id
stringlengths
12
16
title
stringlengths
6
140
description
stringlengths
76
139k
cpes
listlengths
0
0
cvss_v4_0
null
cvss_v3_1
float64
2.5
10
cvss_v3_0
float64
1.9
10
cvss_v2_0
null
ICSMA-18-179-01
Medtronic MyCareLink Patient Monitor
The affected product contains a hard-coded operating system password. An attacker with physical access can remove the case of the device, connect to the debug port, and use the password to gain privileged access to the operating systemCVE-2018-8870 has been assigned to this vulnerability. A CVSS v3 base score of 6.4 ha...
[]
null
null
6.2
null
ICSA-20-184-02
ABB System 800xA Information Manager
The affected product is vulnerable to a remote code execution attack that may allow an attacker to remotely execute arbitrary code. Successful exploitation of this vulnerability requires luring a user (on a host with the vulnerable IM component installed) to access a malicious website that instructs the user 's browser...
[]
null
null
8.8
null
ICSA-19-134-02
Siemens SIMATIC WinCC and SIMATIC PCS 7
An attacker with network access to affected installations, which are configured without "Encrypted Communication", can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this se...
[]
null
null
9.8
null
ICSA-23-166-14
Siemens Teamcenter Visualization and JT2Go
The affected applications contain a null pointer dereference vulnerability while parsing specially crafted CGM files. An attacker could leverage this vulnerability to crash the application causing denial of service condition. The affected applications contain an out of bounds read past the end of an allocated buffer wh...
[]
null
7.8
null
null
ICSA-20-191-02
Rockwell Automation Logix Designer Studio 5000
The affected product is vulnerable to an xml external entity (XXE) vulnerability, which may allow an attacker to view hostnames or other resources from the program.CVE-2020-12025 has been assigned to this vulnerability. A CVSS v3 base score of 3.6 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:C/C:...
[]
null
null
3.6
null
ICSA-22-069-11
Siemens SINUMERIK MC
The sc SUID binary on affected devices provides several commands that are used to execute system commands or modify system files. A specific set of operations using sc could allow local attackers to escalate their privileges to root.
[]
null
7.8
null
null
ICSA-19-094-03
Rockwell Automation Stratix 5400/5410/5700/8000/8300 and ArmorStratix 5700
Sending a specially crafted open shortest path first version 3 (OSPFv3) packet could allow an unauthenticated, adjacent attacker to cause an affected device to reload, resulting in a denial-of-service condition.CVE-2018-0466 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been calculated; the C...
[]
null
null
7.4
null
ICSA-23-199-06
GE Digital CIMPLICITY
All versions of GE Digital CIMPLICITY that are not adhering to SDG guidance and accepting documents from untrusted sources are vulnerable to memory corruption issues due to insufficient input validation, including issues such as out-of-bounds reads and writes, use-after-free, stack-based buffer overflows, uninitialized...
[]
null
null
6.6
null
ICSA-19-330-02
ABB Relion 650 and 670 Series
An attacker may use a specially crafted message to force the device to reboot, which could cause a denial of service.CVE-2019-18247 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).
[]
null
null
5.3
null
ICSA-20-315-04
Siemens SIMATIC S7-300 CPUs and SINUMERIK Controller (Update A)
Sending multiple specially crafted packets to the affected devices could cause a Denial-of-Service on port 102. A cold restart is required to recover the service.
[]
null
5.9
null
null
ICSMA-18-226-01
Philips IntelliSpace Cardiovascular Vulnerabilities
For ISCV Version 2.x or prior and Xcelera Version 4.1 or prior, an attacker with escalated privileges could access folders which contain executables where authenticated users have write permissions, and could then execute arbitrary code with local administrative permissions.CVE-2018-14789 has been assigned to this vuln...
[]
null
null
4.2
null
ICSA-18-212-02
Johnson Controls Metasys and BCPro
This vulnerability results from improper error handling in HTTP-based communications with the server, which could allow an attacker to obtain technical information.CVE-2018-10624 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/...
[]
null
null
4.3
null
ICSA-20-084-01
VISAM Automation Base (VBASE) (Update B)
Input passed in the URL is not properly verified before use, which may allow an attacker to read arbitrary files from local resources.CVE-2020-7008 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). Weak or insecure ...
[]
null
null
9
null
ICSA-20-324-03
Real Time Automation EtherNet/IP
The affected product is vulnerable to a stack-based buffer overflow, which may allow an attacker to send a specially crafted packet that may result in a denial-of-service condition or code execution.CVE-2020-25159 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector ...
[]
null
null
9.8
null
ICSA-24-228-01
Siemens SCALANCE M-800, RUGGEDCOM RM1224
Affected devices do not properly validate the length of inputs when performing certain configuration changes in the web interface allowing an authenticated attacker to cause a denial of service condition. The device needs to be restarted for the web interface to become available again. Affected devices do not properly ...
[]
null
6.5
null
null
ICSA-20-324-04
Schneider Electric Interactive Graphical SCADA System (IGSS)
An improper restriction of operations within the bounds of a memory buffer vulnerability could cause remote code execution when a malicious CGF (Configuration Group File) is imported to IGSS Definition.CVE-2020-7550 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vecto...
[]
null
null
7.8
null
ICSA-21-222-06
Siemens Energy AGT and SGT Solutions
** UNSUPPORTED WHEN ASSIGNED ** A DNS client stack-based buffer overflow in ipdnsc_decode_name() affects Wind River VxWorks 6.5 through 7. NOTE: This vulnerability only affects products that are no longer supported by the maintainer.
[]
null
9.8
null
null
ICSA-20-224-08
Siemens SICAM A8000 RTUs
The login screen does not sufficiently sanitize input, which enables an attacker to generate specially crafted log messages. If an unsuspecting victim views the log messages via the web browser, these log messages might be interpreted and executed as code by the web application. This Cross-Site-Scripting (XSS) vulnerab...
[]
null
8.3
null
null
ICSA-19-162-01
Siemens Siveillance VMS
An attacker with network access to port 80/TCP could change device properties without authorization. No user interaction is required to exploit this security vulnerability. Successful exploitation compromises confidentiality, integrity and availability of the targeted system. At the time of advisory publication no publ...
[]
null
null
7.1
null
ICSA-20-105-08
Siemens KTK, SIDOOR, SIMATIC, and SINAMICS (Update C)
The Interniche-based TCP Stack can be forced to make very expensive calls for every incoming packet which can lead to a denial of service.
[]
null
7.5
null
null
ICSA-21-110-04
Delta Electronics CNCSoft ScreenEditor
The affected product is vulnerable to an out-of-bounds read while processing project files, which may allow an attacker to execute arbitrary code.CVE-2021-22668 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
[]
null
null
7.8
null
ICSA-20-128-01
Advantech WebAccess Node
An improper validation vulnerability exists that could allow an attacker to inject specially crafted input into memory where it can be executed.CVE-2020-12022 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). Multip...
[]
null
null
6.5
null
ICSA-19-150-01
AVEVA Vijeo Citect and CitectSCADA
A vulnerability has been identified that may allow an authenticated local user access to Citect user credentials.CVE-2019-10981 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N).
[]
null
null
6.5
null
ICSA-19-024-02
PHOENIX CONTACT FL SWITCH
This vulnerability may allow an attacker to trick the web browser into transmitting unwanted commands.CVE-2018-13993 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The switch lacks a login time-out feature to pre...
[]
null
null
5.3
null
ICSA-22-314-01
Siemens Parasolid
The affected application contains an out of bounds read past the end of an allocated structure while parsing specially crafted X_T files. This could allow an attacker to execute code in the context of the current process. (ZDI-CAN-17745) The affected application contains an out of bounds write past the end of an alloca...
[]
null
7.8
null
null
ICSA-22-104-09
Siemens SCALANCE X-300 Switches
Affected devices do not properly validate the HTTP headers of incoming requests. This could allow an unauthenticated remote attacker to crash affected devices. The webserver of affected devices calculates session ids and nonces in an insecure manner. This could allow an unauthenticated remote attacker to brute-force se...
[]
null
7.4
null
null
ICSA-23-059-02
Hitachi Energy Gateway Station
A vulnerability exists in the ICCP stack due to validation flaw in the process establishing the ICCP communication. The validation flaw will cause a denial-of-service condition when ICCP of SYS600 is requested to forward any data item updates with timestamps too far in the future. By default, ICCP is not configured and...
[]
null
null
7.5
null
ICSA-20-154-04
ABB Central Licensing System
Confidential data is written in an unprotected file, which may allow an attacker to login to the affected node as a low privileged user and read confidential data from an unprotected file.CVE-2020-8481 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (A...
[]
null
null
7.8
null
ICSMA-20-233-01
Philips SureSigns VS4
The product receives input or data, but it does not validate or incorrectly validates that the input has the properties required to process the data safely and correctly.
[]
null
null
2.1
null
ICSA-23-215-04
Sensormatic Electronics VideoEdge
In Sensormatic VideoEdge versions prior to 6.1.1, a local user could edit the VideoEdge configuration file and interfere with VideoEdge operation.
[]
null
null
7.1
null
ICSA-21-257-01
Digi PortServer TS 16
Properly formatted POST requests to multiple resources on the HTTP and HTTPS web servers of the Digi PortServer TS 16 Rack device do not require authentication or authentication tokens. This vulnerability could allow an attacker to enable the SNMP service and manipulate the community strings to achieve further control....
[]
null
null
9.6
null
ICSA-21-348-02
Schneider Electric Rack PDU (Update A)
An attacker could access the system with elevated privileges when a privileged account clicks on a malicious URL that compromises the security token. CVE-2021-22825 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:L/UI:R/S:C/C:N/I:H/A:L).....
[]
null
null
6.5
null
ICSA-17-234-05
Saia Burgess Controls PCD Controllers
In certain circumstances, the device pads Ethernet frames with memory contents.CVE-2017-9628 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).
[]
null
null
5.3
null
ICSA-18-137-04
Delta Electronics Delta Industrial Automation TPEditor (Update A)
Parsing a malformed program file may cause heap-based buffer overflow vulnerability, which may allow remote code execution.CVE-2018-8871 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L).
[]
null
null
7.3
null
ICSA-17-306-01
Siemens SIMATIC PCS 7 (Update A)
An authenticated, remote attacker who is member of the "administrators" group couldcrash services by sending specially crafted messages to the DCOM interface.
[]
null
null
4.9
null
ICSA-24-046-14
Siemens Polarion ALM
The affected product is vulnerable due to weak file and folder permissions in the installation path. An attacker with local access could exploit this vulnerability to escalate privileges to NT AUTHORITY\SYSTEM. The REST API endpoints of doorsconnector of the affected product lacks proper authentication. An unauthentica...
[]
null
7.3
null
null
ICSA-22-041-01
Siemens SIMATIC Industrial Products (Update A)
An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations. CVE-2021-37185 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the ...
[]
null
7.5
null
null
ICSA-22-013-01
Mitsubishi Electric MELSEC-F Series
The affected product is vulnerable due to a lack of administrative controls, which may allow an attacker to remotely send specially crafted packets and cause a denial-of-service condition or other unspecified effects.CVE-2021-20612 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; ...
[]
null
null
7.5
null
ICSA-23-080-05
VISAM VBASE Automation Base
Versions of VISAM VBASE Automation Base prior to 11.7.5 may disclose information if a valid user opens a specially crafted file. CVE-2022-41696 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N). Versions of VISAM VBA...
[]
null
null
5.5
null
ICSA-18-060-01
ICSA-18-060-01_Siemens SIMATIC, SIMOTION, and SINUMERIK (Update A)
Multiple buffer overflows could allow attackers to execute arbitrary code. Local access to the system is required to exploit this vulnerability. CVE-2017-5705, CVE-2017-5706, and CVE-2017-5707 have been assigned to these vulnerabilities. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:L/A...
[]
null
null
8.2
null
ICSA-21-280-02
Mobile Industrial Robots Vehicles and MiR Fleet Software
An authenticated local attacker with an account on the MiR robot operating system can exploit a Linux kernel vulnerability to perform privilege escalation to root or cause a denial-of-service condition.CVE-2017-7184 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vecto...
[]
null
null
7.5
null
ICSA-23-166-13
Siemens SICAM A8000 Devices
The web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges. The affected devices contain the hash of the root password in a hard-coded form, which could ...
[]
null
6.8
null
null
ICSA-17-285-02
WECON Technology Co., Ltd. LeviStudio HMI Editor
Multiple stack-based buffer overflow vulnerabilities have been identified in which the application does not verify string size before copying to memory, the attacker may then be able to crash the application or run arbitrary code.CVE-2017-13999 has been assigned to these vulnerabilities. A CVSS v3 base score of 7.5 has...
[]
null
null
7.5
null
ICSA-23-320-09
Siemens COMOS
MPXJ through 8.1.3 allows XXE attacks. This affects the GanttProjectReader and PhoenixReader components. common/InputStreamHelper.java in Packwood MPXJ before 8.3.5 allows directory traversal in the zip stream handler flow, leading to the writing of files to arbitrary locations. Open Design Alliance Drawings SDK before...
[]
null
9.6
null
null
ICSA-21-131-10
Siemens SCALANCE XM-400 and XR-500 Devices
The OSPF protocol implementation in affected devices incorrectly handles the number of LSA fields in combination with other modified fields. An unauthenticated remote attacker could create a permanent denial-of-service condition by sending specially crafted OSPF packets. Successful exploitation requires OSPF to be ena...
[]
null
7.5
null
null
ICSA-18-263-02
Rockwell Automation RSLinx Classic
This vulnerability may allow a remote threat actor to intentionally send a malformed CIP packet to Port 44818, causing the software application to stop responding and crash. This vulnerability also has the potential to exploit a buffer overflow condition, which may allow the threat actor to remotely execute arbitrary c...
[]
null
null
8.6
null
ICSA-19-227-03
Siemens SCALANCE Products (Update A)
An authenticated attacker with network access to to port 22/tcp of an affected device may cause a Denial-of-Service condition. The security vulnerability could be exploited by an authenticated attacker with network access to the affected device. No user interaction is required to exploit this vulnerability. The vulnera...
[]
null
6.6
null
null
ICSMA-23-047-01
BD Alaris Infusion Central
Alaris Infusion Central versions 1.1-1.3.2 may contain a recoverable password after installation, which could allow an attacker to disclose or tamper with resident personal data. Patient health data is not stored in the database, although some side installations may choose to store personal data. CVE-2022-47376 has bee...
[]
null
7.3
null
null
ICSA-21-287-02
Uffizio GPS Tracker
Visiting through the browser or doing curl on the vulnerable host at Port 9000 responds with JSON body, revealing information about deployed GPS devices.CVE-2020-17483 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)....
[]
null
null
4.3
null
ICSA-22-174-01
Yokogawa STARDOM
The affected product transmits sensitive information in cleartext, which may allow an attacker sniffing network traffic on the controller to read/change configuration settings or update the controller with tampered firmware.CVE-2022-29519 has been assigned to this vulnerability. A CVSS v3 base score of 4.8 has been cal...
[]
null
null
6.3
null
ICSA-24-023-01
APsystems Energy Communication Unit (ECU-C) Power Control Software
APsystems ENERGY COMMUNICATION UNIT (ECU-C) Power Control Software V4.1NA, V3.11.4, W2.1NA, V4.1SAA, C1.2.2 allows attackers to access sensitive data and execute specific commands and functions with full admin rights. This could lead to multiple attacks in the product's range.
[]
null
8.8
null
null
ICSA-23-320-04
Siemens Mendix Runtime
A capture-replay flaw in the platform could have an impact to apps built with the platform, if certain preconditions are met that depend on the app's model and access control design. This could allow authenticated attackers to access or modify objects without proper authorization, or escalate privileges in the conte...
[]
null
6.8
null
null
ICSA-22-270-02
Hitachi Energy APM Edge
The affected product is vulnerable to a privilege escalation attack, which could allow an attacker to escalate a user account to root.CVE-2021-4034 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H). The affected prod...
[]
null
null
7.8
null
ICSA-20-352-01
Emerson Rosemount X-STREAM
The affected products are vulnerable to improper authentication for accessing log and backup data, which could allow an attacker with a specially crafted URL to obtain access to sensitive information.CVE-2020-27254 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector...
[]
null
null
7.5
null
ICSA-21-103-07
Siemens Web Server of SCALANCE X200 (Update A)
Incorrect processing of POST requests in the webserver may result in write out of bounds in heap. An attacker might leverage this to cause denial-of-service on the device and potentially remotely execute code. Incorrect processing of POST requests in the web server may write out of bounds in stack. An attacker might le...
[]
null
9.8
null
null
ICSA-22-104-14
Siemens SIMATIC STEP 7 (TIA Portal)
An attacker could achieve privilege escalation on the web server of certain devices due to improper access control vulnerability in the engineering system software. The attacker needs to have direct access to the impacted web server.
[]
null
6.4
null
null
ICSA-22-286-04
Siemens SIMATIC S7-1200 and S7-1500 CPU Families
Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication. This could allow attackers to discover the private key of a CPU product family ...
[]
null
9.3
null
null
ICSA-23-264-05
Rockwell Automation Connected Components Workbench
Connected Components Workbench utilizes CefSharp version 81.3.100 that contains a use after free vulnerability in Google Chrome versions before 86.0.4240.198. If exploited, a remote threat actor could potentially perform a sandbox escape via a crafted HTML page. Connected Components Workbench utilizes CefSharp version ...
[]
null
null
8.8
null
ICSA-19-260-03
Honeywell Performance IP Cameras and Performance NVRs
The integrated web server of the affected devices could allow remote attackers to obtain web configuration data in JSON format for IP cameras and NVRs (Network Video Recorders), which can be accessed without authentication over the network.CVE-2019-13523 has been assigned to this vulnerability. A CVSS v3 base score of ...
[]
null
null
5.3
null
ICSA-17-152-02
NXP i.MX Product Family
When the device is configured in security enabled configuration. SDP could be used to download a small section of code to an unprotected region of memory.CVE-2017-7936 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:P/AC:H/PR:N/UI:N/S:U/C:L/I:H/A:L)....
[]
null
null
6
null
ICSA-24-011-09
Siemens SIMATIC CN 4100
The "intermediate installation" system state of the affected application allows an attacker to add their own login credentials to the device. This allows an attacker to remotely login as root and take control of the device even after the affected device is fully set up. The affected application allows IP configuration ...
[]
null
9.8
null
null
ICSA-17-208-01
Continental AG Infineon S-Gold 2 (PMB 8876)
An attacker with a physical connection to the TCU may exploit a buffer overflow condition that exists in the processing of AT commands. This may allow arbitrary code execution on the baseband radio processor of the TCU.CVE-2017-9647 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been assigned;...
[]
null
null
8.8
null
ICSA-22-013-04
Siemens SIPROTEC 5 Devices
An improper input validation vulnerability in the web server could allow an unauthenticated user to access device information.
[]
null
6.5
null
null
ICSA-21-336-02
Johnson Controls Entrapass
The affected product is vulnerable to an exposure of sensitive information to an unauthorized actor.CVE-2021-36198 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L).
[]
null
null
8.3
null
ICSA-18-011-01
WECON Technology Co., Ltd. LeviStudio HMI Editor
Specially-crafted malicious files may be able to cause stack-based buffer overflow vulnerabilities, which may allow remote code execution. CVE-2017-16739 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L). A specially...
[]
null
null
5.3
null
ICSA-19-134-02
Siemens SIMATIC WinCC and SIMATIC PCS 7
An attacker with network access to affected installations, which are configured without "Encrypted Communication", can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this se...
[]
null
null
9.8
null
ICSA-22-195-12
Siemens SRCS VPN Feature in SIMATIC CP Devices
The application lacks proper validation of user-supplied data when parsing specific messages. This could result in a heap-based buffer overflow. An attacker could leverage this vulnerability to execute code in the context of device. The application does not correctly escape some user provided fields during the authenti...
[]
null
7.6
null
null
ICSA-21-350-13
Siemens Questa and ModelSim
The affected product is vulnerable to insufficiently protected keys required for decrypting intellectual property data, which could allow an attacker to discover the keys and bypass the protection intended by IEEE 1735 standard. CVE-2021-42023 has been assigned to this vulnerability. A CVSS v3 base score of 9.0 has bee...
[]
null
null
9
null
ICSA-23-199-07
WellinTech KingHistorian
An information disclosure vulnerability exists in the User authentication functionality of WellinTech KingHistorian 35.01.00.05. A specially crafted network packet can lead to a disclosure of sensitive information. An attacker can sniff network traffic to leverage this vulnerability. An integer conversion vulnerability...
[]
null
null
8.1
null
ICSA-20-014-01
GE PACSystems RX3i
Sending specially manipulated packets can cause the module state to change to halt-mode, resulting in a denial-of-service condition. An operator must reboot the CPU module after removing battery or energy pack to recover from halt-mode.CVE-2019-13524 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 ...
[]
null
null
7.5
null
ICSA-20-042-10
Siemens SCALANCE S-600 (Update B)
The integrated configuration web server of the affected devices could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link. User interaction is required for a successful exploitation. The user must be logged into the web interface in order for the exploitation to s...
[]
null
7.5
null
null
ICSA-19-031-01
Schneider Electric EVLink Parking
A hard-coded credentials vulnerability exists that could enable an attacker to gain access to the device.CVE-2018-7800 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). A code injection vulnerability exists that cou...
[]
null
null
6.4
null
ICSA-24-226-08
Ocean Data Systems Dream Report
In Ocean Data Systems Dream Report, a path traversal vulnerability could allow an attacker to perform remote code execution through the injection of a malicious dynamic-link library (DLL). In Ocean Data Systems Dream Report, an incorrect permission vulnerability could allow a local unprivileged attacker to escalate the...
[]
null
7.8
null
null
ICSA-19-022-01
Johnson Controls Facility Explorer
A path traversal vulnerability exists that an attacker could exploit, in certain circumstances, using valid platform (administrator) credentials to access a file or directory outside of the restricted location.
[]
null
null
6.6
null
ICSA-22-195-04
Siemens Simcenter Femap
The affected application contains an out of bounds write past the end of an allocated structure while parsing specially crafted X_T files. This could allow an attacker to execute code in the context of the current process. (ZDI-CAN-17293)
[]
null
7.8
null
null
ICSMA-19-022-01
Dräger Infinity Delta
A malformed network packet may cause the monitor to reboot. By repeatedly sending the malformed network packet, an attacker may be able to disrupt patient monitoring by causing the monitor to repeatedly reboot until it falls back to default configuration and loses network connectivity.CVE-2018-19010 has been assigned t...
[]
null
null
8.4
null
ICSA-18-305-04
Fr. Sauter AG CASE Suite
An XXE vulnerability exists when processing parameter entities, which may allow remote file disclosure.CVE-2018-17912 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
[]
null
null
7.5
null
ICSA-24-039-01
Qolsys IQ Panel 4, IQ4 HUB
In Qolsys IQ Panel 4 and IQ4 Hub versions prior to 4.4.2, panel software, under certain circumstances, could allow unauthorized access to settings.
[]
null
7.3
null
null
ICSA-19-178-05
Advantech WebAccess/SCADA
A path traversal vulnerability is caused by a lack of proper validation of a user-supplied path prior to use in file operations. An attacker can leverage this vulnerability to delete files while posing as an administrator.CVE-2019-10985 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calcu...
[]
null
null
9.8
null
ICSMA-19-353-01
Philips Veradius Unity, Pulsera, and Endura Dual WAN Routers
The router software uses an encryption scheme that is not strong enough for the level of protection required.CVE-2019-18263 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).
[]
null
null
5.3
null
ICSA-22-242-01
Hitachi Energy FACTS Control Platform (FCP) Product
Hitachi Energy is aware of public reports of multiple vulnerabilities in open-source software components (OpenSSL and Node.JS) used in the FACTS Control Platform (FCP) product. Versions are available to remediate the identified vulnerabilities.CVE-2020-1968, CVE-2020-8172, CVE-2020-8174, CVE-2020-8201, CVE-2020-8252, C...
[]
null
null
8.1
null
ICSA-20-093-01
B&R Automation Studio
A privilege escalation vulnerability in the upgrade service in B&R Automation Studio could allow authenticated users to delete arbitrary files via an exposed interface.CVE-2019-19100 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/...
[]
null
null
5.5
null
ICSA-21-222-01
Siemens JT2Go and Teamcenter Visualization products
An out-of-bounds write issue exists in the DXF file-recovering procedure in the Open Design Alliance Drawings SDK (All versions prior to 2022.4) resulting from the lack of proper validation of user-supplied data. This can result in a write past the end of an allocated buffer and allow attackers to cause a denial-of-ser...
[]
null
5.5
null
null
ICSA-18-347-01
Schneider Electric GUIcon Eurotherm
A type confusion vulnerability exists on pcwin.dll that could cause remote code to be executed when parsing a GD1 file.CVE-2018-7813 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). A type confusion vulnerability e...
[]
null
null
7.8
null
ICSA-17-304-01
ABB FOX515T
An improper input validation vulnerability has been identified, allowing a local attacker to provide a malicious parameter to the script that is not validated by the application, This could enable the attacker to retrieve any file on the server.CVE-2017-14025 has been assigned to this vulnerability. A CVSS v3 base scor...
[]
null
null
6.2
null
ICSA-22-235-01
ARC Informatique PcVue (Update A)
The affected device stores sensitive information in cleartext, which may allow an authenticated user to access session data stored in the OAuth database belonging to legitimate users. CVE-2022-2569 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (AV:L/AC...
[]
null
null
5.5
null
ICSA-19-136-02
Fuji Electric Alpha7 PC Loader
An out-of-bounds read vulnerability has been identified, which may crash the system.CVE-2019-10975 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:L).
[]
null
null
3.3
null
ICSA-20-224-06
Siemens Desigo CC
Affected applications are delivered with a 3rd party component (BIRT) that contains a remote code execution vulnerability if the Advanced Reporting Engine is enabled. The vulnerability could allow a remote unauthenticated attacker to execute arbitrary commands on the server with SYSTEM privileges.
[]
null
9.8
null
null
ICSA-22-349-20
Siemens Teamcenter Visualization and JT2Go
The CGM_NIST_Loader.dll contains a null pointer dereference vulnerability while parsing specially crafted CGM files. An attacker could leverage this vulnerability to crash the application causing denial of service condition. The CGM_NIST_Loader.dll contains a null pointer dereference vulnerability while parsing special...
[]
null
3.3
null
null
ICSA-18-200-01
AVEVA InduSoft Web Studio and InTouch Machine Edition
A remote user could send a carefully crafted packet to exploit a stack-based buffer overflow vulnerability during tag, alarm, or event related actions such as read and write, with potential for code to be executed.CVE-2018-10620 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; t...
[]
null
null
9.8
null
ICSA-24-123-02
Delta Electronics DIAEnergie
Delta Electronics DIAEnergie is vulnerable to an SQL injection vulnerability that exists in the script Handler_CFG.ashx. An authenticated attacker can exploit this issue to potentially compromise the system on which DIAEnergie is deployed. Delta Electronics DIAEnergie is vulnerable to an SQL injection vulnerability tha...
[]
null
8.8
null
null
ICSA-21-231-02
Baker Hughes Bently Nevada 3500
The affected products utilize a weak encryption algorithm for storage and transmission of sensitive data, which may allow an attacker to more easily obtain credentials used for access.CVE-2021-32997 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:N...
[]
null
null
8.2
null
ICSA-23-299-08
Sielco Radio Link and Analog FM Transmitters
The cookie session ID is of insufficient length and can be exploited by brute force, which may allow a remote attacker to obtain a valid session, bypass authentication, and manipulate the transmitter. The application interface allows users to perform certain actions via HTTP requests without performing any validity che...
[]
null
6.5
null
null
ICSA-24-046-04
Siemens CP343-1 Devices
Affected products incorrectly validate TCP sequence numbers. This could allow an unauthenticated remote attacker to create a denial of service condition by injecting spoofed TCP RST packets.
[]
null
7.5
null
null
ICSA-18-184-01
Rockwell Automation Allen-Bradley Stratix 5950
A vulnerability in the ingress flow creation functionality of the Cisco ASA could allow an unauthenticated, remote threat actor to cause the CPU to increase upwards of 100 percent utilization, causing a denial-of-service (DoS) condition on an affected system.CVE-2018-0228 has been assigned to this vulnerability. A CVSS...
[]
null
null
8.6
null
ICSA-21-257-12
Siemens SINEMA Server
Missing authentication for functionality that requires administrative user identity could allow an attacker to obtain encoded system configuration backup files. This is only possible through network access to the affected system, and successful exploitation requires no system privileges.
[]
null
4.7
null
null
ICSA-22-242-06
Honeywell ControlEdge
The affected product root credentials are hard-coded and not changed automatically when first commissioned, which may allow an attacker with SSH access to the device to gain full control.CVE-2022-30318 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:...
[]
null
null
9.8
null
ICSA-22-109-03
FANUC ROBOGUIDE Simulation Platform
The affected product is vulnerable to misconfigured binaries, allowing users on the target PC with SYSTEM level privileges access to overwrite the binary and modify files to gain privilege escalation.CVE-2021-38483 has been assigned to this vulnerability. A CVSS v3 base score of 6.0 has been calculated; the CVSS vector...
[]
null
null
6.1
null
ICSA-18-081-02
Beckhoff TwinCAT
Several kernel drivers lack proper validation of user-supplied pointer values. An attacker who is able to execute code on the target may be able to exploit this vulnerability to obtain SYSTEM privileges. CVE-2018-7502 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vec...
[]
null
null
7.8
null
ICSA-24-270-05
goTenna Pro ATAK Plugin
The goTenna Pro ATAK Plugin uses a weak password for the QR broadcast message. If the QR broadcast message is captured over RF it is possible to decrypt it and use it to decrypt all future and past messages sent via encrypted broadcast. In the goTenna Pro ATAK Plugin application, the encryption keys are stored along wi...
[]
null
4.3
null
null