[LOG DATE: 2024-01-12] The #3 Chiller vibrates when the subway passes below at rush hour. This is normal. Do not dispatch a tech unless the vibration exceeds 5.0 ips.
[LOG DATE: 2024-02-14] If the domestic water pump starts short-cycling, check the pressure transducer on the suction side. It gets clogged with sediment from the city main. Tap it gently before replacing.
[LOG DATE: 2023-11-05] Tenant on 14th floor always complains about heat on Mondays. It's because the BMS sets back to 'Occupied' too late. Manually override the setpoint to 72F at 6:00 AM on Mondays.
[LOG DATE: 2024-03-22] LL97 compliance check: We are currently getting a 'C' grade. To improve to 'B', we need to fix the steam trap leaks in the basement mechanical room.