page_text
stringlengths
6
11.8k
200
CEC-2024.pdf
114
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 108 Section 12 — Wiring methods Scope Δ 12-000 Scope (see Appendix B ) 1) The prov isions of Section 12 apply to all low -voltage and extra-low -voltage wiring inst allations except for a) Class 2 circuits unless otherwise sp...
201
CEC-2024.pdf
115
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 109 e) other suitable material. 5) Direct buried cables shall be ins talled so that they run adjacent to each other and do not cr oss over each other and with a layer of screened sand with a maximum particle size of 4.75 mm o...
202
CEC-2024.pdf
116
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 110 12-018 Entry of raceways and cables into buildings Holes in out er walls or roofs of buildings throu gh which raceways or cables pass shall be filled to prevent infiltration of mois ture. 12-020 Wiring under raised floors...
203
CEC-2024.pdf
117
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 111 Conductors General 12-100 Types of insulated conductors and cables (see Appendix B ) 1) Insulat ed conductor s and cables shall be suitable for the location in which they will be ins talled with respect to, but not limit e...
204
CEC-2024.pdf
118
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 112 b) the conductors are insulated for the voltage of the circuit having the highest voltage; and c) none of the conductors of the circuits of lower voltages is directly connected to a lighting branch circuit. 3) Where single-cond...
205
CEC-2024.pdf
119
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 113 Δ 5) Joints or splices in conductor s and cables in grade level in-ground enclosures shall be in accordance with Subrule 6) b) and suitable for wet locations. 6) Splices in undergrou nd runs of cable, if required due to da...
206
CEC-2024.pdf
120
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 114 12-120 Supporting of conductors (see Appendix B ) 1) Conductor s shall be supported so that no damaging s train is imposed on the termi nals of any electrical apparatus or devices or on joints or taps. 2) Conductor s in v...
207
CEC-2024.pdf
121
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 115 12-302 Types of insulated conductors and cables Insulat ed conductor s and cables shall be of types suitable for exposure to the weather as indicate d in Table 19 . Δ 12-304 Location of insulated conductors and cables In...
208
CEC-2024.pdf
122
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 116 conduit or is permanently separated fr om other sy st ems by a continuous fixed non-conductor other than the insulation on the conductor s. 12-318 Overhead installations 1) When neutral supported cables are used, the foll...
209
CEC-2024.pdf
123
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 117 c) tem perature; d) degree of enclosure; and e) exposure to mechanical damage. 2) Flexible cord shall be permit ted to be used for a) electrical equipment for household or similar use that is int ended to be i) moved fr...
210
CEC-2024.pdf
124
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 118 c) the connection of s tationary equipment to facilitat e its int erchange; d) the connection of electrical components between which relative motion is necessary; and e) the connection of equipment used in conjunction with...
211
CEC-2024.pdf
125
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 119 Δ 12-506 Method of installation (see Appendices B and G ) 1) The cable shall be run in continuous lengths between outlet boxes, junction boxes, and panel boxes as a loop s yst em, and the joints, splices, and taps shall be ...
212
CEC-2024.pdf
126
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 120 Δ 12-516 Protection for cable in concealed installations (see Appendices B and G ) 1) Where the cable is run throu gh studs , jois ts, or similar member s, the out er surfaces of the cable shall be kept a distance of at lea...
213
CEC-2024.pdf
127
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 121 Δ 12-552 Maximum voltage Type NMD90 and NMWU cables shall not be used where the voltage exceeds 300 V between any two conductor s. Δ 12-554 Use of Type NMD90 and NMWU cables Type NMD90 and NMWU cables shall be permit ted i...
214
CEC-2024.pdf
128
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 122 2) Running boards and guard stri ps shall be at least 19 mm × 38 mm, and the edges of the running board shall proj ect at least 12 mm beyond the cables. 3) Guard stri ps shall be at leas t as high as the cable and placed ...
215
CEC-2024.pdf
129
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 123 Δ 12-576 Provision for bonding Where Type NMD90 or NMWU cable is used, prov ision for bonding to gr ound shall be made in accordance with Section 10 .Armoured cable 12-600 Armoured cable Rules Rules 12-602 to 12-618 app...
216
CEC-2024.pdf
130
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 124 3) Where armoured cable is fas tened to equipment, the connector or clamp shall be of such design as to leave the insulating bushing or its equivalent visible for inspection. 4) Where conductor s connect ed to open wiring...
217
CEC-2024.pdf
131
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 125 3) Where the cable is run as concealed wiring and it is impracticable to prov ide the supports required by Subrule 1), the cable shall be permit ted to be fished and need not be supported between boxes and fit tings.Miner...
218
CEC-2024.pdf
132
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 126 2) Where mineral-insulat ed cable, aluminum-sheathed cable, or copper -sheathed cable is installed on the face of a wall, partition, ceiling, or struc tural member within 1.5 m of the floor , and in all locations where su...
219
CEC-2024.pdf
133
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 127 Bot tom shield — a prot ective layer that is between the floor and the Type FCC cable to pro tect the cable fr om physical damage. Insulating end — an insulator designed to electrically insulat e the exposed ends of Type F...
220
CEC-2024.pdf
134
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 128 12-816 Connection to other systems Power feed, bonding, and shield sys tem connections between the Type FCC s ys tem and other wiring sy st ems shall be accomplished in a transition assembly intende d for surface or recess...
221
CEC-2024.pdf
135
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 129 c) each enclosure or cable sheath is of the same mat erial and has the same physical charact eristics. 2) Except for cable tray , no raceway or compartment of a multiple-channel raceway shall contain conductor s that are ...
222
CEC-2024.pdf
136
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 130 Δ e) the diamete r s and cr oss-sectional areas of Type DLO cables shall be as indicate d in Table 10D or as obtained by field measurement. 5) Notwithsta nding Subrule 4), the maximum permitt ed number of conductor s shal...
223
CEC-2024.pdf
137
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 131 12-934 Protection for raceways Raceways ins talled less than 2 m above grade in an area where they are subject to mechanical damage shall be a) of the rigid st eel type; b) prot ect ed by location; or c) prot ect ed by...
224
CEC-2024.pdf
138
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 132 4) Notwithsta nding Subrule 3), where rigid metal conduit prot rudes throu gh the enclosure wall and there are not sufficient threads to accommodat e a bushing in accordance with Rule 12-906 1), additional threading shall...
225
CEC-2024.pdf
139
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 133 12-1108 Field bends (see Appendix B ) 1) Rigid PVC conduit shall be permitt ed to be bent in the field, prov ided that bending equipment specifically int ended for the purpose is used. 2) The minimum bending radius shall ...
226
CEC-2024.pdf
140
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 134 c) each length of split straight conduit and each split coupling is tightly clamped at both ends, with additional clamps spaced not more than 500 mm apart; d) non-removable band clamps made of st ainless st eel are used; ...
227
CEC-2024.pdf
141
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 135 Rigid RTRC conduit 12-1200 Scope Rules 12-1202 to 12-1220 apply only to the inst allation of rigid RTRC conduit Types AG, BG, and XW. 12-1202 Use 1) Rigid RTRC conduit Types AG, BG, and XW shall be permit ted to be instal...
228
CEC-2024.pdf
142
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 136 12-1252 Restrictions on use HDPE conduit, HDPE conductor s-in-conduit, and fit tings shall not be used above ground except as permitt ed by Rule 12-1250 b). 12-1254 Method of installation (see Appendix B ) 1) All cut edge...
229
CEC-2024.pdf
143
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 137 Liquid-tight flexible conduit 12-1300 Scope Rules 12-1302 to 12-1308 apply only to liquid-tight flexible conduit. 12-1302 Use of liquid-tight flexible metal and non-metallic conduit 1) Liquid-tight flexible conduit shall...
230
CEC-2024.pdf
144
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 138 c) for direct earth burial. 12-1406 Supports Electrical metallic tubing shall be instal led as a complete s ys tem and shall be securely fas ten ed in place within 1 m of each outlet box, junction box, cabinet, or fit tin...
231
CEC-2024.pdf
145
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 139 2) Subrule 1) shall not prevent the use of insulated conductor s having t emperature ratings in excess of 75 °C, but such insulat ed conductors shall not have ampacities exceeding those of 90 °C insulated conductor s rega...
232
CEC-2024.pdf
146
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 140 12-1614 Flat cable systems 1) Flat cables consisting of parallel conductor s and side wings formed with integr al insulation specifically designed for field installation in metal surface raceways with tap fit tings and en...
233
CEC-2024.pdf
147
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 141 12-1714 Area of conductors in underfloor raceways 1) The aggregate cr oss-sectional area of the insulated conductor s and bare conductor s and their insulation in an underfloor raceway shall not exceed 40% of the inter io...
234
CEC-2024.pdf
148
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 142 2) The junction boxes shall be cons tructed of metal and shall be electrically continuous with the header s. 3) Electrical continuity of cellular metal-floor member s shall be obtained by spot welding or other equivalent ...
235
CEC-2024.pdf
149
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 143 3) Busways, split ter s, and fit tings shall not be placed a) where subject to mechanical damage; b) where subject to corr osive vapour s; c) in hoist ways; or d) in storage-b att ery r ooms. 4) Busways shall be permitt ...
236
CEC-2024.pdf
150
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 144 b) prov ided with fire s tops in accordance with Rule 2-128 . 3) Busways shall be provid ed with adequate prot ection against mechanical damage and personal contact with live parts for a dis tance of 2 m above any floor in...
237
CEC-2024.pdf
151
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 145 2) Wireways shall be securely support ed at inter vals of not more than 1.5 m, unless they are plainly marked to indicate greate r dis tances. 3) Dead-ends of wireways shall be closed by fit tings. 4) Wireways shall be pro...
238
CEC-2024.pdf
152
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 146 b) 300 mm vertical clearance fr om the top of the cable tray to all ceilings, heating ducts, and heating equipment and 150 mm for short length obs tructions; c) 600 mm horizontal clearance on one side of cable trays mount ...
239
CEC-2024.pdf
153
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 147 12-2208 Provisions for bonding (see Appendix M ) 1) Except as prov ided for in Subrules 2) and 3), metal cable tray shall be bonded at inter vals not exceeding 15 m and the size of bonding conductor s shall be based on the...
240
CEC-2024.pdf
154
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 148 9) Cablebus shall be permit ted to extend transver sely throu gh partitions or walls, including firewalls, prov ided that the section within the wall is continuous, pro tect ed against physical damage, unventilate d, and,...
241
CEC-2024.pdf
155
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 149 Power feed connector — an electr o-mechanical connector used to connect a) the output fr om a Class 2 power supply to a power dist ribution cable; b) the output fr om a Class 2 power supply directly to the busbar; or c) ...
242
CEC-2024.pdf
156
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 150 b) be inst alled in accordance with Section 16 . 12-2312 Disconnecting means 1) To allow for servicing or maintena nce of extra-low -voltage suspended ceiling power distri bution sy st ems, a disconnecting means shall be ...
243
CEC-2024.pdf
157
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 151 c) suitable cut -offs to prot ect against the vertical spread of fire are prov ided where floor s are pierced; and Δ d) busbar s rated 1200 A or less have i) conductor supports that are suitable for the purpose and spaced ...
244
CEC-2024.pdf
158
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 152 3) Boxes made wholly or in part of aluminum shall not be embedded in concrete containing reinforcing s tee l unless a) the concret e is known to contain no chloride additives; or b) the box has been treated with a bitumi...
245
CEC-2024.pdf
159
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 153 12-3020 Outlet boxes, etc., in damp places Where boxes, cabinets, and fit tings are instal led in damp places, they shall be placed or construct ed so as to prevent mois ture from enter ing and accumulating in them. Δ 12...
246
CEC-2024.pdf
160
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 154 4) Multi-outlet assemblies shall not be concealed within the building finish, but a) the back and sides of i) metal assemblies shall be permitt ed to be set in plas ter applied aft er the assembly is in place; or ii) no...
247
CEC-2024.pdf
161
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 155 4) Notwithsta nding Subrule 1), enclosures for overcurrent devices, contr oller s, and ext ernally operat ed switches shall be permit ted to be used as raceways for wiring associat ed with instru ment transformer s and en...
248
CEC-2024.pdf
162
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 12 Wiring methods March 2024 © 2024 Canadian Standards Association 156 c) for angle and U pulls or runs of cable, i) have a dis tance between each raceway or cable entry inside the box and the opposit e wall of the box of at least six times the trade diamete r of the larges t raceway or equi...
249
CEC-2024.pdf
163
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 157 Section 14 — Protection and control Scope 14-000 Scope (see Appendix B ) This Section applies to the prot ection and contr ol of electrical circuits and apparatus inst alled in accordance with the requirements of ...
250
CEC-2024.pdf
164
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 158 Protective devices General 14-100 Overcurrent protection of conductors (see Appendix B ) 1) Each ungr ounded conductor shall be prot ect ed by an overcurrent device at the point where it receives its supply of cur...
251
CEC-2024.pdf
165
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 159 iv) ter minates in service equipment in accordance with Section 6 . 2) Notwithsta nding Subrule 1), consumer ’s service conductor s shall be permitt ed to be prot ected by an overcurrent device at the service equip...
252
CEC-2024.pdf
166
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 160 c) as pr ovided for by other Rules of this Code. 2) Except as prov ided for by Subrule 1) c), the rating of overcurrent prot ection shall not exceed a) 15 A for No. 14 AWG copper conductor s; b) 20 A for No. 12 AW...
253
CEC-2024.pdf
167
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 161 14-206 Fuseholders for plug fuses Fuseholder s for plug fuses shall be of the so-called “covered” type where readily accessible to unauthorized per sons. 14-208 Rating of fuses 1) Plug fuses shall be rated at not...
254
CEC-2024.pdf
168
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 162 2) If the batt ery voltage drops to a value insufficient to operate the circuit breaker overcurrent element a) the circuit breaker shall automatically trip; or b) an alarm shall operat e continuously until the ba...
255
CEC-2024.pdf
169
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 163 3) Where multiple disconnecting means as in Subrule 1) b) are prov ided, suitable warning signs shall be placed on or adjacent to each disconnecting means so that all of the disconnecting means must be opened to e...
256
CEC-2024.pdf
170
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 164 iii) the switc h is rat ed at not less than 10 A, 125 V; 5 A, 250 V; or for the four -way types, 5 A, 125 V; 2 A, 250 V; c) canopy switch es contr olling a tungs ten-fi lament lamp load shall be “T” rat ed or shal...
257
CEC-2024.pdf
171
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 14 Protection and control March 2024 © 2024 Canadian Standards Association 165 disconnecting of the apparatus fr om the supply circuit shall be permitt ed to be arranged so that it also disconnects the remot e contr ol circuit fr om the supply circuit. 14-610 Protection of circuits supplying...
258
CEC-2024.pdf
172
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 16 Class 1 and Class 2 circuits March 2024 © 2024 Canadian Standards Association 166 Section 16 — Class 1 and Class 2 circuits General 16-000 Scope (see Appendix B ) 1) This Section applies to a) Class 1 and Class 2 remot e contr ol circuits; b) Class 1 and Class 2 signal circuits; c) Clas...
259
CEC-2024.pdf
173
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 16 Class 1 and Class 2 circuits March 2024 © 2024 Canadian Standards Association 167 16-102 Methods of installation for Class 1 circuits The equipment and insulated conductor s of Class 1 circuits shall be ins talled in accordance with the requirements of other appr opriate Sections of this ...
260
CEC-2024.pdf
174
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 16 Class 1 and Class 2 circuits March 2024 © 2024 Canadian Standards Association 168 16-118 Class 1 circuits extending aerially beyond a building Class 1 circuits that ext end aerially beyond a building shall comply with Rules 12-300 to 12-318 .Class 2 circuits 16-200 Limitations of Class 2...
261
CEC-2024.pdf
175
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 16 Class 1 and Class 2 circuits March 2024 © 2024 Canadian Standards Association 169 16-204 Marking A Class 2 power supply unit shall have permanent markings that are readily visible aft er inst allation to indicate a) the class of supply and its electrical rating; and b) suitability for wet ...
262
CEC-2024.pdf
176
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 16 Class 1 and Class 2 circuits March 2024 © 2024 Canadian Standards Association 170 2) Where electric lighting or power conductor s are bare, all Class 2 circuit insulat ed conductor s and cables in the same r oom or space shall be enclosed in a metal raceway that is bonded to gr ound, and ...
263
CEC-2024.pdf
177
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 16 Class 1 and Class 2 circuits March 2024 © 2024 Canadian Standards Association 171 iii) 60 V continuous dc; and iv) 24.8 V peak for inter rupted dc (square wave dc at a rate of 10 to 200 Hz); and b) for wet locations (not including immers ion) i) 15 V rms for sinusoidal ac; ii) 21.2 V pe...
264
CEC-2024.pdf
178
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 16 Class 1 and Class 2 circuits March 2024 © 2024 Canadian Standards Association 172 3) Where communication cable not marked with the suffix “-LP” is used a) the maximum current that each insulated conductor shall be permitt ed to carry shall be as specified in Table 60 , based on i) the si...
265
CEC-2024.pdf
179
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 173 Section 18 — Hazardous locations Scope and introduction 18-000 Scope (see Appendices B and J ) 1) This Section applies to locations in which electrical equipment and wiring are subject to the conditions indicate d by...
266
CEC-2024.pdf
180
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 174 EPL Dc — equipment for explosive dus t atmospheres, having an “enhanced” level of prot ection, that is not a source of ignition in normal operation and may have some additional prot ection to ensure that it remains i...
267
CEC-2024.pdf
181
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 175 Seals — Explosion seal — a seal that a) when installed at a cable or conduit entry to an explosion-pr oof, flamepr oof “d”, or flamepr oof “db”, enclosure, prevents the ignition of an explosive gas atmosphere outsid...
268
CEC-2024.pdf
182
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 176 Zone 22 — a location in which an explosive dus t atmosphere, in the form of a cloud of dust in air , is not likely to occur in normal operation but, if it does occur , will per sis t for a short period only . 18-004 C...
269
CEC-2024.pdf
183
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 177 6) Equipment with a type of prot ection permit ted in a Zone 20, Zone 21, or Zone 22 location shall be suitable for one of the following: a) Group IIIC , combustible metal dust s; b) Group IIIB , combustible dust oth...
270
CEC-2024.pdf
184
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 178 b) have the metal coverings continuously covered with insulating material and bonded to gr ound at the point of termi nation in the hazardous location only . 18-062 Optical fiber cable (see Appendix B ) Optical fiber ...
271
CEC-2024.pdf
185
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 179 c) the location is continuously monitored by a combustible gas det ection sy st em that will i) activat e an alarm when the gas concentration reaches 20% of the lower flammable limit; ii) activat e ventilating equipm...
272
CEC-2024.pdf
186
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 180 Δ 18-078 Threaded joints (see Appendix B ) 1) Threaded joints that are required to be explosion-proof, flameproof “d”, or flameproof “db” shall be permitt ed to be either tapered or s traight, and shall comply with the...
273
CEC-2024.pdf
187
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 181 4) Where a cable gland entry to an increased safety “e” enclosure is thr ough a clearance hole, an O-ring, sealing washer , or sealing locknut shall be used to maintain the degree of prot ection. 5) Cables shall be in...
274
CEC-2024.pdf
188
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 182 18-110 Flexible cords, Zone 1 1) Flexible cords shall be permitt ed to be used for connection between a portable lamp, or other portable utilization equipment, and the fixed portion of its supply circuit and, where u...
275
CEC-2024.pdf
189
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 183 b) the pot ential discharge energy is det ermined to be non-incendive for the application; and c) the pot ential discharge energy calculation is document ed and authenticat ed by the per son assuming responsibility f...
276
CEC-2024.pdf
190
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 184 5) Except as permitt ed in Subrule 6), flammable fluid migration seals for conduit shall be installed where a) the conduit leaves the Zone 2 location uninterrupt ed between the seal and the point at which the condui...
277
CEC-2024.pdf
191
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 185 4) Where flexible connections are subject to oil or other corros ive conditions, the insulation of the conductor s shall be suitable for the condition or shall be prot ected by means of a suitable sheath. 5) Wiring m...
278
CEC-2024.pdf
192
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 18 Hazardous locations March 2024 © 2024 Canadian Standards Association 186 b) where suspended by threaded rigid conduit s tems longer than 300 mm, prov ided with i) permanent and effective bracing against later al displacement at a level not more than 300 mm from the point of at tachment to...
279
CEC-2024.pdf
193
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 187 Section 20 — Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, f...
280
CEC-2024.pdf
194
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 188 Δ 8) Except as permitt ed by Subrule 11), electrical wiring and equipment, any portion of which is below t...
281
CEC-2024.pdf
195
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 189 Propane vehicle fuel dispensers, container filling, and storage 20-030 Scope (see Appendix B ) Rules 20-0...
282
CEC-2024.pdf
196
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 190 2) Where dispensing devices are supplied by rigid metal conduit, the requirements of Rule 20-006 2) and ...
283
CEC-2024.pdf
197
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 191 2) Permanently ins talled luminaires that are located over lanes thr ough which vehicles are commonly dri...
284
CEC-2024.pdf
198
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 192 20-302 Hazardous locations 1) The following areas shall be Zone 1 locations: a) where adequate ventilat...
285
CEC-2024.pdf
199
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 193 b) the panel is non-combus tible and effectively isolates the hazardous area from the area in which the ...
286
CEC-2024.pdf
200
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 194 b) the electr ostaticall y charged exposed elements of the hand gun shall be capable of being energized o...
287
CEC-2024.pdf
201
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 195 Δ 5) Except as permitt ed by Subrule 6), electrical wiring and equipment, any portion of which is in or be...
288
CEC-2024.pdf
202
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 196 2) Where s tanchions, ros trums, and docks are not locat ed, or are not likely to be located , in a hazar...
289
CEC-2024.pdf
203
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 20 Flammable liquid and gasoline dispensing, service stations, garages, bulk storage plants, finishing processes, and aircraft hangars March 2024 © 2024 Canadian Standards Association 197 4) Equipment shall not be operated in areas where maintena nce operations likely to release hazardous va...
290
CEC-2024.pdf
204
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 22 Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present March 2024 © 2024 Canadian Standards Association 198 Section 22 — Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present General 22-000 Scope This Section ap...
291
CEC-2024.pdf
205
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 22 Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present March 2024 © 2024 Canadian Standards Association 199 3) Flexible cords, portable power cables, and at tachment plugs for portable equipment shall comply with the requirements of Subrules 1) and 2)...
292
CEC-2024.pdf
206
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 22 Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present March 2024 © 2024 Canadian Standards Association 200 Drainage, sealing, and exclusion of moisture and corrosive vapour 22-300 Drip loops Where exposed insulat ed conductor s or non-metallic-sheath...
293
CEC-2024.pdf
207
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 22 Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present March 2024 © 2024 Canadian Standards Association 201 Continuous positive pressure ventilation — a ventilation s ys tem capable of maintaining a positive pressure in a r oom or area and of changing...
294
CEC-2024.pdf
208
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 22 Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present March 2024 © 2024 Canadian Standards Association 202 3) Electrical equipment ins talled in a wet or damp Cat egory 2 location shall be in accordance with the applicable requirements of this Code, ...
295
CEC-2024.pdf
209
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 22 Locations in which corrosive liquids, vapours, or excessive moisture are likely to be present March 2024 © 2024 Canadian Standards Association 203 4) Devices such as receptacles and general-use switc hes inst alled where wash-down operation is performed shall be prot ected by a suitable en...
296
CEC-2024.pdf
210
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 24 Patient care areas March 2024 © 2024 Canadian Standards Association 204 Section 24 — Patient care areas 24-000 Scope (see Appendix B ) 1) This Section applies to the inst allation of a) electrical wiring and equipment within patient care areas of health care facilities; and b) the portio...
297
CEC-2024.pdf
211
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 24 Patient care areas March 2024 © 2024 Canadian Standards Association 205 Health care facility adminis tration — the unit responsible for planning, organizing, directing, and contr olling the health care facility in accordance with the policies of the health care facility and government s ta...
298
CEC-2024.pdf
212
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 24 Patient care areas March 2024 © 2024 Canadian Standards Association 206 24-104 Circuits in basic care areas (see Appendix B ) 1) The branch circuits supplying receptacles or permanently connect ed equipment in basic care areas shall be supplied fr om a gr ounded dis tribution sy st em. 2) ...
299
CEC-2024.pdf
213
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 24 Patient care areas March 2024 © 2024 Canadian Standards Association 207 Δ 5) Each panelboard supplying branch circuits as described in Rule 24-104 3) and locat ed in a basic care area shall be bonded to gr ound by a copper bonding conductor that is a) inst alled in the same raceway as the ...