Chapter
stringclasses
6 values
Reference
stringlengths
1
17
Body
stringlengths
62
23.1k
URL
stringlengths
26
42
Chapter 3 Wiring Methods and Materials
315.17(B)(1)
Type MV cable joints, terminations, or connectors shall be durably marked on the surface. [315.17(B)(1)](https://2023.antflix.net#315.17(B)(1))
https://2023.antflix.net#315.17(B)(1)
Chapter 3 Wiring Methods and Materials
315.17(B)(2)
Type MV cable joints, terminations, or connectors shall be marked by means of a durably printed tag or label attached to joint or termination. [315.17(B)(2)](https://2023.antflix.net#315.17(B)(2))
https://2023.antflix.net#315.17(B)(2)
Chapter 3 Wiring Methods and Materials
315.17(C)
Type MV cable joints and cable terminations shall be permitted to be marked to indicate special characteristics, such as limited smoke and sunlight resistance. [315.17(C)](https://2023.antflix.net#315.17(C))
https://2023.antflix.net#315.17(C)
Chapter 3 Wiring Methods and Materials
315.30
A qualified person(s) with documented training and experience shall perform the installation and testing of Type MV cable. A qualified person(s) with documented training and experience in the installation of Type MV cable joints shall perform the installation of Type MV cable joints. A qualified person(s) with documented training and experience in the installation of Type MV cable terminations shall perform the installation of Type MV cable terminations. Informational Note No. 1: See ANSI/NECA/NCSCB 600-2020, Standard for Installing and Maintaining Medium-Voltage Cable, and IEEE 576, Recommended Practice for Installation, Termination, and Testing of Insulated Power Cables as Used in Industrial and Commercial Applications, for information about accepted industry practices and installation procedures for medium-voltage cable. Informational Note No. 2: Where medium-voltage cable is used for dc circuits, low frequency polarization can create hazardous voltages. When handling the cable these voltages could be present or could develop on dc stressed cable while the circuit is energized. Solidly grounding the cable prior to contacting, cutting or disconnecting cables in dc circuits is a method to discharge these voltages. [315.30](https://2023.antflix.net#315.30)
https://2023.antflix.net#315.30
Chapter 3 Wiring Methods and Materials
315.32(A)
Type MV cable shall be permitted for use on power systems rated up to and including 35,000 volts, nominal, as follows: In wet or dry locations.In raceways.In cable trays, where identified for the use, in accordance with 392.10, 392.20(B), (C), and (D), 392.22(C), 392.30(B)(1), 392.46, 392.56, and 392.60. Type MV cable that has an overall metallic sheath or armor, complies with the requirements for Type MC cable, and is identified as "MV or MC" shall be permitted to be installed in cable trays in accordance with 392.10(B)(2).In messenger-supported wiring in accordance with Part II of Article 396.As exposed runs in accordance with 305.3. Type MV cable that has an overall metallic sheath or armor, complies with the requirements for Type MC cable, and is identified as "MV or MC" shall be permitted to be installed as exposed runs of metal-clad cable in accordance with 305.3.Corrosive conditions where exposed to oils, greases, vapors, gases, fumes, liquids, or other substances having a deleterious effect on the conductor or insulation shall be of a type suitable for the application.Conductors in parallel in accordance with 310.10(G).Type MV cable used where exposed to direct sunlight shall be identified for the use.Direct buried in accordance with 315.36. [315.32(A)](https://2023.antflix.net#315.32(A))
https://2023.antflix.net#315.32(A)
Chapter 3 Wiring Methods and Materials
315.32(B)
Type MV cable joints and terminations shall be permitted for use on power systems rated up to and including 35,000 volts, nominal, as follows: Type MV cable joints and terminations, used where exposed to direct sunlight, shall be identified for the use. Direct buried. Where used intermittently or continuously submerged in water at a depth not exceeding 7 m (23 ft) type MV cable joints and terminations shall be identified for the use. The environmental operating temperature range shall be identified. Where used in one or more of the following conditions Type MV cable joints and terminations shall be identified for the use: Underground chambers Tunnels Conduits Manholes Vaults Corrosive conditions where exposed to oils, greases, vapors, gases, fumes, liquids, or other substances having a deleterious effect on the joint or termination shall be of a type suitable for the application. In cable trays, where identified for use, in accordance with 392.10, 392.20(B), (C) and (D), 392.22(C), 392.30(B)(1), 392.46, 392.56, and 392.60. Informational Note No. 1: The "uses permitted" is not an all-inclusive list. Informational Note No. 2: See IEEE-404, IEEE Standard for Extruded and Laminated Dielectric Shielded Cable Joints Rated 2.5kV to 500kV, for more information on cable joints. Cable joints are often referred to as splices. However, the term splice includes many other applications not included in the definition of a cable joint. Informational Note No. 3: See IEEE-48, IEEE Standard for Test Procedures and Requirements for Alternating-Current Cable Terminations Used on Shielded Cables Having Laminated insulation Rated 2.5 kV through 765 kV or Extruded Insulation Rated 2.5 kV through 500 kV, for information on terminations. Type MV cable terminations include terminations used to connect directly to equipment or insulators. Informational Note No. 4: See IEEE-386, IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Rated 2.5kV through 35 kV, and IEEE-1215, IEEE Guide for the Application of Separable Insulated Connectors, for more information on separable insulated connectors. Type MV cable terminations also include separable insulated connectors, which are a type of pluggable cable termination and can be used for connection to equipment, such as switchgear or transformers. A separable connector has a matching interface that the separable connector plugs into on the equipment, such as switchgear or transformers. Separable connectors can also be ganged together to form a distribution junction using specialized junction brackets. [315.32(B)](https://2023.antflix.net#315.32(B))
https://2023.antflix.net#315.32(B)
Chapter 3 Wiring Methods and Materials
315.36
Type MV conductors and cables used for direct burial applications shall be shielded, identified for such use, and installed in accordance with 305.15. Exception No. 1: Nonshielded multiconductor cables rated 2001 volts to 2400 volts shall be permitted if the cable has an overall metallic sheath or armor. The metallic shield, sheath, or armor shall be connected to a grounding electrode conductor, a grounding busbar, or a grounding electrode. Exception No. 2: Airfield lighting cable used in series circuits that are rated up to 5000 volts and are powered by regulators shall be permitted to be nonshielded. Informational Note to Exception No. 2: Federal Aviation Administration (FAA) Advisory Circulars (ACs) provide additional practices and methods for airport lighting. [315.36](https://2023.antflix.net#315.36)
https://2023.antflix.net#315.36
Chapter 3 Wiring Methods and Materials
315.40
Type MV cable terminated in equipment or installed in pull boxes or vaults shall be secured and supported by metallic or nonmetallic supports suitable to withstand the weight by cable ties listed and identified for securement and support, or other approved means, at intervals not exceeding 1.5 m (5 ft) from terminations or a maximum of 1.8 m (6 ft) between supports. [315.40](https://2023.antflix.net#315.40)
https://2023.antflix.net#315.40
Chapter 3 Wiring Methods and Materials
315.44
Nonshielded, ozone-resistant insulated conductors with a maximum phase-to-phase voltage of 5000 volts shall be permitted in Type MC cables in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation. For other establishments, solid dielectric insulated conductors operated above 2000 volts in permanent installations shall have ozone-resistant insulation and shall be shielded. All metallic insulation shields shall be connected to a grounding electrode conductor, a grounding busbar, an equipment grounding conductor, or a grounding electrode. Equipment grounding conductors installed with circuits using medium voltage cables shall be sized according to 250.190(C). Informational Note: The primary purposes of shielding are to confine the voltage stresses to the insulation, dissipate insulation leakage current, and drain off the capacitive charging current. Exception No. 1: Nonshielded insulated conductors listed by a qualified testing laboratory shall be permitted for use up to 2400 volts under the following conditions: (1) Conductors shall have insulation resistant to electric discharge and surface tracking, or the insulated conductor(s) shall be covered with a material resistant to ozone, electric discharge, and surface tracking. (2) Where used in wet locations, the insulated conductor(s) shall have an overall nonmetallic jacket or a continuous metallic sheath. (3) Insulation and jacket thicknesses shall be in accordance with Table 315.10(B). Exception No. 2: Nonshielded insulated conductors listed by a qualified testing laboratory shall be permitted for use up to 5000 volts to replace existing nonshielded conductors, on existing equipment in industrial establishments only, under the following conditions: (1) Where the condition of maintenance and supervision ensures that only qualified personnel install and service the installation. (2) Conductors shall have insulation resistant to electric discharge and surface tracking, or the insulated conductor(s) shall be covered with a material resistant to ozone, electric discharge, and surface tracking. (3) Where used in wet locations, the insulated conductor(s) shall have an overall nonmetallic jacket or a continuous metallic sheath, (4) Insulation and jacket thicknesses shall be in accordance with Table 315.10(B). Informational Note: Relocation or replacement of equipment may not comply with the term existing as related to this exception. Exception No. 3: Where permitted in 315.36, Exception No. 2. [315.44](https://2023.antflix.net#315.44)
https://2023.antflix.net#315.44
Chapter 3 Wiring Methods and Materials
315.45
Type MV cable joints and terminations shall be provided with means to connect the metallic insulation shield to ground if required. [315.45](https://2023.antflix.net#315.45)
https://2023.antflix.net#315.45
Chapter 3 Wiring Methods and Materials
315.60(A)(1)
Ampacities for solid dielectric-insulated conductors shall be permitted to be determined by tables or under engineering supervision, as provided in 315.60(B) and (C). The ampacity of Type MV cable installed in cable tray shall be determined in accordance with 392.80(B). [315.60(A)(1)](https://2023.antflix.net#315.60(A)(1))
https://2023.antflix.net#315.60(A)(1)
Chapter 3 Wiring Methods and Materials
315.60(A)(2)
Where more than one calculated or tabulated ampacity could apply for a given circuit length, the lowest value shall be used. Exception: Where different ampacities apply to portions of a circuit, the higher ampacity shall be permitted to be used if the total portion(s) of the circuit with the lower ampacity does not exceed the lesser of 3.0 m (10 ft) or 10 percent of the total circuit. Informational Note: See 110.40 for conductor temperature limitations due to termination provisions. [315.60(A)(2)](https://2023.antflix.net#315.60(A)(2))
https://2023.antflix.net#315.60(A)(2)
Chapter 3 Wiring Methods and Materials
315.60(B)
Under engineering supervision, conductor ampacities shall be permitted to be calculated by using the following general equation: [315.60(B)] where: Tc = conductor temperature (°C) Ta = ambient temperature (°C) ΔTd = dielectric loss temperature rise Rdc = dc resistance of conductor at temperature, Tc Yc = component ac resistance resulting from skin effect and proximity effect Rca = effective thermal resistance between conductor and surrounding ambient Informational Note: The dielectric loss temperature rise (ΔTd) is negligible for single circuit extruded dielectric cables rated below 46 kV. [315.60(B)](https://2023.antflix.net#315.60(B))
https://2023.antflix.net#315.60(B)
Chapter 3 Wiring Methods and Materials
315.60(C)
Ampacities for conductors rated 2001 volts to 35,000 volts shall be as specified in Table 315.60(C)(1) through Table 315.60(C)(20). Ampacities for ambient temperatures other than those specified in the ampacity tables shall be corrected in accordance with 315.60(D)(4). Informational Note No. 1: See IEEE 835, Standard Power Cable Ampacity Tables, and the references therein for availability of all factors and constants for ampacities calculated in accordance with 315.60(A). Informational Note No. 2: See 210.19, Informational Note, for voltage drop on branch circuits that this section does not take into consideration. See 215.2(A)(2), Informational Note No. 2, for voltage drop on feeders that this section does not take into consideration. Table 315.60(C)(1) Ampacities of Insulated Single Copper Conductor Cables Triplexed in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 65 74 - - 6 90 99 100 110 4 120 130 130 140 2 160 175 170 195 1 185 205 195 225 1/0 215 240 225 255 2/0 250 275 260 295 3/0 290 320 300 340 4/0 335 375 345 390 250 375 415 380 430 350 465 515 470 525 500 580 645 580 650 750 750 835 730 820 1000 880 980 850 950 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(2) Ampacities of Insulated Single Aluminum Conductor Cables Triplexed in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 50 57 - - 6 70 77 75 84 4 90 100 100 110 2 125 135 130 150 1 145 160 150 175 1/0 170 185 175 200 2/0 195 215 200 230 3/0 225 250 230 265 4/0 265 290 270 305 250 295 325 300 335 350 365 405 370 415 500 460 510 460 515 750 600 665 590 660 1000 715 800 700 780 Note: Refer to 315.60(E) for basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(3) Ampacities of Insulated Single Copper Conductor Isolated in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—15,000 Volts Ampacity 15,001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 83 93 - - - - 6 110 120 110 125 - - 4 145 160 150 165 - - 2 190 215 195 215 - - 1 225 250 225 250 225 250 1/0 260 290 260 290 260 290 2/0 300 330 300 335 300 330 3/0 345 385 345 385 345 380 4/0 400 445 400 445 395 445 250 445 495 445 495 440 490 350 550 615 550 610 545 605 500 695 775 685 765 680 755 750 900 1000 885 990 870 970 1000 1075 1200 1060 1185 1040 1160 1250 1230 1370 1210 1350 1185 1320 1500 1365 1525 1345 1500 1315 1465 1750 1495 1665 1470 1640 1430 1595 2000 1605 1790 1575 1755 1535 1710 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(4) Ampacities of Insulated Single Aluminum Conductor Isolated in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—15,000 Volts Ampacity 15,001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 64 71 - - - - 6 85 95 87 97 - - 4 115 125 115 130 - - 2 150 165 150 170 - - 1 175 195 175 195 175 195 1/0 200 225 200 225 200 225 2/0 230 260 235 260 230 260 3/0 270 300 270 300 270 300 4/0 310 350 310 350 310 345 250 345 385 345 385 345 380 350 430 480 430 480 430 475 500 545 605 535 600 530 590 750 710 790 700 780 685 765 1000 855 950 840 940 825 920 1250 980 1095 970 1080 950 1055 1500 1105 1230 1085 1215 1060 1180 1750 1215 1355 1195 1335 1165 1300 2000 1320 1475 1295 1445 1265 1410 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(5) Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 59 66 - - 6 79 88 93 105 4 105 115 120 135 2 140 154 165 185 1 160 180 185 210 1/0 185 205 215 240 2/0 215 240 245 275 3/0 250 280 285 315 4/0 285 320 325 360 250 320 355 360 400 350 395 440 435 490 500 485 545 535 600 750 615 685 670 745 1000 705 790 770 860 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(6) Ampacities of an Insulated Three-Conductor Aluminum Cable Isolated in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 46 51 - - 6 61 68 72 80 4 81 90 95 105 2 110 120 125 145 1 125 140 145 165 1/0 145 160 170 185 2/0 170 185 190 215 3/0 195 215 220 245 4/0 225 250 255 285 250 250 280 280 315 350 310 345 345 385 500 385 430 425 475 750 495 550 540 600 1000 585 650 635 705 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(7) Ampacities of an Insulated Triplexed or Three Single-Conductor Copper Cables in Isolated Conduit in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 55 61 - - 6 75 84 83 93 4 97 110 110 120 2 130 145 150 165 1 155 175 170 190 1/0 180 200 195 215 2/0 205 225 225 255 3/0 240 270 260 290 4/0 280 305 295 330 250 315 355 330 365 350 385 430 395 440 500 475 530 480 535 750 600 665 585 655 1000 690 770 675 755 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(8) Ampacities of an Insulated Triplexed or Three Single-Conductor Aluminum Cables in Isolated Conduit in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 43 48 - - 6 58 65 65 72 4 76 85 84 94 2 100 115 115 130 1 120 135 130 150 1/0 140 155 150 170 2/0 160 175 175 200 3/0 190 210 200 225 4/0 215 240 230 260 250 250 280 255 290 350 305 340 310 350 500 380 425 385 430 750 490 545 485 540 1000 580 645 565 640 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(9) Ampacities of an Insulated Three-Conductor Copper Cable in Isolated Conduit in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 52 58 - - 6 69 77 83 92 4 91 100 105 120 2 125 135 145 165 1 140 155 165 185 1/0 165 185 195 215 2/0 190 210 220 245 3/0 220 245 250 280 4/0 255 285 290 320 250 280 315 315 350 350 350 390 385 430 500 425 475 470 525 750 525 585 570 635 1000 590 660 650 725 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(10) Ampacities of an Insulated Three-Conductor Aluminum Cable in Isolated Conduit in Air Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 8 41 46 - - 6 53 59 64 71 4 71 79 84 94 2 96 105 115 125 1 110 125 130 145 1/0 130 145 150 170 2/0 150 165 170 190 3/0 170 190 195 220 4/0 200 225 225 255 250 220 245 250 280 350 275 305 305 340 500 340 380 380 425 750 430 480 470 520 1000 505 560 550 615 Note: Refer to 315.60(E) for the basis of ampacities, 315.10(A) for conductor maximum operating temperature and application, and 315.60(D)(4) for the ampacity correction factors where the ambient air temperature is other than 40°C (104°F). Table 315.60(C)(11) Ampacities of Three Single-Insulated Copper Conductors in Underground Electrical Ducts (Three Conductors per Electrical Duct) Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit [See Figure 315.60(D)(3), Detail 1.] 8 64 69 - - 6 85 92 90 97 4 110 120 115 125 2 145 155 155 165 1 170 180 175 185 1/0 195 210 200 215 2/0 220 235 230 245 3/0 250 270 260 275 4/0 290 310 295 315 250 320 345 325 345 350 385 415 390 415 500 470 505 465 500 750 585 630 565 610 1000 670 720 640 690 Three Circuits [See Figure 315.60(D)(3), Detail 2.] 8 56 60 - - 6 73 79 77 83 4 95 100 99 105 2 125 130 130 135 1 140 150 145 155 1/0 160 175 165 175 2/0 185 195 185 200 3/0 210 225 210 225 4/0 235 255 240 255 250 260 280 260 280 350 315 335 310 330 500 375 405 370 395 750 460 495 440 475 1000 525 565 495 535 Six Circuits [See Figure 315.60(D)(3), Detail 3.] 8 48 52 - - 6 62 67 64 68 4 80 86 82 88 2 105 110 105 115 1 115 125 120 125 1/0 135 145 135 145 2/0 150 160 150 165 3/0 170 185 170 185 4/0 195 210 190 205 250 210 225 210 225 350 250 270 245 265 500 300 325 290 310 750 365 395 350 375 1000 410 445 390 415 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(12) Ampacities of Three Single-Insulated Aluminum Conductors in Underground Electrical Ducts (Three Conductors per Electrical Duct) Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit [See Figure 315.60(D)(3), Detail 1.] 8 50 54 - - 6 66 71 70 75 4 86 93 91 98 2 115 125 120 130 1 130 140 135 145 1/0 150 160 155 165 2/0 170 185 175 190 3/0 195 210 200 215 4/0 225 245 230 245 250 250 270 250 270 350 305 325 305 330 500 370 400 370 400 750 470 505 455 490 1000 545 590 525 565 Three Circuits [See Figure 315.60(D)(3), Detail 2.] 8 44 47 - - 6 57 61 60 65 4 74 80 77 83 2 96 105 100 105 1 110 120 110 120 1/0 125 135 125 140 2/0 145 155 145 155 3/0 160 175 165 175 4/0 185 200 185 200 250 205 220 200 220 350 245 265 245 260 500 295 320 290 315 750 370 395 355 385 1000 425 460 405 440 Six Circuits [See Figure 315.60(D)(3), Detail 3.] 8 38 41 - - 6 48 52 50 54 4 62 67 64 69 2 80 86 80 88 1 91 98 90 99 1/0 105 110 105 110 2/0 115 125 115 125 3/0 135 145 130 145 4/0 150 165 150 160 250 165 180 165 175 350 195 210 195 210 500 240 255 230 250 750 290 315 280 305 1000 335 360 320 345 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(13) Ampacities of Three Insulated Copper Conductors Cabled Within an Overall Covering (Three-Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct) Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit [See Figure 315.60(D)(3), Detail 1.] 8 59 64 - - 6 78 84 88 95 4 100 110 115 125 2 135 145 150 160 1 155 165 170 185 1/0 175 190 195 210 2/0 200 220 220 235 3/0 230 250 250 270 4/0 265 285 285 305 250 290 315 310 335 350 355 380 375 400 500 430 460 450 485 750 530 570 545 585 1000 600 645 615 660 Three Circuits [See Figure 315.60(D)(3), Detail 2.] 8 53 57 - - 6 69 74 75 81 4 89 96 97 105 2 115 125 125 135 1 135 145 140 155 1/0 150 165 160 175 2/0 170 185 185 195 3/0 195 210 205 220 4/0 225 240 230 250 250 245 265 255 270 350 295 315 305 325 500 355 380 360 385 750 430 465 430 465 1000 485 520 485 515 Six Circuits [See Figure 315.60(D)(3), Detail 3.] 8 46 50 - - 6 60 65 63 68 4 77 83 81 87 2 98 105 105 110 1 110 120 115 125 1/0 125 135 130 145 2/0 145 155 150 160 3/0 165 175 170 180 4/0 185 200 190 200 250 200 220 205 220 350 240 270 245 275 500 290 310 290 305 750 350 375 340 365 1000 390 420 380 405 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(14) Ampacities of Three Insulated Aluminum Conductors Cabled Within an Overall Covering (Three-Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct) Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit [See Figure 315.60(D)(3), Detail 1.] 8 46 50 - - 6 61 66 69 74 4 80 86 89 96 2 105 110 115 125 1 120 130 135 145 1/0 140 150 150 165 2/0 160 170 170 185 3/0 180 195 195 210 4/0 205 220 220 240 250 230 245 245 265 350 280 310 295 315 500 340 365 355 385 750 425 460 440 475 1000 495 535 510 545 Three Circuits [See Figure 315.60(D)(3), Detail 2.] 8 41 44 - - 6 54 58 59 64 4 70 75 75 81 2 90 97 100 105 1 105 110 110 120 1/0 120 125 125 135 2/0 135 145 140 155 3/0 155 165 160 175 4/0 175 185 180 195 250 190 205 200 215 350 230 250 240 255 500 280 300 285 305 750 345 375 350 375 1000 400 430 400 430 Six Circuits [See Figure 315.60(D)(3), Detail 3.] 8 36 39 - - 6 46 50 49 53 4 60 65 63 68 2 77 83 80 86 1 87 94 90 98 1/0 99 105 105 110 2/0 110 120 115 125 3/0 130 140 130 140 4/0 145 155 150 160 250 160 170 160 170 350 190 205 190 205 500 230 245 230 245 750 280 305 275 295 1000 320 345 315 335 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(15) Ampacities of Single Insulated Copper Conductors Directly Buried in Earth Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit, Three Conductors [See Figure 315.60(D)(3), Detail 9.] 8 110 115 - - 6 140 150 130 140 4 180 195 170 180 2 230 250 210 225 1 260 280 240 260 1/0 295 320 275 295 2/0 335 365 310 335 3/0 385 415 355 380 4/0 435 465 405 435 250 470 510 440 475 350 570 615 535 575 500 690 745 650 700 750 845 910 805 865 1000 980 1055 930 1005 Two Circuits, Six Conductors [See Figure 315.60(D)(3), Detail 10.] 8 100 110 - - 6 130 140 120 130 4 165 180 160 170 2 215 230 195 210 1 240 260 225 240 1/0 275 295 255 275 2/0 310 335 290 315 3/0 355 380 330 355 4/0 400 430 375 405 250 435 470 410 440 350 520 560 495 530 500 630 680 600 645 750 775 835 740 795 1000 890 960 855 920 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(16) Ampacities of Single Insulated Aluminum Conductors Directly Buried in Earth Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit, Three Conductors [See Figure 315.60(D)(3), Detail 9.] 8 85 90 - - 6 110 115 100 110 4 140 150 130 140 2 180 195 165 175 1 205 220 185 200 1/0 230 250 215 230 2/0 265 285 245 260 3/0 300 320 275 295 4/0 340 365 315 340 250 370 395 345 370 350 445 480 415 450 500 540 580 510 545 750 665 720 635 680 1000 780 840 740 795 Two Circuits, Six Conductors [See Figure 315.60(D)(3), Detail 10.] 8 80 85 - - 6 100 110 95 100 4 130 140 125 130 2 165 180 155 165 1 190 200 175 190 1/0 215 230 200 215 2/0 245 260 225 245 3/0 275 295 255 275 4/0 310 335 290 315 250 340 365 320 345 350 410 440 385 415 500 495 530 470 505 750 610 655 580 625 1000 710 765 680 730 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(17) Ampacities of Three Insulated Copper Conductors Cabled Within an Overall Covering (Three-Conductor Cable), Directly Buried in Earth Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit [See Figure 315.60(D)(3), Detail 5.] 8 85 89 - - 6 105 115 115 120 4 135 150 145 155 2 180 190 185 200 1 200 215 210 225 1/0 230 245 240 255 2/0 260 280 270 290 3/0 295 320 305 330 4/0 335 360 350 375 250 365 395 380 410 350 440 475 460 495 500 530 570 550 590 750 650 700 665 720 1000 730 785 750 810 Two Circuits [See Figure 315.60(D)(3), Detail 6.] 8 80 84 - - 6 100 105 105 115 4 130 140 135 145 2 165 180 170 185 1 185 200 195 210 1/0 215 230 220 235 2/0 240 260 250 270 3/0 275 295 280 305 4/0 310 335 320 345 250 340 365 350 375 350 410 440 420 450 500 490 525 500 535 750 595 640 605 650 1000 665 715 675 730 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(18) Ampacities of Three Insulated Aluminum Conductors Cabled Within an Overall Covering (Three-Conductor Cable), Directly Buried in Earth Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit [See Figure 315.60(D)(3), Detail 5.] 8 65 70 - - 6 80 88 90 95 4 105 115 115 125 2 140 150 145 155 1 155 170 165 175 1/0 180 190 185 200 2/0 205 220 210 225 3/0 230 250 240 260 4/0 260 280 270 295 250 285 310 300 320 350 345 375 360 390 500 420 450 435 470 750 520 560 540 580 1000 600 650 620 665 Two Circuits [See Figure 315.60(D)(3), Detail 6.] 8 60 66 - - 6 75 83 80 95 4 100 110 105 115 2 130 140 135 145 1 145 155 150 165 1/0 165 180 170 185 2/0 190 205 195 210 3/0 215 230 220 240 4/0 245 260 250 270 250 265 285 275 295 350 320 345 330 355 500 385 415 395 425 750 480 515 485 525 1000 550 590 560 600 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(19) Ampacities of Three Triplexed Single Insulated Copper Conductors Directly Buried in Earth Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit, Three Conductors [See Figure 315.60(D)(3), Detail 7.] 8 90 95 - - 6 120 130 115 120 4 150 165 150 160 2 195 205 190 205 1 225 240 215 230 1/0 255 270 245 260 2/0 290 310 275 295 3/0 330 360 315 340 4/0 375 405 360 385 250 410 445 390 410 350 490 580 470 505 500 590 635 565 605 750 725 780 685 740 1000 825 885 770 830 Two Circuits, Six Conductors [See Figure 315.60(D)(3), Detail 8.] 8 85 90 - - 6 110 115 105 115 4 140 150 140 150 2 180 195 175 190 1 205 220 200 215 1/0 235 250 225 240 2/0 265 285 255 275 3/0 300 320 290 315 4/0 340 365 325 350 250 370 395 355 380 350 445 480 425 455 500 535 575 510 545 750 650 700 615 660 1000 740 795 690 745 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. Table 315.60(C)(20) Ampacities of Three Triplexed Single Insulated Aluminum Conductors Directly Buried in Earth Conductor Size (AWG or kcmil) Temperature Rating of Conductor 2001—5000 Volts Ampacity 5001—35,000 Volts Ampacity 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 One Circuit, Three Conductors [See Figure 315.60(D)(3), Detail 7.] 8 70 75 - - 6 90 100 90 95 4 120 130 115 125 2 155 165 145 155 1 175 190 165 175 1/0 200 210 190 205 2/0 225 240 215 230 3/0 255 275 245 265 4/0 290 310 280 305 250 320 350 305 325 350 385 420 370 400 500 465 500 445 480 750 580 625 550 590 1000 670 725 635 680 Two Circuits, Six Conductors [See Figure 315.60(D)(3), Detail 8.] 8 65 70 - - 6 85 95 85 90 4 110 120 105 115 2 140 150 135 145 1 160 170 155 170 1/0 180 195 175 190 2/0 205 220 200 215 3/0 235 250 225 245 4/0 265 285 255 275 250 290 310 280 300 350 350 375 335 360 500 420 455 405 435 750 520 560 485 525 1000 600 645 565 605 Note: Refer to 315.60(F) for basis of ampacities and Table 315.10(A) for the temperature rating of the conductor. [315.60(C)](https://2023.antflix.net#315.60(C))
https://2023.antflix.net#315.60(C)
Chapter 3 Wiring Methods and Materials
315.60(D)(1)
Ampacities shown in Table 315.60(C)(3), Table 315.60(C)(4), Table 315.60(C)(15), and Table 315.60(C)(16) shall apply for cables with shields grounded at one point only. Where shields for these cables are grounded at more than one point, ampacities shall be adjusted to take into consideration the heating due to shield currents. Informational Note: Tables other than those listed contain the ampacity of cables with shields grounded at multiple points. [315.60(D)(1)](https://2023.antflix.net#315.60(D)(1))
https://2023.antflix.net#315.60(D)(1)
Chapter 3 Wiring Methods and Materials
315.60(D)(2)
Where the burial depth of direct burial or electrical duct bank circuits is modified from the values shown in a figure or table, ampacities shall be permitted to be modified as indicated in 315.60(D)(2)(a) and (D)(2)(b). No ampacity adjustments shall be required where the burial depth is decreased. Where burial depths are increased in part(s) of an electrical duct run, a decrease in ampacity of the conductors shall not be required, provided the total length of parts of the duct run increased in depth is less than 25 percent of the total run length.Where burial depths are deeper than shown in a specific underground ampacity table or figure, an ampacity derating factor of 6 percent per 300 mm (1 ft) increase in depth for all values of rho shall be permitted. [315.60(D)(2)](https://2023.antflix.net#315.60(D)(2))
https://2023.antflix.net#315.60(D)(2)
Chapter 3 Wiring Methods and Materials
315.60(D)(3)
At locations where electrical ducts enter equipment enclosures from underground, spacing between such ducts, as shown in Figure 315.60(D)(3), shall be permitted to be reduced without requiring the ampacity of conductors therein to be reduced. FIGURE 315.60(D)(3) Cable Installation Dimensions for Use with Table 315.60(C)(11) Through Table 315.60(C)(20). [315.60(D)(3)](https://2023.antflix.net#315.60(D)(3))
https://2023.antflix.net#315.60(D)(3)
Chapter 3 Wiring Methods and Materials
315.60(D)(4)
Ampacities for ambient temperatures other than those specified in the ampacity tables shall be corrected in accordance with Table 315.60(D)(4) or shall be permitted to be calculated using the following equation: [315.60(D)(4)] where: I' = ampacity corrected for ambient temperature I = ampacity shown in the table for Tc and Ta Tc = temperature rating of conductor (°C) Ta' = new ambient temperature (°C) Ta = ambient temperature used in the table (°C) Informational Note: See 110.40 for ambient temperature adjustments for terminals. Table 315.60(D)(4) Ambient Temperature Correction Factors For ambient temperatures other than 40°C (104°F), multiply the allowable ampacities specified in the ampacity tables by the appropriate factor shown below. Ambient Temperature (°C) Temperature Rating of Conductor Ambient Temperature (°F) 90°C 105°C 10 or less 1.26 1.21 50 or less 11—15 1.22 1.18 51—59 16—20 1.18 1.14 60—68 21—25 1.14 1.11 69—77 26—30 1.10 1.07 78—86 31—35 1.05 1.04 87—95 36—40 1.00 1.00 96—104 41—45 0.95 0.96 105—113 46—50 0.89 0.92 114—122 51—55 0.84 0.88 123—131 56—60 0.77 0.83 132—140 61—65 0.71 0.78 141—149 66—70 0.63 0.73 150—158 71—75 0.55 0.68 159—167 76—80 0.45 0.62 168—176 81—85 0.32 0.55 177—185 86—90 - 0.48 186—194 91—95 - 0.39 195—203 96—100 - 0.28 204—212 [315.60(D)(4)](https://2023.antflix.net#315.60(D)(4))
https://2023.antflix.net#315.60(D)(4)
Chapter 3 Wiring Methods and Materials
315.60(E)
Ampacities for conductors and cables in air shall be as specified in Table 315.60(C)(1) through Table 315.60(C)(10). Ampacities shall be based on the following: Conductor temperatures of 90°C (194°F) and 105°C (221°F)Ambient air temperature of 40°C (104°F)Informational Note: See 315.60(D)(4) where the ambient air temperature is other than 40°C (104°F). [315.60(E)](https://2023.antflix.net#315.60(E))
https://2023.antflix.net#315.60(E)
Chapter 3 Wiring Methods and Materials
315.60(F)
Ampacities for conductors and cables in underground electrical ducts and direct buried in earth shall be as specified in Table 315.60(C)(11) through Table 315.60(C)(20). Ampacities shall be based on the following: Ambient earth temperature of 20°C (68°F)Arrangement in accordance with Figure 315.60(D)(3)100 percent load factorThermal resistance (Rho) of 90Conductor temperatures 90°C (194°F) and 105°C (221°F)Minimum burial depths to the top electrical ducts or cables shall be in accordance with 305.15.Maximum depth to the top of electrical duct banks shall be 750 mm (30 in.), and maximum depth to the top of direct-buried cables shall be 900 mm (36 in.). [315.60(F)](https://2023.antflix.net#315.60(F))
https://2023.antflix.net#315.60(F)
Chapter 3 Wiring Methods and Materials
320.1
This article covers the use, installation, and construction specifications for armored cable, Type AC. [320.1](https://2023.antflix.net#320.1)
https://2023.antflix.net#320.1
Chapter 3 Wiring Methods and Materials
320.6
Type AC cable and associated fittings shall be listed. [320.6](https://2023.antflix.net#320.6)
https://2023.antflix.net#320.6
Chapter 3 Wiring Methods and Materials
320.10
Type AC cable shall be permitted as follows: For feeders and branch circuits in both exposed and concealed installationsIn cable traysIn dry locationsEmbedded in plaster finish on brick or other masonry, except in damp or wet locationsTo be run or fished in the air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampnessInformational Note: The "Uses Permitted" is not an all-inclusive list. [320.10](https://2023.antflix.net#320.10)
https://2023.antflix.net#320.10
Chapter 3 Wiring Methods and Materials
320.12
Type AC cable shall not be used as follows: Where subject to physical damageIn damp or wet locationsIn air voids of masonry block or tile walls where such walls are exposed or subject to excessive moisture or dampnessWhere exposed to corrosive conditionsEmbedded in plaster finish on brick or other masonry in damp or wet locations [320.12](https://2023.antflix.net#320.12)
https://2023.antflix.net#320.12
Chapter 3 Wiring Methods and Materials
320.15
Exposed runs of cable, except as provided in 300.11(B), shall closely follow the surface of the building finish or of running boards. Exposed runs shall also be permitted to be installed on the underside of joists where supported at each joist and located so as not to be subject to physical damage. [320.15](https://2023.antflix.net#320.15)
https://2023.antflix.net#320.15
Chapter 3 Wiring Methods and Materials
320.17
Type AC cable shall be protected in accordance with 300.4(A), (C), and (D) where installed through or parallel to framing members. [320.17](https://2023.antflix.net#320.17)
https://2023.antflix.net#320.17
Chapter 3 Wiring Methods and Materials
320.23
Type AC cables in accessible attics or roof spaces shall be installed as specified in 320.23(A) and (B). [320.23](https://2023.antflix.net#320.23)
https://2023.antflix.net#320.23
Chapter 3 Wiring Methods and Materials
320.23(A)
Where run across the top of framing members, or across the face of rafters or studding within 2.1 m (7 ft) of the floor or horizontal surface, the cable shall be protected by guard strips that are at least as high as the cable. Where this space is not accessible by permanently installed stairs or ladders, protection shall only be required within 1.8 m (6 ft) of the nearest edge of the scuttle hole or attic entrance. [320.23(A)](https://2023.antflix.net#320.23(A))
https://2023.antflix.net#320.23(A)
Chapter 3 Wiring Methods and Materials
320.23(B)
Where the cable is installed parallel to the sides of rafters, studs, or ceiling or floor joists, neither guard strips nor running boards shall be required, and the installation shall also comply with 300.4(D). [320.23(B)](https://2023.antflix.net#320.23(B))
https://2023.antflix.net#320.23(B)
Chapter 3 Wiring Methods and Materials
320.24
Bends in Type AC cable shall be made such that the cable is not damaged. The radius of the curve of the inner edge of any bend shall not be less than five times the diameter of the Type AC cable. [320.24](https://2023.antflix.net#320.24)
https://2023.antflix.net#320.24
Chapter 3 Wiring Methods and Materials
320.30(A)
Type AC cable shall be supported and secured by staples; cable ties listed and identified for securement and support; straps, hangers, or similar fittings; or other approved means designed and installed so as not to damage the cable. Type AC cable fittings shall be permitted as a means of cable support. [320.30(A)](https://2023.antflix.net#320.30(A))
https://2023.antflix.net#320.30(A)
Chapter 3 Wiring Methods and Materials
320.30(B)
Unless otherwise permitted, Type AC cable shall be secured within 300 mm (12 in.) of every outlet box, junction box, cabinet, or fitting and at intervals not exceeding 1.4 m (41/2 ft). [320.30(B)](https://2023.antflix.net#320.30(B))
https://2023.antflix.net#320.30(B)
Chapter 3 Wiring Methods and Materials
320.30(C)
Unless otherwise permitted, Type AC cable shall be supported at intervals not exceeding 1.4 m (41/2 ft). Horizontal runs of Type AC cable installed in wooden or metal framing members or similar supporting means shall be considered supported and secured where such support does not exceed 1.4 m (41/2 ft) intervals. [320.30(C)](https://2023.antflix.net#320.30(C))
https://2023.antflix.net#320.30(C)
Chapter 3 Wiring Methods and Materials
320.30(D)
Type AC cable shall be permitted to be unsupported and unsecured where the cable complies with any of the following: Is fished between access points through concealed spaces in finished buildings or structures and supporting is impracticableIs not more than 600 mm (2 ft) in length at terminals where flexibility is necessaryIs not more than 1.8 m (6 ft) in length from the last point of cable support to the point of connection to a luminaire(s) or other electrical equipment and the cable and point of connection are within an accessible ceiling [320.30(D)](https://2023.antflix.net#320.30(D))
https://2023.antflix.net#320.30(D)
Chapter 3 Wiring Methods and Materials
320.40
At all points where the armor of AC cable terminates, a fitting shall be provided to protect wires from abrasion, unless the design of the outlet boxes or fittings is such as to afford equivalent protection, and, in addition, an insulating bushing or its equivalent protection shall be provided between the conductors and the armor. The connector or clamp by which the Type AC cable is fastened to boxes or cabinets shall be of such design that the insulating bushing or its equivalent will be visible for inspection. Where change is made from Type AC cable to other cable or raceway wiring methods, a box, fitting, or conduit body shall be installed at junction points as required in 300.15. [320.40](https://2023.antflix.net#320.40)
https://2023.antflix.net#320.40
Chapter 3 Wiring Methods and Materials
320.80
The ampacity shall be determined in accordance with 310.14. [320.80](https://2023.antflix.net#320.80)
https://2023.antflix.net#320.80
Chapter 3 Wiring Methods and Materials
320.80(A)
Armored cable installed in thermal insulation shall have conductors rated at 90°C (194°F). The ampacity of cable installed in these applications shall not exceed that of a 60°C (140°F) rated conductor. The 90°C (194°F) rating shall be permitted to be used for ampacity adjustment and correction calculations; however, the ampacity shall not exceed that of a 60°C (140°F) rated conductor. Where more than two Type AC cables containing two or more current-carrying conductors in each cable are installed in contact with thermal insulation, caulk, or sealing foam without maintaining spacing between cables, the ampacity of each conductor shall be adjusted in accordance with Table 310.15(C)(1). [320.80(A)](https://2023.antflix.net#320.80(A))
https://2023.antflix.net#320.80(A)
Chapter 3 Wiring Methods and Materials
320.80(B)
The ampacity of Type AC cable installed in cable tray shall be determined in accordance with 392.80(A). [320.80(B)](https://2023.antflix.net#320.80(B))
https://2023.antflix.net#320.80(B)
Chapter 3 Wiring Methods and Materials
320.100
Type AC cable shall have an armor of flexible metal tape and shall have an internal bonding strip of copper or aluminum in intimate contact with the armor for its entire length. [320.100](https://2023.antflix.net#320.100)
https://2023.antflix.net#320.100
Chapter 3 Wiring Methods and Materials
320.104
Insulated conductors shall be of a type listed in Table 310.4(1) or those identified for use in this cable. In addition, the conductors shall have an overall moisture-resistant and fire-retardant fibrous covering. For Type ACT, a moisture-resistant fibrous covering shall be required only on the individual conductors. [320.104](https://2023.antflix.net#320.104)
https://2023.antflix.net#320.104
Chapter 3 Wiring Methods and Materials
320.108
Type AC cable shall provide an adequate path for fault current as required by 250.4(A)(5) or (B)(4) to act as an equipment grounding conductor. [320.108](https://2023.antflix.net#320.108)
https://2023.antflix.net#320.108
Chapter 3 Wiring Methods and Materials
320.120
The cable shall be marked in accordance with 310.8, except that Type AC shall have ready identification of the manufacturer by distinctive external markings on the cable armor throughout its entire length. [320.120](https://2023.antflix.net#320.120)
https://2023.antflix.net#320.120
Chapter 3 Wiring Methods and Materials
322.1
This article covers the use, installation, and construction specifications for flat cable assemblies, Type FC. [322.1](https://2023.antflix.net#322.1)
https://2023.antflix.net#322.1
Chapter 3 Wiring Methods and Materials
322.6
Type FC and associated fittings shall be listed. [322.6](https://2023.antflix.net#322.6)
https://2023.antflix.net#322.6
Chapter 3 Wiring Methods and Materials
322.10
Flat cable assemblies shall be permitted only as follows: As branch circuits to supply suitable tap devices for lighting, small appliances, or small power loads. The rating of the branch circuit shall not exceed 30 amperes.Where installed for exposed work.In locations where they will not be subjected to physical damage. Where a flat cable assembly is installed less than 2.5 m (8 ft) above the floor or fixed working platform, it shall be protected by a cover identified for the use.In surface metal raceways identified for the use. The channel portion of the surface metal raceway systems shall be installed as complete systems before the flat cable assemblies are pulled into the raceways. [322.10](https://2023.antflix.net#322.10)
https://2023.antflix.net#322.10
Chapter 3 Wiring Methods and Materials
322.12
Flat cable assemblies shall not be used as follows: Where exposed to corrosive conditions, unless suitable for the applicationIn hoistways or on elevators or escalatorsIn any hazardous (classified) location, except as specifically permitted by other articles in this Code.Outdoors or in wet or damp locations unless identified for the use [322.12](https://2023.antflix.net#322.12)
https://2023.antflix.net#322.12
Chapter 3 Wiring Methods and Materials
322.30
The flat cable assemblies shall be supported by means of their special design features, within the surface metal raceways. The surface metal raceways shall be supported as required for the specific raceway to be installed. [322.30](https://2023.antflix.net#322.30)
https://2023.antflix.net#322.30
Chapter 3 Wiring Methods and Materials
322.40(A)
Each flat cable assembly dead end shall be terminated in an end-cap device identified for the use. The dead-end fitting for the enclosing surface metal raceway shall be identified for the use. [322.40(A)](https://2023.antflix.net#322.40(A))
https://2023.antflix.net#322.40(A)
Chapter 3 Wiring Methods and Materials
322.40(B)
Luminaire hangers installed with the flat cable assemblies shall be identified for the use. [322.40(B)](https://2023.antflix.net#322.40(B))
https://2023.antflix.net#322.40(B)
Chapter 3 Wiring Methods and Materials
322.40(C)
Fittings to be installed with flat cable assemblies shall be designed and installed to prevent physical damage to the cable assemblies. [322.40(C)](https://2023.antflix.net#322.40(C))
https://2023.antflix.net#322.40(C)
Chapter 3 Wiring Methods and Materials
322.40(D)
All extensions from flat cable assemblies shall be made by approved wiring methods, within the junction boxes, installed at either end of the flat cable assembly runs. [322.40(D)](https://2023.antflix.net#322.40(D))
https://2023.antflix.net#322.40(D)
Chapter 3 Wiring Methods and Materials
322.56(A)
Splices shall be made in listed junction boxes. [322.56(A)](https://2023.antflix.net#322.56(A))
https://2023.antflix.net#322.56(A)
Chapter 3 Wiring Methods and Materials
322.56(B)
Taps shall be made between any phase conductor and the grounded conductor or any other phase conductor by means of devices and fittings identified for the use. Tap devices shall be rated at not less than 15 amperes, or more than 300 volts to ground, and shall be marked in accordance with 322.120(C). [322.56(B)](https://2023.antflix.net#322.56(B))
https://2023.antflix.net#322.56(B)
Chapter 3 Wiring Methods and Materials
322.100
Flat cable assemblies shall consist of two, three, four, or five conductors. [322.100](https://2023.antflix.net#322.100)
https://2023.antflix.net#322.100
Chapter 3 Wiring Methods and Materials
322.104
Flat cable assemblies shall have conductors of 10 AWG special stranded copper wires. [322.104](https://2023.antflix.net#322.104)
https://2023.antflix.net#322.104
Chapter 3 Wiring Methods and Materials
322.112
The entire flat cable assembly shall be formed to provide a suitable insulation covering all the conductors and using one of the materials recognized in Table 310.4(1) for general branch-circuit wiring. [322.112](https://2023.antflix.net#322.112)
https://2023.antflix.net#322.112
Chapter 3 Wiring Methods and Materials
322.120(A)
In addition to the provisions of 310.8, Type FC cable shall have the temperature rating durably marked on the surface at intervals not exceeding 600 mm (24 in.). [322.120(A)](https://2023.antflix.net#322.120(A))
https://2023.antflix.net#322.120(A)
Chapter 3 Wiring Methods and Materials
322.120(B)
The grounded conductor shall be identified throughout its length by means of a distinctive and durable white or gray marking. Informational Note: The color gray may have been used in the past as an ungrounded conductor. Care should be taken when working on existing systems. [322.120(B)](https://2023.antflix.net#322.120(B))
https://2023.antflix.net#322.120(B)
Chapter 3 Wiring Methods and Materials
322.120(C)
Terminal blocks identified for the use shall have distinctive and durable markings for color or word coding. The grounded conductor section shall have a white marking or other suitable designation. The next adjacent section of the terminal block shall have a black marking or other suitable designation. The next section shall have a red marking or other suitable designation. The final or outer section, opposite the grounded conductor section of the terminal block, shall have a blue marking or other suitable designation. [322.120(C)](https://2023.antflix.net#322.120(C))
https://2023.antflix.net#322.120(C)
Chapter 3 Wiring Methods and Materials
324.1
This article covers a field-installed wiring system for branch circuits incorporating Type FCC cable and associated accessories as defined by the article. The wiring system is designed for installation under carpet squares. [324.1](https://2023.antflix.net#324.1)
https://2023.antflix.net#324.1
Chapter 3 Wiring Methods and Materials
324.6
Type FCC cable and associated fittings shall be listed. [324.6](https://2023.antflix.net#324.6)
https://2023.antflix.net#324.6
Chapter 3 Wiring Methods and Materials
324.10(A)
Use of FCC systems shall be permitted both for general-purpose and appliance branch circuits and for individual branch circuits. [324.10(A)](https://2023.antflix.net#324.10(A))
https://2023.antflix.net#324.10(A)
Chapter 3 Wiring Methods and Materials
324.10(B)(1)
Voltage between ungrounded conductors shall not exceed 300 volts. Voltage between ungrounded conductors and the grounded conductor shall not exceed 150 volts. [324.10(B)(1)](https://2023.antflix.net#324.10(B)(1))
https://2023.antflix.net#324.10(B)(1)
Chapter 3 Wiring Methods and Materials
324.10(B)(2)
General-purpose and appliance branch circuits shall have ratings not exceeding 20 amperes. Individual branch circuits shall have ratings not exceeding 30 amperes. [324.10(B)(2)](https://2023.antflix.net#324.10(B)(2))
https://2023.antflix.net#324.10(B)(2)
Chapter 3 Wiring Methods and Materials
324.10(C)
Use of FCC systems shall be permitted on hard, sound, smooth, continuous floor surfaces made of concrete, ceramic, or composition flooring, wood, and similar materials. [324.10(C)](https://2023.antflix.net#324.10(C))
https://2023.antflix.net#324.10(C)
Chapter 3 Wiring Methods and Materials
324.10(D)
Use of FCC systems shall be permitted on wall surfaces in surface metal raceways. [324.10(D)](https://2023.antflix.net#324.10(D))
https://2023.antflix.net#324.10(D)
Chapter 3 Wiring Methods and Materials
324.10(E)
Use of FCC systems in damp locations shall be permitted. [324.10(E)](https://2023.antflix.net#324.10(E))
https://2023.antflix.net#324.10(E)
Chapter 3 Wiring Methods and Materials
324.10(F)
Materials used for floors heated in excess of 30°C (86°F) shall be identified as suitable for use at these temperatures. [324.10(F)](https://2023.antflix.net#324.10(F))
https://2023.antflix.net#324.10(F)
Chapter 3 Wiring Methods and Materials
324.10(G)
Any portion of an FCC system with a height above floor level exceeding 2.3 mm (0.090 in.) shall be tapered or feathered at the edges to floor level. [324.10(G)](https://2023.antflix.net#324.10(G))
https://2023.antflix.net#324.10(G)
Chapter 3 Wiring Methods and Materials
324.12
FCC systems shall not be used in the following locations: Outdoors or in wet locationsWhere subject to corrosive vaporsIn any hazardous (classified) locationIn residential buildingsIn school and hospital buildings, other than administrative office areas [324.12](https://2023.antflix.net#324.12)
https://2023.antflix.net#324.12
Chapter 3 Wiring Methods and Materials
324.18
Crossings of more than two Type FCC cable runs shall not be permitted at any one point. Crossings of a Type FCC cable over or under a flat communications or signal cable shall be permitted. In each case, a grounded layer of metal shielding shall separate the two cables, and crossings of more than two flat cables shall not be permitted at any one point. [324.18](https://2023.antflix.net#324.18)
https://2023.antflix.net#324.18
Chapter 3 Wiring Methods and Materials
324.30
All FCC system components shall be firmly anchored to the floor or wall using an adhesive or mechanical anchoring system identified for this use. Floors shall be prepared to ensure adherence of the FCC system to the floor until the carpet squares are placed. [324.30](https://2023.antflix.net#324.30)
https://2023.antflix.net#324.30
Chapter 3 Wiring Methods and Materials
324.40(A)
All Type FCC cable connections shall use connectors identified for their use, installed such that electrical continuity, insulation, and sealing against dampness and liquid spillage are provided. All bare cable ends shall be insulated and sealed against dampness and liquid spillage using listed insulating ends. [324.40(A)](https://2023.antflix.net#324.40(A))
https://2023.antflix.net#324.40(A)
Chapter 3 Wiring Methods and Materials
324.40(B)
All receptacles and connections shall be constructed and installed so as to maintain proper polarization of the system. [324.40(B)](https://2023.antflix.net#324.40(B))
https://2023.antflix.net#324.40(B)
Chapter 3 Wiring Methods and Materials
324.40(C)(1)
A metal top shield shall be installed over all floor-mounted Type FCC cable, connectors, and insulating ends. The top shield shall completely cover all cable runs, corners, connectors, and ends. [324.40(C)(1)](https://2023.antflix.net#324.40(C)(1))
https://2023.antflix.net#324.40(C)(1)
Chapter 3 Wiring Methods and Materials
324.40(C)(2)
A bottom shield shall be installed beneath all Type FCC cable, connectors, and insulating ends. [324.40(C)(2)](https://2023.antflix.net#324.40(C)(2))
https://2023.antflix.net#324.40(C)(2)
Chapter 3 Wiring Methods and Materials
324.40(D)
Power feed, grounding connection, and shield system connection between the FCC system and other wiring systems shall be accomplished in a transition assembly identified for this use. [324.40(D)](https://2023.antflix.net#324.40(D))
https://2023.antflix.net#324.40(D)
Chapter 3 Wiring Methods and Materials
324.40(E)
Metal shields shall be connected to each other and to boxes, receptacle housings, self-contained devices, and transition assemblies using metal-shield connectors. [324.40(E)](https://2023.antflix.net#324.40(E))
https://2023.antflix.net#324.40(E)
Chapter 3 Wiring Methods and Materials
324.41
Floor-mounted Type FCC cable, cable connectors, and insulating ends shall be covered with carpet squares not larger than 1.0 m (39.37 in.) square. Carpet squares that are adhered to the floor shall be attached with release-type adhesives. [324.41](https://2023.antflix.net#324.41)
https://2023.antflix.net#324.41
Chapter 3 Wiring Methods and Materials
324.42(A)
All receptacles, receptacle housings, and self-contained devices used with the FCC system shall be identified for this use and shall be connected to the Type FCC cable and metal shields. Connection from any equipment grounding conductor of the Type FCC cable shall be made to the shield system at each receptacle. [324.42(A)](https://2023.antflix.net#324.42(A))
https://2023.antflix.net#324.42(A)
Chapter 3 Wiring Methods and Materials
324.42(B)
Receptacle housings and self-contained devices designed either for floor mounting or for in-wall or on-wall mounting shall be permitted for use with the FCC system. Receptacle housings and self-contained devices shall incorporate means for facilitating entry and termination of Type FCC cable and for electrically connecting the housing or device with the metal shield. Receptacles and self-contained devices shall comply with 406.4. Power and communications outlets installed together in common housing shall be permitted in accordance with 800.133(A)(3), Exception No. 2. [324.42(B)](https://2023.antflix.net#324.42(B))
https://2023.antflix.net#324.42(B)
Chapter 3 Wiring Methods and Materials
324.56(A)
Alterations to FCC systems shall be permitted. New cable connectors shall be used at new connection points to make alterations. It shall be permitted to leave unused cable runs and associated cable connectors in place and energized. All cable ends shall be covered with insulating ends. [324.56(A)](https://2023.antflix.net#324.56(A))
https://2023.antflix.net#324.56(A)
Chapter 3 Wiring Methods and Materials
324.56(B)
All transition assemblies shall be identified for their use. Each assembly shall incorporate means for facilitating entry of the Type FCC cable into the assembly, for connecting the Type FCC cable to grounded conductors, and for electrically connecting the assembly to the metal cable shields and to equipment grounding conductors. [324.56(B)](https://2023.antflix.net#324.56(B))
https://2023.antflix.net#324.56(B)
Chapter 3 Wiring Methods and Materials
324.60
All metal shields, boxes, receptacle housings, and self-contained devices shall be electrically continuous to the equipment grounding conductor of the supplying branch circuit. All such electrical connections shall be made with connectors identified for this use. The electrical resistivity of such shield system shall not be more than that of one conductor of the Type FCC cable used in the installation. [324.60](https://2023.antflix.net#324.60)
https://2023.antflix.net#324.60
Chapter 3 Wiring Methods and Materials
324.100(A)
Type FCC cable shall be listed for use with the FCC system and shall consist of three, four, or five flat copper conductors, one of which shall be an equipment grounding conductor. [324.100(A)](https://2023.antflix.net#324.100(A))
https://2023.antflix.net#324.100(A)
Chapter 3 Wiring Methods and Materials
324.100(B)(1)
All top and bottom shields shall be of designs and materials identified for their use. Top shields shall be metal. Both metallic and nonmetallic materials shall be permitted for bottom shields. [324.100(B)(1)](https://2023.antflix.net#324.100(B)(1))
https://2023.antflix.net#324.100(B)(1)
Chapter 3 Wiring Methods and Materials
324.100(B)(2)
Metal shields shall have cross-sectional areas that provide for electrical resistivity of not more than that of one conductor of the Type FCC cable used in the installation. [324.100(B)(2)](https://2023.antflix.net#324.100(B)(2))
https://2023.antflix.net#324.100(B)(2)
Chapter 3 Wiring Methods and Materials
324.101
Metal components of the system shall be either corrosion resistant, coated with corrosion-resistant materials, or insulated from contact with corrosive substances. [324.101](https://2023.antflix.net#324.101)
https://2023.antflix.net#324.101
Chapter 3 Wiring Methods and Materials
324.112
The insulating material of the cable shall be moisture resistant and flame retardant. All insulating materials in the FCC systems shall be identified for their use. [324.112](https://2023.antflix.net#324.112)
https://2023.antflix.net#324.112
Chapter 3 Wiring Methods and Materials
324.120(A)
Type FCC cable shall be clearly and durably marked on both sides at intervals of not more than 610 mm (24 in.) with the information required by 310.8(A) and with the following additional information: Material of conductorsMaximum temperature ratingAmpacity [324.120(A)](https://2023.antflix.net#324.120(A))
https://2023.antflix.net#324.120(A)
Chapter 3 Wiring Methods and Materials
324.120(B)
Conductors shall be clearly and durably identified on both sides throughout their length as specified in 310.6. [324.120(B)](https://2023.antflix.net#324.120(B))
https://2023.antflix.net#324.120(B)
Chapter 3 Wiring Methods and Materials
326.1
This article covers the use, installation, and construction specifications for integrated gas spacer cable, Type IGS. [326.1](https://2023.antflix.net#326.1)
https://2023.antflix.net#326.1
Chapter 3 Wiring Methods and Materials
326.10
Type IGS cable shall be permitted for use underground, including direct burial in the earth, as the following: Service-entrance conductorsFeeder or branch-circuit conductorsService conductors, underground [326.10](https://2023.antflix.net#326.10)
https://2023.antflix.net#326.10
Chapter 3 Wiring Methods and Materials
326.12
Type IGS cable shall not be used as interior wiring or be exposed in contact with buildings. [326.12](https://2023.antflix.net#326.12)
https://2023.antflix.net#326.12
Chapter 3 Wiring Methods and Materials
326.24
Where the coilable nonmetallic conduit and cable are bent for installation purposes or are flexed or bent during shipment or installation, the radius of the curve of the inner edge measured to the inside of the bend shall not be less than specified in Table 326.24. Table 326.24 Minimum Radii of Bends Conduit Size Minimum Radii Metric Designator Trade Size mm in. 53 2 600 24 78 3 900 35 103 4 1150 45 [326.24](https://2023.antflix.net#326.24)
https://2023.antflix.net#326.24
Chapter 3 Wiring Methods and Materials
326.26
A run of Type IGS cable between pull boxes or terminations shall not contain more than the equivalent of four quarter bends (360 degrees total), including those bends located immediately at the pull box or terminations. [326.26](https://2023.antflix.net#326.26)
https://2023.antflix.net#326.26
Chapter 3 Wiring Methods and Materials
326.40
Terminations and splices for Type IGS cable shall be identified as a type that is suitable for maintaining the gas pressure within the conduit. A valve and cap shall be provided for each length of the cable and conduit to check the gas pressure or to inject gas into the conduit. [326.40](https://2023.antflix.net#326.40)
https://2023.antflix.net#326.40
Chapter 3 Wiring Methods and Materials
326.80
The ampacity of Type IGS cable shall not exceed the values shown in Table 326.80. Table 326.80 Ampacity of Type IGS Cable Size (kcmil) Amperes Size (kcmil) Amperes 250 119 2500 376 500 168 3000 412 750 206 3250 429 1000 238 3500 445 1250 266 3750 461 1500 292 4000 476 1750 315 4250 491 2000 336 4500 505 2250 357 4750 519 [326.80](https://2023.antflix.net#326.80)
https://2023.antflix.net#326.80
Chapter 3 Wiring Methods and Materials
326.104
The conductors shall be solid aluminum rods, laid parallel, consisting of one to nineteen 12.7 mm (1/2 in.) diameter rods. The minimum conductor size shall be 250 kcmil, and the maximum size shall be 4750 kcmil. [326.104](https://2023.antflix.net#326.104)
https://2023.antflix.net#326.104
Chapter 3 Wiring Methods and Materials
326.112
The insulation shall be dry kraft paper tapes and a pressurized sulfur hexafluoride gas (SF6), both approved for electrical use. The nominal gas pressure shall be 138 kPa gauge (20 lb/in.2 gauge). The thickness of the paper spacer shall be as specified in Table 326.112. Table 326.112 Paper Spacer Thickness Size (kcmil) Thickness mm in. 250—1000 1.02 0.040 1250—4750 1.52 0.060 [326.112](https://2023.antflix.net#326.112)
https://2023.antflix.net#326.112