility for the proper operation of the equipment due to loss of draft and for any heal th hazard or nuisance that may occur as a result of the new or altered building. Such respon sibilities shall then be assumed by the owner of the previously constructed building. Similarly, should such owner fail to grant consent within 45 days from the date of the second notice or fail to signify his or her refusal, he or she shall then assume al l responsibilities as prescribed above. 501.1.1.6 Procedure. It shall be the obligation of the owner of the new or altered building to: 1. Prepare and submit a chimney and vent plan to the department pursuant to Section 107.18 of the New York City Buildin g Code . 2. Provide required notification pursuant to Section 501.1.1.3 of this code. 3. Provide plans pursuant to Section 501.1.1.3.3 of this code. 4. Prepare and submit construction documents to the department pursuant to Section 28 - 104 of the Administ rative Code for the alteration of existing chimneys or vents which conform to the requirements of this chapter; 5. Obtain permit(s) for the proposed work in accordance with Section 28 - 105 of the Administrative Code ; 6. Schedule this work so as to create a minimum of disturbance to the occupants of the affected building; 7. Provide such essential services as are normally supplied by the equipment while it is out of service; 8. Where necessary, support such extended chim neys, vents and equipment from this building or to carry up such chimneys or vents within his or her building; 9. Provide for the maintenance, repair, and/or replacement of such extensions and added equipment; 10. Make such alterations of the same materia l as the original chimney or vent so as to maintain the same quality and appear- ance, except where the owner of the chimney or vent shall give his or her consent to do otherwise. All work shall be done in such fashion as to maintain the architectural aesthe tics of the existing building. Where there is practical difficulty in complying strictly with the provisions of this item, the commissioner may permit an equally safe alternative; 11. Comply with the tenant protection plan requirements of Section 28 - 120 of the Administrative Code ; and 12. Comply with inspection and sign - off requirements of Section 28 - 116 of the Administrative Code . 501.1.1.7 Existing violations. Any existing violations on the previously constructed equipment shall be corrected by the owner of the equipment before any equipment is added or alterations made at the expense of the owner of the new or altered building . 501.1.1.8 Variance. The commissioner may grant a variance in accordance with the provisions of this code. 501.2 General. Every ap pliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Exception: Commercial cooking appliances vented by a Type I hood installed in accordance with Section 507 of the New York City Mechanical Code . 501. 2.1 Design. Chimneys and vents shall be designed and constructed so as to provide the necessary draft and capacity for each appliance connected to completely exhaust the products of combustion to the outside air. The temperature on adjacent combus- tible surfaces shall not be raised above 160°F ( 71.1 °C). Chimneys and vents shall be designed to resist the effects of condensa tion that would cause deterioration of the chimney or vent. 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 501.2.2 Outlets. The outlet shall be arranged so that the flue gases are not directed so that they jeopardize people, overheat combustible structures, or enter building openings in the vicinity of the outlet. Gas - fired appliances shall be vented in accordance with this code and NFPA 54. 501.2. 3 Support. Chimneys and vents shall not be supported by the equipment they serve unless such equipment has been specifi- cally designed for such loads. 501.2.4 Changes in appliance fuels. Masonry chimneys shall be constructed in accordance with Section 507. 501.2.5 Ex haust gases from internal combustion engines and turbines. Exhaust pipes shall be constructed in accordance with Section 508. 501.3 Masonry chimneys. Masonry chimneys shall be constructed in accordance with Section 503.5.3 and the New York City Building Co de . 501.4 Minimum size of chimney or vent. Chimneys and vents shall be sized in accordance with Sections 503 and 504. 501.5 Abandoned inlet openings. Abandoned inlet openings in chimneys and vents shall be closed by an approved method. 501.6 Positive press ure. Where an appliance equipped with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications. 501.7 Connection to fireplace. Connection of appliances to ch imney flues serving fireplaces shall be in accordance with Sections 501.7.1 through 501.7.3. 501.7.1 Closure and access. A noncombustible seal shall be provided below the point of connection to prevent entry of room air into the flue. Means shall be provided for access to the flue for inspection and cleaning. 501.7.2 Connection to factory - built fireplace flue. An appliance shall not be connected to a flue serving a factory - built fire- place unless the appliance is specifically listed for such installation. The connection shall be made in accordance with the appli- ance manufacturer’s instructions . 501.7.3 Connection to masonry fireplace flue. A connector shall extend from the appliance to the flue serving a masonry fireplace such that the flue gases are exhausted directly into the flue. The connector shall be accessible or removable for i nspec- tion and cleaning of both th e connector and the flue. Listed direct connection devices shall be installed in accordance with their listing. 501.8 Appliances not required to be vented. The following appliances shall not be required to be vented: 1. Ranges. 2. Built - in domestic cooking units listed and marked for optional venting. 3. Hot plates and laundry stoves. 4. Type 1 clothes dryers (Type 1 clothes dryers shall be exhausted in accordance with the requirements of Section 504 of the New York City Mechanical Code ). 5. A single booste r - type automatic instantaneous water heater, where designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the heater is installed in a commercial kitchen having a mechanical exhaust system. Where installed in this manner, the draft hood, if required, shall be in place and unaltered and the draft hood outlet shall be not less than 36 inches ( 914 .4 mm) vertically and 6 inches ( 152 .4 mm) horizontally from any surface other than the heater. 6. Refrigerators. 7. Co unter appliances. 8. Specialized appliances of limited input such as laboratory burners and gas lights. 9. Recirculating direct - fired industrial air heaters as provided for in Section 612. Where the appliances listed in Items 5 through 9 above are installe d so that the aggregate input rating exceeds 20 British thermal units (Btu) per hour per cubic foot (207 watts per m 3 ) of volume of the room or space in which such appliances are installed, one or more shall be provided with venting systems or other approv ed means for conveying the vent gases to the outdoor atmosphere so that the aggregate input rating of the remaining unvented appliances does not exceed 20 Btu per hour per cubic foot (207 watts per m 3 ). Where the room or space in which the appliance is ins talled is directly connected to another room or space by a doorway, archway, or other opening of comparable size that cannot be closed, the volume of such adjacent room or space shall be permitted to be in cluded in the calculations. 501.9 Chimney entrance. Connectors shall connect to a masonry chimney flue at a point not less than 12 inches ( 304.8 mm) or one chimney diameter above the lowest portion of the interior of the chimney flue. 501.10 Connections to exhauster. Appliance connections to a chimney or v ent equipped with a power exhauster shall be made on the inlet side of the exhauster. Joints and vent systems on the positive pressure side of the exhauster shall be sealed to prevent flue - gas leakage as specified by the manufacturer’s instructions for the exhauster or in accordance with this code . 501.11 Masonry chimneys. Masonry chimneys utilized to vent appliances shall be located, constructed and sized as specified in the manufacturer’s instructions for the appliances being vented and Section 503. ‡‡‡ 50 1.12 Residential and low - heat appliances flue lining systems. Flue lining systems for use with residential - type and low - heat appliances shall be limited to the following: 1. Clay flue lining complying with the requirements of ASTM C 315 or equivalent. Clay flue lining shall be installed in accordance with the New York City Building Code . 2. Listed chimney lining systems complying with UL 1777 (new and existing chimneys) or ULC - S635 (existing chimneys) or ULC - S640 (new chimneys). 3. Other approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate at temperatures up to 1,800°F ( 9 82.2 °C). 501.13 Category I appliance flue lining systems. Flue lining systems for use with Category I appliances shall be limited to the following: 1. Flue lining systems complying with Section 501.12. 2. Chimney lining systems listed and labeled for use with gas appliances with draft hoods and other Category I gas appliances listed and labeled for use with Type B vents. 501.14 Category II, III and IV appliance venting systems. The design, sizing and installation of vents for Category II, III and IV appliances shall be in accordance with the appliance manufacture r’s instructions . 501.15 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an appliance is connected to an existing chimney or vent during the process of a new installation, the chimney o r vent shall comply with Sections 501.15.1 through 501.15.4. 501.15.1 Size. The chimney or vent shall be resized as necessary to control flue gas condensation in the interior of the chimney or vent and to provide the appliance or appliances served with the required draft. For Category I appliances, the resizing shall be in accordance with Section 502. 501.15.2 Flue passageways. The flue gas passageway shall be free of obstructions and combustible deposits and shall be cleaned if previously used for venting a solid or liquid fuel - burning appliance or fireplace. The flue liner, chimney inner wall or vent inner wall shall be continuous and shall be free of cracks, gaps, perforations or other damage or deterioration that would allow the escape of combustion prod ucts, including gases, moisture and creosote. 501.15.3 Cleanout. Masonry chimney flues shall be provided with a cleanout opening having a minimum height of 6 inches ( 152.4 mm). The upper edge of the opening shall be located not less than 6 inches ( 152.4 mm) below the lowest chimney inlet opening. The cleanout shall be provided with a tight - fitting, noncombustible cover of a minimum size of 8 inches by 8 inches ( 203.2 mm by 203.2 mm). 501.15.4 Clearances. Chimneys and vents shall have airspace clearance to combustibles in accordance with the New York City Building Code a nd the chimney or vent manufacturer’s instructions . Exception: Masonry chimneys without the required air - space clearances shall be permitted to be used if lined or relined with a chimney lining system listed for use in chimneys with reduced clearances in a ccordance with UL 1777 or ULC - S635 . The chimney clearance shall be not less than permitted by the terms of the chimney liner listing and the manufacturer’s instructions. 501.15.4.1 Fireblocking. Noncombustible fireblocking shall be provided in accordance w ith the New York City Building Code . 501.15.5 Testing. Testing of existing chimneys shall be in accordance with Section 1705.32 of the New York City Building Code . 501.16 Drains. A drain shall be provided for all chimneys and gas vents to remove rain water and condensation. The drain shall be not less than 1 inch ( 25.4 mm) in diameter and shall be equipped with an appropriately - sized p - trap with automatic trap seal primer in accor dance with Section 1002 of the New York City Plumbing Code or a float drain trap installed in accordance with the manufacturer’s requirements . The drain shall be sized by the design engineer and shall be suitable for the chimney area. For listed chimneys a nd gas vents, the connection tap into the chimney shall be determined by the manufacturer and connected to the drain piping in accor dance with the listing and instructions . On all outdoor chimneys and gas vents, the connection and drain shall be installed indoors as close as practicable to the chimney base to prevent freezing. 501.17 Outdoor chimneys and vents. Outdoor portions of chimneys or vents shall be provided with integral R - 8 insulation or be provided with an R - 8 insulation enclosure, where exposed to the outdoors for more than 5 feet (1524 mm). 501.17.1 Type B vents. Type B vents shall not be considered exposed to the outdoors in the following conditions: 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT 1. A type B vent of a listed chimney system passing through an unused masonry chimney provided with a sealed cap that prevents airflow within the confines of the masonry chimney; or 2. A type B vent passing through an unventilated enclosure or chase insulated to R - 8. SECTION FGC 502 VENTS 502.1 General. Vents , except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accord- ance with UL 441 and labeled or field fabricated in accordance with NFPA 211. Type L vents shall be tested in accordance with UL 641. Vents for Category II, III and IV appliances shall be tested in accordance with UL 1738. Plastic piping shall be listed and installed in accordance with the terms of its listing and the appliance manufacturer’s instructions. 502.2 Connectors required. Connectors sh all be used to connect appliances to the vertical chimney or vent, except where the chimney or vent is attached directly to the appliance. Vent connector size, material, construction and installation shall be in accor dance with Section 503. 502.3 Vent appl ication. The application of vents shall be in accordance with Table 503.4. 502.4 Insulation shield. Where vents pass through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the vent and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the vent manufacturer’s instructions . Where vents pass through attic space, the shield sh all terminate not less than 2 inches ( 50.8 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed vent system shall be installed in accordance w ith the manufacturer’s instru ctions . 502.5 Installation. Vent systems shall be sized, installed and terminated in accordance with the vent and appliance manufacturer’s instructions and Section 503. 502.6 Support of vents. All portions of vents shall be adequately supported for the des ign and weight of the materials employed. 502.7 Protection against physical damage. In concealed locations, where a vent is installed through holes or notches in studs, joists, rafters or similar members less than 1 1 / 2 inches ( 38 .1 mm) from the nearest edg e of the member, the vent shall be protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch ( 1.4 61 mm) (No. 16 gage) shall cover the area of the vent where the member is notched or bored and shall extend not less than 4 inches ( 101.6 mm) above sole plates, below top plates and to each side of a stud, joist or rafter. 502.7.1 Door swing. Appliance and equipment vent terminals shall be located such that doors cannot swing within 12 inches ( 304.8 mm) horizontally of the vent terminal. Door stops or closers shall not be installed to obtain this clearance. Means of protecting the clearance that are not easily overridden or removed may be used to obtain this clearance. SECTION FGC 503 VENTING OF APPL IANCES 503.1 General. The venting of appliances shall be in accordance with Sections 503.2 through 503.16. 503.2 Venting systems required. Except as permitted in Sections 503.2.1 through 503.2.4 and 501.8, all appliances shall be connected to venting syste ms. 503.2.1 Ventilating hoods. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications in accordance with Section 503.3.4 and to vent industrial appliances, such as where the process itsel f requires fume disposal. 503.2.2 Reserved. 503.2.3 Direct - vent appliances. Listed direct - vent appliances shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturer’s instructions and Section 503.8. 50 3.2.4 Appliances with integral vents. An appliance incorporating integral venting means shall be considered properly vented where installed in accordance with its listing , the manufacturer’s instructions and Section 503.8. 503.2.5 Incinerators. Commercial - industrial - type incinerators shall be vented in accordance with NFPA 82. 503.3 Design and construction. Venting systems shall be designed and constructed so as to convey all flue and vent gases to the outdoors. 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 503.3.1 Appliance draft requirements. A venting system shall satisfy the draft requirements of the appliance in accordance with the manufacturer’s instructions. 503.3.2 Design and construction. Appliances required to be vented shall be connected to a venting syste m designed and installed in accordance with the provisions of Sections 503.4 through 503.16. 503.3.3 Mechanical draft systems. Mechanical draft systems shall comply with the following: 1. Mechanical draft systems shall be listed and shall be installed in a ccordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer’s instructions . 2. Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced d raft design. 3. Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of flue or vent gases into a building. 4. Vent connectors serving appliances ve nted by natural draft shall not be connected to any portion of mechanical draft systems operating under positive pressure. 5. Where a mechanical draft system is employed, provisions shall be made to prevent the flow of gas to the main burners when the draf t system is not performing so as to satisfy the operating requirements of the appliance for safe performance. 6. The exit terminals of mechanical draft systems shall be not less than 7 feet ( 2133.6 mm) above finished ground level where located adjacent to public walkways and shall be located as specified in Section 503.8, Items 1 and 2. 503.3.4 Ventilating hoods and exhaust systems. Ventilating hoods and exhaust systems shall be permitted to be used to vent appli- ances installed in commercial applications. W here automatically operated appliances, other than commercial cooking appliances, are vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the appliance and when the power means of exhaust is in operation. 503.3.5 Air ducts and furnace plenums. Venting systems shall not extend into or pass through any fabricated air duct or furnace plenum. 503.3.6 Above - ceiling air - handling spaces. Where a venting system passes through an above - ceiling air - handling space or other nonducted portion of an air - handling system, such space shall be accessible for inspection. The venting system sha ll conform to one of the following requirements: 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appl iance or vent manufacturer’s instructions. 2. The venting system shall be installed such that fittings and joints between sections are not installed in the above - ceiling space. 3. The venting system shall be installed in a sealed metal conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. 503.4 Type of venting system to be used. The type of venting system to be used shall be in accordance with Table 503.4 . TABLE 503.4 TYPE OF VENTING SYSTEM TO BE USED GAS UTILIZATION EQUIPMENT TYPE OF VENTING SYSTEM Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Type B gas vent (Section 503.6) Chimney (Section 503.5) Single - wall metal pipe (Section 503.7) Listed chimney lining system for gas venting (Section 503.5.3) Listed vented wall furnaces Type B - W gas vent (Sections 503.6, 608) Category II equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category III equipment As specified or furnished by manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Category IV equipment As specified or furnished b y manufacturers of listed equipment (Sections 503.4.1, 503.4.2) Incinerators In accordance with NFPA 82 Equipment which may be converted to use of solid fuel Chimney (Section 503.5) Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 Unlisted combination gas - and oil - burning equipment Chimney (Section 503.5) Listed combination gas - and oil - burning equipment Type L vent (Section 503.6) or chimney (Section 503.5) Combination gas - and solid fuel - burning equipment Chimney (Section 503.5) Equipment listed for us e with chimneys only Chimney (Section 503.5) Unlisted equipment Chimney (Section 503.5) Decorative appliance in vented fireplace Chimney Direct vent equipment See Section 503.2.3 Appliances with integral vent See Section 503.2.4 503.4.1 Plastic piping. Plastic piping used for venting appliances listed for use with such venting materials shall be listed and installed in accordance with the terms of its listing and the manufacturers’ instructions. Installation shall be in accordance with the New York City Building Code . PVC shall not be permitted. 503.4.1.1 Plastic vent joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer’s instructions. Where a primer is required, it shall be of a contrasting color. 503.4.2 Special gas vent. Special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers’ instructions. 503.4.2.1 Inspection of special gas ve nts. Before replacing an existing appliance or connecting a vent connector to a special gas vent, the special gas vent shall be examined to ascertain that it is clear and free of obstructions. 503.4.2.2 Unsafe special gas vents. Where inspection reveals th at an existing special gas vent is not safe for the intended appli- cation, it shall be repaired or replaced. 503.4.2.3 Test run. All special gas vents shall be test run by the registered design professional or special inspector responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products o f combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional or special inspector responsible for the test and shall be submitted in writing to the department. 503.4.2.4 Requirement of a smoke test. A smoke test shall be conducted in accordance with Section 503.4.2.5. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a representative of the commissioner. In the alternativ e, the commissioner may accept a test report instead of requiring that it be witnessed by a representative of the commissioner. Such test report of the registered design professional or special inspector responsible for the test which shall be submitted in writin g to the department. 503.4.2.5 Smoke test. To determine the tightness of vent constru ction, a smoke test shall be conducted in accordance with the following conditions and requirements: 1. The equipment, materials, power and labor necessary for such test shall be furnished by, and at the expense of, either the owner or holder of the work p ermit. 2. If the test shows any evidence of leakage or other defects, such leakage or other defects shall be corrected in accordance with the requirements of this chapter, and the test shall be repeated until the results are satisfactory. 3. The vent shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the special gas vent shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the special gas vent. 4. Testing and inspection of existing and new negative pres sure chimneys and vents shall be in accordance with Section 1705.32 of the New York City Building Code . 503.5 Masonry, metal, and factory - built chimneys. Masonry, metal and factory - built chimneys shall comply with Sections 503.5.1 through 503.5.10. 503.5.1 Factory - built chimneys. Factory - built chimneys shall be installed in accordance with their listing and the manufac- turer’s instructions. Factory - built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such applicat ion. 503.5.2 Metal chimneys. Metal chimneys shall be built and installed in accordance with NFPA 211. 503.5.3 Masonry chimneys. Masonry chimneys shall be built and installed in accordance with Chapter 21 of the New York City Building Code and NFPA 211 and shall be lined with approved clay flue lining, a listed chimney lining system or other approved material that will resist corro sion, erosion, softening or cracking from vent gases at temperatures up to 1,800°F ( 982 .2 °C). Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max MaxConnected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H Exception: Masonry chimney flues serving listed gas appliances with draft hoods, Category I appliances and other gas ap- pliances listed for use with Type B vents s hall be permitted to be lined with a chimney lining system specifically listed for use only with such appliances. The liner shall be installed in accordance with the liner manufacturer’s instructions and the terms of the listing. A permanent identifying la bel shall be attached at the point where the connection is to be made to the liner. The label shall read: “This chimney liner is for appliances that burn gas only. Do not connect to solid or liquid fuel - burning appliances or incinerators.” For installation of gas vents in existing masonry chimneys, see Section 503.6.3. ‡‡‡ 503.5.4 Chimney termination. Chimneys serving gas - fired equipment shall comply with the appliance listing, the manufac- turer’s instructions , Figure 503.5.4 and the following requirements: 1. Chimneys , vents and flues serving appliances or fireplaces with outlet temperatures less than 600°F ( 315.6 °C) shall extend not less than 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse within 10 feet (3048 mm) of the chimney, vent or flue outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys, vents or flues located beyond 10 feet (3048 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 2. Chimneys serving appliances or fireplac es with outlet temperatures between 600°F ( 315.6 °C) and 1000°F ( 537.8 °C) shall extend not less than 10 feet (3048 mm) above the highest construction, such as a roof ridge, or parapet wall or penthouse within 20 feet (6096 mm) of the chimney outlet, whether the construction is on the same building as the chimney or on another building. However, such constructions do not include other chimneys, and vents or open structural framing. Any chimneys located beyond 20 feet (6096 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 3. Chimneys serving appliances or fireplaces with outlet temperatures greater than 1000°F ( 537.8 °C) shall extend not less than 20 feet (6096 mm) above the highest construction, such as roof ridge, parapet wall, penthouse, or other obstruction within 50 feet (15 240 mm) of the chimney outlet, whether the construction is on the same building as the chimney or in another buildin g. However, such constructions do not include other chimneys, vents, or open structural framing. Any chimneys located beyond 50 feet (15 240 mm) from such construction, but not more than the distance determined by Equation 5 - 1, shall be at least as high as the construction. 4. Termination caps shall not be permitted. A drain shall be installed in accordance with Section 801.22 of the New York City Mechanical Code . A positive means shall be provided to prevent water from entering the appliance. Exception: Termination caps shall b e permitted on listed factory - built chimneys unless otherwise prohibited by the New York City Air Pollution Control Code . 5. Decorative shrouds shall not be installed at the termination of factory - built chimneys except where such shrouds are listed and lab eled for use with the specific factory - built chimney system and are installed in accordance with the manufacturers’ instruc- tions . 6. The following equation shall be used for determining the distances referred to in Items 1, 2 and 3 of this section. D = F × √ A (Equation 5 - 1) where: D = Distance, in feet, measured from the center of the chimney , vent or flue outlet to the nearest edge of the construction. If a single chimney is divided into multiple smaller flues or chimneys, measure from the center of the chimney outlet that is closest to the nearest edge of the construction. F = Value determined from table below. A = Free area, in square inches, of chimney flue space outlet. If a single chimney is divided into multiple smaller flues or chimneys, the total aggregate free area of such flue and chimney outlets shall be used to calculate “A”. “F” FACTOR FOR DETERMINING CHIMNEY DISTANCES Type of Fuel “F” Factor 600°F ( 315.6 °C) and less 600°F ( 315.6 °C) to 1000°F ( 537.8 °C) Greater than 1000°F ( 537.8 °C) Gas 2 2 3 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.5.4 TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE - WALL METAL PIPES SERVING RESIDENTIAL - TYPE AND LOW - HEAT APPLIANCES 503.5.5 Size of chimneys. The effective area of a chimney venting system serving listed appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be determined in accordance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent con- nector and chimney flue shall be not less than the area of the appliance flue collar or draft hood ou tlet, nor greater than seven times the draft hood outlet area. 3. For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shal l be not less than the area of the larger draft hood outlet plu s 50 percent of the area of the smaller draft hood outlet, nor greater than seven times the smallest draft hood outlet area. 4. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 5. Other approved engineering methods. 503.5.6 Inspection of chimneys. Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and it shall be cleane d if previously used for venting solid or liquid fuel - burning appliances or fireplaces. 503.5.6.1 Chimney lining. Chimneys shall be lined in accordance with NFPA 211. Exception: Where an existing chimney complies with Sections 503.5.6 through 503.5.6.5 and its sizing is in accordance with Section 503.5.5, its continued use shall be allowed where the appliance vented by such chimney is replaced by an appliance of similar type, input rating and efficiency. 503.5.6.2 Cleanouts. Cleanouts shall be examined to d etermine if they will remain tightly closed when not in use. 503.5.6.3 Unsafe chimneys. Where inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined or replaced with a vent or chi mney to conform to NFPA 211 and it shall be suitable for the appliances to be vented. ‡‡‡ 503.5.6.4 Test run. All new chimneys shall be test run by the registered design professional responsible for the testing under operating conditions to demonstrate fire safety and the complete exhausting of smoke and the products of combustion to the outer air. The results of such test run shall be certified as correct by the registered design professional responsible f or the test and shall be submitted in writing to the department. Exception: A test run in accordance with this section may be conducted and certified to the department by the permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. The test run shall not require a registered design professional or special inspector. ‡‡‡ 503.5.6.5 Requirement of a smoke test. A smoke test shall be made as outlined below. Any faults or leaks found shall be corrected. Such smoke test shall be witnessed by a repre sentative of the commissioner. In lieu thereof, the commissioner may accept the test report of the registered design professional or special inspector responsible for the test that shall be submitted in writing to the department. Exception: A smoke test ma y be performed by or under the supervision of a permit - holder when the work is performed as part of a limited alteration application, as defined in Section 28 - 101.5 of the Administrative Code. Such test shall not be required to be witnessed by the depart ment, registered design professional, or special inspector. 503.5.6.5.1 Smoke test. To determine the tightness of chimney construction, a smoke test shall be made in accordance with the following conditions and requirements: 1. The equipment, materials, po wer and labor necessary for such test shall be furnished by, and at the expense of, the owner or holder of the work permit. 2. If the test shows any evidence of leakage or other defects, such defects shall be corrected in accordance with the require- ment of this chapter and the test shall be repeated until the results are satisfactory. 3. Method of test. The chimney shall be filled with a thick penetrating smoke produced by one or more smoke machines, or smoke bombs, or other equivalent method. As the smoke appears at the stack opening on the roof, such opening shall be tightly closed and a pressure equivalent to 1 / 2 inch (12.7 mm) column of water measured at the base of the stack, shall be applied. The test shall be applied for a length of time sufficient to permit the inspection of the chimney. 503.5.7 Chimneys serving appliances burning other fuels. Chimneys serving app liances burning other fuels shall comply with Sections 503.5.7.1 through 503.5.7.4. 503.5.7.1 Solid fuel - burning appliances. An appliance shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 503.5.7.2 Liquid fu el - burning appliances. Where one chimney flue serves gas appliances and liquid fuel - burning appliances, the appliances shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the appliances are automatically controlled, they shall be equipped with safet y shutoff devices. 503.5.7.3 Combinati on gas - and solid fuel - burning appliances. A combination gas - and solid fuel - burning appliance shall be permitted to be connected to a single chimney flue where equipped with a manual reset device to shut off gas to the main burn er in the event of sustained back draft or flue gas spillage. The chi mney flue shall be sized to properly vent the appliance. 503.5.7.4 Combination gas - and oil fuel - burning appliances. A listed combination gas - and oil fuel - burning appliance shall be permitted to be connected to a single chimney flue. The chimney flue shal l be sized to properly vent the appliance. 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/HGAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650T FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650T FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 503.5.8 Support of chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Factory - built chimneys shall be supported and spaced in accordance with their listings and the manufacturer’s instructions. 503.5.9 Cleanouts. Where a chimney that formerly carried flue products from liquid or solid fuel - burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight - fitting cover and shall be installed at the base of all chimneys in accordance with the rules of the New York City Department of Environmental Protection . The cleanout shall be gas tight if the chimney is to be of positive pressure. 503.5.10 S pace surrounding lining or vent. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. The insertion of another liner or vent withi n the chimney as provided in this code and the liner or vent manufacturer’s instructions shall not be prohibited. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry, metal or factory - bui lt chimney, shall not be used to supply combustion air. Such space shall not be prohibited from supplying combustion air to direct - vent appliances designed for installation in a solid fuel - burning fireplace and installed in accordance with the listing and the manufacturer’s instructions. 503.6 Gas vents. Gas vents shall comply with Sections 503.6.1 through 503.6.13 (see Section 202, Definitions). 503.6.1 Installation, general. Gas vents shall be installed in accordance with the terms of their listings and manufacturer’s instruc- tions. 503.6.2 Type B - W vent capacity. A Type B - W gas vent shall have a listed capacity not less than that of the listed vented wall furnace to which it is connected. 503.6.3 Gas vents installed within masonry chimneys. Gas vents installed within masonry chimneys shall be installed in accordance with the terms of their listing and the manufacturer’s instructions . Gas vents installed within masonry chimneys shall be identified with a permanent label installed at the point where the vent enters the chimney. The label shall contain the following langua ge: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.4 Gas vent terminations. A gas vent shall terminate in accordance with one of the following: 1. Gas vents that are 12 inches ( 304.8 mm) or less in size and located not less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obs truction shall terminate above the roof in accordance with Figure 503.6.4 . 2. Gas vents that are over 12 inches ( 304.8 mm) in size or are located less than 8 feet ( 2438 .4 mm) from a vertical wall or similar obstruction shall terminate not less than 2 feet ( 60 9.6 mm) above the highest point where they pass through the roof and not less than 2 feet ( 60 9.6 mm) above any portion of a building within 10 feet (3048 mm) horizontally. 3. As provided for direct - vent systems in Section 503.2.3 . 4. As provided for app liances with integral vents in Section 503.2.4 . 5. As provided for mechanical draft systems in Section 503.3.3. 6. As provided for ventilating hoods and exhaust systems in Section 503.3.4. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by the following formula: D = 2 √ A (Equation 5 - 2) where: D = Distance, in feet, measured from the center of the vent outlet to the nearest edge of the construction. A = Free area, in square inches, of vent flue space. 503.6.4.1 Decorative shrouds. Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with the manufacturer’s instructions . All gas vents shall terminate in an approved vent or cowl, which shall prevent downdrafts and prevent rain and debris from entering the vent. 503.6.5 Minimum height. A Type B or L gas vent shall terminate not less than 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood or flue collar. A Type B - W gas vent shall terminate not less than 12 feet ( 3657.6 mm) in vertical height above the bottom of the wall furnace. 503.6.6 Roof terminations. Gas vents shall extend through the roof flashing, roof jack or ro of thimble and terminate with a listed cap or listed roof assembly. 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 503.6.7 Forced air inlets. Gas vents shall terminate not less than 3 feet ( 914 .4 mm) above any forced air inlet located within 10 feet (3048 mm). 503.6.8 Exterior wall penetrations. A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 503.2. 4 and 503.3.3. ROOF PITCH H (min) ft Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0 Over 12/12 to 14/12 5.0 Over 14/12 to 16/12 6.0 Over 16/12 to 18/12 7.0 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. FIGURE 503.6.4 TERMINATION LOCATIONS FOR GAS VENTS WITH LISTED CAPS 12 INCHES OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 503.6.9 Size of gas vents. Venting systems shall be sized and constructed in accordance with Section 504 or other approved engi- neering methods acceptable to the commissioner. Gas vents shall also comply with the manufacturers’ instructions. 503.6.9.1 Category I appliances. The sizing of natural draft venting systems serving one or more listed appliances equippe d with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accord ance with one of the following methods: 1. The provisions of Section 504. 2. For sizing an individual gas vent for a single, draft - hood - equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet, nor greater than seven times the draft hood outlet area. 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 3. For sizing a gas vent connected to two appliances with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, nor greater than seven tim es the smaller draft hood outlet area. 4. E ngineering practices acceptable to the commissioner . 503.6.9.2 Vent offsets. Type B and L vents sized in accordance with Item 2 or 3 of Section 503.6.9.1 shall extend in a generally vertical direction with offsets not exceeding 45 degrees (0.79 rad), excep t that a vent system having not more than one 60 - degree (1.04 rad) offset shall be permitted. Any angle greater than 45 degrees (0.79 rad) from the vertical is considered horizontal . The total horizontal distance of a vent plus the horizontal vent connecto r serving draft - hood - equipped appliances shall be not greater than 75 percent of the vertical height of the vent. 503.6.9.3 Category II, III, and IV appliances. The sizing of gas vents or plastic pipe specified by the appliance manufacturer for Category II , III, and IV appliances shall be in accordance with the appliance manufacturer’s instructions. 503.6.9.4 Mechanical draft. Chimney venting systems using mechanical draft shall be designed and sized to develop a positive flow adequate to carry all products of combustion to the outside atmosphere . 503.6.10 Multistory prohibited. Common venting systems for appliances located on more than one floor level shall be prohibited. 503.6.11 Support of gas vents. Gas vents shall be supported and spaced in accordance w ith their listings and the manufacturer’s instructions. 503.6.12 Marking. Gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: “This gas vent is for appliances that burn gas. Do not connect to solid or liquid fuel - burning appliances or incinerators.” 503.6.13 Fastener penetrations. Screws, rivets and other fasteners shall not penetrate the inner wall of double - wall gas vents, except at the transiti on from an appliance draft hood outlet, a flue collar or a single - wall metal connector to a double - wall vent. 503.7 Single - wall metal pipe. Single - wall metal pipe vents shall comply with Sections 503.7.1 through 503.7.13. 503.7.1 Construction. Single - wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch ( 0. 77 mm) thick , or other approved, noncombustible, corrosion - resistant material. 503.7.2 Climate protection. Uninsulated single - wall metal pipe shall not be used outdoors for venting appliances. 503.7.3 Termination. Single - wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar. Single - wall metal pipe shall extend not less than 2 feet ( 609.6 mm) above the highest point where it passes through a roof of a building and not less than 2 feet ( 609.6 mm) higher than any portion of a building within a horizontal distance of 10 fe et (3048 mm) ( see Figure 503.5.4 ). An approved cap or roof assembly shall be attached to the terminus of a single - wall metal pipe (see also Section 503.7.9, Item 3). However, such constructions do not include chimneys or other vents, or open structural fra ming. The single - wall metal pipe shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. 503.7.4 Limitations of use. Single - wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outdoor atmosphere. 503.7.5 Roof penetrations. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jack, or roof thimble. Where a single - wall metal pipe passes through a roof constructed of combustible material, a noncombustible, non - ventilating thimble shall be used at the point of passage. The thimble shall extend not less than 18 inches ( 457 .2 mm) a bove and 6 inches ( 152 .4 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 503.7.7. 503.7.6 Installation. Single - wall metal pipe shall not originate in any unoccup ied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. The installation of a single - wall metal pipe through an exterior combustible wall shall comply with Section 503.7.7. 503.7.7 Single - wall penetrations of combustible walls. A single - wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: 1. For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be not less than 4 inches ( 101.6 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet ( 1828.8 mm) of metal pipe in the open between the draft hood outlet and the t himble, the thimble shall be permitted to be not less than 2 inches ( 50.8 mm) larger in diameter than the metal pipe. 2. For unlisted appliances having draft hoods, the thimble shall be not less than 6 inches ( 152.4 mm) larger in diameter than the metal pi pe. 3. For residential and low - heat appliances, the thimble shall be not less than 12 inches ( 304.8 mm) larger in diameter than the metal pipe. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a sufficient distance from the metal pipe to provide the specified clearance from such metal pipe to combustible material. Any material used to close up such open ing shal l be noncombustible. 503.7.8 Clearances. Minimum clearances from single - wall metal pipe to combustible material shall be in accordance with Table 503.10.5. The clearance from single - wall metal pipe to combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 308.2. 503.7.9 Size of single - wall metal pipe. A venting system constructed of single - wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions: 1. For a draft - hood - equipped applia nce, in accordance with Section 504. 2. For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall be not less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall be not greater than seven times the draft hood outlet area. 3. Other approved engineering methods. 503.7.10 Pipe geometry. Any shaped single - wall metal pipe shall be permitted to be used, provided that its equivalent effective area is equa l to the effective area of the round pipe for which it is substituted, and provided that the minimum internal dimension of th e pipe is not less than 2 inches ( 50.8 mm). 503.7.11 Termination capacity. The vent cap or a roof assembly shall have a venting cap acity of not less than that of the pipe to which it is attached. 503.7.12 Support of single - wall metal pipe. All portions of single - wall metal pipe shall be supported for the design and weight of the material employed. 503.7.13 Marking. Single - wall metal p ipe shall comply with the marking provisions of Section 503.6.12. ‡‡‡ 503.8 Venting system termination location. The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet ( 914 .4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not includ e chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5 - 2. Exception: Horizontally terminate d direct - vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer’s instructions and Section 503.8, Item 3. 2. Where permitted, through - the - wall vents for Category I, II , III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment. 3. Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer’s instructions. In addition, hori- zontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet ( 2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 fee t ( 914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm ). 3.3. The vent system shall terminate at least 4 feet ( 1219.2 mm) below, 4 feet ( 1219.2 mm) ho rizontally from or 1 foot ( 304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet ( 914.4 mm) to an interior corner formed by two walls perpendicular to each other . 3. 5. The vent termination shall not be mounted directly above or within 3 feet ( 914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches ( 914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner . 3.8. The maximum heat input of a ll appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h ( 102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer’s listing and instructions . 503.9 Condensation drainage. Provisions shall be made to collect and dispose of condensate from venting systems serving Category II and IV appliances and noncategorized condensing appliances in accordance with Section 307 . 503.10 Vent connectors for Category I appliances. Vent connectors for Category I appliances shall comply with Sections 503.10.1 throu gh 503.10.14 . 503.10.1 Where required. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single - wall metal pipe, except where the gas vent, chimney, or single - wall metal pipe is directly connected to the appliance. 503.10.2 Materials. Vent connectors shall be constructed in accordance with Sections 503.10.2.1 through 503.10.2. 3 ‡ . 503.10.2.1 General. A vent connector shall be made of noncombustible corrosion - resistant material capable of withstanding the vent gas temperature produced by the appliance and of sufficient thickness to withstand physical damage. 503.10.2.2 Vent connectors located in uncond itioned areas. Where the vent connector used for an appliance having a draft hood or a Category I appliance is located in or passes through attics, crawl spaces or other unconditioned spaces, that portion of the vent connector shall be listed Type B, Type L or listed vent material having equivalent insulation properties. * 503.10.2.3 Vent connector installation. Vent connectors shall be installed in accordance with one of the following: 1. Connectors with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible con- struction shall be installed in accordance with the terms of their listing, the manufacturer’s instructions and Section 803.10.4 of the Ne w York City Mechanical Code. 2. Connectors of appliances with flue gas temperatures less than 500°F (260°C) that pass through walls or partitions of combustible construction shall be insulated with a field - applied wrap assembly in accordance with Section 8 03.10.4.2 of the New York City Mechanical Code. 3. Residential - type appliance connectors installed in accordance with Section 503.10.2.3.1. 4. Low - heat appliance connectors installed in accordance with Section 503.10.2.3.2. 5. Medium - heat appliance connect ors installed in accordance with Section 503.10.2.3.3. *Section 503.10.2.3 was added by Local Law 77 of 2023 . This law has an effective date of June 10, 2023. ‡‡‡ 503.10.2.3 .1 Residential - type appliance connectors. Where vent connectors for residential - type appliances are not in- stalled in attics or other unconditioned spaces, connectors for listed appliances having draft hoods, appliances having draft hoods and equipped with listed conversion burners and Category I appliances shall be one of the following: 1. Type B or Type L vent material. 2. Galvanized sheet steel not less than 0.018 inch (0.46 mm) thick. 3. Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 inch (0.69 mm) thick. 4. Stainless steel sheet not less than 0.012 inch (0.31 mm) thick. 5. Smooth interior wall metal pipe having resistance to heat and corrosion equal to or greater than that of Item 2, 3 or 4. 6. A list ed vent connector. Vent connectors shall not be covered with insulation. ‡‡‡ 503.10.2. 3.2 Low - heat appliances . A vent connector for low - heat appliance s shall be a factory - built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Tab le 503.10.2. 3.2 ‡ . Factory - built chimney sections shall be joined together in accordance with the chimney manufa cturer’s in- structions. TABLE 503.10.2. 3.2 ‡ MINIMUM THICKNESS FOR GALVANIZED STEEL VENT CONNECTORS FOR LOW - HEAT APPLIANCES DIAMETER OF CONNECTOR (inches) MINIMUM THICKNESS (inch) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 43722 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 43722 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 For SI: 1 inch = 25.4 mm. ‡‡‡ 503.10.2. 3.3 Medium - heat appliances. Vent connectors for medium - heat appliances shall be constructed of factory - built medium - heat chimney sections or steel of a thickness not less than that specified in Table 503.10.2. 3.3 ‡ and shall comply with the following: 1. A steel vent connector for an appliance with a vent gas temperature in excess of 1000 °F ( 537.8 °C) measured at the entrance to the connector shall be lined with medium - duty fire brick (ASTM C 64, Type F), or the equivalent. 2. The lining shall be not less than 2 1 / 2 inches ( 63.5 mm ) thick for a vent connector having a diameter or greatest cross - sectional dimensi on of 18 inches ( 457 .2 mm) or less . 3. The lining shall be not less than 4 1 / 2 inches ( 114.3 mm ) thick laid on the 4 1 / 2 - inch ( 114 .3 mm) bed for a vent connector having a diameter or greatest cross - sectional dimension greater than 18 inches ( 457 .2 mm ). 4. Factory - built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer’s instructions . TA BLE 503.10.2. 3.3 ‡ MINIMUM THICKNESS FOR STEEL VENT CONNECTORS FOR MEDIUM - HEAT APPLIANCES VENT CONNECTOR SIZE DIAMETER (inches) AREA (square inches) MINIMUM THICKNESS (inch) Up to 14 Up to 154 0.053 Over 14 to 16 154 to 201 0.067 Over 16 to 18 201 to 254 0.093 Over 18 Larger than 254 0.123 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 . 503.10.3 Size of vent connector. Vent connectors shall be sized in accordance with Sections 503.10.3.1 through 503.10.3.5. 503.10.3.1 Single draft hood and fan - assisted. A vent connector for an appliance with a single draft hood or for a Category I fan - assisted combustion system appliance shall be sized and installed in accordance with Section 504 or other approved engineer- ing methods. 503.10.3.2 Multiple draft hoods. For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum 1 - foot ( 304.8 mm) rise. 503.10.3.3 Multiple appliances. Where two or more appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 504 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 503.10.3.4 Common connector/manifold. Where two or more appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highe st level consistent with available headroom and the required clearance to combustible materials and shall be sized in accordance with Section 504 or other approved engin eer- ing methods. As an alternate method applicable only where there are two draft hood -e quipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 5 0 percent of the area of the smaller flue collar outlet. 503.10.3.5 Size incre ase . Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the appliance input, the size increase shall be made at the appliance draft hood outlet. 503.10.4 Two or more appliances connec ted to a single vent or chimney. Where two or more vent connectors enter a common gas vent, chimney flue or single - wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible ma terial. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or IV appliances. 503.10.4.1 Two or more openings . Where t wo or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the verti cal in accordance with Figure 503.10.4.1 . FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 FIGURE 503.10.4.1 OPPOSING OPENINGS IN CHIMNEY 503.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 503.10.5 . Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the com- bustible material is prote cted as specified for vent connectors in Table 308.2. TABLE 503.10.5 a CLEARANCES FOR CONNECTORS APPLIANCE MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL Listed Type B gas vent material Listed Type L vent material Single - wall metal pipe Factory - built chimney sections Listed appliances with draft hoods and appliances listed for use with Type B gas vents As listed As listed 6 inches As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 inches 6 inches 9 inches As listed Residential appliances listed for use with Type L vents Not permitted As listed 9 inches As listed Listed gas - fired toilets Not permitted As listed As listed As listed Unlisted residential appliances with draft hood Not permitted 6 inches 9 inches As listed Residential and low - heat appliances other than above Not permitted 9 inches 18 inches As listed Medium - heat appliances Not permitted Not permitted 36 inches As listed For SI: 1 inch = 25.4 mm. a. These clearances shall apply unless the manufacturer’s installation instructions for a listed appliance or connector specify differ ent clearances, in which case the listed clearances shall apply. 503.10.6 Joints. Joints between sections of connector and connections to flue collars and draft hood outlets shall be tight - fitting and fastened by one of the following methods 1. Galvanized steel – Overlapping joint with sheet metal screws or rivets at a minimum of 4 locations for diameters not greater than 12 inches (304.8mm) and 8 locations for diameters greater than 12 inches (304.8 mm). 2. Carbon steel – Overlapping joint with 1 / 2 inch (12.7 mm) tack welds at a minimum of 4 locations for diameters up to 12 inches (304.8 mm) and 8 locations for diameters larg er than 12 inches (304.8 mm). 3. Carbon steel – continuous butt welded perimeter. 4. Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in accordance with the manufacturer’s instructions. 503.10.7 Slope. A vent connector shall be installed without dips or sags and shall slope upward toward the vent or chimney not less than 1 / 4 inch per foot (21 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers’ instructions. 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 503.10.8 Length of vent connector. The maximum horizontal length of a single - wall connector shall be 75 percent of the height of the chimne y or vent except for engineered systems. The maximum horizontal length of a Type B double - wall connector shall be 100 percent of the height of the chimney or vent except for engineered systems. 503.10.9 Support. A vent connector shall be supported in accor dance with the manufacturer’s recommendations for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints. 503.10.10 Chimney connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the conne ctor shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue (see Section 501.9). 503.10.11 Inspection. The entire length of a vent connector shall be provided with ready access for inspection, cleaning and replace- ment. 503.10.12 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace. 503.10.13 Passage through ceilings, floors or walls. Single - wall m etal pipe connectors shall not pass through any wall, floor or ceiling except as permitted by Section 503.7.4. 503.10.14 Medium - heat connectors. Vent connectors for medium - heat appliances shall not pass through walls or partitions con- structed of combustibl e material. 503.11 Vent connectors for Category II, III, and IV appliances. Vent connectors for Category II, III , and IV appliances shall be as specified for the venting systems in accordance with Section 503.4. 503.12 Draft hoods and draft controls. The i nstallation of draft hoods and draft controls shall comply with Sections 503.12.1 through 503.12.7. 503.12.1 Appliances requiring draft hoods. Vented appliances shall be installed with draft hoods. Exception: Direct - vent appliances, fan - assisted combustion system appliances, appliances requiring chimney draft for operation, appliances equipped with blast, power, or pressure burners that are not listed for use with draft hoods , and appliances designed for forced venting. 503.12.2 Installation. A draft hood s upplied with or forming a part of a listed vented appliance shall be installed without alteration, exactly as furnished and specified by the appliance manufacturer. 503.12.2.1 Draft hood required. If a draft hood is not supplied by the appliance manufactur er where one is required, a draft hood shall be installed, shall be of a listed or approved type and, in the absence of other instructions, shall be of the same siz e as the appliance flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. 503.12.2.2 Special design draft hood. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the appliance manufacturer and s hall be approved by the department . 503.1 2.3 Draft control devices. Where a draft control device is part of the appliance or is supplied by the appliance manufacturer, it shall be installed in accordance with the manufacturer’s instructions. In the absence of manufacturer’s instructions, the dev i ce shall be attached to the flue collar of the appliance or as near to the appliance as practical. 503.12.4 Additional devices. Appliances requiring a controlled chimney draft shall be permitted to be equipped with a listed double - acting barometric - draft r egulator installed and adjusted in accordance with the manufacturers’ instructions. 503.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any differe nce in pressure between the hood or regulator and the combustion air supply. 503.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and sha ll be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checkin g vent operation. 503.12.7 Clearance. A draft hood shall be located so its relief opening is not less than 6 inches ( 152.4 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser cleara nce is indicated on the appliance label, the clearance shall be not less than that specified on the label. Such clearances shall not be reduced. 503.12.8 Thermal safety (spill) switches. Thermal safety (spill) switches shall be installed on barometric - draft regulators and all other appurtenances that allow dilution air into chimneys or vents. Thermal safety (spill) switches shall be interlocked with all of the appliances connected to the same chimney or gas vent. 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets 503.13 Manually operated dampers. A manually operated damper sha ll not be placed in the vent connector for any appliance. Fixed baffles shall not be classified as manually operated dampers. 503.14 Automatically operated vent dampers. An automatically operated vent damper shall be of a listed type complete with safety c ontrols to prove open position of the damper and/or appropriate draft before appliance operation. The automatically operated dampers shall be installed in accordance with the manufacturer’s instructions. An automatic vent damper device shall not be install ed on an existing appliance unless the appliance is listed and labeled and the device is installed in accordance with the terms of its listing. The name of the installer and date of installation shall be marked on a label affixed to the damper device. 503. 15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney or vent. The following shall not be considered as obstructions: 1. Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the terms of their listing and manufacturer’s instructions . 2. Approved draft regulators and safety controls that are designed and installed in accordance with approved engineering methods . 3. Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing and manu- facturer’s instructions. 4. Approved economizers, heat reclaimers and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided that the appliance manufacturer’s instructions cover the installation of such a device in the vent ing system and performance in accordance with Sections 503.3 and 503.3.1 is obtained. 5. Vent dampers serv ing listed appliances installed in accordance with Sections 504.2.1 and 504.3.1 or other approved engineering methods. 503.16 Outside wall penetrations. Where vents, including those for direct - vent appliances, penetrate outside walls of buildings, the annu lar spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion produ cts into the building. SECTION FGC 504 SIZING OF CATEGORY I APPLIANCE VENTING SYSTEMS 504.1 Definitions. The following definitions apply to the tables in this section. APPLIANCE CATEGORIZED VENT DIAMETER/AREA. The minimum vent area/diameter permissible for Category I appliances to maintain a non - positive vent static pressure when tested in accordance with nationally recognized standar ds. FAN - ASSISTED COMBUSTION SYSTEM. An appliance equipped with an integral mechanical means to either draw or force prod- ucts of combustion through the combustion chamber or heat exchanger. FAN Min. The minimum input rating of a Category I fan - assisted appl iance attached to a vent or connector. FAN Max. The maximum input rating of a Category I fan - assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft - hood - equipped appliance attached to a vent or connector. FAN + FAN. The maximum combined appliance input rating of two or more Category I fan - assisted appliances attached to the common vent. FAN + NAT. The maximum combined appliance input rating of one or more Category I fan - assisted appliances and on e or more Category I draft - hood - equipped appliances attached to the common vent. NA. Vent configuration is not allowed due to potential for condensate formation or pressurization of the venting system, or not a pplicable due to physical or geometric restrai nts. NAT + NAT. The maximum combined appliance input rating of two or more Category I draft - hood - equipped appliances attached to the common vent. 504.2 Application of single - appliance vent Tables 504.2(1) through 504.2(6). The application of Tables 504.2(1 ) through 504.2(6) shall be subject to the requirements of Sections 504.2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 .2.1 through 504.2.17 . 504.2.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The ins tallation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent system shall be determined using the “NAT Max” col umn. 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 .5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 2. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance, using the “FAN Min” column to determine the minimum capacity of the vent system. Where the corresponding “FAN Min” is “NA,” the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.2.2 Minimum size. Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the smaller size shall be permitted to be used pr ovided that all of the following requirements are met: 1. The total vent height (H) is not less than 10 feet (3048 mm). 2. Vents for appliance draft hood outlets or flue collars 12 inches ( 304.8 mm) in diameter or smaller are not reduced more than one tabl e size. 3. Vents for appliance draft hood outlets or flue collars larger than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes. 4. The maximum capacity listed in the tables for a fan - assisted appliance is reduced by 10 percent (0. 90 × maximum table capac- ity). 5. The draft hood outlet is greater than 4 inches ( 101.6 mm) in diameter. Do not connect a 3 - inch - diameter ( 76 .2 mm) vent to a 4 - inch - diameter ( 101.6 mm) draft hood outlet. This provision shall not apply to fan - assisted applia nces. TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 TABLE 504.2(1) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 78 46 0 152 86 0 251 141 0 375 205 0 524 285 0 698 370 0 897 470 2 13 51 36 18 97 67 27 157 105 32 232 157 44 321 217 53 425 285 63 543 370 4 21 49 34 30 94 64 39 153 103 50 227 153 66 316 211 79 419 279 93 536 362 6 25 46 32 36 91 61 47 149 100 59 223 149 78 310 205 93 413 273 110 530 354 8 0 0 84 50 0 165 94 0 276 155 0 415 235 0 583 320 0 780 415 0 1,006 537 2 12 57 40 16 109 75 25 178 120 28 263 180 42 365 247 50 483 322 60 619 418 5 23 53 38 32 103 71 42 171 115 53 255 173 70 356 237 83 473 313 99 607 407 8 28 49 35 39 98 66 51 164 109 64 247 165 84 347 227 99 463 303 117 596 396 10 0 0 88 53 0 175 100 0 295 166 0 447 255 0 631 345 0 847 450 0 1,096 585 2 12 61 42 17 118 81 23 194 129 26 289 195 40 402 273 48 533 355 57 684 457 5 23 57 40 32 113 77 41 187 124 52 280 188 68 392 263 81 522 346 95 671 446 10 30 51 36 41 104 70 54 176 115 67 267 175 88 376 245 104 504 330 122 651 427 15 0 0 94 58 0 191 112 0 327 187 0 502 285 0 716 390 0 970 525 0 1,263 682 2 11 69 48 15 136 93 20 226 150 22 339 225 38 475 316 45 633 414 53 815 544 5 22 65 45 30 130 87 39 219 142 49 330 217 64 463 300 76 620 403 90 800 529 10 29 59 41 40 121 82 51 206 135 64 315 208 84 445 288 99 600 386 116 777 507 15 35 53 37 48 112 76 61 195 128 76 301 198 98 429 275 115 580 373 134 755 491 20 0 0 97 61 0 202 119 0 349 202 0 540 307 0 776 430 0 1,057 575 0 1,384 752 2 10 75 51 14 149 100 18 250 166 20 377 249 33 531 346 41 711 470 50 917 612 5 21 71 48 29 143 96 38 242 160 47 367 241 62 519 337 73 697 460 86 902 599 10 28 64 44 38 133 89 50 229 150 62 351 228 81 499 321 95 675 443 112 877 576 15 34 58 40 46 124 84 59 217 142 73 337 217 94 481 308 111 654 427 129 853 557 20 48 52 35 55 116 78 69 206 134 84 322 206 107 464 295 125 634 410 145 830 537 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGHT (H) (feet) LATERAL (L) (feet) VENT DIAMETER — (D) inches 3 4 5 6 7 8 9 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 100 64 0 213 128 0 374 220 0 587 336 0 853 475 0 1,173 650 0 1,548 855 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 9 81 56 13 166 112 14 283 185 18 432 280 27 613 394 33 826 535 42 1,072 700 5 21 77 54 28 160 108 36 275 176 45 421 273 58 600 385 69 811 524 82 1,055 688 10 27 70 50 37 150 102 48 262 171 59 405 261 77 580 371 91 788 507 107 1,028 668 15 33 64 NA 44 141 96 57 249 163 70 389 249 90 560 357 105 765 490 124 1,002 648 20 56 58 NA 53 132 90 66 237 154 80 374 237 102 542 343 119 743 473 139 977 628 30 NA NA NA 73 113 NA 88 214 NA 104 346 219 131 507 321 149 702 444 171 929 594 50 0 0 101 67 0 216 134 0 397 232 0 633 363 0 932 518 0 1,297 708 0 1,730 952 2 8 86 61 11 183 122 14 320 206 15 497 314 22 715 445 26 975 615 33 1,276 813 5 20 82 NA 27 177 119 35 312 200 43 487 308 55 702 438 65 960 605 77 1,259 798 10 26 76 NA 35 168 114 45 299 190 56 471 298 73 681 426 86 935 589 101 1,230 773 15 59 70 NA 42 158 NA 54 287 180 66 455 288 85 662 413 100 911 572 117 1,203 747 20 NA NA NA 50 149 NA 63 275 169 76 440 278 97 642 401 113 888 556 131 1,176 722 30 NA NA NA 69 131 NA 84 250 NA 99 410 259 123 605 376 141 844 522 161 1,125 670 100 0 NA NA NA 0 218 NA 0 407 NA 0 665 400 0 997 560 0 1,411 770 0 1,908 1,040 2 NA NA NA 10 194 NA 12 354 NA 13 566 375 18 831 510 21 1,155 700 25 1,536 935 5 NA NA NA 26 189 NA 33 347 NA 40 557 369 52 820 504 60 1,141 692 71 1,519 926 10 NA NA NA 33 182 NA 43 335 NA 53 542 361 68 801 493 80 1,118 679 94 1,492 910 15 NA NA NA 40 174 NA 50 321 NA 62 528 353 80 782 482 93 1,095 666 109 1,465 895 20 NA NA NA 47 166 NA 59 311 NA 71 513 344 90 763 471 105 1,073 653 122 1,438 880 30 NA NA NA NA NA NA 78 290 NA 92 483 NA 115 726 449 131 1,029 627 149 1,387 849 50 NA NA NA NA NA NA NA NA NA 147 428 NA 180 651 405 197 944 575 217 1,288 787 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 0 0 1,12 1 570 0 1,64 5 850 0 2,267 1,17 0 0 2,98 3 1,53 0 0 3,80 2 1,96 0 0 4,72 1 2,43 0 0 5,73 7 2,95 0 0 6,85 3 3,52 0 2 75 675 455 103 982 650 138 1,346 890 178 1,76 9 1,17 0 225 2,25 0 1,48 0 296 2,78 2 1,85 0 360 3,37 7 2,22 0 426 4,03 0 2,67 0 4 110 668 445 147 975 640 191 1,338 880 242 1,76 1 1,16 0 300 2,24 2 1,47 5 390 2,77 4 1,83 5 469 3,37 0 2,21 5 555 4,02 3 2,66 0 6 128 661 435 171 967 630 219 1,330 870 276 1,75 3 1,15 0 341 2,23 5 1,47 0 437 2,76 7 1,82 0 523 3,36 3 2,21 0 618 4,01 7 2,65 0 8 0 0 1,26 1 660 0 1,85 8 970 0 2,571 1,32 0 0 3,39 9 1,74 0 0 4,33 3 2,22 0 0 5,38 7 2,75 0 0 6,55 5 3,36 0 0 7,83 8 4,01 0 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) 2 71 770 515 98 1,12 4 745 130 1,543 1,02 0 168 2,03 0 1,34 0 212 2,58 4 1,70 0 278 3,19 6 2,11 0 336 3,88 2 2,56 0 401 4,63 4 3,05 0 5 115 758 503 154 1,11 0 733 199 1,528 1,01 0 251 2,01 3 1,33 0 311 2,56 3 1,68 5 398 3,18 0 2,09 0 476 3,86 3 2,54 5 562 4,61 2 3,04 0 8 137 746 490 180 1,09 7 720 231 1,514 1,00 0 289 2,00 0 1,32 0 354 2,55 2 1,67 0 450 3,16 3 2,07 0 537 3,85 0 2,53 0 630 4,60 2 3,03 0 10 0 0 1,37 7 720 0 2,03 6 1,06 0 0 2,825 1,45 0 0 3,74 2 1,92 5 0 4,78 2 2,45 0 0 5,95 5 3,05 0 0 7,25 4 3,71 0 0 8,68 2 4,45 0 2 68 852 560 93 1,24 4 850 124 1,713 1,13 0 161 2,25 6 1,48 0 202 2,86 8 1,89 0 264 3,55 6 2,34 0 319 4,32 2 2,84 0 378 5,15 3 3,39 0 5 112 839 547 149 1,22 9 829 192 1,696 1,10 5 243 2,23 8 1,46 1 300 2,84 9 1,87 1 382 3,53 6 2,31 8 458 4,30 1 2,81 8 540 5,13 2 3,37 1 10 142 817 525 187 1,20 4 795 238 1,669 1,08 0 298 2,20 9 1,43 0 364 2,81 8 1,84 0 459 3,50 4 2,28 0 546 4,26 8 2,78 0 641 5,09 9 3,34 0 15 0 0 1,59 6 840 0 2,38 0 1,24 0 0 3,323 1,72 0 0 4,42 3 2,27 0 0 5,67 8 2,90 0 0 7,09 9 3,62 0 0 8,66 5 4,41 0 0 10,3 93 5,30 0 2 63 1,01 9 675 86 1,49 5 985 114 2,062 1,35 0 147 2,71 9 1,77 0 186 3,46 7 2,26 0 239 4,30 4 2,80 0 290 5,23 2 3,41 0 346 6,25 1 4,08 0 5 105 1,00 3 660 140 1,47 6 967 182 2,041 1,32 7 229 2,69 6 1,74 8 283 3,44 2 2,23 5 355 4,27 8 2,77 7 426 5,20 4 3,38 5 501 6,22 2 4,05 7 10 135 977 635 177 1,44 6 936 227 2,009 1,28 9 283 2,65 9 1,71 2 346 3,40 2 2,19 3 432 4,23 4 2,73 9 510 5,15 9 3,34 3 599 6,17 5 4,01 9 15 155 953 610 202 1,41 8 905 257 1,976 1,25 0 318 2,62 3 1,67 5 385 3,36 3 2,15 0 479 4,19 2 2,70 0 564 5,11 5 3,30 0 665 6,12 9 3,98 0 20 0 0 1,75 6 930 0 2,63 7 1,35 0 0 3,701 1,90 0 0 4,94 8 2,52 0 0 6,37 6 3,25 0 0 7,98 8 4,06 0 0 9,78 5 4,98 0 0 11,7 53 6,00 0 2 59 1,15 0 755 81 1,69 4 1,10 0 107 2,343 1,52 0 139 3,09 7 2,00 0 175 3,95 5 2,57 0 220 4,91 6 3,20 0 269 5,98 3 3,91 0 321 7,15 4 4,70 0 5 101 1,13 3 738 135 1,67 4 1,07 9 174 2,320 1,49 8 219 3,07 1 1,97 8 270 3,92 6 2,54 4 337 4,88 5 3,17 4 403 5,95 0 3,88 0 475 7,11 9 4,66 2 10 130 1,10 5 710 172 1,64 1 1,04 5 220 2,282 1,46 0 273 3,02 9 1,94 0 334 3,88 0 2,50 0 413 4,83 5 3,13 0 489 5,89 6 3,83 0 573 7,06 3 4,60 0 15 150 1,07 8 688 195 1,60 9 1,01 8 248 2,245 1,42 5 306 2,98 8 1,91 0 372 3,83 5 2,46 5 459 4,78 6 3,09 0 541 5,84 4 3,79 5 631 7,00 7 4,57 5 20 167 1,05 2 665 217 1,57 8 990 273 2,210 1,39 0 335 2,94 8 1,88 0 404 3,79 1 2,43 0 495 4,73 7 3,05 0 585 5,79 2 3,76 0 689 6,95 3 4,55 0 (continued) TABLE 504.2(2) TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Ma x Mln Max Max Mln Max Max Mln Max Max 6 0 38 77 45 59 15 1 85 85 24 9 14 0 12 6 37 3 20 4 16 5 52 2 28 4 21 1 695 36 9 26 7 894 469 37 1 1,1 18 569 53 7 1.6 39 849 2 39 51 36 60 96 66 85 15 6 10 4 12 3 23 1 15 6 15 9 32 0 21 3 20 1 423 28 4 25 1 541 368 34 7 673 453 49 8 979 648 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) 4 NA NA 33 74 92 63 10 2 15 2 10 2 14 6 22 5 15 2 18 7 31 3 20 8 23 7 416 27 7 29 5 533 360 40 9 664 443 58 4 971 638 6 NA NA 31 83 89 60 11 4 14 7 99 16 3 22 0 14 8 20 7 30 7 20 3 26 3 409 27 1 32 7 526 352 44 9 656 433 63 8 962 627 8 0 37 83 50 58 16 4 93 83 27 3 15 4 12 3 41 2 23 4 16 1 58 0 31 9 20 6 777 41 4 25 8 1,0 02 536 36 0 1,2 57 658 52 1 1,8 52 967 2 39 56 39 59 10 8 75 83 17 6 11 9 12 1 26 1 17 9 15 5 36 3 24 6 19 7 482 32 1 24 6 617 417 33 9 768 513 48 6 1,1 20 743 5 NA NA 37 77 10 2 69 10 7 16 8 11 4 15 1 25 2 17 1 19 3 35 2 23 5 24 5 470 31 1 30 5 604 404 41 8 754 500 59 8 1,1 04 730 8 NA NA 33 90 95 64 12 2 16 1 10 7 17 5 24 3 16 3 22 3 34 2 22 5 28 0 458 30 0 34 4 591 392 47 0 740 486 66 5 1.0 89 715 10 0 37 87 53 57 17 4 99 82 29 3 16 5 12 0 44 4 25 4 15 8 62 8 34 4 20 2 844 44 9 25 3 1,0 93 584 35 1 1,3 73 718 50 7 2,0 31 1,0 57 2 39 61 41 59 11 7 80 82 19 3 12 8 11 9 28 7 19 4 15 3 40 0 27 2 19 3 531 35 4 24 2 681 456 33 2 849 559 47 5 1,2 42 848 5 52 56 39 76 11 1 76 10 5 18 5 12 2 14 8 27 7 18 6 19 0 38 8 26 1 24 1 518 34 4 29 9 667 443 40 9 834 544 58 4 1,2 24 825 10 NA NA 34 97 10 0 68 13 2 17 1 11 2 18 8 26 1 17 1 23 7 36 9 24 1 29 6 497 32 5 36 3 643 423 49 2 808 520 68 8 1,1 94 788 15 0 36 93 57 56 19 0 11 1 80 32 5 18 6 11 6 49 9 28 3 15 3 71 3 38 8 19 5 966 52 3 24 4 1.2 59 681 33 6 1.5 91 838 48 8 2,3 74 1,2 37 2 38 69 47 57 13 6 93 80 22 5 14 9 11 5 33 7 22 4 14 8 47 3 31 4 18 7 631 41 3 23 2 812 543 31 9 1,0 15 673 45 7 1.4 91 983 5 51 63 44 75 12 8 86 10 2 21 6 14 0 14 4 32 6 21 7 18 2 45 9 29 8 23 1 616 40 0 28 7 795 526 39 2 997 657 56 2 1,4 69 963 10 NA NA 39 95 11 6 79 12 8 20 1 13 1 18 2 30 8 20 3 22 8 43 8 28 4 28 4 592 38 1 34 9 768 501 47 0 966 628 66 4 1,4 33 928 15 NA NA NA NA NA 72 15 8 18 6 12 4 22 0 29 0 19 2 27 2 41 8 26 9 33 4 568 36 7 40 4 742 484 54 0 937 601 75 0 1,3 99 894 20 0 35 96 60 54 20 0 11 8 78 34 6 20 1 11 4 53 7 30 6 14 9 77 2 42 8 19 0 1,0 53 57 3 23 8 1,3 79 750 32 6 1,7 51 927 47 3 2,6 31 1,3 46 2 37 74 50 56 14 8 99 78 24 8 16 5 11 3 37 5 24 8 14 4 52 8 34 4 18 2 708 46 8 22 7 914 611 30 9 1,1 46 754 44 3 1.6 89 1.0 98 5 50 68 47 73 14 0 94 10 0 23 9 15 8 14 1 36 3 23 9 17 8 51 4 33 4 22 4 692 45 7 27 9 896 596 38 1 1,1 26 734 54 7 1,6 65 1,0 74 10 NA NA 41 93 12 9 86 12 5 22 3 14 6 17 7 34 4 22 4 22 2 49 1 31 6 27 7 666 43 7 33 9 866 570 45 7 1,0 92 702 64 6 1,6 26 1,0 37 15 NA NA NA NA NA 80 15 5 20 8 13 6 21 6 32 5 21 0 26 4 46 9 30 1 32 5 640 41 9 39 3 838 549 52 6 1,0 60 677 73 0 1,5 87 1,0 05 20 NA NA NA NA NA NA 18 6 19 2 12 6 25 4 30 6 19 6 30 9 44 8 28 5 37 4 616 40 0 44 8 810 526 59 2 1,0 28 651 80 8 1,5 50 973 (continued) TABLE 504.2(1) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Connected directly to vent HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) inches 10 12 14 16 18 20 22 24 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 Min Max Max Min Max Max Mi n Max Max Mi n Max Max Min Max Max Min Max Max Min Max Max Min Max Max 30 0 0 1,97 7 1,06 0 0 3,00 4 1,55 0 0 4,25 2 2,17 0 0 5,72 5 2,92 0 0 7,42 0 3,77 0 0 9,34 1 4,75 0 0 11,4 83 5,85 0 0 13,84 8 7,06 0 2 54 1,35 1 865 74 2,00 4 1,31 0 98 2,78 6 1,80 0 12 7 3,69 6 2,38 0 15 9 4,73 4 3,05 0 19 9 5,90 0 3,81 0 24 1 7,19 4 4,65 0 28 5 8,617 5,60 0 5 96 1,33 2 851 12 7 1,98 1 1,28 9 16 4 2,75 9 1,77 5 20 6 3,66 6 2,35 0 25 2 4,70 1 3,02 0 31 2 5,86 3 3,78 3 37 3 7,15 5 4,62 2 43 9 8,574 5,55 2 10 12 5 1,30 1 829 16 4 1,94 4 1,25 4 20 9 2,71 6 1,73 3 25 9 3,61 7 2,30 0 31 6 4,64 7 2,97 0 38 6 5,80 3 3,73 9 45 6 7,09 0 4,57 4 53 5 8,505 5,47 1 15 14 3 1,27 2 807 18 7 1,90 8 1,22 0 23 7 2,67 4 1,69 2 29 2 3,57 0 2,25 0 35 4 4,59 4 2,92 0 43 1 5,74 4 3,69 5 50 7 7,02 6 4,52 7 59 0 8,437 5,39 1 20 16 0 1,24 3 784 20 7 1,87 3 1,18 5 26 0 2,63 3 1,65 0 31 9 3,52 3 2,20 0 38 4 4,54 2 2,87 0 46 7 5,68 6 3,65 0 54 8 6,96 4 4,48 0 63 9 8,370 5,31 0 30 19 5 1,18 9 745 24 6 1,80 7 1,13 0 30 5 2,55 5 1,58 5 36 9 3,43 3 2,13 0 44 0 4,44 2 2,78 5 54 0 5,57 4 3,56 5 63 5 6,84 2 4,37 5 73 9 8,239 5,22 5 50 0 0 2,23 1 1,19 5 0 3,44 1 1,82 5 0 4,93 4 2,55 0 0 6,71 1 3,44 0 0 8,77 4 4,46 0 0 11,1 29 5,63 5 0 13,7 67 6,94 0 0 16,69 4 8,43 0 2 41 1,62 0 1,01 0 66 2,43 1 1,51 3 86 3,40 9 2,12 5 11 3 4,55 4 2,84 0 14 1 5,86 4 3,67 0 17 1 7,33 9 4,63 0 20 9 8,98 0 5,69 5 25 1 10,78 8 6,86 0 5 90 1,60 0 996 11 8 2,40 6 1,49 5 15 1 3,38 0 2,10 2 19 1 4,52 0 2,81 3 23 4 5,82 6 3,63 9 28 3 7,29 5 4,59 7 33 6 8,93 3 5,65 4 39 4 10,73 7 6,81 8 10 11 8 1,56 7 972 15 4 2,36 6 1,46 6 19 6 3,33 2 2,06 4 24 3 4,46 4 2,76 7 29 5 5,76 3 3,58 5 35 5 7,22 4 4,54 2 41 9 8,85 5 5,58 5 49 1 10,65 2 6,74 9 15 13 6 1,53 6 948 17 7 2,32 7 1,43 7 22 2 3,28 5 2,02 6 27 4 4,40 9 2,72 1 33 0 5,70 1 3,53 4 39 6 7,15 5 4,51 1 46 5 8,77 9 5,54 6 54 2 10,57 0 6,71 0 20 15 1 1,50 5 924 19 5 2,28 8 1,40 8 24 4 3,23 9 1,98 7 30 0 4,35 6 2,67 5 36 1 5,64 1 3,48 1 43 3 7,08 6 4,47 9 50 6 8,70 4 5,50 6 58 6 10,48 8 6,67 0 30 18 3 1,44 6 876 23 2 2,21 4 1,34 9 28 7 3,15 0 1,91 0 34 7 4,25 3 2,63 1 41 2 5,52 3 3,43 1 49 4 6,95 3 4,42 1 57 7 8,55 7 5,44 4 67 2 10,32 8 6,60 3 100 0 0 2,49 1 1,31 0 0 3,92 5 2,05 0 0 5,72 9 2,95 0 0 7,91 4 4,05 0 0 10,4 85 5,30 0 0 13,4 54 6,70 0 0 16,8 17 8,60 0 0 20,57 8 10,3 00 2 30 1,97 5 1,17 0 44 3,02 7 1,82 0 72 4,31 3 2,55 0 95 5,83 4 3,50 0 12 0 7,59 1 4,60 0 13 8 9,57 7 5,80 0 16 9 11,8 03 7,20 0 20 4 14,26 4 8,80 0 5 82 1,95 5 1,15 9 10 7 3,00 2 1,80 3 13 6 4,28 2 2,53 1 17 2 5,79 7 3,47 5 20 8 7,54 8 4,56 6 24 5 9,52 8 5,76 9 29 3 11,7 48 7,16 2 34 1 14,20 4 8,75 6 10 10 8 1,92 3 1,14 2 14 2 2,96 1 1,77 5 18 0 4,23 1 2,50 0 22 3 5,73 7 3,43 4 26 8 7,47 8 4,50 9 31 8 9,44 7 5,71 7 37 4 11,6 58 7,10 0 43 6 14,10 5 8,68 3 15 12 6 1,89 2 1,12 4 16 3 2,92 0 1,74 7 20 6 4,18 2 2,46 9 25 2 5,67 8 3,39 2 30 4 7,40 9 4,45 1 35 8 9,36 7 5,66 5 41 8 11,5 69 7,03 7 48 7 14,00 7 8,61 0 20 14 1 1,86 1 1,10 7 18 1 2,88 0 1,71 9 22 6 4,13 3 2,43 8 27 7 5,61 9 3,35 1 33 0 7,34 1 4,39 4 38 7 9,28 9 5,61 3 45 2 11,4 82 6,97 5 52 3 13,91 0 8,53 7 30 17 0 1,80 2 1,07 1 21 5 2,80 3 1,66 3 26 5 4,03 7 2,37 5 31 9 5,50 5 3,26 7 37 8 7,20 9 4,27 9 44 6 9,13 6 5,50 9 51 4 11,3 10 6,85 0 59 2 13,72 0 8,39 1 50 24 1 1,68 8 1,00 0 29 2 2,65 7 1,55 0 35 0 3,85 6 2,25 0 41 5 5,28 9 3,10 0 48 6 6,95 6 4,05 0 57 2 8,84 1 5,30 0 65 9 10,9 79 6,60 0 75 2 13,35 4 8,10 0 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T LATER AL TYPE B DOUBLE - WALL CONNECTOR DIAMETER - — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 (H) (feet) (L) (feet) APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 13 0 NA NA 18 0 NA NA 24 7 NA NA 32 0 NA NA 401 NA NA 581 5 NA NA 25 NA NA 49 NA NA 82 NA NA 11 7 NA NA 16 5 NA NA 23 1 NA NA 29 8 NA NA 376 NA NA 561 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 14 5 NA NA 19 8 NA NA 26 6 84 59 0 35 0 10 0 728 446 139 1,02 4 651 5 NA NA 26 NA NA 52 NA NA 88 NA NA 13 4 NA NA 18 3 NA NA 24 7 NA NA 32 8 14 9 711 423 201 1,00 7 640 8 NA NA 24 NA NA 48 NA NA 83 NA NA 12 7 NA NA 17 5 NA NA 23 9 NA NA 31 8 17 3 695 410 231 990 623 10 2 NA NA 31 NA NA 61 NA NA 10 3 NA NA 16 2 NA NA 22 1 68 51 9 29 8 82 65 5 38 8 98 810 491 136 1,14 4 724 5 NA NA 28 NA NA 57 NA NA 96 NA NA 14 8 NA NA 20 4 NA NA 27 7 12 4 63 8 36 5 14 6 791 466 196 1,12 4 712 10 NA NA 25 NA NA 50 NA NA 87 NA NA 13 9 NA NA 19 1 NA NA 26 3 15 5 61 0 34 7 18 2 762 444 240 1,09 3 668 15 2 NA NA 35 NA NA 67 NA NA 11 4 NA NA 17 9 53 47 5 25 0 64 61 3 33 6 77 77 9 44 1 92 968 562 127 1,37 6 841 5 NA NA 35 NA NA 62 NA NA 10 7 NA NA 16 4 NA NA 23 1 99 59 4 31 3 11 8 75 9 41 6 13 9 946 533 186 1,35 2 828 10 NA NA 28 NA NA 55 NA NA 97 NA NA 15 3 NA NA 21 6 12 6 56 5 29 6 14 8 72 7 39 4 17 3 912 567 229 1,31 5 777 15 NA NA NA NA NA 48 NA NA 89 NA NA 14 1 NA NA 20 1 NA NA 28 1 17 1 69 8 37 5 19 8 880 485 259 1,28 0 742 20 2 NA NA 38 NA NA 74 NA NA 12 4 NA NA 20 1 51 52 2 27 4 61 67 8 37 5 73 86 7 49 1 87 1,08 3 627 121 1,54 8 953 5 NA NA 36 NA NA 68 NA NA 11 6 NA NA 18 4 80 50 3 25 4 95 65 8 35 0 11 3 84 5 46 3 13 3 1,05 9 597 179 1,52 3 933 10 NA NA NA NA NA 60 NA NA 10 7 NA NA 17 2 NA NA 23 7 12 2 62 7 33 2 14 3 81 1 44 0 16 7 1,02 2 566 221 1,48 2 879 15 NA NA NA NA NA NA NA NA 97 NA NA 15 9 NA NA 22 0 NA NA 31 4 16 5 78 0 41 8 19 1 987 541 251 1,44 3 840 20 NA NA NA NA NA NA NA NA 83 NA NA 14 8 NA NA 20 6 NA NA 29 6 18 6 75 0 39 7 21 4 955 513 277 1,40 6 807 (continued) TABLE 504.2(2) — continued TYPE B DOUBLE - WALL GAS VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) VENT DIAMETER — (D) Inches 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT FAN NAT FAN NAT Ml n Ma x Ma x Ml n Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Ma x Ma x Mln Max Max Mln Max Max Mln Max Max Mln Max Max 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 30 0 34 99 63 53 21 1 12 7 76 37 2 21 9 11 0 58 4 33 4 14 4 84 9 47 2 18 4 1,16 8 647 22 9 1,54 2 852 31 2 1.97 1 1,05 6 454 2,99 6 1,54 5 2 37 80 56 55 16 4 11 1 76 28 1 18 3 10 9 42 9 27 9 13 9 61 0 39 2 17 5 823 533 21 9 1,06 9 698 29 6 1,34 6 863 424 1,99 9 1,30 8 5 49 74 52 72 15 7 10 6 98 27 1 17 3 13 6 41 7 27 1 17 1 59 5 38 2 21 5 806 521 26 9 1,04 9 684 36 6 1,32 4 846 524 1,97 1 1,28 3 10 N A N A N A 91 14 4 98 12 2 25 5 16 8 17 1 39 7 25 7 21 3 57 0 36 7 26 5 777 501 32 7 1,01 7 662 44 0 1,28 7 821 620 1,92 7 1,23 4 15 N A N A N A 11 5 13 1 N A 15 1 23 9 15 7 20 8 37 7 24 2 25 5 54 7 34 9 31 2 750 481 37 9 985 638 50 7 1,25 1 794 702 1,88 4 1,20 5 20 N A N A N A N A N A N A 18 1 22 3 N A 24 6 35 7 22 8 29 8 52 4 33 3 36 0 723 461 43 3 955 615 57 0 1,21 6 768 780 1,84 1 1,16 6 30 N A N A N A N A N A N A N A N A N A N A N A N A 38 9 47 7 30 5 46 1 670 426 54 1 895 574 70 4 1,14 7 720 937 1.75 9 1,10 1 50 0 33 99 66 51 21 3 13 3 73 39 4 23 0 10 5 62 9 36 1 13 8 92 8 51 5 17 6 1,29 2 704 22 0 1,72 4 948 29 5 2,22 3 1,18 9 428 3,43 2 1,81 8 2 36 84 61 53 18 1 12 1 73 31 8 20 5 10 4 49 5 31 2 13 3 71 2 44 3 16 8 971 613 20 9 1,27 3 811 28 0 1,61 5 1,00 7 401 2,42 6 1,50 9 5 48 80 N A 70 17 4 11 7 94 30 8 19 8 13 1 48 2 30 5 16 4 69 6 43 5 20 4 953 602 25 7 1,25 2 795 34 7 1,59 1 991 496 2,39 6 1,49 0 10 N A N A N A 89 16 0 N A 11 8 29 2 18 6 16 2 46 1 29 2 20 3 67 1 42 0 25 3 923 583 31 3 1,21 7 765 41 8 1,55 1 963 589 2,34 7 1,45 5 15 N A N A N A 11 2 14 8 N A 14 5 27 5 17 4 19 9 44 1 28 0 24 4 64 6 40 5 29 9 894 562 36 3 1,18 3 736 48 1 1,51 2 934 668 2,29 9 1,42 1 20 N A N A N A N A N A N A 17 6 25 7 N A 23 6 42 0 26 7 28 5 62 2 38 9 34 5 866 543 41 5 1,15 0 708 54 4 1,47 3 906 741 2,25 1 1,38 7 30 N A N A N A N A N A N A N A N A N A 31 5 37 6 N A 37 3 57 3 N A 44 2 809 502 52 1 1,08 6 649 67 4 1,39 9 848 892 2,15 9 1,31 8 100 0 N A N A N A 49 21 4 N A 69 40 3 N A 10 0 65 9 39 5 13 1 99 1 55 5 16 6 1,40 4 765 20 7 1,90 0 1,03 3 27 3 2,47 9 1,30 0 395 3,91 2 2,04 2 2 N A N A N A 51 19 2 N A 70 35 1 N A 98 56 3 37 3 12 5 82 8 50 8 15 8 1,15 2 698 19 6 1,53 2 933 25 9 1,97 0 1,16 8 371 3,02 1 1,81 7 5 N A N A N A 67 18 6 N A 90 34 2 N A 12 5 55 1 36 6 15 6 81 3 50 1 19 4 1,13 4 688 24 0 1,51 1 921 32 2 1,94 5 1,15 3 460 2,99 0 1,79 6 10 N A N A N A 85 17 5 N A 11 3 32 4 N A 15 3 53 2 35 4 19 1 78 9 48 6 23 8 1,10 4 672 29 3 1,47 7 902 38 9 1.90 5 1,13 3 547 2,93 8 1,76 3 15 N A N A N A 13 2 16 2 N A 13 8 31 0 N A 18 8 51 1 34 3 23 0 76 4 47 3 28 1 1,07 5 656 34 2 1,44 3 884 44 7 1,86 5 1,11 0 618 2,88 8 1,73 0 20 N A N A N A N A N A N A 16 8 29 5 N A 22 4 48 7 N A 27 0 73 9 45 8 32 5 1,04 6 639 39 1 1,41 0 864 50 7 1,82 5 1,08 7 690 2,83 8 1,69 6 30 N A N A N A N A N A N A 23 1 26 4 N A 30 1 44 8 N A 35 5 68 5 N A 41 8 988 NA 49 1 1,34 3 824 63 1 1,74 7 1,04 1 834 2,73 9 1,62 7 50 N A N A N A N A N A N A N A N A N A N A N A N A 54 0 58 4 N A 61 7 866 NA 71 1 1,20 5 NA 89 5 1,59 1 NA 1,13 8 2,54 7 1,48 9 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(3) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector HEIGH T (H) (feet) LATER AL (L) (feet) TYPE B DOUBLE - WALL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 82 NA NA 13 7 NA NA 21 6 47 58 1 30 3 57 76 2 42 1 68 985 55 8 81 1,2 40 717 111 1,7 93 1,1 12 5 NA NA NA NA NA 76 NA NA 12 8 NA NA 19 8 75 56 1 28 1 90 74 1 39 3 10 6 962 52 6 12 5 1,2 16 683 169 1,7 66 1,0 94 10 NA NA NA NA NA 67 NA NA 11 5 NA NA 18 4 NA NA 26 3 11 5 70 9 37 3 13 5 927 50 0 15 8 1,1 76 648 210 1,7 21 1,0 25 15 NA NA NA NA NA NA NA NA 10 7 NA NA 17 1 NA NA 24 3 NA NA 35 3 15 6 893 47 6 18 1 1,1 39 621 239 1,6 79 981 20 NA NA NA NA NA NA NA NA 91 NA NA 15 9 NA NA 22 7 NA NA 33 2 17 6 860 45 0 20 3 1,1 03 592 264 1,6 38 940 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 18 8 NA NA 28 8 NA NA 41 6 24 9 1,0 35 555 318 1,5 60 877 50 2 NA NA NA NA NA 92 NA NA 16 1 NA NA 25 1 NA NA 35 1 51 84 0 47 7 61 1,1 06 63 3 72 1,4 13 812 99 2,0 80 1,2 43 5 NA NA NA NA NA NA NA NA 15 1 NA NA 23 0 NA NA 32 3 83 81 9 44 5 98 1,0 83 59 6 11 6 1,3 87 774 155 2,0 52 1,2 25 10 NA NA NA NA NA NA NA NA 13 8 NA NA 21 5 NA NA 30 4 NA NA 42 4 12 6 1,0 47 56 7 14 7 1,3 47 733 195 2,0 06 1,1 47 15 NA NA NA NA NA NA NA NA 12 7 NA NA 19 9 NA NA 28 2 NA NA 40 0 14 6 1,0 10 53 9 17 0 1,3 07 702 222 1,9 61 1,0 99 20 NA NA NA NA NA NA NA NA NA NA NA 18 5 NA NA 26 4 NA NA 37 6 16 5 977 51 1 19 0 1,2 69 669 246 1,9 16 1,0 50 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 32 7 NA NA 46 8 23 3 1,1 96 623 295 1,8 32 984 Minimum In- ternal Area of Chim- ney (square inches) 12 19 28 38 50 63 78 95 132 Maximum In- ternal Area of Chim- ney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(4) MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Max Min Max Max 6 2 NA NA 28 NA NA 52 NA NA 86 NA NA 130 NA NA 180 NA NA 247 NA NA 319 NA NA 400 NA NA 580 5 NA NA 25 NA NA 48 NA NA 81 NA NA 116 NA NA 164 NA NA 230 NA NA 297 NA NA 375 NA NA 560 8 2 NA NA 29 NA NA 55 NA NA 93 NA NA 145 NA NA 197 NA NA 265 NA NA 349 382 725 445 549 1,02 1 650 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 5 NA NA 26 NA NA 51 NA NA 87 NA NA 133 NA NA 182 NA NA 246 NA NA 327 NA NA 422 673 1,00 3 638 8 NA NA 23 NA NA 47 NA NA 82 NA NA 126 NA NA 174 NA NA 237 NA NA 317 NA NA 408 747 985 621 10 2 NA NA 31 NA NA 61 NA NA 102 NA NA 161 NA NA 220 216 518 297 271 654 387 373 808 490 536 1,14 2 722 5 NA NA 28 NA NA 56 NA NA 95 NA NA 147 NA NA 203 NA NA 276 334 635 364 459 789 465 657 1,12 1 710 10 NA NA 24 NA NA 49 NA NA 86 NA NA 137 NA NA 189 NA NA 261 NA NA 345 547 758 441 771 1,08 8 665 15 2 NA NA 35 NA NA 67 NA NA 113 NA NA 178 166 473 249 211 611 335 264 776 440 362 965 560 520 1,37 3 840 5 NA NA 32 NA NA 61 NA NA 106 NA NA 163 NA NA 230 261 591 312 325 775 414 444 942 531 637 1,34 8 825 10 NA NA 27 NA NA 54 NA NA 96 NA NA 151 NA NA 214 NA NA 294 392 722 392 531 907 504 749 1,30 9 774 15 NA NA NA NA NA 46 NA NA 87 NA NA 138 NA NA 198 NA NA 278 452 692 372 606 873 481 841 1,27 2 738 20 2 NA NA 38 NA NA 73 NA NA 123 NA NA 200 163 520 273 206 675 374 258 864 490 252 1,07 9 625 508 1,54 4 950 5 NA NA 35 NA NA 67 NA NA 115 NA NA 183 80 NA 252 255 655 348 317 842 461 433 1,05 5 594 623 1,51 8 930 10 NA NA NA NA NA 59 NA NA 105 NA NA 170 NA NA 235 312 622 330 382 806 437 517 1,01 6 562 733 1,47 5 875 15 NA NA NA NA NA NA NA NA 95 NA NA 156 NA NA 217 NA NA 311 442 773 414 591 979 539 823 1,43 4 835 20 NA NA NA NA NA NA NA NA 80 NA NA 144 NA NA 202 NA NA 292 NA NA 392 663 944 510 911 1,39 4 800 (continued) TABLE 504.2(4) — continued MASONRY CHIMNEY Number of Appliances Single Appliance Type Category I Appliance Vent Connection Single - wall metal connector HEIGH T (H) (feet) LATER AL (L) (feet) SINGLE - WALL METAL CONNECTOR DIAMETER — (D) Inches to be used with chimney areas within the size limits at bottom 3 4 5 6 7 8 9 10 12 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NAT Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Ma x Ma x Min Max Ma x Min Max Max Min Max Max 30 2 NA NA 41 NA NA 81 NA NA 136 NA NA 215 158 578 302 200 759 420 249 982 556 340 1,23 7 715 489 1,78 9 1,11 0 5 NA NA NA NA NA 75 NA NA 127 NA NA 196 NA NA 279 245 737 391 306 958 524 417 1,21 0 680 600 1,76 0 1,09 0 10 NA NA NA NA NA 66 NA NA 113 NA NA 182 NA NA 260 300 703 370 370 920 496 500 1,16 8 644 708 1,71 3 1,02 0 15 NA NA NA NA NA NA NA NA 105 NA NA 168 NA NA 240 NA NA 349 428 884 471 572 1,12 8 615 798 1,66 8 975 20 NA NA NA NA NA NA NA NA 88 NA NA 155 NA NA 223 NA NA 327 NA NA 445 643 1,08 9 585 883 1,62 4 932 30 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 182 NA NA 281 NA NA 408 NA NA 544 1,05 5 1,53 9 865 50 2 NA NA NA NA NA 91 NA NA 160 NA NA 250 NA NA 350 191 837 475 238 1,10 3 631 323 1,40 8 810 463 2,07 6 1,24 0 5 NA NA NA NA NA NA NA NA 149 NA NA 228 NA NA 321 NA NA 442 293 1,07 8 593 398 1,38 1 770 571 2,04 4 1,22 0 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 10 NA NA NA NA NA NA NA NA 136 NA NA 212 NA NA 301 NA NA 420 355 1,03 8 562 447 1,33 7 728 674 1,99 4 1,14 0 15 NA NA NA NA NA NA NA NA 124 NA NA 195 NA NA 278 NA NA 395 NA NA 533 546 1,29 4 695 761 1,94 5 1,09 0 20 NA NA NA NA NA NA NA NA NA NA NA 180 NA NA 258 NA NA 370 NA NA 504 616 1,25 1 660 844 1,89 8 1,04 0 30 NA NA NA NA NA 48 NA NA NA NA NA NA NA NA NA NA NA 318 NA NA 458 NA NA 610 1,00 9 1,80 5 970 Minimum Internal Area of Chimney (square inches) 12 19 28 38 50 63 78 95 132 Maximum Internal Area of Chimney (square inches) Seven times the listed appliance categorized vent area, flue collar area or draft hood outlet area. For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER — ( D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 22 37 26 35 66 46 46 106 72 58 164 104 77 225 142 92 296 185 109 376 237 128 466 289 2 23 41 31 37 75 55 48 121 86 60 183 124 79 253 168 95 333 220 112 424 282 131 526 345 3 24 44 35 38 81 62 49 132 96 62 199 139 82 275 189 97 363 248 114 463 317 134 575 386 8 1 22 40 27 35 72 48 49 114 76 64 176 109 84 243 148 100 320 194 118 408 248 138 507 303 2 23 44 32 36 80 57 51 128 90 66 195 129 86 269 175 103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 10 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257 146 542 314 2 23 47 33 36 86 59 51 136 93 67 206 134 91 282 182 109 374 238 128 479 305 149 596 372 3 24 50 37 37 92 67 52 146 104 69 220 150 94 303 205 111 402 268 131 515 342 152 642 417 15 1 21 50 30 33 89 53 47 142 83 64 220 120 88 298 163 110 389 214 134 493 273 162 609 333 2 22 53 35 35 96 63 49 153 99 66 235 142 91 320 193 112 419 253 137 532 323 165 658 394 3 24 55 40 36 102 71 51 163 111 68 248 160 93 339 218 115 445 286 140 565 365 167 700 444 20 1 21 54 31 33 99 56 46 157 87 62 246 125 86 334 171 107 436 224 131 552 285 158 681 347 2 22 57 37 34 105 66 48 167 104 64 259 149 89 354 202 110 463 265 134 587 339 161 725 414 3 23 60 42 35 110 74 50 176 116 66 271 168 91 371 228 113 486 300 137 618 383 164 764 466 30 1 20 62 33 31 113 59 45 181 93 60 288 134 83 391 182 103 512 238 125 649 305 151 802 372 2 21 64 39 33 118 70 47 190 110 62 299 158 85 408 215 105 535 282 129 679 360 155 840 439 3 22 66 44 34 123 79 48 198 124 64 309 178 88 423 242 108 555 317 132 706 405 158 874 494 50 1 19 71 36 30 133 64 43 216 101 57 349 145 78 477 197 97 627 257 120 797 330 144 984 403 2 21 73 43 32 137 76 45 223 119 59 358 172 81 490 234 100 645 306 123 820 392 148 1,014 478 3 22 75 48 33 141 86 46 229 134 61 366 194 83 502 263 103 661 343 126 842 441 151 1,043 538 100 1 18 82 37 28 158 66 40 262 104 53 442 150 73 611 204 91 810 266 112 1,038 341 135 1,285 417 2 19 83 44 30 161 79 42 267 123 55 447 178 75 619 242 94 822 316 115 1,054 405 139 1,306 494 3 20 84 50 31 163 89 44 272 138 57 452 109 78 627 272 97 834 355 118 1,069 455 142 1,327 555 VENT CONNECTOR CAPACITY COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER (D) — inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 523 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGH T (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND DIAMETER — (D) inches 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 2 174 764 496 223 1,046 653 281 1,371 853 346 1,772 1,080 NA NA NA NA NA NA NA NA NA 4 180 897 616 230 1,231 827 287 1,617 1,081 352 2,069 1,370 NA NA NA NA NA NA NA NA NA 6 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 8 2 186 822 516 238 1,126 696 298 1,478 910 365 1,920 1,150 NA NA NA NA NA NA NA NA NA 4 192 952 644 244 1,307 884 305 1,719 1,150 372 2,211 1,460 471 2,737 1,800 560 3,319 2,180 662 3,957 2,590 6 198 1,050 772 252 1,445 1,072 313 1,902 1,390 380 2,434 1,770 478 3,018 2,180 568 3,665 2,640 669 4,373 3,130 10 2 196 870 536 249 1,195 730 311 1,570 955 379 2,049 1,205 NA NA NA NA NA NA NA NA NA 4 201 997 664 256 1,371 924 318 1,804 1,205 387 2,332 1,535 486 2,887 1,890 581 3,502 2,280 686 4,175 2,710 6 207 1,095 792 263 1,509 1,118 325 1,989 1,455 395 2,556 1,865 494 3,169 2,290 589 3,849 2,760 694 4,593 3,270 15 2 214 967 568 272 1,334 790 336 1,760 1,030 408 2,317 1,305 NA NA NA NA NA NA NA NA NA 4 221 1,085 712 279 1,499 1,006 344 1,978 1,320 416 2,579 1,665 523 3,197 2,060 624 3,881 2,490 734 4,631 2,960 6 228 1,181 856 286 1,632 1,222 351 2,157 1,610 424 2,796 2,025 533 3,470 2,510 634 4,216 3,030 743 5,035 3,600 20 2 223 1,051 596 291 1,443 840 357 1,911 1,095 430 2,533 1,385 NA NA NA NA NA NA NA NA NA 4 230 1,162 748 298 1,597 1,064 365 2,116 1,395 438 2,778 1,765 554 3,447 2,180 661 4,190 2,630 772 5,005 3,130 6 237 1,253 900 307 1,726 1,288 373 2,287 1,695 450 2,984 2,145 567 3,708 2,650 671 4,511 3,190 785 5,392 3,790 30 2 216 1,217 632 286 1,664 910 367 2,183 1,190 461 2,891 1,540 NA NA NA NA NA NA NA NA NA 4 223 1,316 792 294 1,802 1,160 376 2,366 1,510 474 3,110 1,920 619 3,840 2,365 728 4,861 2,860 847 5,606 3,410 6 231 1,400 952 303 1,920 1,410 384 2,524 1,830 485 3,299 2,340 632 4,080 2,875 741 4,976 3,480 860 5,961 4,150 50 2 206 1,479 689 273 2,023 1,007 350 2,659 1,315 435 3,548 1,665 NA NA NA NA NA NA NA NA NA 4 213 1,561 860 281 2,139 1,291 359 2,814 1,685 447 3,730 2,135 580 4,601 2,633 709 5,569 3,185 851 6,633 3,790 6 221 1,631 1,031 290 2,242 1,575 369 2,951 2,055 461 3,893 2,605 594 4,808 3,208 724 5,826 3,885 867 6,943 4,620 100 2 192 1,923 712 254 2,644 1,050 326 3,490 1,370 402 4,707 1,740 NA NA NA NA NA NA NA NA NA 4 200 1,984 888 263 2,731 1,346 336 3,606 1,760 414 4,842 2,220 523 5,982 2,750 639 7,254 3,330 769 8,650 3,950 6 208 2,035 1,064 272 2,811 1,642 346 3,714 2,150 426 4,968 2,700 539 6,143 3,350 654 7,453 4,070 786 8,892 4,810 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — (D ) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,206 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 841 712 1,542 1,200 995 2,093 1,625 1,300 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,360 4,971 3,862 2,790 6,016 4,670 3,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,352 3,120 6,749 5,261 3,800 30 1,658 1,327 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,480 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 8,597 6,986 5,000 10,681 8,648 5,920 13,004 10,499 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 281 458 524 344 3 NA NA 34 NA NA 62 121 131 95 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 NA NA 32 NA NA 57 125 126 89 184 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 NA NA 35 NA NA 64 130 138 100 191 208 144 241 287 197 302 381 256 370 489 328 501 609 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 240 253 150 302 335 196 372 429 252 506 534 308 2 NA NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 NA NA 36 89 91 67 129 144 102 197 217 148 257 299 203 320 398 265 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 NA NA 34 83 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 NA NA 39 87 100 70 127 160 109 193 243 157 255 333 215 331 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 325 165 306 425 217 390 538 276 546 664 336 2 52 59 36 82 103 64 120 163 101 182 252 144 243 346 197 317 453 259 400 574 331 558 709 403 3 55 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 51 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 819 425 3 54 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 49 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 623 293 376 793 375 520 983 458 3 52 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 140 205 585 192 269 774 249 345 993 321 476 1,236 393 2 48 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 788 299 358 1,011 383 490 1,259 469 3 51 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 801 339 368 1,027 431 506 1,280 527 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) TYPE B DOUBLE - WALL COMMON VENT DIAMETER — ( D ) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 113 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 118 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 529 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 633 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 133 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 203 109 491 270 129 633 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 26 47 29 40 87 53 57 140 86 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 93 54 57 153 87 76 261 129 103 366 184 123 498 247 145 652 321 168 825 407 3 27 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 164 125 511 229 153 658 297 184 824 375 2 25 55 31 39 105 55 56 174 89 74 299 134 103 419 192 128 558 260 156 718 339 187 900 432 3 26 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 159 760 382 190 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 25 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 26 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 192 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 25 60 32 38 122 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 26 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 405 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 24 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 26 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 24 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 956 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 742 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,089 606 1,905 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 2,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. mm, 1 British thermal unit per hour = 0.2931 W. Numbr of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT ( H ) (feet) CONNECTOR RISE SINGLE - WALL METAL VENT CONNECTOR DIAMETER ( D ) — inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 366 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 186 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 269 381 634 348 519 793 437 8 1 NA NA 21 NA NA 40 NA NA 68 195 208 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 343 489 244 420 640 317 569 813 403 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 30 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 368 586 289 466 755 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 921 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 365 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 492 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 806 320 429 1,058 425 596 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1,090 466 610 1,386 597 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,210 488 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT HEIGHT ( H ) (feet) MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 190 81 NA 276 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 66 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA 821 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,885 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. mm, 1 British thermal unit per hour = 0.2931 W. Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTOR CAPACITY TOTAL VENT HEIGHT ( H ) (feet) CONNECTOR RISE ( R ) (feet) VENT CONNECTOR DIAMETER — ( D ) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 – 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 64 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 COMMON VENT CAPACITY TOTAL VENT HEIGHT ( H ) (feet) COMMON VENT DIAMETER — ( D) i nches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. � � � � Number of Appliances Single Appliance Type Draft hood equipped Appliance Vent Connection Connected directly to pipe or vent HEIGHT ( H ) (feet) LATERAL ( L ) (feet) VENT DIAMETER — ( D ) inches 3 4 5 6 7 8 10 12 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 0 39 70 116 170 232 312 500 750 2 31 55 94 141 194 260 415 620 5 28 51 88 128 177 242 390 600 8 0 42 76 126 185 252 340 542 815 2 32 61 102 154 210 284 451 680 5 29 56 95 141 194 264 430 648 10 24 49 86 131 180 250 406 625 10 0 45 84 138 202 279 372 606 912 2 35 67 111 168 233 311 505 760 5 32 61 104 153 215 289 480 724 10 27 54 94 143 200 274 455 700 15 NA 46 84 130 186 258 432 666 15 0 49 91 151 223 312 420 684 1,040 2 39 72 122 186 260 350 570 865 5 35 67 110 170 240 325 540 825 10 30 58 103 158 223 308 514 795 15 NA 50 93 144 207 291 488 760 20 NA NA 82 132 195 273 466 726 20 0 53 101 163 252 342 470 770 1,190 2 42 80 136 210 286 392 641 990 5 38 74 123 192 264 364 610 945 10 32 65 115 178 246 345 571 910 15 NA 55 104 163 228 326 550 870 20 NA NA 91 149 214 306 525 832 30 0 56 108 183 276 384 529 878 1,370 2 44 84 148 230 320 441 730 1,140 5 NA 78 137 210 296 410 694 1,080 10 NA 68 125 196 274 388 656 1,050 15 NA NA 113 177 258 366 625 1,000 20 NA NA 99 163 240 344 596 960 30 NA NA NA NA 192 295 540 890 50 0 NA 120 210 310 443 590 980 1,550 2 NA 95 171 260 370 492 820 1,290 5 NA NA 159 234 342 474 780 1,230 10 NA NA 146 221 318 456 730 1,190 15 NA NA NA 200 292 407 705 1,130 20 NA NA NA 185 276 384 670 1,080 30 NA NA NA NA 222 330 605 1,010 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.2(6) EXTERIOR MASONRY CHIMNEY Number of Appliances Single Appliance Type NAT Appliance Vent Connection Type B double - wall connector MINIMUM ALLOWABLE INPUT RATING OF SPACE - HEATING APPLIANCE IN THOUSANDS OF BTU PER HOUR VENT HEIGHT (feet) Internal area of chimney (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA NA NA NA 233 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches)HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA 419 445 485 50 NA NA NA NA NA NA NA 763 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA 215 259 349 8 NA NA NA NA 197 226 264 352 10 NA NA NA NA 214 245 278 358 15 NA NA NA NA NA 296 331 398 20 NA NA NA NA NA 352 387 457 30 NA NA NA NA NA NA 507 581 50 NA NA NA NA NA NA NA NA 5 to 16°F Local 99% Winter Design Temperature: 5 to 16°F 6 NA NA NA NA NA NA NA 416 8 NA NA NA NA NA NA 312 423 10 NA NA NA NA NA 289 331 430 15 NA NA NA NA NA NA 393 485 20 NA NA NA NA NA NA 450 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA 972 - 10 to 4°F Local 99% Winter Design Temperature: - 10 to 4°F 6 NA NA NA NA NA NA NA 484 8 NA NA NA NA NA NA NA 494 10 NA NA NA NA NA NA NA 513 15 NA NA NA NA NA NA NA 586 20 NA NA NA NA NA NA NA 650 30 NA NA NA NA NA NA NA 805 50 NA NA NA NA NA NA NA 1,003 - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.2.3 Vent offsets. Single - appliance venting configurations with zero (0) lateral lengths in Tables 504.2(1), 504.2(2) and 504.2(5) shall not have elbows in the venting system. Single - appliance venting configurations with lateral lengths include two 90 - degree (1.57 rad) elbows. For each addi tional elbow up to and including 45 degrees (0.79 rad), the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each additional elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1 .57 rad), the maximum cap acity listed in the venting tables shall be reduced by 10 percent. Where multiple offsets occur in a vent, the total lateral length of all offsets combined shall not exceed that specified in Tables 504.2(1) through 504.2(5). 504.2.4 Zero lateral. Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top outlet draft hood or flue collar. 504.2.5 Reserved. 504.2.6 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent capacity (FAN Min) determi ned from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 504.2.7 Liner system sizing and connections . List ed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.2(1) or 504.2(2) for Type B vents with the maximum capacity reduced by 20 percent (0.80 × maximum capacity ) and the minimum capacity as shown in Table 504.2( 1) or 504.2(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 504.2.3. The 20 - percent reduction for corrugated metallic chimney liner systems includes an allow ance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Connections between chimney liners and listed double - wall connectors shall be made with listed adapters designed for such pur- pose. 504.2.8 Vent area and diameter. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the v ertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area or draft hood outlet area unless designed in accordance with approved engineering methods. 504.2.9 Chimney and vent locations. Tables 504.2(1), 504.2(2), 504.2(3), 504.2(4) and 504.2(5) shall be used only for chimneys and vents not exposed to the outdoors below the roof line. Table 504.2(3) in combination with Table 504.2(6) shall be used for clay - tile - lined exterior masonry chim neys, provided that all of the following are met: 1. Vent connector is a Type B double - wall. 2. Vent connector length is limited to 1 1 / 2 feet for each inch ( 18 mm for each mm ) of vent connector diameter. 3. The appliance is draft hood equipped. 4. The inpu t rating is less than the maximum capacity given by Table 504.2(3). 5. For a water heater, the outdoor design temperature is not less than 5°F ( - 15°C). 6. For a space - heating appliance, the input rating is greater than the minimum capacity given by Table 5 04.2(6). Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: The installation of vents serving listed appliances shall be permitted to be in accordance with the appliance man ufac- turer’s instructions and the terms of the listing. 504.2.10 Corrugated vent connector size. Corrugated vent connectors shall be not smaller than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. 504.2.1 1 Vent connector size limitation. Vent connectors shall not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 504.2.12 Component commingling. In a sing le run of vent or vent connector, different diameters and types of vent and connector components shall be permitted to be used, provided that all such sizes and types are permitted by the tables. 504.2.13 Draft hood conversion accessories. Draft hood conve rsion accessories for use with masonry chimneys venting listed Cat- egory I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed acces- sories. 504.2.14 Table interpolation. Interpolation shal l be permitted in calculating capacities for vent dimensions that fall between the table entries. 504.2.15 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.2.16 Engineering calculations. For vent heights less tha n 6 feet ( 1828.8 mm ) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. Signed and sealed calculations shall be submitted with filing application. 504.2.17 Height entries. Where the actual height of a vent falls between entries in the height column of the applicable table in Tables 504.2(1) through 504.2(6), either interpolation shall be used or the lower appliance input rating shown in the table entries shall be used for F AN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. 504.3 Application of multiple appliance vent Tables 504.3(1) through 504.3( 7b) . The application of Tables 504.3(1) through 504.3(7) shall be subject to the requirements of Sections 504.3.1 through 504.3.28 . TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 TABLE 504.3(1) TYPE B DOUBLE - WALL VENT Number of Appliances Single Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NAT FAN NA T FAN NA T FAN N A T Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Ma x Mi n M ax Max Mi n Ma x Ma x M i n Max Ma x Mi n Ma x M a x 6 1 22 37 26 35 66 46 46 10 6 72 58 16 4 10 4 77 22 5 142 92 296 185 1 0 9 376 237 128 466 2 8 9 2 23 41 31 37 75 55 48 12 1 86 60 18 3 12 4 79 25 3 168 95 333 220 1 1 2 424 282 131 526 3 4 5 3 24 44 35 38 81 62 49 13 2 96 62 19 9 13 9 82 27 5 189 97 363 248 1 1 4 463 317 134 575 3 8 6 8 1 22 40 27 35 72 48 49 11 4 76 64 17 6 10 9 84 24 3 148 10 0 320 194 1 1 8 408 248 138 507 3 0 3 2 23 44 32 36 80 57 51 12 8 90 66 19 5 12 9 86 26 9 175 10 3 356 230 1 2 454 294 141 564 3 5 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA 1 8 3 24 47 36 37 87 64 53 13 9 10 1 67 21 0 14 5 88 29 0 198 10 5 384 258 1 2 3 492 330 143 612 4 0 2 10 1 22 43 28 34 78 50 49 12 3 78 65 18 9 11 3 89 25 7 154 10 6 341 200 1 2 5 436 257 146 542 3 1 4 2 23 47 33 36 86 59 51 13 6 93 67 20 6 13 4 91 28 2 182 10 9 374 238 1 2 8 479 305 149 596 3 7 2 3 24 50 37 37 92 67 52 14 6 10 4 69 22 0 15 0 94 30 3 205 11 1 402 268 1 3 1 515 342 152 642 4 1 7 15 1 21 50 30 33 89 53 47 14 2 83 64 22 0 12 0 88 29 8 163 11 0 389 214 1 3 4 493 273 162 609 3 3 3 2 22 53 35 35 96 63 49 15 3 99 66 23 5 14 2 91 32 0 193 11 2 419 253 1 3 7 532 323 165 658 3 9 4 3 24 55 40 36 10 2 71 51 16 3 11 1 68 24 8 16 0 93 33 9 218 11 5 445 286 1 4 0 565 365 167 700 4 4 4 20 1 21 54 31 33 99 56 46 15 7 87 62 24 6 12 5 86 33 4 171 10 7 436 224 1 3 1 552 285 158 681 3 4 7 2 22 57 37 34 10 5 66 48 16 7 10 4 64 25 9 14 8 89 35 4 202 11 0 463 265 1 3 4 587 339 161 725 4 1 4 3 23 60 42 35 11 0 74 50 17 6 11 6 66 27 1 16 8 91 37 1 228 11 3 486 300 1 3 7 618 383 164 764 4 6 6 30 1 20 62 33 31 11 3 59 45 18 1 93 60 28 8 13 4 93 39 1 182 10 3 512 238 1 2 5 649 305 151 802 3 7 2 2 21 64 39 33 11 8 70 47 19 0 11 0 62 29 9 15 8 95 40 8 215 10 5 535 282 1 2 9 679 360 155 840 4 3 9 3 22 66 44 34 12 3 79 48 19 8 12 4 64 30 9 17 8 99 42 3 242 10 8 555 317 1 3 2 706 405 158 874 4 9 4 50 1 19 71 36 30 13 3 64 43 21 6 10 1 57 34 9 14 5 89 47 7 197 97 627 257 1 2 0 797 330 144 984 4 0 3 2 21 73 43 32 13 7 76 45 22 3 11 9 59 35 8 17 2 91 49 0 234 10 0 645 306 1 2 3 820 392 148 1,01 4 4 7 8 3 22 75 48 33 14 1 86 46 22 9 13 4 61 36 6 19 4 93 50 2 263 10 3 661 343 4 1 2 6 842 441 151 1,04 3 5 3 8 100 1 18 82 37 28 15 8 66 40 26 2 10 4 53 44 2 15 0 73 61 1 204 91 810 266 1 1 2 1,038 341 135 1,28 5 4 1 7 2 19 83 44 30 16 1 79 42 26 7 12 3 55 44 7 17 8 75 61 9 242 94 822 316 1 1 5 1,054 405 139 1,30 6 4 9 4 3 20 84 50 31 16 3 89 44 27 2 13 8 57 45 2 10 9 78 62 7 272 97 834 955 1 1 8 1,069 455 142 1,32 7 5 5 5 COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater CHIMNEYS AND VENTS 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA 334 398 393 334 0 50 NA NA NA NA NA 714 707 579 100 NA NA NA NA NA NA NA 1,600 27 °F to 36°F Local 99% Winter Design Temperature: 27 °F to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA 111 142 183 233 253 274 305 20 NA NA 187 230 284 307 330 362 30 NA NA NA 330 319 419 445 485 50 NA NA NA NA NA 672 705 763 100 NA NA NA NA NA NA NA 1,554 (continued) T ABLE 504.3(7b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17°F to 26°F Local 99% Winter Design Temperature: 17°F to 26°F 6 0 55 99 141 182 215 259 349 8 52 74 111 154 197 226 264 352 10 NA 90 125 169 214 245 278 358 15 NA NA 167 212 263 296 331 398 20 NA NA 212 258 316 352 387 457 30 NA NA NA 362 429 470 507 581 50 NA NA NA NA NA 723 766 862 100 NA NA NA NA NA NA NA 1,669 5°F to 16°F Local 99% Winter Design Temperature: 5°F to 16°F 6 NA 78 121 166 214 252 301 416 8 NA 94 135 182 230 269 312 423 10 NA 111 149 198 250 289 331 430 6 92 81 65 140 116 103 204 161 147 309 248 200 404 314 260 547 434 335 672 520 410 8 101 90 73 155 129 114 224 178 163 339 275 223 444 348 290 602 480 378 740 577 465 10 110 97 79 169 141 124 243 194 178 367 299 242 477 377 315 649 522 405 800 627 495 15 125 112 91 195 164 144 283 228 206 427 352 280 556 444 365 753 612 465 924 733 565 20 136 123 102 215 183 160 314 255 229 475 394 310 621 499 405 842 688 423 1,035 826 640 30 152 138 118 244 210 185 361 297 266 547 459 360 720 585 470 979 808 605 1,209 975 740 50 167 153 134 279 244 214 421 353 310 641 547 423 854 706 550 1,164 977 705 1,451 1,188 860 100 175 163 NA 311 277 NA 489 421 NA 751 658 479 1,025 873 625 1,408 1,215 800 1,784 1,502 975 (continued) TABLE 504.3(1) - continued TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIG HT (H) (feet) CONNEC TOR RISE (R) (feet) 12 14 16 18 20 22 24 APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T FAN NA T Min Max Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Ma x Ma x Mi n Max Ma x Mi n Ma x Ma x 6 2 174 764 496 22 3 1,0 46 563 28 1 1,3 71 853 34 5 1,7 32 1,0 80 N A NA NA N A NA NA N A NA NA 4 180 897 616 23 0 1,2 31 827 28 7 1,6 17 1,0 81 35 2 2,0 69 1,3 70 N A NA NA N A NA NA N A NA NA 6 NA N A NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA N A NA NA 8 2 186 822 516 23 8 1,1 26 696 29 8 1,4 78 910 36 5 1,9 20 1,1 50 N A NA NA N A NA NA N A NA NA 4 192 952 644 21 4 1,3 07 884 30 5 1,7 19 1,1 50 37 2 2,2 11 1,4 60 47 1 2,7 37 1,8 00 56 0 3,31 9 2,1 80 66 2 3,9 57 2,5 90 CHIMNEYS AND VENTS 6 198 1,05 0 772 25 2 1,4 45 1,0 72 31 3 1,9 02 1,3 90 38 0 2,4 34 1,8 70 47 8 3,0 18 2,1 80 56 8 3,66 5 2,6 40 66 8 4,3 73 3,1 30 10 2 196 870 536 24 9 1,1 95 730 31 1 1,5 70 955 37 9 2,0 49 1,2 05 N A NA NA N A NA NA N A NA NA 4 201 997 664 25 6 1,3 71 924 31 8 1,8 04 1,2 05 38 7 2,3 32 1,5 35 48 6 2,8 87 1,8 90 58 1 3,50 2 2,2 80 68 6 4,1 75 2,7 10 6 207 1,09 5 792 26 3 1,5 09 1,1 18 32 5 1,9 89 1,4 55 39 5 2,5 56 1,8 65 49 4 2,3 09 2,2 90 58 9 3,84 9 2,7 60 69 4 4,5 93 3,2 70 15 2 214 967 568 23 2 1,3 51 790 33 6 1,7 60 1,2 05 40 8 2,3 17 1,3 05 N A NA NA N A NA NA N A NA NA 4 221 1,08 5 715 27 9 1,4 99 1,0 06 34 4 1,9 78 1,3 20 41 6 2,5 79 1,6 65 52 3 3,1 97 2,0 50 62 4 3,88 1 2,4 90 73 4 4,6 31 2,9 60 6 228 1,18 1 856 28 6 1,6 32 1,2 22 35 1 2,1 57 1,6 10 42 4 2,7 96 2,0 25 53 3 3,4 70 2,5 10 63 4 4,21 6 3,0 90 74 3 5,0 35 3,6 00 20 2 223 1,05 1 996 29 1 1,4 63 840 35 7 1,9 11 1,0 95 43 0 2,5 33 1,3 85 N A NA NA N A NA NA N A NA NA 4 230 1,16 2 748 29 8 1,5 97 1,0 54 36 5 2,1 16 1,3 95 43 8 2,7 78 1,7 65 55 4 3,4 47 2,1 80 65 1 4,19 0 2,6 30 77 2 5,0 05 3,1 90 6 237 1,25 3 900 30 7 1,7 26 1,2 88 37 3 2,2 87 1,6 95 45 0 2,9 84 2,1 45 56 7 3,7 08 2,6 90 67 1 4,51 1 3,1 90 78 5 5,3 92 3,7 90 30 2 216 1,21 7 632 28 6 1,6 64 910 36 7 2,1 83 1,1 90 46 1 2,8 91 1,3 40 N A NA NA N A NA NA N A NA NA 4 223 1,31 6 792 29 4 1,8 02 1,1 60 37 6 2,3 66 1,5 10 47 4 3,1 10 1,9 20 61 9 3,8 40 2,3 65 72 8 4,86 1 2,8 60 84 7 5,6 06 3,4 10 6 231 1,40 0 952 30 3 1,9 20 1,4 10 38 4 2,5 24 1,8 30 48 5 3,2 99 2,3 40 63 2 4,0 80 2,8 75 74 0 4,97 6 3,4 80 86 0 5,9 51 4,1 50 CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater CHIMNEYS AND VENTS 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA 334 398 393 334 0 50 NA NA NA NA NA 714 707 579 100 NA NA NA NA NA NA NA 1,600 27 °F to 36°F Local 99% Winter Design Temperature: 27 °F to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA 111 142 183 233 253 274 305 20 NA NA 187 230 284 307 330 362 30 NA NA NA 330 319 419 445 485 50 NA NA NA NA NA 672 705 763 100 NA NA NA NA NA NA NA 1,554 (continued) T ABLE 504.3(7b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17°F to 26°F Local 99% Winter Design Temperature: 17°F to 26°F 6 0 55 99 141 182 215 259 349 8 52 74 111 154 197 226 264 352 10 NA 90 125 169 214 245 278 358 15 NA NA 167 212 263 296 331 398 20 NA NA 212 258 316 352 387 457 30 NA NA NA 362 429 470 507 581 50 NA NA NA NA NA 723 766 862 100 NA NA NA NA NA NA NA 1,669 5°F to 16°F Local 99% Winter Design Temperature: 5°F to 16°F 6 NA 78 121 166 214 252 301 416 8 NA 94 135 182 230 269 312 423 10 NA 111 149 198 250 289 331 430 CHIMNEYS AND VENTS 15 NA NA 193 247 305 346 393 485 20 NA NA NA 293 360 408 450 547 30 NA NA NA 377 450 531 580 682 50 NA NA NA NA NA 797 853 972 100 NA NA NA NA NA NA NA 1,833 - 10°F to 4°F Local 99% Winter Design Temperature: - 10°F to 4°F 6 NA NA 145 196 249 296 349 484 8 NA NA 159 213 269 320 371 494 10 NA NA 175 231 292 339 397 513 15 NA NA NA 283 351 404 457 586 20 NA NA NA 333 408 468 528 650 30 NA NA NA NA NA 603 667 805 50 NA NA NA NA NA NA 955 1,003 100 NA NA NA NA NA NA NA NA - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615 .16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.3.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent connector shall be determined using the NAT Max column. 2. The maximum capacity of the vertical vent or chimney shall be determined using the FAN+NAT column when the seco nd appliance is a fan - assisted appliance, or the NAT+NAT column when the second appliance is equipped with a draft hood. 3. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance. 3.1. The minimum capacity of the vent co nnector shall be determined using the FAN Min column. 3.2. The FAN+FAN column shall be used where the second appliance is a fan - assisted appliance, and the FAN+NAT column shall be used where the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.3.2 Connector length limit. The vent connector shall be routed to the vent utilizing the shortest possible route. Except as provided in Section 504.3.3, the maximum vent connector horizontal length shall be 1 1 / 2 feet for each inch ( 18 mm for each mm ) of connector diameter as shown in Table 5 04.3.2 . TABLE 504.3.2 MAXIMUM VENT CONNECTOR LENGTH CONNECTOR DIAMETER (inches) CONNECTOR MAXIMUM HORIZONTAL LENGTH (feet) 3 4 1 / 2 4 6 CHIMNEYS AND VENTS 5 7 1 / 2 6 9 7 10 1 / 2 8 12 9 13 1 / 2 10 15 12 18 14 21 16 24 18 27 20 30 22 33 24 36 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 504.3.3 Connectors with longer lengths. Connectors with longer horizontal lengths than those listed in Section 504.3.2 are permitted under the following conditions: 1. The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length allowed by Section 504.3.2. For example, the maximum length listed in Table 504.3.2 for a 4 - inch ( 101.6 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet ( 1828.8 mm) but not exceeding 12 feet ( 3657.6 mm), the maximum ca pacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet ( 3657.6 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent ( 0.80 × maximum vent capacity). 2. For a connector serving a fan - assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double - wall connectors, Table 504.2(1) shall be used. For single - w all connectors, Table 504.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single - appliance vent, as if the other appliances were not present. 504.3.4 Vent connector manifold. Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 × maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent connector manifold ( Lm ) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent connector manifold diameter (D) (see Figure 504.3.4). 504.3.5 Common vertical vent offset. Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 504.3.6. The horizonta l length of the common vent offset (Lo) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D) . Where multiple offsets occur in a common vent, the total horizontal length of all offsets combined shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D ). 504.3.6 Elbows in vents. For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent . For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. CHIMNEYS AND VENTS FIGURE 504.3.4 USE OF A MANIFOLD COMMON VENT CONNECTOR 504.3.7 Elbows in connectors. The vent connector capacities listed in the common vent sizing tables include allowance for two 90 - degree (1.57 rad) elbows. For each additional elbow up to and including 45 degrees (0.79 rad), the maximum vent connector capac ity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. 50 4.3.8 Common vent minimum size. The cross - sectional area of the common vent shall be equal to or greater than the cross - sectional area of the largest connector. 504.3.9 Common vent fittings. At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors. CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater CHIMNEYS AND VENTS 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA 334 398 393 334 0 50 NA NA NA NA NA 714 707 579 100 NA NA NA NA NA NA NA 1,600 27 °F to 36°F Local 99% Winter Design Temperature: 27 °F to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA 111 142 183 233 253 274 305 20 NA NA 187 230 284 307 330 362 30 NA NA NA 330 319 419 445 485 50 NA NA NA NA NA 672 705 763 100 NA NA NA NA NA NA NA 1,554 (continued) T ABLE 504.3(7b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17°F to 26°F Local 99% Winter Design Temperature: 17°F to 26°F 6 0 55 99 141 182 215 259 349 8 52 74 111 154 197 226 264 352 10 NA 90 125 169 214 245 278 358 15 NA NA 167 212 263 296 331 398 20 NA NA 212 258 316 352 387 457 30 NA NA NA 362 429 470 507 581 50 NA NA NA NA NA 723 766 862 100 NA NA NA NA NA NA NA 1,669 5°F to 16°F Local 99% Winter Design Temperature: 5°F to 16°F 6 NA 78 121 166 214 252 301 416 8 NA 94 135 182 230 269 312 423 10 NA 111 149 198 250 289 331 430 CHIMNEYS AND VENTS 15 NA NA 193 247 305 346 393 485 20 NA NA NA 293 360 408 450 547 30 NA NA NA 377 450 531 580 682 50 NA NA NA NA NA 797 853 972 100 NA NA NA NA NA NA NA 1,833 - 10°F to 4°F Local 99% Winter Design Temperature: - 10°F to 4°F 6 NA NA 145 196 249 296 349 484 8 NA NA 159 213 269 320 371 494 10 NA NA 175 231 292 339 397 513 15 NA NA NA 283 351 404 457 586 20 NA NA NA 333 408 468 528 650 30 NA NA NA NA NA 603 667 805 50 NA NA NA NA NA NA 955 1,003 100 NA NA NA NA NA NA NA NA - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615 .16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.3.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent connector shall be determined using the NAT Max column. 2. The maximum capacity of the vertical vent or chimney shall be determined using the FAN+NAT column when the seco nd appliance is a fan - assisted appliance, or the NAT+NAT column when the second appliance is equipped with a draft hood. 3. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance. 3.1. The minimum capacity of the vent co nnector shall be determined using the FAN Min column. 3.2. The FAN+FAN column shall be used where the second appliance is a fan - assisted appliance, and the FAN+NAT column shall be used where the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.3.2 Connector length limit. The vent connector shall be routed to the vent utilizing the shortest possible route. Except as provided in Section 504.3.3, the maximum vent connector horizontal length shall be 1 1 / 2 feet for each inch ( 18 mm for each mm ) of connector diameter as shown in Table 5 04.3.2 . TABLE 504.3.2 MAXIMUM VENT CONNECTOR LENGTH CONNECTOR DIAMETER (inches) CONNECTOR MAXIMUM HORIZONTAL LENGTH (feet) 3 4 1 / 2 4 6 CHIMNEYS AND VENTS 5 7 1 / 2 6 9 7 10 1 / 2 8 12 9 13 1 / 2 10 15 12 18 14 21 16 24 18 27 20 30 22 33 24 36 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 504.3.3 Connectors with longer lengths. Connectors with longer horizontal lengths than those listed in Section 504.3.2 are permitted under the following conditions: 1. The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length allowed by Section 504.3.2. For example, the maximum length listed in Table 504.3.2 for a 4 - inch ( 101.6 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet ( 1828.8 mm) but not exceeding 12 feet ( 3657.6 mm), the maximum ca pacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet ( 3657.6 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent ( 0.80 × maximum vent capacity). 2. For a connector serving a fan - assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double - wall connectors, Table 504.2(1) shall be used. For single - w all connectors, Table 504.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single - appliance vent, as if the other appliances were not present. 504.3.4 Vent connector manifold. Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 × maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent connector manifold ( Lm ) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent connector manifold diameter (D) (see Figure 504.3.4). 504.3.5 Common vertical vent offset. Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 504.3.6. The horizonta l length of the common vent offset (Lo) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D) . Where multiple offsets occur in a common vent, the total horizontal length of all offsets combined shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D ). 504.3.6 Elbows in vents. For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent . For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. CHIMNEYS AND VENTS FIGURE 504.3.4 USE OF A MANIFOLD COMMON VENT CONNECTOR 504.3.7 Elbows in connectors. The vent connector capacities listed in the common vent sizing tables include allowance for two 90 - degree (1.57 rad) elbows. For each additional elbow up to and including 45 degrees (0.79 rad), the maximum vent connector capac ity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. 50 4.3.8 Common vent minimum size. The cross - sectional area of the common vent shall be equal to or greater than the cross - sectional area of the largest connector. 504.3.9 Common vent fittings. At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors. CHIMNEYS AND VENTS 504.3.9.1 Tee and wye fittings. Tee and wye fittings connected to a common gas vent shall be considered as part of the common gas vent and shall be constructed of materials consistent with that of the common gas vent. 504.3.10 Reserved. 504.3.11 Connector rise measurement. Connector ris e (R) for each appliance connector shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together. 504.3.12 Vent height measurement. For multiple units of appliances all located on one floor, availabl e total height (H) shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent. 504.3.13 Reserved. 504.3.14 Reserved. 504.3.15 Reserved. 504.3.16 Reserved. 504.3.17 Vertical vent maximum size. Where two or more appliances are connected to a vertical vent or chim- ney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area or draft hood out let area unless designed in accordance with approved engineering methods. 504.3.18 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent con- nector capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined from the tables shall be greater than the highest appliance input rating. 504.3.19 Liner system sizing and connections. Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.3(1) or 504.3(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 × maximum capacity) and the minimum capacity as shown in Table 504.3(1) or 504.3(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Sections 504.3.5 and 504.3.6. The 20 - percent reduction for corrugated metallic chimney liner syste ms includes an allowance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Where double - wall connectors are required, tee and wye fittings used to connect to the common vent chimney liner shall be listed double - wall fittings. Connec tions between chimney liners and listed double - wall fittings shall be made with listed adapter fittings designed for such purpose. 504.3.20 Chimney and vent location. Tables 504.3(1), 504.3(2), 504.3(3), 504.3(4 ), and 504.3(5) shall be used only for chimne ys and vents not exposed to the outdoors below the roof line. Tables 504.3(6a), 504.3(6b), 504.3(7a) and 504.3(7b) shall be used for clay - tile - lined exterior masonry chimneys, provided that all of the following con- ditions are met: 1. Vent connectors are Type B double wall . 2. Not less than one appliance is draft hood equipped. 3. The combined appliance input rating is less than the maximum capacity given by Table 504.3(6a) for NAT+NAT or Table 504.3(7a) for FAN+NAT. 4. The input rating of each space - hea ting appliance is greater than the minimum input rating given by Table 504.3(6b) for NAT+NAT or Table 504.3(7b) for FAN+NAT. 5. The vent connector sizing is in accordance with Table 504.3(3). 504.3.21 Connector maximum and minimum size. Vent connectors sha ll not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. Vent connectors for draft hood - equipped appliances shall not be smaller than the draft hood out let diameter. Where a vent connector size(s) determined from the tables for a fan - assisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size(s) shall be permitted provided that the installation complies with all of the foll owing conditions: CHIMNEYS AND VENTS 50 2 206 1,47 9 689 27 3 2,0 23 1,0 07 35 0 2,6 59 1,3 15 43 5 3,5 48 1,6 65 N A NA NA N A NA NA N A NA NA 4 213 1,56 1 860 28 1 2,1 99 1,2 91 35 9 2,8 14 1,6 85 44 7 3,7 30 2,1 35 58 0 4,6 01 2,6 33 70 9 5,56 0 3,1 85 85 1 6,6 33 3,7 90 6 221 1,63 1 1,0 31 29 0 2,2 42 1,5 75 36 9 2,9 51 1,0 55 46 1 3,8 93 2,6 05 59 4 4,8 08 3,2 08 72 4 5,82 0 3,8 85 86 7 6,9 43 4,6 20 100 2 192 1,92 3 712 25 4 2,6 44 1,0 50 32 6 3,4 90 1,3 70 40 2 4,7 07 1,7 40 N A NA NA N A NA NA N A NA NA 4 200 1,98 4 888 26 3 2,7 31 1,3 46 33 6 3,6 06 1,7 60 41 4 4,8 42 2,2 20 52 3 5,9 82 2,7 50 63 9 7,25 4 3,3 30 76 9 8,6 30 3,9 50 6 208 2,03 5 1,0 64 27 2 2,8 11 1,6 42 34 6 3,7 14 2,1 50 42 6 4,9 68 2,7 00 59 9 6,1 43 3,3 50 65 4 7,45 3 4,0 70 78 6 8,8 92 4,8 10 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater CHIMNEYS AND VENTS 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA 334 398 393 334 0 50 NA NA NA NA NA 714 707 579 100 NA NA NA NA NA NA NA 1,600 27 °F to 36°F Local 99% Winter Design Temperature: 27 °F to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA 111 142 183 233 253 274 305 20 NA NA 187 230 284 307 330 362 30 NA NA NA 330 319 419 445 485 50 NA NA NA NA NA 672 705 763 100 NA NA NA NA NA NA NA 1,554 (continued) T ABLE 504.3(7b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17°F to 26°F Local 99% Winter Design Temperature: 17°F to 26°F 6 0 55 99 141 182 215 259 349 8 52 74 111 154 197 226 264 352 10 NA 90 125 169 214 245 278 358 15 NA NA 167 212 263 296 331 398 20 NA NA 212 258 316 352 387 457 30 NA NA NA 362 429 470 507 581 50 NA NA NA NA NA 723 766 862 100 NA NA NA NA NA NA NA 1,669 5°F to 16°F Local 99% Winter Design Temperature: 5°F to 16°F 6 NA 78 121 166 214 252 301 416 8 NA 94 135 182 230 269 312 423 10 NA 111 149 198 250 289 331 430 CHIMNEYS AND VENTS 15 NA NA 193 247 305 346 393 485 20 NA NA NA 293 360 408 450 547 30 NA NA NA 377 450 531 580 682 50 NA NA NA NA NA 797 853 972 100 NA NA NA NA NA NA NA 1,833 - 10°F to 4°F Local 99% Winter Design Temperature: - 10°F to 4°F 6 NA NA 145 196 249 296 349 484 8 NA NA 159 213 269 320 371 494 10 NA NA 175 231 292 339 397 513 15 NA NA NA 283 351 404 457 586 20 NA NA NA 333 408 468 528 650 30 NA NA NA NA NA 603 667 805 50 NA NA NA NA NA NA 955 1,003 100 NA NA NA NA NA NA NA NA - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615 .16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.3.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent connector shall be determined using the NAT Max column. 2. The maximum capacity of the vertical vent or chimney shall be determined using the FAN+NAT column when the seco nd appliance is a fan - assisted appliance, or the NAT+NAT column when the second appliance is equipped with a draft hood. 3. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance. 3.1. The minimum capacity of the vent co nnector shall be determined using the FAN Min column. 3.2. The FAN+FAN column shall be used where the second appliance is a fan - assisted appliance, and the FAN+NAT column shall be used where the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.3.2 Connector length limit. The vent connector shall be routed to the vent utilizing the shortest possible route. Except as provided in Section 504.3.3, the maximum vent connector horizontal length shall be 1 1 / 2 feet for each inch ( 18 mm for each mm ) of connector diameter as shown in Table 5 04.3.2 . TABLE 504.3.2 MAXIMUM VENT CONNECTOR LENGTH CONNECTOR DIAMETER (inches) CONNECTOR MAXIMUM HORIZONTAL LENGTH (feet) 3 4 1 / 2 4 6 CHIMNEYS AND VENTS 5 7 1 / 2 6 9 7 10 1 / 2 8 12 9 13 1 / 2 10 15 12 18 14 21 16 24 18 27 20 30 22 33 24 36 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 504.3.3 Connectors with longer lengths. Connectors with longer horizontal lengths than those listed in Section 504.3.2 are permitted under the following conditions: 1. The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length allowed by Section 504.3.2. For example, the maximum length listed in Table 504.3.2 for a 4 - inch ( 101.6 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet ( 1828.8 mm) but not exceeding 12 feet ( 3657.6 mm), the maximum ca pacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet ( 3657.6 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent ( 0.80 × maximum vent capacity). 2. For a connector serving a fan - assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double - wall connectors, Table 504.2(1) shall be used. For single - w all connectors, Table 504.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single - appliance vent, as if the other appliances were not present. 504.3.4 Vent connector manifold. Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 × maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent connector manifold ( Lm ) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent connector manifold diameter (D) (see Figure 504.3.4). 504.3.5 Common vertical vent offset. Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 504.3.6. The horizonta l length of the common vent offset (Lo) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D) . Where multiple offsets occur in a common vent, the total horizontal length of all offsets combined shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D ). 504.3.6 Elbows in vents. For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent . For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. CHIMNEYS AND VENTS FIGURE 504.3.4 USE OF A MANIFOLD COMMON VENT CONNECTOR 504.3.7 Elbows in connectors. The vent connector capacities listed in the common vent sizing tables include allowance for two 90 - degree (1.57 rad) elbows. For each additional elbow up to and including 45 degrees (0.79 rad), the maximum vent connector capac ity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. 50 4.3.8 Common vent minimum size. The cross - sectional area of the common vent shall be equal to or greater than the cross - sectional area of the largest connector. 504.3.9 Common vent fittings. At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors. CHIMNEYS AND VENTS 504.3.9.1 Tee and wye fittings. Tee and wye fittings connected to a common gas vent shall be considered as part of the common gas vent and shall be constructed of materials consistent with that of the common gas vent. 504.3.10 Reserved. 504.3.11 Connector rise measurement. Connector ris e (R) for each appliance connector shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together. 504.3.12 Vent height measurement. For multiple units of appliances all located on one floor, availabl e total height (H) shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent. 504.3.13 Reserved. 504.3.14 Reserved. 504.3.15 Reserved. 504.3.16 Reserved. 504.3.17 Vertical vent maximum size. Where two or more appliances are connected to a vertical vent or chim- ney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area or draft hood out let area unless designed in accordance with approved engineering methods. 504.3.18 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent con- nector capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined from the tables shall be greater than the highest appliance input rating. 504.3.19 Liner system sizing and connections. Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.3(1) or 504.3(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 × maximum capacity) and the minimum capacity as shown in Table 504.3(1) or 504.3(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Sections 504.3.5 and 504.3.6. The 20 - percent reduction for corrugated metallic chimney liner syste ms includes an allowance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Where double - wall connectors are required, tee and wye fittings used to connect to the common vent chimney liner shall be listed double - wall fittings. Connec tions between chimney liners and listed double - wall fittings shall be made with listed adapter fittings designed for such purpose. 504.3.20 Chimney and vent location. Tables 504.3(1), 504.3(2), 504.3(3), 504.3(4 ), and 504.3(5) shall be used only for chimne ys and vents not exposed to the outdoors below the roof line. Tables 504.3(6a), 504.3(6b), 504.3(7a) and 504.3(7b) shall be used for clay - tile - lined exterior masonry chimneys, provided that all of the following con- ditions are met: 1. Vent connectors are Type B double wall . 2. Not less than one appliance is draft hood equipped. 3. The combined appliance input rating is less than the maximum capacity given by Table 504.3(6a) for NAT+NAT or Table 504.3(7a) for FAN+NAT. 4. The input rating of each space - hea ting appliance is greater than the minimum input rating given by Table 504.3(6b) for NAT+NAT or Table 504.3(7b) for FAN+NAT. 5. The vent connector sizing is in accordance with Table 504.3(3). 504.3.21 Connector maximum and minimum size. Vent connectors sha ll not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. Vent connectors for draft hood - equipped appliances shall not be smaller than the draft hood out let diameter. Where a vent connector size(s) determined from the tables for a fan - assisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size(s) shall be permitted provided that the installation complies with all of the foll owing conditions: CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater CHIMNEYS AND VENTS 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA 334 398 393 334 0 50 NA NA NA NA NA 714 707 579 100 NA NA NA NA NA NA NA 1,600 27 °F to 36°F Local 99% Winter Design Temperature: 27 °F to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA 111 142 183 233 253 274 305 20 NA NA 187 230 284 307 330 362 30 NA NA NA 330 319 419 445 485 50 NA NA NA NA NA 672 705 763 100 NA NA NA NA NA NA NA 1,554 (continued) T ABLE 504.3(7b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17°F to 26°F Local 99% Winter Design Temperature: 17°F to 26°F 6 0 55 99 141 182 215 259 349 8 52 74 111 154 197 226 264 352 10 NA 90 125 169 214 245 278 358 15 NA NA 167 212 263 296 331 398 20 NA NA 212 258 316 352 387 457 30 NA NA NA 362 429 470 507 581 50 NA NA NA NA NA 723 766 862 100 NA NA NA NA NA NA NA 1,669 5°F to 16°F Local 99% Winter Design Temperature: 5°F to 16°F 6 NA 78 121 166 214 252 301 416 8 NA 94 135 182 230 269 312 423 10 NA 111 149 198 250 289 331 430 CHIMNEYS AND VENTS 15 NA NA 193 247 305 346 393 485 20 NA NA NA 293 360 408 450 547 30 NA NA NA 377 450 531 580 682 50 NA NA NA NA NA 797 853 972 100 NA NA NA NA NA NA NA 1,833 - 10°F to 4°F Local 99% Winter Design Temperature: - 10°F to 4°F 6 NA NA 145 196 249 296 349 484 8 NA NA 159 213 269 320 371 494 10 NA NA 175 231 292 339 397 513 15 NA NA NA 283 351 404 457 586 20 NA NA NA 333 408 468 528 650 30 NA NA NA NA NA 603 667 805 50 NA NA NA NA NA NA 955 1,003 100 NA NA NA NA NA NA NA NA - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615 .16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.3.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent connector shall be determined using the NAT Max column. 2. The maximum capacity of the vertical vent or chimney shall be determined using the FAN+NAT column when the seco nd appliance is a fan - assisted appliance, or the NAT+NAT column when the second appliance is equipped with a draft hood. 3. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance. 3.1. The minimum capacity of the vent co nnector shall be determined using the FAN Min column. 3.2. The FAN+FAN column shall be used where the second appliance is a fan - assisted appliance, and the FAN+NAT column shall be used where the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.3.2 Connector length limit. The vent connector shall be routed to the vent utilizing the shortest possible route. Except as provided in Section 504.3.3, the maximum vent connector horizontal length shall be 1 1 / 2 feet for each inch ( 18 mm for each mm ) of connector diameter as shown in Table 5 04.3.2 . TABLE 504.3.2 MAXIMUM VENT CONNECTOR LENGTH CONNECTOR DIAMETER (inches) CONNECTOR MAXIMUM HORIZONTAL LENGTH (feet) 3 4 1 / 2 4 6 CHIMNEYS AND VENTS 5 7 1 / 2 6 9 7 10 1 / 2 8 12 9 13 1 / 2 10 15 12 18 14 21 16 24 18 27 20 30 22 33 24 36 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 504.3.3 Connectors with longer lengths. Connectors with longer horizontal lengths than those listed in Section 504.3.2 are permitted under the following conditions: 1. The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length allowed by Section 504.3.2. For example, the maximum length listed in Table 504.3.2 for a 4 - inch ( 101.6 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet ( 1828.8 mm) but not exceeding 12 feet ( 3657.6 mm), the maximum ca pacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet ( 3657.6 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent ( 0.80 × maximum vent capacity). 2. For a connector serving a fan - assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double - wall connectors, Table 504.2(1) shall be used. For single - w all connectors, Table 504.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single - appliance vent, as if the other appliances were not present. 504.3.4 Vent connector manifold. Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 × maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent connector manifold ( Lm ) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent connector manifold diameter (D) (see Figure 504.3.4). 504.3.5 Common vertical vent offset. Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 504.3.6. The horizonta l length of the common vent offset (Lo) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D) . Where multiple offsets occur in a common vent, the total horizontal length of all offsets combined shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D ). 504.3.6 Elbows in vents. For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent . For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. CHIMNEYS AND VENTS FIGURE 504.3.4 USE OF A MANIFOLD COMMON VENT CONNECTOR 504.3.7 Elbows in connectors. The vent connector capacities listed in the common vent sizing tables include allowance for two 90 - degree (1.57 rad) elbows. For each additional elbow up to and including 45 degrees (0.79 rad), the maximum vent connector capac ity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. 50 4.3.8 Common vent minimum size. The cross - sectional area of the common vent shall be equal to or greater than the cross - sectional area of the largest connector. 504.3.9 Common vent fittings. At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors. CHIMNEYS AND VENTS 504.3.9.1 Tee and wye fittings. Tee and wye fittings connected to a common gas vent shall be considered as part of the common gas vent and shall be constructed of materials consistent with that of the common gas vent. 504.3.10 Reserved. 504.3.11 Connector rise measurement. Connector ris e (R) for each appliance connector shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together. 504.3.12 Vent height measurement. For multiple units of appliances all located on one floor, availabl e total height (H) shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent. 504.3.13 Reserved. 504.3.14 Reserved. 504.3.15 Reserved. 504.3.16 Reserved. 504.3.17 Vertical vent maximum size. Where two or more appliances are connected to a vertical vent or chim- ney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area or draft hood out let area unless designed in accordance with approved engineering methods. 504.3.18 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent con- nector capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined from the tables shall be greater than the highest appliance input rating. 504.3.19 Liner system sizing and connections. Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.3(1) or 504.3(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 × maximum capacity) and the minimum capacity as shown in Table 504.3(1) or 504.3(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Sections 504.3.5 and 504.3.6. The 20 - percent reduction for corrugated metallic chimney liner syste ms includes an allowance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Where double - wall connectors are required, tee and wye fittings used to connect to the common vent chimney liner shall be listed double - wall fittings. Connec tions between chimney liners and listed double - wall fittings shall be made with listed adapter fittings designed for such purpose. 504.3.20 Chimney and vent location. Tables 504.3(1), 504.3(2), 504.3(3), 504.3(4 ), and 504.3(5) shall be used only for chimne ys and vents not exposed to the outdoors below the roof line. Tables 504.3(6a), 504.3(6b), 504.3(7a) and 504.3(7b) shall be used for clay - tile - lined exterior masonry chimneys, provided that all of the following con- ditions are met: 1. Vent connectors are Type B double wall . 2. Not less than one appliance is draft hood equipped. 3. The combined appliance input rating is less than the maximum capacity given by Table 504.3(6a) for NAT+NAT or Table 504.3(7a) for FAN+NAT. 4. The input rating of each space - hea ting appliance is greater than the minimum input rating given by Table 504.3(6b) for NAT+NAT or Table 504.3(7b) for FAN+NAT. 5. The vent connector sizing is in accordance with Table 504.3(3). 504.3.21 Connector maximum and minimum size. Vent connectors sha ll not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. Vent connectors for draft hood - equipped appliances shall not be smaller than the draft hood out let diameter. Where a vent connector size(s) determined from the tables for a fan - assisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size(s) shall be permitted provided that the installation complies with all of the foll owing conditions: CHIMNEYS AND VENTS 1. Vent connectors for fan - assisted appliance flue collars 12 inches ( 304.8 mm ) in diameter or smaller are not reduced by more than one table size ( e.g., 12 inches to 10 inches ( 304.8 mm to 254 mm) is a one - size reduc- tion ) and those large r than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes ( e.g., 24 inches to 20 inches ( 609.6 mm to 508 mm) is a two - size reduction ). 2. The fan - assisted appliance(s) is common vented with a draft - hood - equipped appliance(s). 3. The vent connector has a smooth interior wall. 504.3.22 Component commingling. All combinations of pipe sizes, single - wall and double - wall metal pipe shall be allowed within any connector run(s) or within the common vent, provided that all of the appropriate tables permit all of the desired sizes and types of pipe, as if they were used for the entire length of the subject connector or vent. Where single - wall and Type B double - wall metal pipes are used for vent connectors within the same venting system, the com mon vent must be sized using Table 504.3(2) or 504.3(4), as appropriate. 504.3.23 Draft hood conversion accessories. Draft hood conversion accessories for use with masonry chimneys venting listed Category I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed accessories. 504.3.24 Multiple sizes permitt ed. Where a table permits more than one diameter of pipe to be used for a connector or vent, all the permitted sizes shall be permitted to be used. 504.3.25 Table interpolation. Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table entries. 504.3.26 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.3.27 Engineering calculations. For vent heights less than 6 feet ( 1828.8 mm) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. 504.3.28 Height entries. Where the actual height of a vent falls between entries in the height column of the appli- cable table in Tables 504.3(1) thro ugh 504.3(7b), either interpolation shall be used or the lower appliance input rating shown in the table shall be used for FAN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. SECTION FGC 505 DIRECT - VENT, INTEGRAL VENT, MECHANICAL VENT AND VENTILATION/EXHAUST HOOD VENTING 505.1 General. The installation of direct - vent and integral vent appliances shall be in accordance with Section 503. Mechanical venting systems and exhaust hood venting system s shall be designed and installed in accordance with Section 503. 505.1.1 Commercial cooking appliances vented by exhaust hoods. Refer to Chapter 5 of the New York City Me- chanical Code . 505.1.2 Interlock requirements. Where commercial cooking appliances ar e vented by means of the Type I or Type II kitchen exhaust hood system that serves such appliances, the exhaust system shall be fan powered and the appliances shall be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating. The meth od of interlock between the exhaust hood system and the appliances equipped with standing pilot burner ignition systems shall not cause such pilots to be extinguished. Where a solenoid valve is installed in the gas piping as part of an interlock system, ga s piping shall not be installed to bypass such valve. Dampers shall not be installed in the exhaust system. Exception: An interlock between the cooking appliance(s) and the exhaust hood system shall not be required where heat sensors or other approved meth ods automatically activate the exhaust hood system when cooking operations occur. CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 12 14 16 18 20 22 24 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 900 696 588 1,284 990 815 1,735 1,336 1,065 2,253 1,732 1,345 2,838 2,180 1,660 3,488 2,677 1,970 4,205 3,226 2,390 8 994 773 652 1,423 1,103 912 1,927 1,491 1,190 2,507 1,936 1,510 3,162 2,439 1,860 3,890 2,998 2,200 4,695 3,616 2,680 10 1,076 941 712 1,542 1,200 995 2,093 1,625 1,500 2,727 2,113 1,645 3,444 2,665 2,030 4,241 3,278 2,400 5,123 3,957 2,920 15 1,247 986 825 1,794 1,410 1,158 2,440 1,910 1,510 3,184 2,484 1,910 4,026 3,133 2,160 4,971 3,862 2,790 6,016 4,670 9,400 20 1,405 1,116 916 2,006 1,588 1,290 2,722 2,147 1,690 3,561 2,798 2,140 4,548 3,552 2,640 5,573 4,332 3,120 6,749 5,231 3,800 30 1,658 1,325 1,025 2,373 1,892 1,525 3,220 2,558 1,990 4,197 3,326 2,520 5,303 4,193 3,110 6,539 5,157 3,680 7,940 6,247 4,430 50 2,024 1,640 1,280 2,911 2,347 1,863 3,964 3,183 2,430 5,184 4,149 3,075 6,567 5,240 3,800 8,116 6,458 4,500 9,837 7,813 5,475 100 2,569 2,131 1,670 3,732 3,076 2,450 5,125 4,202 3,200 6,749 5,509 4,050 5,897 6,986 5,000 10,681 8,648 5,920 13,704 10,439 7,200 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater CHIMNEYS AND VENTS 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA 334 398 393 334 0 50 NA NA NA NA NA 714 707 579 100 NA NA NA NA NA NA NA 1,600 27 °F to 36°F Local 99% Winter Design Temperature: 27 °F to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA 111 142 183 233 253 274 305 20 NA NA 187 230 284 307 330 362 30 NA NA NA 330 319 419 445 485 50 NA NA NA NA NA 672 705 763 100 NA NA NA NA NA NA NA 1,554 (continued) T ABLE 504.3(7b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17°F to 26°F Local 99% Winter Design Temperature: 17°F to 26°F 6 0 55 99 141 182 215 259 349 8 52 74 111 154 197 226 264 352 10 NA 90 125 169 214 245 278 358 15 NA NA 167 212 263 296 331 398 20 NA NA 212 258 316 352 387 457 30 NA NA NA 362 429 470 507 581 50 NA NA NA NA NA 723 766 862 100 NA NA NA NA NA NA NA 1,669 5°F to 16°F Local 99% Winter Design Temperature: 5°F to 16°F 6 NA 78 121 166 214 252 301 416 8 NA 94 135 182 230 269 312 423 10 NA 111 149 198 250 289 331 430 CHIMNEYS AND VENTS 15 NA NA 193 247 305 346 393 485 20 NA NA NA 293 360 408 450 547 30 NA NA NA 377 450 531 580 682 50 NA NA NA NA NA 797 853 972 100 NA NA NA NA NA NA NA 1,833 - 10°F to 4°F Local 99% Winter Design Temperature: - 10°F to 4°F 6 NA NA 145 196 249 296 349 484 8 NA NA 159 213 269 320 371 494 10 NA NA 175 231 292 339 397 513 15 NA NA NA 283 351 404 457 586 20 NA NA NA 333 408 468 528 650 30 NA NA NA NA NA 603 667 805 50 NA NA NA NA NA NA 955 1,003 100 NA NA NA NA NA NA NA NA - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615 .16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.3.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent connector shall be determined using the NAT Max column. 2. The maximum capacity of the vertical vent or chimney shall be determined using the FAN+NAT column when the seco nd appliance is a fan - assisted appliance, or the NAT+NAT column when the second appliance is equipped with a draft hood. 3. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance. 3.1. The minimum capacity of the vent co nnector shall be determined using the FAN Min column. 3.2. The FAN+FAN column shall be used where the second appliance is a fan - assisted appliance, and the FAN+NAT column shall be used where the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.3.2 Connector length limit. The vent connector shall be routed to the vent utilizing the shortest possible route. Except as provided in Section 504.3.3, the maximum vent connector horizontal length shall be 1 1 / 2 feet for each inch ( 18 mm for each mm ) of connector diameter as shown in Table 5 04.3.2 . TABLE 504.3.2 MAXIMUM VENT CONNECTOR LENGTH CONNECTOR DIAMETER (inches) CONNECTOR MAXIMUM HORIZONTAL LENGTH (feet) 3 4 1 / 2 4 6 CHIMNEYS AND VENTS 5 7 1 / 2 6 9 7 10 1 / 2 8 12 9 13 1 / 2 10 15 12 18 14 21 16 24 18 27 20 30 22 33 24 36 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 504.3.3 Connectors with longer lengths. Connectors with longer horizontal lengths than those listed in Section 504.3.2 are permitted under the following conditions: 1. The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length allowed by Section 504.3.2. For example, the maximum length listed in Table 504.3.2 for a 4 - inch ( 101.6 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet ( 1828.8 mm) but not exceeding 12 feet ( 3657.6 mm), the maximum ca pacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet ( 3657.6 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent ( 0.80 × maximum vent capacity). 2. For a connector serving a fan - assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double - wall connectors, Table 504.2(1) shall be used. For single - w all connectors, Table 504.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single - appliance vent, as if the other appliances were not present. 504.3.4 Vent connector manifold. Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 × maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent connector manifold ( Lm ) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent connector manifold diameter (D) (see Figure 504.3.4). 504.3.5 Common vertical vent offset. Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 504.3.6. The horizonta l length of the common vent offset (Lo) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D) . Where multiple offsets occur in a common vent, the total horizontal length of all offsets combined shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D ). 504.3.6 Elbows in vents. For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent . For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. CHIMNEYS AND VENTS FIGURE 504.3.4 USE OF A MANIFOLD COMMON VENT CONNECTOR 504.3.7 Elbows in connectors. The vent connector capacities listed in the common vent sizing tables include allowance for two 90 - degree (1.57 rad) elbows. For each additional elbow up to and including 45 degrees (0.79 rad), the maximum vent connector capac ity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. 50 4.3.8 Common vent minimum size. The cross - sectional area of the common vent shall be equal to or greater than the cross - sectional area of the largest connector. 504.3.9 Common vent fittings. At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors. CHIMNEYS AND VENTS 504.3.9.1 Tee and wye fittings. Tee and wye fittings connected to a common gas vent shall be considered as part of the common gas vent and shall be constructed of materials consistent with that of the common gas vent. 504.3.10 Reserved. 504.3.11 Connector rise measurement. Connector ris e (R) for each appliance connector shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together. 504.3.12 Vent height measurement. For multiple units of appliances all located on one floor, availabl e total height (H) shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent. 504.3.13 Reserved. 504.3.14 Reserved. 504.3.15 Reserved. 504.3.16 Reserved. 504.3.17 Vertical vent maximum size. Where two or more appliances are connected to a vertical vent or chim- ney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area or draft hood out let area unless designed in accordance with approved engineering methods. 504.3.18 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent con- nector capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined from the tables shall be greater than the highest appliance input rating. 504.3.19 Liner system sizing and connections. Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.3(1) or 504.3(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 × maximum capacity) and the minimum capacity as shown in Table 504.3(1) or 504.3(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Sections 504.3.5 and 504.3.6. The 20 - percent reduction for corrugated metallic chimney liner syste ms includes an allowance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Where double - wall connectors are required, tee and wye fittings used to connect to the common vent chimney liner shall be listed double - wall fittings. Connec tions between chimney liners and listed double - wall fittings shall be made with listed adapter fittings designed for such purpose. 504.3.20 Chimney and vent location. Tables 504.3(1), 504.3(2), 504.3(3), 504.3(4 ), and 504.3(5) shall be used only for chimne ys and vents not exposed to the outdoors below the roof line. Tables 504.3(6a), 504.3(6b), 504.3(7a) and 504.3(7b) shall be used for clay - tile - lined exterior masonry chimneys, provided that all of the following con- ditions are met: 1. Vent connectors are Type B double wall . 2. Not less than one appliance is draft hood equipped. 3. The combined appliance input rating is less than the maximum capacity given by Table 504.3(6a) for NAT+NAT or Table 504.3(7a) for FAN+NAT. 4. The input rating of each space - hea ting appliance is greater than the minimum input rating given by Table 504.3(6b) for NAT+NAT or Table 504.3(7b) for FAN+NAT. 5. The vent connector sizing is in accordance with Table 504.3(3). 504.3.21 Connector maximum and minimum size. Vent connectors sha ll not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. Vent connectors for draft hood - equipped appliances shall not be smaller than the draft hood out let diameter. Where a vent connector size(s) determined from the tables for a fan - assisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size(s) shall be permitted provided that the installation complies with all of the foll owing conditions: CHIMNEYS AND VENTS 1. Vent connectors for fan - assisted appliance flue collars 12 inches ( 304.8 mm ) in diameter or smaller are not reduced by more than one table size ( e.g., 12 inches to 10 inches ( 304.8 mm to 254 mm) is a one - size reduc- tion ) and those large r than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes ( e.g., 24 inches to 20 inches ( 609.6 mm to 508 mm) is a two - size reduction ). 2. The fan - assisted appliance(s) is common vented with a draft - hood - equipped appliance(s). 3. The vent connector has a smooth interior wall. 504.3.22 Component commingling. All combinations of pipe sizes, single - wall and double - wall metal pipe shall be allowed within any connector run(s) or within the common vent, provided that all of the appropriate tables permit all of the desired sizes and types of pipe, as if they were used for the entire length of the subject connector or vent. Where single - wall and Type B double - wall metal pipes are used for vent connectors within the same venting system, the com mon vent must be sized using Table 504.3(2) or 504.3(4), as appropriate. 504.3.23 Draft hood conversion accessories. Draft hood conversion accessories for use with masonry chimneys venting listed Category I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed accessories. 504.3.24 Multiple sizes permitt ed. Where a table permits more than one diameter of pipe to be used for a connector or vent, all the permitted sizes shall be permitted to be used. 504.3.25 Table interpolation. Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table entries. 504.3.26 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.3.27 Engineering calculations. For vent heights less than 6 feet ( 1828.8 mm) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. 504.3.28 Height entries. Where the actual height of a vent falls between entries in the height column of the appli- cable table in Tables 504.3(1) thro ugh 504.3(7b), either interpolation shall be used or the lower appliance input rating shown in the table shall be used for FAN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. SECTION FGC 505 DIRECT - VENT, INTEGRAL VENT, MECHANICAL VENT AND VENTILATION/EXHAUST HOOD VENTING 505.1 General. The installation of direct - vent and integral vent appliances shall be in accordance with Section 503. Mechanical venting systems and exhaust hood venting system s shall be designed and installed in accordance with Section 503. 505.1.1 Commercial cooking appliances vented by exhaust hoods. Refer to Chapter 5 of the New York City Me- chanical Code . 505.1.2 Interlock requirements. Where commercial cooking appliances ar e vented by means of the Type I or Type II kitchen exhaust hood system that serves such appliances, the exhaust system shall be fan powered and the appliances shall be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating. The meth od of interlock between the exhaust hood system and the appliances equipped with standing pilot burner ignition systems shall not cause such pilots to be extinguished. Where a solenoid valve is installed in the gas piping as part of an interlock system, ga s piping shall not be installed to bypass such valve. Dampers shall not be installed in the exhaust system. Exception: An interlock between the cooking appliance(s) and the exhaust hood system shall not be required where heat sensors or other approved meth ods automatically activate the exhaust hood system when cooking operations occur. CHIMNEYS AND VENTS TABLE 504.3(2) TYPE B DOUBLE - WALL VENT Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 26 NA NA 46 NA NA 71 NA NA 102 207 223 140 262 293 183 325 373 234 447 463 286 2 NA NA 31 NA NA 55 NA NA 85 168 182 123 215 251 167 271 331 219 334 422 287 458 524 344 3 NA NA 34 NA NA 62 NA 131 93 175 198 138 222 273 188 279 361 247 344 462 316 468 574 385 8 1 NA NA 27 NA NA 48 NA NA 75 NA NA 106 226 240 145 285 316 191 352 403 244 481 502 299 2 N A NA 32 NA NA 57 125 126 89 181 193 127 234 266 173 293 353 228 360 450 292 492 560 355 3 N A NA 35 NA NA 64 130 138 100 181 208 144 241 287 197 302 381 256 370 489 328 501 600 400 10 1 NA NA 28 NA NA 50 119 121 77 182 186 110 260 253 150 302 335 196 372 429 252 506 534 308 CHIMNEYS AND VENTS 2 N A NA 33 84 85 59 124 134 91 189 203 132 248 278 183 311 369 235 381 473 302 517 589 368 3 N A NA 36 89 91 67 129 144 102 197 217 148 258 299 203 320 398 255 391 511 339 528 637 413 15 1 NA NA 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 452 266 556 596 324 2 N A NA 34 85 94 62 121 150 97 185 230 138 246 314 189 321 411 248 407 522 317 568 646 387 3 N A NA 39 87 100 70 127 160 109 193 243 157 255 333 215 831 438 281 418 557 360 579 690 437 20 1 49 56 30 78 97 54 115 152 84 175 238 120 233 323 165 306 425 217 390 539 276 546 664 336 2 5 2 59 36 82 103 64 120 163 101 182 252 144 243 306 191 317 453 259 400 574 331 558 709 403 3 5 5 62 40 87 107 72 125 172 113 190 264 164 252 363 223 326 476 294 412 607 375 570 750 457 30 1 47 60 31 77 110 57 112 175 89 169 278 129 226 380 175 296 497 230 378 630 294 528 779 358 2 5 1 62 37 81 115 67 117 185 106 177 290 152 236 397 208 307 521 274 389 662 349 541 817 425 3 5 4 64 42 85 119 76 122 193 120 185 300 172 244 412 235 316 542 309 400 690 394 555 855 482 50 1 46 69 34 75 128 60 109 207 96 162 336 137 217 460 188 284 604 245 364 768 314 507 951 384 2 4 9 71 40 79 132 72 114 215 113 170 345 164 226 473 223 294 523 293 376 793 375 520 983 458 3 5 2 72 45 83 136 82 119 221 123 178 353 186 235 486 252 304 640 331 387 816 423 535 1,013 518 100 1 45 79 34 71 150 61 104 249 98 153 424 100 205 585 192 269 714 240 345 993 321 476 1,236 393 2 4 8 80 41 75 153 73 110 255 115 160 428 167 212 593 228 279 758 299 358 1,011 383 490 1,259 469 3 5 1 81 46 79 157 85 114 260 129 168 433 190 222 603 256 289 807 339 368 1,027 431 506 1,280 527 CHIMNEYS AND VENTS COMMON VENT CAPACITY VENT HEIGHT (H) (feet) TYPE B DOUBLE - WALL VENT AND CONNECTOR DIAMETER – (D) inches 4 5 6 7 8 9 10 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 78 64 NA 115 99 200 158 144 304 244 196 398 310 257 541 429 332 665 515 407 8 NA 87 71 NA 126 111 218 173 159 331 269 218 436 342 285 592 473 373 730 569 460 10 NA 94 76 163 137 120 237 189 174 357 292 236 467 369 309 638 512 398 787 617 487 15 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 20 131 138 98 208 177 156 305 247 223 463 383 302 606 487 395 824 673 512 1,013 808 626 30 145 132 113 236 202 180 350 286 257 535 446 349 703 570 459 958 790 593 1,183 952 723 50 159 145 128 268 233 208 406 337 296 622 527 410 833 686 535 1,139 954 689 1,418 1,157 838 100 166 153 NA 297 263 NA 469 398 NA 726 603 464 999 846 606 1,378 1,185 780 1,741 1,459 948 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(3) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Type B double - wall connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) TYPE B DOUBLE - WALL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 24 33 21 39 62 40 52 106 67 65 194 101 87 274 141 104 370 201 124 479 253 145 599 319 2 26 43 28 41 79 52 53 135 85 67 230 124 89 324 173 107 436 232 127 562 300 148 694 378 3 27 49 34 42 92 61 55 155 97 69 262 143 91 369 200 109 491 270 129 533 349 151 795 439 8 1 24 39 22 39 72 41 55 117 69 71 213 105 94 304 148 113 414 210 134 539 267 156 682 335 2 2 6 47 29 40 87 53 57 140 16 73 246 127 97 350 179 116 473 240 137 615 311 160 776 394 3 2 7 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 572 358 163 848 452 10 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 2 6 50 29 40 93 54 57 153 87 76 264 129 103 366 184 123 498 247 145 652 321 168 825 407 CHIMNEYS AND VENTS 3 2 7 55 35 41 105 63 58 170 100 78 284 148 106 397 209 126 540 281 147 705 366 171 893 463 15 1 24 48 23 38 93 44 54 154 74 72 277 114 100 384 161 125 511 229 153 658 297 184 824 375 2 2 5 55 31 39 105 55 56 174 89 74 299 134 103 419 182 128 558 260 156 718 339 187 900 452 3 2 6 59 35 41 115 64 57 189 102 76 319 153 105 448 215 131 597 292 189 760 382 180 960 486 20 1 24 52 24 37 102 46 53 172 77 71 313 119 98 437 173 123 584 239 150 752 312 180 943 397 2 2 5 58 31 39 114 56 55 190 91 73 335 138 101 467 199 126 625 270 153 805 354 184 1,011 452 3 2 6 63 35 40 123 65 57 204 104 75 353 157 104 493 222 129 661 301 156 851 396 187 1,067 505 30 1 24 54 25 37 111 48 52 182 82 69 357 127 96 504 187 119 680 255 145 883 337 175 1,115 432 2 2 5 60 32 38 132 58 54 208 95 72 376 145 99 531 209 122 715 287 149 928 378 179 1,171 484 3 2 6 64 36 40 131 66 56 221 107 74 392 163 101 554 233 125 746 317 152 968 418 182 1,220 535 50 1 23 51 25 36 116 51 51 209 89 67 408 143 92 582 213 115 798 294 140 1,049 392 168 1,334 506 2 2 4 59 32 37 127 61 53 225 102 70 421 161 95 604 235 118 827 326 143 1,085 433 172 1,379 558 3 2 6 64 36 39 135 69 55 237 115 72 435 80 98 624 260 121 854 357 147 1,118 474 176 1,421 611 100 1 23 46 24 35 108 50 49 208 92 65 428 155 88 640 237 109 907 334 134 1,222 454 161 1,589 596 2 2 4 53 31 37 120 60 51 224 105 67 444 174 92 660 260 113 933 368 138 1,253 497 165 1,626 651 3 25 59 35 38 130 68 53 237 118 69 458 193 94 679 285 116 936 399 141 1,282 540 169 1,661 705 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1,041 853 NA 8 NA 80 28 NA 130 53 NA 193 82 NA 279 119 NA 384 163 NA 501 218 724 636 278 1,144 937 408 10 NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 605 538 236 776 686 302 1,226 1,010 454 15 NA NA 36 NA 152 67 NA 233 106 NA 334 152 523 467 212 682 611 283 874 781 365 1,374 1,156 546 20 NA NA 41 NA NA 75 NA 250 122 NA 368 172 565 508 243 743 668 325 955 858 419 1,513 1,286 648 30 NA NA NA NA NA NA NA 270 137 NA 404 198 615 564 278 816 747 381 1,062 969 496 1,702 1,473 749 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 620 328 879 831 461 1,165 1,039 606 1,900 1,692 922 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 348 NA NA 499 NA NA 669 1,053 1,921 1,058 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. CHIMNEYS AND VENTS TABLE 504.3(4) MASONRY CHIMNEY Number of Appliances Two or more Appliance Type Category I Appliance Vent Connection Single - wall metal connector VENT CONNECTOR CAPACITY VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) SINGLE - WALL METAL VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 9 10 APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT Min Max Max Min Max Ma40x52 Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 6 1 NA NA 21 NA NA 39 NA NA 66 179 191 100 231 271 140 292 365 200 362 474 252 499 594 316 2 NA NA 28 NA NA 52 NA NA 84 136 227 123 239 321 172 301 432 231 373 557 299 509 696 376 3 NA NA 34 NA NA 61 134 153 97 193 258 142 247 365 202 309 491 263 381 634 348 519 703 437 8 1 NA NA 2 1 NA NA 40 NA NA 68 195 108 103 250 298 146 313 407 207 387 530 263 529 672 331 2 NA NA 28 NA NA 52 137 139 85 202 240 125 258 343 177 323 465 238 397 607 309 540 766 391 3 NA NA 34 NA NA 62 143 156 98 210 264 145 266 376 205 332 509 274 407 663 356 551 838 450 10 1 NA NA 22 NA NA 41 130 151 70 202 225 106 267 316 151 333 434 213 410 571 273 558 727 343 2 NA NA 29 NA NA 53 136 150 86 210 255 128 276 358 181 346 489 244 420 640 317 569 813 403 CHIMNEYS AND VENTS 3 NA NA 34 97 102 62 143 166 99 217 277 147 284 389 207 352 530 279 430 694 363 580 880 459 15 1 NA NA 23 NA NA 43 129 151 73 199 271 112 268 376 161 349 502 225 445 646 291 623 808 366 2 NA NA 60 92 103 54 135 170 88 207 295 132 277 411 189 359 548 256 456 706 334 634 884 424 3 NA NA 34 96 112 63 141 185 101 215 315 151 286 439 213 358 585 289 466 735 378 646 945 479 20 1 NA NA 23 87 99 45 128 167 76 197 303 117 265 425 169 345 569 235 439 734 306 614 920 347 2 NA NA 30 91 111 55 134 185 90 205 325 136 274 455 195 355 610 266 450 787 348 627 986 443 3 NA NA 35 96 119 64 140 199 103 213 343 154 282 481 219 363 644 298 461 831 391 639 1,042 496 30 1 NA NA 24 86 108 47 126 187 80 193 347 124 259 402 183 338 665 250 430 864 330 600 1,089 421 2 NA NA 31 91 119 57 132 203 93 201 366 142 269 518 205 348 699 282 442 908 372 613 1,145 473 3 NA NA 35 95 127 65 138 216 105 209 381 160 277 540 229 358 729 312 452 946 412 626 1,193 524 50 1 NA NA 24 85 113 50 124 204 87 188 392 139 252 567 208 328 778 287 417 1,022 383 582 1,302 492 2 NA NA 31 89 123 60 130 218 100 196 408 158 262 588 230 339 805 320 429 1,058 425 595 1,346 545 3 NA NA 35 94 131 68 136 231 112 205 422 176 271 607 255 349 731 351 440 1,090 456 610 1,386 587 100 1 NA NA 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1,181 444 560 1,537 580 2 NA NA 30 88 115 59 127 215 102 190 425 169 253 636 254 326 899 361 415 1,200 438 575 1,570 634 3 NA NA 34 93 124 67 133 228 115 199 438 188 262 654 279 337 921 392 427 1,238 529 589 1,604 687 COMMON VENT CAPACITY VENT MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) CHIMNEYS AND VENTS HEIGHT (H) (feet) 12 19 28 38 50 63 78 113 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT FAN +FAN FAN +NAT NAT +NAT 6 NA NA 25 NA 118 45 NA 176 71 NA 255 102 NA 348 142 NA 455 187 NA 579 245 NA 846 NA 8 NA NA 28 NA 128 52 NA 150 81 NA 275 118 NA 380 162 NA 497 217 NA 633 277 1,136 928 405 10 NA NA 31 NA 136 56 NA 205 89 NA 295 129 NA 405 175 NA 532 234 171 680 300 1,216 1,000 450 15 NA NA 36 NA NA 65 NA 230 105 NA 335 150 NA 400 210 677 602 280 866 772 360 1,359 1,139 540 20 NA NA NA NA NA 74 NA 247 120 NA 362 170 NA 503 240 765 661 321 947 849 415 1,495 1,264 640 30 NA NA NA NA NA NA NA NA 135 NA 398 195 NA 558 275 808 739 377 1,052 957 490 1,682 1,447 740 50 NA NA NA NA NA NA NA NA NA NA NA NA NA 612 325 NA NA 456 1,152 1,076 600 1,879 1,672 910 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 494 NA NA 663 2,006 1,835 1,046 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 1 foot = 304.8mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(5) SINGLE - WALL METAL PIPE OR TYPE ASBESTOS CEMENT VENT Number of Appliances Two or more Appliance Type Draft hood - equipped Appliance Vent Connection Direct to pipe or vent VENT CONNECTION CAPACITY TOTAL VENT HEIGHT (H) (feet) CONNECTOR RISE (R) (feet) VENT CONNECTOR DIAMETER – (D) inches 3 4 5 6 7 8 MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 - 8 1 21 40 68 102 146 205 2 28 53 86 124 178 235 3 34 61 98 147 204 275 15 1 23 44 77 117 179 240 2 30 56 92 134 194 265 3 35 61 102 155 216 298 30 and up 1 25 49 84 129 190 270 2 31 58 97 145 211 295 3 36 68 107 164 232 321 COMMON VENT CAPACITY TOTAL VENT HEIGHT (H) (feet) COMMON VENT DIAMETER – (D) inches 4 5 6 7 8 10 12 COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 6 48 78 111 155 205 320 NA CHIMNEYS AND VENTS 8 55 89 128 175 234 365 505 10 59 95 136 190 250 395 560 15 71 115 168 228 305 480 690 20 80 129 186 260 340 550 790 30 NA 147 215 300 400 650 940 50 NA NA NA 360 490 810 1,190 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(6a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 25 46 71 103 143 188 246 NA 8 28 53 82 119 163 218 278 408 10 31 56 90 131 177 236 302 454 15 NA 67 106 152 212 283 365 546 20 NA NA NA NA NA 325 419 648 30 NA NA NA NA NA NA 496 749 50 NA NA NA NA NA NA NA 922 100 NA NA NA NA NA NA NA NA TABLE 504.3(6b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type NAT + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 CHIMNEYS AND VENTS 37 °F or Greater Local 99% Winter Design Temperature: 37° F or Greater 6 0 0 0 0 0 0 0 NA 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA NA NA NA 184 0 0 30 NA NA NA NA NA 393 334 0 50 NA NA NA NA NA NA NA 579 100 NA NA NA NA NA NA NA NA 27 to 36°F Local 99% Winter Design Temperature: 27 to 36°F 6 0 0 68 NA NA 180 212 NA 8 0 0 82 NA NA 187 214 263 10 0 51 NA NA NA 201 225 265 15 NA NA NA NA NA 253 274 305 20 NA NA NA NA NA 307 330 362 30 NA NA NA NA NA NA 445 485 50 NA NA NA NA NA NA NA 763 100 NA NA NA NA NA NA NA NA (continued) TABLE 504.3(6b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hou r VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17 to 26°F Local 99% Winter Design Temperature: 17 to 26°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA 264 352 10 NA NA NA NA NA NA 278 358 15 NA NA NA NA NA NA 331 398 20 NA NA NA NA NA NA 387 457 30 NA NA NA NA NA NA NA 581 50 NA NA NA NA NA NA NA 862 100 NA NA NA NA NA NA NA NA 5 °F to 16°F Local 99% Winter Design Temperature: 5 °F to 16°F 6 NA NA NA NA NA NA NA NA 8 NA NA NA NA NA NA NA NA CHIMNEYS AND VENTS 10 NA NA NA NA NA NA NA 430 15 NA NA NA NA NA NA NA 485 20 NA NA NA NA NA NA NA 547 30 NA NA NA NA NA NA NA 682 50 NA NA NA NA NA NA NA NA 100 NA NA NA NA NA NA NA NA 4°F or Lower Local 99% Winter Design Temperature: 4°F or Lower Not recommended for any vent configurations For SI: °C – (°F – 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615. 16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. TABLE 504.3(7a) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Combined Appliance Maximum Input Rating in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 6 74 119 178 257 351 458 582 853 8 80 130 193 279 384 501 636 937 10 84 138 207 299 409 538 686 1,010 15 NA 152 233 334 467 611 781 1,156 20 NA NA 250 368 508 668 858 1,286 30 NA NA NA 404 564 747 969 1,473 50 NA NA NA NA NA 831 1,089 1,692 100 NA NA NA NA NA NA NA 1,921 TABLE 504.3(7b) EXTERIOR MASONRY CHIMNEY Number of Appliances Two or more Appliance Type FAN + NAT Appliance Vent Connection Type B double - wall connector Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 37°F or Greater Local 99% Winter Design Temperature: 37°F or Greater CHIMNEYS AND VENTS 6 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 15 NA 0 0 0 0 0 0 0 20 NA NA 123 190 249 184 0 0 30 NA NA NA 334 398 393 334 0 50 NA NA NA NA NA 714 707 579 100 NA NA NA NA NA NA NA 1,600 27 °F to 36°F Local 99% Winter Design Temperature: 27 °F to 36°F 6 0 0 68 116 156 180 212 266 8 0 0 82 127 167 187 214 263 10 0 51 97 141 183 201 225 265 15 NA 111 142 183 233 253 274 305 20 NA NA 187 230 284 307 330 362 30 NA NA NA 330 319 419 445 485 50 NA NA NA NA NA 672 705 763 100 NA NA NA NA NA NA NA 1,554 (continued) T ABLE 504.3(7b) — continued EXTERIOR MASONRY CHIMNEY Minimum Allowable Input Rating of Space - heating Appliance in Thousands of Btu per Hour VENT HEIGHT (feet) INTERNAL AREA OF CHIMNEY (square inches) 12 19 28 38 50 63 78 113 17°F to 26°F Local 99% Winter Design Temperature: 17°F to 26°F 6 0 55 99 141 182 215 259 349 8 52 74 111 154 197 226 264 352 10 NA 90 125 169 214 245 278 358 15 NA NA 167 212 263 296 331 398 20 NA NA 212 258 316 352 387 457 30 NA NA NA 362 429 470 507 581 50 NA NA NA NA NA 723 766 862 100 NA NA NA NA NA NA NA 1,669 5°F to 16°F Local 99% Winter Design Temperature: 5°F to 16°F 6 NA 78 121 166 214 252 301 416 8 NA 94 135 182 230 269 312 423 10 NA 111 149 198 250 289 331 430 CHIMNEYS AND VENTS 15 NA NA 193 247 305 346 393 485 20 NA NA NA 293 360 408 450 547 30 NA NA NA 377 450 531 580 682 50 NA NA NA NA NA 797 853 972 100 NA NA NA NA NA NA NA 1,833 - 10°F to 4°F Local 99% Winter Design Temperature: - 10°F to 4°F 6 NA NA 145 196 249 296 349 484 8 NA NA 159 213 269 320 371 494 10 NA NA 175 231 292 339 397 513 15 NA NA NA 283 351 404 457 586 20 NA NA NA 333 408 468 528 650 30 NA NA NA NA NA 603 667 805 50 NA NA NA NA NA NA 955 1,003 100 NA NA NA NA NA NA NA NA - 11°F or Lower Local 99% Winter Design Temperature: - 11°F or Lower Not recommended for any vent configurations For SI: °C = (°F - 32)/1.8, 1 inch = 25.4 mm, 1 square inch = 615 .16 mm 2 , 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 504.3.1 Vent obstructions. These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: 1. The maximum capacity of the vent connector shall be determined using the NAT Max column. 2. The maximum capacity of the vertical vent or chimney shall be determined using the FAN+NAT column when the seco nd appliance is a fan - assisted appliance, or the NAT+NAT column when the second appliance is equipped with a draft hood. 3. The minimum capacity shall be determined as if the appliance were a fan - assisted appliance. 3.1. The minimum capacity of the vent co nnector shall be determined using the FAN Min column. 3.2. The FAN+FAN column shall be used where the second appliance is a fan - assisted appliance, and the FAN+NAT column shall be used where the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 504.3.2 Connector length limit. The vent connector shall be routed to the vent utilizing the shortest possible route. Except as provided in Section 504.3.3, the maximum vent connector horizontal length shall be 1 1 / 2 feet for each inch ( 18 mm for each mm ) of connector diameter as shown in Table 5 04.3.2 . TABLE 504.3.2 MAXIMUM VENT CONNECTOR LENGTH CONNECTOR DIAMETER (inches) CONNECTOR MAXIMUM HORIZONTAL LENGTH (feet) 3 4 1 / 2 4 6 CHIMNEYS AND VENTS 5 7 1 / 2 6 9 7 10 1 / 2 8 12 9 13 1 / 2 10 15 12 18 14 21 16 24 18 27 20 30 22 33 24 36 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 504.3.3 Connectors with longer lengths. Connectors with longer horizontal lengths than those listed in Section 504.3.2 are permitted under the following conditions: 1. The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length allowed by Section 504.3.2. For example, the maximum length listed in Table 504.3.2 for a 4 - inch ( 101.6 mm) connector is 6 feet (1829 mm). With a connector length greater than 6 feet ( 1828.8 mm) but not exceeding 12 feet ( 3657.6 mm), the maximum ca pacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet ( 3657.6 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent ( 0.80 × maximum vent capacity). 2. For a connector serving a fan - assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double - wall connectors, Table 504.2(1) shall be used. For single - w all connectors, Table 504.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single - appliance vent, as if the other appliances were not present. 504.3.4 Vent connector manifold. Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 × maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent connector manifold ( Lm ) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent connector manifold diameter (D) (see Figure 504.3.4). 504.3.5 Common vertical vent offset. Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 504.3.6. The horizonta l length of the common vent offset (Lo) shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D) . Where multiple offsets occur in a common vent, the total horizontal length of all offsets combined shall not exceed 1 1 / 2 feet for each inch ( 18 mm for each mm ) of common vent diameter (D ). 504.3.6 Elbows in vents. For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent . For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. CHIMNEYS AND VENTS FIGURE 504.3.4 USE OF A MANIFOLD COMMON VENT CONNECTOR 504.3.7 Elbows in connectors. The vent connector capacities listed in the common vent sizing tables include allowance for two 90 - degree (1.57 rad) elbows. For each additional elbow up to and including 45 degrees (0.79 rad), the maximum vent connector capac ity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. 50 4.3.8 Common vent minimum size. The cross - sectional area of the common vent shall be equal to or greater than the cross - sectional area of the largest connector. 504.3.9 Common vent fittings. At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors. CHIMNEYS AND VENTS 504.3.9.1 Tee and wye fittings. Tee and wye fittings connected to a common gas vent shall be considered as part of the common gas vent and shall be constructed of materials consistent with that of the common gas vent. 504.3.10 Reserved. 504.3.11 Connector rise measurement. Connector ris e (R) for each appliance connector shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together. 504.3.12 Vent height measurement. For multiple units of appliances all located on one floor, availabl e total height (H) shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent. 504.3.13 Reserved. 504.3.14 Reserved. 504.3.15 Reserved. 504.3.16 Reserved. 504.3.17 Vertical vent maximum size. Where two or more appliances are connected to a vertical vent or chim- ney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area or draft hood out let area unless designed in accordance with approved engineering methods. 504.3.18 Multiple input rate appliances. For appliances with more than one input rate, the minimum vent con- nector capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined from the tables shall be greater than the highest appliance input rating. 504.3.19 Liner system sizing and connections. Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.3(1) or 504.3(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 × maximum capacity) and the minimum capacity as shown in Table 504.3(1) or 504.3(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Sections 504.3.5 and 504.3.6. The 20 - percent reduction for corrugated metallic chimney liner syste ms includes an allowance for one long - radius 90 - degree (1.57 rad) turn at the bottom of the liner. Where double - wall connectors are required, tee and wye fittings used to connect to the common vent chimney liner shall be listed double - wall fittings. Connec tions between chimney liners and listed double - wall fittings shall be made with listed adapter fittings designed for such purpose. 504.3.20 Chimney and vent location. Tables 504.3(1), 504.3(2), 504.3(3), 504.3(4 ), and 504.3(5) shall be used only for chimne ys and vents not exposed to the outdoors below the roof line. Tables 504.3(6a), 504.3(6b), 504.3(7a) and 504.3(7b) shall be used for clay - tile - lined exterior masonry chimneys, provided that all of the following con- ditions are met: 1. Vent connectors are Type B double wall . 2. Not less than one appliance is draft hood equipped. 3. The combined appliance input rating is less than the maximum capacity given by Table 504.3(6a) for NAT+NAT or Table 504.3(7a) for FAN+NAT. 4. The input rating of each space - hea ting appliance is greater than the minimum input rating given by Table 504.3(6b) for NAT+NAT or Table 504.3(7b) for FAN+NAT. 5. The vent connector sizing is in accordance with Table 504.3(3). 504.3.21 Connector maximum and minimum size. Vent connectors sha ll not be increased in size more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter or draft hood outlet diameter. Vent connectors for draft hood - equipped appliances shall not be smaller than the draft hood out let diameter. Where a vent connector size(s) determined from the tables for a fan - assisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size(s) shall be permitted provided that the installation complies with all of the foll owing conditions: CHIMNEYS AND VENTS 1. Vent connectors for fan - assisted appliance flue collars 12 inches ( 304.8 mm ) in diameter or smaller are not reduced by more than one table size ( e.g., 12 inches to 10 inches ( 304.8 mm to 254 mm) is a one - size reduc- tion ) and those large r than 12 inches ( 304.8 mm) in diameter are not reduced more than two table sizes ( e.g., 24 inches to 20 inches ( 609.6 mm to 508 mm) is a two - size reduction ). 2. The fan - assisted appliance(s) is common vented with a draft - hood - equipped appliance(s). 3. The vent connector has a smooth interior wall. 504.3.22 Component commingling. All combinations of pipe sizes, single - wall and double - wall metal pipe shall be allowed within any connector run(s) or within the common vent, provided that all of the appropriate tables permit all of the desired sizes and types of pipe, as if they were used for the entire length of the subject connector or vent. Where single - wall and Type B double - wall metal pipes are used for vent connectors within the same venting system, the com mon vent must be sized using Table 504.3(2) or 504.3(4), as appropriate. 504.3.23 Draft hood conversion accessories. Draft hood conversion accessories for use with masonry chimneys venting listed Category I fan - assisted appliances shall be listed and installed in accordance with the manufacturer’s instructions for such listed accessories. 504.3.24 Multiple sizes permitt ed. Where a table permits more than one diameter of pipe to be used for a connector or vent, all the permitted sizes shall be permitted to be used. 504.3.25 Table interpolation. Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table entries. 504.3.26 Extrapolation prohibited. Extrapolation beyond the table entries shall not be permitted. 504.3.27 Engineering calculations. For vent heights less than 6 feet ( 1828.8 mm) and greater than shown in the tables, engineering methods shall be used to calculate vent capacities. 504.3.28 Height entries. Where the actual height of a vent falls between entries in the height column of the appli- cable table in Tables 504.3(1) thro ugh 504.3(7b), either interpolation shall be used or the lower appliance input rating shown in the table shall be used for FAN MAX and NAT MAX column values and the higher appliance input rating shall be used for the FAN MIN column values. SECTION FGC 505 DIRECT - VENT, INTEGRAL VENT, MECHANICAL VENT AND VENTILATION/EXHAUST HOOD VENTING 505.1 General. The installation of direct - vent and integral vent appliances shall be in accordance with Section 503. Mechanical venting systems and exhaust hood venting system s shall be designed and installed in accordance with Section 503. 505.1.1 Commercial cooking appliances vented by exhaust hoods. Refer to Chapter 5 of the New York City Me- chanical Code . 505.1.2 Interlock requirements. Where commercial cooking appliances ar e vented by means of the Type I or Type II kitchen exhaust hood system that serves such appliances, the exhaust system shall be fan powered and the appliances shall be interlocked with the exhaust hood system to prevent appliance operation when the exhaust hood system is not operating. The meth od of interlock between the exhaust hood system and the appliances equipped with standing pilot burner ignition systems shall not cause such pilots to be extinguished. Where a solenoid valve is installed in the gas piping as part of an interlock system, ga s piping shall not be installed to bypass such valve. Dampers shall not be installed in the exhaust system. Exception: An interlock between the cooking appliance(s) and the exhaust hood system shall not be required where heat sensors or other approved meth ods automatically activate the exhaust hood system when cooking operations occur. CHIMNEYS AND VENTS SECTION FGC 506 FACTORY - BUILT CHIMNEYS 506.1 Building heating appliances. Factory - built chimneys for building heating appliances producing flue gases having a temperature not greater than 1,000°F ( 537.8 °C), measured at the entrance to the chimney, shall be listed and labeled in accordance with UL 103 and shall be installed and terminated in accordance with the manufacturer’s in- structions and this code . 506.2 Support. Where fac tory - built chimneys are supported by structural members, such as joists and rafters, such members shall be designed to support the additional load. 506.3 Medium - heat appliances. Factory - built chimneys for medium - heat appliances producing flue gases having a temperature above 1,000°F ( 537.8 °C), measured at the entrance to the chimney, shall be listed and labeled in accord- ance with UL 959 and shall be installed and terminated in accordance with the manufacturer’s instructions and this code . SECTION FGC 507 CHANGES IN APPLIANCE FUELS 507.1 Changes in appliance fuels. Conversion of appliances from solid or liquid fuel to natural gas or the addition of natural gas, shall be made in accordance with this code. Conversion from natural gas to, or the addition of, #2 fuel oil for a heating appliance shall be made only if: 1. The chimney design meets the requirements of this chapter for the conversion fuel and the chimney is test run and smoke tested in accordance with Sections 503.5.6.4 and 503.5.6.5. 2 . The chimney is sized to provide adequate draft and to vent the combustion products for the new fuel. 3. The chimney is thoroughly cleaned prior to the conversion to remove collected flue deposits. SECTION FGC 508 EXHAUST GASES FROM INTERNAL COMBUSTION EN GINES AND TURBINES 508.1 Exhaust system construction. The exhaust system from internal combustion engines and turbines shall be constructed in accordance with Section 811 of the New York City Mechanical Code .