id
stringlengths
12
16
title
stringlengths
6
140
description
stringlengths
76
139k
cpes
listlengths
0
0
cvss_v4_0
null
cvss_v3_1
float64
2.5
10
cvss_v3_0
float64
1.9
10
cvss_v2_0
null
ICSA-20-170-05
Rockwell Automation FactoryTalk View SE
The affected product does not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE).CVE-2020-12029 has been assigned to this vulnerability. A CVSS v3 base score of 9.0 ...
[]
null
null
4.3
null
ICSA-23-047-04
Siemens Brownfield Connectivity Gateway
ImportedSymbols in debug/macho (for Open or OpenFat) in Go before 1.16.10 and 1.17.x before 1.17.3 Accesses a Memory Location After the End of a Buffer, aka an out-of-bounds slice situation. Go before 1.16.10 and 1.17.x before 1.17.3 allows an archive/zip Reader.Open panic via a crafted ZIP archive containing an invali...
[]
null
7.5
null
null
ICSA-19-255-01
3S-Smart Software Solutions GmbH CODESYS V3 Web Server
Specially crafted http or https requests may allow an attacker access to files outside the restricted working directory of the controller.CVE-2019-13532 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). Specially cr...
[]
null
null
10
null
ICSA-24-072-01
Schneider Electric EcoStruxure Power Design
All versions of Schneider Electric EcoStruxure Power Design - Ecodial NL, INT, and FR deserializes untrusted data which could allow an attacker to perform code execution when a malicious project file is loaded into the application by a valid user.
[]
null
7.8
null
null
ICSA-21-040-05
Siemens TIA Administrator (Update A)
Manipulating certain files in specific folders could allow a local attacker to execute code with SYSTEM privileges. The security vulnerability could be exploited by an attacker with a valid account and limited access rights on the system.
[]
null
7.8
null
null
ICSA-18-151-02
GE MDS PulseNET and MDS PulseNET Enterprise
Java Remote Method Invocation (RMI) input port may be exploited to allow unauthenticated users to launch applications and support remote code execution through Web Services.CVE-2018-10611 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/...
[]
null
null
4.3
null
ICSA-20-042-02
Siemens Industrial Products SNMP (Update F)
An error in the message handling of SNMP messages allows remote attackers to cause a denial of service and possibly execute arbitrary code via a crafted packet sent on port 161/udp (SNMP). The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitatio...
[]
null
6.5
null
null
ICSA-19-213-02
Fuji Electric FRENIC Loader
The affected product is vulnerable to an out-of-bounds read vulnerability, which may allow an attacker to read limited information from the device.CVE-2019-13512 has been assigned to this vulnerability. A CVSS v3 base score of 4.4 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:L).
[]
null
null
4.4
null
ICSA-19-227-02
Fuji Electric Alpha5 Smart Loader
Multiple buffer overflow issues have been identified. An attacker could use specially crafted project files to overflow the buffer and execute code under the privileges of the application.CVE-2019-13520 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV...
[]
null
null
7.8
null
ICSA-23-180-02
Schneider Electric EcoStruxure Operator Terminal Expert
Schneider Electric EcoStruxure operator Terminal Expert versions 3.3 SP1 and prior are vulnerable to a code injection attack that could allow an attacker to execute arbitrary code and gain access to all information on the machine.
[]
null
null
7.8
null
ICSA-21-243-02
FANUC Robot Controllers (Update A)
The affected products are vulnerable to integer coercion errors, which cause the device to crash. A restart is required.CVE-2021-32996 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:H). The affected products are vuln...
[]
null
null
7.4
null
ICSA-22-102-05
Aethon TUG Home Base Server
An unauthenticated attacker can arbitrarily add new users with administrative privileges and delete or modify existing users.CVE-2022-1066 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:N). An unauthenticated attacke...
[]
null
null
7.6
null
ICSA-21-119-03
Johnson Controls Exacq Technologies exacqVision
The affected product calculates or uses an incorrect maximum or minimum value that is one more or one less than the correct value.CVE-2021-3156 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H).
[]
null
null
7
null
ICSA-22-195-16
Siemens EN100 Ethernet Module
Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint manupulating a specific argument. This could allow an attacker to crash the affected application leading to a denial of service condition
[]
null
8.6
null
null
ICSA-20-021-01
ICSA-20-021-01_Honeywell Maxpro VMS & NVR
The affected products are vulnerable to an unsafe deserialization of untrusted data. An attacker may be able to remotely modify deserialized data without authentication using a specially crafted web request, resulting in remote code execution.CVE-2020-6959 has been assigned to this vulnerability. A CVSS v3 base score o...
[]
null
null
9.8
null
ICSA-18-254-02
Fuji Electric V-Server Lite
A maliciously crafted project file may cause a buffer overflow, which may allow the attacker to execute arbitrary code.CVE-2018-10637 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
[]
null
null
7.8
null
ICSA-21-280-01
Johnson Controls exacqVision Server Bundle
The software does not properly assign, modify, track, or check privileges. This could allow unauthenticated users access to credentials stored in the exacqVision Server.CVE-2021-27664 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N...
[]
null
null
9.8
null
ICSA-19-304-03
Honeywell equIP and Performance Series IP Cameras
A vulnerability exists where the affected product allows unauthenticated access to audio streaming over HTTP.CVE-2019-18230 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
[]
null
null
7.5
null
ICSA-24-130-03
Delta Electronics InfraSuite Device Master
Delta Electronics InfraSuite Device Master contains a deserialization of untrusted data vulnerability because it runs a version of Apache ActiveMQ (5.15.2) which is vulnerable to CVE-2023-46604.
[]
null
9.8
null
null
ICSA-20-063-03
Omron PLC CJ Series
An attacker can send a series of specific data packets within a short period, causing a service error on the PLC Ethernet module, which in turn causes a PLC service denied result.CVE-2020-6986 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/...
[]
null
null
7.5
null
ICSA-21-168-01
Schneider Electric Enerlin'X Com 'X 510
This vulnerability may allow disclosure of device configuration information to any authenticated user when a specially crafted request is sent to the device.CVE-2021-22769 has been assigned to this vulnerability. A CVSS v3 base score of 8.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L...
[]
null
null
8.5
null
ICSA-23-026-07
Landis+Gyr E850
Landis+Gyr E850 (ZMQ200) web application navigation depends on the value of the session cookie. The web application could become inaccessible for the user if an attacker changes the cookie values.-CVE-2022-3083 has been assigned to this vulnerability. A CVSS v3 base score of 3.9 has been assigned; the CVSS vector strin...
[]
null
null
3.9
null
ICSA-21-350-16
Siemens Healthineers syngo fastView (Update A)
The affected application lacks proper validation of user-supplied data when parsing DICOM files, which could result in an out-of-bounds write past the end of an allocated structure. An attacker could leverage this vulnerability to execute code in the context of the current process.CVE-2021-40367 has been assigned to th...
[]
null
null
7.8
null
ICSA-23-068-05
Hitachi Energy Relion 670, 650 and SAM600-IO Series
The Hitachi Energy Relion update package signature validation contains an improper access control vulnerability. A tampered update package could cause the IED to restart. After a restart, the device returns to normal operation.An attacker could exploit the vulnerability by gaining access to the system with security pri...
[]
null
null
4.5
null
ICSA-22-132-02
Mitsubishi Electric MELSOFT iQ AppPortal
Apache HTTP Server Versions 2.4.0 to 2.4.46 allow unprivileged local users to stop httpd on Windows.CVE-2020-13938 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H). In Apache HTTP Server Versions 2.4.0 to 2.4.46 a spe...
[]
null
null
7.5
null
ICSA-20-196-07
Siemens Opcenter Execution Core (Update B)
An authenticated user with the ability to create containers, packages or register defects could perform stored Cross-Site Scripting (XSS) attacks within the vulnerable software. The impact of this attack could result in the session cookies of legitimate users being stolen. Should the attacker gain access to these cooki...
[]
null
5.5
null
null
ICSA-22-179-03
Advantech iView
The affected product is vulnerable to multiple SQL injections, which may allow an unauthorized attacker to disclose information.CVE-2022-2135 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). The affected product is...
[]
null
null
9.8
null
ICSA-22-223-01
Siemens Simcenter STAR-CCM+
Affected applications expose user, host and display name of users, when the public license server is used. This could allow an attacker to retrieve this information.
[]
null
5.3
null
null
ICSA-21-350-12
Siemens SIMATIC ITC
websockets.c in LibVNCServer prior to 0.9.12 did not properly decode certain WebSocket frames. A malicious attacker could exploit this by sending specially crafted WebSocket frames to a server, causing a heap-based buffer overflow. LibVNC before commit a83439b9fbe0f03c48eb94ed05729cb016f8b72f contains multiple heap out...
[]
null
6.5
null
null
ICSA-19-178-01
ABB PB610 Panel Builder 600
The ABB CP635 HMI component implements hidden administrative accounts used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool Panel Builder 600 to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are used over both HTTP(S) and FTP. There ...
[]
null
null
6.5
null
ICSA-20-189-01
Grundfos CIM 500
The affected product responds to unauthenticated requests for password storage files.CVE-2020-10605 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). The affected product stores plaintext credentials, which may allo...
[]
null
null
7.5
null
ICSA-22-151-01
Fuji Electric Alpha7 PC Loader
The affected product is vulnerable to a stack-based buffer overflow while processing a specifically crafted project file, which may allow an attacker to execute arbitrary code.CVE-2022-1888 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:...
[]
null
null
7.8
null
ICSA-23-103-02
Siemens JT Open and JT Utilities
The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted JT files. This could allow an attacker to execute code in the context of the current process.
[]
null
7.8
null
null
ICSA-23-068-02
B&R Systems Diagnostics Manager
A reflected cross-site scripting (XSS) vulnerability exists in System Diagnostics Manager of B&R Automation Runtime versions >=3.00 and <=C4.93 that enables a remote attacker to execute arbitrary JavaScript in the context of the user’s browser session. CVE-2022-4286 has been assigned to this vulnerability. A CVSS v3 ba...
[]
null
null
6.1
null
ICSA-21-320-02
Mitsubishi Electric GOT products
The affected product is vulnerable to an information tampering vulnerability, which may allow an attacker to send a malicious packet to rewrite the device value and adversely affect the system 's operation.CVE-2021-20601 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS ve...
[]
null
null
7.5
null
ICSA-24-130-02
alpitronic Hypercharger EV charger
If misconfigured, the charging devices can expose a web interface protected by authentication. If the default credentials are not changed, an attacker can use public knowledge to access the device as an administrator.
[]
null
null
8.2
null
ICSA-20-345-02
Host Engineering H2-ECOM100 Module
The length of the affected product 's input fields is verified only on the client side when receiving input from the configuration web server, which may allow an attacker to bypass the check and send input to crash the device.CVE-2020-25195 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been c...
[]
null
null
7.5
null
ICSA-24-219-01
Delta Electronics DIAScreen
A crafted DPA file could force Delta Electronics DIAScreen to overflow a stack-based buffer, which could allow an attacker to execute arbitrary code.
[]
null
7.8
null
null
ICSA-18-030-01
PHOENIX CONTACT mGuard
mGuard devices rely on internal checksums for verification of the internal integrity of the update packages. Verification may not always be performed correctly, allowing an attacker to modify firmware update packages. CVE-2018-5441 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; ...
[]
null
null
7.8
null
ICSA-24-046-07
Siemens Tecnomatix Plant Simulation
The affected application contains an out of bounds write past the end of an allocated buffer while parsing a specially crafted WRL file. This could allow an attacker to execute code in the context of the current process. The affected application is vulnerable to heap-based buffer overflow while parsing specially crafte...
[]
null
7.8
null
null
ICSA-23-082-01
RoboDK
RoboDK versions 5.5.3 and prior contain an insecure permission assignment to critical directories vulnerability, which could allow a local user to escalate privileges and write files to the RoboDK process and achieve code execution. CVE-2023-1516 has been assigned to this vulnerability. A CVSS v3 base score of 7.9 has...
[]
null
null
7.9
null
ICSA-23-285-14
Hikvision Access Control and Intercom Products
Some access control products are vulnerable to a session hijacking attack because the product does not update the session ID after a user successfully logs in. To exploit the vulnerability, attackers have to request the session ID at the same time as a valid user logs in, and gain device operation permissions by forgin...
[]
null
null
4.3
null
ICSA-17-250-01
SpiderControl SCADA Web Server
Authenticated, non-administrative local users are able to alter service executables with escalated privileges which could allow an attacker to execute arbitrary code under the context of the current system services.CVE-2017-12728 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; th...
[]
null
null
5.3
null
ICSA-22-242-07
Honeywell Experion LX
The affected product uses the EpicMo protocol that does not have authentication features, which may allow an attacker with access to this protocol over a network to manipulate firmware or cause a denial-of-service condition.CVE-2022-30317 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been ass...
[]
null
null
9.1
null
ICSA-18-338-02
SpiderControl SCADA WebServer
Reflected cross-site scripting (non-persistent) could allow an attacker to send a crafted URL that contains JavaScript, which can be reflected off the web application to the victim 's browser. CVE-2018-18991 has been assigned to this vulnerability. A CVSS v3 base score of 6.1 has been calculated; the CVSS vector string...
[]
null
null
6.1
null
ICSA-19-134-09
Siemens SIMATIC Panels and WinCC (TIA Portal)
Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. ...
[]
null
7.5
null
null
ICSA-24-011-03
Rapid Software LLC Rapid SCADA
By utilizing a Zip Slip vulnerability in the unpacking routine, an attacker can supply a malicious configuration file to achieve remote code execution. By appending path traversal characters to the filename when using a specific command, an attacker can read arbitrary files from the system. Due to improper permissions ...
[]
null
5.3
null
null
ICSA-19-225-03
ICSA-19-225-03_Siemens SCALANCE X Switches (Update D)
An attacker may send large message packages repeatedly to the telnet service, which may allow a denial-of-service condition.CVE-2019-10942 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).
[]
null
null
8.6
null
ICSA-21-257-02
Johnson Controls Sensormatic Electronics KT-1
The KT-1 door controller is susceptible to replay attacks.CVE-2021-27662 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L).
[]
null
null
8.6
null
ICSMA-22-151-02
BD Synapsys
The affected product is vulnerable due to an insufficient session expiration. An unauthorized physical breach of a BD Synapsys workstation would be negligible due to the sequence of events that must occur in a specific order, however successful exploitation could lead to modification of ePHI, PHI, or PII. The result co...
[]
null
null
5.7
null
ICSA-20-343-03
Schneider Electric Easergy T300
The affected product is vulnerable to a missing authentication for critical function vulnerability, which may allow an attacker to expose information, cause a denial-of-service condition, and remotely execute arbitrary code.CVE-2020-7561 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been cal...
[]
null
null
6.3
null
ICSA-20-042-12
Siemens SIPROTEC 4 and SIPROTEC Compact
Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Si...
[]
null
7.5
null
null
ICSA-23-157-02
Mitsubishi Electric MELSEC iQ-R Series/iQ-F Series
Authentication bypass vulnerability in FTP function on EtherNet/IP module due to weak password requirements allows a remote unauthenticated attacker to access to the module via FTP by dictionary attack or password sniffing. Authentication bypass vulnerability in FTP function on EtherNet/IP module due to use of hard-co...
[]
null
null
6.3
null
ICSA-21-194-13
Siemens SINAMICS PERFECT HARMONY GH180 (Update A)
A remote unauthenticated attacker with network access could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks. CVE-2020-15782 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been calculated; the CVSS vector string is (AV:N/AC:H/...
[]
null
null
8.1
null
ICSA-17-208-04
Rockwell Automation Allen-Bradley Stratix and ArmorStratix
Cisco Systems, Inc. has identified multiple SNMP remote code execution vulnerabilities in Cisco IOS and IOS XE Software affecting version of Allen-Bradley Stratix and ArmorStratix. To exploit these vulnerabilities via SNMP v2c or earlier, attacker must know the SNMP read-only community string for the affected system. T...
[]
null
null
8.8
null
ICSMA-23-331-01
BD FACSChorus
In BD FACSChorus v5.0, v5.1, v3.0, and v3.1, the respective workstation operating system does not restrict what devices can interact with its USB ports. If exploited, a threat actor with physical access to the workstation could gain access to system information and potentially exfiltrate data. In the BD FACSChorus v5.0...
[]
null
3.2
null
null
ICSMA-20-343-01
GE Healthcare Imaging and Ultrasound Products
The affected products may allow specific credentials to be exposed during transport over the network.CVE-2020-25175 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The affected products may allow exposed/default c...
[]
null
null
9.8
null
ICSA-18-354-01
Horner Automation Cscape
An improper input validation vulnerability has been identified that may be exploited by processing specially crafted POC files lacking user input validation. This may allow an attacker to read confidential information and remotely execute arbitrary code.CVE-2018-19005 has been assigned to this vulnerability. A CVSS v3 ...
[]
null
null
6.6
null
ICSA-21-182-04
Mitsubishi Electric Air Conditioning System
Web functions of Mitsubishi Electric air conditioning systems have a privilege escalation vulnerability due to incorrect implementation of the authentication algorithm. This vulnerability may allow an attacker to impersonate an administrator and tamper with information (e.g., operation information and configuration of ...
[]
null
null
7.1
null
ICSA-17-250-01
SpiderControl SCADA Web Server
Authenticated, non-administrative local users are able to alter service executables with escalated privileges which could allow an attacker to execute arbitrary code under the context of the current system services.CVE-2017-12728 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; th...
[]
null
null
5.3
null
ICSA-23-150-01
Advantech WebAccess/SCADA
If an attacker can trick an authenticated user into loading a maliciously crafted .zip file onto Advantech WebAccess version 8.4.5, a web shell could be used to give the attacker full control of the SCADA server.
[]
null
null
7.3
null
ICSA-19-122-03
Sierra Wireless AirLink ALEOS (Update B)
A specially crafted authenticated HTTP request can inject arbitrary commands, resulting in remote code execution.CVE-2018-4061 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H). Activating SNMPD outside of the WebUI ...
[]
null
null
5.9
null
ICSA-19-155-02
PHOENIX CONTACT FL NAT SMx
An unauthorized user can access the web interface using an authorized IP address, which may allow full access to the device configuration. This attack is only possible if an authorized session is still active on the system.CVE-2019-9744 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calcu...
[]
null
null
8.8
null
ICSA-21-194-10
Siemens RUGGEDCOM ROS
The DHCP client in affected devices fails to properly sanitize incoming DHCP packets. This could allow an unauthenticated remote attacker to cause memory to be overwritten, potentially allowing remote code execution.
[]
null
8.1
null
null
ICSA-18-219-01
Delta Electronics CNCSoft and ScreenEditor
Multiple stack-based buffer overflow vulnerabilities cause the software to crash due to lacking user input validation before copying data from project files onto the stack. CVE-2018-10636 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI...
[]
null
null
4.3
null
ICSA-23-255-01
Hitachi Energy Lumada APM Edge
The public API function BIO_new_NDEF is a helper function used for streaming ASN.1 data via a BIO. It is primarily used internally to OpenSSL to support the SMIME, CMS and PKCS7 streaming capabilities, but may also be called directly by end user applications. The function receives a BIO from the caller, prepends a new ...
[]
null
null
5.9
null
ICSA-21-049-02
Mitsubishi Electric FA Engineering Software Products (Update F)
A malicious attacker may cause a denial-of-service condition by spoofing MELSEC, GOT, or FREQROL, and returning crafted reply packets.CVE-2021-20587 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). A malicious atta...
[]
null
null
7.5
null
ICSA-22-258-04
Siemens Mendix SAML Module
Affected versions of the module insufficiently protect from packet capture replay. This could allow unauthorized remote attackers to bypass authentication and get access to the application. For compatibility reasons, fix versions still contain this issue, but only when the not recommended, non default configuration ...
[]
null
7.4
null
null
ICSA-20-219-03
Geutebrück G-Cam and G-Code
Using a specially crafted URL command, a remote authenticated user can execute commands as root.CVE-2020-16205 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).
[]
null
null
7.2
null
ICSA-18-004-01
Delta Electronics Delta Industrial Automation Screen Editor
Stack-based buffer overflow vulnerabilities caused by processing specially crafted .dpb files may allow an attacker to remotely execute arbitrary code.CVE-2017-16751 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H)....
[]
null
null
5.5
null
ICSA-19-157-01
Optergy Proton Enterprise Building Management System
The application suffers from username disclosure via its username reset functionality. An attacker can enumerate and disclose all the valid users on the system. Furthermore, when calling a certain page from a remote location, the following internal information can be divulged for the current system: Name, Internal IP A...
[]
null
null
7.3
null
ICSA-18-275-01
Delta Electronics ISPSoft
By opening a crafted file, an attack can cause the application to read past the boundary allocated to a stack object, which could allow execution of code under the context of the application.CVE-2018-14800 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string i...
[]
null
null
5.3
null
ICSA-21-049-02
Mitsubishi Electric FA Engineering Software Products (Update F)
A malicious attacker may cause a denial-of-service condition by spoofing MELSEC, GOT, or FREQROL, and returning crafted reply packets.CVE-2021-20587 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H). A malicious atta...
[]
null
null
7.5
null
ICSMA-20-170-06
BD Alaris PCU (Update A)
The affected products incorporate a vulnerable Linux kernel which is vulnerable to uncontrolled resource consumption due to a hard-coded Linux kernel maximum segment size overflow. This could allow an attacker to cause a denial of service, affecting the wireless functionality of the vulnerable devices.CVE-2019-11479 ha...
[]
null
null
5.3
null
ICSA-21-217-01
HCC Embedded InterNiche TCP/IP stack, NicheLite (Update B)
When parsing DNS domain names, there are no checks on whether a domain name compression pointer is pointing within the bounds of the packet, which may result in an out-of-bounds read.CVE-2020-25767 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/...
[]
null
null
7.5
null
ICSA-20-191-01
Phoenix Contact Automation Worx Software Suite
Due to insufficient input data validation while processing project files the buffer could be overflown. An attacker could use a specially crafted project file to exploit and execute code under the privileges of the application.CVE-2020-12497 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been ...
[]
null
null
7.8
null
ICSA-19-078-02
Columbia Weather Systems MicroServer
A cross-site scripting error exists that does not properly validate input, which may allow arbitrary web script to be executed.CVE-2018-18875 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L). A path traversal vulner...
[]
null
null
7.3
null
ICSA-21-315-01
WECON PLC Editor
The affected product is vulnerable to a stack-based buffer overflow while processing project files, which may allow an attacker to execute arbitrary code.CVE-2021-42705 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:...
[]
null
null
7.8
null
ICSA-20-161-02
Mitsubishi Electric MELSEC iQ-R Series (Update C)
An attacker can cause a denial-of-service condition at the Ethernet port by sending a specially crafted packet.CVE-2020-13238 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).
[]
null
null
5.3
null
ICSA-22-013-03
Siemens Energy PLUSCONTROL
ICMP echo packets with fake IP options allow sending ICMP echo reply messages to arbitrary hosts on the network. (FSMD-2021-0004) The total length of an UDP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on a use...
[]
null
7.5
null
null
ICSA-22-097-02
ABB SPIET800 and PNI800
The affected product is vulnerable to errors in handling out-of-order packets, which may cause the device to stop responding to any Ethernet-based requests. The resulting denial-of-service condition will not self-resolve, requiring a reboot to restore normal operation.CVE-2021-22285 has been assigned to this vulnerabil...
[]
null
null
7.5
null
ICSA-22-069-03
Siemens SINEC NMS
A privileged authenticated attacker could execute arbitrary commands in the local database by sending specially crafted requests to the webserver of the affected application. The affected system allows to upload JSON objects that are deserialized to Java objects. Due to insecure deserialization of user-supplied content...
[]
null
7.3
null
null
ICSA-17-341-03
PHOENIX CONTACT FL COMSERVER, FL COM SERVER, and PSI-MODEM/ETH
The cross-site scripting vulnerability has been identified, which may allow remote code execution.CVE-2017-16723 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:N/I:L/A:H).
[]
null
null
8.2
null
ICSA-22-270-03
Rockwell Automation ThinManager ThinServer
The affected product is vulnerable to a heap-based buffer overflow. An attacker could send a specifically crafted TFTP or HTTPS request, causing a heap-based buffer overflow that crashes the ThinServer process. This could expose the server to arbitrary remote code execution.CVE-2022-38742 has been assigned to this vuln...
[]
null
null
8.1
null
ICSA-20-210-01
Secomea GateManager
An attacker can send a negative value and overwrite arbitrary data.CVE-2020-14500 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). The affected product is vulnerable to an off-by-one error, which may allow an attack...
[]
null
null
9.1
null
ICSA-24-226-04
Rockwell Automation Pavilion8
A vulnerability exists in the affected product due to lack of encryption of sensitive information. The vulnerability results in data being sent between the Console and the Dashboard without encryption, which can be seen in the logs of proxy servers, potentially impacting the data's confidentiality.
[]
null
7.4
null
null
ICSA-22-097-02
ABB SPIET800 and PNI800
The affected product is vulnerable to errors in handling out-of-order packets, which may cause the device to stop responding to any Ethernet-based requests. The resulting denial-of-service condition will not self-resolve, requiring a reboot to restore normal operation.CVE-2021-22285 has been assigned to this vulnerabil...
[]
null
null
7.5
null
ICSA-18-046-03
Schneider Electric IGSS Mobile
IGSS Mobile app lacks certificate pinning during the TLS/SSL connection establishing process. This issue could allow an attacker to execute a man-in-the-middle attack. CVE-2017-9968 has been assigned to this vulnerability. A CVSS v3 base score of 6.4 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:R/S...
[]
null
null
6
null
ICSA-22-132-06
Siemens SIMATIC WinCC
An authenticated attacker could escape the WinCC Kiosk Mode by opening the printer dialog in the affected application in case no printer is installed. CVE-2022-24287 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
[]
null
7.8
null
null
ICSA-18-128-02
Siemens Siveillance VMS (Update A)
The Recording Server, Management Server, and Management Client on ports 6473/TCP local connection only, 7474/TCP, 8966/TCP local connection only, and port 9993/TCP use an exploitable .NET Framework Remoting deserialization level. The security vulnerability could be exploited by an attacker with access to the vulnerable...
[]
null
null
8.1
null
ICSA-22-195-05
Siemens RUGGEDCOM ROX
Affected devices do not properly validate user input, making them susceptible to command injection. An attacker with access to either the shell or the web CLI with administrator privileges could access the underlying operating system as the root user.
[]
null
7.2
null
null
ICSMA-21-343-01
Hillrom Welch Allyn Cardio Products
The impacted products, when configured to use SSO, are affected by an improper authentication vulnerability. This vulnerability allows the application to accept manual entry of any active directory (AD) account provisioned in the application without supplying a password, resulting in access to the application as the su...
[]
null
null
8.1
null
ICSA-23-152-02
HID Global SAFE
The External Visitor Manager portal of HID�s SAFE versions 5.8.0 through 5.11.3 are vulnerable to manipulation within web fields in the application programmable interface (API). An attacker could log in using account credentials available through a request generated by an internal user and then manipulate the visitor-i...
[]
null
7.3
null
null
ICSA-23-103-13
Siemens SCALANCE Switch Families
In Wind River VxWorks, memory allocator has a possible overflow in calculating the memory block's size to be allocated by calloc(). As a result, the actual memory allocated is smaller than the buffer size specified by the arguments, leading to memory corruption. An issue was discovered in Wind River VxWorks. The memory...
[]
null
9.8
null
null
ICSA-21-068-04
Siemens SINEMA Remote Connect Server
The webserver could allow unauthorized actions via special urls for unpriviledged users. The settings of the UMC authorization server could be changed to add a rogue server by an attacker authenticating with unprivilege user rights. Unpriviledged users can access services when guessing the url. An attacker could impact...
[]
null
6.3
null
null
ICSA-22-006-03
IDEC PLCs
An attacker may obtain the user credentials from the communication between the PLC and the software. As a result, the PLC user program may be uploaded, altered, and/or downloaded.CVE-2021-37400 has been assigned to this vulnerability. A CVSS v3 base score of 7.6 has been calculated; the CVSS vector string is (AV:A/AC:L...
[]
null
null
7.6
null
ICSA-21-315-06
Siemens SCALANCE W1750D
A remote buffer overflow vulnerability was discovered in HPE Aruba Instant (IAP). Successful exploitation could allow for unauthenticated remote code execution, potentially resulting in the execution of arbitrary code as a privileged user on the underlying system. CVE-2021-37726 has been assigned to this vulnerability....
[]
null
4.9
null
null
ICSA-24-030-03
Mitsubishi Electric MELSEC WS Series Ethernet Interface Module
An authentication bypass vulnerability exists in the MELSEC WS Series Ethernet Interface Modules. A remote unauthenticated attacker can bypass authentication by capture-replay attack and illegally login to the modules. As a result, the remote attacker who has logged in illegally may be able to disclose or tamper with t...
[]
null
5.9
null
null
ICSA-23-236-05
CODESYS Development System
In CODESYS Development System versions from 3.5.11.0 and before 3.5.19.20 a missing integrity check might allow an unauthenticated remote attacker to manipulate the content of notifications received via HTTP by the CODESYS notification server.
[]
null
null
9.6
null
ICSA-17-278-01A
GE CIMPLICITY (Update A)
A function reads a packet to indicate the next packet length. The next packet length is not verified, allowing a buffer overwrite that could lead to an arbitrary remote code execution. CVE-2017-12732 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been assigned; the CVSS vector string is (AV:A/...
[]
null
null
6.8
null