0 to 70% (vs. fixed speed) while reducing installation time.

<|ref|>image<|/ref|><|det|>[[55, 240, 405, 515]]<|/det|>

<|ref|>sub_title<|/ref|><|det|>[[55, 525, 199, 540]]<|/det|>

SPECIFICATIONS

<|ref|>table<|/ref|><|det|>[[55, 546, 487, 954]]<|/det|>

Indoor enclosuresIP20 Open, TYPE 1, TYPE 12
Outdoor enclosuresTYPE 3R, TYPE 4X
Input supply1.5 - 600 hp (frame A - D) wall or base mounted
Ambient temperature14°F - 113°F (-10°C - 45°C)
CommunicationHigher temperatures can be achieved by derating the output amperage of the drive 10% for up to 122°F (50°C)
AltitudesModbus® RTU, Metasys N2, FLN, and BACnet standard
Others available with option cards
Relative humidityAt altitudes from 0 to 1,000 meters (0 to 3,300 ft)
Nameplate rated current is available
Derate for altitudes above 1,000 (3,300 ft) with a maximum operating altitude of 3,000 m (9,900 ft)
Consult factory for applications above 3,000 m (9,900 ft)
Electrical input powerLower than 95% without condensation
Electrical input power3 phase 380 V to 480 V ±10%
1 phase 200 V to 240 V ±10%
3 phase 200 V to 240 V ±10%
3 phase 525 V to 600 V ±10%
Frequency 50 or 60 Hz, ±2 Hz
Electrical output power3 phase from 0 to V supply

<|ref|>sub_title<|/ref|><|det|>[[511, 307, 751, 385]]<|/det|>

AQUAVAR® IPC VARIABLE SPEED CONTROLLER

<|ref|>sub_title<|/ref|><|det|>[[512, 430, 597, 444]]<|/det|>

FEATURES

<|ref|>text<|/ref|><|det|>[[511, 451, 934, 955]]<|/det|>

  • Easier start-up and programming with Start-Up Genie- Wide range of standard and permanent magnet motors with power up to 600 hp- Multi-pump configuration for up to four (4) pumps - no need for programmable logic controller (PLC)- Remote commissioning and monitoring with USB connectivity and software- Two wire multi-pump connection for faster installation- Hand on, off, and auto-on buttons available for easy pump operation at the keypad. No toggling between local and remote operation- System redundancy with multi-master control in case of drive failure- BACnet and Modbus as a standard for seamless BMS integration- Submersible and above ground applications- Wide range of voltage and enclosure options- True 208 V coverage- Dedicated single phase input- Remote commissioning and monitoring with USB connectivity and software- In-panel or handheld keypad with backlit display- Alarm Log for last 5 alarms and maintenance events- EMC/RFI filters and dual DC-link reactors to reduce drive noise emissions and interference- I/O expansion cards, factory installed or field configured