CSA C22.1:24 Section 24 Patient care areas March 2024 © 2024 Canadian Standards Association 208 24-112 Circuits in intermediate and critical care areas (see Appendix B ) The branch circuits supplying receptacles or other permanently connect ed equipment in inter mediate or critical care areas shall be supplied fr...
301
CEC-2024.pdf
215
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 24 Patient care areas March 2024 © 2024 Canadian Standards Association 209 ii) RW75 XLPE; iii) RW90 EP; or iv) RW90 XLPE; c) have the insulation of one circuit conductor coloured orange and the other coloured brow n; d) have the orange-insulat ed conductor connect ed to the nickel screw of ...
302
CEC-2024.pdf
216
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 24 Patient care areas March 2024 © 2024 Canadian Standards Association 210 24-302 Circuits in essential electrical systems (see Appendix B ) 1) An essential electrical sy st em shall consist of circuits that supply loads designated by the health care facility administ ration as being essentia...
303
CEC-2024.pdf
217
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 211 Section 26 — Installation of electrical equipment General 26-000 Reserved for future use. 26-002 Connection to identified terminals or leads Wherever a device having an identified terminal or lead is...
304
CEC-2024.pdf
218
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 212 c) equipment other than transformers is prov ided with i) a means of absorbing gases generated by arcing inside the case; or ii) a pressure relief device; d) transformer s with ratings exceeding 25 ...
305
CEC-2024.pdf
219
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 213 or on Column 4 of Table 2 or 4 , unless equipment using other types of fuses is marked as being suitable for such use. Capacitors 26-200 Capacitors exempted The requirements of Rules 26-202 to 26-22...
306
CEC-2024.pdf
220
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 214 b) the rating of the disconnecting means, the overcurrent device, and the size of the motor circuit conductor s need not be greate r than would be required without the capacitor; and c) the ampacity ...
307
CEC-2024.pdf
221
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 215 26-242 Outdoor transformer and unit substation installations 1) Except as permitt ed by Subrule 2), where transformer s or unit subs tations, including their conductor s, cables, and contr ol and pro...
308
CEC-2024.pdf
222
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 216 26-250 Overcurrent protection for power and distribution transformer circuits rated over 750 V 1) Except as permitt ed in Subrules 2), 3), and 4), each ungrou nded conductor of the transformer feeder...
309
CEC-2024.pdf
223
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 217 device shall be considered as prot ecting secondary conductors rated at 125% or more of the rated secondary current. 2) Notwithsta nding Subrule 1), a transformer having an overcurrent device on the ...
310
CEC-2024.pdf
224
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 218 ii) the enclosures are ins talled outdoor s, if filled with an insulating medium that will burn in air . 26-262 Marking of transformers Each transformer shall be prov ided with a nameplat e bearing th...
311
CEC-2024.pdf
225
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 219 26-306 Barbed wire The fence shall be topped with not less than three st rands of barbed wire. 26-308 Setting of posts 1) Pos ts shall be set at a depth of 1.1 m for end, gat e, and corner pos ts an...
312
CEC-2024.pdf
226
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 220 2) Wood shall be impregnat ed, treat ed, or well paint ed before assembly and, where in contact with the earth or concrete, shall be impregnated or otherwise suitably treat ed against decay .Electrica...
313
CEC-2024.pdf
227
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 221 26-402 Indoor installations of lightning arresters 1) Where lightning arrest ers are instal led in a building, they shall be locat ed well away fro m all equipment other than that which they prot ect...
314
CEC-2024.pdf
228
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 222 26-554 Use of incandescent lamps as resistance devices 1) Incandescent lamps shall be permit ted to be used a) as pr otectiv e resis tor s for automatic contr oller s; or b) where a deviation has be...
315
CEC-2024.pdf
229
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 223 26-654 Branch circuits for residential occupancies Branch circuits for all residential occupancies (including dwelling units and single dwellings) shall meet the following requirements: a) receptacl...
316
CEC-2024.pdf
230
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 224 26-658 Arc-fault protection of branch circuits for dwelling units (see Appendix B ) Arc-fault prot ection of branch circuits for dwelling units shall meet the following requirements: a) Each branch ci...
317
CEC-2024.pdf
231
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 225 26-702 Bonding of receptacles (see Appendix B ) 1) Where gr ounding-type receptacles are used in exis ting installations to replace the ungrou nded type, the ground ing t erminal shall be effectively ...
318
CEC-2024.pdf
232
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 226 d) locat ed within 7.5 m of the rooft op electrical equipment; e) locat ed not less than 750 mm above the finished roof; and f) prot ect ed from mechanical damage. 26-712 Sump pump receptacles (see ...
319
CEC-2024.pdf
233
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 227 l) at leas t one receptacle shall be provid ed for each cord-connect ed central vacuum sy st em, where the complete duct for such a central vacuum sy st em is ins talled; m) public corridors in buildi...
320
CEC-2024.pdf
234
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 228 Electric heating and cooking appliances 26-740 Location of non-portable appliances Non-portable electric heating and cooking appliances shall be ins talled so that the danger of igniting adjacent co...
321
CEC-2024.pdf
235
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 229 b) if the appliance has more than one individual heating element, each controll ed by a switc h, no main switch need be prov ided. 3) For the purpose of this Rule, two or more separate built -in cooki...
322
CEC-2024.pdf
236
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 230 Pipe organs 26-900 Installation of electrically operated pipe organs 1) Organ blower motor s, when located remot e fr om the organ console, shall be prov ided with a pilot lamp located at the organ ...
323
CEC-2024.pdf
237
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 26 Installation of electrical equipment March 2024 © 2024 Canadian Standards Association 231 e) the supply cables shall be run from an out door connection facility , above or below gro und, to the main dist ribution panelboard in accordance with the requirements of Section 12 . 2) Notwithsta ...
324
CEC-2024.pdf
238
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 232 Section 28 — Motors and generators Scope 28-000 Scope This Section supplements or amends the general requirements of this Code and applies to the inst allation, wiring methods, conductor s, prot ection, and contr ol...
325
CEC-2024.pdf
239
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 233 28-014 Methods of guarding Methods of guarding of motor s having exposed live parts shall be by a) inst allation in a room or enclosure that is accessible only to authorized per sons; b) inst allation on a suitable...
326
CEC-2024.pdf
240
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 234 insulated conductor s, except that where the tap conductors do not exceed 7.5 m in length, they shall be permitt ed to be sized in accordance with Subrule 1) or 2), prov ided that the ampacity so det ermined is not...
327
CEC-2024.pdf
241
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 235 2) The overcurrent device required by Subrule 1) shall be a) a non-time-delay fuse; b) a time-delay fuse; c) an inverse-time circuit breaker; d) an instantaneou s-trip (magnetic only) circuit int errupte r applie...
328
CEC-2024.pdf
242
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 236 28-206 Grouping of motors on a single branch circuit Two or more motor s shall be permit ted to be grouped under the prot ection of a single set of branch circuit overcurrent devices having a rating or setting calc...
329
CEC-2024.pdf
243
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 237 Overload and overheating protection 28-300 Overload protection required The branch circuit conductor s and control equipment of each motor shall have overload pr otection, except as permitt ed by Rule 28-308 . 28-...
330
CEC-2024.pdf
244
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 238 28-312 Automatic restarting after overload Where automatic res tarting of a motor after a shut down on overload could cause injury to persons, the overload or overheating devices prot ecting the motor shall be arra...
331
CEC-2024.pdf
245
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 239 28-502 Control location A motor contr olled manually , either directly or by remote contr ol of a motor start er , shall have the means to operat e of the contr oller locat ed as follows: a) the contr oller shall ...
332
CEC-2024.pdf
246
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 240 b) a hors epower rating not less than that of the larges t motor in the gr oup if a motor -circuit switch is used. 3) A disconnecting means for a motor , motor start er , or contr oller shall comply with Subrule 1)...
333
CEC-2024.pdf
247
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 241 b) where int ended to serve as a single disconnecting means for a motor branch circuit, motor , and contr oller or s tarter , also be i) locat ed in accordance with Subrule 3); or ii) capable of being locked in th...
334
CEC-2024.pdf
248
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 242 2) Subrule 1) shall not be deemed to require use of overcurrent devices rated or set at less than 15 A. 28-710 Overload protection The branch circuit insulated conductor s and control equipment for each motor -comp...
335
CEC-2024.pdf
249
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 243 28-806 Overcurrent protection 1) Each ungr ounded conductor on the supply side of the controll er shall be prot ected by an overcurrent device rated or set in accordance with Rule 28-200 for the larges t full load ...
336
CEC-2024.pdf
250
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 28 Motors and generators March 2024 © 2024 Canadian Standards Association 244 Δ 28-904 Conductor size 1) Where the generator is designed to prevent being overloaded, the conductor s fr om the generator output terminals to the fir st overcurrent prot ection device shall have an ampacity of not...
337
CEC-2024.pdf
251
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 245 Section 30 — Installation of lighting equipment 30-000 Scope This Section applies to the inst allation of lighting equipment and supplements or amends the general requirements of this Code. 30-002 Spe...
338
CEC-2024.pdf
252
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 246 30-104 Protection (see Appendix B ) The maximum rating of an overcurrent device prot ecting a branch circuit containing luminaires, lampholders, or lighting track shall be as follows: a) when ins talle...
339
CEC-2024.pdf
253
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 247 2) Lampholders and luminaires of the pendant or suspended type, and lampholder s and luminaires of the bare lamp type, shall not be inst alled in clothes closets. Installation of lighting equipment 30-...
340
CEC-2024.pdf
254
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 248 30-310 Luminaire as a raceway 1) Insulat ed branch circuit conductor s run throu gh a luminaire shall be contained in a raceway that is an integral part of the luminaire and that meets the requirements...
341
CEC-2024.pdf
255
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 249 30-322 Totally enclosed gasketted luminaires Incandescent totally enclosed gaskett ed luminaires, unless marked as suitable for the purpose, shall not be mount ed on a combustible ceiling. 30-324 Inst...
342
CEC-2024.pdf
256
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 250 30-500 — Reserved for future use .Lampholders 30-600 Connections to lampholders The identified insulated conductor , if present, shall be connected to the lampholder screwshell. 30-602 Switched lampho...
343
CEC-2024.pdf
257
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 251 3) The metal cabinet, if not part of the luminaire, shall be installed as close as possible to the luminaire. 4) Where display cases are not permanently ins talled, no part of a secondary circuit shall b...
344
CEC-2024.pdf
258
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 252 30-808 Liquid-filled transformers Transformers of the liquid-filled type shall not be used unless they are filled with a non-flammable liquid. 30-810 Transformers — Secondary connection 1) The high-vol...
345
CEC-2024.pdf
259
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 253 30-906 Luminaires designed for thermal insulation contact The recessed portion of every recessed luminaire marked “Type IC” or “Type IC, inherently prot ect ed” shall be permitt ed to be in contact wit...
346
CEC-2024.pdf
260
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 254 3) Rules 30-1002 to 30-1118 cover only that portion of the inst allation that is outside the buildings. 30-1002 Service equipment 1) Service equipment shall comply with Section 6 for low -voltage insta...
347
CEC-2024.pdf
261
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 255 30-1012 Pole-top branch circuit wiring Pole-top branch circuit wiring, exclusive of leads prov ided with the floodlights to which they are connect ed, shall be run a) as lead-sheathed cable or rubber ...
348
CEC-2024.pdf
262
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 256 30-1028 Installation of lightning arresters Where lightning arrest ers are instal led, a common ground ing conductor and common electr ode shall be permitt ed to be used for ground ing primary and seco...
349
CEC-2024.pdf
263
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 30 Installation of lighting equipment March 2024 © 2024 Canadian Standards Association 257 30-1114 Protection of lampholders Notwithsta nding Rule 30-104 , lampholders shall be permitt ed to be connect ed to branch circuits prot ect ed by overcurrent devices rat ed or set at not more than 30...
350
CEC-2024.pdf
264
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 32 Fire alarm systems, smoke alarms, carbon monoxide alarms, and fire pumps March 2024 © 2024 Canadian Standards Association 258 Section 32 — Fire alarm systems, smoke alarms, carbon monoxide alarms, and fire pumps (See Appendix G )32-000 Scope (see Appendix B ) 1) This Section applies to t...
351
CEC-2024.pdf
265
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 32 Fire alarm systems, smoke alarms, carbon monoxide alarms, and fire pumps March 2024 © 2024 Canadian Standards Association 259 32-104 Equipment bonding 1) Exposed non-current -carrying metal parts of electrical equipment, including outlet boxes, conductor enclosures, raceways, and cabinets...
352
CEC-2024.pdf
266
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 32 Fire alarm systems, smoke alarms, carbon monoxide alarms, and fire pumps March 2024 © 2024 Canadian Standards Association 260 b) incorporat ed in a cable, having a metal armour or sheath, of a type selected in accordance with Rule 12-102 3); c) inst alled in rigid non-metallic conduit wher...
353
CEC-2024.pdf
267
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 34 Signs and outline lighting March 2024 © 2024 Canadian Standards Association 261 Section 34 — Signs and outline lighting 34-000 Scope 1) This Section applies to signs and outline lighting in which the sources of light are a) incandescent lamps; b) fluorescent lamps; c) high-voltage lumin...
354
CEC-2024.pdf
268
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 34 Signs and outline lighting March 2024 © 2024 Canadian Standards Association 262 34-108 Supporting means Poles, mas ts, st andards, or devices designed as mechanical supports or used as electrical raceways shall be suitable. 34-110 Bonding 1) All conductive non-current -carrying parts of ...
355
CEC-2024.pdf
269
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 34 Signs and outline lighting March 2024 © 2024 Canadian Standards Association 263 34-308 Neon supply installation 1) Neon supplies shall be ins talled in locations such that they are accessible and capable of being removed and replaced. 2) Where that location is in an att ic, bulkhead, or ...
356
CEC-2024.pdf
270
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 34 Signs and outline lighting March 2024 © 2024 Canadian Standards Association 264 34-402 High-voltage cables in show windows and similar locations Where high-voltage cables used with signs hang freely in the air and are not enclosed in raceways, as in show windows and similar locations, the...
357
CEC-2024.pdf
271
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 265 Section 36 — High-voltage installations General 36-000 Scope (see Appendix B ) 1) This Section applies to instal lations operating at voltages in excess of 750 V. 2) The supply authority and the inspection dep...
358
CEC-2024.pdf
272
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 266 3) Suitable warning signs shall be erect ed in a conspicuous place adjacent to fuses and shall warn operators not to replace fuses while the supply circuit is energized. 4) Where the possibility of feedback ex...
359
CEC-2024.pdf
273
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 267 36-104 Shielding of thermoset insulated conductors (see Appendix B ) 1) Except as permitt ed in Subrules 2), 3), and 4), shielding shall be provided over the thermoset insulation of each permanently inst alled ...
360
CEC-2024.pdf
274
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 268 36-114 Joints in sheathed cables 1) Splices or taps in sheathed cables shall have the conductor or cable covered with insulation and shall have shielding, when used, electrically and mechanically equivalent to...
361
CEC-2024.pdf
275
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 269 b) there is no access to the fuses where the fuses may be energized from either side, unless the isolating or disconnecting means on both sides of the fuses are in the de-energized position; and c) there is no...
362
CEC-2024.pdf
276
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 270 b) have the gr ound r ods inter connected by gr ound grid conductor s not less than No. 2/0 AWG bare copper buried to a maximum depth of 600 mm below the rough st ation grade and a minimum depth of 150 mm belo...
363
CEC-2024.pdf
277
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 271 connect ed to the stati on are to be found, shall not exceed the tolerable values specified in Table 52 . 3) When a s tation ground electr ode design is selected according to the proced ure specified in the Not...
364
CEC-2024.pdf
278
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 272 d) a metal wat er main inside or adjacent to the stati on gr ound electrod e area shall be gr ounded by at least one copper conductor of not less than No. 2/0 AWG copper , at inter vals not exceeding 12 m; e)...
365
CEC-2024.pdf
279
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 36 High-voltage installations March 2024 © 2024 Canadian Standards Association 273 iii) have dimensions appro ximate ly 1.2 m × 1.8 m; and iv) be permitt ed to be covered by a layer of crushed st one, asphalt, or concret e not exceeding 150 mm in depth. 36-312 Grounding of metallic fence en...
366
CEC-2024.pdf
280
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 274 Section 38 — Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with ...
367
CEC-2024.pdf
281
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 275 38-011 Insulation and types of conductors 1) Conductor s in hois tways, in or on cars or platforms, in...
368
CEC-2024.pdf
282
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 276 conduit, or wireways, except that mineral-insulat ed cable, aluminum-sheathed cable, copper - sheathed ...
369
CEC-2024.pdf
283
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 277 contr oller ter minal s tuds without regard to the current -carrying capacity requirements of Section ...
370
CEC-2024.pdf
284
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 278 and cables are support ed and prot ected fr om physical damage and are of a jacket ed and flame-t est ...
371
CEC-2024.pdf
285
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 279 38-037 Wiring in hoistways, machine rooms, control rooms, and machinery spaces and control spaces Unl...
372
CEC-2024.pdf
286
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 280 8) Where there is more than one driving machine in a machine r oom, the disconnecting means shall be n...
373
CEC-2024.pdf
287
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 281 3) The disconnecting means shall be numbered to correspond to the identifying number of the car whose ...
374
CEC-2024.pdf
288
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 38 Elevators, dumbwaiters, material lifts, escalators, moving walks, lifts for persons with physical disabilities, and similar equipment March 2024 © 2024 Canadian Standards Association 282 38-082 Bonding of equipment The frames of all motor s, generators, machines, and contr ollers, and the...
375
CEC-2024.pdf
289
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 40 Electric cranes and hoists March 2024 © 2024 Canadian Standards Association 283 Section 40 — Electric cranes and hoists 40-000 Scope This Section applies to features of the ins tallations of electrical equipment prov iding circuits for electric cranes, hois ts, and monorails, and suppleme...
376
CEC-2024.pdf
290
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 40 Electric cranes and hoists March 2024 © 2024 Canadian Standards Association 284 permitt ed to be increased to a maximum of 12 m if the separation between contact conductor s is increased proportionat ely . 2) Rigid main contact conductor s shall be secured to insulating supports spaced at ...
377
CEC-2024.pdf
291
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 42 Electric welders March 2024 © 2024 Canadian Standards Association 285 Section 42 — Electric welders General 42-000 Scope This Section applies to the inst allation of electric welders and supplements or amends the general requirements of this Code. 42-002 Special terminology In this Sect...
378
CEC-2024.pdf
292
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 42 Electric welders March 2024 © 2024 Canadian Standards Association 286 b) the rating or setting otherwise required by this Rule results in too frequent opening of the overcurrent device. 3) The maximum rating or set ting of an overcurrent device prot ecting a feeder supplying a gr oup of t...
379
CEC-2024.pdf
293
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 42 Electric welders March 2024 © 2024 Canadian Standards Association 287 42-016 Overcurrent protection 1) Every resis tance welder shall have overcurrent prot ection rated or set at not more than 300% of the rated primary current of the welder unless the overcurrent device prot ecting the in...
380
CEC-2024.pdf
294
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 44 Theatre installations March 2024 © 2024 Canadian Standards Association 288 Section 44 — Theatre installations Scope 44-000 Scope This Section applies to electrical equipment and ins tallations in buildings or parts of a building designed, inten ded, or used for dramatic, operatic, motion p...
381
CEC-2024.pdf
295
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 44 Theatre installations March 2024 © 2024 Canadian Standards Association 289 44-208 Fuses Fuses on switch boards shall be a) of either the plug or cartridge type; and b) prov ided with enclosures in addition to the switch board enclosure. 44-210 Overcurrent protection 1) All circuits leav...
382
CEC-2024.pdf
296
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 44 Theatre installations March 2024 © 2024 Canadian Standards Association 290 44-302 Metal work 1) The metal work for footlights, border s, prosc enium sidelights, and s trips shall be not less than 0.78 mm thick. 2) The metal work for bunches and portable st rips shall be not less than 0.5...
383
CEC-2024.pdf
297
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 44 Theatre installations March 2024 © 2024 Canadian Standards Association 291 2) Receptacles intende d for the connection of incandescent lamps shall a) have an ampere rating not less than 15 A; and b) be supplied by insulat ed conductors not smaller than No. 12 AWG copper or No. 10 AWG alum...
384
CEC-2024.pdf
298
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 46 Emergency power supply, unit equipment, exit signs, and life safety systems March 2024 © 2024 Canadian Standards Association 292 Section 46 — Emergency power supply, unit equipment, exit signs, and life safety systems 46-000 Scope (see Appendix B ) 1) This Section applies to the inst allat...
385
CEC-2024.pdf
299
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 46 Emergency power supply, unit equipment, exit signs, and life safety systems March 2024 © 2024 Canadian Standards Association 293 46-108 Wiring method (see Appendices B and G ) 1) Except as permitt ed by Subrule 3), Rule 46-304 3), and Rule 46-400 2), the following insulat ed conductor s sh...
386
CEC-2024.pdf
300
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 46 Emergency power supply, unit equipment, exit signs, and life safety systems March 2024 © 2024 Canadian Standards Association 294 the emergency power supply and located outside the generator ro om shall be prot ect ed against fire exposure to provide continued operation in compliance with t...
387
CEC-2024.pdf
301
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 46 Emergency power supply, unit equipment, exit signs, and life safety systems March 2024 © 2024 Canadian Standards Association 295 46-306 Remote lamps (see Appendix B ) 1) The size of insulated circuit conductors to remote lamps shall be such that the voltage drop does not exceed 5% of the m...
388
CEC-2024.pdf
302
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 52 Diagnostic imaging installations March 2024 © 2024 Canadian Standards Association 296 Section 52 — Diagnostic imaging installations 52-000 Scope 1) This Section applies to the inst allation of X-ray and other diagnost ic imaging equipment operating at any frequency and supplements or amen...
389
CEC-2024.pdf
303
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 52 Diagnostic imaging installations March 2024 © 2024 Canadian Standards Association 297 52-012 Control 1) For stationary equipment, the low -voltage circuit of the s tep-u p transformer shall contain an overcurrent device that a) has no exposed live parts; b) prot ects the radiographic cir...
390
CEC-2024.pdf
304
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 298 Section 54 — Community antenna distribution and radio and television installations 54-000 Scope 1) This Section supplements or amends the general requirements of this ...
391
CEC-2024.pdf
305
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 299 Community antenna distribution 54-100 Conductors 1) The conductor s used in community ante nna dis tribution shall consist of coaxial cable having a central inner con...
392
CEC-2024.pdf
306
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 300 the out er conductive shield of the coaxial cable shall be ground ed at the building as close to the point of cable entry as possible. 2) Where the outer conductive s...
393
CEC-2024.pdf
307
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 301 2) Where the electric lighting or power conductor s are bare, all community ante nna dist ribution cables in the same r oom or space shall be enclosed in a gr ounded m...
394
CEC-2024.pdf
308
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 302 Conductors outside buildings 54-600 Overhead cables on poles The instal lation of overhead community ante nna distri bution cables in proxim ity to power conductor s ...
395
CEC-2024.pdf
309
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 303 d) placed with a layer of sand 75 mm deep, both above and below the cable, if in rocky or s tony gr ound; e) placed at a minimum depth of 900 mm under an area that is ...
396
CEC-2024.pdf
310
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 304 Grounding for receiving equipment and amateur transmitting equipment 54-900 Material for grounding conductor The ground ing conductor shall be of copper , aluminum al...
397
CEC-2024.pdf
311
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 54 Community antenna distribution and radio and television installations March 2024 © 2024 Canadian Standards Association 305 54-1006 Amplifiers Audio amplifier s that are located outside the transmit ter housing shall be suitably housed and shall be locat ed to be readily accessible and adequ...
398
CEC-2024.pdf
312
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 56 Optical fiber cables March 2024 © 2024 Canadian Standards Association 306 Section 56 — Optical fiber cables Scope 56-000 Scope This Section applies to the inst allation of optical fiber cables in conjunction with electrical sy st ems and supplements or amends the general requirements of t...
399
CEC-2024.pdf
313
tradeloom_data/ElectricalDataSourcesClean/CEC and Ontario Amendments/CEC-2024.pdf
CSA C22.1:24 Section 56 Optical fiber cables March 2024 © 2024 Canadian Standards Association 307 b) communication circuits in accordance with Section 60 ; or c) community ant enna dis tribution and radio and tel evision circuits in accordance with Section 54 . 2) Conductive optical fiber cables shall not occupy...