question_text string | answer_text string | key_concepts list | sft_response string | question_type string | reasoning_steps list | sft_instruction string | difficulty_level string | explanation_text string | knowledge_domain string |
|---|---|---|---|---|---|---|---|---|---|
某10 kV馈线配置过电流保护,电流互感器变比为400/5,继电器一次侧等效电流整定值对应的二次电流为1.25 A。若该馈线发生三相短路,折算到CT一次侧的短路电流为600 A,求:(1)保护的一次侧启动电流;(2)600 A一次短路电流对应的CT二次电流;(3)判断该故障电流是否达到保护启动值。 | CT变比为400/5=80。(1)一次侧启动电流为1.25×80=100 A;(2)600 A一次短路电流对应的二次电流为600/80=7.5 A;(3)7.5 A大于1.25 A,因此该短路电流达到过电流保护的启动值。 | [
"电流互感器变比",
"过电流保护",
"一次启动电流",
"二次电流折算",
"动作条件",
"动作时限"
] | CT变比为K_I=400/5=80。一次侧启动电流为I_{set,1}=1.25×80=100 A;600 A一次短路电流折算到二次侧为I_{f,2}=600/80=7.5 A。因为7.5 A大于继电器二次启动整定值1.25 A,所以过电流保护满足启动条件。需要注意,是否最终跳闸还要结合动作时限、出口回路及闭锁条件进一步判断。 | 计算题 | [
"计算CT变比:K_I=400/5=80。",
"将继电器二次整定值1.25 A乘以变比,得到一次侧启动电流100 A。",
"将一次侧短路电流600 A除以变比,得到二次侧故障电流7.5 A。",
"比较7.5 A与二次启动整定值1.25 A,确认故障电流满足启动条件。",
"说明达到启动值不等同于立即跳闸,还需检查动作时限和出口逻辑。"
] | 已知10 kV馈线CT变比为400/5,过电流继电器二次整定电流为1.25 A,三相短路时一次短路电流为600 A。请计算一次启动电流和故障时的二次电流,并判断保护是否启动。 | 中等 | 电流互感器变比K_I=I_{1N}/I_{2N}=400/5=80。继电器二次整定电流折算到一次侧时,应乘以CT变比,因此一次启动电流I_{set,1}=1.25×80=100 A。故障电流折算到二次侧时,应除以CT变比,得到I_{f,2}=600/80=7.5 A。由于7.5 A超过继电器1.25 A的二次启动整定值,保护元件满足启动条件;实际跳闸还需结合动作时限、出口逻辑及其他闭锁条件判断。 | 保护整定与配合 |
某变电站运行中,发现一组运行中的电流互感器(CT)二次回路端子出现接触异常,需要处理端子。问:为什么严禁在一次设备带电且CT一次有电流时直接开断CT二次回路?处理此类缺陷应重点关注什么? | 严禁直接开断。CT二次回路开路时,二次电流被迫中断,铁芯磁通显著增大,可能在二次侧产生危险的高电压,危及人身安全,并可能导致CT绝缘损坏、铁芯剩磁增大以及保护和测量回路失效。处理前应按现场规程采取停电、隔离或使用专用短接措施,并确认相关保护和安全措施。 | [
"电流互感器",
"CT二次回路开路",
"二次感应电压",
"铁芯磁通",
"保护回路失效",
"专用短接措施"
] | CT正常运行时,二次回路应保持闭合,二次电流用于抵消一次电流产生的磁势。若直接开断二次回路,二次电流中断,铁芯磁通和二次感应电压可能显著升高,开路点可能出现危险高电压,并造成CT绝缘损坏、剩磁增大以及保护和测量回路失效。因此,不能在一次有电流时直接拆开CT二次回路。处理前应按照现场规程进行停电、隔离或使用合格的专用短接措施,并核实对相关保护、测量回路的影响;不得使用普通导线随意短接或操作。 | 故障分析题 | [
"识别故障对象为运行中CT的二次回路,而不是普通低压控制回路。",
"分析CT正常工作时二次回路闭合且阻抗较低,二次电流对一次磁势具有平衡作用。",
"判断二次回路开路后,二次电流中断,铁芯磁通和二次感应电压可能显著升高。",
"由此得出直接开断可能造成人身触电、设备绝缘损坏及保护测量异常。",
"处理时应依据规程完成停电、隔离或可靠短接,并评估对保护装置的影响。"
] | 请分析为什么严禁在CT一次有电流时直接开断其二次回路,并说明处理CT二次端子异常时应遵循的基本安全原则。 | 中等 | 正常运行时,CT二次绕组产生的磁势用于抵消一次电流产生的磁势,二次回路近似处于低阻抗闭合状态。若二次回路突然开路,二次电流无法流通,铁芯磁通和二次感应电动势可能大幅升高,开路点还可能出现危险电压。因此,不能将带负荷CT的二次端子直接拆开或断开。实际处理必须遵守现场运行规程,由具备资质的人员确认一次系统状态、保护影响范围及短接和隔离措施;短接应使用合格的试验端子或专用短接工具,不能用普通导线随意操作。 | 二次回路 |
关于110 kV输电线路三段式距离保护,下列说法中正确的是:A.距离Ⅰ段通常保护线路全长并带较长延时;B.距离Ⅰ段通常按线路全长的80%~85%整定,通常无意时限动作;C.距离Ⅱ段只保护本线路首端,且必须无延时动作;D.距离Ⅲ段仅用于保护母线。 | B。 | [
"距离保护",
"测量阻抗",
"距离Ⅰ段",
"保护范围",
"后备保护"
] | 正确选项是B。距离保护根据测量阻抗判断故障距离。距离Ⅰ段为保证选择性,通常按被保护线路全长的80%~85%整定,通常不设置人为延时;距离Ⅱ段延伸至相邻线路的一部分,并设置一定时限;距离Ⅲ段作为本线路及相邻元件的后备保护,动作时限通常更长。 | 单项选择题 | [
"明确距离保护通过测量阻抗反映故障距离。",
"考虑测量误差、过渡电阻和区外故障影响,Ⅰ段不能无选择地覆盖线路全长。",
"根据常用整定原则,Ⅰ段保护范围通常为线路全长的80%~85%。",
"核对各选项后,B项符合距离保护分段整定原则。"
] | 请判断关于110 kV输电线路三段式距离保护的说法哪一项正确,并说明距离Ⅰ段、Ⅱ段和Ⅲ段在保护范围及动作时限方面的基本特点。 | 基础 | 距离保护依据测量到的故障阻抗判断故障位置。为避免受对端母线外部故障、测量误差和过渡电阻等因素影响,距离Ⅰ段通常只保护被保护线路全长的约80%~85%,并以较短固有时间或近似无延时动作。距离Ⅱ段应延伸到相邻线路的一部分并带有时限,距离Ⅲ段主要作为本线路及相邻元件的后备保护。 | 继电保护原理 |
Power System Relay Protection Practice Q&A Dataset
This dataset contains relay protection practice questions, answers, and explanations for electrical engineering, covering protection principles, fault identification, setting logic, secondary circuits, and substation operations. The web-text records are organized with fields such as knowledge domain, question type, difficulty, key concepts, and reasoning steps for targeted search and filtering. It supports supervised fine-tuning of power engineering question-answering models, knowledge coverage evaluation, and the development of learning support tools.
Technical Specifications
| Field | Type | Description |
|---|---|---|
| answer_text | string | Original answer to the practice question, which may contain an option, judgment, calculation result, or short-answer conclusion. |
| key_concepts | array | Key relay protection concepts, equipment, parameters, or criteria extracted from the question, answer, and explanation. |
| sft_response | string | A complete supervised fine-tuning target response that combines the answer and explanation with professional reasoning. |
| question_text | string | Original text of a power system relay protection practice question. |
| question_type | string | Question format inferred from how the problem is presented and answered. |
| reasoning_steps | array | Ordered steps that organize the explanation into judgments, calculations, references to principles, or derivations of the conclusion. |
| sft_instruction | string | A user question or domain-specific instruction based on the original question and prepared for supervised fine-tuning. |
| difficulty_level | string | Question difficulty based on the breadth of knowledge covered, reasoning complexity, and calculation or analysis requirements. |
| explanation_text | string | Original explanation of the answer, relay protection principles, fault identification criteria, setting logic, or operational procedures. |
| knowledge_domain | string | Primary professional knowledge domain inferred from the question and explanation. |
Compliance Statement
| Authorization Type | CC-BY-NC-SA 4.0 (Attribution–NonCommercial–ShareAlike) |
| Commercial Use | Requires exclusive subscription or authorization contract (monthly or per-invocation charging) |
| Privacy and Anonymization | No PII, no real company names, simulated scenarios follow industry standards |
| Compliance System | Compliant with China's Data Security Law / EU GDPR / supports enterprise data access logs |
Source & Contact
- Downloads last month
- 58