CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. SPECIFIC APPLIANCES 6 - 10 2022 NEW YORK CITY FUEL GAS CODE 623.5.1 Clearances. A minimum clearance of 24 inches ( 609.6 mm) shall be maintained between the cooking top and combustible material above th e hood. The hood shall be at least as wide as the open - top broiler unit and be centered over the unit. 623.6 Commercial cooking appliance venting. Commercial cooking appliances, other than those exempted by Sec- tion 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1. 623.7 Domestic ventilation. When a hood is provided for a domestic cooking applia nce, the exhaust and make - up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code . Household cooking appliances shall have a vertical clearance above the cooking top of not le ss than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches ( 609.6 mm) , measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed: 1. The undersi de of the combustible material or metal cabinet above the cooking top is protected with not less than 1 / 4 - inch ( 6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick. 2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less tha n 1 / 4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance. 3. A listed cooking appliance or microwave o ven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance. SECTION FGC 624 WATER HEATERS 624.1 General. Water heaters shall be tested in accordance with ANSI Z21.10.1 /CSA 4.1 and ANSI Z21.10.3 /CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions . Water heaters utilizing fuels other than fuel gas shall be regulated by the New Yor k City Mechanical Code . Approval for water heaters 350,000 Btu/h input ( 102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection. 624.1.1 Installation requirements. The requirements for water heaters relative to s izing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following: 1. No person shall install or maintain in any dwelling unit a gas fuel - fired water heater unless the heater obtains combust ion air directly from the outside of the building. 2. No person shall install or maintain a gas - fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas - fueled heater is i nstalled. 3. Each heater shall be connected to a flue or outlet pipe. 624.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space - heating applications shall be listed and labeled f or such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an “H” code stamp. They shall be installed in accordance with the manufacturer’s instructions , the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code . SECTION FGC 625 REFRIGERATORS 625.1 General. Refrigerators shall be tested in accordance with ANSI Z21.19 /CSA 1.4 a nd shall be installed in ac- cordance with the manufacturer’s instructions . Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instr uctions are not available, not less than 2 inches ( 50.8 SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 11 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches ( 304.8 mm) above the top. SECTION FGC 626 GAS - FIRED TOILETS 626.1 General. Gas - fired toilets are not approved for use in New York City . 626.2 Reserved. SECTION FGC 627 AIR CONDITIONING APPLIANCES 627.1 General. Gas - fired air - conditioning appliances shall be tested in accordance with ANSI Z21.40.1 /CGA 2.91 or ANSI Z21.40.2 /CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions . 627.2 Independent piping. Gas piping serving heating appli ances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402). 627.3 Connection of gas engine - powered air conditioners. To protect against the effects of normal vibra tion in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1. 627.4 Clearances for indoor installation. Air - condition ing appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 . Exceptions: 1. Air - conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions . Air - conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearanc es to combustible material, provided that the combustible material is protected in ac- cordance with Table 308.2. 2. Air - conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accorda nce with such listing and the manufacturer’s instructions. 627.5 Alcove and closet installation. Air - conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air - conditioning appliances in alcoves and closets shall not be reduced by the protection methods de- scribed in Table 308.2. 627.6 Installation. Air - conditioning appliances shall be installed in ac cordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of nonc ombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof. 627.7 Plenums and air ducts. A plenum supplied as a part of the air - conditioning appliance shall be installed in accorda nce with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The me thod of connecting supply and return ducts shall facilitate proper circulation of air. Where the air - conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air. 627.8 Refrigeration coils. A refrigeration coil shall not be installed in conjunction with a forced - air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duc t system and cooling coil at the air throughput necessary for heating or CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. SPECIFIC APPLIANCES 6 - 10 2022 NEW YORK CITY FUEL GAS CODE 623.5.1 Clearances. A minimum clearance of 24 inches ( 609.6 mm) shall be maintained between the cooking top and combustible material above th e hood. The hood shall be at least as wide as the open - top broiler unit and be centered over the unit. 623.6 Commercial cooking appliance venting. Commercial cooking appliances, other than those exempted by Sec- tion 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1. 623.7 Domestic ventilation. When a hood is provided for a domestic cooking applia nce, the exhaust and make - up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code . Household cooking appliances shall have a vertical clearance above the cooking top of not le ss than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches ( 609.6 mm) , measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed: 1. The undersi de of the combustible material or metal cabinet above the cooking top is protected with not less than 1 / 4 - inch ( 6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick. 2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less tha n 1 / 4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance. 3. A listed cooking appliance or microwave o ven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance. SECTION FGC 624 WATER HEATERS 624.1 General. Water heaters shall be tested in accordance with ANSI Z21.10.1 /CSA 4.1 and ANSI Z21.10.3 /CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions . Water heaters utilizing fuels other than fuel gas shall be regulated by the New Yor k City Mechanical Code . Approval for water heaters 350,000 Btu/h input ( 102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection. 624.1.1 Installation requirements. The requirements for water heaters relative to s izing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following: 1. No person shall install or maintain in any dwelling unit a gas fuel - fired water heater unless the heater obtains combust ion air directly from the outside of the building. 2. No person shall install or maintain a gas - fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas - fueled heater is i nstalled. 3. Each heater shall be connected to a flue or outlet pipe. 624.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space - heating applications shall be listed and labeled f or such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an “H” code stamp. They shall be installed in accordance with the manufacturer’s instructions , the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code . SECTION FGC 625 REFRIGERATORS 625.1 General. Refrigerators shall be tested in accordance with ANSI Z21.19 /CSA 1.4 a nd shall be installed in ac- cordance with the manufacturer’s instructions . Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instr uctions are not available, not less than 2 inches ( 50.8 SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 11 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches ( 304.8 mm) above the top. SECTION FGC 626 GAS - FIRED TOILETS 626.1 General. Gas - fired toilets are not approved for use in New York City . 626.2 Reserved. SECTION FGC 627 AIR CONDITIONING APPLIANCES 627.1 General. Gas - fired air - conditioning appliances shall be tested in accordance with ANSI Z21.40.1 /CGA 2.91 or ANSI Z21.40.2 /CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions . 627.2 Independent piping. Gas piping serving heating appli ances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402). 627.3 Connection of gas engine - powered air conditioners. To protect against the effects of normal vibra tion in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1. 627.4 Clearances for indoor installation. Air - condition ing appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 . Exceptions: 1. Air - conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions . Air - conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearanc es to combustible material, provided that the combustible material is protected in ac- cordance with Table 308.2. 2. Air - conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accorda nce with such listing and the manufacturer’s instructions. 627.5 Alcove and closet installation. Air - conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air - conditioning appliances in alcoves and closets shall not be reduced by the protection methods de- scribed in Table 308.2. 627.6 Installation. Air - conditioning appliances shall be installed in ac cordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of nonc ombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof. 627.7 Plenums and air ducts. A plenum supplied as a part of the air - conditioning appliance shall be installed in accorda nce with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The me thod of connecting supply and return ducts shall facilitate proper circulation of air. Where the air - conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air. 627.8 Refrigeration coils. A refrigeration coil shall not be installed in conjunction with a forced - air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duc t system and cooling coil at the air throughput necessary for heating or SPECIFIC APPLIANCES 6 - 12 2022 NEW YORK CITY FUEL GAS CODE cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace. Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element. 627.9 Cooling units used with heating boilers. Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent th e chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air - handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with f low control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 627.10 Switches in electrical supply line. Means for interrupting the electrical supply to the air - conditioning appli- ance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower. SECTION FGC 628 ILLUMINATING APPLIANCES 628.1 General. Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer’s instructions . 628.2 Moun ting on buildings. Illuminating appliances designed for wall or ceiling mounting shall be securely at- tached to substantial structures in such a manner that they are not dependent on the gas piping for support. 628.3 Mounting on posts. Illuminating applianc es designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted in accordance with the requirements of the New York City Building Code . Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them. 628.4 Appliance pressure regulators. Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pres sure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance. SECTION FGC 629 CERAMIC KILNS 629.1 General. Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1. Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on an approved engineering evaluation. SEC TION FGC 630 INFRARED RADIANT HEATERS 630.1 General. Infrared radiant heaters shall be tested in accordance with ANSI Z83.19 /CSA 2.35 or ANSI Z83.20 /CSA 2.34 and shall be installed in accordance with the manufacturer’s instructions . 630.2 Support. Infrared radiant heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hangers and brackets shall be of noncombustible material. 630.3 Combustion and ventilation air. Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m 3 /min/kW) of the aggrega te CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. SPECIFIC APPLIANCES 6 - 10 2022 NEW YORK CITY FUEL GAS CODE 623.5.1 Clearances. A minimum clearance of 24 inches ( 609.6 mm) shall be maintained between the cooking top and combustible material above th e hood. The hood shall be at least as wide as the open - top broiler unit and be centered over the unit. 623.6 Commercial cooking appliance venting. Commercial cooking appliances, other than those exempted by Sec- tion 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1. 623.7 Domestic ventilation. When a hood is provided for a domestic cooking applia nce, the exhaust and make - up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code . Household cooking appliances shall have a vertical clearance above the cooking top of not le ss than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches ( 609.6 mm) , measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed: 1. The undersi de of the combustible material or metal cabinet above the cooking top is protected with not less than 1 / 4 - inch ( 6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick. 2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less tha n 1 / 4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance. 3. A listed cooking appliance or microwave o ven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance. SECTION FGC 624 WATER HEATERS 624.1 General. Water heaters shall be tested in accordance with ANSI Z21.10.1 /CSA 4.1 and ANSI Z21.10.3 /CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions . Water heaters utilizing fuels other than fuel gas shall be regulated by the New Yor k City Mechanical Code . Approval for water heaters 350,000 Btu/h input ( 102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection. 624.1.1 Installation requirements. The requirements for water heaters relative to s izing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following: 1. No person shall install or maintain in any dwelling unit a gas fuel - fired water heater unless the heater obtains combust ion air directly from the outside of the building. 2. No person shall install or maintain a gas - fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas - fueled heater is i nstalled. 3. Each heater shall be connected to a flue or outlet pipe. 624.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space - heating applications shall be listed and labeled f or such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an “H” code stamp. They shall be installed in accordance with the manufacturer’s instructions , the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code . SECTION FGC 625 REFRIGERATORS 625.1 General. Refrigerators shall be tested in accordance with ANSI Z21.19 /CSA 1.4 a nd shall be installed in ac- cordance with the manufacturer’s instructions . Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instr uctions are not available, not less than 2 inches ( 50.8 SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 11 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches ( 304.8 mm) above the top. SECTION FGC 626 GAS - FIRED TOILETS 626.1 General. Gas - fired toilets are not approved for use in New York City . 626.2 Reserved. SECTION FGC 627 AIR CONDITIONING APPLIANCES 627.1 General. Gas - fired air - conditioning appliances shall be tested in accordance with ANSI Z21.40.1 /CGA 2.91 or ANSI Z21.40.2 /CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions . 627.2 Independent piping. Gas piping serving heating appli ances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402). 627.3 Connection of gas engine - powered air conditioners. To protect against the effects of normal vibra tion in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1. 627.4 Clearances for indoor installation. Air - condition ing appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 . Exceptions: 1. Air - conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions . Air - conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearanc es to combustible material, provided that the combustible material is protected in ac- cordance with Table 308.2. 2. Air - conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accorda nce with such listing and the manufacturer’s instructions. 627.5 Alcove and closet installation. Air - conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air - conditioning appliances in alcoves and closets shall not be reduced by the protection methods de- scribed in Table 308.2. 627.6 Installation. Air - conditioning appliances shall be installed in ac cordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of nonc ombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof. 627.7 Plenums and air ducts. A plenum supplied as a part of the air - conditioning appliance shall be installed in accorda nce with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The me thod of connecting supply and return ducts shall facilitate proper circulation of air. Where the air - conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air. 627.8 Refrigeration coils. A refrigeration coil shall not be installed in conjunction with a forced - air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duc t system and cooling coil at the air throughput necessary for heating or SPECIFIC APPLIANCES 6 - 12 2022 NEW YORK CITY FUEL GAS CODE cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace. Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element. 627.9 Cooling units used with heating boilers. Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent th e chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air - handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with f low control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 627.10 Switches in electrical supply line. Means for interrupting the electrical supply to the air - conditioning appli- ance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower. SECTION FGC 628 ILLUMINATING APPLIANCES 628.1 General. Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer’s instructions . 628.2 Moun ting on buildings. Illuminating appliances designed for wall or ceiling mounting shall be securely at- tached to substantial structures in such a manner that they are not dependent on the gas piping for support. 628.3 Mounting on posts. Illuminating applianc es designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted in accordance with the requirements of the New York City Building Code . Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them. 628.4 Appliance pressure regulators. Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pres sure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance. SECTION FGC 629 CERAMIC KILNS 629.1 General. Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1. Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on an approved engineering evaluation. SEC TION FGC 630 INFRARED RADIANT HEATERS 630.1 General. Infrared radiant heaters shall be tested in accordance with ANSI Z83.19 /CSA 2.35 or ANSI Z83.20 /CSA 2.34 and shall be installed in accordance with the manufacturer’s instructions . 630.2 Support. Infrared radiant heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hangers and brackets shall be of noncombustible material. 630.3 Combustion and ventilation air. Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m 3 /min/kW) of the aggrega te CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. SPECIFIC APPLIANCES 6 - 10 2022 NEW YORK CITY FUEL GAS CODE 623.5.1 Clearances. A minimum clearance of 24 inches ( 609.6 mm) shall be maintained between the cooking top and combustible material above th e hood. The hood shall be at least as wide as the open - top broiler unit and be centered over the unit. 623.6 Commercial cooking appliance venting. Commercial cooking appliances, other than those exempted by Sec- tion 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1. 623.7 Domestic ventilation. When a hood is provided for a domestic cooking applia nce, the exhaust and make - up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code . Household cooking appliances shall have a vertical clearance above the cooking top of not le ss than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches ( 609.6 mm) , measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed: 1. The undersi de of the combustible material or metal cabinet above the cooking top is protected with not less than 1 / 4 - inch ( 6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick. 2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less tha n 1 / 4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance. 3. A listed cooking appliance or microwave o ven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance. SECTION FGC 624 WATER HEATERS 624.1 General. Water heaters shall be tested in accordance with ANSI Z21.10.1 /CSA 4.1 and ANSI Z21.10.3 /CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions . Water heaters utilizing fuels other than fuel gas shall be regulated by the New Yor k City Mechanical Code . Approval for water heaters 350,000 Btu/h input ( 102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection. 624.1.1 Installation requirements. The requirements for water heaters relative to s izing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following: 1. No person shall install or maintain in any dwelling unit a gas fuel - fired water heater unless the heater obtains combust ion air directly from the outside of the building. 2. No person shall install or maintain a gas - fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas - fueled heater is i nstalled. 3. Each heater shall be connected to a flue or outlet pipe. 624.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space - heating applications shall be listed and labeled f or such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an “H” code stamp. They shall be installed in accordance with the manufacturer’s instructions , the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code . SECTION FGC 625 REFRIGERATORS 625.1 General. Refrigerators shall be tested in accordance with ANSI Z21.19 /CSA 1.4 a nd shall be installed in ac- cordance with the manufacturer’s instructions . Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instr uctions are not available, not less than 2 inches ( 50.8 SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 11 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches ( 304.8 mm) above the top. SECTION FGC 626 GAS - FIRED TOILETS 626.1 General. Gas - fired toilets are not approved for use in New York City . 626.2 Reserved. SECTION FGC 627 AIR CONDITIONING APPLIANCES 627.1 General. Gas - fired air - conditioning appliances shall be tested in accordance with ANSI Z21.40.1 /CGA 2.91 or ANSI Z21.40.2 /CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions . 627.2 Independent piping. Gas piping serving heating appli ances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402). 627.3 Connection of gas engine - powered air conditioners. To protect against the effects of normal vibra tion in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1. 627.4 Clearances for indoor installation. Air - condition ing appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 . Exceptions: 1. Air - conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions . Air - conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearanc es to combustible material, provided that the combustible material is protected in ac- cordance with Table 308.2. 2. Air - conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accorda nce with such listing and the manufacturer’s instructions. 627.5 Alcove and closet installation. Air - conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air - conditioning appliances in alcoves and closets shall not be reduced by the protection methods de- scribed in Table 308.2. 627.6 Installation. Air - conditioning appliances shall be installed in ac cordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of nonc ombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof. 627.7 Plenums and air ducts. A plenum supplied as a part of the air - conditioning appliance shall be installed in accorda nce with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The me thod of connecting supply and return ducts shall facilitate proper circulation of air. Where the air - conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air. 627.8 Refrigeration coils. A refrigeration coil shall not be installed in conjunction with a forced - air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duc t system and cooling coil at the air throughput necessary for heating or SPECIFIC APPLIANCES 6 - 12 2022 NEW YORK CITY FUEL GAS CODE cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace. Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element. 627.9 Cooling units used with heating boilers. Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent th e chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air - handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with f low control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 627.10 Switches in electrical supply line. Means for interrupting the electrical supply to the air - conditioning appli- ance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower. SECTION FGC 628 ILLUMINATING APPLIANCES 628.1 General. Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer’s instructions . 628.2 Moun ting on buildings. Illuminating appliances designed for wall or ceiling mounting shall be securely at- tached to substantial structures in such a manner that they are not dependent on the gas piping for support. 628.3 Mounting on posts. Illuminating applianc es designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted in accordance with the requirements of the New York City Building Code . Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them. 628.4 Appliance pressure regulators. Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pres sure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance. SECTION FGC 629 CERAMIC KILNS 629.1 General. Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1. Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on an approved engineering evaluation. SEC TION FGC 630 INFRARED RADIANT HEATERS 630.1 General. Infrared radiant heaters shall be tested in accordance with ANSI Z83.19 /CSA 2.35 or ANSI Z83.20 /CSA 2.34 and shall be installed in accordance with the manufacturer’s instructions . 630.2 Support. Infrared radiant heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hangers and brackets shall be of noncombustible material. 630.3 Combustion and ventilation air. Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m 3 /min/kW) of the aggrega te SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 13 input rating of all such heaters installed in the space. Exhaust openings for removing flue products shall be above the level of the heaters. 630.4 Installation in commercial garages and air - craft hangars. Overhead infrared heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 631 BOILERS 631.1 Standards. Boilers shall be listed in accordance with the requirements of ANSI Z21.13 /CSA 4.9 o r UL 795. If applicable, the boiler shall be designed and constructed in accordance with the requirements of ASME CSD - 1 and as applicable, the ASME Boiler and Pressure Vessel Code , Sections I, II, IV, V, VI and IX and NFPA 85 . Low - pressure boilers shall co nform to the requirements of 12 NYCRR Part 4 and high - pressure boilers shall conform to the require- ments of 12 NYCRR Part 14. 631.2 Installation. In addition to the requirements of this code, the installation of boilers shall be in accordance with the manu facturer’s instructions and the New York City Mechanical Code . Operating instructions of a permanent type shall be attached to the boiler. Spill switches must be installed on all flue gas draft openings and interlocked with all vented appliances. Boilers shall have all controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. The manufacturer’s rating data and the nameplate sha ll be attached to the boiler. 631.3 Clearance to combustible materials. Clearances to combustible materials shall be in accordance with Section 308.4. SECTION FGC 632 EQUIPMENT INSTALLED IN EXISTING UNLISTED BOILERS 632.1 General. Gas equipment installed i n existing unlisted boilers shall comply with Section 631.1 and shall be installed in accordance with the manufacturer’s instructions and the New York City Mechanical Code . SECTION FGC 633 STATIONARY FUEL CELL POWER SYSTEMS 633.1 General. Stationary fuel c ell power systems having a power output not exceeding 10 MW shall be tested in accordance with ANSI/CSA America FC 1 and shall be installed in accordance with the manufacturer’s instructions , NFPA 853, the New York City Building Code , the New York City Fir e Code and the New York City Electrical Code . Indoor stationary fuel cell power systems used in hydrogen generating systems shall be located in accordance with the requirements of Section 706 of this code. SECTION FGC 634 CHIMNEY DAMPER OPENING AREA 634.1 Free opening area of chimney dampers. Where an unlisted decorative appliance for installation in a vented fireplace is installed, the fireplace damper shall have a permanent free opening equal to or greater than specified in Table 634.1. TABLE 634.1 FREE OPENING AREA OF CHIMNEY DAMPER FOR VENTING FLUE GASES FROM UNLISTED DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES CHIMNEY HEIGHT (feet) MINIMUM PERMANENT FREE OPENING (square inches) a 8 13 20 29 39 51 64 SPECIFIC APPLIANCES 6 - 14 2022 NEW YORK CITY FUEL GAS CODE Appliance input rating (Btu per hour) 6 7,800 14,000 23,200 34,000 46,400 62,400 80,000 8 8,400 15,200 25,200 37,000 50,400 68,000 86,000 10 9,000 16,800 27,600 40,400 55,800 74,400 96,400 15 9,800 18,200 30,200 44,600 62,400 84,000 108,800 20 10,600 20,200 32,600 50,400 68,400 94,000 122,200 30 11,200 21,600 36,600 55,200 76,800 105,800 138,600 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645. 16 m 2 , 1 British thermal unit per hour = 0.2931 W. a. The first six minimum permanent free openings (8 to 51 square inches) correspond approximately to the cross - sectional areas of chimneys having diameters of 3 through 8 inches, respectively. The 64 - square - inch opening corresponds to the cross - sectional area of standard 8 - inch by 8 - inch chimney tile. SECTION FGC 635 GASEOUS HYDROGEN SYSTEMS 635.1 Installation. The installation of gaseous hydrogen systems shall be in accordance with the applicable require- ments of the New York City Fire Code , the New York City Building Code , and Chapter 7 of this code . SECTION FGC 636 OUTDOOR DECORATIVE APPLIANCES 636.1 General. Permanently fixed - in - place outdoor decorative appliances shall be tested in accordance with ANSI Z21.97 /CSA 2.41 and shall be installed in accordance with the manufacturer’s instructions. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. SPECIFIC APPLIANCES 6 - 10 2022 NEW YORK CITY FUEL GAS CODE 623.5.1 Clearances. A minimum clearance of 24 inches ( 609.6 mm) shall be maintained between the cooking top and combustible material above th e hood. The hood shall be at least as wide as the open - top broiler unit and be centered over the unit. 623.6 Commercial cooking appliance venting. Commercial cooking appliances, other than those exempted by Sec- tion 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1. 623.7 Domestic ventilation. When a hood is provided for a domestic cooking applia nce, the exhaust and make - up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code . Household cooking appliances shall have a vertical clearance above the cooking top of not le ss than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches ( 609.6 mm) , measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed: 1. The undersi de of the combustible material or metal cabinet above the cooking top is protected with not less than 1 / 4 - inch ( 6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick. 2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less tha n 1 / 4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance. 3. A listed cooking appliance or microwave o ven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance. SECTION FGC 624 WATER HEATERS 624.1 General. Water heaters shall be tested in accordance with ANSI Z21.10.1 /CSA 4.1 and ANSI Z21.10.3 /CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions . Water heaters utilizing fuels other than fuel gas shall be regulated by the New Yor k City Mechanical Code . Approval for water heaters 350,000 Btu/h input ( 102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection. 624.1.1 Installation requirements. The requirements for water heaters relative to s izing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following: 1. No person shall install or maintain in any dwelling unit a gas fuel - fired water heater unless the heater obtains combust ion air directly from the outside of the building. 2. No person shall install or maintain a gas - fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas - fueled heater is i nstalled. 3. Each heater shall be connected to a flue or outlet pipe. 624.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space - heating applications shall be listed and labeled f or such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an “H” code stamp. They shall be installed in accordance with the manufacturer’s instructions , the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code . SECTION FGC 625 REFRIGERATORS 625.1 General. Refrigerators shall be tested in accordance with ANSI Z21.19 /CSA 1.4 a nd shall be installed in ac- cordance with the manufacturer’s instructions . Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instr uctions are not available, not less than 2 inches ( 50.8 SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 11 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches ( 304.8 mm) above the top. SECTION FGC 626 GAS - FIRED TOILETS 626.1 General. Gas - fired toilets are not approved for use in New York City . 626.2 Reserved. SECTION FGC 627 AIR CONDITIONING APPLIANCES 627.1 General. Gas - fired air - conditioning appliances shall be tested in accordance with ANSI Z21.40.1 /CGA 2.91 or ANSI Z21.40.2 /CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions . 627.2 Independent piping. Gas piping serving heating appli ances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402). 627.3 Connection of gas engine - powered air conditioners. To protect against the effects of normal vibra tion in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1. 627.4 Clearances for indoor installation. Air - condition ing appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 . Exceptions: 1. Air - conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions . Air - conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearanc es to combustible material, provided that the combustible material is protected in ac- cordance with Table 308.2. 2. Air - conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accorda nce with such listing and the manufacturer’s instructions. 627.5 Alcove and closet installation. Air - conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air - conditioning appliances in alcoves and closets shall not be reduced by the protection methods de- scribed in Table 308.2. 627.6 Installation. Air - conditioning appliances shall be installed in ac cordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of nonc ombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof. 627.7 Plenums and air ducts. A plenum supplied as a part of the air - conditioning appliance shall be installed in accorda nce with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The me thod of connecting supply and return ducts shall facilitate proper circulation of air. Where the air - conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air. 627.8 Refrigeration coils. A refrigeration coil shall not be installed in conjunction with a forced - air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duc t system and cooling coil at the air throughput necessary for heating or SPECIFIC APPLIANCES 6 - 12 2022 NEW YORK CITY FUEL GAS CODE cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace. Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element. 627.9 Cooling units used with heating boilers. Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent th e chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air - handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with f low control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 627.10 Switches in electrical supply line. Means for interrupting the electrical supply to the air - conditioning appli- ance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower. SECTION FGC 628 ILLUMINATING APPLIANCES 628.1 General. Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer’s instructions . 628.2 Moun ting on buildings. Illuminating appliances designed for wall or ceiling mounting shall be securely at- tached to substantial structures in such a manner that they are not dependent on the gas piping for support. 628.3 Mounting on posts. Illuminating applianc es designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted in accordance with the requirements of the New York City Building Code . Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them. 628.4 Appliance pressure regulators. Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pres sure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance. SECTION FGC 629 CERAMIC KILNS 629.1 General. Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1. Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on an approved engineering evaluation. SEC TION FGC 630 INFRARED RADIANT HEATERS 630.1 General. Infrared radiant heaters shall be tested in accordance with ANSI Z83.19 /CSA 2.35 or ANSI Z83.20 /CSA 2.34 and shall be installed in accordance with the manufacturer’s instructions . 630.2 Support. Infrared radiant heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hangers and brackets shall be of noncombustible material. 630.3 Combustion and ventilation air. Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m 3 /min/kW) of the aggrega te SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 13 input rating of all such heaters installed in the space. Exhaust openings for removing flue products shall be above the level of the heaters. 630.4 Installation in commercial garages and air - craft hangars. Overhead infrared heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 631 BOILERS 631.1 Standards. Boilers shall be listed in accordance with the requirements of ANSI Z21.13 /CSA 4.9 o r UL 795. If applicable, the boiler shall be designed and constructed in accordance with the requirements of ASME CSD - 1 and as applicable, the ASME Boiler and Pressure Vessel Code , Sections I, II, IV, V, VI and IX and NFPA 85 . Low - pressure boilers shall co nform to the requirements of 12 NYCRR Part 4 and high - pressure boilers shall conform to the require- ments of 12 NYCRR Part 14. 631.2 Installation. In addition to the requirements of this code, the installation of boilers shall be in accordance with the manu facturer’s instructions and the New York City Mechanical Code . Operating instructions of a permanent type shall be attached to the boiler. Spill switches must be installed on all flue gas draft openings and interlocked with all vented appliances. Boilers shall have all controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. The manufacturer’s rating data and the nameplate sha ll be attached to the boiler. 631.3 Clearance to combustible materials. Clearances to combustible materials shall be in accordance with Section 308.4. SECTION FGC 632 EQUIPMENT INSTALLED IN EXISTING UNLISTED BOILERS 632.1 General. Gas equipment installed i n existing unlisted boilers shall comply with Section 631.1 and shall be installed in accordance with the manufacturer’s instructions and the New York City Mechanical Code . SECTION FGC 633 STATIONARY FUEL CELL POWER SYSTEMS 633.1 General. Stationary fuel c ell power systems having a power output not exceeding 10 MW shall be tested in accordance with ANSI/CSA America FC 1 and shall be installed in accordance with the manufacturer’s instructions , NFPA 853, the New York City Building Code , the New York City Fir e Code and the New York City Electrical Code . Indoor stationary fuel cell power systems used in hydrogen generating systems shall be located in accordance with the requirements of Section 706 of this code. SECTION FGC 634 CHIMNEY DAMPER OPENING AREA 634.1 Free opening area of chimney dampers. Where an unlisted decorative appliance for installation in a vented fireplace is installed, the fireplace damper shall have a permanent free opening equal to or greater than specified in Table 634.1. TABLE 634.1 FREE OPENING AREA OF CHIMNEY DAMPER FOR VENTING FLUE GASES FROM UNLISTED DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES CHIMNEY HEIGHT (feet) MINIMUM PERMANENT FREE OPENING (square inches) a 8 13 20 29 39 51 64 SPECIFIC APPLIANCES 6 - 14 2022 NEW YORK CITY FUEL GAS CODE Appliance input rating (Btu per hour) 6 7,800 14,000 23,200 34,000 46,400 62,400 80,000 8 8,400 15,200 25,200 37,000 50,400 68,000 86,000 10 9,000 16,800 27,600 40,400 55,800 74,400 96,400 15 9,800 18,200 30,200 44,600 62,400 84,000 108,800 20 10,600 20,200 32,600 50,400 68,400 94,000 122,200 30 11,200 21,600 36,600 55,200 76,800 105,800 138,600 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645. 16 m 2 , 1 British thermal unit per hour = 0.2931 W. a. The first six minimum permanent free openings (8 to 51 square inches) correspond approximately to the cross - sectional areas of chimneys having diameters of 3 through 8 inches, respectively. The 64 - square - inch opening corresponds to the cross - sectional area of standard 8 - inch by 8 - inch chimney tile. SECTION FGC 635 GASEOUS HYDROGEN SYSTEMS 635.1 Installation. The installation of gaseous hydrogen systems shall be in accordance with the applicable require- ments of the New York City Fire Code , the New York City Building Code , and Chapter 7 of this code . SECTION FGC 636 OUTDOOR DECORATIVE APPLIANCES 636.1 General. Permanently fixed - in - place outdoor decorative appliances shall be tested in accordance with ANSI Z21.97 /CSA 2.41 and shall be installed in accordance with the manufacturer’s instructions. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. SPECIFIC APPLIANCES 6 - 10 2022 NEW YORK CITY FUEL GAS CODE 623.5.1 Clearances. A minimum clearance of 24 inches ( 609.6 mm) shall be maintained between the cooking top and combustible material above th e hood. The hood shall be at least as wide as the open - top broiler unit and be centered over the unit. 623.6 Commercial cooking appliance venting. Commercial cooking appliances, other than those exempted by Sec- tion 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1. 623.7 Domestic ventilation. When a hood is provided for a domestic cooking applia nce, the exhaust and make - up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code . Household cooking appliances shall have a vertical clearance above the cooking top of not le ss than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches ( 609.6 mm) , measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed: 1. The undersi de of the combustible material or metal cabinet above the cooking top is protected with not less than 1 / 4 - inch ( 6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick. 2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less tha n 1 / 4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance. 3. A listed cooking appliance or microwave o ven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance. SECTION FGC 624 WATER HEATERS 624.1 General. Water heaters shall be tested in accordance with ANSI Z21.10.1 /CSA 4.1 and ANSI Z21.10.3 /CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions . Water heaters utilizing fuels other than fuel gas shall be regulated by the New Yor k City Mechanical Code . Approval for water heaters 350,000 Btu/h input ( 102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection. 624.1.1 Installation requirements. The requirements for water heaters relative to s izing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following: 1. No person shall install or maintain in any dwelling unit a gas fuel - fired water heater unless the heater obtains combust ion air directly from the outside of the building. 2. No person shall install or maintain a gas - fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas - fueled heater is i nstalled. 3. Each heater shall be connected to a flue or outlet pipe. 624.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space - heating applications shall be listed and labeled f or such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an “H” code stamp. They shall be installed in accordance with the manufacturer’s instructions , the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code . SECTION FGC 625 REFRIGERATORS 625.1 General. Refrigerators shall be tested in accordance with ANSI Z21.19 /CSA 1.4 a nd shall be installed in ac- cordance with the manufacturer’s instructions . Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instr uctions are not available, not less than 2 inches ( 50.8 SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 11 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches ( 304.8 mm) above the top. SECTION FGC 626 GAS - FIRED TOILETS 626.1 General. Gas - fired toilets are not approved for use in New York City . 626.2 Reserved. SECTION FGC 627 AIR CONDITIONING APPLIANCES 627.1 General. Gas - fired air - conditioning appliances shall be tested in accordance with ANSI Z21.40.1 /CGA 2.91 or ANSI Z21.40.2 /CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions . 627.2 Independent piping. Gas piping serving heating appli ances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402). 627.3 Connection of gas engine - powered air conditioners. To protect against the effects of normal vibra tion in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1. 627.4 Clearances for indoor installation. Air - condition ing appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 . Exceptions: 1. Air - conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions . Air - conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearanc es to combustible material, provided that the combustible material is protected in ac- cordance with Table 308.2. 2. Air - conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accorda nce with such listing and the manufacturer’s instructions. 627.5 Alcove and closet installation. Air - conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air - conditioning appliances in alcoves and closets shall not be reduced by the protection methods de- scribed in Table 308.2. 627.6 Installation. Air - conditioning appliances shall be installed in ac cordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of nonc ombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof. 627.7 Plenums and air ducts. A plenum supplied as a part of the air - conditioning appliance shall be installed in accorda nce with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The me thod of connecting supply and return ducts shall facilitate proper circulation of air. Where the air - conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air. 627.8 Refrigeration coils. A refrigeration coil shall not be installed in conjunction with a forced - air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duc t system and cooling coil at the air throughput necessary for heating or SPECIFIC APPLIANCES 6 - 12 2022 NEW YORK CITY FUEL GAS CODE cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace. Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element. 627.9 Cooling units used with heating boilers. Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent th e chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air - handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with f low control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 627.10 Switches in electrical supply line. Means for interrupting the electrical supply to the air - conditioning appli- ance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower. SECTION FGC 628 ILLUMINATING APPLIANCES 628.1 General. Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer’s instructions . 628.2 Moun ting on buildings. Illuminating appliances designed for wall or ceiling mounting shall be securely at- tached to substantial structures in such a manner that they are not dependent on the gas piping for support. 628.3 Mounting on posts. Illuminating applianc es designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted in accordance with the requirements of the New York City Building Code . Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them. 628.4 Appliance pressure regulators. Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pres sure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance. SECTION FGC 629 CERAMIC KILNS 629.1 General. Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1. Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on an approved engineering evaluation. SEC TION FGC 630 INFRARED RADIANT HEATERS 630.1 General. Infrared radiant heaters shall be tested in accordance with ANSI Z83.19 /CSA 2.35 or ANSI Z83.20 /CSA 2.34 and shall be installed in accordance with the manufacturer’s instructions . 630.2 Support. Infrared radiant heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hangers and brackets shall be of noncombustible material. 630.3 Combustion and ventilation air. Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m 3 /min/kW) of the aggrega te SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 13 input rating of all such heaters installed in the space. Exhaust openings for removing flue products shall be above the level of the heaters. 630.4 Installation in commercial garages and air - craft hangars. Overhead infrared heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 631 BOILERS 631.1 Standards. Boilers shall be listed in accordance with the requirements of ANSI Z21.13 /CSA 4.9 o r UL 795. If applicable, the boiler shall be designed and constructed in accordance with the requirements of ASME CSD - 1 and as applicable, the ASME Boiler and Pressure Vessel Code , Sections I, II, IV, V, VI and IX and NFPA 85 . Low - pressure boilers shall co nform to the requirements of 12 NYCRR Part 4 and high - pressure boilers shall conform to the require- ments of 12 NYCRR Part 14. 631.2 Installation. In addition to the requirements of this code, the installation of boilers shall be in accordance with the manu facturer’s instructions and the New York City Mechanical Code . Operating instructions of a permanent type shall be attached to the boiler. Spill switches must be installed on all flue gas draft openings and interlocked with all vented appliances. Boilers shall have all controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. The manufacturer’s rating data and the nameplate sha ll be attached to the boiler. 631.3 Clearance to combustible materials. Clearances to combustible materials shall be in accordance with Section 308.4. SECTION FGC 632 EQUIPMENT INSTALLED IN EXISTING UNLISTED BOILERS 632.1 General. Gas equipment installed i n existing unlisted boilers shall comply with Section 631.1 and shall be installed in accordance with the manufacturer’s instructions and the New York City Mechanical Code . SECTION FGC 633 STATIONARY FUEL CELL POWER SYSTEMS 633.1 General. Stationary fuel c ell power systems having a power output not exceeding 10 MW shall be tested in accordance with ANSI/CSA America FC 1 and shall be installed in accordance with the manufacturer’s instructions , NFPA 853, the New York City Building Code , the New York City Fir e Code and the New York City Electrical Code . Indoor stationary fuel cell power systems used in hydrogen generating systems shall be located in accordance with the requirements of Section 706 of this code. SECTION FGC 634 CHIMNEY DAMPER OPENING AREA 634.1 Free opening area of chimney dampers. Where an unlisted decorative appliance for installation in a vented fireplace is installed, the fireplace damper shall have a permanent free opening equal to or greater than specified in Table 634.1. TABLE 634.1 FREE OPENING AREA OF CHIMNEY DAMPER FOR VENTING FLUE GASES FROM UNLISTED DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES CHIMNEY HEIGHT (feet) MINIMUM PERMANENT FREE OPENING (square inches) a 8 13 20 29 39 51 64 SPECIFIC APPLIANCES 6 - 14 2022 NEW YORK CITY FUEL GAS CODE Appliance input rating (Btu per hour) 6 7,800 14,000 23,200 34,000 46,400 62,400 80,000 8 8,400 15,200 25,200 37,000 50,400 68,000 86,000 10 9,000 16,800 27,600 40,400 55,800 74,400 96,400 15 9,800 18,200 30,200 44,600 62,400 84,000 108,800 20 10,600 20,200 32,600 50,400 68,400 94,000 122,200 30 11,200 21,600 36,600 55,200 76,800 105,800 138,600 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645. 16 m 2 , 1 British thermal unit per hour = 0.2931 W. a. The first six minimum permanent free openings (8 to 51 square inches) correspond approximately to the cross - sectional areas of chimneys having diameters of 3 through 8 inches, respectively. The 64 - square - inch opening corresponds to the cross - sectional area of standard 8 - inch by 8 - inch chimney tile. SECTION FGC 635 GASEOUS HYDROGEN SYSTEMS 635.1 Installation. The installation of gaseous hydrogen systems shall be in accordance with the applicable require- ments of the New York City Fire Code , the New York City Building Code , and Chapter 7 of this code . SECTION FGC 636 OUTDOOR DECORATIVE APPLIANCES 636.1 General. Permanently fixed - in - place outdoor decorative appliances shall be tested in accordance with ANSI Z21.97 /CSA 2.41 and shall be installed in accordance with the manufacturer’s instructions. CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment specifically identified herein. The approval, design, installation, construction, maintenance, alteration and re pair of nongas - fired appliances shall be regulated by the New York City Mechanical Code . 601.2 Fireplaces. Fireplaces (solid fuel type or ANSI Z21.50 /CSA 2.22 ) shall be installed with tight - fitting noncom- bustible fireplace doors to control infiltration los ses in construction type listed here: 1. Masonry or factory - built fireplaces designed to allow an open burn. 2. Whenever a decorative appliance (ANSI Standard Z21.60 /CSA 2.26 gas - log style unit) is installed in a vented solid fuel fireplace. 3. Vented deco rative gas fireplace appliances (ANSI Standard Z21.50 /CSA 2.22 units). Fireplaces shall be provided with a source of combustion air as required by the fireplace construction provisions of the New York City Building Code . 601.3 Flame safeguard device. All f uel gas space - heating appliances installed or used in a building occupied as a residence shall be equipped with an automatic flame safeguard device that shall shut off the fuel supply to the main burner or group of burners when the flame or pilot light the reof is extinguished. SECTION FGC 602 DECORATIVE GAS - FIRED APPLIANCES FOR INSTALLLATION IN FIREPLACES 602.1 General. Decorative appliances for installation in approved solid fuel - burning fireplaces shall be tested in ac- cordance with ANSI Z21.60 /CSA 2.26 an d shall be installed in accordance with the manufacturer’s instructions . Man- ually lighted natural gas decorative appliances shall be tested in accordance with ANSI Z21.84. 602.2 Flame safeguard device. Decorative appliances for installation in approved solid fuel - burning fireplaces, with the exception of those tested in accordance with ANSI Z21.84, shall utilize a direct ignition device, an ignitor or a pilot flame to ignite the fuel at the main burner, and shall be equipped with a flame safeguard device. The flame safeguard device shall automatically shut off the fuel supply to a main burner or group of burners when the means of ignition of such burners becomes inoperative. 602.3 Prohibited installation s. Decorative appliances for installation in fireplaces shall not be installed where pro- hibited by Section 303.3. SECTION FGC 603 LOG LIGHTERS 603.1 General. Log lighters shall be installed in accordance with the manufacturer’s instructions . 603.2 Automati c valves. Automatic valves or semiautomatic valves shall be provided and shall comply with the applicable provisions of ANSI Z21.21/CSA 6.5. SPECIFIC APPLIANCES 6 - 2 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 604 VENTED GAS FIREPLACES (DECORATIVE APPLIANCES) 604.1 General. Vented gas fireplaces shall be tested in accordance with ANSI Z21.50 /CSA 2.22 , shall be installed in accordance with the manufacturer’s instructions and shall be designed and equipped as specified in Section 602.2. 604.2 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. SECTION FGC 605 VENTED GAS FIREPLACE HEATERS 605.1 General. Vented gas fireplace heaters shall be installed in accordance with the manufacturer’s instructions , shall be tested i n accordance with ANSI Z21.88 /CSA 2.33 and shall be designed and equipped as specified in Section 602.2. The installation of unvented gas fired space heaters, gas stoves, gas logs, gas fireplaces and gas fireplace inserts is prohibited. 605.2 Separate flue s. Separate flues shall be provided for every fireplace and fireplace stove. 605.3 Combustion air supply. The requirements of the New York City Energy Conservation Code concerning com- bustion air supply shall be followed. SECTION FGC 606 RESERVED SECTION FGC 607 COMMERCIAL - INDUSTRIAL INCINERATORS AND CREMATORIES 607.1 Incinerators and crematories , commercial - industrial. Commercial - industrial - type incinerators and cremato- ries shall be constructed and installed in accordance with NFPA 82. 607.2 Compliance. All new and existing refuse disposal systems shall be installed, altered and maintained in buildings in conformity wit h the applicable provisions of the Administrative Code and the New York City Air Pollution Control Code . SECTION FGC 608 VENTED WALL FURNACES 608.1 General. Vented wall furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 608.2 Venting. Vented wall furnaces shall be vented in accordance with Section 503. 608.3 Location. Vented wall furnaces shall be located so as not to cause a fire hazard to walls, floors, combustible fu rnishings or doors. Vented wall furnaces installed between bathrooms and adjoining rooms shall not circulate air from bathrooms to other parts of the building. 608.4 Door swing. Vented wall furnaces shall be located so that a door cannot swing within 12 in ches ( 304.8 mm) of an air inlet or air outlet of such furnace measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance. 608.5 Ducts prohibited. Ducts shall not be attached to wall furnaces. Casing extension boots shall not be installed unless listed as part of the appliance. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 3 608.6 Access. Vented wall furnaces shall be provided with access for cleaning of heating surfaces, removal of burners, replacement of sections, motors, controls, filters and other working parts, and for adjustments and lubrication of parts requiring such attention. Panels, grilles and access doors that are required to be removed for normal servicing opera- tions shall not be attached to the building construction. SECTION FGC 609 FLOOR FURNACES 609.1 General. Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer’s instructions . 609.2 Placement. The following provisions apply to floor furnaces : 1. Floor s. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space. 2. Walls and corners. The register of a floor furnace with a horizontal warm - air outlet shall not be placed closer than 6 inches ( 152 .4 mm) to the nearest wall. A distance of not less than 18 inches ( 457 .2 mm) from two adjoin- ing sides of the floor furnace register to walls shall be provided to eliminate the neces sity of occupants walking over the warm - air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches ( 152 .4 mm) to a wall. Wall - register models shall not be placed closer than 6 inches ( 152 .4 mm) to a corner. 3. Draperies. Th e furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches ( 304.8 mm) to any portion of the register of the furnace. 4. Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncom- bustible construction having at least a 2 - hour fire rating, except that floor furnace enclosure s in one - and two - family dwellings shall be constructed of noncombustible materials with a fire - resistance rating not less than 1 hour. 5. Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floo r furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace. 609.3 Bracing. The floor around the furnace shall be braced and headed with a support framework designed in accordance wi th the New York City Building Code . 609.4 Clearance. The lowest portion of the floor furnace shall have not less than a 6 - inch ( 152 .4 mm) clearance from the grade level; except where the lower 6 inch ( 152 .4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches ( 50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch ( 304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch ( 457 .2 mm) minimum clearance. 609.5 Reserved. 609.6 Reserved. 609.7 Enclosures. Enclosures of floor furnaces shall be constructed entirely of noncomb ustible materials with a fire - resistance rating of at least 1 - hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace. 609.8 Duc t temperature. The outlet duct temperature of warm - air heating furnaces shall not be greater than 250°F ( 121.1 °C). 609.9 One - and two - family dwellings. Floor furnace enclosures shall be constructed of noncombustible materials with a fire - resistance rating of at least 1 - hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54. SPECIFIC APPLIANCES 6 - 4 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 610 DUCT FURNACES 610.1 General. Duct furnaces shall be tested in accordance with ANSI Z83.8 /CSA 2.6 or UL 795 and shall be installed in accordance with the manufacturer’s instructions . 610.2 Access panels. Ducts connected to duct furnaces shall have removable access panels on both the upstream and downstream sides of the furnace. 610.3 Location of draft hood and controls. The controls, combustion air inlets and draft hoods for duct furnaces shall be located outside of the ducts. The draft hood shall be located in the same enclosure from which combustion air is taken. 610.4 Circulating air. Where a duct furnace is installed so that supply ducts convey air to areas outside the space containing the furnace, the return air shall be conveyed by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. The duct furnace shall be installed on the positive pressure side of the circu- lating air blower. 610.5 Unvented duct furnaces. Unvented duct furnaces are prohibited. SECTION FGC 611 NONRECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 611.1 General. Nonrecirculating direct - fired industrial air heaters shall be listed to ANSI Z83.4/CSA 3.7 and shall be installed in accordance with the manufacturer’s instructions. 611.2 Installation. Nonrecirculating direct - fired industrial air heaters shall not be use d to supply any area containing sleeping quarters. Nonrecirculating direct - fired industrial air heaters shall be installed only in industrial or commercial occupancies. Nonrecirculating direct - fired industrial air heaters shall be permitted to provide vent ilation air. 611.3 Clearance from combustible materials. Nonrecirculating direct - fired industrial air heaters shall be installed with a clearance from combustible materials of not less than that shown on the rating plate and in the manufacturer’s instructi ons. 611.4 Supply air. All air handled by a nonrecirculating direct - fired industrial air heater, including combustion air, shall be ducted directly from the outdoors. 611.5 Outdoor air louvers. If outdoor air louvers of either the manual or automatic type are used, such devices shall be proven to be in the open position prior to allowing the main burners to operate. 611.6 Atmospheric vents and gas reliefs or bleeds. Nonrecirculating direct - fired industrial air heaters with valve train components equipped wi th atmospheric vents or gas reliefs or bleeds shall have their atmospheric vent lines or gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter . An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 611.7 Relief opening. The design of the installation shall include provisions to permit nonrecirculating direct - fired industrial air heaters to operate at rated capacity without overpressurizing the space served by the heaters by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a c ombination of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by approved engineering methods. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 611.8 Access. Nonrecirculating direct - fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters and other working parts; and for adjustment and lubrication of parts requiring maintenance. 611.9 Purging. Inlet ducting, where used, shall be purged by not less than four air changes prior to an igniti on attempt. SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 5 611.10 Controls. Direct - fired make - up air heaters shall be equipped with airflow - sensing devices, safety shutoff de- vices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their lis ting. SECTION FGC 612 RECIRCULATING DIRECT - FIRED INDUSTRIAL AIR HEATERS 612.1 General. Recirculating direct - fired industrial air heaters shall be listed to ANSI Z83.18 and shall be installed in accordance with the manufacturer’s instructions . 612.2 Locatio n. Recirculating direct - fired industrial air heaters shall be installed only in industrial and commercial occupancies. Recirculating direct - fired air heaters shall not serve any area containing sleeping quarters. Recirculating direct - fired industrial air h eaters shall not be installed in hazardous locations or in buildings that contain flammable solids, liquids or gases, explosive materials or substances that can become toxic when exposed to flame or heat. 612.3 Installation. Direct - fired industrial air hea ters shall be permitted to be installed in accordance with their listing and the manufacturer’s instructions. Direct - fired industrial air heaters shall be installed only in industrial or commer- cial occupancies. Direct - fired industrial air heaters shall be permitted to provide fresh air ventilation. 612.4 Clearance from combustible materials. Direct - fired industrial air heaters shall be installed with a clearance from combustible material of not less than that shown on the label and in the manufacturer’s ins tructions. 612.5 Air supply. Air to direct - fired industrial air heaters shall be taken from the building, ducted directly from out- doors, or a combination of both. Direct - fired industrial air heaters shall incorporate a means to supply outside venti- lation a ir to the space at a rate of not less than 4 cubic feet per minute per 1,000 Btu per hour (0.38 m 3 per min per kW) of rated input of the heater. If a separate means is used to supply ventilation air, an interlock shall be provided so as to lock out the mai n burner operation until the mechanical means is verified. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. 612.6 Atmospheric vents, gas reliefs or bleeds. Direct - fired industrial air heaters with valve train components equipped with atmospheric vents, gas reliefs or bleeds shall have their atmospheric vent lines and gas reliefs or bleeds lead to the outdoors. Means shall be employed on these lines to prevent water from entering and to prevent blockage by insects and foreign matter. An atmospheric vent line shall not be required to be provided on a valve train component equipped with a listed vent limiter. 612.7 Relief opening. The design of the installation shall include adequate provision to permit direct - fired industrial air heaters to operate at rated capacity by taking into account the structure’s designed infiltration rate, providing properly designed relief openings or an interlocked power exhaust system, or a combi nation of these methods. The structure’s designed infiltration rate and the size of relief openings shall be determined by a registered design profes- sional. Relief openings shall be permitted to be louvers or counterbalanced gravity dampers. Motorized damp ers or closable louvers shall be permitted to be used, provided they are verified to be in their full open position prior to main burner operation. 612.8 Controls. Recirculating direct - fired air heaters shall be equipped with airflow - sensing devices, safet y shutoff devices, operating temperature controls and thermally actuated temperature limit controls in accordance with the terms of their listing. SECTION FGC 613 CLOTHES DRYERS 613.1 General. Clothes dryers shall be tested in accordance with ANSI Z21.5.1 /CSA 7.1 or ANSI Z21.5.2 /CSA 7.2 , and shall be installed in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 6 - 6 2022 NEW YORK CITY FUEL GAS CODE SECTION FGC 614 CLOTHES DRYER EXHAUST 614.1 Clothes dryer exhaust. Clothes dryer exhaust shall be in accordance with Section 504 of the New York City Mechanical Code . SECTION FGC 615 SAUNA HEATERS 615.1 General. Sauna heaters shall be installed in accordance with the manufacturer’s instructions . 615.2 Location and protect ion. Sauna heaters shall be located so as to minimize the possibility of accidental contact by a person in the room. 615.2.1 Guards. Sauna heaters shall be protected from accidental contact by an approved guard or barrier of ma- terial having a low coefficient of thermal conductivity. The guard shall not substantially affect the transfer of heat from the heater to the room. 615.3 Access. Panels, grilles and access doors that are required to be removed for normal servicing operations shall not be attached to the building. 615.4 Combustion and dilution air intakes. Sauna heaters of other than the direct - vent type shall be installed with the draft hood and combustion air intake located outside the sauna room. Where the combustion air inlet and the draft hood are in a dressing room adjacent to the sauna room, there shall be provisions to prevent physically blocking the combustion air inlet and the draft hood inlet, and to prevent physical contact with the draft hood and vent assembly, or warning notices shall be posted to avoid such contact. Any warning notice shall be easily readable, shall contrast with its background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. 615.5 Combustion and ventilation air. Combustion air shall not be taken from inside the sauna room. Combustion and ventilation air for a sauna heater not of the direct - vent type shall be provided to the are a in which the combustion air inlet and draft hood are located in accordance with Section 304. 615.6 Heat and time controls. Sauna heaters shall be equipped with a thermostat which will limit room temperature to 194°F (90°C). If the thermostat is not an in tegral part of the sauna heater, the heat - sensing element shall be located within 6 inches ( 152 .4 mm) of the ceiling. If the heat - sensing element is a capillary tube and bulb, the assembly shall be attached to the wall or other support, and shall be protec ted against physical damage. 615.6.1 Timers. A timer, if provided to control main burner operation, shall have a maximum operating time of 1 hour. The control for the timer shall be located outside the sauna room. 615.7 Sauna room. A ventilation opening in to the sauna room shall be provided. The opening shall be not less than 4 inches by 8 inches ( 101.6 mm by 203 .2 mm) located near the top of the door into the sauna room. 615.7.1 Warning notice. Warning notice. The following permanent notice, constructed of approved material, shall be mechanically attached to the sauna room on the outside: WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. The wor ds shall contrast with the background and the wording shall be in letters not less than 1 / 4 inch (6.4 mm) high. Exception: This section shall not apply to one - and two - family dwellings. SECTION FGC 616 ENGINE AND GAS TURBINE - POWERED EQUIPMENT AND APPLIANCE S SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 7 616.1 Powered equipment. Permanently installed equipment powered by internal combustion engines and turbines shall be installed in accordance with the manufacturer’s instructions and NFPA 37. Stationary engine generator as- semblies shall meet the requirements of UL 2200. 616.2 Gas supply connection. Equipment powered by internal combustion engines and turbines shall not be rigidly connected to the gas supply piping. SECTION FGC 617 POOL AND SPA HEATERS 617.1 General. Pool and spa heaters shall be tested in accordance with ANSI Z21. 56 /CSA 4.7 and shall be installed in accordance with the manufacturer’s instructions . SECTION FGC 618 FORCED - AIR WARM - AIR FURNACES 618.1 General. Forced - air warm - air furnaces shall be tested in accordance with ANSI Z21.47 /CSA 2.3 or UL 795 and shall be ins talled in accordance with the manufacturer’s instructions. 618.2 Forced - air furnaces. The minimum unobstructed total area of outdoor and return air ducts or openings to a forced - air warm - air furnace shall be not less than 2 square inches for each 1,000 Btu /h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions. The minimum un- obstructed total area of supply ducts from a forced - air warm - air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer’s instructions . Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer’s instructions . 618.3 Dampers. Volume dampers shall not be placed in the air inlet to a furnace in a manner that will reduce the required air to the furnace. 618.4 Prohibited sources. Outdoor or return air for forced - air heating or forced - air heating and cooling systems shall not be taken from the following locations: 1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent opening from a plumbing drainage system or the discharge outlet of an exhaust fan, unless the outlet is 3 feet 914 .4 mm) above the outside air inlet. 2. Where there is the presence of objectiona ble odors, fumes or flammable vapors; or where located less than 10 feet (3048 mm) above the surface of any abutting public way or driveway; or where located at grade level by a sidewalk, street, alley or driveway. 3. A hazardous or insanitary location or a refrigeration machinery room as defined in the New York City Mechanical Code . 4. A room or space, the volume of which is less than 25 percent of the entire volume served by such system. Where connected by a permanent opening having an area sized in accordance with Section 618.2, adjoining rooms or spaces shall be considered as a single room or space for the purpose of determining the volume of such rooms or spaces. Exception: The minimum volume requirement shall not a pply where the amount of return air taken from a room or space is less than or equal to the amount of supply air delivered to such room or space. 5. A room or space containing an appliance where such a room or space serves as the sole source of return air. Exception: This shall not apply where: 1. The appliance is a direct - vent appliance or an appliance not requiring a vent in accordance with Section 501.8. 2. The room or space complies with the following requirements: SPECIFIC APPLIANCES 6 - 8 2022 NEW YORK CITY FUEL GAS CODE 2.1. The return air shall be taken fro m a room or space having a volume exceeding 1 cubic foot for each 10 Btu/h (9. 6 L /W) of combined input rating of all fuel - burning appliances therein. 2.2. The volume of supply air discharged back into the same space shall be approximately equal to the volu me of return air taken from the space. 2.3. Return - air inlets shall not be located within 10 feet (3048 mm) of a draft hood in the same room or space or the combustion chamber of any atmospheric burner appliance in the same room or space . 3. Rooms or space s containing solid fuel - burning appliances, provided that return - air inlets are located not less than 10 feet (3048 mm) from the firebox of such appliances. 6. A closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room or unconditioned att ic. Exceptions : 1. Where return air intakes are located not less than 10 feet (3048 mm) from cooking appliances and serve only the kitchen area, taking return air from a kitchen area shall not be prohibited. 2. Dedicated forced - air systems serving only a g arage shall not be prohibited from obtaining return air from the garage. 7. A crawl space by means of direct connection to the return side of forced - air system. Transfer openings in the crawl space enclosure shall not be prohibited. 618.5 Screen. Required outdoor air inlets for residential portions of a building shall be covered with a screen having 1 / 4 - inch (6.4 mm) openings. Required outdoor air inlets serving a nonresidential portion of a building shall be covered with screen having openings larger than 1 / 4 inch (6.4 mm) and not larger than 1 inch 25 .4 mm). 618.6 Return - air limitation. Return air from one dwelling unit shall not be discharged into anoth er dwelling unit. 618.7 Furnace plenums and air ducts. Where a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space containing the furnace, the return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside of the space containing the furnace. SECTION FGC 619 CONVERSION BURNERS 619.1 Conversion burners. The installation of conversion burners shall conform to ANSI Z21.8 and ASME CSD - 1, including Appendix C . SECTION FGC 620 UNIT HEATERS 620.1 General. Unit heaters shall be tested in accordance with ANSI Z83.8 /CSA 2.6 and shall be installed in accord- ance with the manufacturer’s instructions . 620.2 Support. Suspended - type unit heaters shall be supported by elements that are designed and constructed to ac- commodate the weight and dynamic loads. Hangers and brackets shall be of noncombustible material. 620.3 Ductwork. Ducts shall not be connected to a unit heater unless the heater is listed for such installation. 620.4 Clearance. Suspended - type unit heaters shall be installed with clearances to combustible materials of not less than 18 inches ( 457 .2 mm) at the sides, 12 inches ( 304.8 mm) at the bottom and 6 inches ( 152 .4 mm) above the top where the unit heater has an internal draft hood or 1 inch ( 25 .4 mm) above the top of the sloping side of the vertical draft hood. Floor - mounted - type unit heaters shall be installed with clearances to combustible materials at the back and one side only of not le ss than 6 inches ( 152 .4 mm). Where the flue gases are vented horizontally, the 6 - inch ( 152 .4 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. Floor - mounted - type unit heaters shall not be installed on combustible floors unless listed for such installation. Clearances for servicing all unit heaters shall be in accordance with the manufacturer’s instructions . SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 9 Exception: Unit heaters listed for reduced clearance shall be permitted to be installed with such clearances in accordance with their listing and the manufacturer’s instructions and as approved by the department . 620.5 Installation in commercial garages and aircraft hangars. Unit heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 621 UNVENTED ROOM HEATERS 621.1 General. The installation of unvented room heaters is prohibited. 621.2 Reserved. 621.3 Reserved. 621.4 Reserved. 621.5 Reserved. 621.6 Reserved. 621.7 Reserved. SECTION FGC 622 VENTED ROOM HEATERS 622.1 General. Vented room heaters shall be tested in accordance with ANSI Z21.86/CSA 2.32, installed in accord- ance with the manufacturer’s instructions , and shall be designed and equipped as specified in Section 602.2 of this code . SECTION FGC 623 COOKING APPLIANCES 62 3.1 Cooking appliances. Cooking appliances that are designed for permanent installation, including ranges, ovens, stoves, broilers, grills, fryers, griddles, hot plates and barbecues, shall be tested in accordance with ANSI Z21.1 /CSA 6.5 , ANSI Z21.58 /CSA 1 .6 or ANSI Z83.11 /CSA 1.8 and shall be installed in accordance with the manufacturer’s instructions . 623.1.1 LPG. Except as may be permitted by the New York City Fire Code , cooking appliances using LPG are prohibited. 623.2 Prohibited location. Cooking app liances designed, tested, listed and labeled for use in commercial occupancies shall not be installed within dwelling units or within any area where domestic cooking operations occur. Exception: Appliances that are also listed as domestic cooking appliances. 623.2.1 Barbeque grills. Barbeque grills piped to natural gas shall not be installed or operated within 10 feet (3048 mm) of any combustible waste or combustible material including combustibl e building surfaces, balconies and decks. 623.3 Domestic appliances. Cooking appliances installed within dwelling units and within areas where domestic cooking operations occur shall be listed and labeled as household - type appliances for domestic use. 623. 4 Domestic range installation. Domestic ranges installed on combustible floors shall be set on their own bases or legs and shall be installed with clearances of not less than that shown on the label. 623.5 Open - top broiler unit hoods. A ventilating hood sh all be provided above a domestic open - top broiler unit, unless otherwise listed for forced down draft ventilation. SPECIFIC APPLIANCES 6 - 10 2022 NEW YORK CITY FUEL GAS CODE 623.5.1 Clearances. A minimum clearance of 24 inches ( 609.6 mm) shall be maintained between the cooking top and combustible material above th e hood. The hood shall be at least as wide as the open - top broiler unit and be centered over the unit. 623.6 Commercial cooking appliance venting. Commercial cooking appliances, other than those exempted by Sec- tion 501.8, shall be vented by connecting the appliance to a vent or chimney in accordance with this code and the appliance manufacturer’s instructions or the appliance shall be vented in accordance with Section 505.1.1. 623.7 Domestic ventilation. When a hood is provided for a domestic cooking applia nce, the exhaust and make - up air systems shall be properly engineered and designed in accordance with Chapter 5 of this code and the New York City Mechanical Code . Household cooking appliances shall have a vertical clearance above the cooking top of not le ss than 30 inches (760 mm) to combustible material and metal cabinets. A minimum clearance of 24 inches ( 609.6 mm) , measured to the underside of the above cabinet or combustible material, is permitted where one of the following is installed: 1. The undersi de of the combustible material or metal cabinet above the cooking top is protected with not less than 1 / 4 - inch ( 6.4 mm) insulating millboard covered with sheet metal not less than 0.0122 inch (0.3 mm) thick. 2. A metal ventilating hood constructed of sheet metal not less than 0.0122 inch (0.3 mm) thick is installed above the cooking top with a clearance of not less tha n 1 / 4 inch (6.4 mm) between the hood and the underside of the combustible material or metal cabinet. The hood shall have a width not less than the width of the appliance and shall be centered over the appliance. 3. A listed cooking appliance or microwave o ven is installed over a listed cooking appliance and in compliance with the terms of the manufacturer’s installation instructions for the upper appliance. SECTION FGC 624 WATER HEATERS 624.1 General. Water heaters shall be tested in accordance with ANSI Z21.10.1 /CSA 4.1 and ANSI Z21.10.3 /CSA 4.3 and shall be installed in accordance with the manufacturer’s instructions . Water heaters utilizing fuels other than fuel gas shall be regulated by the New Yor k City Mechanical Code . Approval for water heaters 350,000 Btu/h input ( 102.6 kW) and above shall be obtained from the New York City Department of Environmental Protection. 624.1.1 Installation requirements. The requirements for water heaters relative to s izing, relief valves, drain pans and scald protection shall be in accordance with the New York City Plumbing Code and the following: 1. No person shall install or maintain in any dwelling unit a gas fuel - fired water heater unless the heater obtains combust ion air directly from the outside of the building. 2. No person shall install or maintain a gas - fueled water heater in a room occupied for sleeping purposes, or cause or permit to be occupied for sleeping purposes any room in which a gas - fueled heater is i nstalled. 3. Each heater shall be connected to a flue or outlet pipe. 624.2 Water heaters utilized for space heating. Water heaters utilized both to supply potable hot water and provide hot water for space - heating applications shall be listed and labeled f or such applications by the manufacturer, and shall be built in accordance with Section IV of the ASME Boiler and Pressure Vessel Code with an “H” code stamp. They shall be installed in accordance with the manufacturer’s instructions , the ASME Boiler and Pressure Vessel Code and the New York City Plumbing Code . SECTION FGC 625 REFRIGERATORS 625.1 General. Refrigerators shall be tested in accordance with ANSI Z21.19 /CSA 1.4 a nd shall be installed in ac- cordance with the manufacturer’s instructions . Refrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer’s instructions. If such instr uctions are not available, not less than 2 inches ( 50.8 SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 11 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches ( 304.8 mm) above the top. SECTION FGC 626 GAS - FIRED TOILETS 626.1 General. Gas - fired toilets are not approved for use in New York City . 626.2 Reserved. SECTION FGC 627 AIR CONDITIONING APPLIANCES 627.1 General. Gas - fired air - conditioning appliances shall be tested in accordance with ANSI Z21.40.1 /CGA 2.91 or ANSI Z21.40.2 /CGA 2.92 and shall be installed in accordance with the manufacturer’s instructions . 627.2 Independent piping. Gas piping serving heating appli ances shall be permitted to also serve cooling appliances where such heating and cooling appliances cannot be operated simultaneously (see Section 402). 627.3 Connection of gas engine - powered air conditioners. To protect against the effects of normal vibra tion in service, gas engines shall not be rigidly connected to the gas supply piping. Where units are powered by internal combustion engines and turbines, installation shall comply with Section 616.1. 627.4 Clearances for indoor installation. Air - condition ing appliances installed in rooms other than alcoves and closets shall be installed with clearances not less than those specified in Section 308.3 . Exceptions: 1. Air - conditioning appliances listed for installation at lesser clearances than those specified in Section 308.3 shall be permitted to be installed in accordance with such listing and the manufacturer’s instructions . Air - conditioning appliances installed in rooms other than alcoves and closets shall be permitted to be installed with reduced clearanc es to combustible material, provided that the combustible material is protected in ac- cordance with Table 308.2. 2. Air - conditioning appliances listed for installation at greater clearances than those specified in Section 308.3 shall be installed in accorda nce with such listing and the manufacturer’s instructions. 627.5 Alcove and closet installation. Air - conditioning appliances installed in spaces such as alcoves and closets shall be specifically listed for such installation and installed in accordance with the terms of such listing. The installation clearances for air - conditioning appliances in alcoves and closets shall not be reduced by the protection methods de- scribed in Table 308.2. 627.6 Installation. Air - conditioning appliances shall be installed in ac cordance with the manufacturer’s instructions. Unless the appliance is listed for installation on a combustible surface such as a floor or roof, or unless the surface is protected in an approved manner, the appliance shall be installed on a surface of nonc ombustible construction with noncombustible material and surface finish and with no combustible material against the underside thereof. 627.7 Plenums and air ducts. A plenum supplied as a part of the air - conditioning appliance shall be installed in accorda nce with the appliance manufacturer’s instructions. Where a plenum is not supplied with the appliance, such plenum shall be installed in accordance with the fabrication and installation instructions provided by the plenum and appliance manufacturer. The me thod of connecting supply and return ducts shall facilitate proper circulation of air. Where the air - conditioning appliance is installed within a space separated from the spaces served by the appliance, the air circulated by the appliance shall be conveyed by ducts that are sealed to the casing of the appliance and that separate the circulating air from the combustion and ventilation air. 627.8 Refrigeration coils. A refrigeration coil shall not be installed in conjunction with a forced - air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duc t system and cooling coil at the air throughput necessary for heating or SPECIFIC APPLIANCES 6 - 12 2022 NEW YORK CITY FUEL GAS CODE cooling, whichever is greater. Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure. Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace. Means shall be provided for disposal of condensate and to prevent dripping of condensate onto the heating element. 627.9 Cooling units used with heating boilers. Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent th e chilled medium from entering the heating boiler. Where hot water heating boilers are connected to heating coils located in air - handling units where they might be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with f low control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 627.10 Switches in electrical supply line. Means for interrupting the electrical supply to the air - conditioning appli- ance and to its associated cooling tower (if supplied and installed in a location remote from the air conditioner) shall be provided within sight of and not over 50 feet (15 240 mm) from the air conditioner and cooling tower. SECTION FGC 628 ILLUMINATING APPLIANCES 628.1 General. Illuminating appliances shall be tested in accordance with ANSI Z21.42 and shall be installed in accordance with the manufacturer’s instructions . 628.2 Moun ting on buildings. Illuminating appliances designed for wall or ceiling mounting shall be securely at- tached to substantial structures in such a manner that they are not dependent on the gas piping for support. 628.3 Mounting on posts. Illuminating applianc es designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted in accordance with the requirements of the New York City Building Code . Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them. 628.4 Appliance pressure regulators. Where an appliance pressure regulator is not supplied with an illuminating appliance and the service line is not equipped with a service pressure regulator, an appliance pres sure regulator shall be installed in the line to the illuminating appliance. For multiple installations, one regulator of adequate capacity shall be permitted to serve more than one illuminating appliance. SECTION FGC 629 CERAMIC KILNS 629.1 General. Kilns shall be listed and labeled unless otherwise approved in accordance with Section 105.1. Electric kilns shall comply with UL 499. The approval of unlisted appliances in accordance with Section 105.1 shall be based on an approved engineering evaluation. SEC TION FGC 630 INFRARED RADIANT HEATERS 630.1 General. Infrared radiant heaters shall be tested in accordance with ANSI Z83.19 /CSA 2.35 or ANSI Z83.20 /CSA 2.34 and shall be installed in accordance with the manufacturer’s instructions . 630.2 Support. Infrared radiant heaters shall be safely and adequately fixed in an approved position independent of gas and electric supply lines. Hangers and brackets shall be of noncombustible material. 630.3 Combustion and ventilation air. Where unvented infrared heaters are installed, natural or mechanical means shall provide outdoor ventilation air at a rate of not less than 4 cfm per 1,000 Btu/h (0.38 m 3 /min/kW) of the aggrega te SPECIFIC APPLIANCES 2022 NEW YORK CITY FUEL GAS CODE 6 - 13 input rating of all such heaters installed in the space. Exhaust openings for removing flue products shall be above the level of the heaters. 630.4 Installation in commercial garages and air - craft hangars. Overhead infrared heaters installed in garages for more than three motor vehicles or in aircraft hangars shall be installed in accordance with Sections 305.9, 305.10 and 305.11. SECTION FGC 631 BOILERS 631.1 Standards. Boilers shall be listed in accordance with the requirements of ANSI Z21.13 /CSA 4.9 o r UL 795. If applicable, the boiler shall be designed and constructed in accordance with the requirements of ASME CSD - 1 and as applicable, the ASME Boiler and Pressure Vessel Code , Sections I, II, IV, V, VI and IX and NFPA 85 . Low - pressure boilers shall co nform to the requirements of 12 NYCRR Part 4 and high - pressure boilers shall conform to the require- ments of 12 NYCRR Part 14. 631.2 Installation. In addition to the requirements of this code, the installation of boilers shall be in accordance with the manu facturer’s instructions and the New York City Mechanical Code . Operating instructions of a permanent type shall be attached to the boiler. Spill switches must be installed on all flue gas draft openings and interlocked with all vented appliances. Boilers shall have all controls set, adjusted and tested by the installer. A complete control diagram together with complete boiler operating instructions shall be furnished by the installer. The manufacturer’s rating data and the nameplate sha ll be attached to the boiler. 631.3 Clearance to combustible materials. Clearances to combustible materials shall be in accordance with Section 308.4. SECTION FGC 632 EQUIPMENT INSTALLED IN EXISTING UNLISTED BOILERS 632.1 General. Gas equipment installed i n existing unlisted boilers shall comply with Section 631.1 and shall be installed in accordance with the manufacturer’s instructions and the New York City Mechanical Code . SECTION FGC 633 STATIONARY FUEL CELL POWER SYSTEMS 633.1 General. Stationary fuel c ell power systems having a power output not exceeding 10 MW shall be tested in accordance with ANSI/CSA America FC 1 and shall be installed in accordance with the manufacturer’s instructions , NFPA 853, the New York City Building Code , the New York City Fir e Code and the New York City Electrical Code . Indoor stationary fuel cell power systems used in hydrogen generating systems shall be located in accordance with the requirements of Section 706 of this code. SECTION FGC 634 CHIMNEY DAMPER OPENING AREA 634.1 Free opening area of chimney dampers. Where an unlisted decorative appliance for installation in a vented fireplace is installed, the fireplace damper shall have a permanent free opening equal to or greater than specified in Table 634.1. TABLE 634.1 FREE OPENING AREA OF CHIMNEY DAMPER FOR VENTING FLUE GASES FROM UNLISTED DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES CHIMNEY HEIGHT (feet) MINIMUM PERMANENT FREE OPENING (square inches) a 8 13 20 29 39 51 64 SPECIFIC APPLIANCES 6 - 14 2022 NEW YORK CITY FUEL GAS CODE Appliance input rating (Btu per hour) 6 7,800 14,000 23,200 34,000 46,400 62,400 80,000 8 8,400 15,200 25,200 37,000 50,400 68,000 86,000 10 9,000 16,800 27,600 40,400 55,800 74,400 96,400 15 9,800 18,200 30,200 44,600 62,400 84,000 108,800 20 10,600 20,200 32,600 50,400 68,400 94,000 122,200 30 11,200 21,600 36,600 55,200 76,800 105,800 138,600 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch = 645. 16 m 2 , 1 British thermal unit per hour = 0.2931 W. a. The first six minimum permanent free openings (8 to 51 square inches) correspond approximately to the cross - sectional areas of chimneys having diameters of 3 through 8 inches, respectively. The 64 - square - inch opening corresponds to the cross - sectional area of standard 8 - inch by 8 - inch chimney tile. SECTION FGC 635 GASEOUS HYDROGEN SYSTEMS 635.1 Installation. The installation of gaseous hydrogen systems shall be in accordance with the applicable require- ments of the New York City Fire Code , the New York City Building Code , and Chapter 7 of this code . SECTION FGC 636 OUTDOOR DECORATIVE APPLIANCES 636.1 General. Permanently fixed - in - place outdoor decorative appliances shall be tested in accordance with ANSI Z21.97 /CSA 2.41 and shall be installed in accordance with the manufacturer’s instructions.