| CHAPTER 7 | |
| COMBUSTION | |
| , VENTILATION, AND DILUTION | |
| AIR | |
| SECTION MC 701 | |
| GENERAL | |
| 701.1 Scope. | |
| The | |
| provisions of this chapter shall govern the requirements for combustion, ventilation, and dilution | |
| air for fuel | |
| - | |
| burning appliances other than gas | |
| - | |
| fired appliances. The requirements for combustion, ventilation, and | |
| dilution air for gas | |
| - | |
| fired appliances shal | |
| l be in accordance with | |
| the New York City Fuel Gas Code. | |
| 701.2 Combustion, ventilation, and dilution air required. | |
| Every room or space containing fuel | |
| - | |
| burning appliances | |
| shall be provided with combustion, ventilation, and dilution air as required by this c | |
| ode. Combustion, ventilation, | |
| and dilution air shall be provided in accordance with Section 702, 703, 704, 705, 706 or 707. Direct | |
| - | |
| vent appliances | |
| or equipment that do not draw combustion air from inside of the building are not required to be considered in | |
| the | |
| determination of the combustion and dilution air requirements and shall be installed in accordance with the equip- | |
| ment manufacturer’s instructions and listing. Combustion air requirements shall be determined based on the simul- | |
| taneous operation of all f | |
| uel | |
| - | |
| burning appliances drawing combustion, ventilation, and dilution air from the room or | |
| space. Combustion, ventilation, and dilution air shall be obtained solely from the outdoors for fuel | |
| - | |
| burning appli- | |
| ances with an input greater than 350,000 Btu/h (102. | |
| 6 kW). The room or space containing fuel | |
| - | |
| burning appliances | |
| shall comply with the requirements of Sections C402.5.3 and R402.4.4, as applicable, of the | |
| New York City Energy | |
| Conservation Code | |
| and Section 1012 of this code. | |
| 701.3 Circulation of air. | |
| The equi | |
| pment and appliances within every room containing fuel | |
| - | |
| burning appliances shall | |
| be installed so as to allow free circulation of air. Provisions shall be made to allow for the simultaneous operation of | |
| mechanical exhaust systems, fireplaces or other equipme | |
| nt and appliances operating in the same room or space from | |
| which combustion, ventilation, and dilution air is being drawn. Such provisions shall prevent the operation of such | |
| appliances, equipment and systems from affecting the supply of combustion, ventil | |
| ation, and dilution air. | |
| 701.3.1 Makeup air for fuel | |
| - | |
| burning devices. | |
| Where exhaust fans are installed, makeup air shall be provided to | |
| replace the exhausted air. Calculations shall be provided on the construction documents to validate the use of the | |
| exhaust fan(s) and compliance with this chapter. | |
| 701.3.2 Ventilation air f | |
| or fuel | |
| - | |
| burning devices. | |
| Where ventilation air is brought in by mechanical means for | |
| heat generation mitigation, provisions must be made for proper air balance to prevent a negative or positive pressure | |
| in the boiler and to discharge the ventilation air di | |
| rectly to the outside. | |
| 701.4 Crawl space and attic space. | |
| For the purposes of this chapter, an opening to a naturally ventilated crawl space | |
| or attic space shall be considered equivalent to an opening to the outdoors. | |
| 701.4.1 Crawl space. | |
| Where lower combu | |
| stion air openings connect with crawl spaces, such spaces shall have | |
| unobstructed openings to the outdoors at least twice that required for the | |
| combustion air openings | |
| . The height of | |
| the crawl space shall comply with the requirements of the | |
| New York City B | |
| uilding Code | |
| and shall be without | |
| obstruction to the free flow of air. | |
| 701.4.2 Attic space. | |
| Where combustion air is obtained from an attic area, the attic ventilating openings shall not | |
| be subject to ice or snow blockage, and the attic shall have not less | |
| than 30 inches (762 mm) vertical clear height | |
| at its maxi | |
| - | |
| mum point. Attic ventilation openings shall be sufficient to provide the required volume of combustion | |
| air and the attic ventilation required by the | |
| New York City Building Code. | |
| The combustion air o | |
| penings shall be | |
| provided with a sleeve of not less than 0.019 inch (0.48 mm) (No.26 Gage) galvanized steel or other approved | |
| material extending from the appliance enclosure to at least 6 inches ( | |
| 152.4 | |
| mm) above the top of the ceiling joists | |
| and insulation | |
| . | |
| 701.5 Prohibited sources. | |
| Openings and ducts shall not connect appliance enclosures with a space in which the | |
| operation of a fan will adversely affect the flow of the combustion, ventilation, and dilution air. Combustion, venti- | |
| lation, and dilution air sh | |
| all not be subject to ice or snow blockage. No combustion, ventilation, and dilution air inlet | |
| COMBUSTION, VENTILATION, AND DILUTION AIR | |
| shall be less than 30 inches (762 mm) above grade. Combustion, ventilation, and dilution air shall not be obtained | |
| from a hazardous location, except where the fu | |
| el | |
| - | |
| fired appliances are located within the hazardous location and are | |
| installed in accordance with this code. Combustion, ventilation, and dilution air shall not be taken from a refrigeration | |
| machinery room, except where a refrigerant vapor detector system | |
| is installed to automatically shut off the combus- | |
| tion process in the event of refrigerant leakage. For structures in flood hazard areas, air shall be obtained from a | |
| location complying with the additional requirements of Appendix G of the | |
| New York City Bu | |
| ilding Code. | |
| SECTION MC 702 | |
| INSIDE AIR | |
| 702.1 All air from indoors. | |
| Combustion, ventilation, and dilution air shall be permitted to be obtained entirely from | |
| the indoors in buildings that are not of unusually tight construction. In buildings of | |
| unusually tight construction, | |
| combustion air shall be obtained from the outdoors in accordance with Section 703, 705, 706 or 707. | |
| 702.2 Air from the same room or space. | |
| The room or space containing fuel | |
| - | |
| burning appliances shall be an uncon- | |
| fined space as de | |
| fined in Section 202. | |
| 702.3 Air from adjacent spaces. | |
| Where the volume of the room in which the fuel | |
| - | |
| burning appliances are located | |
| does not comply with Section 702.2, additional inside combustion, ventilation, and dilution air shall be obtained by | |
| opening | |
| the room to adjacent spaces so that the combined volume of all communicating spaces meets the volumetric | |
| requirement of Section 702.2. Openings connecting the spaces shall comply with Sections 702.3.1, 702.3.2 and Fig- | |
| ure A | |
| - | |
| 1 of Appendix A. | |
| 702.3.1 Number | |
| and location of openings. | |
| Two openings shall be provided, one within 1 foot ( | |
| 304.8 | |
| mm) of the | |
| ceiling of the room and one within 1 foot ( | |
| 304.8 | |
| mm) of the floor. | |
| 702.3.2 Size of openings. | |
| The net free area of each opening, calculated in accordance with Sect | |
| ion 708, shall be | |
| a minimum of 1 square inch per 1,000 Btu/h (2201 mm | |
| 2 | |
| /kW) of input rating of the fuel | |
| - | |
| burning appliances draw- | |
| ing combustion, ventilation, and dilution air from the communicating spaces and shall be not less than 100 square | |
| inches (64 516 m | |
| m | |
| 2 | |
| ). | |
| SECTION MC 703 | |
| OUTDOOR AIR | |
| 703.1 All air from the outdoors. | |
| Where all combustion, ventilation, and dilution air is to be provided by outdoor | |
| air, the required combustion, ventilation, and dilution air shall be obtained by direct opening by louver or a | |
| duct(s) | |
| from the boiler room to the outdoors. Openings connecting the room to the outdoor air shall comply with Sections | |
| 703.1.1 through 703.1.2 of this code, and Figures 304.6.1(1), 304.6.1(2), 304.6.1(3) and 304.6.2 of | |
| the New York | |
| City Fuel Gas Code | |
| . | |
| The size of the openings connecting the room to the outdoor air supply shall also comply with | |
| any applicable rules of the New York City Department of Environmental Protection. | |
| 703.1.1 Two | |
| - | |
| permanent | |
| - | |
| openings method. | |
| Two permanent openings, one commencing within 12 inches (304.8 | |
| mm) at the top and one commencing within 12 inches (304.8 mm) of the bottom of the room, shall be provided. | |
| The openings shall communicate directly, or by ducts, with the outdoors or spaces th | |
| at freely communicate with | |
| the outdoors as follows: | |
| 1. | |
| Where directly communicating with the outdoors, or where communicating with the outdoors through verti- | |
| cal ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/h (550 mm | |
| 2 | |
| /kW | |
| ) of | |
| total input rating of all equipment in the room. | |
| 2. | |
| Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free | |
| area of not less than 1 square inch per 2,000 Btu/H (1100 mm | |
| 2 | |
| /kW) of total input rating of all e | |
| quipment in | |
| the room. | |
| 703.1.2 One | |
| - | |
| permanent | |
| - | |
| opening method. | |
| One permanent opening, commencing within 12 inches (304.8 mm) of | |
| the top of the enclosure, shall be provided. The equipment shall have clearances of at least 1 inch (25.4 mm) from | |
| the sides and b | |
| ack and 6 inches (152.4 mm) from the front of the appliance. The opening shall directly communicate | |
| with the outdoors or through a vertical or horizontal duct to the outdoors or spaces that freely communicate with | |
| mm) at the top and one commencing within 12 inches (304.8 mm) of the bottom of the room, shall be provided. | |
| The openings shall communicate directly, or by ducts, with the outdoors or spaces th | |
| at freely communicate with | |
| the outdoors as follows: | |
| 1. | |
| Where directly communicating with the outdoors, or where communicating with the outdoors through verti- | |
| cal ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/h (550 mm | |
| 2 | |
| /kW | |
| ) of | |
| total input rating of all equipment in the room. | |
| 2. | |
| Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free | |
| area of not less than 1 square inch per 2,000 Btu/H (1100 mm | |
| 2 | |
| /kW) of total input rating of all e | |
| quipment in | |
| the room. | |
| 703.1.2 One | |
| - | |
| permanent | |
| - | |
| opening method. | |
| One permanent opening, commencing within 12 inches (304.8 mm) of | |
| the top of the enclosure, shall be provided. The equipment shall have clearances of at least 1 inch (25.4 mm) from | |
| the sides and b | |
| ack and 6 inches (152.4 mm) from the front of the appliance. The opening shall directly communicate | |
| with the outdoors or through a vertical or horizontal duct to the outdoors or spaces that freely communicate with | |
| COMBUSTION, VENTILATION, AND DILUTION AIR | |
| the outdoors and shall have a minimum free | |
| area of 1 square inch per 3,000 Btu/h (734 mm | |
| 2 | |
| /kW) of the total input | |
| rating of all equipment located in the enclosure, and not less than the sum of the areas of all vent connectors in the | |
| space. | |
| SECTION MC 704 | |
| COMBINED USE OF INSIDE AND OUTDOOR AIR | |
| (COND | |
| ITION 1) | |
| 704.1 Combination of air from inside and outdoors. | |
| This section shall apply only to appliances located in confined | |
| spaces in buildings not of unusually tight construction. Where the volumes of rooms and spaces are combined for | |
| the purpose of provi | |
| ding indoor combustion air, such rooms and spaces shall communicate through permanent open- | |
| ings in compliance with Sections 702.3.1 and 702.3.2. The required combustion, ventilation, and dilution air shall | |
| be obtained by opening the room to the outdoors usi | |
| ng a combination of inside and outdoor air, prorated in accord- | |
| ance with Section 704.1.6. The ratio of interior spaces shall comply with Section 704.1.5. The number, location and | |
| ratios of openings connecting the space with the outdoor air shall comply with | |
| Sections 704.1.1 through 704.1.4. | |
| 704.1.1 Number and location of openings. | |
| At least two openings shall be provided, one within 1 foot ( | |
| 304.8 | |
| mm) of the ceiling of the room and one within 1 foot ( | |
| 304.8 | |
| mm) of the floor. | |
| 704.1.2 Ratio of direct openings. | |
| Wh | |
| ere direct openings to the outdoors are provided in accordance with Section | |
| 703.1, the ratio of direct openings shall be the sum of the net free areas of both direct openings to the outdoors, | |
| divided by the sum of the required areas for both such openings | |
| as determined in accordance with Section 703.1.2. | |
| 704.1.3 Ratio of horizontal openings. | |
| Where openings connected to the outdoors through horizontal ducts are | |
| pro | |
| - | |
| vided in accordance with Section 703.1, the ratio of horizontal openings shall be the sum of | |
| the net free areas | |
| of both such openings, divided by the sum of the required areas for both such openings as determined in accord- | |
| ance with Section 703.1.3. | |
| 704.1.4 Ratio of vertical openings. | |
| Where openings connected to the outdoors through vertical ducts | |
| are provided | |
| in accordance with Section 703.1, the ratio of vertical openings shall be the sum of the net free areas of both such | |
| openings, divided by the sum of the required areas for both such openings as determined in accordance with | |
| Section 703.1.4. | |
| 70 | |
| 4.1.5 Ratio of interior spaces. | |
| The ratio of interior spaces shall be the available volume of all communicating | |
| spaces, divided by the required volume as determined in accordance with Sections 702.2 and 702.3. | |
| 704.1.6 Prorating of inside and outdoor air. | |
| In spaces that utilize a combination of inside and outdoor air, the | |
| sum of the ratios of all direct openings, horizontal openings, vertical openings and interior spaces shall equal or | |
| exceed 1. | |
| SECTION MC 705 | |
| COMBINED USE OF INSIDE AND OUTDOOR AIR | |
| (CONDITI | |
| ON 2) | |
| 705.1 General. | |
| This section shall apply only to appliances located in unconfined spaces in buildings of unusually | |
| tight construction. Combustion air supplied by a combined use of indoor and outdoor air shall be supplied through | |
| openings and ducts ext | |
| ending to the appliance room or to the vicinity of the appliance. | |
| 705.1.1 Openings and supply ducts. | |
| Openings shall be provided, located and sized in accordance with Sections | |
| 702.3.1 and 702.3.2; additionally, there shall be one opening to the outdoors hav | |
| ing a free area of at least 1 square | |
| inch per 5,000 Btu/h (440 mm | |
| 2 | |
| /kW) of total input of all appliances in the space. | |
| SECTION MC 706 | |
| MECHANICAL COMBUSTION AIR SUPPLY | |
| 706.1 Rate of air supplied. | |
| Where all combustion air is provided by a mechanical air suppl | |
| y system, the combustion | |
| air shall be supplied from the outdoors at a rate of not less than 0.35 cubic feet per minute per 1,000 Btu/h (0.034 | |
| COMBUSTION, VENTILATION, AND DILUTION AIR | |
| m | |
| 3 | |
| /min per kW) of total input rating for all the fuel | |
| - | |
| burning appliances located within the space. Combustion air | |
| rates shall also comply with any applicable rules of the New York City Department of Environmental Protection. | |
| The mechanical air supply shall be sufficient to accommodate combustion air, ventilation air, and dilution air re- | |
| quirements of the installation. | |
| 706.1.1 Appliance interlock. | |
| Each of the appliances served shall be interlocked with the mechanical air supply | |
| system to prevent main burner operation when the mechanical air supply system is not in operation. The air flow | |
| and the damper operation shall be | |
| proven prior to burner operation. | |
| SECTION MC 707 | |
| DIRECT CONNECTION | |
| 707.1 General. | |
| Fuel | |
| - | |
| burning appliances that are listed and labeled for direct combustion air connection to the out- | |
| doors shall be installed in accordance with the manufacturer’s instruction | |
| s. | |
| SECTION MC 708 | |
| COMBUSTION AIR DUCTS | |
| 708.1 General. | |
| Combustion air ducts shall comply with all of the following: | |
| 1. | |
| Be of galvanized steel complying with Chapter 6 or of equivalent corrosion | |
| - | |
| resistant material approved for | |
| this application. | |
| Exception: | |
| Within dwelling units, unobstructed stud and joist spaces shall not be prohibited from conveying | |
| combustion air, provided that not more than one required fireblock is removed. | |
| 2. | |
| Have a minimum dimension of 3 inches ( | |
| 76.2 | |
| mm) in all directions. | |
| 3. | |
| Termin | |
| ate in an unobstructed space allowing free movement of combustion air to the appliances. | |
| 4. | |
| Have the same cross | |
| - | |
| sectional areas as the free area of the openings to which they connect. | |
| 5. | |
| Serve a single appliance enclosure. | |
| 6. | |
| Not serve both upper and lo | |
| wer combustion air openings where both such openings are used. The separation | |
| between ducts serving upper and lower combustion air openings shall be maintained to the source of combus- | |
| tion air. | |
| 7. | |
| Not be screened where terminating in an attic space. | |
| 8. | |
| No | |
| t slope downward toward the source of combustion air, where serving the upper required combustion air | |
| opening. | |
| 9. | |
| Be constructed so that the remaining space surrounding a chimney or chimney liner, installed within a masonry, | |
| metal or factory | |
| - | |
| built chimney | |
| cannot be used to supply combustion, ventilation and dilution air, except for | |
| direct vent appliances designed and installed in accordance with the equipment manufacturer’s instructions | |
| and listing. | |
| 10. | |
| Be insulated in accordance with Section C402.5.3 of t | |
| he | |
| New York City Energy Conservation Code | |
| . | |
| SECTION MC 709 | |
| OPENING OBSTRUCTIONS | |
| 709.1 General. | |
| The required size of openings for combustion, ventilation, and dilution air shall be based on the net | |
| free area of each opening. The net free area of an opening s | |
| hall be that specified by the manufacturer of the opening | |
| covering. In the absence of such information, openings covered with metal louvers shall be deemed to have a net | |
| free area of 60 percent of the area of the opening, and openings covered with wood lou | |
| vers shall be deemed to have | |
| a net free area of 10 percent of the area of the opening. Louvers and grills shall be fixed in the open position. | |
| Exception: | |
| Operable louvers shall be interlocked with the appliance so that they are proven to be in the full open | |
| position prior to main burner ignition and during main burner operation. Means shall be provided to prevent the | |
| COMBUSTION, VENTILATION, AND DILUTION AIR | |
| main burner from igniting if the louvers | |
| fail to open during burner startup and to shut down the main burner if the | |
| louvers close during operation. | |
| 709.2 Dampered openings. | |
| Where the combustion air openings are provided with automatic, smoke or fire dampers, | |
| the dampers shall be | |
| electrically interlocked with the appliances served, so as to prevent operation of any appliance | |
| that draws combustion and dilution air from the room when any of the dampers are closed. Manually operated damp- | |
| ers shall not be installed in combustion air ope | |
| nings. The damper opening shall be proven prior to burner operation | |
| . | |
| Dampers shall be provided in accordance with Chapter 6. | |
| 709.3 Caution sign. | |
| A sign stating, “Louvers, dampers and/or ventilation openings must not be blocked or disabled.” | |
| shall be perman | |
| ently affixed, in clear view, and adjacent to the opening(s) within the room containing the equipment. | |
| The letters used on the sign shall be at least 1 inch ( | |
| 25.4 | |
| mm) in height. | |
| SECTION MC 710 | |
| OPENING LOCATION AND PROTECTION | |
| 710.1 General. | |
| Combustion air o | |
| penings to the outdoors shall comply with the location and protection provisions | |
| applicable to outside air intake openings of Sections 401.5 and 401.6. |