200 | CEC-2024.pdf | 114 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 108 Section
12 — Wiring methods Scope
Δ
12-000 Scope (see Appendix B )
1) The prov isions of Section 12 apply to all low -voltage and extra-low -voltage wiring inst allations except
for a)
Class 2 circuits unless otherwise sp... | |
201 | CEC-2024.pdf | 115 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 109 e)
other suitable material.
5) Direct buried cables shall be ins talled so that they run adjacent to each other and do not cr oss over each
other and with a layer of screened sand with a maximum particle size of 4.75 mm o... | |
202 | CEC-2024.pdf | 116 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 110 12-018
Entry of raceways and cables into buildings
Holes in out er walls or roofs of buildings throu gh which raceways or cables pass shall be filled to prevent
infiltration of mois ture.
12-020 Wiring under raised floors... | |
203 | CEC-2024.pdf | 117 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 111 Conductors
General
12-100
Types of insulated conductors and cables (see Appendix B )
1) Insulat ed conductor s and cables shall be suitable for the location in which they will be ins talled with
respect to, but not limit e... | |
204 | CEC-2024.pdf | 118 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA C22.1:24
Section 12
Wiring methods
March 2024 © 2024 Canadian Standards Association 112
b) the conductors are insulated for the voltage of the circuit having the highest voltage; and
c) none of the conductors of the circuits of lower voltages is directly connected to a lighting
branch circuit.
3) Where single-cond... | |
205 | CEC-2024.pdf | 119 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 113 Δ
5) Joints or splices in conductor s and cables in grade level in-ground enclosures shall be in accordance with
Subrule 6) b) and suitable for wet locations.
6) Splices in undergrou nd runs of cable, if required due to da... | |
206 | CEC-2024.pdf | 120 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 114 12-120
Supporting of conductors (see Appendix B )
1) Conductor s shall be supported so that no damaging s train is imposed on the termi nals of any electrical
apparatus or devices or on joints or taps.
2) Conductor s in v... | |
207 | CEC-2024.pdf | 121 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 115
12-302
Types of insulated conductors and cables
Insulat ed conductor s and cables shall be of types suitable for exposure to the weather as indicate d in Table
19 .
Δ 12-304 Location of insulated conductors and cables
In... | |
208 | CEC-2024.pdf | 122 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 116 conduit
or is permanently separated fr om other sy st ems by a continuous fixed non-conductor other than
the insulation on the conductor s.
12-318 Overhead installations
1) When neutral supported cables are used, the foll... | |
209 | CEC-2024.pdf | 123 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 117 c)
tem perature;
d) degree of enclosure; and
e) exposure to mechanical damage.
2) Flexible cord shall be permit ted to be used for a)
electrical equipment for household or similar use that is int ended to be i)
moved fr... | |
210 | CEC-2024.pdf | 124 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 118 c)
the connection of s tationary equipment to facilitat e its int erchange;
d) the connection of electrical components between which relative motion is necessary; and
e) the connection of equipment used in conjunction with... | |
211 | CEC-2024.pdf | 125 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 119 Δ
12-506 Method of installation (see Appendices B and G )
1) The cable shall be run in continuous lengths between outlet boxes, junction boxes, and panel boxes
as a loop s yst em, and the joints, splices, and taps shall be ... | |
212 | CEC-2024.pdf | 126 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 120 Δ
12-516 Protection for cable in concealed installations (see Appendices B and G )
1) Where the cable is run throu gh studs , jois ts, or similar member s, the out er surfaces of the cable shall
be kept a distance of at lea... | |
213 | CEC-2024.pdf | 127 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 121 Δ
12-552 Maximum voltage
Type NMD90 and NMWU cables shall not be used where the voltage exceeds 300 V between any two conductor
s.
Δ 12-554 Use of Type NMD90 and NMWU cables
Type NMD90 and NMWU cables shall be permit ted i... | |
214 | CEC-2024.pdf | 128 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 122 2)
Running boards and guard stri ps shall be at least 19 mm × 38 mm, and the edges of the running board
shall proj ect at least 12 mm beyond the cables.
3) Guard stri ps shall be at leas t as high as the cable and placed ... | |
215 | CEC-2024.pdf | 129 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 123 Δ
12-576 Provision for bonding
Where Type NMD90 or NMWU cable is used, prov ision for bonding to gr ound shall be made in accordance
with Section 10 .Armoured
cable 12-600
Armoured cable Rules
Rules 12-602 to 12-618 app... | |
216 | CEC-2024.pdf | 130 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 124 3)
Where armoured cable is fas tened to equipment, the connector or clamp shall be of such design as to
leave the insulating bushing or its equivalent visible for inspection.
4) Where conductor s connect ed to open wiring... | |
217 | CEC-2024.pdf | 131 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 125
3)
Where the cable is run as concealed wiring and it is impracticable to prov ide the supports required by
Subrule 1), the cable shall be permit ted to be fished and need not be supported between boxes and
fit tings.Miner... | |
218 | CEC-2024.pdf | 132 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 126 2)
Where mineral-insulat ed cable, aluminum-sheathed cable, or copper -sheathed cable is installed on the
face of a wall, partition, ceiling, or struc tural member within 1.5 m of the floor , and in all locations
where su... | |
219 | CEC-2024.pdf | 133 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 127 Bot
tom shield — a prot ective layer that is between the floor and the Type FCC cable to pro tect the cable
fr om physical damage.
Insulating end — an insulator designed to electrically insulat e the exposed ends of Type F... | |
220 | CEC-2024.pdf | 134 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 128 12-816
Connection to other systems
Power feed, bonding, and shield sys tem connections between the Type FCC s ys tem and other wiring sy
st ems shall be accomplished in a transition assembly intende d for surface or recess... | |
221 | CEC-2024.pdf | 135 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 129 c)
each enclosure or cable sheath is of the same mat erial and has the same physical charact
eristics.
2) Except for cable tray , no raceway or compartment of a multiple-channel raceway shall contain conductor
s that are ... | |
222 | CEC-2024.pdf | 136 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 130 Δ
e) the diamete r s and cr oss-sectional areas of Type DLO cables shall be as indicate d in Table 10D
or as obtained by field measurement.
5) Notwithsta nding Subrule 4), the maximum permitt ed number of conductor s shal... | |
223 | CEC-2024.pdf | 137 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 131 12-934
Protection for raceways
Raceways ins talled less than 2 m above grade in an area where they are subject to mechanical damage shall
be
a) of the rigid st eel type;
b) prot ect ed by location; or
c) prot ect ed by... | |
224 | CEC-2024.pdf | 138 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 132 4)
Notwithsta nding Subrule 3), where rigid metal conduit prot rudes throu gh the enclosure wall and there
are not sufficient threads to accommodat e a bushing in accordance with Rule 12-906 1), additional
threading shall... | |
225 | CEC-2024.pdf | 139 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 133 12-1108
Field bends (see Appendix B )
1) Rigid PVC conduit shall be permitt ed to be bent in the field, prov ided that bending equipment specifically
int ended for the purpose is used.
2) The minimum bending radius shall ... | |
226 | CEC-2024.pdf | 140 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 134 c)
each length of split straight conduit and each split coupling is tightly clamped at both ends, with additional
clamps spaced not more than 500 mm apart;
d) non-removable band clamps made of st ainless st eel are used; ... | |
227 | CEC-2024.pdf | 141 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 135
Rigid
RTRC conduit 12-1200
Scope
Rules 12-1202 to 12-1220 apply only to the inst allation of rigid RTRC conduit Types AG, BG, and XW.
12-1202 Use
1) Rigid RTRC conduit Types AG, BG, and XW shall be permit ted to be instal... | |
228 | CEC-2024.pdf | 142 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 136 12-1252
Restrictions on use
HDPE conduit, HDPE conductor s-in-conduit, and fit tings shall not be used above ground except as permitt
ed by Rule 12-1250 b).
12-1254 Method of installation (see Appendix B )
1) All cut edge... | |
229 | CEC-2024.pdf | 143 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 137 Liquid-tight
flexible conduit 12-1300
Scope
Rules 12-1302 to 12-1308 apply only to liquid-tight flexible conduit.
12-1302 Use of liquid-tight flexible metal and non-metallic conduit
1) Liquid-tight flexible conduit shall... | |
230 | CEC-2024.pdf | 144 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 138 c)
for direct earth burial.
12-1406 Supports
Electrical metallic tubing shall be instal led as a complete s ys tem and shall be securely fas ten ed in place within
1 m of each outlet box, junction box, cabinet, or fit tin... | |
231 | CEC-2024.pdf | 145 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 139 2)
Subrule 1) shall not prevent the use of insulated conductor s having t emperature ratings in excess of
75 °C, but such insulat ed conductors shall not have ampacities exceeding those of 90 °C insulated
conductor s rega... | |
232 | CEC-2024.pdf | 146 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 140 12-1614
Flat cable systems
1) Flat cables consisting of parallel conductor s and side wings formed with integr al insulation specifically
designed for field installation in metal surface raceways with tap fit tings and en... | |
233 | CEC-2024.pdf | 147 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 141 12-1714
Area of conductors in underfloor raceways
1) The aggregate cr oss-sectional area of the insulated conductor s and bare conductor s and their insulation
in an underfloor raceway shall not exceed 40% of the inter io... | |
234 | CEC-2024.pdf | 148 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 142 2)
The junction boxes shall be cons tructed of metal and shall be electrically continuous with the header
s.
3) Electrical continuity of cellular metal-floor member s shall be obtained by spot welding or other equivalent
... | |
235 | CEC-2024.pdf | 149 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 143 3)
Busways, split ter s, and fit tings shall not be placed a)
where subject to mechanical damage;
b) where subject to corr osive vapour s;
c) in hoist ways; or
d) in storage-b att ery r ooms.
4) Busways shall be permitt ... | |
236 | CEC-2024.pdf | 150 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 144 b)
prov ided with fire s tops in accordance with Rule 2-128 .
3) Busways shall be provid ed with adequate prot ection against mechanical damage and personal contact
with live parts for a dis tance of 2 m above any floor in... | |
237 | CEC-2024.pdf | 151 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 145
2)
Wireways shall be securely support ed at inter vals of not more than 1.5 m, unless they are plainly marked
to indicate greate r dis tances.
3) Dead-ends of wireways shall be closed by fit tings.
4) Wireways shall be pro... | |
238 | CEC-2024.pdf | 152 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 146 b)
300 mm vertical clearance fr om the top of the cable tray to all ceilings, heating ducts, and heating
equipment and 150 mm for short length obs tructions;
c) 600 mm horizontal clearance on one side of cable trays mount ... | |
239 | CEC-2024.pdf | 153 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 147 12-2208
Provisions for bonding (see Appendix M )
1) Except as prov ided for in Subrules 2) and 3), metal cable tray shall be bonded at inter vals not exceeding
15 m and the size of bonding conductor s shall be based on the... | |
240 | CEC-2024.pdf | 154 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 148 9)
Cablebus shall be permit ted to extend transver sely throu gh partitions or walls, including firewalls, prov
ided that the section within the wall is continuous, pro tect ed against physical damage, unventilate
d, and,... | |
241 | CEC-2024.pdf | 155 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 149 Power
feed connector — an electr o-mechanical connector used to connect
a) the output fr om a Class 2 power supply to a power dist ribution cable;
b) the output fr om a Class 2 power supply directly to the busbar; or
c) ... | |
242 | CEC-2024.pdf | 156 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 150
b)
be inst alled in accordance with Section 16 .
12-2312 Disconnecting means
1) To allow for servicing or maintena nce of extra-low -voltage suspended ceiling power distri bution sy
st ems, a disconnecting means shall be ... | |
243 | CEC-2024.pdf | 157 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 151
c)
suitable cut -offs to prot ect against the vertical spread of fire are prov ided where floor s are pierced; and
Δ d) busbar s rated 1200 A or less have i)
conductor supports that are suitable for the purpose and spaced ... | |
244 | CEC-2024.pdf | 158 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 152
3)
Boxes made wholly or in part of aluminum shall not be embedded in concrete containing reinforcing
s tee l unless a)
the concret e is known to contain no chloride additives; or
b) the box has been treated with a bitumi... | |
245 | CEC-2024.pdf | 159 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 153
12-3020
Outlet boxes, etc., in damp places
Where boxes, cabinets, and fit tings are instal led in damp places, they shall be placed or construct ed so as
to prevent mois ture from enter ing and accumulating in them.
Δ 12... | |
246 | CEC-2024.pdf | 160 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 154
4)
Multi-outlet assemblies shall not be concealed within the building finish, but a)
the back and sides of i)
metal assemblies shall be permitt ed to be set in plas ter applied aft er the assembly is in place;
or
ii) no... | |
247 | CEC-2024.pdf | 161 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 155
4)
Notwithsta nding Subrule 1), enclosures for overcurrent devices, contr oller s, and ext ernally operat
ed switches shall be permit ted to be used as raceways for wiring associat ed with instru ment transformer
s and en... | |
248 | CEC-2024.pdf | 162 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
12 Wiring
methods March
2024 © 2024 Canadian Standards Association 156
c)
for angle and U pulls or runs of cable, i)
have a dis tance between each raceway or cable entry inside the box and the opposit e wall
of the box of at least six times the trade diamete r of the larges t raceway or equi... | |
249 | CEC-2024.pdf | 163 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 157
Section
14 — Protection and control Scope
14-000
Scope (see Appendix B )
This Section applies to the prot ection and contr ol of electrical circuits and apparatus inst alled in accordance
with the requirements of ... | |
250 | CEC-2024.pdf | 164 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 158
Protective
devices General
14-100
Overcurrent protection of conductors (see Appendix B )
1) Each ungr ounded conductor shall be prot ect ed by an overcurrent device at the point where it receives
its supply of cur... | |
251 | CEC-2024.pdf | 165 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 159
iv)
ter minates in service equipment in accordance with Section 6 .
2) Notwithsta nding Subrule 1), consumer ’s service conductor s shall be permitt ed to be prot ected by an
overcurrent device at the service equip... | |
252 | CEC-2024.pdf | 166 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 160 c)
as pr ovided for by other Rules of this Code.
2) Except as prov ided for by Subrule 1) c), the rating of overcurrent prot ection shall not exceed a)
15 A for No. 14 AWG copper conductor s;
b) 20 A for No. 12 AW... | |
253 | CEC-2024.pdf | 167 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 161 14-206
Fuseholders for plug fuses
Fuseholder s for plug fuses shall be of the so-called “covered” type where readily accessible to unauthorized
per sons.
14-208 Rating of fuses
1) Plug fuses shall be rated at not... | |
254 | CEC-2024.pdf | 168 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 162 2)
If the batt ery voltage drops to a value insufficient to operate the circuit breaker overcurrent element
a)
the circuit breaker shall automatically trip; or
b) an alarm shall operat e continuously until the ba... | |
255 | CEC-2024.pdf | 169 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 163 3)
Where multiple disconnecting means as in Subrule 1) b) are prov ided, suitable warning signs shall be
placed on or adjacent to each disconnecting means so that all of the disconnecting means must be
opened to e... | |
256 | CEC-2024.pdf | 170 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 164 iii)
the switc h is rat ed at not less than 10 A, 125 V; 5 A, 250 V; or for the four -way types, 5 A, 125
V; 2 A, 250 V;
c) canopy switch es contr olling a tungs ten-fi lament lamp load shall be “T” rat ed or shal... | |
257 | CEC-2024.pdf | 171 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
14 Protection
and control March
2024 © 2024 Canadian Standards Association 165
disconnecting
of the apparatus fr om the supply circuit shall be permitt ed to be arranged so that it also disconnects
the remot e contr ol circuit fr om the supply circuit.
14-610 Protection of circuits supplying... | |
258 | CEC-2024.pdf | 172 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
16 Class
1 and Class 2 circuits March
2024 © 2024 Canadian Standards Association 166 Section
16 — Class 1 and Class 2 circuits General
16-000
Scope (see Appendix B )
1) This Section applies to a)
Class 1 and Class 2 remot e contr ol circuits;
b) Class 1 and Class 2 signal circuits;
c) Clas... | |
259 | CEC-2024.pdf | 173 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
16 Class
1 and Class 2 circuits March
2024 © 2024 Canadian Standards Association 167 16-102
Methods of installation for Class 1 circuits
The equipment and insulated conductor s of Class 1 circuits shall be ins talled in accordance with the requirements
of other appr opriate Sections of this ... | |
260 | CEC-2024.pdf | 174 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
16 Class
1 and Class 2 circuits March
2024 © 2024 Canadian Standards Association 168 16-118
Class 1 circuits extending aerially beyond a building
Class 1 circuits that ext end aerially beyond a building shall comply with Rules 12-300 to 12-318 .Class
2 circuits 16-200
Limitations of Class 2... | |
261 | CEC-2024.pdf | 175 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
16 Class
1 and Class 2 circuits March
2024 © 2024 Canadian Standards Association 169 16-204
Marking
A Class 2 power supply unit shall have permanent markings that are readily visible aft er inst allation to indicate
a) the class of supply and its electrical rating; and
b) suitability for wet ... | |
262 | CEC-2024.pdf | 176 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
16 Class
1 and Class 2 circuits March
2024 © 2024 Canadian Standards Association 170 2)
Where electric lighting or power conductor s are bare, all Class 2 circuit insulat ed conductor s and cables
in the same r oom or space shall be enclosed in a metal raceway that is bonded to gr ound, and
... | |
263 | CEC-2024.pdf | 177 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
16 Class
1 and Class 2 circuits March
2024 © 2024 Canadian Standards Association 171 iii)
60 V continuous dc; and
iv) 24.8 V peak for inter rupted dc (square wave dc at a rate of 10 to 200 Hz); and
b) for wet locations (not including immers ion) i)
15 V rms for sinusoidal ac;
ii) 21.2 V pe... | |
264 | CEC-2024.pdf | 178 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
16 Class
1 and Class 2 circuits March
2024 © 2024 Canadian Standards Association 172 3)
Where communication cable not marked with the suffix “-LP” is used a)
the maximum current that each insulated conductor shall be permitt ed to carry shall be as specified
in Table 60 , based on i)
the si... | |
265 | CEC-2024.pdf | 179 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 173 Section
18 — Hazardous locations Scope
and introduction 18-000
Scope (see Appendices B and J )
1) This Section applies to locations in which electrical equipment and wiring are subject to the conditions
indicate d by... | |
266 | CEC-2024.pdf | 180 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 174 EPL
Dc — equipment for explosive dus t atmospheres, having an “enhanced” level of prot ection, that
is not a source of ignition in normal operation and may have some additional prot ection to ensure
that it remains i... | |
267 | CEC-2024.pdf | 181 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 175
Seals
— Explosion
seal — a seal that
a) when installed at a cable or conduit entry to an explosion-pr oof, flamepr oof “d”, or flamepr oof “db”,
enclosure, prevents the ignition of an explosive gas atmosphere outsid... | |
268 | CEC-2024.pdf | 182 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 176 Zone
22 — a location in which an explosive dus t atmosphere, in the form of a cloud of dust in air , is not likely
to occur in normal operation but, if it does occur , will per sis t for a short period only .
18-004 C... | |
269 | CEC-2024.pdf | 183 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 177 6)
Equipment with a type of prot ection permit ted in a Zone 20, Zone 21, or Zone 22 location shall be suitable
for one of the following: a)
Group IIIC , combustible metal dust s;
b) Group IIIB , combustible dust oth... | |
270 | CEC-2024.pdf | 184 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 178 b)
have the metal coverings continuously covered with insulating material and bonded to gr ound at
the point of termi nation in the hazardous location only .
18-062 Optical fiber cable (see Appendix B )
Optical fiber ... | |
271 | CEC-2024.pdf | 185 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 179 c)
the location is continuously monitored by a combustible gas det ection sy st em that will i)
activat e an alarm when the gas concentration reaches 20% of the lower flammable limit;
ii) activat e ventilating equipm... | |
272 | CEC-2024.pdf | 186 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 180 Δ
18-078 Threaded joints (see Appendix B )
1) Threaded joints that are required to be explosion-proof, flameproof “d”, or flameproof “db” shall be
permitt ed to be either tapered or s traight, and shall comply with the... | |
273 | CEC-2024.pdf | 187 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 181 4)
Where a cable gland entry to an increased safety “e” enclosure is thr ough a clearance hole, an O-ring,
sealing washer , or sealing locknut shall be used to maintain the degree of prot ection.
5) Cables shall be in... | |
274 | CEC-2024.pdf | 188 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 182 18-110
Flexible cords, Zone 1
1) Flexible cords shall be permitt ed to be used for connection between a portable lamp, or other portable
utilization equipment, and the fixed portion of its supply circuit and, where u... | |
275 | CEC-2024.pdf | 189 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 183 b)
the pot ential discharge energy is det ermined to be non-incendive for the application; and
c) the pot ential discharge energy calculation is document ed and authenticat ed by the per son assuming
responsibility f... | |
276 | CEC-2024.pdf | 190 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 184 5)
Except as permitt ed in Subrule 6), flammable fluid migration seals for conduit shall be installed where
a)
the conduit leaves the Zone 2 location uninterrupt ed between the seal and the point at which the
condui... | |
277 | CEC-2024.pdf | 191 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 185
4)
Where flexible connections are subject to oil or other corros ive conditions, the insulation of the conductor
s shall be suitable for the condition or shall be prot ected by means of a suitable sheath.
5) Wiring m... | |
278 | CEC-2024.pdf | 192 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
18 Hazardous
locations March
2024 © 2024 Canadian Standards Association 186 b)
where suspended by threaded rigid conduit s tems longer than 300 mm, prov ided with i)
permanent and effective bracing against later al displacement at a level not more than 300
mm from the point of at tachment to... | |
279 | CEC-2024.pdf | 193 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 187 Section
20 — Flammable liquid and gasoline dispensing, service
stations, garages, bulk storage plants, f... | |
280 | CEC-2024.pdf | 194 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 188 Δ
8) Except as permitt ed by Subrule 11), electrical wiring and equipment, any portion of which is below t... | |
281 | CEC-2024.pdf | 195 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 189 Propane
vehicle fuel dispensers, container filling, and storage 20-030
Scope (see Appendix B )
Rules 20-0... | |
282 | CEC-2024.pdf | 196 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 190 2)
Where dispensing devices are supplied by rigid metal conduit, the requirements of Rule 20-006 2) and
... | |
283 | CEC-2024.pdf | 197 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 191 2)
Permanently ins talled luminaires that are located over lanes thr ough which vehicles are commonly dri... | |
284 | CEC-2024.pdf | 198 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 192 20-302
Hazardous locations
1) The following areas shall be Zone 1 locations: a)
where adequate ventilat... | |
285 | CEC-2024.pdf | 199 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 193 b)
the panel is non-combus tible and effectively isolates the hazardous area from the area in which
the ... | |
286 | CEC-2024.pdf | 200 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 194 b)
the electr ostaticall y charged exposed elements of the hand gun shall be capable of being energized o... | |
287 | CEC-2024.pdf | 201 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 195
Δ
5) Except as permitt ed by Subrule 6), electrical wiring and equipment, any portion of which is in or be... | |
288 | CEC-2024.pdf | 202 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 196 2)
Where s tanchions, ros trums, and docks are not locat ed, or are not likely to be located , in a hazar... | |
289 | CEC-2024.pdf | 203 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
20 Flammable
liquid and gasoline dispensing, service stations, garages, bulk storage plants,
finishing processes, and aircraft hangars March
2024 © 2024 Canadian Standards Association 197 4)
Equipment shall not be operated in areas where maintena nce operations likely to release hazardous
va... | |
290 | CEC-2024.pdf | 204 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
22 Locations
in which corrosive liquids, vapours, or excessive moisture are likely to be present
March
2024 © 2024 Canadian Standards Association 198 Section
22 — Locations in which corrosive liquids, vapours, or excessive
moisture are likely to be present General
22-000
Scope
This Section ap... | |
291 | CEC-2024.pdf | 205 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
22 Locations
in which corrosive liquids, vapours, or excessive moisture are likely to be present
March
2024 © 2024 Canadian Standards Association 199 3)
Flexible cords, portable power cables, and at tachment plugs for portable equipment shall comply with
the requirements of Subrules 1) and 2)... | |
292 | CEC-2024.pdf | 206 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
22 Locations
in which corrosive liquids, vapours, or excessive moisture are likely to be present
March
2024 © 2024 Canadian Standards Association 200 Drainage,
sealing, and exclusion of moisture and corrosive vapour 22-300
Drip loops
Where exposed insulat ed conductor s or non-metallic-sheath... | |
293 | CEC-2024.pdf | 207 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
22 Locations
in which corrosive liquids, vapours, or excessive moisture are likely to be present
March
2024 © 2024 Canadian Standards Association 201 Continuous
positive pressure ventilation — a ventilation s ys tem capable of maintaining a positive pressure
in a r oom or area and of changing... | |
294 | CEC-2024.pdf | 208 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
22 Locations
in which corrosive liquids, vapours, or excessive moisture are likely to be present
March
2024 © 2024 Canadian Standards Association 202 3)
Electrical equipment ins talled in a wet or damp Cat egory 2 location shall be in accordance with the applicable
requirements of this Code, ... | |
295 | CEC-2024.pdf | 209 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
22 Locations
in which corrosive liquids, vapours, or excessive moisture are likely to be present
March
2024 © 2024 Canadian Standards Association 203 4)
Devices such as receptacles and general-use switc hes inst alled where wash-down operation is performed
shall be prot ected by a suitable en... | |
296 | CEC-2024.pdf | 210 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
24 Patient
care areas March
2024 © 2024 Canadian Standards Association 204 Section
24 — Patient care areas 24-000
Scope (see Appendix B )
1) This Section applies to the inst allation of a)
electrical wiring and equipment within patient care areas of health care facilities; and
b) the portio... | |
297 | CEC-2024.pdf | 211 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
24 Patient
care areas March
2024 © 2024 Canadian Standards Association 205
Health
care facility adminis tration — the unit responsible for planning, organizing, directing, and contr
olling the health care facility in accordance with the policies of the health care facility and government
s ta... | |
298 | CEC-2024.pdf | 212 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
24 Patient
care areas March
2024 © 2024 Canadian Standards Association 206 24-104
Circuits in basic care areas (see Appendix B )
1) The branch circuits supplying receptacles or permanently connect ed equipment in basic care areas shall
be supplied fr om a gr ounded dis tribution sy st em.
2) ... | |
299 | CEC-2024.pdf | 213 | tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf | CSA
C22.1:24 Section
24 Patient
care areas March
2024 © 2024 Canadian Standards Association 207 Δ
5) Each panelboard supplying branch circuits as described in Rule 24-104 3) and locat ed in a basic care
area shall be bonded to gr ound by a copper bonding conductor that is a)
inst alled in the same raceway as the ... |