s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 39 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
15
DEFINITIONS
2-1 GENERAL .
The definitions contained in this chapter apply to the terms used in this UFC. Where
terms are not defined in this chapter or within another chapter , they are defined in the
referenced UFC, code or standard applicable to the cont... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 40 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
16 \6\ CFPE /6/ offices are as follows /1/:
a. U.S. Army - HQ USACE/CECW -CE.
b. U.S. Navy - NAVFACENG SYSCOM HQ , \6\ Chief Fire Protection
Engineer /6/ .
c. U.S. Marine Corps - HQMC Code LF.
d. U.S. Air Force - AFCEC/CO .
e. \1\Defense Logistics Agency (... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 41 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
17 containing telecommunication equipment that serves more than one Facility , a portion of
an Installation or the entire Installation . This section does not apply to the room in a
Facility that contains the incoming telecommunications service fo r that spec... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 42 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
18
Fire Protection Engineer.
Designated (or Service) Fire Protection Engineer (DFPE).
The DoD fire protection engineer that oversees that Area of Responsibility for that
project . This is sometimes referred to as the “cognizant” fire protection engineer.
N... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 43 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
19
Major Project.
A project that includes any one of the following:
a. \5\ Adding /5/ to an existing Facility .
b. \5\Work to a facility that co nsists /5/ of 50 percent or more of the total floor
area of an existing Facility .
c. Design or construction of... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 44 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
20
Noncombustible Materi al.
A material that, in the form in which it is used and under the conditions anticipated will
not ignite, burn, support combustion, or release flammable vapors, when subjected to
fire or heat. Materials that are reported as passing AS... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 45 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
21 A pipe that transports water from the Distribution Main to the Service Lateral . A service
main can be connected to a Distribution Main , Service L ateral or another service main.
A main with three or more fire hydrants connected to it is a service main. A ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 46 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
22 This Pag e Intentionally Left Blank |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 47 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
23
USE AND OCCUPANCY CL ASSIFICATION
3-1 GENERAL
This UFC utilizes criteria from both IBC and NFPA 101. Care must be exercised when
using this UFC to ensure proper use of IBC and NFPA 101.
3-2 INTERNATIONAL BUILDI NG CODE (IBC).
General .
The IBC mu... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 48 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
24 “Occupancy Classification and Use” must be used /6/. Where the maximum allowable
quantities are exceeded in NFPA 400, the H occupancy classification (H -1, H-2, etc .)
must be defined in accordance with IBC for High-Hazard Group H occupancies , except
as mod... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 49 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
25
SPECIAL DETAILED REQUIREMENTS BASED ON USE
4-1 GENERAL .
This Chapter provides specific criteria for special or unique occupancies and hazards
and supersedes IBC Chapter 4 in its entirety. For special or unique occupancies and
hazards not addressed in... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 50 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
26 controls in such enclosures are provided with connection to the installation fire alarm
communic ation network by the installation.
Conform to the requirements listed in the paragraph entitled “Aircraft
Facilities” . Provide separate manual controls for act... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 51 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
27
\6\ Weather coverings are structures that control the amount of direct
sunlight on aircraft parked on the flight line , see Figure 4- 1 and Figure 4- 2. Weather
coverings used for aircraft on the flight line must comply with all of the following:
a. Const... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 52 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
28 Figure 4 -2 Example of Weather Covering
Facilities Housing Unmanned Aerial Vehicles (UAV) or Remotely Piloted
Aircraft (RPA).
\2\For this UFC, an Unmanned Aerial Vehicle (UAV) or Remotely Piloted
Aircraft (RPA) consists of just the vehicle; and, an U... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 53 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
29
Facilities designed to support \2\UAS, /2/ UAV, or RPA that have both of the
following must be \ 2\provided with sprinklers designed/2/ in accordance with NFPA 30,
\2\Storage of Liquids in Cont ainers – Storage Occupancies /2/:
a. Has a door opening less th... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 54 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
30 UAS housing area by 1- hour fire barrier walls. Floor elevations must be
arranged to prevent a spill within the UAV or UAS housing area from
flowing into adjacent areas. Adjacent areas are not permitted to have
their required egress through the UAV or UAS hou... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 55 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
31 will apply. Where it is not poss ible to meet all criteria, coordinate with the DFPE for
guidance. The service explosives safety regulations include:
• For Navy projects, NAVSEA OP -5, Volume 1.
• For Army projects, AR 385- 10 and DA PAM 385- 64
• For Air ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 56 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
32 occupancies from supporting spaces must not be less than the required separation of H -2
occupancies from other occupancies and must also comply with any fire rated
requirements of DESR 6055.09 and service explosive safety regulations .
[C] 4 -5.4.3
Sup... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 57 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
33 from one part of the operation to another. A mitigation w ould be 4- hour fire rated
concrete blast containment walls .
Exterior walls must be rated in accordance with IBC C hapter titled “ Types of
Construction”.
Fire Suppression Systems .
Complete au... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 58 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
34
Water Spray Systems: Water spray systems, including high speed and
ultra-high-speed deluge systems must be designed and installed in accordance with
NFPA 15 unless otherwise not ed herein or in the applicable DoD or Service explosives
safety regulation.
H... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 59 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
35 self-contained deluge systems are primarily intended for personnel protection, although
they provide limited building/equipment protection.
When used, self -contained deluge systems must be connected to the
existing water supply .
Portable, self -contained ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 60 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
36
Accessory Magazines and Armories . 4-5.7.1.1 Accessory magazines and
armories containing limited quantities of ammunition and explosives for reasons of
operational necessity at police stations, security facilit ies and similar type facilities are not
requ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 61 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
37 accomplished during the design, a preliminary risk assessment must be performe d. The
hazard(s) must be accurately defined. A potential fire or thermal hazard with an
unacceptable risk requires personnel protection in accordance with explosives safety
require... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 62 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
38
Due to combat mission needs it may be necessary to construct combat
related Ammunition and Explosives Facilities that do not comply with the detached
building requirement of IBC for H -1 and H -2 occupancies. Where an H -1 building area is
attached to a liv... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 63 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
39
Separate the room or space containing the anechoic chamber from the
remainder of the facility with 2- hour fire rated construction.
Provide sprinkler protection inside the anechoic chamber that complies with
the following “Sprinkler Protection” paragr aph i... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 64 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
40 This section applies to all DoD facilities housing government -owned or -managed
animals. These facilities must comply with NFPA 150 and the requirements of this
UFC.
This section does not apply to retail kennels, riding stables , private or club stables , or... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 65 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
41 Animal housing or animal research facilities may require smoke control in order to
ensure a clean atmosphere in the animal housing or research area is maintained in the
event of a fire. If products of combustion enter the animal housing or research area, it
co... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 66 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
42 A perimeter fence or wall in accordance with the installation’s facility standards must be
provided not less than 100 feet from the structure. An adjacent facility ext erior wall
maybe part of the perimeter separation.
[C] 4 -8.1.1
For information pertainin... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 67 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
43 The BESS- Li room must be dedicated to DoD owned and operated BESS -Li operation.
BESS- Li rooms must not be used for any other purpose other than the lithium batteries
and required/approved switching. Third party owned and operated BESS -Li that are
supporti... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 68 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
44 The partitions separating the battery cabinets or open battery racks will help limit the
spread of a fire from one battery or battery system to another. The partitions need to be
floor to ceiling/roof/floor above. Any penetrations need to be firestopped for an... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 69 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
45
Storage in BESS -Li Rooms. Flammable and combustible materials must
not be stored in BESS -Li rooms .
Use Group. For Building Code and Life Safety code purposes, BESS -Li
rooms in occupied structures must be classified as occupancy Use Group H -3.
Batter... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 70 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
46
Pulverizing Equipment.
Use components designed and constructed in accordance with requirements of NFPA
850.
4-11 COMMISSARIES AND EXC HANGES.
Mixed Occupancy.
Commissaries and Exchanges that are part of another facility (i.e., mixed occupancy) and the C... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 71 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
47
Provide for constant visual supervision of cell areas. Central supervisory
control area must be separated from cell areas by not less than one- hour fir e-rated
construction.
Fire alarm notification in cell areas must be at a constantly attended
location,... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 72 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
48
Telecom munication areas must comply with NFPA 76 , in lieu of NFPA 75 .
Buildings housing telecommunication areas must be of noncombustible construction.
Co-located Facility .
For Facilities that house telecommunication areas that have occupancies and ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 73 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
49 Note: Consult with the DFPE to determine the extent , or boundary, of the Electronic
Equipment Area.
For areas with finished ceilings, use concealed pendent or concealed
sidewall sprinklers. For areas without finished ceilings, use upright sprinklers... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 74 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
50
Electrical equipment must be protected by disconnecting the power upon
activation of the fire sprinkler system in the electronic spaces, unless power disconnect is
permitted by manual means indicated above.
The disconnect must be installed downstream of any... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 75 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
51
Activation of any elevator machine room, hoistway, or lobby smoke detector
must activate the Facility fire alarm system and send the affected elevator s to the
designated floor.
Sprinkler Protection .
Where sprinklers are provided in the Facility , provi... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 76 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
52 damage. Discharge to a floor drain may be permitted only if the drain is sized to
accommodate full flow (minimum of 40 gpm) . Discharge to service sinks or similar
plumbing fixt ures is not permitted.
The top of the hoistway and machine room sprinklers m... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 77 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
53 ROOM / AREA PROVIDE SPRINKLER
(Not Applicable for
Buildings Without Sprinkler
Protection) PROVIDE SMOKE DETECTOR to
INITIATE ELEVATOR
FIREFIGHTERS SERVICE and
BUILDING FIRE ALARM SYSTEM
MACHINE ROOM YES YES
ELEVATOR LOBBIES YES YES
PIT AREA YES NO ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 78 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
54
Elevator
Cab
Counter Weight
Machine Room
Figure 4-2 Electric Traction Elevator
Elevator Lobby
Elevator Lobby
Elevator Lobby
SD
SD
SD
Test
SD
FS |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 79 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
55
Machine Roo m
Elevator
Cab
Hydraulic
Piping
Figure 4-3 Direct Plunger Hydraulic Elevator
Elevator Lobby
Elevator Lobby
Elevator Lobby
SD
SD
SD
SD
Test
FS
No more than 24 inches
above the pit floor |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 80 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
56
4-17 EMERGENCY SERVICES C OMMUNICATIONS CENTERS.
Facilities and equipment that are used for the receipt of alarm sig nals and telephone
calls for assistance, and dispatching of fire, police, or emergency medical services
personnel and equipme... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 81 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
57 Family housing outside the United States and its territories and possessions , constru cted
or leased- constructed, must comply with provisions of this section and the H ost Nation
fire protection requirements .
DoD- Leased Family Housing.
DoD personnel oc... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 82 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
58
Residential type range top cooking surfaces must be equipped with a UL
300A listed residential range top extinguishing system or the cooking surface must be
equipped with burners and controls that have their temperature limited to a maximum
temperature of 6... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 83 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
59
A single building is often used for storage o f both flammable and
combustible liquids and hazardous materials. Requirements for the storage of hazardous
waste are separate and distinct from the storage of hazardous materials.
Comply with the requirements ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 84 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
60 c. Exterior walls must be of noncombustible construction when the Facility is
more than 50 f eet (15.3 m) from another building or property line.
d. Interior walls/ceilings must be 4- hour fire barriers if the Facility shares at
least one wall with a Facil... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 85 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
61
Walls must not obstruct more than two sides of the structure, or, walls may
obstruct portions of multiple sides of the structure, provided that the sum of the walls
does not exceed 50 percent of the structure’s perimeter. /2/
The outdoor storage area must ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 86 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
62 Mechanical penthouses and mechanical stories are not considered occupied floor
levels.
Buildings Greater than 420 f eet (128 m) .
The provisions of this UFC are not intended to appl y to buildings greater than 420 f eet
(128 m) in height. For buildings exc... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 87 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
63
Use of threaded pipe must be avoided. Where threaded connections are
used, requirements of ANSI B1.20.1 must be met. A safety factor of eight over normal
pressure must be used.
Tubing runs must have as few bends as possible, but must have at least
one be... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 88 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
64
Automatic fire suppression systems must be provided for all other indoor
transformers rated 35 kV or greater and all must be enclosed by 1 -hour fire -rated barriers.
Fire suppression system type must be one of the following.
a. Water mist system with o... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 89 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
65 b. Clean Agent in accordance with NFPA 2001.
Oil Storage and Oil Purification Rooms .
Oil storage and oil purification rooms must be protected by one of the following
automatic fire suppression systems .
a. Water mist system with operating pressure greater t... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 90 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
66 Hypobaric chambers must comply with NFPA 99B.
4-27 LABORATORIES .
General .
Laboratories using chemicals must comply with NFPA 45.
[C] 4 -27.1
The occupancy specific maximum allowable q uantities in NFPA 45 take precedence
over the general maximum all... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 91 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
67
A manually activated smoke exhaust system must be provided for
structures three stories or more in height. The smoke exhaust system must be designed
for a minimum of six air changes/hour throughout the entire building.
Provide complete automatic spri nk... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 92 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
68 4-33 MORALE WELFARE AND R ECREATION FACILITIES (MWR).
Clubs, bowling centers, craft shops (including hobby shops, woodworking, auto
centers) , and similar recreational facilities with an occupant load of 50 or more must be
protected with automatic sprinkler ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 93 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
69
Hose Station Requirements .
Hose stations in accordance with NFPA 14 must be located 25 feet upstream and
downstream of each gate. These hose stations must be equally spaced at no more than 300 feet intervals along the walls on both sides of the lock chamber.... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 94 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
70 4-36 OXYGEN .
General .
Comply with NFPA 55 and NFPA 400, except as modified by this UFC.
Gaseous oxygen ( GOX ).
Bulk GOX Systems.
Comply with provisions of NFPA 55 for the installation and location of bulk
GOX.
Bulk GOX must be located either abo... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 95 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
71
Fixed tanks having combined capacity of 100 gal (380 L) or less or portable
tanks , \2\/2/must comply with applicable provisions NFPA 51 and NFPA 99, regardless of
occupancy.
Where tanks have a single or combined capacity of more than 100 gal (380
L), tank... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 96 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
72 1) 1) Noncombustible construction having blank walls 10 ft (3 m) above
and 10 ft (3 m) on each side of the equipment .
Regulators and other control equipment are permitted to be located indoors
in a noncombustible building detached or cut off from main buildi ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 97 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
73
Automatic Sprinkler Protection.
Complete automatic sprinkler protection must be provided , regardless of floor area or
construction type.
Smoke Detection .
Provide smoke detectors in accordance with NFPA 101 .
A smoke detector must be provided for e... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 98 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
74
Locate facilities or operations involving the storage, mixing, or handling of
non-flammable pesticides a minimum of 100 f eet (30.5 m) from the nearest Facility or
occupied structure.
Facilities of Type I construction as defined by t he IBC, may be located... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 99 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
75 b. UFC 4 -150-02.
c. NFPA 30 .
d. NFPA 30A.
e. NFPA 307 (if liquids are handled in bulk quantities across general purpose
piers and wharves).
f. "Guide on Mar ine Terminal Fire Protection and Emergency Evacuation",
Oil Companies International Marine Forum ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 100 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
76
The separation distance between other equipment (including adjacent
transformers) must be as indicated in Table 4-5.
When fire barriers are utilized, comply with the following:
a. Barriers must be of concrete block or reinforced concrete construction
adeq... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 101 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
77 a. There must be no window openings in first -story walls within a horizontal
distance of 10 f eet (3 m) from the transformers. Existing window openings
must be closed using brick or concrete block.
b. Overhanging eaves, where they exist, must be noncombustib... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 102 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
78 Table 4-5 Separation Distance Between Outdoor Fluid Insulated Transformers and
Equipment ( Including Other Transformers)
Liquid Fluid Volume
gal (m³) Distance
ft. (m)
Less Flammable <10,000 (3 7.9) 5 (1.5)
>10,000 (3 7.9) 25 (7.6)
Mineral Oil <500 ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 103 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
79
Grouping: Pods separated by less than 4 feet (1.2 m) are considered a
group. The size of the group will be determined by the area of the pods, plus the area
between the pods. A group of pods having a total area less than 75 ft2 (7.0 m2) will follow
the req... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 104 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
80
Relocatable facilities must have the same fire protection \2\and/2/
construction \2\/2/requirements as non- relocatable facilities.
Provide a minimum separation of 50 f eet (15.3 m) between groups of high
hazard occupanc ies, as d efined by NFPA 101 and 15... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 105 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
81 (i.e. electric d oor strikes, magnetic locks, etc.) that would restrict single- motion door
operation.
Fire Alarm and Mass Notification System (MNS).
See UFC 4 -010-05 for requirements pertaining to the installation of fire
alarm and MNS devices within a S... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 106 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
82
The separation area must be a clear zone adjacent to the tension fabric
structure.
The clear zone cannot be used for storage and must be clear of vegetation
(maintained lawn is permitted).
The clear zone may be used as a street or driveway, but not fo... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 107 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
83 Provide automatic sprinklers in all trash /recycling chutes installed within a Facilit y
4-47 VEHICLE PARKING, STO RAGE, MAINTENANCE, A ND REPAIR
FACILITIES .
General.
Facilities used for parking or storage of motor vehicles must comply with
NFPA 88A.
... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 108 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
84
Complete automatic sprinkler protection must be provided for warehouses
and storage Facilities , rega rdless of floor area or construction type.
Automatic sprinkler systems may be omitted for Facilities with an area less
than 5,000 ft2 (465 m2) with app... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 109 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
85
Requirements.
Protect in accordance with NFPA 13, except as noted below.
The ceiling density must be increased by 10 percent or one additional level
of in-rack sprinklers where c ombustible bins are stored in racks.
Mini-storage and retrieval systems... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 110 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
86 4-49 WATERFRONT FACILITIE S.
Waterfront and harbor facilities must comply with all of the following, as applicable:
a. NFPA 303 .
b. NFPA 307 .
c. NFPA 312 .
d. UFC 4 -152-01.
e. UFC 4 -150-02.
f. UFC 4 -151-10.
g. UFC 4 -213-10.
h. UFC 4 -213-12
i. ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 111 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
87
GENERAL BUILDING HEIG HTS AND AREAS
5-1 GENERAL .
Allowances or exceptions that require the Facility to be protected throughout by an
approved automatic sprinkler system may only be applied where the system is an
approved, electrically supervised automati... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 112 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
88
This Page Intentionally Left Blank |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 113 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
89
TYPES OF CONSTRUCTIO N
6-1 GENERAL .
Conform to the requir ements of IBC Chapter 6, except as modified by this UFC.
6-2 SEPARATION BETWEEN BUILDINGS.
Conform to the requirements of the IBC, except as modified by this UFC. |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 114 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
90
This Page Intentionally Left Blank
|
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 115 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
91
FIRE AND SMOKE PROTE CTION FEATURES
7-1 GENERAL .
Confo rm to the requirements of NFPA 101 except as noted below.
Where IBC Chapter 5 or 6 specifically references IBC Chapter 7, utilize the specific IBC
Chapter 7 reference.
Note: For example, IBC Secti... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 116 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
92
Ceilings .
Listed floor/ceiling or roof/ceiling assemblies that utilize suspended gypsum wallboard or
acoustical tile ceilings must not be used to achieve required fire resistance rating of building structural elements.
7-5 SMOKE AND HEAT VENTS .
General .... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 117 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
93
INTERIOR FINISH ES
8-1 GENERAL .
Conform to the requirements of NFPA 101 .
8-2 DROP -OUT PANELS .
Drop -out panels , as defined in NFPA 13, must not be used.
8-3 INSULATION.
Requirements.
Use thermal and acoustical insulation with a flame spread (FS... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 118 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
94 Recognized Testing Laboratory (NRTL ), as noncombustible roof deck
construction.
b. Insulation installed above roof decks where the entire roof construction
assembly, including the insulation, is UL- listed as Fire Classified, or FM -
approved for Class I roo... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 119 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
95
FIRE PROTECTION SYSTEMS
9-1 FIRE DEPARTMENT (EME RGENCY) VEHICLE ACCE SS.
All-Weather Ground Access .
All Facilities greater than 5,000 ft2 (465 m2), or more than two stories in height , must
have at least one means of all -weather ground access to allo... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 120 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
96
Fire Department Connection.
Facilities with fire department connections for fire suppression systems must be
provided with suitable all -weather ground access surface for any apparatus within 150
feet (45 m) of such fire d epartment connections.
9-2 FIRE F... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 121 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
97 c. Three -story and above - 1,000 gpm (3,785 L/min) for 90 minutes. /3/
9-3 SERVICE MAINS AND LATERALS .
General .
Service Mains and Service Laterals must comply with AWWA M31, NFPA
24 and UFC 3 -230-01, except wher e specifically modified by this UFC.
... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 122 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
98
For NFPA 13D systems, the minimum Service Lateral size must be based
on hydraulic calculations.
The minimum residual pressure in a Service Lateral must not be less than
20 psi at the greater of Fire Flow or Fire Water Demand. This residual pressure mus... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 123 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
99
Wet barrel or California- type hydrants are preferable in areas where there is
no danger of freezing. Dry barrel or traffic -type hydrants must be used in areas where
there is a danger of freezing. Hydrants must be aboveground type and match the type
used o... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 124 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
100 airfield obstruction authority may approve individual hydrants up to 30
inches (760 mm) above the adjacent airfield pavement . /6/
[C] 9 -3.5.7.h
For additional information see the Service specific airfield clearance criteria. The
measurement i s taken from... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 125 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
101 f. \2\ Fire hydrants protecting aircraft parking and servicing aprons must be
spaced at 300 feet (91 m) maximum intervals along one side ./2/
Protection.
Hydrants located adjacent to parking areas , vehicle traffic areas or other areas subject
to mechanica... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 126 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
102
In calculating the fire protection water storage requirement, a reduction in
storage capacity is acceptable if an adequate replenishment source is available. Factors
that m ust be evaluated include the reliability of the makeup supply , its sustained flow
c... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 127 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
103 Provide white painted stenciled letters and arrows, a minimum of 2- in. (50 mm) in height
and visible from at least three sides when v iewed from the floor.
The maximum \2\fire suppression system demand must /2/ not exceed 140
percent of rated pump capacity.... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 128 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
104 Note: The lowest available static pressure should be utilized in determining churn
pressure so that the stop pressure can be achieved with low pressure. The 5 psi
differential is used to allow for gauge error. \2\
/2/Fire pump activation (run) must transm... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 129 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
105
Electric Circuits for Diesel Engine Driven Pumps.
Provide separate hard- wired electric circuit s for the pump controller , engine starting
system battery charger and hard- wired electric circuit for the engine block h eater.
Test Connections .
Provide... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 130 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
106
All working (shop) drawings, regardless of the type of fire suppression
system, must meet the drawing requirements in NFPA 13 for Working Drawings, unless
the system specific standard has requirements for wor king drawings.
For new or modified systems, wor... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 131 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
107 Conduct waterflow tests, in accordance with the procedures contained in NFPA 291 to
determine available water supply for the water -based fire extinguishing systems. The
flow test must be performed under the direction of the QFPE .
Note: Hydraulic calculat... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 132 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
108
When installed as part of a fire pump system, piping and fitt ings suitable for
potable water must be used upstream of the backflow preventer in accordance with local
environmental requirements. The backflow preventer must be located where required by
NFP... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 133 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
109
Complete automatic sprinkler protec tion must be provided \5\ where
required by other codes or standards and for the following /5/:
Single -story, Type I or II construction Facilities greater than 15,000 ft2
(1,394 m2) gross floor area
Multi -story ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 134 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
110
/2/Storage occupancies , in mixed use Facilities , must follow the
misce llaneous storage and storage provisions of NFPA 13.
Wet pipe , single -interlock preaction, and non-interlock preaction sprinkler
systems must use the requirements for “wet” listed ... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 135 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
111
Hose stream requirements must be in accordance with Table 9- 4 unless
otherwise modified by this UFC .
Table 9 -4 Hose Stream Demand and Duration
Hazard Category Hose Demand, gpm (lpm)
Duration, min Ceilings 60 ft (18.3 m)
or less Ceilings greater tha... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 136 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
112
Sprinkler systems permitted by this UFC to be supplied from the domestic
plumbing may be designed using the pipe schedule method in NFPA 13.
The addition of no more than 20 sprinklers to an existing system is
permitted to be designed using the pipe schedul... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 137 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
113
Nitrogen Generation Systems .
Design the nitrogen generation system so all equipment is installed within
the confines of the riser room with the exception of a connection for a manual gas
analyzer .
Provide a nitrogen generation system that is capable of... |
s3://digitalcorpora/corpora/files/CC-MAIN-2021-31-PDF-UNTRUNCATED/zipfiles/0000-0999/0000.zip | 0000719.pdf | 138 | UFC 3 -600-01
8 August 2016
Change 6, 6 May 2021
114
The QFPE must coordinate with the Structural Engineer to determine the
proper seismic design category for the project, in accordance with the IBC or ASCE
guidelines. Seismic restraint is not required for Seismic design category A or B , except
as otherwi... |