#!/usr/bin/env python3
# Copyright (c) 2025-2026, RTE (https://www.rte-france.com)
# This Source Code Form is subject to the terms of the Mozilla Public License, version 2.0.
# If a copy of the Mozilla Public License, version 2.0 was not distributed with this file,
# you can obtain one at http://mozilla.org/MPL/2.0/.
# SPDX-License-Identifier: MPL-2.0
"""Per-load-flow micro-benchmark: what makes "slow mode" 6x slower than "fast".
Isolates a SINGLE ``run_ac`` on the post-contingency (N-1) state and times it
under each load-flow parameter variant, so the cost of the per-action
reassessment (`utils/reassessment.py` re-simulates every prioritized action
with one AC LF each) can be attributed to a specific knob rather than guessed.
Key result on the full France grid (`bare_env_20240828T0100Z`, contingency
``P.SAOL31RONCI`` → overload ``BEON L31CPVAN``): the entire slow/fast gap is
the **transformer tap-changer voltage-control mode**. The provider default
(incremental outer loop) needs ~57 Newton iterations/LF; switching to
``AFTER_GENERATOR_VOLTAGE_CONTROL`` converges in ~20 for the same branch
current (<0.5 % delta). Disabling tap control entirely (the *old* fast mode)
is only marginally faster still but changes the currents. See
``docs/performance/history/reassessment-fast-mode-tap-control.md``.
Usage (from repo root, backend venv active)::
python benchmarks/bench_load_flow_modes.py
python benchmarks/bench_load_flow_modes.py --contingency P.SAOL31RONCI \
--overload "BEON L31CPVAN" --reps 3
Override the grid with ``BENCH_NETWORK_PATH`` (see ``_bench_common``).
"""
from __future__ import annotations
import argparse
import time
import pypowsybl as pp
import pypowsybl.loadflow as lf
from _bench_common import NETWORK_PATH
def _base_params(**override):
"""The recommender's slow-mode default (NetworkManager._create_default_lf_parameters).
``override`` accepts any ``lf.Parameters`` attribute plus a special
``provider`` dict that is merged into ``provider_parameters``.
"""
provider = {
"useActiveLimits": "true",
"svcVoltageMonitoring": "false",
"voltageRemoteControl": "false",
"writeReferenceTerminals": "false",
"slackBusSelectionMode": "MOST_MESHED",
"maxOuterLoopIterations": "100",
}
provider.update(override.pop("provider", {}))
p = lf.Parameters(
read_slack_bus=False,
write_slack_bus=False,
voltage_init_mode=override.pop("voltage_init_mode", lf.VoltageInitMode.PREVIOUS_VALUES),
transformer_voltage_control_on=override.pop("transformer_voltage_control_on", True),
use_reactive_limits=override.pop("use_reactive_limits", True),
shunt_compensator_voltage_control_on=override.pop("shunt_compensator_voltage_control_on", True),
phase_shifter_regulation_on=override.pop("phase_shifter_regulation_on", True),
distributed_slack=True,
dc_use_transformer_ratio=False,
twt_split_shunt_admittance=True,
provider_parameters=provider,
)
for k, v in override.items():
setattr(p, k, v)
return p
def main() -> None:
ap = argparse.ArgumentParser(description=__doc__)
ap.add_argument("--contingency", default="P.SAOL31RONCI")
ap.add_argument("--overload", default="BEON L31CPVAN")
ap.add_argument("--reps", type=int, default=3)
args = ap.parse_args()
net = pp.network.load(f"{NETWORK_PATH}/grid.xiidm")
# Seed a valid state (DC_VALUES init — no previous voltages exist yet),
# then apply the contingency on a fresh variant and seed it too, so every
# timed config below starts from a converged PREVIOUS_VALUES baseline.
seed = _base_params(voltage_init_mode=lf.VoltageInitMode.DC_VALUES)
lf.run_ac(net, parameters=seed)
net.clone_variant(net.get_variant_ids()[0], "n1")
net.set_working_variant("n1")
try:
net.update_lines(id=args.contingency, connected1=False, connected2=False)
except Exception:
net.update_2_windings_transformers(id=args.contingency, connected1=False, connected2=False)
lf.run_ac(net, parameters=seed)
def run(label: str, params) -> None:
ts = []
res = None
for _ in range(args.reps):
t = time.perf_counter()
try:
res = lf.run_ac(net, parameters=params)
except Exception as e: # noqa: BLE001
print(f" {label:<44s} FAILED ({str(e)[:50]})")
return
ts.append(time.perf_counter() - t)
r0 = res[0]
try:
ln = net.get_lines(attributes=["i1", "i2"]).loc[args.overload]
imax = f"{max(abs(ln.i1), abs(ln.i2)):.1f}A"
except Exception:
imax = "n/a"
print(f" {label:<44s} {min(ts):6.3f}s {r0.status.name:<10s} "
f"nr={getattr(r0, 'iteration_count', '?'):>3} I={imax}")
print(f"Grid={NETWORK_PATH} contingency={args.contingency} overload={args.overload}")
print(f"Per-LF run_ac ({args.reps} reps, min):")
run("SLOW default (incremental tap control)", _base_params())
run("FAST-old (transformer+shunt ctrl OFF)", _base_params(
transformer_voltage_control_on=False, shunt_compensator_voltage_control_on=False))
run("FAST-new (tap ctrl AFTER_GENERATOR)", _base_params(
provider={"transformerVoltageControlMode": "AFTER_GENERATOR_VOLTAGE_CONTROL"}))
run("slow, shunt ctrl OFF only", _base_params(shunt_compensator_voltage_control_on=False))
run("slow, transformer ctrl OFF only", _base_params(transformer_voltage_control_on=False))
run("slow, reactive_limits OFF", _base_params(use_reactive_limits=False))
run("slow, phase_shifter_reg OFF", _base_params(phase_shifter_regulation_on=False))
if __name__ == "__main__":
main()