| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| VENTILATION | |
| 403.1 Ventilation system. | |
| Mechanical ventilation shall be | |
| provided | |
| by a method of supply air and return or exhaust air. The | |
| amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be | |
| prohibited | |
| from producing negative or positive pressure; such pressures shall not r | |
| esult in door opening forces in excess of those indicated | |
| in the | |
| New York City Building Code | |
| and shall not prevent doors from closing as required by the | |
| New York City Building Code | |
| . | |
| The | |
| method | |
| to convey ventilation air shall be designed and installed in ac | |
| cordance with Chapter 6. | |
| 403.2 Outdoor air required. | |
| The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. | |
| Exception: | |
| The minimum required rate of outdoor air may be reduced where the registered design professional demo | |
| nstrates | |
| that an engineered ventilation system is designed in accordance with ASHRAE 62.1 | |
| Indoor Air Quality Procedure | |
| . | |
| 403.2.1 Recirculation of air. | |
| The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that | |
| required by | |
| Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, | |
| except that: | |
| 1. | |
| Ventilation air shall not be recirculated from one dwelling | |
| unit | |
| to another or to dissimilar occupancies. | |
| 2. | |
| Supply air to a | |
| swimming pool and associated deck areas shall not be recirculated unless such air is | |
| dehumidified | |
| to | |
| maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other | |
| uses or occupancies | |
| . | |
| 3. | |
| Where mech | |
| anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be | |
| prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- | |
| culation of air is prohibited, all | |
| air supplied to such spaces shall be exhausted, including any air in excess of that | |
| required by Table 403.3.1.1. | |
| 4. | |
| Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation | |
| is prohibited. Recircula | |
| tion of air that is contained completely within such spaces shall not be prohibited. | |
| 403.2.2 Transfer air. | |
| Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from | |
| occupiable spaces is not prohibited from serving a | |
| s makeup air for required exhaust systems in such spaces as kitchens, | |
| baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide | |
| the flow rates as specified in Section 403.3.1.1. The requir | |
| ed outdoor airflow rates specified in Table 403.3.1.1 shall be | |
| introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. | |
| 403.3 Outdoor air and local exhaust airflow rates. | |
| Buildings that are no | |
| t more than three stories in height above grade plane, | |
| and that (i) are within Occupancy Group R | |
| - | |
| 2 or Occupancy Group R | |
| - | |
| 3, (ii) are adult homes or enriched living housing as | |
| described in Section 308.3.1 of the | |
| New York City Building Code, | |
| within Occupancy | |
| Group I | |
| - | |
| 1 and have 16 occupants or fewer, | |
| or (iii) are community residences or intermediate | |
| - | |
| care facilities as described in Section 308.3.2 of the | |
| New York City Building | |
| Code, | |
| shall be provided with outdoor air and local exhaust in accordance with Section | |
| 403.3.1.1.2. All other buildings intended | |
| to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. | |
| 403.3.1 Reserved. | |
| 403.3.1.1 Outdoor airflow rate. | |
| Ventilation systems shall be designed t | |
| o have the capacity to supply the minimum | |
| outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each | |
| habitable space, the ventilation system shall be designed to deliver the required rate of outdoor | |
| airflow to the breathing | |
| zone. The occupant load utilized for design of the ventilation system shall be | |
| not less than the number | |
| determined | |
| from | |
| the estimated maximum occupant load rate | |
| indicated | |
| in Table 403.3.1.1 | |
| . | |
| Ventilation rates for | |
| occupancies not represented | |
| in Table 403.3.1.1 | |
| shall be those for a listed occupancy classification that is most similar in terms of occupant density, | |
| activities and building construction; or shall be determined by an approved engineering analysis. The ven | |
| tilation system | |
| shall be designed to supply the required rate of ventilation air continuously | |
| during | |
| the period the building is occupied, | |
| except as otherwise stated in other provisions of the code. | |
| With the exception of non | |
| - | |
| tobacco hookah establishments, t | |
| he ventilation rates in Table 403.3.1.1 | |
| are based on the | |
| absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non | |
| - | |
| tobacco hookah | |
| establishment, the ventilation system serving the space shall be designed to provide v | |
| entilation over and above that re- | |
| quired by Table 403.3.1.1 | |
| in accordance with accepted engineering practice. | |
| Exceptions: | |
| 1. | |
| The occupant load is not required to be | |
| determined | |
| based on the estimated maximum occupant load rate indi- | |
| cated in Table 403.3 | |
| .1.1 wh | |
| ere | |
| approved statistical data | |
| documents | |
| the accuracy of an alternate anticipated | |
| occupant load. | |
| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| VENTILATION | |
| 403.1 Ventilation system. | |
| Mechanical ventilation shall be | |
| provided | |
| by a method of supply air and return or exhaust air. The | |
| amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be | |
| prohibited | |
| from producing negative or positive pressure; such pressures shall not r | |
| esult in door opening forces in excess of those indicated | |
| in the | |
| New York City Building Code | |
| and shall not prevent doors from closing as required by the | |
| New York City Building Code | |
| . | |
| The | |
| method | |
| to convey ventilation air shall be designed and installed in ac | |
| cordance with Chapter 6. | |
| 403.2 Outdoor air required. | |
| The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. | |
| Exception: | |
| The minimum required rate of outdoor air may be reduced where the registered design professional demo | |
| nstrates | |
| that an engineered ventilation system is designed in accordance with ASHRAE 62.1 | |
| Indoor Air Quality Procedure | |
| . | |
| 403.2.1 Recirculation of air. | |
| The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that | |
| required by | |
| Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, | |
| except that: | |
| 1. | |
| Ventilation air shall not be recirculated from one dwelling | |
| unit | |
| to another or to dissimilar occupancies. | |
| 2. | |
| Supply air to a | |
| swimming pool and associated deck areas shall not be recirculated unless such air is | |
| dehumidified | |
| to | |
| maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other | |
| uses or occupancies | |
| . | |
| 3. | |
| Where mech | |
| anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be | |
| prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- | |
| culation of air is prohibited, all | |
| air supplied to such spaces shall be exhausted, including any air in excess of that | |
| required by Table 403.3.1.1. | |
| 4. | |
| Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation | |
| is prohibited. Recircula | |
| tion of air that is contained completely within such spaces shall not be prohibited. | |
| 403.2.2 Transfer air. | |
| Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from | |
| occupiable spaces is not prohibited from serving a | |
| s makeup air for required exhaust systems in such spaces as kitchens, | |
| baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide | |
| the flow rates as specified in Section 403.3.1.1. The requir | |
| ed outdoor airflow rates specified in Table 403.3.1.1 shall be | |
| introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. | |
| 403.3 Outdoor air and local exhaust airflow rates. | |
| Buildings that are no | |
| t more than three stories in height above grade plane, | |
| and that (i) are within Occupancy Group R | |
| - | |
| 2 or Occupancy Group R | |
| - | |
| 3, (ii) are adult homes or enriched living housing as | |
| described in Section 308.3.1 of the | |
| New York City Building Code, | |
| within Occupancy | |
| Group I | |
| - | |
| 1 and have 16 occupants or fewer, | |
| or (iii) are community residences or intermediate | |
| - | |
| care facilities as described in Section 308.3.2 of the | |
| New York City Building | |
| Code, | |
| shall be provided with outdoor air and local exhaust in accordance with Section | |
| 403.3.1.1.2. All other buildings intended | |
| to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. | |
| 403.3.1 Reserved. | |
| 403.3.1.1 Outdoor airflow rate. | |
| Ventilation systems shall be designed t | |
| o have the capacity to supply the minimum | |
| outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each | |
| habitable space, the ventilation system shall be designed to deliver the required rate of outdoor | |
| airflow to the breathing | |
| zone. The occupant load utilized for design of the ventilation system shall be | |
| not less than the number | |
| determined | |
| from | |
| the estimated maximum occupant load rate | |
| indicated | |
| in Table 403.3.1.1 | |
| . | |
| Ventilation rates for | |
| occupancies not represented | |
| in Table 403.3.1.1 | |
| shall be those for a listed occupancy classification that is most similar in terms of occupant density, | |
| activities and building construction; or shall be determined by an approved engineering analysis. The ven | |
| tilation system | |
| shall be designed to supply the required rate of ventilation air continuously | |
| during | |
| the period the building is occupied, | |
| except as otherwise stated in other provisions of the code. | |
| With the exception of non | |
| - | |
| tobacco hookah establishments, t | |
| he ventilation rates in Table 403.3.1.1 | |
| are based on the | |
| absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non | |
| - | |
| tobacco hookah | |
| establishment, the ventilation system serving the space shall be designed to provide v | |
| entilation over and above that re- | |
| quired by Table 403.3.1.1 | |
| in accordance with accepted engineering practice. | |
| Exceptions: | |
| 1. | |
| The occupant load is not required to be | |
| determined | |
| based on the estimated maximum occupant load rate indi- | |
| cated in Table 403.3 | |
| .1.1 wh | |
| ere | |
| approved statistical data | |
| documents | |
| the accuracy of an alternate anticipated | |
| occupant load. | |
| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| VENTILATION | |
| 403.1 Ventilation system. | |
| Mechanical ventilation shall be | |
| provided | |
| by a method of supply air and return or exhaust air. The | |
| amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be | |
| prohibited | |
| from producing negative or positive pressure; such pressures shall not r | |
| esult in door opening forces in excess of those indicated | |
| in the | |
| New York City Building Code | |
| and shall not prevent doors from closing as required by the | |
| New York City Building Code | |
| . | |
| The | |
| method | |
| to convey ventilation air shall be designed and installed in ac | |
| cordance with Chapter 6. | |
| 403.2 Outdoor air required. | |
| The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. | |
| Exception: | |
| The minimum required rate of outdoor air may be reduced where the registered design professional demo | |
| nstrates | |
| that an engineered ventilation system is designed in accordance with ASHRAE 62.1 | |
| Indoor Air Quality Procedure | |
| . | |
| 403.2.1 Recirculation of air. | |
| The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that | |
| required by | |
| Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, | |
| except that: | |
| 1. | |
| Ventilation air shall not be recirculated from one dwelling | |
| unit | |
| to another or to dissimilar occupancies. | |
| 2. | |
| Supply air to a | |
| swimming pool and associated deck areas shall not be recirculated unless such air is | |
| dehumidified | |
| to | |
| maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other | |
| uses or occupancies | |
| . | |
| 3. | |
| Where mech | |
| anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be | |
| prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- | |
| culation of air is prohibited, all | |
| air supplied to such spaces shall be exhausted, including any air in excess of that | |
| required by Table 403.3.1.1. | |
| 4. | |
| Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation | |
| is prohibited. Recircula | |
| tion of air that is contained completely within such spaces shall not be prohibited. | |
| 403.2.2 Transfer air. | |
| Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from | |
| occupiable spaces is not prohibited from serving a | |
| s makeup air for required exhaust systems in such spaces as kitchens, | |
| baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide | |
| the flow rates as specified in Section 403.3.1.1. The requir | |
| ed outdoor airflow rates specified in Table 403.3.1.1 shall be | |
| introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. | |
| 403.3 Outdoor air and local exhaust airflow rates. | |
| Buildings that are no | |
| t more than three stories in height above grade plane, | |
| and that (i) are within Occupancy Group R | |
| - | |
| 2 or Occupancy Group R | |
| - | |
| 3, (ii) are adult homes or enriched living housing as | |
| described in Section 308.3.1 of the | |
| New York City Building Code, | |
| within Occupancy | |
| Group I | |
| - | |
| 1 and have 16 occupants or fewer, | |
| or (iii) are community residences or intermediate | |
| - | |
| care facilities as described in Section 308.3.2 of the | |
| New York City Building | |
| Code, | |
| shall be provided with outdoor air and local exhaust in accordance with Section | |
| 403.3.1.1.2. All other buildings intended | |
| to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. | |
| 403.3.1 Reserved. | |
| 403.3.1.1 Outdoor airflow rate. | |
| Ventilation systems shall be designed t | |
| o have the capacity to supply the minimum | |
| outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each | |
| habitable space, the ventilation system shall be designed to deliver the required rate of outdoor | |
| airflow to the breathing | |
| zone. The occupant load utilized for design of the ventilation system shall be | |
| not less than the number | |
| determined | |
| from | |
| the estimated maximum occupant load rate | |
| indicated | |
| in Table 403.3.1.1 | |
| . | |
| Ventilation rates for | |
| occupancies not represented | |
| in Table 403.3.1.1 | |
| shall be those for a listed occupancy classification that is most similar in terms of occupant density, | |
| activities and building construction; or shall be determined by an approved engineering analysis. The ven | |
| tilation system | |
| shall be designed to supply the required rate of ventilation air continuously | |
| during | |
| the period the building is occupied, | |
| except as otherwise stated in other provisions of the code. | |
| With the exception of non | |
| - | |
| tobacco hookah establishments, t | |
| he ventilation rates in Table 403.3.1.1 | |
| are based on the | |
| absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non | |
| - | |
| tobacco hookah | |
| establishment, the ventilation system serving the space shall be designed to provide v | |
| entilation over and above that re- | |
| quired by Table 403.3.1.1 | |
| in accordance with accepted engineering practice. | |
| Exceptions: | |
| 1. | |
| The occupant load is not required to be | |
| determined | |
| based on the estimated maximum occupant load rate indi- | |
| cated in Table 403.3 | |
| .1.1 wh | |
| ere | |
| approved statistical data | |
| documents | |
| the accuracy of an alternate anticipated | |
| occupant load. | |
| VENTILATION | |
| 2. | |
| The occupant load used in computing the required ventilation shall be the maximum number who will occupy | |
| the room or space simultaneously during any 2 | |
| - | |
| hour p | |
| eriod. | |
| 3. | |
| Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air | |
| intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in | |
| accordance with ASHRAE 62.1 a | |
| nd comply with footnote k of Table 403.3.1.1. These conditions include, but | |
| are not limited to: | |
| 3.1. | |
| Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow | |
| requirements will be reset. Note: Examples of | |
| measures for estimating such variations include: occupancy | |
| scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per | |
| person using occupancy sensors such as those based on indoor CO | |
| 2 | |
| concentrations. | |
| 3.2. | |
| Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation | |
| system airflows and temperatures. | |
| 3.3. | |
| A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli | |
| ng or | |
| exhaust air makeup. | |
| TABLE 403.3.1.1 | |
| MINIMUM VENTILATION RATES | |
| OCCUPANCY CLASSIFICATION | |
| OCCUPANT DENSITY | |
| #/1000 FT | |
| 2a | |
| PEOPLE OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE, R | |
| p | |
| CFM/PERSON | |
| AREA OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE R | |
| a | |
| CFM/FT | |
| 2a | |
| EXHAUST | |
| AIRFLOW | |
| RATE | |
| CFM/FT | |
| 2a | |
| Correctional facilities | |
| Booking/waiting | |
| 50 | |
| 7.5 | |
| 0.06 | |
| | |
| Cells | |
| without plumbing fixtures | |
| 25 | |
| 5 | |
| 0.12 | |
| | |
| with plumbing fixtures | |
| g | |
| 25 | |
| 5 | |
| 0.12 | |
| 1.0 | |
| Day room | |
| 30 | |
| 5 | |
| 0.06 | |
| | |
| Correctional facilities | |
| Dining halls | |
| (see food and | |
| beverage service) | |
| — | |
| — | |
| — | |
| — | |
| Guard stations | |
| 15 | |
| 5 | |
| 0.06 | |
| — | |
| Dry cleaners, laundries | |
| Coin | |
| - | |
| operated dry cleaner | |
| 20 | |
| 15 | |
| — | |
| — | |
| Coin | |
| - | |
| operated laundries | |
| 20 | |
| 7.5 | |
| 0.06 | |
| — | |
| Commercial dry cleaner | |
| l | |
| 30 | |
| 30 | |
| — | |
| — | |
| Commercial laundry | |
| 10 | |
| 25 | |
| — | |
| — | |
| Storage, pick up | |
| 30 | |
| 7.5 | |
| 0.12 | |
| — | |
| Education | |
| Art classroom | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.7 | |
| VENTILATION | |
| Auditoriums | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Classrooms (ages 5 | |
| - | |
| 8) | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Classrooms (age 9 plus) | |
| 35 | |
| 10 | |
| 0.12 | |
| — | |
| Computer lab | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Corridors (see public spaces) | |
| — | |
| — | |
| — | |
| — | |
| Day care (through age 4) | |
| 25 | |
| 10 | |
| 0.18 | |
| — | |
| Lecture classroom | |
| 65 | |
| 7.5 | |
| 0.06 | |
| — | |
| Lecture hall (fixed seats) | |
| 150 | |
| 7.5 | |
| 0.06 | |
| — | |
| Locker/dressing rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.25 | |
| Media center | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Multiuse assembly | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Music/theater/dance | |
| 35 | |
| 10 | |
| 0.06 | |
| — | |
| Science laboratories | |
| g, k | |
| 25 | |
| 10 | |
| 0.18 | |
| 1.0 | |
| Sports locker rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.5 | |
| Wood/metal shops | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.5 | |
| Food and beverage service | |
| Bars, cocktail lounges | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Cafeteria, fast food | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Dining rooms | |
| 70 | |
| 7.5 | |
| 0.18 | |
| — | |
| Kitchens (cooking) | |
| b | |
| — | |
| — | |
| — | |
| 0.7 | |
| Non | |
| - | |
| tobacco smoking | |
| establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Hotels, motels, resorts and dormitories | |
| Bathrooms/toilet | |
| | |
| private | |
| g | |
| | |
| | |
| | |
| 25/50 | |
| f | |
| Bedroom/living room | |
| 10 | |
| 5 | |
| 0.06 | |
| | |
| Conference/meeting | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Dormitory sleeping areas | |
| 20 | |
| 5 | |
| 0.06 | |
| | |
| Gambling casinos | |
| 120 | |
| 7.5 | |
| 0.18 | |
| | |
| Lobbies/prefunction | |
| 30 | |
| 7.5 | |
| 0.06 | |
| | |
| Multipurpose assembly | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Laboratories | |
| j | |
| Biological | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| VENTILATION | |
| Chemical | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| Industrial and nonteaching | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Nonproduction chemical labs | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Offices | |
| Conference rooms | |
| 50 | |
| 5 | |
| 0.06 | |
| — | |
| Main entry lobbies | |
| 10 | |
| 5 | |
| 0.06 | |
| — | |
| Office spaces | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Reception areas | |
| 30 | |
| 5 | |
| 0.06 | |
| — | |
| Telephone/data entry | |
| 60 | |
| 5 | |
| 0.06 | |
| | |
| Private dwellings, single and multiple | |
| Garages, common for multiple units | |
| b | |
| — | |
| — | |
| — | |
| 0.75 | |
| Kitchens and Kitchenettes | |
| b | |
| , | |
| m | |
| | |
| | |
| | |
| 25/100 | |
| f | |
| Living areas | |
| c, i | |
| Based upon number of | |
| bedrooms. First bed- | |
| room, 2; each additional | |
| bedroom, 1 | |
| 0.35 ACH but not less | |
| than 15 cfm/person | |
| — | |
| — | |
| Toilet rooms and bathrooms | |
| g | |
| | |
| | |
| | |
| 20/50 | |
| f | |
| Public spaces | |
| Corridors | |
| — | |
| — | |
| 0.06 | |
| — | |
| Courtrooms | |
| 70 | |
| 5 | |
| 0.06 | |
| — | |
| Elevator car | |
| | |
| | |
| | |
| 1.0 | |
| Legislative chambers | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Libraries | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| Museums (childrens) | |
| 40 | |
| 7.5 | |
| 0.12 | |
| | |
| Museums/galleries | |
| 40 | |
| 7.5 | |
| 0.06 | |
| | |
| Places of religious worship | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Public spaces | |
| Shower room (per shower head) | |
| g | |
| — | |
| — | |
| — | |
| 50/20 | |
| f | |
| Toilet rooms | |
| – | |
| public | |
| g | |
| — | |
| — | |
| — | |
| 50/70 | |
| e | |
| VENTILATION | |
| Retail stores, sales floors and | |
| showroom | |
| floors | |
| Dressing rooms | |
| — | |
| — | |
| — | |
| 0.25 | |
| Mall common areas | |
| 40 | |
| 7.5 | |
| 0.06 | |
| — | |
| Sales | |
| 15 | |
| 7.5 | |
| 0.12 | |
| — | |
| Shipping and receiving | |
| — | |
| — | |
| 0.12 | |
| — | |
| Smoking lounges and non | |
| - | |
| tobacco | |
| smoking establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Storage rooms | |
| — | |
| — | |
| 0.12 | |
| — | |
| Warehouses (see storage) | |
| | |
| | |
| | |
| | |
| Specialty shops | |
| Automotive motor | |
| - | |
| fuel dispensing | |
| stations | |
| b | |
| — | |
| — | |
| — | |
| 1.5 | |
| Barber | |
| 25 | |
| 7.5 | |
| 0.06 | |
| 0.5 | |
| Beauty salons (without nail salon | |
| services) | |
| b | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Nail salons | |
| b, h | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Embalming room | |
| b | |
| | |
| | |
| | |
| 2.0 | |
| Pet shops (animal areas) | |
| b | |
| 10 | |
| 7.5 | |
| 0.18 | |
| 0.9 | |
| Supermarkets | |
| 8 | |
| 7.5 | |
| 0.06 | |
| | |
| Sports and amusement | |
| Bowling alleys (seating areas) | |
| 40 | |
| 10 | |
| 0.12 | |
| — | |
| Disco/dance floors | |
| 100 | |
| 20 | |
| 0.06 | |
| — | |
| Game arcades | |
| 20 | |
| 7.5 | |
| 0.18 | |
| | |
| Gym, stadium, arena (play area) | |
| — | |
| — | |
| 0.30 | |
| — | |
| Heath club/aerobics room | |
| 40 | |
| 20 | |
| 0.06 | |
| — | |
| Health | |
| club/weight room | |
| 10 | |
| 20 | |
| 0.06 | |
| — | |
| Ice arenas without combustion engines | |
| — | |
| — | |
| 0.30 | |
| 0.5 | |
| Spectator areas | |
| 150 | |
| 7.5 | |
| 0.06 | |
| | |
| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| VENTILATION | |
| 403.1 Ventilation system. | |
| Mechanical ventilation shall be | |
| provided | |
| by a method of supply air and return or exhaust air. The | |
| amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be | |
| prohibited | |
| from producing negative or positive pressure; such pressures shall not r | |
| esult in door opening forces in excess of those indicated | |
| in the | |
| New York City Building Code | |
| and shall not prevent doors from closing as required by the | |
| New York City Building Code | |
| . | |
| The | |
| method | |
| to convey ventilation air shall be designed and installed in ac | |
| cordance with Chapter 6. | |
| 403.2 Outdoor air required. | |
| The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. | |
| Exception: | |
| The minimum required rate of outdoor air may be reduced where the registered design professional demo | |
| nstrates | |
| that an engineered ventilation system is designed in accordance with ASHRAE 62.1 | |
| Indoor Air Quality Procedure | |
| . | |
| 403.2.1 Recirculation of air. | |
| The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that | |
| required by | |
| Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, | |
| except that: | |
| 1. | |
| Ventilation air shall not be recirculated from one dwelling | |
| unit | |
| to another or to dissimilar occupancies. | |
| 2. | |
| Supply air to a | |
| swimming pool and associated deck areas shall not be recirculated unless such air is | |
| dehumidified | |
| to | |
| maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other | |
| uses or occupancies | |
| . | |
| 3. | |
| Where mech | |
| anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be | |
| prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- | |
| culation of air is prohibited, all | |
| air supplied to such spaces shall be exhausted, including any air in excess of that | |
| required by Table 403.3.1.1. | |
| 4. | |
| Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation | |
| is prohibited. Recircula | |
| tion of air that is contained completely within such spaces shall not be prohibited. | |
| 403.2.2 Transfer air. | |
| Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from | |
| occupiable spaces is not prohibited from serving a | |
| s makeup air for required exhaust systems in such spaces as kitchens, | |
| baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide | |
| the flow rates as specified in Section 403.3.1.1. The requir | |
| ed outdoor airflow rates specified in Table 403.3.1.1 shall be | |
| introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. | |
| 403.3 Outdoor air and local exhaust airflow rates. | |
| Buildings that are no | |
| t more than three stories in height above grade plane, | |
| and that (i) are within Occupancy Group R | |
| - | |
| 2 or Occupancy Group R | |
| - | |
| 3, (ii) are adult homes or enriched living housing as | |
| described in Section 308.3.1 of the | |
| New York City Building Code, | |
| within Occupancy | |
| Group I | |
| - | |
| 1 and have 16 occupants or fewer, | |
| or (iii) are community residences or intermediate | |
| - | |
| care facilities as described in Section 308.3.2 of the | |
| New York City Building | |
| Code, | |
| shall be provided with outdoor air and local exhaust in accordance with Section | |
| 403.3.1.1.2. All other buildings intended | |
| to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. | |
| 403.3.1 Reserved. | |
| 403.3.1.1 Outdoor airflow rate. | |
| Ventilation systems shall be designed t | |
| o have the capacity to supply the minimum | |
| outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each | |
| habitable space, the ventilation system shall be designed to deliver the required rate of outdoor | |
| airflow to the breathing | |
| zone. The occupant load utilized for design of the ventilation system shall be | |
| not less than the number | |
| determined | |
| from | |
| the estimated maximum occupant load rate | |
| indicated | |
| in Table 403.3.1.1 | |
| . | |
| Ventilation rates for | |
| occupancies not represented | |
| in Table 403.3.1.1 | |
| shall be those for a listed occupancy classification that is most similar in terms of occupant density, | |
| activities and building construction; or shall be determined by an approved engineering analysis. The ven | |
| tilation system | |
| shall be designed to supply the required rate of ventilation air continuously | |
| during | |
| the period the building is occupied, | |
| except as otherwise stated in other provisions of the code. | |
| With the exception of non | |
| - | |
| tobacco hookah establishments, t | |
| he ventilation rates in Table 403.3.1.1 | |
| are based on the | |
| absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non | |
| - | |
| tobacco hookah | |
| establishment, the ventilation system serving the space shall be designed to provide v | |
| entilation over and above that re- | |
| quired by Table 403.3.1.1 | |
| in accordance with accepted engineering practice. | |
| Exceptions: | |
| 1. | |
| The occupant load is not required to be | |
| determined | |
| based on the estimated maximum occupant load rate indi- | |
| cated in Table 403.3 | |
| .1.1 wh | |
| ere | |
| approved statistical data | |
| documents | |
| the accuracy of an alternate anticipated | |
| occupant load. | |
| VENTILATION | |
| 2. | |
| The occupant load used in computing the required ventilation shall be the maximum number who will occupy | |
| the room or space simultaneously during any 2 | |
| - | |
| hour p | |
| eriod. | |
| 3. | |
| Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air | |
| intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in | |
| accordance with ASHRAE 62.1 a | |
| nd comply with footnote k of Table 403.3.1.1. These conditions include, but | |
| are not limited to: | |
| 3.1. | |
| Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow | |
| requirements will be reset. Note: Examples of | |
| measures for estimating such variations include: occupancy | |
| scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per | |
| person using occupancy sensors such as those based on indoor CO | |
| 2 | |
| concentrations. | |
| 3.2. | |
| Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation | |
| system airflows and temperatures. | |
| 3.3. | |
| A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli | |
| ng or | |
| exhaust air makeup. | |
| TABLE 403.3.1.1 | |
| MINIMUM VENTILATION RATES | |
| OCCUPANCY CLASSIFICATION | |
| OCCUPANT DENSITY | |
| #/1000 FT | |
| 2a | |
| PEOPLE OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE, R | |
| p | |
| CFM/PERSON | |
| AREA OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE R | |
| a | |
| CFM/FT | |
| 2a | |
| EXHAUST | |
| AIRFLOW | |
| RATE | |
| CFM/FT | |
| 2a | |
| Correctional facilities | |
| Booking/waiting | |
| 50 | |
| 7.5 | |
| 0.06 | |
| | |
| Cells | |
| without plumbing fixtures | |
| 25 | |
| 5 | |
| 0.12 | |
| | |
| with plumbing fixtures | |
| g | |
| 25 | |
| 5 | |
| 0.12 | |
| 1.0 | |
| Day room | |
| 30 | |
| 5 | |
| 0.06 | |
| | |
| Correctional facilities | |
| Dining halls | |
| (see food and | |
| beverage service) | |
| — | |
| — | |
| — | |
| — | |
| Guard stations | |
| 15 | |
| 5 | |
| 0.06 | |
| — | |
| Dry cleaners, laundries | |
| Coin | |
| - | |
| operated dry cleaner | |
| 20 | |
| 15 | |
| — | |
| — | |
| Coin | |
| - | |
| operated laundries | |
| 20 | |
| 7.5 | |
| 0.06 | |
| — | |
| Commercial dry cleaner | |
| l | |
| 30 | |
| 30 | |
| — | |
| — | |
| Commercial laundry | |
| 10 | |
| 25 | |
| — | |
| — | |
| Storage, pick up | |
| 30 | |
| 7.5 | |
| 0.12 | |
| — | |
| Education | |
| Art classroom | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.7 | |
| VENTILATION | |
| Auditoriums | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Classrooms (ages 5 | |
| - | |
| 8) | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Classrooms (age 9 plus) | |
| 35 | |
| 10 | |
| 0.12 | |
| — | |
| Computer lab | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Corridors (see public spaces) | |
| — | |
| — | |
| — | |
| — | |
| Day care (through age 4) | |
| 25 | |
| 10 | |
| 0.18 | |
| — | |
| Lecture classroom | |
| 65 | |
| 7.5 | |
| 0.06 | |
| — | |
| Lecture hall (fixed seats) | |
| 150 | |
| 7.5 | |
| 0.06 | |
| — | |
| Locker/dressing rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.25 | |
| Media center | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Multiuse assembly | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Music/theater/dance | |
| 35 | |
| 10 | |
| 0.06 | |
| — | |
| Science laboratories | |
| g, k | |
| 25 | |
| 10 | |
| 0.18 | |
| 1.0 | |
| Sports locker rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.5 | |
| Wood/metal shops | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.5 | |
| Food and beverage service | |
| Bars, cocktail lounges | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Cafeteria, fast food | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Dining rooms | |
| 70 | |
| 7.5 | |
| 0.18 | |
| — | |
| Kitchens (cooking) | |
| b | |
| — | |
| — | |
| — | |
| 0.7 | |
| Non | |
| - | |
| tobacco smoking | |
| establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Hotels, motels, resorts and dormitories | |
| Bathrooms/toilet | |
| | |
| private | |
| g | |
| | |
| | |
| | |
| 25/50 | |
| f | |
| Bedroom/living room | |
| 10 | |
| 5 | |
| 0.06 | |
| | |
| Conference/meeting | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Dormitory sleeping areas | |
| 20 | |
| 5 | |
| 0.06 | |
| | |
| Gambling casinos | |
| 120 | |
| 7.5 | |
| 0.18 | |
| | |
| Lobbies/prefunction | |
| 30 | |
| 7.5 | |
| 0.06 | |
| | |
| Multipurpose assembly | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Laboratories | |
| j | |
| Biological | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| VENTILATION | |
| Chemical | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| Industrial and nonteaching | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Nonproduction chemical labs | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Offices | |
| Conference rooms | |
| 50 | |
| 5 | |
| 0.06 | |
| — | |
| Main entry lobbies | |
| 10 | |
| 5 | |
| 0.06 | |
| — | |
| Office spaces | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Reception areas | |
| 30 | |
| 5 | |
| 0.06 | |
| — | |
| Telephone/data entry | |
| 60 | |
| 5 | |
| 0.06 | |
| | |
| Private dwellings, single and multiple | |
| Garages, common for multiple units | |
| b | |
| — | |
| — | |
| — | |
| 0.75 | |
| Kitchens and Kitchenettes | |
| b | |
| , | |
| m | |
| | |
| | |
| | |
| 25/100 | |
| f | |
| Living areas | |
| c, i | |
| Based upon number of | |
| bedrooms. First bed- | |
| room, 2; each additional | |
| bedroom, 1 | |
| 0.35 ACH but not less | |
| than 15 cfm/person | |
| — | |
| — | |
| Toilet rooms and bathrooms | |
| g | |
| | |
| | |
| | |
| 20/50 | |
| f | |
| Public spaces | |
| Corridors | |
| — | |
| — | |
| 0.06 | |
| — | |
| Courtrooms | |
| 70 | |
| 5 | |
| 0.06 | |
| — | |
| Elevator car | |
| | |
| | |
| | |
| 1.0 | |
| Legislative chambers | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Libraries | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| Museums (childrens) | |
| 40 | |
| 7.5 | |
| 0.12 | |
| | |
| Museums/galleries | |
| 40 | |
| 7.5 | |
| 0.06 | |
| | |
| Places of religious worship | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Public spaces | |
| Shower room (per shower head) | |
| g | |
| — | |
| — | |
| — | |
| 50/20 | |
| f | |
| Toilet rooms | |
| – | |
| public | |
| g | |
| — | |
| — | |
| — | |
| 50/70 | |
| e | |
| VENTILATION | |
| Retail stores, sales floors and | |
| showroom | |
| floors | |
| Dressing rooms | |
| — | |
| — | |
| — | |
| 0.25 | |
| Mall common areas | |
| 40 | |
| 7.5 | |
| 0.06 | |
| — | |
| Sales | |
| 15 | |
| 7.5 | |
| 0.12 | |
| — | |
| Shipping and receiving | |
| — | |
| — | |
| 0.12 | |
| — | |
| Smoking lounges and non | |
| - | |
| tobacco | |
| smoking establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Storage rooms | |
| — | |
| — | |
| 0.12 | |
| — | |
| Warehouses (see storage) | |
| | |
| | |
| | |
| | |
| Specialty shops | |
| Automotive motor | |
| - | |
| fuel dispensing | |
| stations | |
| b | |
| — | |
| — | |
| — | |
| 1.5 | |
| Barber | |
| 25 | |
| 7.5 | |
| 0.06 | |
| 0.5 | |
| Beauty salons (without nail salon | |
| services) | |
| b | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Nail salons | |
| b, h | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Embalming room | |
| b | |
| | |
| | |
| | |
| 2.0 | |
| Pet shops (animal areas) | |
| b | |
| 10 | |
| 7.5 | |
| 0.18 | |
| 0.9 | |
| Supermarkets | |
| 8 | |
| 7.5 | |
| 0.06 | |
| | |
| Sports and amusement | |
| Bowling alleys (seating areas) | |
| 40 | |
| 10 | |
| 0.12 | |
| — | |
| Disco/dance floors | |
| 100 | |
| 20 | |
| 0.06 | |
| — | |
| Game arcades | |
| 20 | |
| 7.5 | |
| 0.18 | |
| | |
| Gym, stadium, arena (play area) | |
| — | |
| — | |
| 0.30 | |
| — | |
| Heath club/aerobics room | |
| 40 | |
| 20 | |
| 0.06 | |
| — | |
| Health | |
| club/weight room | |
| 10 | |
| 20 | |
| 0.06 | |
| — | |
| Ice arenas without combustion engines | |
| — | |
| — | |
| 0.30 | |
| 0.5 | |
| Spectator areas | |
| 150 | |
| 7.5 | |
| 0.06 | |
| | |
| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| VENTILATION | |
| 403.1 Ventilation system. | |
| Mechanical ventilation shall be | |
| provided | |
| by a method of supply air and return or exhaust air. The | |
| amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be | |
| prohibited | |
| from producing negative or positive pressure; such pressures shall not r | |
| esult in door opening forces in excess of those indicated | |
| in the | |
| New York City Building Code | |
| and shall not prevent doors from closing as required by the | |
| New York City Building Code | |
| . | |
| The | |
| method | |
| to convey ventilation air shall be designed and installed in ac | |
| cordance with Chapter 6. | |
| 403.2 Outdoor air required. | |
| The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. | |
| Exception: | |
| The minimum required rate of outdoor air may be reduced where the registered design professional demo | |
| nstrates | |
| that an engineered ventilation system is designed in accordance with ASHRAE 62.1 | |
| Indoor Air Quality Procedure | |
| . | |
| 403.2.1 Recirculation of air. | |
| The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that | |
| required by | |
| Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, | |
| except that: | |
| 1. | |
| Ventilation air shall not be recirculated from one dwelling | |
| unit | |
| to another or to dissimilar occupancies. | |
| 2. | |
| Supply air to a | |
| swimming pool and associated deck areas shall not be recirculated unless such air is | |
| dehumidified | |
| to | |
| maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other | |
| uses or occupancies | |
| . | |
| 3. | |
| Where mech | |
| anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be | |
| prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- | |
| culation of air is prohibited, all | |
| air supplied to such spaces shall be exhausted, including any air in excess of that | |
| required by Table 403.3.1.1. | |
| 4. | |
| Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation | |
| is prohibited. Recircula | |
| tion of air that is contained completely within such spaces shall not be prohibited. | |
| 403.2.2 Transfer air. | |
| Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from | |
| occupiable spaces is not prohibited from serving a | |
| s makeup air for required exhaust systems in such spaces as kitchens, | |
| baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide | |
| the flow rates as specified in Section 403.3.1.1. The requir | |
| ed outdoor airflow rates specified in Table 403.3.1.1 shall be | |
| introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. | |
| 403.3 Outdoor air and local exhaust airflow rates. | |
| Buildings that are no | |
| t more than three stories in height above grade plane, | |
| and that (i) are within Occupancy Group R | |
| - | |
| 2 or Occupancy Group R | |
| - | |
| 3, (ii) are adult homes or enriched living housing as | |
| described in Section 308.3.1 of the | |
| New York City Building Code, | |
| within Occupancy | |
| Group I | |
| - | |
| 1 and have 16 occupants or fewer, | |
| or (iii) are community residences or intermediate | |
| - | |
| care facilities as described in Section 308.3.2 of the | |
| New York City Building | |
| Code, | |
| shall be provided with outdoor air and local exhaust in accordance with Section | |
| 403.3.1.1.2. All other buildings intended | |
| to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. | |
| 403.3.1 Reserved. | |
| 403.3.1.1 Outdoor airflow rate. | |
| Ventilation systems shall be designed t | |
| o have the capacity to supply the minimum | |
| outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each | |
| habitable space, the ventilation system shall be designed to deliver the required rate of outdoor | |
| airflow to the breathing | |
| zone. The occupant load utilized for design of the ventilation system shall be | |
| not less than the number | |
| determined | |
| from | |
| the estimated maximum occupant load rate | |
| indicated | |
| in Table 403.3.1.1 | |
| . | |
| Ventilation rates for | |
| occupancies not represented | |
| in Table 403.3.1.1 | |
| shall be those for a listed occupancy classification that is most similar in terms of occupant density, | |
| activities and building construction; or shall be determined by an approved engineering analysis. The ven | |
| tilation system | |
| shall be designed to supply the required rate of ventilation air continuously | |
| during | |
| the period the building is occupied, | |
| except as otherwise stated in other provisions of the code. | |
| With the exception of non | |
| - | |
| tobacco hookah establishments, t | |
| he ventilation rates in Table 403.3.1.1 | |
| are based on the | |
| absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non | |
| - | |
| tobacco hookah | |
| establishment, the ventilation system serving the space shall be designed to provide v | |
| entilation over and above that re- | |
| quired by Table 403.3.1.1 | |
| in accordance with accepted engineering practice. | |
| Exceptions: | |
| 1. | |
| The occupant load is not required to be | |
| determined | |
| based on the estimated maximum occupant load rate indi- | |
| cated in Table 403.3 | |
| .1.1 wh | |
| ere | |
| approved statistical data | |
| documents | |
| the accuracy of an alternate anticipated | |
| occupant load. | |
| VENTILATION | |
| 2. | |
| The occupant load used in computing the required ventilation shall be the maximum number who will occupy | |
| the room or space simultaneously during any 2 | |
| - | |
| hour p | |
| eriod. | |
| 3. | |
| Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air | |
| intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in | |
| accordance with ASHRAE 62.1 a | |
| nd comply with footnote k of Table 403.3.1.1. These conditions include, but | |
| are not limited to: | |
| 3.1. | |
| Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow | |
| requirements will be reset. Note: Examples of | |
| measures for estimating such variations include: occupancy | |
| scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per | |
| person using occupancy sensors such as those based on indoor CO | |
| 2 | |
| concentrations. | |
| 3.2. | |
| Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation | |
| system airflows and temperatures. | |
| 3.3. | |
| A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli | |
| ng or | |
| exhaust air makeup. | |
| TABLE 403.3.1.1 | |
| MINIMUM VENTILATION RATES | |
| OCCUPANCY CLASSIFICATION | |
| OCCUPANT DENSITY | |
| #/1000 FT | |
| 2a | |
| PEOPLE OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE, R | |
| p | |
| CFM/PERSON | |
| AREA OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE R | |
| a | |
| CFM/FT | |
| 2a | |
| EXHAUST | |
| AIRFLOW | |
| RATE | |
| CFM/FT | |
| 2a | |
| Correctional facilities | |
| Booking/waiting | |
| 50 | |
| 7.5 | |
| 0.06 | |
| | |
| Cells | |
| without plumbing fixtures | |
| 25 | |
| 5 | |
| 0.12 | |
| | |
| with plumbing fixtures | |
| g | |
| 25 | |
| 5 | |
| 0.12 | |
| 1.0 | |
| Day room | |
| 30 | |
| 5 | |
| 0.06 | |
| | |
| Correctional facilities | |
| Dining halls | |
| (see food and | |
| beverage service) | |
| — | |
| — | |
| — | |
| — | |
| Guard stations | |
| 15 | |
| 5 | |
| 0.06 | |
| — | |
| Dry cleaners, laundries | |
| Coin | |
| - | |
| operated dry cleaner | |
| 20 | |
| 15 | |
| — | |
| — | |
| Coin | |
| - | |
| operated laundries | |
| 20 | |
| 7.5 | |
| 0.06 | |
| — | |
| Commercial dry cleaner | |
| l | |
| 30 | |
| 30 | |
| — | |
| — | |
| Commercial laundry | |
| 10 | |
| 25 | |
| — | |
| — | |
| Storage, pick up | |
| 30 | |
| 7.5 | |
| 0.12 | |
| — | |
| Education | |
| Art classroom | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.7 | |
| VENTILATION | |
| Auditoriums | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Classrooms (ages 5 | |
| - | |
| 8) | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Classrooms (age 9 plus) | |
| 35 | |
| 10 | |
| 0.12 | |
| — | |
| Computer lab | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Corridors (see public spaces) | |
| — | |
| — | |
| — | |
| — | |
| Day care (through age 4) | |
| 25 | |
| 10 | |
| 0.18 | |
| — | |
| Lecture classroom | |
| 65 | |
| 7.5 | |
| 0.06 | |
| — | |
| Lecture hall (fixed seats) | |
| 150 | |
| 7.5 | |
| 0.06 | |
| — | |
| Locker/dressing rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.25 | |
| Media center | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Multiuse assembly | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Music/theater/dance | |
| 35 | |
| 10 | |
| 0.06 | |
| — | |
| Science laboratories | |
| g, k | |
| 25 | |
| 10 | |
| 0.18 | |
| 1.0 | |
| Sports locker rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.5 | |
| Wood/metal shops | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.5 | |
| Food and beverage service | |
| Bars, cocktail lounges | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Cafeteria, fast food | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Dining rooms | |
| 70 | |
| 7.5 | |
| 0.18 | |
| — | |
| Kitchens (cooking) | |
| b | |
| — | |
| — | |
| — | |
| 0.7 | |
| Non | |
| - | |
| tobacco smoking | |
| establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Hotels, motels, resorts and dormitories | |
| Bathrooms/toilet | |
| | |
| private | |
| g | |
| | |
| | |
| | |
| 25/50 | |
| f | |
| Bedroom/living room | |
| 10 | |
| 5 | |
| 0.06 | |
| | |
| Conference/meeting | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Dormitory sleeping areas | |
| 20 | |
| 5 | |
| 0.06 | |
| | |
| Gambling casinos | |
| 120 | |
| 7.5 | |
| 0.18 | |
| | |
| Lobbies/prefunction | |
| 30 | |
| 7.5 | |
| 0.06 | |
| | |
| Multipurpose assembly | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Laboratories | |
| j | |
| Biological | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| VENTILATION | |
| Chemical | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| Industrial and nonteaching | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Nonproduction chemical labs | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Offices | |
| Conference rooms | |
| 50 | |
| 5 | |
| 0.06 | |
| — | |
| Main entry lobbies | |
| 10 | |
| 5 | |
| 0.06 | |
| — | |
| Office spaces | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Reception areas | |
| 30 | |
| 5 | |
| 0.06 | |
| — | |
| Telephone/data entry | |
| 60 | |
| 5 | |
| 0.06 | |
| | |
| Private dwellings, single and multiple | |
| Garages, common for multiple units | |
| b | |
| — | |
| — | |
| — | |
| 0.75 | |
| Kitchens and Kitchenettes | |
| b | |
| , | |
| m | |
| | |
| | |
| | |
| 25/100 | |
| f | |
| Living areas | |
| c, i | |
| Based upon number of | |
| bedrooms. First bed- | |
| room, 2; each additional | |
| bedroom, 1 | |
| 0.35 ACH but not less | |
| than 15 cfm/person | |
| — | |
| — | |
| Toilet rooms and bathrooms | |
| g | |
| | |
| | |
| | |
| 20/50 | |
| f | |
| Public spaces | |
| Corridors | |
| — | |
| — | |
| 0.06 | |
| — | |
| Courtrooms | |
| 70 | |
| 5 | |
| 0.06 | |
| — | |
| Elevator car | |
| | |
| | |
| | |
| 1.0 | |
| Legislative chambers | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Libraries | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| Museums (childrens) | |
| 40 | |
| 7.5 | |
| 0.12 | |
| | |
| Museums/galleries | |
| 40 | |
| 7.5 | |
| 0.06 | |
| | |
| Places of religious worship | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Public spaces | |
| Shower room (per shower head) | |
| g | |
| — | |
| — | |
| — | |
| 50/20 | |
| f | |
| Toilet rooms | |
| – | |
| public | |
| g | |
| — | |
| — | |
| — | |
| 50/70 | |
| e | |
| VENTILATION | |
| Retail stores, sales floors and | |
| showroom | |
| floors | |
| Dressing rooms | |
| — | |
| — | |
| — | |
| 0.25 | |
| Mall common areas | |
| 40 | |
| 7.5 | |
| 0.06 | |
| — | |
| Sales | |
| 15 | |
| 7.5 | |
| 0.12 | |
| — | |
| Shipping and receiving | |
| — | |
| — | |
| 0.12 | |
| — | |
| Smoking lounges and non | |
| - | |
| tobacco | |
| smoking establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Storage rooms | |
| — | |
| — | |
| 0.12 | |
| — | |
| Warehouses (see storage) | |
| | |
| | |
| | |
| | |
| Specialty shops | |
| Automotive motor | |
| - | |
| fuel dispensing | |
| stations | |
| b | |
| — | |
| — | |
| — | |
| 1.5 | |
| Barber | |
| 25 | |
| 7.5 | |
| 0.06 | |
| 0.5 | |
| Beauty salons (without nail salon | |
| services) | |
| b | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Nail salons | |
| b, h | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Embalming room | |
| b | |
| | |
| | |
| | |
| 2.0 | |
| Pet shops (animal areas) | |
| b | |
| 10 | |
| 7.5 | |
| 0.18 | |
| 0.9 | |
| Supermarkets | |
| 8 | |
| 7.5 | |
| 0.06 | |
| | |
| Sports and amusement | |
| Bowling alleys (seating areas) | |
| 40 | |
| 10 | |
| 0.12 | |
| — | |
| Disco/dance floors | |
| 100 | |
| 20 | |
| 0.06 | |
| — | |
| Game arcades | |
| 20 | |
| 7.5 | |
| 0.18 | |
| | |
| Gym, stadium, arena (play area) | |
| — | |
| — | |
| 0.30 | |
| — | |
| Heath club/aerobics room | |
| 40 | |
| 20 | |
| 0.06 | |
| — | |
| Health | |
| club/weight room | |
| 10 | |
| 20 | |
| 0.06 | |
| — | |
| Ice arenas without combustion engines | |
| — | |
| — | |
| 0.30 | |
| 0.5 | |
| Spectator areas | |
| 150 | |
| 7.5 | |
| 0.06 | |
| | |
| VENTILATION | |
| Swimming pools (pool and deck area) | |
| — | |
| — | |
| 0.48 | |
| — | |
| Storage | |
| Repair garages, enclosed parking | |
| garages | |
| b, d | |
| | |
| | |
| | |
| 0.75 | |
| Warehouses | |
| | |
| | |
| 0.06 | |
| | |
| Theaters | |
| Auditoriums (see education) | |
| — | |
| — | |
| — | |
| — | |
| Lobbies | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Stages, studios | |
| 70 | |
| 10 | |
| 0.06 | |
| | |
| Ticket booths | |
| 60 | |
| 5 | |
| 0.06 | |
| — | |
| Transportation | |
| Platforms | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Transportation waiting | |
| 100 | |
| 7.5 | |
| 0.06 | |
| | |
| Workrooms | |
| Bank vaults/safe deposit | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Computer (without printing) | |
| 4 | |
| 5 | |
| 0.06 | |
| — | |
| Copy, printing rooms | |
| 4 | |
| 5 | |
| 0.06 | |
| 0.5 | |
| Darkrooms | |
| | |
| | |
| | |
| 1.0 | |
| Meat processing | |
| c | |
| 10 | |
| 15 | |
| — | |
| — | |
| Pharmacy (prep. area) | |
| 10 | |
| 5 | |
| 0.18 | |
| | |
| Photo studios | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| For SI: 1 cubic foot per | |
| minute = 0.0004719 m | |
| 3 | |
| /s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508m | |
| 3 | |
| /(s • m | |
| 2 | |
| ), | |
| °C = ((°F) | |
| - | |
| 32) | |
| / | |
| 1.8, | |
| 1 square foot = 0.0929 m | |
| 2 | |
| . | |
| a. | |
| Based upon net occupiable floor area. | |
| b. | |
| Mechanical exhaust required and the | |
| recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3). | |
| c. | |
| Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous. | |
| d. | |
| Ventilation systems in enclosed parking garages sh | |
| all comply with Section 404. | |
| e. | |
| Rates are per water closet or urinal. The higher rate shall be provided where | |
| the exhaust system is designed to operate intermittently. The lower rate | |
| shall be permitted only where the exhaust system is designed to operate | |
| continuously while the space served by the toilet facilities is occupied. | |
| f. | |
| Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to oper | |
| ate intermittently. The | |
| lower rate shall | |
| be permitted | |
| only where the exhaust system is designed to operate continuously while the dwelling unit or sleeping unit served by | |
| the toilet facility is occupied. | |
| g. | |
| Mechanical exhaust is required and recirculation from such spaces is prohibited (see Section 403.2.1, | |
| Item 4). | |
| h. | |
| For nail salons, | |
| each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm | |
| per | |
| station. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more re | |
| quired source capture systems operate | |
| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| VENTILATION | |
| 403.1 Ventilation system. | |
| Mechanical ventilation shall be | |
| provided | |
| by a method of supply air and return or exhaust air. The | |
| amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be | |
| prohibited | |
| from producing negative or positive pressure; such pressures shall not r | |
| esult in door opening forces in excess of those indicated | |
| in the | |
| New York City Building Code | |
| and shall not prevent doors from closing as required by the | |
| New York City Building Code | |
| . | |
| The | |
| method | |
| to convey ventilation air shall be designed and installed in ac | |
| cordance with Chapter 6. | |
| 403.2 Outdoor air required. | |
| The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. | |
| Exception: | |
| The minimum required rate of outdoor air may be reduced where the registered design professional demo | |
| nstrates | |
| that an engineered ventilation system is designed in accordance with ASHRAE 62.1 | |
| Indoor Air Quality Procedure | |
| . | |
| 403.2.1 Recirculation of air. | |
| The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that | |
| required by | |
| Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, | |
| except that: | |
| 1. | |
| Ventilation air shall not be recirculated from one dwelling | |
| unit | |
| to another or to dissimilar occupancies. | |
| 2. | |
| Supply air to a | |
| swimming pool and associated deck areas shall not be recirculated unless such air is | |
| dehumidified | |
| to | |
| maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other | |
| uses or occupancies | |
| . | |
| 3. | |
| Where mech | |
| anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be | |
| prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- | |
| culation of air is prohibited, all | |
| air supplied to such spaces shall be exhausted, including any air in excess of that | |
| required by Table 403.3.1.1. | |
| 4. | |
| Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation | |
| is prohibited. Recircula | |
| tion of air that is contained completely within such spaces shall not be prohibited. | |
| 403.2.2 Transfer air. | |
| Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from | |
| occupiable spaces is not prohibited from serving a | |
| s makeup air for required exhaust systems in such spaces as kitchens, | |
| baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide | |
| the flow rates as specified in Section 403.3.1.1. The requir | |
| ed outdoor airflow rates specified in Table 403.3.1.1 shall be | |
| introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. | |
| 403.3 Outdoor air and local exhaust airflow rates. | |
| Buildings that are no | |
| t more than three stories in height above grade plane, | |
| and that (i) are within Occupancy Group R | |
| - | |
| 2 or Occupancy Group R | |
| - | |
| 3, (ii) are adult homes or enriched living housing as | |
| described in Section 308.3.1 of the | |
| New York City Building Code, | |
| within Occupancy | |
| Group I | |
| - | |
| 1 and have 16 occupants or fewer, | |
| or (iii) are community residences or intermediate | |
| - | |
| care facilities as described in Section 308.3.2 of the | |
| New York City Building | |
| Code, | |
| shall be provided with outdoor air and local exhaust in accordance with Section | |
| 403.3.1.1.2. All other buildings intended | |
| to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. | |
| 403.3.1 Reserved. | |
| 403.3.1.1 Outdoor airflow rate. | |
| Ventilation systems shall be designed t | |
| o have the capacity to supply the minimum | |
| outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each | |
| habitable space, the ventilation system shall be designed to deliver the required rate of outdoor | |
| airflow to the breathing | |
| zone. The occupant load utilized for design of the ventilation system shall be | |
| not less than the number | |
| determined | |
| from | |
| the estimated maximum occupant load rate | |
| indicated | |
| in Table 403.3.1.1 | |
| . | |
| Ventilation rates for | |
| occupancies not represented | |
| in Table 403.3.1.1 | |
| shall be those for a listed occupancy classification that is most similar in terms of occupant density, | |
| activities and building construction; or shall be determined by an approved engineering analysis. The ven | |
| tilation system | |
| shall be designed to supply the required rate of ventilation air continuously | |
| during | |
| the period the building is occupied, | |
| except as otherwise stated in other provisions of the code. | |
| With the exception of non | |
| - | |
| tobacco hookah establishments, t | |
| he ventilation rates in Table 403.3.1.1 | |
| are based on the | |
| absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non | |
| - | |
| tobacco hookah | |
| establishment, the ventilation system serving the space shall be designed to provide v | |
| entilation over and above that re- | |
| quired by Table 403.3.1.1 | |
| in accordance with accepted engineering practice. | |
| Exceptions: | |
| 1. | |
| The occupant load is not required to be | |
| determined | |
| based on the estimated maximum occupant load rate indi- | |
| cated in Table 403.3 | |
| .1.1 wh | |
| ere | |
| approved statistical data | |
| documents | |
| the accuracy of an alternate anticipated | |
| occupant load. | |
| VENTILATION | |
| 2. | |
| The occupant load used in computing the required ventilation shall be the maximum number who will occupy | |
| the room or space simultaneously during any 2 | |
| - | |
| hour p | |
| eriod. | |
| 3. | |
| Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air | |
| intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in | |
| accordance with ASHRAE 62.1 a | |
| nd comply with footnote k of Table 403.3.1.1. These conditions include, but | |
| are not limited to: | |
| 3.1. | |
| Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow | |
| requirements will be reset. Note: Examples of | |
| measures for estimating such variations include: occupancy | |
| scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per | |
| person using occupancy sensors such as those based on indoor CO | |
| 2 | |
| concentrations. | |
| 3.2. | |
| Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation | |
| system airflows and temperatures. | |
| 3.3. | |
| A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli | |
| ng or | |
| exhaust air makeup. | |
| TABLE 403.3.1.1 | |
| MINIMUM VENTILATION RATES | |
| OCCUPANCY CLASSIFICATION | |
| OCCUPANT DENSITY | |
| #/1000 FT | |
| 2a | |
| PEOPLE OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE, R | |
| p | |
| CFM/PERSON | |
| AREA OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE R | |
| a | |
| CFM/FT | |
| 2a | |
| EXHAUST | |
| AIRFLOW | |
| RATE | |
| CFM/FT | |
| 2a | |
| Correctional facilities | |
| Booking/waiting | |
| 50 | |
| 7.5 | |
| 0.06 | |
| | |
| Cells | |
| without plumbing fixtures | |
| 25 | |
| 5 | |
| 0.12 | |
| | |
| with plumbing fixtures | |
| g | |
| 25 | |
| 5 | |
| 0.12 | |
| 1.0 | |
| Day room | |
| 30 | |
| 5 | |
| 0.06 | |
| | |
| Correctional facilities | |
| Dining halls | |
| (see food and | |
| beverage service) | |
| — | |
| — | |
| — | |
| — | |
| Guard stations | |
| 15 | |
| 5 | |
| 0.06 | |
| — | |
| Dry cleaners, laundries | |
| Coin | |
| - | |
| operated dry cleaner | |
| 20 | |
| 15 | |
| — | |
| — | |
| Coin | |
| - | |
| operated laundries | |
| 20 | |
| 7.5 | |
| 0.06 | |
| — | |
| Commercial dry cleaner | |
| l | |
| 30 | |
| 30 | |
| — | |
| — | |
| Commercial laundry | |
| 10 | |
| 25 | |
| — | |
| — | |
| Storage, pick up | |
| 30 | |
| 7.5 | |
| 0.12 | |
| — | |
| Education | |
| Art classroom | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.7 | |
| VENTILATION | |
| Auditoriums | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Classrooms (ages 5 | |
| - | |
| 8) | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Classrooms (age 9 plus) | |
| 35 | |
| 10 | |
| 0.12 | |
| — | |
| Computer lab | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Corridors (see public spaces) | |
| — | |
| — | |
| — | |
| — | |
| Day care (through age 4) | |
| 25 | |
| 10 | |
| 0.18 | |
| — | |
| Lecture classroom | |
| 65 | |
| 7.5 | |
| 0.06 | |
| — | |
| Lecture hall (fixed seats) | |
| 150 | |
| 7.5 | |
| 0.06 | |
| — | |
| Locker/dressing rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.25 | |
| Media center | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Multiuse assembly | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Music/theater/dance | |
| 35 | |
| 10 | |
| 0.06 | |
| — | |
| Science laboratories | |
| g, k | |
| 25 | |
| 10 | |
| 0.18 | |
| 1.0 | |
| Sports locker rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.5 | |
| Wood/metal shops | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.5 | |
| Food and beverage service | |
| Bars, cocktail lounges | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Cafeteria, fast food | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Dining rooms | |
| 70 | |
| 7.5 | |
| 0.18 | |
| — | |
| Kitchens (cooking) | |
| b | |
| — | |
| — | |
| — | |
| 0.7 | |
| Non | |
| - | |
| tobacco smoking | |
| establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Hotels, motels, resorts and dormitories | |
| Bathrooms/toilet | |
| | |
| private | |
| g | |
| | |
| | |
| | |
| 25/50 | |
| f | |
| Bedroom/living room | |
| 10 | |
| 5 | |
| 0.06 | |
| | |
| Conference/meeting | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Dormitory sleeping areas | |
| 20 | |
| 5 | |
| 0.06 | |
| | |
| Gambling casinos | |
| 120 | |
| 7.5 | |
| 0.18 | |
| | |
| Lobbies/prefunction | |
| 30 | |
| 7.5 | |
| 0.06 | |
| | |
| Multipurpose assembly | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Laboratories | |
| j | |
| Biological | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| VENTILATION | |
| Chemical | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| Industrial and nonteaching | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Nonproduction chemical labs | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Offices | |
| Conference rooms | |
| 50 | |
| 5 | |
| 0.06 | |
| — | |
| Main entry lobbies | |
| 10 | |
| 5 | |
| 0.06 | |
| — | |
| Office spaces | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Reception areas | |
| 30 | |
| 5 | |
| 0.06 | |
| — | |
| Telephone/data entry | |
| 60 | |
| 5 | |
| 0.06 | |
| | |
| Private dwellings, single and multiple | |
| Garages, common for multiple units | |
| b | |
| — | |
| — | |
| — | |
| 0.75 | |
| Kitchens and Kitchenettes | |
| b | |
| , | |
| m | |
| | |
| | |
| | |
| 25/100 | |
| f | |
| Living areas | |
| c, i | |
| Based upon number of | |
| bedrooms. First bed- | |
| room, 2; each additional | |
| bedroom, 1 | |
| 0.35 ACH but not less | |
| than 15 cfm/person | |
| — | |
| — | |
| Toilet rooms and bathrooms | |
| g | |
| | |
| | |
| | |
| 20/50 | |
| f | |
| Public spaces | |
| Corridors | |
| — | |
| — | |
| 0.06 | |
| — | |
| Courtrooms | |
| 70 | |
| 5 | |
| 0.06 | |
| — | |
| Elevator car | |
| | |
| | |
| | |
| 1.0 | |
| Legislative chambers | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Libraries | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| Museums (childrens) | |
| 40 | |
| 7.5 | |
| 0.12 | |
| | |
| Museums/galleries | |
| 40 | |
| 7.5 | |
| 0.06 | |
| | |
| Places of religious worship | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Public spaces | |
| Shower room (per shower head) | |
| g | |
| — | |
| — | |
| — | |
| 50/20 | |
| f | |
| Toilet rooms | |
| – | |
| public | |
| g | |
| — | |
| — | |
| — | |
| 50/70 | |
| e | |
| VENTILATION | |
| Retail stores, sales floors and | |
| showroom | |
| floors | |
| Dressing rooms | |
| — | |
| — | |
| — | |
| 0.25 | |
| Mall common areas | |
| 40 | |
| 7.5 | |
| 0.06 | |
| — | |
| Sales | |
| 15 | |
| 7.5 | |
| 0.12 | |
| — | |
| Shipping and receiving | |
| — | |
| — | |
| 0.12 | |
| — | |
| Smoking lounges and non | |
| - | |
| tobacco | |
| smoking establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Storage rooms | |
| — | |
| — | |
| 0.12 | |
| — | |
| Warehouses (see storage) | |
| | |
| | |
| | |
| | |
| Specialty shops | |
| Automotive motor | |
| - | |
| fuel dispensing | |
| stations | |
| b | |
| — | |
| — | |
| — | |
| 1.5 | |
| Barber | |
| 25 | |
| 7.5 | |
| 0.06 | |
| 0.5 | |
| Beauty salons (without nail salon | |
| services) | |
| b | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Nail salons | |
| b, h | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Embalming room | |
| b | |
| | |
| | |
| | |
| 2.0 | |
| Pet shops (animal areas) | |
| b | |
| 10 | |
| 7.5 | |
| 0.18 | |
| 0.9 | |
| Supermarkets | |
| 8 | |
| 7.5 | |
| 0.06 | |
| | |
| Sports and amusement | |
| Bowling alleys (seating areas) | |
| 40 | |
| 10 | |
| 0.12 | |
| — | |
| Disco/dance floors | |
| 100 | |
| 20 | |
| 0.06 | |
| — | |
| Game arcades | |
| 20 | |
| 7.5 | |
| 0.18 | |
| | |
| Gym, stadium, arena (play area) | |
| — | |
| — | |
| 0.30 | |
| — | |
| Heath club/aerobics room | |
| 40 | |
| 20 | |
| 0.06 | |
| — | |
| Health | |
| club/weight room | |
| 10 | |
| 20 | |
| 0.06 | |
| — | |
| Ice arenas without combustion engines | |
| — | |
| — | |
| 0.30 | |
| 0.5 | |
| Spectator areas | |
| 150 | |
| 7.5 | |
| 0.06 | |
| | |
| VENTILATION | |
| Swimming pools (pool and deck area) | |
| — | |
| — | |
| 0.48 | |
| — | |
| Storage | |
| Repair garages, enclosed parking | |
| garages | |
| b, d | |
| | |
| | |
| | |
| 0.75 | |
| Warehouses | |
| | |
| | |
| 0.06 | |
| | |
| Theaters | |
| Auditoriums (see education) | |
| — | |
| — | |
| — | |
| — | |
| Lobbies | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Stages, studios | |
| 70 | |
| 10 | |
| 0.06 | |
| | |
| Ticket booths | |
| 60 | |
| 5 | |
| 0.06 | |
| — | |
| Transportation | |
| Platforms | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Transportation waiting | |
| 100 | |
| 7.5 | |
| 0.06 | |
| | |
| Workrooms | |
| Bank vaults/safe deposit | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Computer (without printing) | |
| 4 | |
| 5 | |
| 0.06 | |
| — | |
| Copy, printing rooms | |
| 4 | |
| 5 | |
| 0.06 | |
| 0.5 | |
| Darkrooms | |
| | |
| | |
| | |
| 1.0 | |
| Meat processing | |
| c | |
| 10 | |
| 15 | |
| — | |
| — | |
| Pharmacy (prep. area) | |
| 10 | |
| 5 | |
| 0.18 | |
| | |
| Photo studios | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| For SI: 1 cubic foot per | |
| minute = 0.0004719 m | |
| 3 | |
| /s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508m | |
| 3 | |
| /(s • m | |
| 2 | |
| ), | |
| °C = ((°F) | |
| - | |
| 32) | |
| / | |
| 1.8, | |
| 1 square foot = 0.0929 m | |
| 2 | |
| . | |
| a. | |
| Based upon net occupiable floor area. | |
| b. | |
| Mechanical exhaust required and the | |
| recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3). | |
| c. | |
| Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous. | |
| d. | |
| Ventilation systems in enclosed parking garages sh | |
| all comply with Section 404. | |
| e. | |
| Rates are per water closet or urinal. The higher rate shall be provided where | |
| the exhaust system is designed to operate intermittently. The lower rate | |
| shall be permitted only where the exhaust system is designed to operate | |
| continuously while the space served by the toilet facilities is occupied. | |
| f. | |
| Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to oper | |
| ate intermittently. The | |
| lower rate shall | |
| be permitted | |
| only where the exhaust system is designed to operate continuously while the dwelling unit or sleeping unit served by | |
| the toilet facility is occupied. | |
| g. | |
| Mechanical exhaust is required and recirculation from such spaces is prohibited (see Section 403.2.1, | |
| Item 4). | |
| h. | |
| For nail salons, | |
| each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm | |
| per | |
| station. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more re | |
| quired source capture systems operate | |
| VENTILATION | |
| continuously during occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table | |
| 403.3.1.1 for the nail salon. | |
| i. | |
| For each dwelling unit within R | |
| - | |
| 2 occupancies, outdoor ventilation air shall be provided by mechanical means when the sum of all exhaust air flow rates, | |
| whether continuous or intermittent, is designed to exceed 75 cfm. When provided, mechanical ventilation | |
| air flow rate shall be approximately equal to the | |
| exhaust air flow rate in accordance with Section 403.1 and shall not be less than that required by the air flow rates prescribed in Table 403.3.1.1. For such | |
| dwelling units, manually operated openable exte | |
| rior wall openings shall not be used to provide required mechanical ventilation air. | |
| j. | |
| During unoccupied hours the ventilation rate and exhaust rates may be reduced to 0.5 cfm/ft | |
| 2 | |
| . | |
| k. | |
| When an educational science laboratory is occupied and hoods are | |
| not in use and hazardous materials are not present, then ventilation rates shall be | |
| consistent with actual use of the space, but not less than 0.5 cfm/ft | |
| 2 | |
| . | |
| l. | |
| See Section 502.6 for additional requirements. | |
| m. | |
| Exception: kitchens and kitchenettes in dwelli | |
| ng units of R | |
| - | |
| 2 occupancy may be naturally ventilated in accordance with Section 402. | |
| 403.3.1.1.1 | |
| Zone outdoor airflow. | |
| The minimum outdoor airflow required to be supplied to each zone shall be de- | |
| termined as a function of occupancy classification and space | |
| air distribution effectiveness in accordance with Sections | |
| 403.3.1.1.1.1 | |
| through 403.3.1.1.1.3. | |
| 403.3.1.1.1.1 Breathing zone outdoor airflow. | |
| The outdoor airflow rate required in the breathing zone | |
| V | |
| bz | |
| of the | |
| occupiable space or spaces in a zone shall be determined in accordance with Equation 4 | |
| - | |
| 1. | |
| V | |
| bz | |
| = R | |
| p | |
| P | |
| z | |
| + R | |
| a | |
| A | |
| z | |
| (Equation 4 | |
| - | |
| 1) | |
| where: | |
| A | |
| z | |
| = | |
| Zone floor area: the net occupiable floor area of the space or spaces in the zone. | |
| p | |
| z | |
| = Zone population: the number of people in the space or spaces in | |
| the zone. | |
| R | |
| p | |
| = | |
| People outdoor air rate: the outdoor airflow rate required per person from Table 403.3.1.1. | |
| R | |
| a | |
| = | |
| Area outdoor air rate: the outdoor airflow rate required per unit area from Table 403.3.1.1. | |
| 403.3.1.1.1.2 Zone air distribution effectiveness | |
| . | |
| The zone air distribution effectiveness (E | |
| z | |
| ) shall be determined | |
| using Table 403.3.1.1.1.2. | |
| TABLE 403.3.1.1.1.2 | |
| ZONE AIR DISTRIBUTION EFFECTIVENESS | |
| a, b, c, d | |
| AIR DISTRIBUTION CONFIGURATION | |
| E | |
| z | |
| Ceiling or floor supply of cool air | |
| 1.0 | |
| e | |
| Ceiling or | |
| floor supply of warm air and floor return | |
| 1.0 | |
| Ceiling supply of warm air and ceiling return | |
| 0.8 | |
| f | |
| Floor supply of warm air and ceiling return | |
| 0.7 | |
| Makeup air drawn in on the opposite side of the | |
| room from the exhaust and/or return | |
| 0.8 | |
| Makeup air | |
| drawn in near to the exhaust and/or re- | |
| turn location | |
| 0.5 | |
| For SI: 1 | |
| foot = 304.8 mm, 1 foot per minute = 0.00506 m/s, | |
| °C = ((°F) | |
| – | |
| 32) /1.8 | |
| . | |
| a. “Cool air” is air cooler than space temperature. | |
| b. “Warm air” is air warmer than space temperature. | |
| c. | |
| “Ceiling” includes any point above the breathing zone. | |
| d. “Floor” includes any point below the breathing zone. | |
| e. | |
| Zone air distribution effectiveness of 1.2 shall be permitted for systems with a floor supply of cool air and ceiling return, | |
| provided that lo | |
| w- | |
| velocity | |
| dis | |
| - | |
| placement | |
| ventilation achieves unidirectional flow and thermal | |
| stratification. | |
| f. | |
| Zone air distribution effectiveness of 1.0 shall be permitted for systems with a ceiling supply of warm air, provided that su | |
| pply air temperature is less | |
| than | |
| 15°F above space temperature and provided that the 150 | |
| foot | |
| - | |
| per | |
| - | |
| minute supply air jet reaches to within | |
| 4 | |
| 1 | |
| / | |
| 2 | |
| feet of floor level. | |
| 403.3.1.1.1.3 Zone outdoor airflow. | |
| The zone outdoor airflow rate (V | |
| oz | |
| ), shall be determined in accordance with | |
| Equation | |
| 4- | |
| 2. | |
| V | |
| oz | |
| = | |
| V | |
| bz | |
| E | |
| z | |
| (Equation 4 | |
| - | |
| 2) | |
| VENTILATION | |
| 403.3.1.1.2 System outdoor airflow. | |
| The outdoor air required to be supplied by each ventilation system shall be | |
| determined in accordance with Sections 403.3.1.1.2.1 through 403.3.1.1.2.3 as a function of system | |
| type and zone | |
| outdoor airflow rates. | |
| 403.3.1.1.2.1 Single zone systems. | |
| Where one air handler supplies a mixture of outdoor air and recirculated return | |
| air to only one zone, the system outdoor air intake flow rate (V | |
| ot | |
| ) shall be determined in accordance wi | |
| th Equation | |
| 4 | |
| - | |
| 3. | |
| V | |
| ot | |
| = V | |
| oz | |
| (Equation 4 | |
| - | |
| 3) | |
| 403.3.1.1.2.2 100 | |
| - | |
| percent outdoor air systems. | |
| Where one air handler supplies only outdoor air to one or more | |
| zones, the system outdoor air intake flow rate (V | |
| ot | |
| ) shall be determined using Equation 4 | |
| - | |
| 4. | |
| V | |
| ot | |
| = | |
| ∑ | |
| V | |
| oz | |
| all | |
| zones | |
| (Equation 4 | |
| - | |
| 4) | |
| 403.3.1.1.2.3 Multiple zone recirculating systems. | |
| Where one air handler supplies a mixture of outdoor air and | |
| recirculated return air to more than one zone, the system outdoor air intake flow rate (V | |
| ot | |
| ) shall be | |
| determined in | |
| accordance with Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4. | |
| 403.3.1.1.2.3.1 Primary outdoor air fraction. | |
| The primary outdoor air fraction (Z | |
| p | |
| ) shall be determined for | |
| each zone in accordance with Equation 4 | |
| - | |
| 5. | |
| Z | |
| p | |
| = V | |
| oz | |
| /V | |
| pz | |
| (Eq | |
| uation 4 | |
| - | |
| 5) | |
| where: | |
| V | |
| pz | |
| = | |
| Primary airflow: The airflow rate supplied to the zone from the air | |
| - | |
| handling unit at which the outdoor air | |
| intake is located. It includes outdoor intake air and recirculated air from that air | |
| - | |
| handling unit but does | |
| not include a | |
| ir transferred or air recirculated to the zone by other means. For design purposes, V | |
| pz | |
| shall | |
| be the zone design primary airflow rate, except for zones with variable air volume supply and V | |
| pz | |
| shall | |
| be the lowest expected primary air | |
| - | |
| flow rate to the zone w | |
| hen it is fully occupied. | |
| 403.3.1.1.2.3.2 System ventilation efficiency. | |
| The system ventilation efficiency (E | |
| v | |
| ) shall be determined using | |
| Table 403.3.1.1.2.3.2 or Appendix A of ASHRAE 62.1. | |
| TABLE 403.3.1.1.2.3.2 | |
| SYSTEM VENTILATION EFFICIENCY | |
| a, b | |
| Max (Z | |
| p | |
| ) | |
| E | |
| v | |
| ≤ | |
| 0.15 | |
| 1 | |
| ≤ | |
| ⸀(特) | |
| ⸹ | |
| ≤ | |
| ⸀㌵ | |
| ⸸ | |
| ≤ | |
| ⸀㐵 | |
| ⸷ | |
| ≤ | |
| ⸀㔵 | |
| ⸶ | |
| ≤ | |
| ⸀㘵 | |
| ⸵ | |
| ≤ | |
| ⸀㜵 | |
| ⸴ | |
| 㸀‰⸀㜵 | |
| ⸳ | |
| 愮⁍愀砀 | |
| ⠀ | |
| 娀 | |
| 瀀 | |
| ⤀猀⁴栀攠氀慲最敳琀⁶慬甀攠漀昀 | |
| 娀 | |
| 瀀 | |
| 挀愀氀挀甀氀愀琀攀搀⁵猀椀渀最⁅焀甀愀琀椀漀渀′′′ | |
| ⴀ | |
| 㔀洀漀渀最氀氀 | |
| 琀栀攀⁺潮攀猀攀爀瘀攀搀礀 琀栀攀礀猀琀攀洀⸀ | |
| 戀⸠䤀渀琀敲瀀漀氀慴椀渀最 戀攀琀眀攀敮⁴愀戀氀攠 | |
| 瘀愀汵攀猀栀愀汬攀 瀀攀爀洀椀瑴攀搀⸀ | |
| 403.3.1.1.2.3.3 Uncorrected outdoor air intake. | |
| The uncorrected outdoor air intake flow rate (V | |
| ou | |
| ) shall be | |
| determined in accordance with Equation 4 | |
| - | |
| 6. | |
| V | |
| ou | |
| = | |
| D | |
| ∑ | |
| R | |
| p | |
| P | |
| z | |
| all | |
| zones | |
| + | |
| ∑ | |
| R | |
| a | |
| A | |
| z | |
| all | |
| zones | |
| (Equation 4 | |
| - | |
| 6) | |
| where: | |
| D | |
| = | |
| Occupant diversity: the ratio of the system population to the sum of the zone populations, determined in | |
| accordance with Equation 4 | |
| - | |
| 7. | |
| VENTILATION | |
| D = | |
| P | |
| s | |
| ∑ | |
| P | |
| z | |
| all | |
| zones | |
| (Equation 4 | |
| - | |
| 7) | |
| where: | |
| P | |
| a | |
| = System population: The total number of occupants in the area served by the system. For design purposes, | |
| P | |
| s | |
| shall be the maximum number of occupants expected to be concurrently in all zones served by the | |
| system. | |
| 403.3.1.1.2.3.4 Outdoor air intake flow ra | |
| te. | |
| The outdoor air intake flow rate ( | |
| V | |
| ot | |
| ) shall be determined in | |
| accordance with Equation 4 | |
| - | |
| 8. | |
| V | |
| ot | |
| = V | |
| ou | |
| /E | |
| v | |
| (Equation 4 | |
| - | |
| 8) | |
| 403.3.1.2 | |
| Short | |
| - | |
| term conditions. | |
| If it is known that peak occupancy will be of short duration and/or ventilation will | |
| be varied or interrupted for a short period of time, the design may be based on the average conditions over a time | |
| period T determined by Equation 4 | |
| - | |
| 9. | |
| T = 3V/V | |
| bz | |
| (Equation 4 | |
| - | |
| 9) | |
| (US) | |
| T = 50V/V | |
| bz | |
| (Equation 4 | |
| - | |
| 9) | |
| (SI) | |
| where: | |
| T | |
| = | |
| averaging time period, minutes | |
| V | |
| = | |
| the volume of the zone of which averaging is being applied, cubic feet | |
| V | |
| bz | |
| = | |
| the breathing zone outdoor airflow calculated using Equation 4 | |
| - | |
| 1 and design valve of the zone pop- | |
| ulation P | |
| z | |
| , cfm | |
| Acceptable design adjustments based on this optional provision include the following: | |
| 1. | |
| Zone with fluctuating occupancy: the zone population ( | |
| P | |
| z | |
| ) may be averaged over time, T. | |
| 2. | |
| Zone with intermittent interruption of supply air: the average outdoor airflow supplied to breathing zone over | |
| time, T, shall be no less than the breathing zone outdoor airflow ( | |
| V | |
| bz | |
| ) calculated using Equation 4 | |
| - | |
| 1. | |
| 3. | |
| A | |
| system with intermittent closure of outdoor air intake: the average | |
| outdoor air intake over time, T, shall be no | |
| less than the minimum outdoor air intake ( | |
| V | |
| ot | |
| ) calculated using Equation 4 | |
| - | |
| 3, 4 | |
| - | |
| 4 or 4 | |
| - | |
| 8, as appropriate. | |
| 403.3.1.3 Exhaust ventilation. | |
| Exhaust airflow rate shall be provided in accordance with the requirements of Table | |
| 403.3.1.1. | |
| Exhaust makeup | |
| air shall be | |
| permitted | |
| to | |
| be any combination of | |
| outdo | |
| or | |
| air, recirculated air and transfer air, | |
| except as limited in accordance with Section 403.2. | |
| 403.3.1.4 System operation. | |
| The minimum flow rate of outdoor air that the ventilation system must be capable of sup- | |
| plying during its operation shall be permitted | |
| to be based on the rate per person indicated in Table 403.3.1.1 and the | |
| actual number of occupants present. | |
| 403.3.1.5 Variable air volume system control. | |
| Variable air volume air distribution systems, other than those designed | |
| to supply only 100 | |
| - | |
| percent ou | |
| tdoor air, shall be provided with controls to regulate the flow of outdoor air. Such control | |
| system shall be designed to maintain the flow rate of outdoor air at a rate of not less than that required by Section 403.3.1 | |
| .1 | |
| over the entire range of supply air | |
| operating rates. | |
| 403.3.1.6 Balancing. | |
| The ventilation air distribution system shall be provided with means to adjust the system to achieve | |
| not less than the minimum ventilation airflow rate as required by Sections 403.3.1.1 and 403.3.1.2. Ventilation syst | |
| ems | |
| shall be balanced by an approved method. Such balancing shall verify that the ventilation system is capable of supplying | |
| and exhausting the airflow rates required by Sections 403.3.1.1 and 403.3.1.2. | |
| SECTION | |
| MC | |
| 404 | |
| ENCLOSED PARKING GARAGES | |
| 404.1 Enclosed parking garages. | |
| Where mechanical ventilation | |
| systems | |
| for enclosed parking garages operate intermittently | |
| , | |
| such operation shall be automatic by means of carbon monoxide detectors applied in conjunction with nitrogen dioxide detec- | |
| tors. Such detectors sha | |
| ll be installed in accordance with their manufacturers’ instructions. Such systems shall operate auto- | |
| matically upon detection of a concentration of carbon monoxide of 25 parts per million (ppm) or nitrogen dioxide of 500 parts | |
| per billion (ppb). | |
| ‡‡‡ Chapter 4 was amended by | |
| Local Law | |
| 77 | |
| of 2023 | |
| . This law has an effective | |
| date of June 10, 2023. | |
| CHAPTER 4 | |
| VENTILATION | |
| SECTION MC 401 | |
| GENERAL | |
| 401.1 Scope. | |
| This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust | |
| systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and | |
| refuse conveyor systems; subslab soil exhaust systems; smoke control systems; energy recovery ventilation systems and other | |
| systems specified in Section 502 shall comply with Chapter 5. | |
| 401 | |
| .2 Ventilation required. | |
| Habitable and occupiable spaces shall be provided with ventilation in accordance with this section. | |
| 1. | |
| Every | |
| occupiable | |
| space shall be: | |
| 1.1. | |
| Naturally ventilated in accordance with Section 402 and mechanically exhausted in | |
| accordance with Table 403.3.1.1; | |
| or | |
| 1.2. | |
| Mechanically ventilated in accordance with Section 403. | |
| 2. | |
| All habitable spaces and occupiable spaces provided with air conditioning shall be mechanically ventilated in accordance | |
| with Section 403. | |
| 3. | |
| Every habitabl | |
| e space | |
| shall be naturally ventilated in accordance with Section 402. | |
| 4. | |
| Every habitable space shall be mechanically ventilated if required by Section 403 | |
| . | |
| Ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be ventilated by mechanical means in accordance | |
| with Section 407. | |
| 401.3 When required. | |
| Ventilation shall be provided during the periods that the room or space is occupied or during operation | |
| of gas appliances. | |
| ‡‡‡ | |
| 401.4 Intake opening location. | |
| Ventilation air intake openings shall compl | |
| y with all of | |
| the following: | |
| 1. | |
| Intake | |
| openings | |
| shall be located | |
| not less than 10 feet (3048 mm) from lot lines or buildings on the same lot. For buildings | |
| on lots measuring less than 20 feet (6096 mm) in width, intake openings shall be located at the cent | |
| erline between lot | |
| lines. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or | |
| public way. | |
| 2. | |
| Outdoor air intakes for office occupancies having occupied floors located more than 75 feet (22 860 mm) above the | |
| lowest level of fire department vehicle access serving spaces above the second story and serving spaces greater than | |
| 10,000 square feet (929 m | |
| 2 | |
| ) of floor area shall be located at least 20 feet (6096 mm) above ground level, at least 30 feet | |
| (91 | |
| 44 mm) from exhaust outlets and other exhaust discharges, and at least 20 feet (6096 mm) from areas that may collect | |
| vehicular exhaust, such as off street loading bays. | |
| 3. | |
| Mechanical and gravity outdoor air intake openings shall be located not less than 10 | |
| feet (3048 mm) horizontally from | |
| any hazardous or noxious contaminant source, such as vents, exhausts (including but not limited to exhaust from dry | |
| cleaning establishments, spray booths, and cooling towers), streets, alleys, parking lots and loading dock | |
| s, except as | |
| specified in Item 3 | |
| of | |
| Section 501.3.1. Outdoor air intake openings shall be permitted to be located less than 10 feet (3048 | |
| mm) horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less | |
| than | |
| 25 feet (7620 mm) vertically above such locations. Where openings front on a street or public way, the distance shall be | |
| measured | |
| to the centerline | |
| of the street or public way. | |
| 4. | |
| Where the requirements of Item 3 above cannot be achieved, | |
| intake | |
| openings shall be located not less than 3 feet (914.4 | |
| mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. | |
| 5. | |
| Intake openings in Group I occupancies shall comply with ANSI/ASHRAE/ASHE 170, as require | |
| d. | |
| VENTILATION | |
| 6. | |
| Intake openings on structures in flood hazard areas shall comply with the additional requirements of Appendix G of the | |
| New York City Building Code. | |
| Exception: | |
| Group R | |
| - | |
| 3 occupancies are not required to comply with Section 401.4. | |
| 401.4.1 Required damp | |
| ers in intake openings. | |
| Outdoor air intakes shall be provided with dampers in accordance with | |
| Chapter 6. | |
| 401.5 Intake opening protection. | |
| Air intake openings that terminate outdoors shall be protected with | |
| corrosion | |
| - | |
| resistant | |
| screens, louvers or grilles. O | |
| penings in louvers, grilles and screens shall be sized in accordance with Table 401.5, and shall be | |
| protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions f | |
| or | |
| exterior wall opening protec | |
| tives in accordance with Section 705 of the | |
| New York City | |
| Building Code. | |
| TABLE 401.5 | |
| OPENING SIZES IN LOUVERS, GRILLES AND SCREENS | |
| PROTECTING OUTDOOR EXHAUST AND AIR INTAKE | |
| OPENINGS | |
| OUTDOOR OPENING TYPE | |
| MINIMUM AND MAXIMUM | |
| OPENING SIZES IN | |
| LOUVERS, | |
| GRILLES AND SCREENS | |
| MEASURED IN ANY | |
| DIRECTION | |
| Intake openings in | |
| residential oc- | |
| cupancies | |
| Not < | |
| 1 | |
| / | |
| 4 | |
| inch and not > | |
| 1 | |
| / | |
| 2 | |
| inch | |
| Intake openings in other | |
| than resi- | |
| dential occupancies | |
| > | |
| 1 | |
| / | |
| 4 | |
| inch and not > 1 inch | |
| For SI: 1 inch = 25.4 mm. | |
| 401.6 | |
| Contaminant sources. | |
| Stationary local sources | |
| producing | |
| air | |
| - | |
| borne particulates, heat, odors, fumes, spray, vapors, | |
| smoke or gases in such quantities as to be irritating or injurious to health shall be provided with an exhaust system in | |
| accordance | |
| with Chap | |
| ter 5 or a means of collection and removal of the contaminants. Such exhaust shall discharge directly to an approved | |
| location at the exterior of the building. | |
| 401.6.1 Wind | |
| - | |
| driven rain. | |
| All exterior louvers for building ventilation systems shall conform to the requirements of Chap- | |
| ter 16 of the | |
| New York City Building Code | |
| , where applicable, and the following: | |
| 1. | |
| Comply with the requirements of AMCA 550. Louvers shall comply with the intru | |
| sion requirements of wind | |
| - | |
| driven | |
| rain without the use of a damper. Outdoor air intake openings located in exterior walls shall meet the provisions for | |
| exterior wall opening protectives in accordance with Chapter 16 of the | |
| New York City Building Code | |
| ; | |
| or | |
| 2. | |
| Be installed on a plenum configured to intercept any wind | |
| - | |
| driven rain penetrating the louver and to prevent the rain | |
| from entering the building ductwork system. Such plenum shall be waterproofed and equipped with a drainage system | |
| to convey water penetrat | |
| ing the louver directly to the outdoors or in accordance with the | |
| New York City Plumbing | |
| Code | |
| . | |
| SECTION MC 402 | |
| NATURAL VENTILATION | |
| 402.1 | |
| General. | |
| Natural ventilation of occupiable and habitable spaces | |
| shall comply with Chapter 12 of the | |
| New York City | |
| Build | |
| ing Code. | |
| 402.2 Reserved. | |
| 402.3 Reserved. | |
| 402.4 Reserved. | |
| SECTION | |
| MC | |
| 403 | |
| MECHANICAL VENTILATION | |
| VENTILATION | |
| 403.1 Ventilation system. | |
| Mechanical ventilation shall be | |
| provided | |
| by a method of supply air and return or exhaust air. The | |
| amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be | |
| prohibited | |
| from producing negative or positive pressure; such pressures shall not r | |
| esult in door opening forces in excess of those indicated | |
| in the | |
| New York City Building Code | |
| and shall not prevent doors from closing as required by the | |
| New York City Building Code | |
| . | |
| The | |
| method | |
| to convey ventilation air shall be designed and installed in ac | |
| cordance with Chapter 6. | |
| 403.2 Outdoor air required. | |
| The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.1.1. | |
| Exception: | |
| The minimum required rate of outdoor air may be reduced where the registered design professional demo | |
| nstrates | |
| that an engineered ventilation system is designed in accordance with ASHRAE 62.1 | |
| Indoor Air Quality Procedure | |
| . | |
| 403.2.1 Recirculation of air. | |
| The outdoor air required by Section 403.3.1.1 shall not be recirculated. Air in excess of that | |
| required by | |
| Section 403.3.1.1 shall not be prohibited from being recirculated as a component of supply air to building spaces, | |
| except that: | |
| 1. | |
| Ventilation air shall not be recirculated from one dwelling | |
| unit | |
| to another or to dissimilar occupancies. | |
| 2. | |
| Supply air to a | |
| swimming pool and associated deck areas shall not be recirculated unless such air is | |
| dehumidified | |
| to | |
| maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other | |
| uses or occupancies | |
| . | |
| 3. | |
| Where mech | |
| anical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be | |
| prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recir- | |
| culation of air is prohibited, all | |
| air supplied to such spaces shall be exhausted, including any air in excess of that | |
| required by Table 403.3.1.1. | |
| 4. | |
| Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation | |
| is prohibited. Recircula | |
| tion of air that is contained completely within such spaces shall not be prohibited. | |
| 403.2.2 Transfer air. | |
| Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from | |
| occupiable spaces is not prohibited from serving a | |
| s makeup air for required exhaust systems in such spaces as kitchens, | |
| baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide | |
| the flow rates as specified in Section 403.3.1.1. The requir | |
| ed outdoor airflow rates specified in Table 403.3.1.1 shall be | |
| introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both. | |
| 403.3 Outdoor air and local exhaust airflow rates. | |
| Buildings that are no | |
| t more than three stories in height above grade plane, | |
| and that (i) are within Occupancy Group R | |
| - | |
| 2 or Occupancy Group R | |
| - | |
| 3, (ii) are adult homes or enriched living housing as | |
| described in Section 308.3.1 of the | |
| New York City Building Code, | |
| within Occupancy | |
| Group I | |
| - | |
| 1 and have 16 occupants or fewer, | |
| or (iii) are community residences or intermediate | |
| - | |
| care facilities as described in Section 308.3.2 of the | |
| New York City Building | |
| Code, | |
| shall be provided with outdoor air and local exhaust in accordance with Section | |
| 403.3.1.1.2. All other buildings intended | |
| to be occupied shall be provided with outdoor air and local exhaust in accordance with Sections 403.3.1.1 through 403.3.1.6. | |
| 403.3.1 Reserved. | |
| 403.3.1.1 Outdoor airflow rate. | |
| Ventilation systems shall be designed t | |
| o have the capacity to supply the minimum | |
| outdoor airflow rate determined in accordance with this section. In each occupiable space and, where required, each | |
| habitable space, the ventilation system shall be designed to deliver the required rate of outdoor | |
| airflow to the breathing | |
| zone. The occupant load utilized for design of the ventilation system shall be | |
| not less than the number | |
| determined | |
| from | |
| the estimated maximum occupant load rate | |
| indicated | |
| in Table 403.3.1.1 | |
| . | |
| Ventilation rates for | |
| occupancies not represented | |
| in Table 403.3.1.1 | |
| shall be those for a listed occupancy classification that is most similar in terms of occupant density, | |
| activities and building construction; or shall be determined by an approved engineering analysis. The ven | |
| tilation system | |
| shall be designed to supply the required rate of ventilation air continuously | |
| during | |
| the period the building is occupied, | |
| except as otherwise stated in other provisions of the code. | |
| With the exception of non | |
| - | |
| tobacco hookah establishments, t | |
| he ventilation rates in Table 403.3.1.1 | |
| are based on the | |
| absence of smoking in occupiable spaces. Where smoking is anticipated in a space other than a non | |
| - | |
| tobacco hookah | |
| establishment, the ventilation system serving the space shall be designed to provide v | |
| entilation over and above that re- | |
| quired by Table 403.3.1.1 | |
| in accordance with accepted engineering practice. | |
| Exceptions: | |
| 1. | |
| The occupant load is not required to be | |
| determined | |
| based on the estimated maximum occupant load rate indi- | |
| cated in Table 403.3 | |
| .1.1 wh | |
| ere | |
| approved statistical data | |
| documents | |
| the accuracy of an alternate anticipated | |
| occupant load. | |
| VENTILATION | |
| 2. | |
| The occupant load used in computing the required ventilation shall be the maximum number who will occupy | |
| the room or space simultaneously during any 2 | |
| - | |
| hour p | |
| eriod. | |
| 3. | |
| Dynamic reset (Demand Controlled Ventilation). The system may be designed to reset the design outdoor air | |
| intake airflow and/or space or zone airflow as operating conditions change. Dynamic reset shall be designed in | |
| accordance with ASHRAE 62.1 a | |
| nd comply with footnote k of Table 403.3.1.1. These conditions include, but | |
| are not limited to: | |
| 3.1. | |
| Variations in occupancy or ventilation airflow in one or more individual zones for which ventilation airflow | |
| requirements will be reset. Note: Examples of | |
| measures for estimating such variations include: occupancy | |
| scheduled by time of day, a direct count of occupants, or an estimate of occupancy or ventilation rate per | |
| person using occupancy sensors such as those based on indoor CO | |
| 2 | |
| concentrations. | |
| 3.2. | |
| Variations in the efficiency with which outdoor air is distributed to the occupants under different ventilation | |
| system airflows and temperatures. | |
| 3.3. | |
| A higher fraction of outdoor air in the air supply due to intake of additional outdoor air for free cooli | |
| ng or | |
| exhaust air makeup. | |
| TABLE 403.3.1.1 | |
| MINIMUM VENTILATION RATES | |
| OCCUPANCY CLASSIFICATION | |
| OCCUPANT DENSITY | |
| #/1000 FT | |
| 2a | |
| PEOPLE OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE, R | |
| p | |
| CFM/PERSON | |
| AREA OUTDOOR | |
| AIRFLOW RATE IN | |
| BREATHING ZONE R | |
| a | |
| CFM/FT | |
| 2a | |
| EXHAUST | |
| AIRFLOW | |
| RATE | |
| CFM/FT | |
| 2a | |
| Correctional facilities | |
| Booking/waiting | |
| 50 | |
| 7.5 | |
| 0.06 | |
| | |
| Cells | |
| without plumbing fixtures | |
| 25 | |
| 5 | |
| 0.12 | |
| | |
| with plumbing fixtures | |
| g | |
| 25 | |
| 5 | |
| 0.12 | |
| 1.0 | |
| Day room | |
| 30 | |
| 5 | |
| 0.06 | |
| | |
| Correctional facilities | |
| Dining halls | |
| (see food and | |
| beverage service) | |
| — | |
| — | |
| — | |
| — | |
| Guard stations | |
| 15 | |
| 5 | |
| 0.06 | |
| — | |
| Dry cleaners, laundries | |
| Coin | |
| - | |
| operated dry cleaner | |
| 20 | |
| 15 | |
| — | |
| — | |
| Coin | |
| - | |
| operated laundries | |
| 20 | |
| 7.5 | |
| 0.06 | |
| — | |
| Commercial dry cleaner | |
| l | |
| 30 | |
| 30 | |
| — | |
| — | |
| Commercial laundry | |
| 10 | |
| 25 | |
| — | |
| — | |
| Storage, pick up | |
| 30 | |
| 7.5 | |
| 0.12 | |
| — | |
| Education | |
| Art classroom | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.7 | |
| VENTILATION | |
| Auditoriums | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Classrooms (ages 5 | |
| - | |
| 8) | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Classrooms (age 9 plus) | |
| 35 | |
| 10 | |
| 0.12 | |
| — | |
| Computer lab | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Corridors (see public spaces) | |
| — | |
| — | |
| — | |
| — | |
| Day care (through age 4) | |
| 25 | |
| 10 | |
| 0.18 | |
| — | |
| Lecture classroom | |
| 65 | |
| 7.5 | |
| 0.06 | |
| — | |
| Lecture hall (fixed seats) | |
| 150 | |
| 7.5 | |
| 0.06 | |
| — | |
| Locker/dressing rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.25 | |
| Media center | |
| 25 | |
| 10 | |
| 0.12 | |
| — | |
| Multiuse assembly | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Music/theater/dance | |
| 35 | |
| 10 | |
| 0.06 | |
| — | |
| Science laboratories | |
| g, k | |
| 25 | |
| 10 | |
| 0.18 | |
| 1.0 | |
| Sports locker rooms | |
| g | |
| — | |
| — | |
| — | |
| 0.5 | |
| Wood/metal shops | |
| g | |
| 20 | |
| 10 | |
| 0.18 | |
| 0.5 | |
| Food and beverage service | |
| Bars, cocktail lounges | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Cafeteria, fast food | |
| 100 | |
| 7.5 | |
| 0.18 | |
| — | |
| Dining rooms | |
| 70 | |
| 7.5 | |
| 0.18 | |
| — | |
| Kitchens (cooking) | |
| b | |
| — | |
| — | |
| — | |
| 0.7 | |
| Non | |
| - | |
| tobacco smoking | |
| establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Hotels, motels, resorts and dormitories | |
| Bathrooms/toilet | |
| | |
| private | |
| g | |
| | |
| | |
| | |
| 25/50 | |
| f | |
| Bedroom/living room | |
| 10 | |
| 5 | |
| 0.06 | |
| | |
| Conference/meeting | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Dormitory sleeping areas | |
| 20 | |
| 5 | |
| 0.06 | |
| | |
| Gambling casinos | |
| 120 | |
| 7.5 | |
| 0.18 | |
| | |
| Lobbies/prefunction | |
| 30 | |
| 7.5 | |
| 0.06 | |
| | |
| Multipurpose assembly | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Laboratories | |
| j | |
| Biological | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| VENTILATION | |
| Chemical | |
| | |
| | |
| 1.0 | |
| 1.0 | |
| Industrial and nonteaching | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Nonproduction chemical labs | |
| — | |
| — | |
| 1.0 | |
| 1.0 | |
| Offices | |
| Conference rooms | |
| 50 | |
| 5 | |
| 0.06 | |
| — | |
| Main entry lobbies | |
| 10 | |
| 5 | |
| 0.06 | |
| — | |
| Office spaces | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Reception areas | |
| 30 | |
| 5 | |
| 0.06 | |
| — | |
| Telephone/data entry | |
| 60 | |
| 5 | |
| 0.06 | |
| | |
| Private dwellings, single and multiple | |
| Garages, common for multiple units | |
| b | |
| — | |
| — | |
| — | |
| 0.75 | |
| Kitchens and Kitchenettes | |
| b | |
| , | |
| m | |
| | |
| | |
| | |
| 25/100 | |
| f | |
| Living areas | |
| c, i | |
| Based upon number of | |
| bedrooms. First bed- | |
| room, 2; each additional | |
| bedroom, 1 | |
| 0.35 ACH but not less | |
| than 15 cfm/person | |
| — | |
| — | |
| Toilet rooms and bathrooms | |
| g | |
| | |
| | |
| | |
| 20/50 | |
| f | |
| Public spaces | |
| Corridors | |
| — | |
| — | |
| 0.06 | |
| — | |
| Courtrooms | |
| 70 | |
| 5 | |
| 0.06 | |
| — | |
| Elevator car | |
| | |
| | |
| | |
| 1.0 | |
| Legislative chambers | |
| 50 | |
| 5 | |
| 0.06 | |
| | |
| Libraries | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| Museums (childrens) | |
| 40 | |
| 7.5 | |
| 0.12 | |
| | |
| Museums/galleries | |
| 40 | |
| 7.5 | |
| 0.06 | |
| | |
| Places of religious worship | |
| 120 | |
| 5 | |
| 0.06 | |
| | |
| Public spaces | |
| Shower room (per shower head) | |
| g | |
| — | |
| — | |
| — | |
| 50/20 | |
| f | |
| Toilet rooms | |
| – | |
| public | |
| g | |
| — | |
| — | |
| — | |
| 50/70 | |
| e | |
| VENTILATION | |
| Retail stores, sales floors and | |
| showroom | |
| floors | |
| Dressing rooms | |
| — | |
| — | |
| — | |
| 0.25 | |
| Mall common areas | |
| 40 | |
| 7.5 | |
| 0.06 | |
| — | |
| Sales | |
| 15 | |
| 7.5 | |
| 0.12 | |
| — | |
| Shipping and receiving | |
| — | |
| — | |
| 0.12 | |
| — | |
| Smoking lounges and non | |
| - | |
| tobacco | |
| smoking establishments | |
| b | |
| 70 | |
| 60 | |
| — | |
| — | |
| Storage rooms | |
| — | |
| — | |
| 0.12 | |
| — | |
| Warehouses (see storage) | |
| | |
| | |
| | |
| | |
| Specialty shops | |
| Automotive motor | |
| - | |
| fuel dispensing | |
| stations | |
| b | |
| — | |
| — | |
| — | |
| 1.5 | |
| Barber | |
| 25 | |
| 7.5 | |
| 0.06 | |
| 0.5 | |
| Beauty salons (without nail salon | |
| services) | |
| b | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Nail salons | |
| b, h | |
| 25 | |
| 20 | |
| 0.12 | |
| 0.6 | |
| Embalming room | |
| b | |
| | |
| | |
| | |
| 2.0 | |
| Pet shops (animal areas) | |
| b | |
| 10 | |
| 7.5 | |
| 0.18 | |
| 0.9 | |
| Supermarkets | |
| 8 | |
| 7.5 | |
| 0.06 | |
| | |
| Sports and amusement | |
| Bowling alleys (seating areas) | |
| 40 | |
| 10 | |
| 0.12 | |
| — | |
| Disco/dance floors | |
| 100 | |
| 20 | |
| 0.06 | |
| — | |
| Game arcades | |
| 20 | |
| 7.5 | |
| 0.18 | |
| | |
| Gym, stadium, arena (play area) | |
| — | |
| — | |
| 0.30 | |
| — | |
| Heath club/aerobics room | |
| 40 | |
| 20 | |
| 0.06 | |
| — | |
| Health | |
| club/weight room | |
| 10 | |
| 20 | |
| 0.06 | |
| — | |
| Ice arenas without combustion engines | |
| — | |
| — | |
| 0.30 | |
| 0.5 | |
| Spectator areas | |
| 150 | |
| 7.5 | |
| 0.06 | |
| | |
| VENTILATION | |
| Swimming pools (pool and deck area) | |
| — | |
| — | |
| 0.48 | |
| — | |
| Storage | |
| Repair garages, enclosed parking | |
| garages | |
| b, d | |
| | |
| | |
| | |
| 0.75 | |
| Warehouses | |
| | |
| | |
| 0.06 | |
| | |
| Theaters | |
| Auditoriums (see education) | |
| — | |
| — | |
| — | |
| — | |
| Lobbies | |
| 150 | |
| 5 | |
| 0.06 | |
| — | |
| Stages, studios | |
| 70 | |
| 10 | |
| 0.06 | |
| | |
| Ticket booths | |
| 60 | |
| 5 | |
| 0.06 | |
| — | |
| Transportation | |
| Platforms | |
| 100 | |
| 7.5 | |
| 0.06 | |
| — | |
| Transportation waiting | |
| 100 | |
| 7.5 | |
| 0.06 | |
| | |
| Workrooms | |
| Bank vaults/safe deposit | |
| 5 | |
| 5 | |
| 0.06 | |
| — | |
| Computer (without printing) | |
| 4 | |
| 5 | |
| 0.06 | |
| — | |
| Copy, printing rooms | |
| 4 | |
| 5 | |
| 0.06 | |
| 0.5 | |
| Darkrooms | |
| | |
| | |
| | |
| 1.0 | |
| Meat processing | |
| c | |
| 10 | |
| 15 | |
| — | |
| — | |
| Pharmacy (prep. area) | |
| 10 | |
| 5 | |
| 0.18 | |
| | |
| Photo studios | |
| 10 | |
| 5 | |
| 0.12 | |
| | |
| For SI: 1 cubic foot per | |
| minute = 0.0004719 m | |
| 3 | |
| /s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508m | |
| 3 | |
| /(s • m | |
| 2 | |
| ), | |
| °C = ((°F) | |
| - | |
| 32) | |
| / | |
| 1.8, | |
| 1 square foot = 0.0929 m | |
| 2 | |
| . | |
| a. | |
| Based upon net occupiable floor area. | |
| b. | |
| Mechanical exhaust required and the | |
| recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3). | |
| c. | |
| Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous. | |
| d. | |
| Ventilation systems in enclosed parking garages sh | |
| all comply with Section 404. | |
| e. | |
| Rates are per water closet or urinal. The higher rate shall be provided where | |
| the exhaust system is designed to operate intermittently. The lower rate | |
| shall be permitted only where the exhaust system is designed to operate | |
| continuously while the space served by the toilet facilities is occupied. | |
| f. | |
| Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to oper | |
| ate intermittently. The | |
| lower rate shall | |
| be permitted | |
| only where the exhaust system is designed to operate continuously while the dwelling unit or sleeping unit served by | |
| the toilet facility is occupied. | |
| g. | |
| Mechanical exhaust is required and recirculation from such spaces is prohibited (see Section 403.2.1, | |
| Item 4). | |
| h. | |
| For nail salons, | |
| each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm | |
| per | |
| station. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more re | |
| quired source capture systems operate | |
| VENTILATION | |
| continuously during occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table | |
| 403.3.1.1 for the nail salon. | |
| i. | |
| For each dwelling unit within R | |
| - | |
| 2 occupancies, outdoor ventilation air shall be provided by mechanical means when the sum of all exhaust air flow rates, | |
| whether continuous or intermittent, is designed to exceed 75 cfm. When provided, mechanical ventilation | |
| air flow rate shall be approximately equal to the | |
| exhaust air flow rate in accordance with Section 403.1 and shall not be less than that required by the air flow rates prescribed in Table 403.3.1.1. For such | |
| dwelling units, manually operated openable exte | |
| rior wall openings shall not be used to provide required mechanical ventilation air. | |
| j. | |
| During unoccupied hours the ventilation rate and exhaust rates may be reduced to 0.5 cfm/ft | |
| 2 | |
| . | |
| k. | |
| When an educational science laboratory is occupied and hoods are | |
| not in use and hazardous materials are not present, then ventilation rates shall be | |
| consistent with actual use of the space, but not less than 0.5 cfm/ft | |
| 2 | |
| . | |
| l. | |
| See Section 502.6 for additional requirements. | |
| m. | |
| Exception: kitchens and kitchenettes in dwelli | |
| ng units of R | |
| - | |
| 2 occupancy may be naturally ventilated in accordance with Section 402. | |
| 403.3.1.1.1 | |
| Zone outdoor airflow. | |
| The minimum outdoor airflow required to be supplied to each zone shall be de- | |
| termined as a function of occupancy classification and space | |
| air distribution effectiveness in accordance with Sections | |
| 403.3.1.1.1.1 | |
| through 403.3.1.1.1.3. | |
| 403.3.1.1.1.1 Breathing zone outdoor airflow. | |
| The outdoor airflow rate required in the breathing zone | |
| V | |
| bz | |
| of the | |
| occupiable space or spaces in a zone shall be determined in accordance with Equation 4 | |
| - | |
| 1. | |
| V | |
| bz | |
| = R | |
| p | |
| P | |
| z | |
| + R | |
| a | |
| A | |
| z | |
| (Equation 4 | |
| - | |
| 1) | |
| where: | |
| A | |
| z | |
| = | |
| Zone floor area: the net occupiable floor area of the space or spaces in the zone. | |
| p | |
| z | |
| = Zone population: the number of people in the space or spaces in | |
| the zone. | |
| R | |
| p | |
| = | |
| People outdoor air rate: the outdoor airflow rate required per person from Table 403.3.1.1. | |
| R | |
| a | |
| = | |
| Area outdoor air rate: the outdoor airflow rate required per unit area from Table 403.3.1.1. | |
| 403.3.1.1.1.2 Zone air distribution effectiveness | |
| . | |
| The zone air distribution effectiveness (E | |
| z | |
| ) shall be determined | |
| using Table 403.3.1.1.1.2. | |
| TABLE 403.3.1.1.1.2 | |
| ZONE AIR DISTRIBUTION EFFECTIVENESS | |
| a, b, c, d | |
| AIR DISTRIBUTION CONFIGURATION | |
| E | |
| z | |
| Ceiling or floor supply of cool air | |
| 1.0 | |
| e | |
| Ceiling or | |
| floor supply of warm air and floor return | |
| 1.0 | |
| Ceiling supply of warm air and ceiling return | |
| 0.8 | |
| f | |
| Floor supply of warm air and ceiling return | |
| 0.7 | |
| Makeup air drawn in on the opposite side of the | |
| room from the exhaust and/or return | |
| 0.8 | |
| Makeup air | |
| drawn in near to the exhaust and/or re- | |
| turn location | |
| 0.5 | |
| For SI: 1 | |
| foot = 304.8 mm, 1 foot per minute = 0.00506 m/s, | |
| °C = ((°F) | |
| – | |
| 32) /1.8 | |
| . | |
| a. “Cool air” is air cooler than space temperature. | |
| b. “Warm air” is air warmer than space temperature. | |
| c. | |
| “Ceiling” includes any point above the breathing zone. | |
| d. “Floor” includes any point below the breathing zone. | |
| e. | |
| Zone air distribution effectiveness of 1.2 shall be permitted for systems with a floor supply of cool air and ceiling return, | |
| provided that lo | |
| w- | |
| velocity | |
| dis | |
| - | |
| placement | |
| ventilation achieves unidirectional flow and thermal | |
| stratification. | |
| f. | |
| Zone air distribution effectiveness of 1.0 shall be permitted for systems with a ceiling supply of warm air, provided that su | |
| pply air temperature is less | |
| than | |
| 15°F above space temperature and provided that the 150 | |
| foot | |
| - | |
| per | |
| - | |
| minute supply air jet reaches to within | |
| 4 | |
| 1 | |
| / | |
| 2 | |
| feet of floor level. | |
| 403.3.1.1.1.3 Zone outdoor airflow. | |
| The zone outdoor airflow rate (V | |
| oz | |
| ), shall be determined in accordance with | |
| Equation | |
| 4- | |
| 2. | |
| V | |
| oz | |
| = | |
| V | |
| bz | |
| E | |
| z | |
| (Equation 4 | |
| - | |
| 2) | |
| VENTILATION | |
| 403.3.1.1.2 System outdoor airflow. | |
| The outdoor air required to be supplied by each ventilation system shall be | |
| determined in accordance with Sections 403.3.1.1.2.1 through 403.3.1.1.2.3 as a function of system | |
| type and zone | |
| outdoor airflow rates. | |
| 403.3.1.1.2.1 Single zone systems. | |
| Where one air handler supplies a mixture of outdoor air and recirculated return | |
| air to only one zone, the system outdoor air intake flow rate (V | |
| ot | |
| ) shall be determined in accordance wi | |
| th Equation | |
| 4 | |
| - | |
| 3. | |
| V | |
| ot | |
| = V | |
| oz | |
| (Equation 4 | |
| - | |
| 3) | |
| 403.3.1.1.2.2 100 | |
| - | |
| percent outdoor air systems. | |
| Where one air handler supplies only outdoor air to one or more | |
| zones, the system outdoor air intake flow rate (V | |
| ot | |
| ) shall be determined using Equation 4 | |
| - | |
| 4. | |
| V | |
| ot | |
| = | |
| ∑ | |
| V | |
| oz | |
| all | |
| zones | |
| (Equation 4 | |
| - | |
| 4) | |
| 403.3.1.1.2.3 Multiple zone recirculating systems. | |
| Where one air handler supplies a mixture of outdoor air and | |
| recirculated return air to more than one zone, the system outdoor air intake flow rate (V | |
| ot | |
| ) shall be | |
| determined in | |
| accordance with Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4. | |
| 403.3.1.1.2.3.1 Primary outdoor air fraction. | |
| The primary outdoor air fraction (Z | |
| p | |
| ) shall be determined for | |
| each zone in accordance with Equation 4 | |
| - | |
| 5. | |
| Z | |
| p | |
| = V | |
| oz | |
| /V | |
| pz | |
| (Eq | |
| uation 4 | |
| - | |
| 5) | |
| where: | |
| V | |
| pz | |
| = | |
| Primary airflow: The airflow rate supplied to the zone from the air | |
| - | |
| handling unit at which the outdoor air | |
| intake is located. It includes outdoor intake air and recirculated air from that air | |
| - | |
| handling unit but does | |
| not include a | |
| ir transferred or air recirculated to the zone by other means. For design purposes, V | |
| pz | |
| shall | |
| be the zone design primary airflow rate, except for zones with variable air volume supply and V | |
| pz | |
| shall | |
| be the lowest expected primary air | |
| - | |
| flow rate to the zone w | |
| hen it is fully occupied. | |
| 403.3.1.1.2.3.2 System ventilation efficiency. | |
| The system ventilation efficiency (E | |
| v | |
| ) shall be determined using | |
| Table 403.3.1.1.2.3.2 or Appendix A of ASHRAE 62.1. | |
| TABLE 403.3.1.1.2.3.2 | |
| SYSTEM VENTILATION EFFICIENCY | |
| a, b | |
| Max (Z | |
| p | |
| ) | |
| E | |
| v | |
| ≤ | |
| 0.15 | |
| 1 | |
| ≤ | |
| ⸀(特) | |
| ⸹ | |
| ≤ | |
| ⸀㌵ | |
| ⸸ | |
| ≤ | |
| ⸀㐵 | |
| ⸷ | |
| ≤ | |
| ⸀㔵 | |
| ⸶ | |
| ≤ | |
| ⸀㘵 | |
| ⸵ | |
| ≤ | |
| ⸀㜵 | |
| ⸴ | |
| 㸀‰⸀㜵 | |
| ⸳ | |
| 愮⁍愀砀 | |
| ⠀ | |
| 娀 | |
| 瀀 | |
| ⤀猀⁴栀攠氀慲最敳琀⁶慬甀攠漀昀 | |
| 娀 | |
| 瀀 | |
| 挀愀氀挀甀氀愀琀攀搀⁵猀椀渀最⁅焀甀愀琀椀漀渀′′′ | |
| ⴀ | |
| 㔀洀漀渀最氀氀 | |
| 琀栀攀⁺潮攀猀攀爀瘀攀搀礀 琀栀攀礀猀琀攀洀⸀ | |
| 戀⸠䤀渀琀敲瀀漀氀慴椀渀最 戀攀琀眀攀敮⁴愀戀氀攠 | |
| 瘀愀汵攀猀栀愀汬攀 瀀攀爀洀椀瑴攀搀⸀ | |
| 403.3.1.1.2.3.3 Uncorrected outdoor air intake. | |
| The uncorrected outdoor air intake flow rate (V | |
| ou | |
| ) shall be | |
| determined in accordance with Equation 4 | |
| - | |
| 6. | |
| V | |
| ou | |
| = | |
| D | |
| ∑ | |
| R | |
| p | |
| P | |
| z | |
| all | |
| zones | |
| + | |
| ∑ | |
| R | |
| a | |
| A | |
| z | |
| all | |
| zones | |
| (Equation 4 | |
| - | |
| 6) | |
| where: | |
| D | |
| = | |
| Occupant diversity: the ratio of the system population to the sum of the zone populations, determined in | |
| accordance with Equation 4 | |
| - | |
| 7. | |
| VENTILATION | |
| D = | |
| P | |
| s | |
| ∑ | |
| P | |
| z | |
| all | |
| zones | |
| (Equation 4 | |
| - | |
| 7) | |
| where: | |
| P | |
| a | |
| = System population: The total number of occupants in the area served by the system. For design purposes, | |
| P | |
| s | |
| shall be the maximum number of occupants expected to be concurrently in all zones served by the | |
| system. | |
| 403.3.1.1.2.3.4 Outdoor air intake flow ra | |
| te. | |
| The outdoor air intake flow rate ( | |
| V | |
| ot | |
| ) shall be determined in | |
| accordance with Equation 4 | |
| - | |
| 8. | |
| V | |
| ot | |
| = V | |
| ou | |
| /E | |
| v | |
| (Equation 4 | |
| - | |
| 8) | |
| 403.3.1.2 | |
| Short | |
| - | |
| term conditions. | |
| If it is known that peak occupancy will be of short duration and/or ventilation will | |
| be varied or interrupted for a short period of time, the design may be based on the average conditions over a time | |
| period T determined by Equation 4 | |
| - | |
| 9. | |
| T = 3V/V | |
| bz | |
| (Equation 4 | |
| - | |
| 9) | |
| (US) | |
| T = 50V/V | |
| bz | |
| (Equation 4 | |
| - | |
| 9) | |
| (SI) | |
| where: | |
| T | |
| = | |
| averaging time period, minutes | |
| V | |
| = | |
| the volume of the zone of which averaging is being applied, cubic feet | |
| V | |
| bz | |
| = | |
| the breathing zone outdoor airflow calculated using Equation 4 | |
| - | |
| 1 and design valve of the zone pop- | |
| ulation P | |
| z | |
| , cfm | |
| Acceptable design adjustments based on this optional provision include the following: | |
| 1. | |
| Zone with fluctuating occupancy: the zone population ( | |
| P | |
| z | |
| ) may be averaged over time, T. | |
| 2. | |
| Zone with intermittent interruption of supply air: the average outdoor airflow supplied to breathing zone over | |
| time, T, shall be no less than the breathing zone outdoor airflow ( | |
| V | |
| bz | |
| ) calculated using Equation 4 | |
| - | |
| 1. | |
| 3. | |
| A | |
| system with intermittent closure of outdoor air intake: the average | |
| outdoor air intake over time, T, shall be no | |
| less than the minimum outdoor air intake ( | |
| V | |
| ot | |
| ) calculated using Equation 4 | |
| - | |
| 3, 4 | |
| - | |
| 4 or 4 | |
| - | |
| 8, as appropriate. | |
| 403.3.1.3 Exhaust ventilation. | |
| Exhaust airflow rate shall be provided in accordance with the requirements of Table | |
| 403.3.1.1. | |
| Exhaust makeup | |
| air shall be | |
| permitted | |
| to | |
| be any combination of | |
| outdo | |
| or | |
| air, recirculated air and transfer air, | |
| except as limited in accordance with Section 403.2. | |
| 403.3.1.4 System operation. | |
| The minimum flow rate of outdoor air that the ventilation system must be capable of sup- | |
| plying during its operation shall be permitted | |
| to be based on the rate per person indicated in Table 403.3.1.1 and the | |
| actual number of occupants present. | |
| 403.3.1.5 Variable air volume system control. | |
| Variable air volume air distribution systems, other than those designed | |
| to supply only 100 | |
| - | |
| percent ou | |
| tdoor air, shall be provided with controls to regulate the flow of outdoor air. Such control | |
| system shall be designed to maintain the flow rate of outdoor air at a rate of not less than that required by Section 403.3.1 | |
| .1 | |
| over the entire range of supply air | |
| operating rates. | |
| 403.3.1.6 Balancing. | |
| The ventilation air distribution system shall be provided with means to adjust the system to achieve | |
| not less than the minimum ventilation airflow rate as required by Sections 403.3.1.1 and 403.3.1.2. Ventilation syst | |
| ems | |
| shall be balanced by an approved method. Such balancing shall verify that the ventilation system is capable of supplying | |
| and exhausting the airflow rates required by Sections 403.3.1.1 and 403.3.1.2. | |
| SECTION | |
| MC | |
| 404 | |
| ENCLOSED PARKING GARAGES | |
| 404.1 Enclosed parking garages. | |
| Where mechanical ventilation | |
| systems | |
| for enclosed parking garages operate intermittently | |
| , | |
| such operation shall be automatic by means of carbon monoxide detectors applied in conjunction with nitrogen dioxide detec- | |
| tors. Such detectors sha | |
| ll be installed in accordance with their manufacturers’ instructions. Such systems shall operate auto- | |
| matically upon detection of a concentration of carbon monoxide of 25 parts per million (ppm) or nitrogen dioxide of 500 parts | |
| per billion (ppb). | |
| VENTILATION | |
| 404.2 Mini | |
| mum ventilation. | |
| Automatic operation of the | |
| system | |
| shall not reduce the ventilation airflow rate below 0.05 cfm | |
| per square foot (0.00025 m | |
| 3 | |
| /s • m | |
| 2 | |
| ) of the floor area and the system shall be capable of producing a ventilation airflow rate of | |
| 0.75 cfm per | |
| square foot (0.0038 m | |
| 3 | |
| /s • m | |
| 2 | |
| ) of floor area. | |
| 404.3 Occupied spaces accessory to public garages. | |
| Connecting | |
| offices, waiting rooms, ticket booths and similar uses that | |
| are accessory to a public garage shall be maintained at a positive pressure and shall be | |
| provided with ventilation in accordance | |
| with Section 403.3. | |
| SECTION | |
| MC | |
| 405 | |
| SYSTEMS CONTROL | |
| 405.1 General. | |
| Mechanical ventilation systems shall be provided with manual or automatic controls that will operate such | |
| systems whenever the spaces are occupied. A | |
| ir | |
| - | |
| conditioning systems that supply required ventilation air shall be provided with | |
| controls designed to automatically maintain the required outdoor air supply rate during occupancy. | |
| 405.2 Manual control. | |
| Each air distribution system shall be provided with | |
| not less than one manual control to stop the | |
| operation of the supply, return, and exhaust fans(s) in an emergency. The manual control shall be provided at an approved | |
| location. A disconnect switch shall not be considered a manual control. | |
| 405.2.1 Office b | |
| uildings. | |
| Any building where the main use or dominant occupancy is classified in Occupancy Group B | |
| having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, | |
| where a system serves a floor or floor | |
| s other than the floor on which the equipment is located, shall be provided with the | |
| following controls, in addition to the controls required by this chapter: | |
| 1. | |
| Manual controls for operating individually each air supply and each exhaust or return fan in t | |
| he system located as | |
| follows: | |
| 1.1. | |
| At the Fire Command Center, and | |
| 1.2. | |
| In the room containing the affected air | |
| - | |
| handling fans. | |
| 2. | |
| Manual controls for operating individually or in groups each remote control reversible fire shutter, when such shutters | |
| are provided in accordance with the provisions of the | |
| New York City Building Code | |
| , or each smoke damper provided | |
| in accordance with the | |
| provisions of the | |
| New York City Building Code | |
| . Such controls shall be located at the Fire | |
| Command Center. | |
| SECTION | |
| MC | |
| 406 | |
| VENTILATION OF UNINHABITED SPACES | |
| 406.1 General. | |
| Uninhabited spaces, such as crawl spaces and attics, shall be provided with natural ventilation openings as | |
| required by the | |
| New York City | |
| Building Code | |
| or shall be | |
| pro | |
| - | |
| vided | |
| with a mechanical exhaust and supply air system. The | |
| mechanical exhaust rate shall | |
| be not less than 0.02 cfm per square foot (0.00001 m | |
| 3 | |
| /s • m | |
| 2 | |
| ) of horizontal area and shall be | |
| automatically controlled to operate when the relative humidity in the space served exceeds 60 percent. | |
| 406.1.1 Methane and radon venting. | |
| The design and material | |
| s used in the installation of the methane and radon vent | |
| systems shall be approved by the commissioner and shall comply with all applicable rules of the Fire Department. | |
| SECTION MC 407 | |
| AMBULATORY CARE FACILITIES AND GROUP I | |
| - | |
| 2 OCCUPANCIES | |
| 407.1 General. | |
| Mec | |
| hanical ventilation for ambulatory care facilities (Group B) and Group I | |
| - | |
| 2 occupancies shall be designed | |
| and installed in accordance with all applicable federal, state and local regulations. | |
| SECTION MC 408 | |
| VENTILATION OF NONPRODUCTION CHEMICAL | |
| LABORATORIES | |
| VENTILATION | |
| 408 | |
| .1 General. | |
| Nonproduction chemical laboratories complying with the hazardous materials quantity limitations of Section | |
| 427 of the | |
| New York City Building Code | |
| shall provide a mechanical ventilation system in accordance with NFPA 45 and Table | |
| 403.3.1.1 o | |
| f this code, except that ducts constructed of combustible materials shall not be permitted. |