Chapter 4 Equipment for General Use
406.7(B)
Attachment plugs shall be installed so that their prongs, blades, or pins are not energized unless inserted into an energized receptacle or cord connectors. No receptacle shall be installed so as to require the insertion of an energized attachment plug as its source of supply. [406.7(B)](https://2023.antflix.net#406.7(...
https://2023.antflix.net#406.7(B)
Chapter 4 Equipment for General Use
406.7(C)
Attachment plug ejector mechanisms shall not adversely affect engagement of the blades of the attachment plug with the contacts of the receptacle. [406.7(C)](https://2023.antflix.net#406.7(C))
https://2023.antflix.net#406.7(C)
Chapter 4 Equipment for General Use
406.7(D)
A flanged surface inlet shall be installed such that the prongs, blades, or pins are not energized unless an energized cord connector is inserted into it. [406.7(D)](https://2023.antflix.net#406.7(D))
https://2023.antflix.net#406.7(D)
Chapter 4 Equipment for General Use
406.8
Receptacles, cord connectors, and attachment plugs shall be constructed such that receptacle or cord connectors do not accept an attachment plug with a different voltage or current rating from that for which the device is intended. However, a 20-ampere T-slot receptacle or cord connector shall be permitted to accept a ...
https://2023.antflix.net#406.8
Chapter 4 Equipment for General Use
406.9(A)
A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is weatherproof when the receptacle is covered (attachment plug cap not inserted and receptacle covers closed). An installation suitable for wet locations shall also be con...
https://2023.antflix.net#406.9(A)
Chapter 4 Equipment for General Use
406.9(B)(1)
Receptacles of 15 amperes and 20 amperes, 125 volts and 250 volts installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. An outlet box hood installed for this purpose shall be listed and shall be identified as extra-duty. Other listed products, enclo...
https://2023.antflix.net#406.9(B)(1)
Chapter 4 Equipment for General Use
406.9(B)(2)
All other receptacles installed in a wet location shall be listed weather-resistant type, and installation shall comply with 406.9(B)(2)(a) or (B)(2)(b). A receptacle installed in a wet location where the product intended to be plugged into it is not attended while in use shall have an enclosure that is weatherproof wi...
https://2023.antflix.net#406.9(B)(2)
Chapter 4 Equipment for General Use
406.9(C)
Receptacles shall not be installed inside of the tub or shower or within a zone measured 900 mm (3 ft) horizontally from any outside edge of the bathtub or shower stall, including the space outside the bathtub or shower stall space below the zone. The zone also includes the space measured vertically from the floor to 2...
https://2023.antflix.net#406.9(C)
Chapter 4 Equipment for General Use
406.9(D)
The enclosure for a receptacle installed in an outlet box flush-mounted in a finished surface shall be made weatherproof by means of a weatherproof faceplate assembly that provides a watertight connection between the plate and the finished surface. [406.9(D)](https://2023.antflix.net#406.9(D))
https://2023.antflix.net#406.9(D)
Chapter 4 Equipment for General Use
406.10(A)
Grounding-type receptacles, cord connectors, and attachment plugs shall be provided with one fixed grounding pole in addition to the circuit poles. The grounding contacting pole of grounding-type plug-in ground-fault circuit interrupters shall be permitted to be of the movable, self-restoring type on circuits operating...
https://2023.antflix.net#406.10(A)
Chapter 4 Equipment for General Use
406.10(B)
Grounding-type receptacles, adapters, cord connections, and attachment plugs shall have a means for connection of an equipment grounding conductor to the grounding pole. A terminal for connection to the grounding pole shall be designated by one of the following:A green-colored hexagonal-headed or -shaped terminal screw...
https://2023.antflix.net#406.10(B)
Chapter 4 Equipment for General Use
406.10(C)
A grounding terminal shall not be used for purposes other than connection to the equipment grounding conductor. [406.10(C)](https://2023.antflix.net#406.10(C))
https://2023.antflix.net#406.10(C)
Chapter 4 Equipment for General Use
406.10(D)
Grounding-type attachment plugs and mating cord connectors and receptacles shall be designed such that the equipment grounding connection is made before the current-carrying connections. Grounding-type devices shall be so designed that grounding poles of attachment plugs cannot be brought into contact with current-carr...
https://2023.antflix.net#406.10(D)
Chapter 4 Equipment for General Use
406.10(E)
Grounding-type attachment plugs shall be used only with a cord having an equipment grounding conductor. Informational Note: See 250.126 for identification of equipment grounding conductor terminals. [406.10(E)](https://2023.antflix.net#406.10(E))
https://2023.antflix.net#406.10(E)
Chapter 4 Equipment for General Use
406.11
The connection of the receptacle grounding terminal shall comply with 250.146. [406.11](https://2023.antflix.net#406.11)
https://2023.antflix.net#406.11
Chapter 4 Equipment for General Use
406.12
All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles in the following locations shall be listed tamper-resistant receptacles: All dwelling units, boathouses, mobile homes and manufactured homes, including their attached and detached garages, accessory buildings, and common areasGuest rooms and guest sui...
https://2023.antflix.net#406.12
Chapter 4 Equipment for General Use
406.13
Single-pole separable connectors shall be listed and labeled and shall comply with 406.13(A) through (D). [406.13](https://2023.antflix.net#406.13)
https://2023.antflix.net#406.13
Chapter 4 Equipment for General Use
406.13(A)
Single-pole separable connectors shall be of either the locking or latching type and marked with the manufacturer's name or identification and voltage and ampere ratings. [406.13(A)](https://2023.antflix.net#406.13(A))
https://2023.antflix.net#406.13(A)
Chapter 4 Equipment for General Use
406.13(B)
Connectors designated for connection to the grounded circuit conductor shall be identified by a white-colored housing; connectors designated for connection to the grounding circuit conductor shall be identified by a green-colored housing. [406.13(B)](https://2023.antflix.net#406.13(B))
https://2023.antflix.net#406.13(B)
Chapter 4 Equipment for General Use
406.13(C)
Single-pole separable connectors shall be permitted to be interchangeable for ac or dc use or for different current ratings or voltages on the same premises, provided they are listed for ac/dc use and marked in a suitable manner to identify the system to which they are intended to be connected. [406.13(C)](https://2023...
https://2023.antflix.net#406.13(C)
Chapter 4 Equipment for General Use
406.13(D)
The use of single-pole separable connectors shall be performed by a qualified person and shall comply with at least one of the following conditions: Connection and disconnection of connectors are only possible where the supply connectors are interlocked to the source, and it is not possible to connect or disconnect con...
https://2023.antflix.net#406.13(D)
Chapter 4 Equipment for General Use
408.1
This article covers switchboards, switchgear, and panelboards. It does not apply to equipment operating at over 1000 volts, except as specifically referenced elsewhere in the Code. [408.1](https://2023.antflix.net#408.1)
https://2023.antflix.net#408.1
Chapter 4 Equipment for General Use
408.2
The use of reconditioned equipment within the scope of this article shall be limited as described in 408.2(A) and (B). If equipment has been damaged by fire, products of combustion, corrosive influences, or water, it shall be specifically evaluated by its manufacturer or a qualified testing laboratory prior to being re...
https://2023.antflix.net#408.2
Chapter 4 Equipment for General Use
408.2(A)
Reconditioned panelboards shall not be permitted. [408.2(A)](https://2023.antflix.net#408.2(A))
https://2023.antflix.net#408.2(A)
Chapter 4 Equipment for General Use
408.2(B)
Reconditioned switchboards and switchgear, or sections of switchboards or switchgear, shall be permitted. [408.2(B)](https://2023.antflix.net#408.2(B))
https://2023.antflix.net#408.2(B)
Chapter 4 Equipment for General Use
408.3(A)
Conductors and busbars on a switchboard, switchgear, or panelboard shall comply with 408.3(A)(1) and (A)(2) as applicable. [408.3(A)](https://2023.antflix.net#408.3(A))
https://2023.antflix.net#408.3(A)
Chapter 4 Equipment for General Use
408.3(A)(1)
Conductors and busbars shall be located so as to be free from physical damage and shall be held firmly in place. [408.3(A)(1)](https://2023.antflix.net#408.3(A)(1))
https://2023.antflix.net#408.3(A)(1)
Chapter 4 Equipment for General Use
408.3(A)(2)
Other than the required interconnections and control wiring, only those conductors that are intended for termination in a vertical section of a switchboard or switchgear shall be located in that section. Exception: Conductors shall be permitted to travel horizontally through vertical sections of switchboards and switch...
https://2023.antflix.net#408.3(A)(2)
Chapter 4 Equipment for General Use
408.3(B)
The arrangement of busbars and conductors shall be such as to avoid overheating due to inductive effects. [408.3(B)](https://2023.antflix.net#408.3(B))
https://2023.antflix.net#408.3(B)
Chapter 4 Equipment for General Use
408.3(C)
Each switchboard, switchgear, or panelboard, if used as service equipment, shall be provided with a main bonding jumper sized in accordance with 250.28(D) or the equivalent placed within the panelboard or one of the sections of the switchboard or switchgear for connecting the grounded service conductor on its supply si...
https://2023.antflix.net#408.3(C)
Chapter 4 Equipment for General Use
408.3(D)
In switchboards and switchgear, load terminals for field wiring shall comply with 408.18(C). [408.3(D)](https://2023.antflix.net#408.3(D))
https://2023.antflix.net#408.3(D)
Chapter 4 Equipment for General Use
408.3(E)(1)
Alternating-current phase arrangement on 3-phase buses shall be A, B, C from front to back, top to bottom, or left to right, as viewed from the front of the switchboard, switchgear, or panelboard. The B phase shall be that phase having the higher voltage to ground on 3-phase, 4-wire, delta-connected systems. Other busb...
https://2023.antflix.net#408.3(E)(1)
Chapter 4 Equipment for General Use
408.3(E)(2)
Direct-current ungrounded buses shall be permitted to be in any order. Arrangement of dc buses shall be field marked as to polarity, grounding system, and nominal voltage. [408.3(E)(2)](https://2023.antflix.net#408.3(E)(2))
https://2023.antflix.net#408.3(E)(2)
Chapter 4 Equipment for General Use
408.3(F)
A caution sign(s) or a label(s) provided in accordance with 408.3(F)(1) through (F)(5) shall comply with 110.21(B). [408.3(F)](https://2023.antflix.net#408.3(F))
https://2023.antflix.net#408.3(F)
Chapter 4 Equipment for General Use
408.3(F)(1)
A switchboard, switchgear, or panelboard containing a 4-wire, delta-connected system where the midpoint of one phase winding is grounded shall be legibly and permanently field marked as follows: CAUTION _____ PHASE HAS _____ VOLTS TO GROUND [408.3(F)(1)](https://2023.antflix.net#408.3(F)(1))
https://2023.antflix.net#408.3(F)(1)
Chapter 4 Equipment for General Use
408.3(F)(2)
A switchboard, switchgear, or panelboard containing an ungrounded ac electrical system as permitted in 250.21 shall be legibly and permanently field marked as follows: CAUTION UNGROUNDED SYSTEM OPERATING - _____ VOLTS BETWEEN CONDUCTORS [408.3(F)(2)](https://2023.antflix.net#408.3(F)(2))
https://2023.antflix.net#408.3(F)(2)
Chapter 4 Equipment for General Use
408.3(F)(3)
A switchboard, switchgear, or panelboard containing a high-impedance grounded neutral ac system in accordance with 250.36 shall be legibly and permanently field marked as follows: CAUTION: HIGH-IMPEDANCE GROUNDED NEUTRAL AC SYSTEM OPERATING - _____ VOLTS BETWEEN CONDUCTORS AND MAY OPERATE - _____ VOLTS TO GROUND FOR IN...
https://2023.antflix.net#408.3(F)(3)
Chapter 4 Equipment for General Use
408.3(F)(4)
A switchboard, switchgear, or panelboard containing an ungrounded dc electrical system in accordance with 250.169 shall be legibly and permanently field marked as follows: CAUTION: UNGROUNDED DC SYSTEM OPERATING - _____ VOLTS BETWEEN CONDUCTORS [408.3(F)(4)](https://2023.antflix.net#408.3(F)(4))
https://2023.antflix.net#408.3(F)(4)
Chapter 4 Equipment for General Use
408.3(F)(5)
A switchboard, switchgear, or panelboard containing a resistive connection between current-carrying conductors and the grounding system to stabilize voltage to ground shall be legibly and permanently field marked as follows: CAUTION: DC SYSTEM OPERATING - _____ VOLTS BETWEEN CONDUCTORS AND MAY OPERATE - _____ VOLTS TO ...
https://2023.antflix.net#408.3(F)(5)
Chapter 4 Equipment for General Use
408.3(G)
The minimum wire-bending space at terminals and minimum gutter space provided in switchboards, switchgear, and panelboards shall be as required in 312.6. [408.3(G)](https://2023.antflix.net#408.3(G))
https://2023.antflix.net#408.3(G)
Chapter 4 Equipment for General Use
408.4(A)
Every circuit and circuit modification shall be provided with a legible and permanent description that complies with all of the following conditions as applicable: Located at each switch or circuit breaker in a switchboard or switchgearIncluded in a circuit directory that is located on the face of, inside of, or in an ...
https://2023.antflix.net#408.4(A)
Chapter 4 Equipment for General Use
408.4(B)
All switchboards, switchgear, and panelboards supplied by a feeder(s) in other than one- or two-family dwellings shall be permanently marked in accordance with the following: With the identification and physical location of where the power originatesWith a label that is permanently affixed and of sufficient durability ...
https://2023.antflix.net#408.4(B)
Chapter 4 Equipment for General Use
408.5
Where conduits or other raceways enter a switchboard, switchgear, floor-standing panelboard, or similar enclosure at the bottom, approved space shall be provided to permit installation of conductors in the enclosure. The wiring space shall not be less than shown in Table 408.5 where the conduit or raceways enter or lea...
https://2023.antflix.net#408.5
Chapter 4 Equipment for General Use
408.6
Switchboards, switchgear, and panelboards shall have a short-circuit current rating not less than the available fault current. In other than one- and two-family dwelling units, the available fault current and the date the calculation was performed shall be field marked on the enclosure at the point of supply. The marki...
https://2023.antflix.net#408.6
Chapter 4 Equipment for General Use
408.7
Unused openings for circuit breakers and switches shall be closed using identified closures, or other approved means that provide protection substantially equivalent to the wall of the enclosure. [408.7](https://2023.antflix.net#408.7)
https://2023.antflix.net#408.7
Chapter 4 Equipment for General Use
408.9
Replacement panelboards shall be permitted to be installed in existing enclosures in accordance with 408.9(A) or (B). [408.9](https://2023.antflix.net#408.9)
https://2023.antflix.net#408.9
Chapter 4 Equipment for General Use
408.9(A)
If the replacement panelboard is listed for the specific enclosure identified by either catalog number or dimensional information, the panelboard shall be permitted to maintain its short-circuit current rating. [408.9(A)](https://2023.antflix.net#408.9(A))
https://2023.antflix.net#408.9(A)
Chapter 4 Equipment for General Use
408.9(B)
If the available fault current is greater than 10,000 amperes, the completed work shall be field labeled. If the available fault current is 10,000 amperes or less, the replacement panelboard shall be identified for the application. Any previously applied listing marks on the cabinet that pertain to the panelboard shall...
https://2023.antflix.net#408.9(B)
Chapter 4 Equipment for General Use
408.16
Switchboards and switchgear in damp or wet locations shall be installed in accordance with 312.2. [408.16](https://2023.antflix.net#408.16)
https://2023.antflix.net#408.16
Chapter 4 Equipment for General Use
408.17
Switchboards and switchgear shall be placed so as to reduce to a minimum the probability of communicating fire to adjacent combustible materials. Where installed over a combustible floor, suitable protection thereto shall be provided. [408.17](https://2023.antflix.net#408.17)
https://2023.antflix.net#408.17
Chapter 4 Equipment for General Use
408.18(A)
For other than a totally enclosed switchboard or switchgear, a space not less than 900 mm (3 ft) shall be provided between the top of the switchboard or switchgear and any combustible ceiling, unless a noncombustible shield is provided between the switchboard or switchgear and the ceiling. [408.18(A)](https://2023.antf...
https://2023.antflix.net#408.18(A)
Chapter 4 Equipment for General Use
408.18(B)
Clearances around switchboards and switchgear shall comply with the provisions of 110.26. [408.18(B)](https://2023.antflix.net#408.18(B))
https://2023.antflix.net#408.18(B)
Chapter 4 Equipment for General Use
408.18(C)
Each section of equipment that requires rear or side access to make field connections shall be so marked by the manufacturer on the front. Section openings requiring rear or side access shall comply with 110.26. Load terminals for field wiring shall comply with 408.18(C)(1), (C)(2), or (C)(3) as applicable. [408.18(C)]...
https://2023.antflix.net#408.18(C)
Chapter 4 Equipment for General Use
408.18(C)(1)
Load terminals for field wiring shall be so located that it is not necessary to reach across uninsulated ungrounded bus in order to make connections. [408.18(C)(1)](https://2023.antflix.net#408.18(C)(1))
https://2023.antflix.net#408.18(C)(1)
Chapter 4 Equipment for General Use
408.18(C)(2)
Where multiple branch or feeder grounded circuit conductor load terminals for field wiring are grouped together in one location, they shall be so located that it is not necessary to reach across uninsulated ungrounded bus, whether or not energized, in order to make connections. Where only one branch or feeder set of lo...
https://2023.antflix.net#408.18(C)(2)
Chapter 4 Equipment for General Use
408.18(C)(3)
Load terminals for ungrounded conductors shall be so located that it is not necessary to reach across energized uninsulated bus in order to make connections. Bus on the line side of service, branch, or feeder disconnects is considered energized with respect to its associated load side circuits. [408.18(C)(3)](https://2...
https://2023.antflix.net#408.18(C)(3)
Chapter 4 Equipment for General Use
408.19
An insulated conductor used within a switchboard or switchgear shall be listed, shall be flame retardant, and shall be rated not less than the voltage applied to it and not less than the voltage applied to other conductors or busbars with which it may come into contact. [408.19](https://2023.antflix.net#408.19)
https://2023.antflix.net#408.19
Chapter 4 Equipment for General Use
408.20
Switchboards and switchgear that have any exposed live parts shall be located in permanently dry locations and then only where under competent supervision and accessible only to qualified persons. Switchboards and switchgear shall be located such that the probability of damage from equipment or processes is reduced to ...
https://2023.antflix.net#408.20
Chapter 4 Equipment for General Use
408.22
Instruments, relays, meters, and instrument transformers located on switchboards and switchgear shall be grounded as specified in 250.170 through 250.178. [408.22](https://2023.antflix.net#408.22)
https://2023.antflix.net#408.22
Chapter 4 Equipment for General Use
408.23
The requirements of 312.8(B) shall apply. [408.23](https://2023.antflix.net#408.23)
https://2023.antflix.net#408.23
Chapter 4 Equipment for General Use
408.30
All panelboards shall have a rating not less than the minimum feeder capacity required for the load calculated in accordance with Part III, IV, or V of Article 220, as applicable. [408.30](https://2023.antflix.net#408.30)
https://2023.antflix.net#408.30
Chapter 4 Equipment for General Use
408.36
In addition to the requirement of 408.30, a panelboard shall be protected by an overcurrent protective device having a rating not greater than that of the panelboard. This overcurrent protective device shall be located within or at any point on the supply side of the panelboard. Exception No. 1: Individual protection s...
https://2023.antflix.net#408.36
Chapter 4 Equipment for General Use
408.36(A)
Panelboards equipped with snap switches rated at 30 amperes or less shall have overcurrent protection of 200 amperes or less. [408.36(A)](https://2023.antflix.net#408.36(A))
https://2023.antflix.net#408.36(A)
Chapter 4 Equipment for General Use
408.36(B)
Where a panelboard is supplied through a transformer, the overcurrent protection required by 408.36 shall be located on the secondary side of the transformer. Exception: A panelboard supplied by the secondary side of a transformer shall be considered as protected by the overcurrent protection provided on the primary si...
https://2023.antflix.net#408.36(B)
Chapter 4 Equipment for General Use
408.36(C)
A 3-phase disconnect or overcurrent device shall not be connected to the bus of any panelboard that has less than 3-phase buses. Delta breakers shall not be installed in panelboards. [408.36(C)](https://2023.antflix.net#408.36(C))
https://2023.antflix.net#408.36(C)
Chapter 4 Equipment for General Use
408.36(D)
Plug-in-type overcurrent protection devices or plug-in type main lug assemblies that are backfed and used to terminate field-installed ungrounded supply conductors shall be secured in place by an additional fastener that requires other than a pull to release the device from the mounting means on the panelboard. [408.36...
https://2023.antflix.net#408.36(D)
Chapter 4 Equipment for General Use
408.37
Panelboards in damp or wet locations shall be installed to comply with 312.2. [408.37](https://2023.antflix.net#408.37)
https://2023.antflix.net#408.37
Chapter 4 Equipment for General Use
408.38
Panelboards shall be mounted in cabinets, cutout boxes, or identified enclosures and shall be dead-front. Where the available fault current is greater than 10,000 amperes, the panelboard and enclosure combination shall be evaluated for the application. Exception: Panelboards other than of the dead-front, externally ope...
https://2023.antflix.net#408.38
Chapter 4 Equipment for General Use
408.39
In panelboards, fuses of any type shall be installed on the load side of any switches. Exception: Fuses installed as part of service equipment in accordance with the provisions of 230.94 shall be permitted on the line side of the service switch. [408.39](https://2023.antflix.net#408.39)
https://2023.antflix.net#408.39
Chapter 4 Equipment for General Use
408.40
Panelboard cabinets and panelboard frames, if of metal, shall be in physical contact with each other and shall be connected to an equipment grounding conductor. Where the panelboard is used with nonmetallic raceway or cable or where separate equipment grounding conductors are provided, a terminal bar for the equipment ...
https://2023.antflix.net#408.40
Chapter 4 Equipment for General Use
408.41
Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another conductor. Exception: Grounded conductors of circuits with parallel conductors shall be permitted to terminate in a single terminal if the terminal is identified for connection of more than one cond...
https://2023.antflix.net#408.41
Chapter 4 Equipment for General Use
408.43
Panelboards shall not be installed in the face-up or face-down position. [408.43](https://2023.antflix.net#408.43)
https://2023.antflix.net#408.43
Chapter 4 Equipment for General Use
408.50
The panels of switchboards and switchgear shall be made of moisture-resistant, noncombustible material. [408.50](https://2023.antflix.net#408.50)
https://2023.antflix.net#408.50
Chapter 4 Equipment for General Use
408.51
Insulated or bare busbars shall be rigidly mounted. [408.51](https://2023.antflix.net#408.51)
https://2023.antflix.net#408.51
Chapter 4 Equipment for General Use
408.52
Instruments, pilot lights, voltage (potential) transformers, and other switchboard or switchgear devices with potential coils shall be supplied by a circuit that is protected by standard overcurrent devices rated 15 amperes or less. Exception No. 1: Overcurrent devices rated more than 15 amperes shall be permitted wher...
https://2023.antflix.net#408.52
Chapter 4 Equipment for General Use
408.54
A panelboard shall be provided with physical means to prevent the installation of more overcurrent devices than that number for which the panelboard was designed, rated, and listed. For the purposes of this section, a 2-pole circuit breaker or fusible switch shall be considered two overcurrent devices; a 3-pole circuit...
https://2023.antflix.net#408.54
Chapter 4 Equipment for General Use
408.55(A)
The enclosure for a panelboard shall have the top and bottom wire-bending space sized in accordance with Table 312.6(B)(2) for the largest conductor entering or leaving the enclosure. Exception No. 1: Either the top or bottom wire-bending space shall be permitted to be sized in accordance with Table 312.6(A) for a pane...
https://2023.antflix.net#408.55(A)
Chapter 4 Equipment for General Use
408.55(B)
Side wire-bending space shall be in accordance with Table 312.6(A) for the largest conductor to be terminated in that space. [408.55(B)](https://2023.antflix.net#408.55(B))
https://2023.antflix.net#408.55(B)
Chapter 4 Equipment for General Use
408.55(C)
Where a raceway or cable entry is in the wall of the enclosure opposite a removable cover, the distance from that wall to the cover shall be permitted to comply with (he distance required for one wire per terminal in Table 312.6(A). The distance between the center of the rear entry and the nearest termination for the e...
https://2023.antflix.net#408.55(C)
Chapter 4 Equipment for General Use
408.56
The distance between uninsulated metal parts, busbars, and other uninsulated live parts shall not be less than specified in Table 408.56. Where close proximity does not cause excessive heating, parts of the same polarity at switches, enclosed fuses, and so forth shall be permitted to be placed as close together as conv...
https://2023.antflix.net#408.56
Chapter 4 Equipment for General Use
408.58
Panelboards shall be durably marked by the manufacturer with the voltage and the current rating and the number of ac phases or dc buses for which they are designed and with the manufacturer's name or trademark in such a manner so as to be visible after installation, without disturbing the interior parts or wiring. [408...
https://2023.antflix.net#408.58
Chapter 4 Equipment for General Use
409.1
This article covers industrial control panels intended for general use and operating at 1000 volts or less. Informational Note: See ANSI/UI. 508A, Standard for Industrial Control Panels, a safety standard for industrial control panels. [409.1](https://2023.antflix.net#409.1)
https://2023.antflix.net#409.1
Chapter 4 Equipment for General Use
409.3
In addition to the requirements of this article, industrial control panels that contain branch circuits for specific loads or components, or are for control of specific types of equipment addressed in other articles of this Code, shall be constructed and installed in accordance with the applicable requirements from tho...
https://2023.antflix.net#409.3
Chapter 4 Equipment for General Use
409.20
The size of the industrial control panel supply conductor shall have an ampacity not less than 125 percent of the full-load current rating of all heating loads plus 125 percent of the full-load current rating of the highest rated motor plus the sum of the full-load current ratings of all other connected motors and appa...
https://2023.antflix.net#409.20
Chapter 4 Equipment for General Use
409.21(A)
Industrial control panels shall be provided with overcurrent protection in accordance with Parts I and II of Article 240. [409.21(A)](https://2023.antflix.net#409.21(A))
https://2023.antflix.net#409.21(A)
Chapter 4 Equipment for General Use
409.21(B)
This protection shall be provided for each incoming supply circuit by either of the following: An overcurrent protective device located ahead of the industrial control panel.A single main overcurrent protective device located within the industrial control panel. Where overcurrent protection is provided as part of the i...
https://2023.antflix.net#409.21(B)
Chapter 4 Equipment for General Use
409.21(C)
The rating or setting of the overcurrent protective device for the circuit supplying the industrial control panel shall not be greater than the sum of the largest rating or setting of the branch-circuit short-circuit and ground-fault protective device provided with the industrial control panel, plus 125 percent of the ...
https://2023.antflix.net#409.21(C)
Chapter 4 Equipment for General Use
409.22(A)
An industrial control panel shall not be installed where the available fault current exceeds its short-circuit current rating as marked in accordance with 409.110(4). [409.22(A)](https://2023.antflix.net#409.22(A))
https://2023.antflix.net#409.22(A)
Chapter 4 Equipment for General Use
409.22(B)
If an industrial control panel is required to be marked with a short-circuit current rating in accordance with 409.110(4), the available fault current at the industrial control panel and the date the available fault current calculation was performed shall be documented and made available to those authorized to inspect,...
https://2023.antflix.net#409.22(B)
Chapter 4 Equipment for General Use
409.30
Disconnecting means that supply motor loads shall comply with Part IX of Article 430. [409.30](https://2023.antflix.net#409.30)
https://2023.antflix.net#409.30
Chapter 4 Equipment for General Use
409.60
Industrial control panels shall be grounded and bonded in accordance with 409.60(A) and (B). [409.60](https://2023.antflix.net#409.60)
https://2023.antflix.net#409.60
Chapter 4 Equipment for General Use
409.60(A)
An equipment grounding conductor sized in accordance with 250.122 shall be connected to an equipment grounding bus or to an equipment grounding termination point provided in a single-section industrial control panel. [409.60(A)](https://2023.antflix.net#409.60(A))
https://2023.antflix.net#409.60(A)
Chapter 4 Equipment for General Use
409.60(B)
Multisection industrial control panels shall be bonded together using an equipment bonding jumper sized in accordance with 250.102(D). [409.60(B)](https://2023.antflix.net#409.60(B))
https://2023.antflix.net#409.60(B)
Chapter 4 Equipment for General Use
409.70
Safety circuits for personnel protection that are subject to damage from surge events shall have surge protection installed within or immediately adjacent to the control panel. [409.70](https://2023.antflix.net#409.70)
https://2023.antflix.net#409.70
Chapter 4 Equipment for General Use
409.100
Table 110.28 shall be used as the basis for selecting industrial control panel enclosures for use in specific locations other than hazardous (classified) locations. The enclosures are not intended to protect against conditions such as condensation, icing, corrosion, or contamination that may occur within the enclosure ...
https://2023.antflix.net#409.100
Chapter 4 Equipment for General Use
409.102
Industrial control panels utilizing busbars shall comply with 409.102(A) and (B). [409.102](https://2023.antflix.net#409.102)
https://2023.antflix.net#409.102
Chapter 4 Equipment for General Use
409.102(A)
Busbars shall be protected from physical damage and be held firmly in place. [409.102(A)](https://2023.antflix.net#409.102(A))
https://2023.antflix.net#409.102(A)
Chapter 4 Equipment for General Use
409.102(B)
The phase arrangement on 3-phase horizontal common power and vertical buses shall be A, B, C from front to back, top to bottom, or left to right, as viewed from the front of the industrial control panel. The B phase shall be that phase having the higher voltage to ground on 3-phase, 4-wire, delta-connected systems. Oth...
https://2023.antflix.net#409.102(B)
Chapter 4 Equipment for General Use
409.104(A)
Industrial control panel enclosures shall not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to other switches or overcurrent devices or other equipment, unless the conductors fill less than 40 percent of the cross-sectional area of the wiring space. In addition,...
https://2023.antflix.net#409.104(A)
Chapter 4 Equipment for General Use
409.104(B)
Wire bending space within industrial control panels for field wiring terminals shall be in accordance with the requirements in 430.10(B). [409.104(B)](https://2023.antflix.net#409.104(B))
https://2023.antflix.net#409.104(B)