<s>[INST] Not Enabled alarm Summary: What cause the alarmWe have not- enabled alarm on 753 drive what could have caused that? the drive cant start/run because of that alarm [/INST] Look at parameter 933 - Start Inhibits, to figure out what is preventing you from running. https://literature.rockwellautomation.com/idc/gr... |
<s>[INST] FT View Client edition. I am wondering if there is a key/script in FT View Release number 13.00.00 (CPR 9 SR 13) that helps Client/Operator finding a tag in all screens. [/INST] The Find/Replace, Cross reference (You can find them from studio toolbar) can help finding tags on Graphic displays and other compon... |
<s>[INST] PF755 with UFB feedback card connected to full digital SSI IFM encoder model RM8001. Bad velocity feedback. PF755 20G11NC060JA0NNN, firmware 16.002 20-750-UFB-1, firmware 1.015 I'm testing a lifting application. In this application is very importat to know the position of the load. In order to know load posit... |
<s>[INST] PF525 testing Can I test my controls for a Powerflex 525 with no motor load? Do any parameters need to be changed to do this? [/INST] Welcome to the Forum ! PF525 will run also without a load connected to it. Just use the parameters you need for your application. PowerFlex drive will output a voltage and a fr... |
<s>[INST] Changing Axis From Position to Torque Mode I'm working on an application that requires the axis to be configured initally as position then changed by the controller program to torque mode. The system is compact logix with Ultra 3000 Sercos. Thanks [/INST] Try to see if Aid 42101 and Aid 44359 could help... Ta... |
<s>[INST] PowerFlex 70 Drive Parameters Is there a way to extract the drive parameters from a powerflex drive that is connect to a PLC5 processor by RIO? I know Drive Executive is not an option but wanted to see if there was another way other than manually recording them. [/INST] Unfortunately, no way.... :smileysad: Y... |
<s>[INST] Kinetix Drive Tripping on E07/E64 fault in MPL Series motor In one of our engineering project we have Kinetix 6000 drives on sercos with MPL series motors 1. Kinetix 6000 Drives2. MPL series Motors3. 2090-UXNFBMP-S15/S20/S30 Series CProblem Being Faced:-We are consistently facing motor feedback noise faults o... |
<s>[INST] Ultra 3000 error code 44 Is there an explanation of error code 44. The tech note i looked at references something about the current power cycle which does not make sense. What will cause the fault and how can you reset it. Does it require that you power down the entire system to clear it. [/INST] Prevention: ... |
<s>[INST] PF700S User Sets Hi! Does anybody know if it's possible to use a feature like PF70/700 User Sets in PF700S drives? I need to run two different motors with just one PF700S and need to reconfigure the drives using a digital input.Thanks.Marcinio - PU2MAS [/INST] PF700s actually doesn't have this feature... You ... |
<s>[INST] FlexPak 3000 Meter Out Signal Type I cannot find anywhere in any manual that I have looked at where it says what type of output the drive's Meter Out 1 & 2 are. Are they voltage? Current? Can we select which? They show that you can select what the analog outs are if you have the expansion board, but not the b... |
<s>[INST] Looking for a good example of speed/position stand alone master/slave for PF755 Hello, I have a customer that has an application with a dual shaft mixer where he is looking to keep the two shafts 180 degrees out of sync with one another using PF755 and absolute encoders as a stand alone application. Is there ... |
<s>[INST] PF70 EC / PF700 VC DriveStatus_AtSpeed bit Hi, I am using a PF700 VC drive and two PF70 EC drives. In my ControlLogix PLC, I am communicating with these drives over Ethernet/IP via 20-COMM-E modules. In my logic, I'd like to make use of the DriveStatus_AtSpeed bit in each of these drives. I am finding that th... |
<s>[INST] Servo motor moves without any order Hi everybody! I introduce me, I'm Camilo from Argentina, and first of all, sorry my english, it's awful, I know! Ok, I'm working in a depalletizer of bottles, what uses 11 servo motors AB, with Kinetix 6000 controllers. The plc is a ControlLogix 5561. The problem is that, a... |
<s>[INST] power flex 40 Summary: need to set rpm according to time entryhell0 i have a power flex 40 drive which i am using in a hydraulic pump now i want any hmi by which i can enter the time value and then accorig to this time valu my drive rpm will set ..example if i enter 60 minuts my drive rpm will set in such man... |
<s>[INST] CIP Messaging in Studio. Is anyone aware of a CIP document that lists your parameter fields shown above (Service Code, Class, etc.) and what the numbers correspond to? [/INST] There are two places: 1. The Rockwell knowledgebase has many of these outlined for various use cases and products: https://rockwellaut... |
<s>[INST] 755 Motion Feed Back fault Summary: Feedback Data Loss FL Fault Hi I have an application where I am using a 755 drive as a motion drive over ethernet controlled by a L73 cpu rev 20. I managed to commission before the hardware got delivered to site and all functioned well. At site I am getting a FeedbackDataLo... |
<s>[INST] Servo Motors and Air Cylinders Hi, I'm looking for a way to make an air cylinder reach its extended position when my servo axis reaches a certain position. The cylinder and servo are 2 separate things. The servo is controlling an elevator type device (up/down) and the cylinder moves a knob in/out to the eleva... |
<s>[INST] Kinetix 300 PositionCommand Problems Summary: Kinetix 300 PositionCommand Shows non commanded valueAt irregular intervals when I command the drive back to 0 (Using K300_EIPMove_AOI) it does not go all the way to 0. It just sits at an actual position of ~2.5 . When i check the I.CommandPosition tag in logix th... |
<s>[INST] ActiveX Gauges and Instrumentation. I was wondering if there is an ActiveX instrumentation package provided by Rockwell, if so, where can I find this? If not is there a recommended 3rd party software that is reputable. I am running FactoryTalk View SE vs.11. [/INST] ActiveX objects are software components s... |
<s>[INST] Ultra 3000 and MPL-A1530U-Ej42aa I have the drive motor combination of the subject. I dont see the motor in the Ultraware list of available motors. Will the Ultra identify the motor? Must I enter a new parameter file to the Ultra? How do I do it? [/INST] hiro, you need to update your Ultraware motor database.... |
<s>[INST] PF700 Error - No Device Application Code Summary: Drive Firmware Reload I have a drive, repaired less than a year ago, that was recently returned to service. The drive powered-up and checked out. Two weeks later, when we planned to put the drive in service, it wouldn't respond. The HIM displayed the following... |
<s>[INST] POWER FLEX 755 X 08 NOT FUNCTIONING, X 05 NOT FUNCTIONING Summary: Drive doesn't start without clearing this faultENVIRONMENT:<o:p></o:p> CAT NO: 20G1A NC 140 AA0NNNNN (Series A) S/N: 27609796 FRN: 9.001 MFD: 2013/07/12<o:p></o:p> CUSTOMER: Ball Beverage Packaging India Pvt. Ltd.<o:p></o:p> QUESTION: As per t... |
<s>[INST] Voltage Signal drop at Powerflex700 drive Dear All, I had installed a Powerflex700 drive and the DDC system employs Voltage analog(0-10Vdc) control to vary the VFDspeed. However, when the system wiring completed and proceed to T&C, the voltage signal was dropped to 7.6Vdc when the DDC Analog output is 10Vdc. ... |
<s>[INST] ultra5000 couldn't get new inertia after attached a load motor our product are ultra5000 and MPL-430P-H motor, use ultraware control. we can get a new inertia after attached a gear to MPL-430P-H, but when we attached our load motor, we couldn't get a new inertia and enter intor error code 23. How shall we do ... |
<s>[INST] PowerFlex 753 Motor Cable Length Is there Motor Cable Length Restrictions Table for PowerFlex 753? [/INST] Informations about Motor Cable Length restrictions are, for all the Rockwell Automation drives, inside the Wiring and Grounding Guide This manual doesn't contain yet a specific table about new PF750 seri... |
<s>[INST] Rotary.ServoFault We have a single servo motor that is controlled by an Ultra 3000 and a 1756-M02AE card / Controllogix. We are getting a servo fault through the PLC program, not the Ultra 3000. The Rotary.Servofault code reads: 16 [/INST] If you're reading the Axis Servo Fault Attribute, that value in the ta... |
<s>[INST] PF700S I am looking for example programs for the PF700s drive. This application is speed matching two machine sections using two PF 700s 7.5 hp drives with synchlink. The application is a bottling machine with a filler section and a sealer (capper) section, the two sections are not physically connected and th... |
<s>[INST] A large dumb drive Hi.Is there anyone else here who quite often needs a large drive (75kw - 315kw) that does not need a great lot of smarts. We do a lot of water pumping jobs so we really don't need all the bells and whistles. We just need rudimentary speed control, EMC filtering (built in) with an ethernet p... |
<s>[INST] 1336E BRF 20 AN impact drive , open frame Summary: Input DC voltage application Hi all. This drive according to its catalog number can use input voltages of 380-480V AC or 513-612V DC. Does anybody have experience with this DC option, is this for the brake only or it could supplement the 3 phase AC input ?If ... |
<s>[INST] Incommunicative Kinetix 5500 Drive (New out of box) I am having an issue getting my servo drives up and running. The PLC is an AB Compact Logix 5380 and the firmware has been updated and I can communicate just fine with it. It will not however communicate with my Kinetix 5500 Servo Drive. I have tried module ... |
<s>[INST] PowerFlex 755 w/CIP Motion - position error held to zero Summary: Servo loop will only run with velocity feed-forward, but will not move at any value of Kp. Environment: Drive - PowerFlex 755, 8A Normal Duty, Stardard Motor - Toshiba – Vector Duty, 3Hp,1800,182TC,TENV,230/460V/60Hz PLC - ControlLogix 1756-L72... |
<s>[INST] Powerflex4, 40, 4M, 525 not following orders.... Summary: They do not follow cmd. freq. nor stop when told to. Hi all, Has anyone experienced their drives not following orders, such as command freq. (the drives tend to hunt around, even to go beyond max freq.) or what's worse, they don't stop when told to. Wh... |
<s>[INST] Encoder 845H I got an 845H encoder connected to a 1769-HSC module, when I power up the encoder my reading increase for CW rotation and decrease for CCW rotation, I just need the opposite, I connected encoder channel A to module channel A1, some clue? Thanks. [/INST] If you are using quadrature mode, you may s... |
<s>[INST] PowerFlex 755 HiP Summary: Codigos de error 49 y 48 en display de 7 segmentos en el interior del power flex 755 HiPTengo un problema con un PowerFlex 755 HiP, los fusibles de entrada antes de la bobina de choque (reactor), se abrieron, despues se volvio a reponer los fusibles, pero al energizar el drive me sa... |
<s>[INST] information hi, my name is Luca, I just started using Rockwell.I have a question? With the power flex 40 i can monitor engine load and then adjust the speed. es. A motor that is moving a propeller in a dense material. if the motor go to 30Hz and at some point starts to grow absorption, the motor have difficul... |
<s>[INST] ULTRA MASTER SOFTWARE I have ultra master software and need a it to allow me to create a custom motor file. Currently, the fields are grayed out. I have ver 1.6Todd [/INST] Here the solution for you... :smileytongue: Take a look to the following screenshot.... I have test it using version 1.62 available to do... |
<s>[INST] Powerflex family parameter list Summary: Parameter spreadsheetDoes anyone know if the powerflex parameter lists are available in spreadsheet format? [/INST] Both Drive Executive and Drive Explorer can save the parameters to a text file that can be imported into Excel. File -> Save As -> .csv and Select the pa... |
<s>[INST] Ultra 5000 logic for a leading edge sensor for registration mark Ok, so I am one of the sick people that use the Ultra 5000, it fit the budget and the project design. I was wondering if anybody has any better logic than this for a registration sensor. The sensor starts off blocked, clears between parts, and t... |
<s>[INST] PF750 drive keep decelerating status not stopped when stop command issues A PF750 drive with 20F11NC085JA0NNNNN. When stop command issues, drive ramp to zero ,but drive continue to keep decelerating status but not stopped. When restart command issue, the drive cannot start. The drive is connected with digital... |
<s>[INST] Gearing questions I have a 1000ppr encoder on axis 1 (Sorter Drive) and 1000ppr encoder on axis 2 (Cut-N-Two Drive). At any given point, I need to go to half speed on axis 2 then back up following axis 1 in a short distance. The application is a Planer Sorter and a Cut-N-Two Drive. Currently I use the PLC to ... |
<s>[INST] PowerFlex 525 Downloads Summary: Trouble downloading/locating electronic data sheets for devicenet mapping of powerflex 525 VFD'sI have found and was able to download the technical data sheet device definition file for a 460V 3 HP drive VFD, but I can't seem to find a drive for a 460V 50 HP drive VFD. I need ... |
<s>[INST] PF755 How to proof test shear pin current limit Summary: Assuming shear pin been underpinned by Rockwell (TUV), should shear pin limit be physically tested?The PF753/755 offers shear pin current limit, but has this been underpinned by Rockwell (TUV) to work? Or should the shear pin limit be physically test? I... |
<s>[INST] Latest Kinetix Firmware 1.116 help Rockwell published this firmware a couple of weeks ago. As of version 1.114 they added remote control of the brake control relay when the drive is disabled. This is from the release notes- This enhancement corresponds to Kinetix 6000 drive firmware revision 1.114 or later, w... |
<s>[INST] Kinetix 5700 to 5500 migration Hi I have a requirement to migrate kinetix 5700 drives onto the 5500 platform, initially it looks pretty straight forward but the 5700 drives have a configurable input setup as an external enable, unfortunately this enable input is not available on the 5500 drives. Both models o... |
<s>[INST] Driven Unwind for Web Tension Control Summary: Please recommend a motor / drive combination Hi, I am trying to pick out a motor / drive combination to handle a driven unwind on a piece of web handling equipment. This unwind will feed a spool of web through a series of rollers that guide it through a machine f... |
<s>[INST] Usage of Drive Logic Command Bits over comm link? Hi, I am going to be using a PowerFlex 70 Enhanced Control drive for the first time. I ordered this with a 20-COMM-E Ethernet/IP to DPI Comm Adaptor. I will be using a ControlLogix PLC with a 1756-ENBT Ethernet/IP module. I'd like this CLX PLC to be completely... |
<s>[INST] Cyclone pump motor Summary: Change of speed, pressure and currentGood day, We have, 550V ac, 220KW motor pushing a cyclone pump. But after changing the propeller the motor misbehaved. At sometime the pressure and current drops and at same time speed slightly increases this happens in the intervals of say 20 m... |
<s>[INST] Powerflex 40P DSI can i use the DSI port on a power flex 40p for IO?? looking to use ethernet comms for controlling the drive but wondered if i could get point i/o or something to hang off the DSI port also [/INST] No, you can't do that... DSI port is only for remote HIM, RS-485 connection to other drives or ... |
<s>[INST] Looking for serial comm module to add two serial ports to 1756 system I have looked all over and I can not find a two port RS-232 serial interface card for my 1756 Contrologix system. Can anyone help? [/INST] Try to search HERE ... Prosoft is a Rockwell Automation Encompass Product Partner I suggest the MVI56... |
<s>[INST] kinetix 6000 drive no display on front just a period Summary: Kinetix 6000 E37 & blank displayThe drive ran fine for a while today. Then the main axis faulted E37 and the drive next to it shows no digits just blank on display other than a period in bottom right corner of display. [/INST] E37 is power phase lo... |
<s>[INST] Megger Servo Motor TL-A230P Is there any issue with Meggering a Servo Motor? I don't see why it would be different from any other AC Motor, but before I try it I want to make sure it won't damage the motor. The specific motor I want to check is an TL-A230P-Bxx2. Since it is rated for 230V, I would only megger... |
<s>[INST] 160 Drive Just curious what is the last date that the 160 drive will be available for sale. I'm trying to convert customer to PowerFlex 4M. Thanks. [/INST] Silver Date for these products is 31 dec 2009 The Silver Date is the last date Rockwell Automation will accept orders for new product shipments, terminati... |
<s>[INST] Circular Interpolation with L30ERM? Summary: Is it possible to create a circular motion with an L30ERM (or less?) CPU and a Kinetics? [/INST] Yes. There are some native instructions inside Logix5000 to do this. Take a look at the Motion Coordinated instructions: MCS MCLM MCCM MCCD MCSD etc. Look in the logix5... |
<s>[INST] Powerflex 700 PTC using Siemens 1PH7 motor I am using a Powerflex 700 to control a Siemens 1PH7 motor. The 1PH7 has a KTY 84 thermistor PTC. According to the Powerflex 700 user manual the HW PTC input (terminals 10 and 23) are for a 1.8k ohm PTC sensor. The Siemens documentation shows the KTY 84 is a resistan... |
<s>[INST] PF 755 syncronized velocity Hello experts. I want to impelement a application with 2 PF755 involved. They are configurated as thw differenet axes in the same Motion Group as Position Loop. The first drive moves at a certain velocity using the JOG command, and I want that the second drive to move at the same v... |
<s>[INST] Inversores PowerFlex 525 Summary: Falhas em - F111 e após F101Satisfação a todos ! Em uma maquina de envase de liquido equipado com Inversores PowerFlex 525, 1° controla mesa giratoria e 2° controla esteira de produto, apresentou certo eventos de alarmes nada comum para nos, primeira anomalia foi a falha no d... |
<s>[INST] Kinetix 5100, disconnect encoder without fault. I would like to know if it is possible, by ethernet ip, to disable the kinetix 5100 drive, it is to be able to disconnect the encoder (through an ATI tool changer), so that, while it is energized, to be able to make the change, and it does not cause an non-recov... |
<s>[INST] How to send commandos to Ultra 3000 by RSlogix500 RS232 HelloI have an Ultra3000i and a Micrologix1200, and I want to send commands from the PLC to the Ultra 3000 by Serial com.Could the MSG command works? How can I configure this instruction?example: I want to send the next command to the Ultra to enable de ... |
<s>[INST] Powerflex 700 fault Hi, We have experienced a few Powerflex 700 drive - Fault 24 (Decel Inhibit) errors over the last week. The drive supplies 2 motors in parallel on a printing press reelstand. We initially changed the drive but the fault occurred again. Every time it has happened the press was running at sp... |
<s>[INST] PLC5 & PFlex using Datalinks over DeviceNet Is it possible to use datalinks, over DeviceNet, with new PFlex 755 and PLC5? PLC5 only being able to do 16 bit and PFlex using 32 bit. Some drives, I think, had a way to set the type of size for the datalinks, either 16 or 32. Thanks, [/INST] Try to take a look to ... |
<s>[INST] PowerFlex 70 drive.Ready Under what conditions does the drivename.Ready bit from the drive go low?? I assume if the drive is powered up, and not faulted, the drivename.Ready bit will be high. Is that correct?? thanks, alan [/INST] Not exactly... :smileytongue: Here the conditions that makes drive ready bit on... |
<s>[INST] myRockwell Automation not loading. I'm trying to get to my +Learning account but when I log into Rockwell Automation all I get is a loading screen. It will sit on the attached image with the red circle rotating for hours. Do I need to clear my cookies or something? [/INST] Do you have any AdBlockers enabled... |
<s>[INST] How to do parameter changes in Armorstart St 284GS like Powerflex. I am new to Armorstart ST 284GS drives. I cound not find any software to configure the parameter for this drive. How to change the parameter? Any software avaialble? in Studio 5000 V33 , Armostart AOP 1.0068 using . there is no parameter optio... |
<s>[INST] Kinetix drives only phasing up to 3... I have 6 drives, on a 1756-M08SE, this is a new startup. Why are my K6K drives only phasing up to 3? [/INST] Are all feedback cables connected? Also is the correct motor selected in RS 5000? Any errors in logix? http://rockwellautomation.custhelp.com/cgi-bin/rockwellauto... |
<s>[INST] 1398-PDM-75 + F-6100 motor bad problem at aux. circuits reset (rare but happening) Summary: 1398-PDM-75 sometimes makes F-6100 motor running away at auxiliary circuits resetI've done many applications since 1998 with 1398-PDM-75 + F-6100 brushless motors. Never had big issues except in an application where, i... |
<s>[INST] I am creating an app using Python or C# and want to read and write tags using my app. How can I do this? Any suggestions? [/INST] ou need an EtherNet/IP protocol stack that specifically support vendor-specific services for R/W Logix5000 data. You can purchase FactoryTalk Linx Gateway which includes a SDK ... |
<s>[INST] Kientix 5700 Feedback Integrity Loss I have a system that has several Kientix 5700 servos responsible for row forming for a palatizing system. According to the customer, for about the past month they have had intermitten instances where one of the 6 row formers faulting out. They had the issue this morning an... |
<s>[INST] Subscribe to E-mails for Specific Keywords or #hashtags Is there a way to subscribe to e-mail updates on specific hashtags, such as [/INST] This is a little bit off the topic, but you can subscribe to product update on the PCDC. This includes new releases, PN, PSA. Soon to be expanded to 'coming soon' and rel... |
<s>[INST] PF40 - Ref Speed w pot With PF40, I use pot for speed reference.With a time ( 4 years) my reference lower ≈ 48 HzI change my drive, the speed reference is OK, with same wiring and a same config. I don't know if this case is documented? [/INST] Do you mean the embedded potentiometer on PF40 or a remote potenti... |
<s>[INST] Frequent Motor Starting I have a case conveyor application that requires frequent starting/stopping of a 1/2 HP squirrel cage motor at 10 times per minute. (3 seconds on - 3 seconds off). I am concerned that if I use a NEMA starter for this application that it will beat itself to death within a year or so. Wo... |
<s>[INST] Using Explicit Messaging to set / write commands to a PF525 VFD. I am trying to send (set) start/stop, direction, and speed reference commands to my PF525 VFD. I was able to get all sorts of information from the drive using explicit messaging. I was also able to set accel & decel times. I have set my VFD star... |
<s>[INST] ControlFLASH Plus V2 is available for download - Free of charge All, ControlFLASH Plus software version 2, part of the Studio 5000 software release, is now available. Updates focus on enhanced productivity. New features include seamless PCDC connectivity in flash devices and manage firmware for download of fi... |
<s>[INST] PF70 w RIO Logic Status Bit 6 - Alarm Detail Summary: What does Logic Status Bit 6 Alarm Indicate on PF70 w RIO ? Hi, I have upgraded some drives from 1336Plus to Powerflex70, The drives are on an RIO network. Tidied up PLC code and configs to get the drives running and they are running fine but I am now gett... |
<s>[INST] flashing/converting a pf525 back to a standalone drive after i have set it for multidrive Summary: i can not download to the drive to make it a standalone drive hello can you advise. I made my 525 multidrive, for a presentation, and now I can not get it back to a standalone drive. I tried studio ver 24, ccw v... |
<s>[INST] Faulty Drive / Faulty Kinetix Hello,1. Is it possible for a faulty servo motor to make a kinetix go bad and vice versa? 2. If a kinetix unit does not come up again what could possibly have gone wrong. regards, K. [/INST] Duplicated thread... the one in the correct board is HERE.... - fuzzy logic \\n </s> |
<s>[INST] DECEL rate versus overshoot. I use PowerFlex 700 drive in Pos/Spd Prof mode (Speed/Torque Mod P88). I noticed that Decel Rate (p142) impact positionning overshoot. If I increase the value of Decel , the final positionning overshoot more . The step type is encoder abs. My logic tells to myself that the longer ... |
<s>[INST] PF400 Parameter lock password lost Hi all, I have bought [/INST] Have you tried following the [Reset to Defaults] procedure, in the user manual? https://literature.rockwellautomation.com/idc/groups/literature/documents/um/22c-um001_-en-e.pdf \\n </s> |
<s>[INST] Pwerflex 700H does not start I have a PF700H that when I issue a start command does not start (20CC300A0A...). The 'start owner' indicates a 1. The 'stop owner' is 0, 'start inhibits' is 0, on 'drive status 2' the active bit and the running bit are 1 (after I have issued a start command). The 'commanded frequ... |
<s>[INST] Changing GML Turbo communication Hi all, I've here a GML Turbo whichhas a communication by RIO with the PLC-5 processor.We gone change the PLC-5 for a L35 compact-logix, and need to change the communication to DH-485. I've readed the 900 page manual of GML, but can't find any instruction to setup a DH-485 com... |
<s>[INST] Kinetix 5500 stuck at precharge when servo motor is connected. I have kinetix 5500 with VPL-B1153F-P motor. When I disconnect the servo motor cable and give 24VDC and 480VAC drive stars up and DC bus voltages rises to 700V. Now when I connect the motor cable to the drive and give 24VDC and then 480VAC, the dr... |
<s>[INST] Powerflex 40 power leak Summary: Voltage creepWe have a Powerflex 40 that appears to continue sending a low voltage to the motor even when stopped, the motor creeps. The display shows no hz being sent to motor. My questions are... is this manageable with a parameter setting? Could the drive be bad? [/INST] It... |